INSTALLATION MANUAL
ICBO # ER-3507 PFS ®
US C
SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain re- placement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fire- place or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard. A hood must be installed when using a vent-free log heater (see , page 18).
This wood burning fireplace complies with UL127- CAN/ULS-S610-M87 standard as a FACTORY BUILT APPLIANCE.
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to deter- mine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
Wood burning Fireplace · Model C42MW

Table of Contents Safety 2 Specifications 3 Fireplace Installation 4 Venting Installation 7 Optional Gas Line Installation 13
Operation and Maintenance 14 Technical Service 15 Parts 16 Replacement Parts 18 Accessories 18
ponents, doors, air inlet system and damper control. b. Use of any component part not manu-
factured or approved by Style Crest, Inc in combination with a Style Crest, Inc fireplace system. Proper installation is the most important step in ensuring safe and continuous operation of fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
This fireplace is not intended to be used as a substitute for a fur- nace to heat an entire home. Use for supplemental heat only.



Selecting location To determine safest and most efficient location for fireplace, you must take into consideration the following guidelines: 1. Location must allow for proper clearances (see Figures 1 and 2). 2. Consider a location where fireplace will not be affected by drafts, air conditioning ducts, windows or doors. 3. A location that avoids cutting of joists or roof rafters will make installation easier. 4. An outside air kit is available with this fireplace (see Optional Outside Air Kit on page 7).
3. Set fireplace directly in front of this open- ing and slide unit back until nailing flanges touch side framing. 4. Check level of fireplace and shim with sheet metal if necessary. 5. Before securing fireplace to prepared framing, ember protector must be placed between hearth extension (not included) and under bottom front edge of fireplace to protect against glowing embers falling through. If fireplace is to be installed on a raised platform, a Z-type ember protec- tor (not included) must be fabricated to fit your required platform height. Ember protector should extend under fireplace a minimum of 1 1/2". Ember protector should be made of galvanized sheet metal (28 gauge minimum) to prevent corrosion. 6. Using screws or nails, secure fireplace to framing through flanges located on sides of fireplace.
Minimum clearance to combustibles Back and sides of fireplace 3/4" minimum* Floor** 0" minimum Perpendicular wall to opening 12" minimum Top spacers 0" minimum Mantel clearances see Mantels, page 6 Chimney outer pipe surface 1" minimum * Not required at nailing flanges ** See step 2 of Framing
37.625"
Minimum/Maximum Chimney Height Minimum height of chimney, measured from base of fireplace to flue gas outlet of termina- tion, is 11.5 feet for straight flue or a flue with one elbow set. Maximum distance between elbows is 2 feet. For systems with two elbow sets, minimum height is 22 feet. Maximum height of any system is 28 feet. This measure- ment includes fireplace, chimney sections and height of termination assembly at level of flue gas outlet (see Figure 18, page 11).
44.25"
Figure 1 - Framing Dimensions
Maintain 3/4" Clearance at
15 7/8"
22 1/2"
52 1/2"
Framing 1. Frame opening for fireplace using dimen- sions shown in Figures 1 and 2. 2. If fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, fireplace must be installed upon a metal or wood panel extending full width and depth of fireplace.
3/4" Clearance Not Required at Nailing Flanges
72 7/8"
Figure 2 - Corner Installation
22" · Sides and · Back of Fireplace

Hearth Extension A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of fireplace opening is required to protect combustible floor construction in front of fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductiv- ity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if material selected has a K factor of 0.25, such as glass fiber, the following formula would apply: 0.25 x 1.0" = 0.30" thickness required 0.84 Thermal conductivity "K" of materials can be obtained from manufacturer or supplier of noncombustible material. If hearth extension is to be covered, use noncombustible mate- rial such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material (see Figure 3).
Seal Gap Fireplace Front
Do Not Block Louver
Hearth Extension, Circulating Modes
Seal Gap Fireplace Front
Fireplace Front Raised Hearth
Hearth Extension, Noncirculating Models
Figure 3 - Hearth Extension

Mantels A mantel may be installed if desired (see Figure 4). Woodwork such as wood trims, mantels or any other combustible material projecting from front face must not be placed within 12" of fireplace opening (and within 9" of top louver opening). Combustible materi- als above 12" and projecting more than 1 1/2" from fireplace must not be placed less than 12" from top opening of fireplace (NFPA STD 211, Sec. 7-3.3.3). Mantels or any other combustible material may come up to side edge of black metal face of fireplace if projection from front face falls within limits shown in Figure 5.
Fan/Blower Kit assembly Fan or blower kit is optional with this fireplace (for circulating models only). Use of blowers or fans other than those manufactured by Style Crest, Inc voids warranty. Fan is oper- ated by pressing rocker switch (see Figure 6) in lower right hand corner of fireplace face. Blower is operated by turning control knob (not shown). Fan/blower kit electrical connections are made through electrical cover plate on side of fireplace a shown in Figure 6.


Wire Nut (3x) (Not Supplied)
Outer Wrapper of Fireplace

Power Source Wiring (Not Supplied)
Electrical Cover Plate and Electrical Bushing Fireplace Chassis Ground
Prewired Receptacle and Ground
Figure 4 - Mantel Clearances to
Figure 6 - Fan Switch-Electrical Bushing

Wiring Instructions 1. Remove electrical cover plate with bush- ing from fireplace by removing 2 sheet metal screws as shown in Figure 6. 2. Slide power source wiring through electri- cal bushing opening and electrical cover plate and make all necessary connec- tions. 3. Slide all wiring connections in electrical housing as shown in Figure 6. 4. Secure electrical cover plate with screws previously removed. Note: Electrical housing and cover plate have sharp edges. Wear protective gloves.
Min. 12" from Perpendicular Side Wall
Figure 5 - Side Mantel Clearance

Optional Outside air Kit (Model AK4/AK4F) Installation of outside air kit should be per- formed during rough framing of fireplace due to the nature of it's location. Outside combus- tion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4). See Figure 24 on page 15 for instruction of operating air kit.
The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.
Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)
Air Inlet Location Must Allow For Bushes or Snow
Air Inlet Eyebrow Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)
Vent Hood Required for Wall Installation
Figure 7 - Outside Air Kit
Chimney Pipe Style Crest, Inc chimney system consists of 12", 18", 24", 36" and 48" snap-lock, double- wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in lineal gain chart (see Figure 8). Lineal gain is actual measurable length of a part after two or more parts are connected.
* The lineal gain for the terminations is measured to the flue gas outlet height.
Figure 8 - Lineal Gain

Assembly and installation of double wall chimney system Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sec- tions must be assembled independently as chimney is installed. When connecting chim- ney directly to fireplace, inner flue pipe sec- tion must be installed first with lanced side up. Outer pipe section can then be installed over flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. Wire will assure proper spacing between inner and outer pipe sections. Note: For Canada, use chimney parts des- ignated HT.
installing double wall snap-lock chimney to- gether, it is important to assure joint between chimney sections is locked. Check by pulling chimney upward after locking. Chimney will not come apart if properly locked. It is not necessary to add screws to keep chimney to- gether (exception - see Figure 11, page 9).
Using ELBOW offsets (30E-8DM) 1. To achieve desired offset, you may install combinations of 12", 18", 24", 36" and 48" length of double wall pipe (see offset chart, page 7, and Figure 9). Note: For systems with 2 elbow sets, mini- mum height is 22 feet. Maximum height for any system is 50 feet. 2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 10, details A and B, page 9). 3. Maximum length of pipe between supports (return elbow or 12S-8DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 9). 4. All pipe connections between offset and return must be secured with two screws on outer pipe only (see Figure 11, page 9). Do not penetrate inner stainless.
Continue to assemble chimney sections as outlined, making sure that both inner and outer pipe sections are locked together. When
6' Max.
6' Max.
Ceiling Support Pipe 12S-8DM
6' Max.
6' Max.
Return Elbow Offset Elbow
6' Max.
6' Max.
Figure 9 - Typical Offset Installation


Figure 10 - Ceiling Support Pipe 12S-8DM

Figure 11 - Elbow Offset
Screws

Firestop Spacers (FS-8DM) Firestop spacers are required at each point where chimney penetrates a floor space. Their purpose is to establish and maintain required clearance between chimney and combustible materials. When pipe passes through a framed opening into a living space above, firestop must be placed onto ceiling from below as shown in Figure 12. They also provide complete separation from one floor space to another or attic space as required by most codes. When double wall pipe passes through a framed opening into an attic space, firestop must be placed into an attic floor as shown in Figure 13.

14 3/8" (36.5 cm) 30" (76.2 cm) 1" (2.5 cm)
If area above is a living space, install
firestop below framed hole.
Figure 12 - Firestop Spacer with Living
If area above is an attic or insulated area,
install firestop above framed hole.
Figure 14 - Roof Opening Measurements
Flashing installation (v6f-8dm or v12f-8dm) Determine flashing to be used with roof open- ing chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 15, page 11). DO NOT NAIL THROUGH FLASHING CONE.
Figure 13 - Firestop Spacer with Attic
Penetrating roof To maintain a 2" clearance to pipe on a roof with a pitch, a rectangular opening must be cut. 1. Determine center point where pipe will penetrate the roof. 2. Determine center point of the roof. Pitch is the distance the roof drops over a given span, usually 12". A 6/12 pitch means that the roof drops 6" for each 12" measure horizontally down from roof rafters. 3. Use roof opening chart (Figure 14) to determine correct opening length and flashing required.
Installing Flashing on a Metal Roof When installing flashing on a metal roof, it is required that putty tape be used between flashing and roof. Flashing must be secured to roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through screw holes. A roof coating must also be ap- plied around perimeter of flashing to provide a proper seal.
Minimum Measurements · Space Above Ceiling · Space Above Ceiling

Terminations with 16" slip pipe sections are available. RTT-8DM and RTTL-8DM are approved for flashing installations. When needed, these adjustable terminations may be used in combination with pipe assembly to achieve correct chimney height. Note: In the rare instance there is a problem with side driven rain or wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft Shield) can be used with round terminations.

RTL-8DM Level of Flue Gas Outlet
Attach Bracket Tabs to Outer Pipe (3 Places) Secure with Screws

Flue Pipe of RTL-8DM Inside Inner Pipe of Chimney
Figure 15 - Flashing Installation
Storm Collar Installation (SC1 or SC2) Place storm collar over pipe and slide down until it is snug against open edge of flashing (see Figure 16). Use SC1 for all round ter- minations and SC2 for all terminations with slip sections. Apply waterproof caulk around perimeter of collar to provide a proper seal.

Chase installations Instructions for chase installations are includ- ed with chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24", center to center and stacked at a vertical height difference of 18" (see Figure 18). Note: If a decorative shroud is to be installed, contact manufacturer for specifications.
Terminations/Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations. In any case, refer to installation instructions supplied with termination. Terminations approved for this fireplace are RT-8DM and RTL-8DM that can be used for flashing or chase and ET- 8DM, ETO-8DM, ETL-8DM and ETLO-8DM for chase style termination only. Figure 17 shows an RTL-8DM round top termination.


18" MIN. TYP.
Figure 18 - Multiple Chase Installation
Chimney Pipe · Waterproof Caulk

10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above highest point where it passes through roof and must be at least 2 feet above highest point of the roof that is within a horizontal distance of 10 feet (see Figure 19).
Finishing fireplace Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc., may make direct contact with sides and top around fireplace face. It is important that combustible materials do not overlap face itself. Brick, glass, tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.

Figure 19 - 10 Foot Rule
EFFECTIVE HEIGHT OF TERMINATION CAP

MIN. HEIGHT OF 22 FT. (WITH 2 ELBOW SETS) MAX. HEIGHT OF 50 FT.

Gas line hook up should be done by your supplier or a qualified service person. Note: Before you proceed, make sure your gas supply is turned off. Use only a 1/2" black iron pipe and appropri- ate fittings. 1. Remove knockout indentation on refracto- ry or firebrick wall located above refractory hearth floor. Knockout indentation must be firmly tapped with any solid object, such as a 1/2" dowel, until it is released. Remove fragmented portions of refractory (see Figure 21). 2. Remove gas line cover plate located on either side of fireplace and pull out insu- lation from gas line conduit sleeve. Save insulation for reuse. 3. Run a 1/2" black iron gas line into fire- place through rear at gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see Figure 22). Note: Secure incoming gas line to wood framing to provide rigidity for threaded end. 4. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement. Install gas appliance or cap off gas line if desired.
If you install a decorative gas appliance (vented gas log), decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS Z21.60 or Z21.84 and shall also be installed in accordance with the National Fuel Gas Code, ANSI 7223NFPA 54 latest edition.
Side Firebrick Finished Side
CAUTION: All gas piping and connections must be tested for leaks after installation is com- pleted. After ensuring that gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
Figure 21 - Gas Line Knockout
Side Firebrick Finished Side
Incoming 1/2" Black Iron Pipe
Seal Opening with Refractory Cement
Provide Enough Threaded End for Fitting Connection
Figure 22 - Gas Line Installation

Glass Doors Glass doors are standard with this fireplace. When fireplace is in operation, doors must be fully opened or fully closed position only or a fire hazard may be created (see Figure 23). A fireplace equipped with glass doors oper- ates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Exces- sive heat within fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be used to assure that both fireplace and glass door retain their beauty and function properly. Both the flue damper and glass doors must be fully opened before starting a fire. This will provide sufficient combustion air and maintain safe temperatures in firebox. IMPORTANT: The glass must be allowed to warm slowly and evenly. Tempered glass will withstand a gradual temperature rise to 550° F, which is more than a normal fire will generate. Such materials as pitch/wax laden logs, very dry mill end lumber and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep fire back from doors and never allow flames to contact glass.
Figure 23 - Glass Doors
Cleaning Glass Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean the glass. Do not clean glass with any cool water if glass is still hot from fire and smoke. A gas line or gas log lighter may be installed for the purpose of installing a vented or vent- free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4 dated August, 1993. If you wish to install an unvented (vent-free) gas log set, only unvented gas log sets which have been found to comply with the standard for unvented room heaters, ANSI Z21.11.2 are to be installed in this fireplace.

Damper handle operation Damper handle, which opens and closes damper blade, is located inside firebox at center towards back wall (see Figure 24). Pushing handle back into keyway slot will free damper blade to automatically open. To close, push handle back into keyhole slot then pull down and forward to lock it in place (see Figure 25).
Figure 24 - Damper Handle Location
For further operating guidelines, instruc- tions and warranty information, please re- fer to your homeowner's guide or contact your authorized dealer.
To Close Damper To Open Damper
Figure 25 - Damper Rod
Technical Service You may have further questions about installation, operation, or troubleshooting. If so, contact Style Crest, Inc. at 1-800-231-4822 or write to:
P. O. Box 19110 Wichita, KS. 67204. When calling or writing, please have your model and serial numbers of your heater ready.
Damper Handle · Damper Weight · Style Crest Service



Wood Burning Fireplace MODEL C42MW This list contains replaceable parts used in your fireplace. When ordering parts, see Replace- ment Parts on page 18 of this manual.
KEY NO. PART NO. DESCRIPTION QTY. 1 ** Insulation Pan 1 2 ** Air Separator 1 3 ** Firebox Top 1 4 108302-01 Air Deflector 1 5 ** Wrapper Top 1 6 ** Firebox Wrapper 1 7 ** Outer Wrapper/Insulation Assembly 1 8 ** Firebox Floor 1 9 ** Wrapper Bottom 1 10 ** Front Face Weldment, Smooth 1 11 see page 18 Left Side Brick Liner 1 12 see page 18 Rear Brick Liner 1 13 see page 18 Right Side Brick Liner 1 14 see page 18 Bottom Brick Liner 1 15 see page 18 Front Bottom Brick Liner 1 16 21198 Blower Access Plate 1 17 20027 Refractory Retainer 2 18 20060 Circulation Plate 1 19 21366 Insulation Retainer 1 20 106959-01 Top Standoff 4 21 20023 Chimney Starter Collar 1 22 20088 Door Stop 1 23 11418 Push On Nut 2 24 20090 Spring Clip 2 25 107001-02 Wood Burning Grate 1 26 106539-02 Grate Retainers 2 27 108424-01 Screen 2 28 ** Side Damper Weldment 1 29 107128-01 Gas Conduit 4 30 108790-01 Screen Rod 2 PARTS AVAILABLE - NOT SHOWN 106685-01 Male Polarized 1.4" Plug 1 14607 Rocker Switch 1 110037-01 Electrical Duct Assembly 1 BD42B Bi-Fold Glass Door (Brushed Brass) 1 ** Not a field replaceable part

Standard brick liner Left - 106971-01 Right - 106970-01 Rear - 108310-01 Bottom Rear 108312-01 Bottom Front 108311-01
Adjustable Hood Antique Brass Finish - GA6053 Black Painted Finish - GA6050 Required when installing a vent-free gas log in this fireplace.
ROOF FLASHING 0 TO 6/12 PITCH - V6F-8DM 6/12 TO 12/12 PITCH - V12F-8DM
Bi-Fold Glass Door (Brushed Brass included on unit) BD42 - Black BD42P - Platinum
Storm Collar SC1-1 For RT-8DM and RTL-8DM SC2-1 For RTT-8DM and RTTL-8DM
30° Offset and return 30E-8DM

Outside Air Kit for Side Wall Installation - AK4
Fan Kit - BK3
Outside Air Kit for Floor Installation - AK4F
Round Top Terminations RT-8DM, RTL-8DM
Round Top Terminations with Slip Section RTT-8DM, RTTL-8DM
Square Chase-Top Termination ET-8DM, ETO-8DM
Econo-Top Termination with Slip Section ETL-8DM, ETLO-8DM
MW9K (9' Vent Kit) 36-8DM 36" Double Wall Pipe 2 2 24-8DM 24" Double Wall Pipe 1 0 18-8DM 18" Double Wall Pipe 0 2 FST-A Adjustable Firestop Thimble 1 1 V6F-8DM Roof Flashing 1 1 SC1-1 Storm Collar 1 1 RTL-8DM Round Cap Termination 1 1
MW8K (8' Vent Kit)

*Use for Most Common Manufactured (Mobile) Home Installations
Vent Kit* Description

This product is manufactured for Style Crest Inc. under the VEXAR
2701 S. Harbor Blvd. Santa Ana, CA 92704 www.fmiproducts.com
108919-01 Rev. H 09/09