Instruction/ maintenance manual of the product 36CF FireplaceXtrordinair
Go to page of 48
36 C F S T /Pier Gas F ir ep lace Tested and Listed by OMNI-Test Laboratories, Inc. Portland, Oregon Report # 028-F-87-5 ANSI Z21.88a-2007 • Built-In Direct Vent Fireplace • Natural Gas or Propane.
2 Introduction © Travis Industries 4090102 100-01212_000 Overview This manual details the installation requirements for the 36 CF ST and Pier fireplace. For operating and maintenance instructions, refer to the 36 CF ST/Pier Owner's Manual (part # 100-01213).
Table of Contents 3 © Travis Industries 4090102 100-01212_000 Introduction Overview ................................................................. 2 Listing Details .......................................................... 2 Safety Precautions Safety Precautions .
4 Safety Precautions © Travis Industries 4090102 100-01212_000 Safety Warnings: • Failure to follow all of the requirements may result in property damage, bodily injury, or even death. • This unit must be installed by a qualified installer to prevent the possibility of an explosion.
Safety Precautions 5 © Travis Industries 4090102 100-01212_000 Safety Warnings (continued): • Allow the heater to cool before carrying out any maintenance or cleaning.
6 Features and Specifications © Travis Industries 4090102 100-01212_000 Installation Options • Residential or Mobile Home • Flush or Recessed Face • Raised or Floor Placement • Horizontal or .
Installation (for qualified installers only) 7 © Travis Industries 4090102 100-01212_000 Packing List • Glass LatchTool • Log Set with Embers and Rock Wool • Remote Control with Wall Mount • .
8 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Massachusetts Requirements NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Installation (for qualified installers only) 9 © Travis Industries 4090102 100-01212_000 Preparing the Fireplace Stand-offs This appliance is shipped with the header and side stand-offs in the retracted position. These stand- offs must be placed in their upright position prior to installing the fireplace.
10 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Fireplace Placement Requirements • Fireplace must be placed in a room with a minimum 96” ceiling. • Fireplace must be placed directly on the sub-floor or wood platform (not on linoleum or carpet).
Installation (for qualified installers only) 11 © Travis Industries 4090102 100-01212_000 Minimum Framing 36 CF ST (See Through) 62-1/2" Minimum 78” Fireplace Enclosure Height NOTE: W e recommend you install the framing after placing the fireplace in position.
12 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Framing Dimensions – 36 CF Pier 18-1/4" 22-1/2 ” NOTE : Do not build into this area - it must be left clear to provide adequate clearance for the vent.
Installation (for qualified installers only) 13 © Travis Industries 4090102 100-01212_000 Attaching Stand-Offs to Framing a b c d e Figure 7.
14 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Required Electrical Connection Make sure power to the heater has been turned off prior to installation (disable the breaker). Do not connect 110-120 VAC to the gas control valve or the on/off circuit on this fireplace.
Installation (for qualified installers only) 15 © Travis Industries 4090102 100-01212_000 Battery Pack / Learn Switch Installation • The battery pack and learn switch must be mounted inside a junction box in a location that may be reached by the 12’ long battery box wires (see Figure 8 ).
16 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Steps for Installing the Battery Box and Learn Switch 1. Remove the control cover and attach the 12’ long battery box wire to the quick connects on the receiver module (see Figure 9 below).
Installation (for qualified installers only) 17 © Travis Industries 4090102 100-01212_000 Remote Synchronization The fireplace is shipped with the remote and fireplace pre-synchronized . Do not synchronize the remote unless you are 100% sure it does not work correctly.
18 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Gas Line Requirements MASSACHUSETTS INSTALLATIONS - WARNING: THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
Installation (for qualified installers only) 19 © Travis Industries 4090102 100-01212_000 Vent Requirements • The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.
20 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Vent Clearances IN THE ENCLOSURE (under 78") Vertical or Horizontal Sections: 6" Clearance Above 3-1/2" Clearance To The Side 2" Clearance Below Horizontal Penetrations (through walls, etc.
Installation (for qualified installers only) 21 © Travis Industries 4090102 100-01212_000 Approved Vent Configurations Exhaust Restrictor Adjustment An exhaust restrictor is built into exhaust vent at the rear of the fireplace. It is used to adjust the flow rate of exhaust gases.
22 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Rear Vent, Horz. Term. (1 45 ° Elbow) • The vent must not exceed 5 feet (see chart below). • Use Exhaust Restrictor Position # 1.
Installation (for qualified installers only) 23 © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Rear Vent, Horz. Term. (1 45 ° , 2 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
24 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Rear Vent, Horz. Term. (1 45 ° , 4 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
Installation (for qualified installers only) 25 © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Rear Vent, Vert. Term. (1 45 ° , 3 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
26 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Top Vent, Horz. Term. (1 45 ° ,1 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
Installation (for qualified installers only) 27 © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Top Vent, Horz. Term. (1 45 ° , 3 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
28 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Top Vent, Vert. Term. (1, 3, or 5 45 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
Installation (for qualified installers only) 29 © Travis Industries 4090102 100-01212_000 Approved Vent Configuration – Top Vent, Vert. Term. (1 45 ° ,2 90 ° Elbows) • The termination must fall within the shaded area shown in the chart. Use the indicated restrictor positions.
30 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Termination Requirements ! Venting terminals shall not be recessed into a wall or siding.
Installation (for qualified installers only) 31 © Travis Industries 4090102 100-01212_000 Hearth Requirements NOTE : Whenever using a hearth over 1” thick, the fireplace will need to be rai sed. Flush Hearth Side View Min.10” Min. 64” (on ST, Pier will vary) Min.
32 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Hearth Requirements – Recessed Hearth A hearth is not required if the fireplace is raised 6 ” above the flooring surface.
Installation (for qualified installers only) 33 © Travis Industries 4090102 100-01212_000 Facing Requirements • Attach the included fiber board (or other non-combustible) to the fireplace and framing (see Figure 22 below).
34 Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Non-Combustible Facing • Non-combustible facing on the front of the fireplace must extend a minimum 16-1/2” from the top of the glass frame (49-1/2” from the base of the fireplace).
Installation (for qualified installers only) 35 © Travis Industries 4090102 100-01212_000 Mantel Requirements • The mantel (combustible or non-combustible) must be a minimum 49-1/2” above the base of the fireplace (see Figure 2 4) . • The maximum mantel depth is 12” (measured from the face).
36 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Steps for Finalizing the Installation WARNING: Prior to removing the glass, shut off gas to the appliance (or remove the batteries from the battery box and shut off electricity to the fireplace).
Finalizing the Installation (for qualified installers only) 37 © Travis Industries 4090102 100-01212_000 7. Check the air shutter following the directions below. Air Shutter Adjustment Let the heater burn for fifteen minutes (make sure the logs and glass are in place).
38 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Glass Frame Removal and Installation WARNING: Prior to removing the glass, shut off gas to the appliance (or remove the batteries from the battery box and shut off electricity to the fireplace).
Finalizing the Installation (for qualified installers only) 39 © Travis Industries 4090102 100-01212_000 Log Set Installation Ember Placement Place the embers along the firebox floor and burner to help conceal the burner . Make sure none of the embers are directly over the burner holes.
40 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Log Installation NOTE : The logs are a mirror-image (same logs fit on left and right side). Both the 36 CF See Through (ST) and Pier use the same log set.
Finalizing the Installation (for qualified installers only) 41 © Travis Industries 4090102 100-01212_000 Top 2 logs (last 2 logs) Picture from opposite side.
42 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 Picture from end (Pier only).
Finalizing the Installation (for qualified installers only) 43 © Travis Industries 4090102 100-01212_000 LP Conversion Instructions Install the conversion kit prior to installing the fireplace to ensure proper gas use. 1 Remove the glass (see page 3 6).
44 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 5 Remove both side burners (4 screws hold each one in place).
Finalizing the Installation (for qualified installers only) 45 © Travis Industries 4090102 100-01212_000 7 The manifolds that secure the three orifices are visible at this point. Detach the air shutter stopper on the mixing tube brackets to gain full access to the orifices (2 screws hold them in place).
46 Finalizing the Installation (for qualified installers only) © Travis Industries 4090102 100-01212_000 1 1 The gas control valve has a propane conversion shaft that alters the outlet pressure. Remove the rubber cap over the propane conversion shaft and twist the small knob so the line points to “LP” (see Figure 27 ).
Finalizing the Installation (for qualified installers only) 47 © Travis Industries 4090102 100-01212_000 Power Heat Duct Installation The optional power heat duct ma y b e used with this fireplace. Refer to the part numbers below if y ou wish to inst a this accessor y .
48 Index © Travis Industries 4090102 100-01212_000 Index Andiron Installation .............................................4 7 Additional Items Required ....................................7 Air Shutter Adjustment ....................................
An important point after buying a device FireplaceXtrordinair 36CF (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought FireplaceXtrordinair 36CF yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data FireplaceXtrordinair 36CF - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, FireplaceXtrordinair 36CF you will learn all the available features of the product, as well as information on its operation. The information that you get FireplaceXtrordinair 36CF will certainly help you make a decision on the purchase.
If you already are a holder of FireplaceXtrordinair 36CF, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime FireplaceXtrordinair 36CF.
However, one of the most important roles played by the user manual is to help in solving problems with FireplaceXtrordinair 36CF. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device FireplaceXtrordinair 36CF along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center