Peninsula woodBurning fireplace OWNER’S OPERATION AND INSTALLATION MANUAL

US C
SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain re placement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21.60, Z21.84 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard.
This wood burning fireplace complies with UL127- CAN/ULS-S610-M87 standard as a FACTORY BUILT APPLIANCE.
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to deter mine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com

Table of Contents Safety 2 Product Dimensions 3 Fireplace Installation 4 Venting Installation 6
Optional Gas Line Installation 12 Operation and Maintenance Guidelines 13 Technical Service 14 Replacement and Accessory Parts 15
This fireplace is intended for installation in ac cordance with the National Fire Protection As sociation Standard for Chimneys, Fireplaces, Vents and Solid-Fuel Burning Fireplaces, NFPA 211, and in accordance with codes such as the BOCA Basic/National Code, the Standard Mechanical Code, and the Uniform Building Code.
This fireplace is not intended to be used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.
doors, air inlet system and damper con trol. b. Use of any component part not manufac
tured or approved by FMI PRODUCTS, LLC in combination with a FMI PROD UCTS, LLC fireplace system. Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Although grounding may not be required by code in your area, it must be electrically grounded in accordance with lo cal codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70.


66 1/4"
Figure 1 - (V)PN36-A Dimensions

Spacers on Sides of Fireplace Provide Required 1" (2.5cm) Clearance
2" (5cm) Min. Clearance From Pipe to Combustibles
selecting location To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines: 1. The location must allow for proper clear ances (see Figure 2). 2. Consider a location where the heat output will not be affected by drafts, air condition ing ducts, windows or doors. 3. A location that avoids the cutting of joists or roof rafters will make installation easier. 4. If an outside air kit is to be installed, ac cessibility to outside combustion air must be considered. This can also be achieved through a vented crawl space in some cases (see Optional Outside Air Kit on page 6). The typical installation for a (V)PN36-A is a projected installation which allows you to ex tend the fireplace any distance into the room. A projection may be ideal for a new addition on an existing, finished wall.

Framing 1. Frame the opening for the fireplace using the dimensions shown in Figures 5, 7 and 8 depending on your installation.

Minimum clearance to combustibles Back and sides of fireplace 1/2" min. Adjacent wall 12" min. Chimney outer pipe surfaces 2" min. Bottom of fireplace to floor 0" min.



2. If fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, fireplace must be installed upon a metal or wood panel extending full width and depth of fireplace. 3. Set fireplace directly in front of opening and slide unit back until nailing flanges touch side framing. 4. Check the level of fireplace and shim with sheet metal if necessary. 5. Before securing fireplace to prepared framing, ember protector (provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing embers (see Figure 7). If fireplace is to be installed on a raised platform, a Z-type ember pro tector (not supplied) must be fabricated to fit your required platform height (see Figure 6). The ember protector should be made of galvanized sheet metal (28 gauge minimum) to prevent corrosion. 6. Using screws or nails, secure fireplace to the framing through flanges located on sides of the fireplace (see Figure 8).
Figure 7 - Ember Protectors

1/2" Minimum to Combustibles

Figure 8 - Nailing Flanges
Hearth Extension A hearth extension projecting a minimum of 16" in front of and a minimum of 8" beyond each side of the fireplace opening is required to protect combustible floor construction in front of fireplace (see Figure 9, page 6). Fabricate a hearth extension using a material which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply: 0.25 x 1.0" = 0.30" thickness required 0.84 Thermal conductivity "K" of materials can be obtained from manufacturer or supplier of noncombustible material. If hearth extension is to be raised, a “Z” type ember protector must be used (see Figure 6 and Figure 10, page 6)
39 7/8" Platform Must Be Solid, Flat, and Fully Supported
“Z” Type Metal Safety Shields Not Supplied
*As Required by Design As Long as Ceiling Clearance is Maintaned
Figure 6 - Framing Firebox with “Z” Type
Nailing Flanges · Ember Protectors

2" X 4" Stud


Figure 11 - Mantel Clearances to
Figure 9 - Hearth Extensions


Combustible Material Must Not Overlap Black Metal Front Face
Figure 12 - Mantel Clearances to Metal
Optional Outside air Kit The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it’s location. Outside combustion air is accessed through and exterior wall or a vented crawl space.
Figure 10 - Raised Hearth Extension
Mantel Clearances Woodwork such as wood trims, mantels or any other combustible material projecting from the front face must not be placed within 9" of fireplace opening. Combustible materials above and projecting more than 1 1/2" from the fireplace front face (see Figure 11) must not be placed less than 12" from effective opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3). Mantels or any other combustible material may also come up to the side edge of the black metal face of the fireplace only if the projection from the front face falls within limits shown in Figure 12.

The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.
For further details on installation of outside air kit, please refer to instructions included with air kit.
Combustible Materials · Face · Ember Protector

Pipe Installation The pipe sections must be assembled inde pendently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections. Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked to gether. When installing double wall snap-lock chimney together, it is important to assure the joint between the chimney sections is locked. Check by pulling chimney upward after lock ing. The chimney will not come apart if prop erly locked. It is not necessary to add screws to keep the chimney together (exception, see Figure 17, page 8).
Secure to Collars with Duct Tape or Screws

Air Inlet Location Must Allow For Bushes or Snow
Vent Hood Required for Wall Installation
Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)
Figure 13 - Outside Air Kit Installation
Chimney Pipe The FMI PRODUCTS, LLC chimney is a snap-lock, double-wall pipe. It consists of a stainless steel inner flue pipe(s), a galvanized outer pipe and a wire spacer. Each section of pipe comes in lengths of 12", 18" 36" and 48". The actual lineal gain for each is measured after each section is fully connected. Lineal gain is the actual measur able length of a part after two or more parts are connected.
15" Galvanized Outer Pipe
Hemmed End 12 3/8" Stainless Inner Pipe
Figure 14 - Pipe Connection
Using ELBOW offsets and Supports Chimney weight above offset rests on return elbow. Straps must be securely nailed to raf ters or joists (see Figure 15, page 8). To achieve desired offset, you may install combinations of 12", 18", 36" and 48" length of double wall pipe (see offset chart and Figure 16, page 8). The chimney support section is a 4" strap and 12" length of pipe. A chimney support is required every 30 feet above fireplace after a straight chimney run or above a return elbow after a straight chimney run (see Figure 17, page 8). This support is designed to relieve the extra weight load on fireplace and elbows when high chimneys are installed.

B
A
Figure 16 - Rise and Offset
Screws

Uncommon circumstances such as neigh boring hills, tall trees, or strong wind areas can cause down drafts in chimney system. In such cases, going beyond the minimum recommended height would be preferable to provide a better draw. The fireplace height approved for any chim ney run with this fireplace system is 40 feet measured from bottom of fireplace to flue outlet-end of pipe (see Figure 22).
Screws or Staples (Min. of 8)
Figure 19 - Firestop Spacer with Living
Screws or Staples (Min. of 8)
Figure 20 - Firestop Spacer with Attic
10 Foot Rule All chimney terminations must extend a mini mum of 3 feet above the highest point where it passes through the roof and must be at least 2 feet above roof with a 10 foot horizontal span (see Figure 21). IMPORTANT: If an exposed portion of chim ney is greater than 4 feet above the roofline, use support wires to keep chimney secure. Support wires may be attached to outer pipe of chimney with screws, if screws do not penetrate inner flue pipe.
15 Ft.
50 Ft.
Figure 21 - 10 Foot Rule
Minimum / Maximum Chimney Height The minimum height of the chimney (mea sured from the base of the fireplace to the flue gas outlet-end of pipe) is 16 feet for a straight run, 16 feet minimum for a run with 1 elbow set and 25 feet minimum for a run with 2 elbow sets. (A set consists of one starter elbow and one return elbow.)
Figure 22 - Maximum Chimney Height


Penetrating Roof To maintain a 2" clearance to pipe on a roof with a pitch, a rectangular opening must be cut. 1. Determine the center point through which pipe will penetrate roof. 2. Determine center point of roof. Pitch is the distance the roof drops over a given span, usually 12". A 6/12 pitch means that the roof drops 6" for each 12" one measure horizontally down from roof rafters. 3. Use roof opening chart (Figure 23) to determine correct opening length and flashing required. 4. Remove shingles around opening mea sured. Cut out this section. 5. Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above highest point of roof cutout. Termination and chimney must extend a minimum of 36" above highest point where it passes through the roof.
Figure 24 - Flashing Installation
Storm Collar Installation Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figures 24 and 25). Apply wa terproof caulking to all seams and notches around storm and also at base around shingles.
19" Min. (48.26cm)
2" Min. (5.08cm)
30" Min. (76.2cm
2" Min. (5.08cm)
2" Min. (5.08cm)
Figure 25 - Storm Collar
Terminations The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination. Terminations approved for this fireplace are RLT-12D, which can be used for flashing or chase and STL-12D for chase style termina tion only. Figure 26, page 11, shows an RLT- 12D round top termination.
Figure 23 - Roof Opening Measurements
Flashing Installation Determine flashing to be used with roof open ing chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 24). DO NOT NAIL THROUGH FLASHING CONE.

finishing fireplace Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc. may make direct contact with sides and top around the fireplace face. It is important that combustible materials do not overlap the face itself. Brick, glass, tile or other noncom bustible materials may overlap the front face provided they do not obstruct essential open ings like louvered slots or any other opening. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.

Installing fireplace facing Any noncombustible material may be used for facing (glass, tile, brick, etc.) as long as proper clearances are adhered to and fireplace openings are not obstructed in any way (see Minimum Clearance to Combustibles, page 4 and Figure 28). Use only heat resistant, noncombustible mor tar or adhesive when securing facing material to front of fireplace. When placing facing at upper edge of effective opening of fireplace, provide “L” shaped piece of metal extending full width of opening (see Figure 28). Secure with sheet metal screws at a distance high enough from edge so it doesn't interfere with operation of doors. This assures that fac ing material will not block openings.
Overlap Shingles (Top and Sides of Flashing Base)
Figure 26 - Terminations
Chase installations Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. Terminations must be separated a minimum of 30" center to cen ter and stacked at a minimum vertical height difference of 18" (see Figure 27). Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.


18" Min. Typ.
Figure 28 - Fireplace Facing (Your Fireplace May Vary from Illustration)
Figure 27 - Multiple Chase Installation
Underlap Shingles

CAUTION: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPER ATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALI FIED SERVICE PERSON.
NOTICE: Before you proceed, make sure your gas supply is turned off. A gas line may be installed for the purpose of installing a vented or vent-free decorative gas appliance available through your local distributor. Use only gas piping approved by local codes. When installing a gas line, a shutoff valve designed for installation outside the appliance is recommended. The gas pipe is intended for connection to a decorative gas appliance that operates using natural or propane/LP gas only. This appliance must have an automatic shutoff device and must comply with the Standard for Decora tive Gas Appliances for Installation in Vented Fireplace, ANSI Z21.60. ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS, ANSI Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE. Use only a 1/2" black iron pipe and appropri ate fittings. 1. Remove knockout indentation on refrac tory or firebrick wall located approximately 2" above refractory hearth floor. Knockout indentation must be firmly tapped with any solid object such as a 1/2" dowel until it is released. Remove fragmented portions of refractory (see Figure 29). 2. Remove gas line cover plate located on rear of fireplace and pull out insulation from gas line conduit sleeve. Save insula tion for reuse. 3. Run gas line into fireplace through the rear at 11 1/4" from floor and through gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see Figure 30). Note: Secure incoming gas line to wood framing to provide rigidity for threaded end. 4. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement, Install gas appliance or cap off gas line if desired.
Side Firebrick Finished Side
Gas Line Conduit Insulation
Figure 29 - Gas Line Knockout
Side Firebrick Finished Side
Incoming 1/2" Black Iron Pipe
Seal Opening with Refractory Cement
Provide Enough Threaded End for Fitting Connection
Figure 30 - Gas Line Installation

Maintenance
Guidelines
Glass Doors Bi-fold glass doors are optional with this fireplace. Check with your local distributor for availability. To install glass doors, refer to installation instructions that are included with kit. When fireplace is in operation, doors must be fully open or fully closed position only or a fire haz ard may be created (see Figure 31). A fireplace equipped with glass doors oper ates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if combustion air gate is not completely open.
Figure 31 - Bi-Fold Glass Doors
Cleaning Glass Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from the fire. To remove doors, refer to instruc tions included with glass door kit.

Grate The grate is designed to provide you with the maximum solid fuel capacity. Do not overload grate or obstruct required air space beneath it. Doing so may cause smoke spillage and a fire hazard.
Guidelines
damper Mechanism The damper control lever is located inside the fire chamber (see Figure 32). Make sure lever is cool before handling. Pull down to close and push up to open. Damper must be open when lighting a fire. Not doing so will cause smoke spillage into the room. When fireplace is not in use, close damper to prevent down drafts to enter room.
Never obstruct flow of combustion and ven tilation air. Keep front of fireplace clear of all obstacles and materials.
Chimney Have your chimney system cleaned and in spected regularly to ensure safe and efficient operation.
Technical Service You may have further questions about instal lation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328- 4537. When calling please have your model and serial numbers of your heater ready. You can also visit web site at www.fmiproducts.com
OUTSIDE AIR HANDLE PULL TO CLOSE PUSH TO OPEN DAMPER CONTROL LEVER PULL DOWN TO CLOSE PUSH UP TO OPEN
Figure 32 - Damper Operation
Outside Air Mechanism The outside air handle is located at the right hand side of fireplace rear refractory (see Figure 32). Pull to close, push to open. Al ways open mechanism when starting a fire. This provides adequate outside combustion air. Close mechanism when not in use to prevent cold air from entering room. Periodi cally check your outside air intake vent hood for any possible obstructions such as snow, bushes, etc.


GRATE
Firestop Spacer FS-10 for Straight Pipe 30FS-10 for 30° Angled Run
EMBER PROTECTORS 20093
Flashing V6F-10DM 0 to 6/12 Pitch V12F-10DM 6/12 to 12/12 Pitch
Double Wall Pipe - 12-12DM, 18-12DM, 24-12DM, 36-12DM, 48-12DM
(Chimney pipe assembly includes outer and inner pipes and comes with wire spacer. Also available in triple wall.)
Return Elbow Starter Elbow
Double Wall 30° elbow/Offset 30E-12DM (Also available in triple wall.)
Double Wall Pipe support assembly 12S-12DM (Also available in triple wall.)
Bi-Fold Glass Doors DG368ST - Brushed Brass DBP368ST - Black with Brass Trim DC368ST - Platinum

2701 S. Harbor Blvd. Santa Ana, CA 92704
115607-01 Rev. D 09/09
1-866-328-4537 www.fmiproducts.com