FS-8700-80 McQuay Micro Tech
Open Protocol
Effective for all systems manufactured after May 1, 2001



This document describes the FieldServer driver used to transfer data between a FieldServer and MicroTech® controllers. Transfers are done using the controller's Data Terminal Communications Protocol. In this document the protocol is referred to as the McQuay Micro Tech Open Protocol. The McQuay Micro Tech Open Protocol driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using McQuay Micro Tech Open Protocol. The FieldServer can emulate either a Server or Client. When emulating a Client, the driver enables the FieldServer to request ‘Everything’ from the McQuay device as well as a number of advanced options which allow specific fields to be read or written and device scaling to be applied. When emulating a Server, the driver provides an emulation of the byte memory of a device and responds to read and write requests. The following important points and limitations should be noted before proceeding with this manual. 1. Arising from a feature of the McQuay Micro Tech Open Protocol is the peculiarity, that when a multi- byte value is written to a McQuay device, the write is done one byte at a time (one byte of data can be transferred per poll/response message pair) allowing for the possibility (at least for a short period) that the multi byte value is only partially correct until all the messages have been completed. 2. The vendor equipment is limited to a maximum of 9600 baud. Given that each message packet can only transfer one byte of data and that some data of interest is multi-byte, users of this protocol should expect low data transfer rates. 3. Port expansion is not supported for this driver. 4. A document identified as Ed15050 MicroTech Network Operations contains important information regarding the connection requirements of 3rd party equipment such as the FieldServer to a Microtech network. The document also defines a number of limitations for such connections. The following quotations from this document outline some of this information.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

PC Connection The PC connection to a MicroTech controller is through an available port A that is configured as TTY. It is best to connect the PC to a level-1 controller because data transmission is the fastest. However, a PC can be connected to any level-2 controller that does not have level-3 controllers connected to it or to any MicroTech level-3 controller. Regardless of where you connect the PC, you have access to the entire network. You can connect two or more PCs to the network, but only one PC can be connected to a particular controller. The PC that you use most often should be connected to the level-1 controller for best performance. For example, you may have one PC that you use on site and another PC that you use off site. In this situation, you may want to connect the on-site PC to the level-1 controller and the modem for the off-site PC to a level-2 or level-3 controller. If a PC is connected to a level-2 controller, a level-1 controller must poll that level-2 controller connected to the PC so that the PC has access to the entire network. Defining a level-2 controller in the level-1 controller Server list causes the level-1 controller to poll the level-2 controller. Port Configuration: The communications port that the PC is connected to must be configured as a TTY port. The default port configuration for most MicroTech controllers sets port A as TTY. The port configuration is a software setting. A separate software setting defines the communications rate of each port. In most controllers, the default rate is 9600 bps. TTY: A TTY port is used to connect a PC for monitoring purposes. It uses the RS-232C interface standard and the Data Terminal Communications protocol. 5. The following quote from “MicroTech® Data Terminal Communication Packets, Open Protocol™ Data Communications Information Packet ” highlights an important limitation of the protocol.
Data terminal communications may be sent via RS-232C or RS-485. Regardless of the electrical standard used for communications, this protocol is a single ended type (i.e., communications to one MicroTech controller maximum). 6. Each MicroTech controller is shipped from the factory with a unique job site password. The passwords are provided by the McQuay International representative at the time of startup. 7. The driver does not validate passwords when configured as a Server. This means that requests to read or write data will succeed even if the password supplied with the request is incorrect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

2.1. Supplied by FieldServer Technologies for this driver
2.2. Provided by Supplier of 3rd Party Equipment
PART # DESCRIPTION McQuay Motor Mount Connector for Port A connection 3. Hardware Connections
The FieldServer is connected to the McQuay device as shown below. Configure the McQuay device according to manufacturer’s instructions.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer. (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a McQuay Micro Tech Open Protocol Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for McQuay Micro Tech Open Protocol communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
4.1. Data Arrays

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters
Data_Format Provide data format. Each Data Array can only take on one format.
Number of Data Objects. Must be larger than the data storage area required for the data being placed in this array.

// Data Arrays // Data_Arrays Data_Array_Name ,Data_Format ,Data_Array_Length DA_AI_01 ,UInt16 ,200 DA_AO_01 ,UInt16 ,200 DA_DI_01 ,Bit ,200 DA_DO_01 ,Bit ,200
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Example

4.2. Client Side Connection Descriptors

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R21
Baud* Specify baud rate 300, 1200, 2400, 4800 and 9600 baud (Vendor limitation). Parity* Specify parity Even (Vendor limitation) Data_Bits* Specify data bits 7 (Vendor limitation) Stop_Bits* Specify stop bits 1 Protocol Specify protocol used MCQ, McQuay Handshaking* Specify hardware handshaking None Poll Delay* Time between internal polls 0-32000 seconds, 1 second
// Client Side Connections Connections Port ,Baud ,Parity ,Data_Bits ,Protocol ,Handshaking ,Poll_Delay P1 ,9600 ,Even ,7 ,McQuay ,None ,0.100s

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Example

4.3. Client Side Node Descriptors
Column Title Function Legal Values
Up to 32 alphanumeric characters
Node_Name Provide name for Node
Network address of the device being polled. If the network address field is set to $00FF, the controller will respond to the packet without regard to its own internal network address
This parameter must be used If units are connected to the FieldServer via a routing device e.g. OPM. The network address consists of the OPM address and the unit address.
Protocol Specify protocol used MCQ, McQuay
Port Specify which port the device is connected to the FieldServer P1-P8, R1-R22
200CFC, 100CFC, 050RPC, 001ASC, 000SCU, Type-Unknown
The name of the McQuay Equipment type being polled. Select one from the list on the left. The equipment type must be known for the driver to operate correctly.
Password Maximum of 8 characters. Ascii characters only. Example 1 of 2 // Client Side Nodes // (No routing device used) Nodes Node_Name ,Node_ID ,Protocol ,Port ,Password ,PLC_Type Chiller ,1 ,McQuay ,P1 ,Abcdefgh ,200CFC Example 2 of 2 // Client Side Nodes // (Routing device with address 3 used) Nodes Node_Name ,Node_ID ,Route ,Protocol ,Port ,Password ,PLC_Type Chiller1 ,66 ,3 ,McQuay ,P1 ,Abcdefgh ,200CFC


2 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters

Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters
Name of Data Array where data is to be stored in the FieldServer
One of the Data Array names from “Data Array” section above
Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above
Function Function of Client Map Descriptor Rdbc, Wrbc, Wrbx
4.4.2. Driver Related Map Descriptor Parameters
Column Title Function Legal Values
One of the node names specified in “Client Node Descriptor” above
Node_Name Name of Node to fetch data from
Length of Map Descriptor. Only one data field can be read or written per poll/response sequence, thus driver assumes a length of 1.
Set to 1 except when reading a direct address.
The name of the data field of interest. Each address with meaningful data in the McQuay device has a name. The field names are defined in a specification for each device type. If the field name is unknown, the Address can be defined. Refer to Appendix A.4 for further information.
‘Everything’ or select a field name from Table 2
If set to No then the driver stores the raw values, if set to Yes, the data is scaled before storing. The device scaling applied is shown in Table 1. Note that ‘Device_Scaling’ has no meaning when writing to a McQuay device.
4.4.3. Timing Parameters
Column Title Function Legal Values Scan_Interval Rate at which data is polled >0.1s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

In this example the Map Descriptor tells the driver to read all data fields known for the Node. The data fields are read sequentially and the value
obtained placed in the Data Array at a location determined by the driver. Appendix A.2 outlines the data read and the Data Array location of each
field. There is no way of telling this command to read some fields more often than others. Each field is read in turn and when the end of the list is
Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Length ,Scan_Interval ,Field_Name ,Device_Scaling
Read Chiller 1 ,DA_CHILLER1 ,0 ,Rdbc ,Chiller1 ,1 ,1.0s ,Everything ,Yes
The values will be
the raw value read
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
storage.
by 10.
field known for the
device.
4.4.4. Map Descriptor Example 1 – Read Everything.
node which in turn
port.
its value stored in this
Array is at least 200,
so that all parameters
Each field read has
on the field name.
length of the Data
reached the driver starts at the beginning again.
Data Array. The
can be stored.
the Map Descriptor in
report the name of
thus it is strongly
used.

This example illustrates how to read data for one particular field of interest. The data is read every 2.0 seconds and the value obtained is stored in
This example illustrates how to write data to control fields in the McQuay device. This example illustrates the use of the Wrbx (write on change)
function. A write message will be generated each time the data at index 0 in the Data Array changes. When writing multibyte fields, several
messages are required to transfer the byte values to the McQuay devices. Note that ‘Device_Scaling’ has no meaning when writing to a McQuay


Chiller10_Op_Mode ,DA_OPERATIONAL_MODES ,10 ,Rdbc ,0s ,Chiller10 ,1 ,Chiller Operation Mode
Chiller1_Op_Mode ,DA_MODES ,0 ,Wrbx ,Chiller1 ,1 ,Chiller Operation Mode
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
4.4.5. Map Descriptor Example 2 – Read a particular Data Field.
device. The user must ensure that valid numbers are written to the data fields.
Ensure that you spell and space the field name exactly as it is
This Map Descriptor reads one single value from the McQuay
the Data Array named DA_OPERATIONAL_MODES at location 10.
4.4.6. Map Descriptor Example 3 – Write.

5.1. Server Side Connection Descriptors

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R23
Baud* Specify baud rate 300, 1200, 2400, 4800 and 9600 baud (Vendor limitation) Parity* Specify parity Even (Vendor limitation) Data_Bits* Specify data bits 7 (Vendor limitation) Stop_Bits* Specify stop bits 1 Protocol Specify protocol used MCQ, McQuay Handshaking* Specify hardware handshaking None Example

// Server Side Connections Connections Port ,Baud ,Parity ,Data_Bits ,Protocol ,Handshaking ,Poll_Delay P1 ,9600 ,Even ,7 ,McQuay ,None ,0.100s
3 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

5.2. Server Side Node Descriptors
Title Function Legal Values
Up to 32 alphanumeric characters
Node_Name Provide name for node
Network address of the device being polled. If the network address field is set to $00FF, the controller will respond to the packet without regard to its own internal network address
This parameter must be used If units are connected to the FieldServer via a routing device e.g. OPM. The network address consists of the OPM address and the unit address.
Protocol Specify protocol used MCQ, McQuay
Specify which port the device is connected to the FieldServer. This parameter is optional for Server side nodes. The reason is that when a poll is received on any port an attempt will be made to match it against any Map Descriptor/node irrespective of the port. If emulating more than one node with the same address, however, the Nodes must be linked to specific ports.
200CFC, 100CFC, 050RPC, 001ASC, 000SCU, Type-Unknown
This parameter has no meaning for a Server but it must be specified to allow the driver to complete its configuration file validation.
This parameter is ignored for a Server. Although every poll contains a password, this driver does no password validation when configured as a Server.
Ascii characters only.

// Server Side Nodes Nodes Node_Name ,Node_ID ,Protocol ,PLC_Type FieldServer ,11 ,McQuay ,200CFC
4 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

5.3. Server Side Map Descriptors
5.3.1. FieldServer Specific Map Descriptor Parameters

Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters
Name of Data Array where data is to be stored in the FieldServer
One of the Data Array names from “Data Array” section above
Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above
5.3.2. Driver Specific Map Descriptor Parameters

One of the node names specified in “Client Node Descriptor” above
Data_Type This commonly used Field Server parameter has no meaning for this driver.
Starting address of read block Addresses cannot be specified in hexadecimal format.
5.3.3. Timing Parameters

Specifies time Server side waits before responding to Client that node is offline on FieldServer Client side.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

This example illustrates how you can configure the FieldServer as a McQuay Micro Tech Open Protocol Server. A single Map Descriptor is used
to emulate a McQuay device’s memory as one large single block of bytes. Any requests in the address range 1-0x270F can be serviced by this
one Map Descriptor. The strategy is simple but has one drawback; a large Data Array which will be mostly empty is used. This does not affect
When a poll is received, the driver looks through the Map Descriptor and finds one with a matching node and one whose address and length cover
10,000 is the maximum length of a Data Array so there is no point in
making the Map Descriptor longer.
Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Address ,Length
Chiller1_emulation ,DA_CHILLER1 ,0 ,Passive ,Chiller1 ,1 ,10000
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
The Node name connects the
definition and possibly to a
Map Descriptor to a Node
port.
5.3.4. Map Descriptor Example – Strategy 1.
Descriptor is used to respond
to polls but does not generate
Passive means that the Map
performance but does use the FieldServer’s memory resource.
any poll’s itself.
Ensure that Data Array’s
length is at least as long
as the Map Descriptor’s.
A data format of BYTE is
the poll’s address.
appropriate,

When a poll is received, the driver looks through the Map Descriptors and finds one with a matching node and one whose address and length
This example differs from the previous example, in that it divides the memory being emulated into chunks to avoid having a large sparse array.
Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Address ,Length
Chiller1_emulation1 ,DA_CHILLER1 ,0 ,Passive ,Chiller1 ,1024 ,256
Chiller1_emulation2 ,DA_CHILLER1 ,256 ,Passive ,Chiller1 ,2048 ,256
A few more Map Descriptors could be
added to serve the remaining data
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
These two address ranges cover
almost all the data fields in a 200
field addresses.
1024 = 0x400 2048 = 0x800
series chiller.
5.3.5. Map Descriptor Example – Strategy 2.
By using the same
offset the data can
all be packed into
a smaller array.
cover the poll’s address.
Array is used for
Descriptors.

Appendix A. Advanced Topics
Appendix A.1. Scaling
User Scaling: The user can specify scaling in the configuration file which allows a value to be scaled before being stored in a Data Array or after being extracted from a data for writing to McQuay device. This scaling is specified by using the following keywords in Map Descriptor definition.
Data_Array_Low_Scale, Data_Array_High_Scale, Device_Low_Scale, Device_High_Scale….. Device Scaling: The raw values read from a McQuay device may be treated as raw values or they may be scaled. Device scaling is the term used to describe the hard-coded scaling specified by McQuay for each data field. By applying device scaling the user can avoid details or knowledge of the scaling and used the converted value directly.
If this scaling is required then use the Device_Scaling parameter (see 4.4.2)
There are 5 device scaling methods. X refers to the raw value obtained from the McQuay device. The method that will be applied to each field is shown in the following table.
Table 1 – Device Scaling Method applied to each Field
Method Id. Device Scaling Method 1 X 2 X / 10 3 ( X – 1000 ) / 10 4 X / 2 5 X - 100 6 ( X – 100 ) / 10 7 ( X / 5 ) + 20 8 ( X / 5 ) + 55 9 ( X / 5 ) 10 ( X / 5 ) - 100
As a Client: - Device and User scaling may be applied.
As a Server. Device Scaling and User scaling is not applied. The raw value written to any data location is stored as is and the raw value read from a Data Array used in formatting the response to a read.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

Appendix A.2. Data Field Name Tables♣
If you do not know the field name it is possible to read the device by specifying the address only. More information is provided in Appendix A.4
1 r Model 3 0x0A08 1 4 r Refrigerant 1 0x0A0B 1 5 r Units of Measure 1 0x0A0C 1 6 r Software Version 2 0x0A0D 1 8 r Software Revision 1 0x0A0F 1 11 r Chiller Unit Temperature Type 1 0x084B 1 12 r Communication Status 1 0x040C 1 13 r Compressor Lift Pressure 2 0x046A 2 15 r Compressor Motor Current 2 0x044C 1 17 r Compressor Motor Current Percent 1 0x044A 1 18 r Compressor Number of Starts 2 0x085F 1 20 r Compressor Operating Hours 2 0x0851 1 22 r Compressor Suction Temperature 2 0x043A 3 24 r Compressor Superheat - Discharge 2 0x046E 2 26 r Compressor Superheat -Suction 2 0x046C 2 28 r Condenser Approach Temperature 2 0x0484 2 30 r Condenser Heat Recovery Unit Present 1 0x083F 1 31 r Condenser Heat Recovery Temperature - Delta 2 0x048A 2 33 r Condenser Heat Recovery Water Temp. - Entering 2 0x0454 3 35 r Condenser Heat Recovery Water Temp. - Leaving 2 0x0456 3 37 r Condenser Pump Status 1 0x0425 1 38 r Condenser Pump # 1 Operating Hours 2 0x085A 1 40 r Condenser Pump # 2 Operating Hours 2 0x085D 1 42 r Condenser Refrigerant Pressure 2 0x0440 2 44 r Condenser Refrigerant Temperature 2 0x0466 3 46 r Condenser Subcooling Temperature 2 0x0480 2 48 r Condenser Water Flow Rate 2 0x0452 1 50 r Condenser Water Flow Status 1 0x045F 1 51 r Condenser Water Rate Sensor 1 0x083D 1 52 r Condenser Water Temperature - Delta 2 0x0488 2 54 r Condenser Water Temperature - Entering 2 0x0436 3
♣ Additional information may be obtained from McQuay International. Request the following document. MicroTech® Series 200 Centrifugal Chiller Data Communications Packet for Open Protocol™ Cent2_22.doc 5 See Appendix A.1.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

56 r Condenser Water Temperature - Leaving 2 0x0434 3 58 r Cooling Tower Control 1 0x0926 1 59 r Cooling Tower Stage 1 0x049A 1 60 r Cooling Tower Valve Position 1 0x049B 1 61 r Discharge Refrigerant Temperature 2 0x043E 3 63 r Evaporator Approach Temperature 2 0x0482 2 65 r Evaporator Pump Status 1 0x0423 1 66 r Evaporator Pump #1 Operating Hours 2 0x0854 1 68 r Evaporator Pump #2Operating Hours 2 0x0857 1 70 r Evaporator Refrigerant Pressure 2 0x0438 2 72 r Evaporator Refrigerant Temperature 2 0x0464 3 74 r Evaporator Water Flow Rate 2 0x0450 1 76 r Evaporator Water Flow Status 1 0x045E 1 77 r Evaporator Water Rate Sensor 1 0x083C 1 78 r Evaporator Water Temperature - Delta 2 0x0486 2 80 r Evaporator Water Temperature - Entering 2 0x0432 3 82 r Evaporator Water Temperature - Leaving 2 0x0430 3 84 r Fault - Current Active 1 0x1C00 1 85 r Last Start Hour 1 0x0861 1 86 r Last Start Minute 1 0x0862 1 87 r Last Start Month 1 0x0863 1 88 r Last Start Date 1 0x0864 1 89 r Last Start Year 1 0x0865 1 90 r Last Stop Hour 1 0x0866 1 91 r Last Stop Minute 1 0x0867 1 92 r Last Stop Month 1 0x0868 1 93 r Last Stop Date 1 0x0869 1 94 r Last Stop Year 1 0x086A 1 95 r Liquid Line Refrigerant Temperature 2 0x043C 3 97 r Oil Pressure - Feed 2 0x0446 2 99 r Oil Pressure - Net 2 0x0468 2 101 r Oil Pressure - Vent 2 0x04AC 2 103 r Oil Temperature - Feed 2 0x0442 3 105 r Oil Temperature - Sump 2 0x0444 3 107 r Outdoor Air Temperature - Network 1 0x0474 2 108 r Refrigerant Detection Sensor 1 0x083E 1 109 r Refrigerant Leak Detection Limit 1 0x044B 1 110 r Unit Status 1 0x0420 1 111 b Capacity Limit Percent 1 0x0475 1 112 b Clear Current Fault 1 0x041E 1 113 b Chiller Operation Mode 1 0x0477 1 114 b Chilled Water Temperature Setpoint 1 0x0476 4
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

115 b Communications Signal 1 0x047D 1 116 b Outdoor Air Temperature - BAS 1 0x0473 5 117 b Master/Server Setpoint 1 0x093C 1 118 b Lead/Lag Mode Setpoint 1 0x093D 1 119 b Enable Lag Setpoint 1 0x093E 1 120 b Disable Lag Setpoint 1 0x093F 1 121 b Lag Standby Setpoint 1 0x0942 1 122 b Lead/Lag Switch Setpoint (Day) 1 0x0948 1 123 b Lead/Lag Switch Setpoint (Hour) 1 0x0949 1 124 r Lead/Lag Status 1 0x0401 1 125 r Lead Unit 1 0x0402 1 126 r Lead Unit Status 1 0x0403 1 127 r Lag Unit Status 1 0x0404 1 128 r Lead Motor Current 1 0x0405 1 129 r Lag Motor Current 1 0x0406 1 130 r Lead Status 1 0x0407 1 131 r Lag Status 1 0x0408 1 132 b Chiller Control mode 1 0x900 1 133 b Chilled Water Temperature Local Setpoint 1 0x901 4 134 r Chilled Water Temperature – Active Setpoint 1 0x905 4 Table 3 - Equipment Type: 050RPC Reciprocating Chiller
3 r Circuit #1 Condenser Approach Temperature 2 0x0497 2 5 r Circuit #1 Condenser Pressure 2 0x0467 2 7 r Circuit #1 Alarm Conditions: Condenser Pressure 2 0x0822 2 9 r Circuit #1 Alarm Conditions: Evaporator Pressure 2 0x0820 2 11 r Circuit #1 Alarm Conditions: Liquid Line Temp 2 0x0826 6 13 r Circuit #1 Alarm Conditions: Suction Temperature 2 0x0824 6 14 r Circuit #1 Current Alarm 1 0x0831 1 16 r Circuit #1 Evaporator Pressure 2 0x0463 2 18 r Circuit #1 Liquid Line Temperature 2 0x0479 6 19 r Circuit #1 Previous Alarm 1 0x0833 1 20 r Circuit #1 Status 1 0x0428 1 22 r Circuit #1 Subcooling Temperature 2 0x049B 2 24 r Circuit #1 Suction Temperature 2 0x0475 6 26 r Circuit #1 Superheat Temperature 2 0x0493 2 28 r Circuit #2 Condenser Approach Temperature 2 0x0499 2 6 See Appendix A.1.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

30 r Circuit #2 Condenser Pressure 2 0x0469 2 32 r Circuit #2 Alarm Conditions: Condenser Pressure 2 0x082A 2 34 r Circuit #2 Alarm Conditions: Evaporator Pressure 2 0x0828 2 36 r Circuit #2 Alarm Conditions: Liquid Line Tempe 2 0x082E 6 38 r Circuit #2 Alarm Conditions: Suction Temperature 2 0x082C 6 39 r Circuit #2 Current Alarm 1 0x0832 1 41 r Circuit #2 Evaporator Pressure 2 0x0465 2 43 r Circuit #2 Liquid Line Temperature 2 0x047B 6 44 r Circuit #2 Previous Alarm 1 0x0834 1 45 r Circuit #2 Status 1 0x0429 1 47 r Circuit #2 Subcooling Temperature 2 0x049D 2 49 r Circuit #2 Suction Temperature 2 0x0477 6 51 r Circuit #2 Superheat Temperature 2 0x0495 2 53 r Compressor #1 Operating Hours 2 0x0862 1 55 r Compressor #1 Starts 2 0x086A 1 57 r Compressor #2 Operating Hours 2 0x0864 1 59 r Compressor #2 Starts 2 0x086C 1 61 r Compressor #3 Operating Hours 2 0x0866 1 63 r Compressor #3 Starts 2 0x086E 1 65 r Compressor #4 Operating Hours 2 0x0868 1 67 r Compressor #4 Starts 2 0x0870 1 69 r Condenser Entering Water Temperature 2 0x0470 6 71 r Condenser Leaving Water Temperature 2 0x0472 6 73 r Evaporator Entering Water Temperature 2 0x046E 6 75 r Evaporator Leaving Water Temperature 2 0x0461 6 76 r Heat/Cool Switch 1 0x08B4 1 78 r OaT 2 0x047D 6 79 r Stage of Capacity 1 0x042B 1 80 r Unit % RLA 1 0x0474 1 81 r Unit Status 1 0x0427 1 82 b Clear Circuit #1 Alarm 1 0x091A 1 83 b Clear Circuit #2 Alarm 1 0x091B 1 84 b Condenser Leaving Water Temperature Setpoint 1 0x097D 1 85 b Evaporator Entering Water Temperature Setpoint 1 0x090D 4 86 b Evaporator Leaving Water Temperature Setpoint 1 0x0905 4 87 b Maximum Water Reset Setpoint 1 0x090C 4 88 b Network Command 1 0x044F 1 89 b Network Demand Limit 1 0x044D 1 90 b Network Leaving Water Temperature Reset 1 0x044E 1 91 b Reset Option Setpoint 1 0x090B 1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

1 r Alarm Contact 1 0x0217 1 2 r Approach Condenser 1 0x0418 1 3 r Calculated Leaving Evaporator Temp Setpoint 1 0x0420 7 4 r Calculated Network Amp Limit Setpoint 1 0x0423 1 5 r Compressor Discharge Temp. 1 0x0407 1 6 r Compressor Suction Temp. - Lo Resolution 1 0x0403 1 7 r Compressor Suction Temp. - Hi Resolution 1 0x041C 7 8 r Condenser Pump 1 0X021C 1 9 r Condenser Refrigerant Pressure 1 0x0411 1 10 r Condenser Refrigerant Temp. 1 0x0408 1 11 r Condenser Water Flow Switch 1 0X050F 1 12 r Cooling Tower Stage 1 1 0x0218 1 13 r Cooling Tower Stage 2 1 0x0219 1 14 r Current Fault 1 0x0428 1 15 r Fault Last 1 0x0834 1 16 r Fault 2 1 0x0835 1 17 r Fault 3 1 0x0836 1 18 r Fault 4 1 0x0837 1 19 r Fault 5 1 0x0838 1 20 r Fault 6 1 0x0839 1 21 r Fault 7 1 0x083A 1 22 r Fault 8 1 0x083B 1 23 r Entering Condenser Water Temp. - Lo Resolution 1 0x0405 1 24 r Entering Condenser Water Temp. - Hi Resolution 1 0x041E 8 25 r Entering Evaporator Water Temp. - Lo Resolution 1 0x0401 1 26 r Entering Evaporator Water Temp. - Hi Resolution 1 0x041A 1 27 r Entering Water Reset 1 0x0438 1 28 r Evaporator Low Pressure Switch 1 0x050E 1 29 r Evaporator Pump 1 0X021B 1 30 r Evaporator Refrigerant Pressure 1 0x0410 1 31 r Evaporator Refrigerant Temp. - Lo Resolution 1 0x0402 1 32 r Evaporator Refrigerant Temp. - Hi Resolution 1 0x041B 7 33 r Evaporator Water Flow Switch 1 0X050F 1 34 r High Discharge Pressure Switch 1 0X050E 1 35 r Hot Gas Solenoid 1 0x0212 1 36 r Leaving Condenser Water Temp. - Lo Resolution 1 0x0406 1 37 r Leaving Condenser Water Temp. - Hi Resolution 1 0x041F 8 38 r Leaving Evaporator Water Temp. - Lo Resolution 1 0x0400 1
7 See Appendix A.1.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

39 r Leaving Evaporator Water Temp. - Hi Resolution 1 0x0419 7 40 r LED Front Panel 1 0x021F 1 41 r Lift Pressure 1 0x0412 1 42 r Liquid Injection Solenoid 1 0x0216 1 43 r Liquid Line Refrigerant Temp. - Lo Resolution 1 0x0404 1 44 r Liquid Line Refrigerant Temp. - Hi Resolution 1 0x041D 8 45 r Liquid Subcool 1 0x0417 1 46 r Load Solenoid 1 0x0211 1 47 r Low Evaporator Pressure Limit 1 0x043B 1 48 r Manual Amp Limit 1 0X043D 1 49 r Manual Amp Limit Setpoint 1 0x0901 1 50 r Maximum Amp Limit 1 0X043C 1 51 r Motor Control Latch Relay 1 0x0213 1 52 r Motor Control Relay 1 0x021E 1 54 r Motor Current Amps 2 0x0435 1 55 r Motor Current Percent 1 0x040C 1 56 r Motor Temperature Switch 1 0x050E 1 58 r Number of Starts 2 0X0432 1 59 r Oil Delta Pressure 1 0X040D 1 60 r Oil Feed Temp. 1 0x0409 1 61 r Oil Gage Pressure 1 0x0415 1 62 r Oil Heater 1 0x0215 1 63 r Oil Pressure Differential Switch 1 0X050E 1 64 r Oil Pump 1 0X021D 1 65 r Oil Sump Temp. 1 0X040A 1 67 r Operating Hours 2 0x0430 1 68 r Panel Rocker Switch 1 0X050E 1 69 r Remote Amp Limit 1 0X043E 1 70 r Remote Chilled Water Reset 1 0x0439 1 71 r Remote Reset or Amp Limit Signal 1 0X040B 1 72 r Remote Start/Stop Switch 1 0X050F 1 73 r Soft Load Limit 1 0X043A 1 74 r Starter Fault Switch 1 0X050F 1 75 r Starter Transition Switch 1 0X050F 1 76 r Superheat 1 0x0416 1 77 r Surge Guard Switch 1 0X050E 1 78 r Unit Status 1 0x0424 1 79 r Unload Solenoid 1 0x0210 1 80 r Vanes Closed Switch 1 0X050F 1 81 r Watchdog Output 1 0x0214 1 82 b Clear Current Fault 1 0X042A 1 83 b Comm Port Baud Rate 1 0x0801 1 84 b Correct Checksum 1 0x0800 1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com


85 b Leaving Evaporator Temperature Setpoint 1 0x0900 7 86 b Maximum Chilled Water Reset Setpoint 1 0x0820 9 87 b Network Amp Reset 1 0x0450 1 88 b Network Chilled Water Reset 1 0X044F 1 89 b Network Start Stop 1 0x0451 1 90 b Reset Option 1 0x0822 1 91 b Soft Reset 1 0x0204 1 92 b Start Mode 1 0x0824 1 93 b Startup Differential Temp. 1 0x0826 9 94 b Shutdown Differential Temp. 1 0x0827 9 Table 5 - Equipment Type : 001ASC Reciprocating Chiller
1 r Active Chilled Water Temperature Setpoint 1 0x045A 4 2 r Ckt#1 Condenser Pressure 2 0x0467 2 4 r Ckt#1 Alarm Conditions: Capacity 1 0x1F13 1 5 r Ckt#1 Alarm Conditions: Condenser Pressure 2 0x1F09 2 7 r Ckt#1 Alarm Conditions: Evap Leaving Water Temp 2 0x1F0F 1 9 r Ckt#1 Alarm Conditions: Evap Pressure 2 0x1F07 2 11 r Ckt#1 Alarm Conditions: Fan Stage 1 0x1F14 1 12 r Ckt#1 Alarm Conditions: Liquid Line Temperature 2 0x1F0D 10 14 r Ckt#1 Alarm Conditions: Outside Air Temp 2 0x1F11 10 16 r Ckt#1 Alarm Conditions: Suction Temperature 2 0x1F0B 10 18 r Ckt#1 Current Alarm 1 0x08B9 1 19 r Ckt#1 Current Alarm HourMinuteMonthDateYear 1 0x1F02 1 20 r Ckt#1 Evaporator Pressure 2 0x0463 2 22 r Ckt#1 Liquid Line Temperature 2 0x0479 10 24 r Ckt#1 Status 1 0x0428 1 25 r Ckt#1 Subcooling Temperature 2 0x04DF 2 27 r Ckt#1 Suction Temperature 2 0x0475 10 29 r Ckt#1 Superheat Temperature 2 0x04D7 2 31 r Compressor #1 Operating Hours 2 0x0862 1 33 r Compressor #1 Starts 2 0x086A 1 35 r Evaporator Entering Water Temperature 2 0x046E 10 37 r Evaporator Leaving Water Temperature 2 0x0461 10 39 r Outdoor Air Temperature 2 0x047D 10 41 r Stage of Cooling 1 0x042B 1 42 r Unit Status 1 0x0427 1
8 See Appendix A.1.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com


43 b Clear Ckt#1 Alarm 1 0x091A 1 44 b Evaporator Entering Water Temperature Setpoint 1 0x090D 2 45 b Evaporator Leaving Water Temperature Setpoint 1 0x0905 2 46 b Maximum Chilled Water Reset Setpoint 1 0x090C 2 47 b Network Command 1 0x044F 1 48 b Network Demand Limit 1 0x044D 1 49 b Network Evaporator Leaving Water Temp Reset 1 0x044E 1 50 b Reset Option Setpoint 1 0x090B 1
1 r Air Velocity 1 0x0434 1 2 r Airflow Status 1 0x045C 1 3 r Current Alarm 1 0x0801 1 4 r Previous Alarm 1 0x1301 1 5 r Building Static Pressure 1 0x0435 1 6 r Compressor #1 Alarm 1 0x081C 1 7 r Compressor #1 Operating Hours 2 0x08AF 1 9 r Compressor #2 Alarm 1 0x081D 1 10 r Compressor #2 Operating Hours 2 0x08B2 1 12 r Compressor #3 Alarm 1 0x081E 1 13 r Compressor #3 Operating Hours 2 0x08B5 1 15 r Compressor #4 Alarm 1 0x081F 1 16 r Compressor #4 Operating Hours 2 0x08B8 1 18 r Compressor #5 Alarm 1 0x0820 1 19 r Compressor #5 Operating Hours 2 0x08BB 1 21 r Compressor #6 Alarm 1 0x0821 1 22 r Compressor #6 Operating Hours 2 0x08BE 1 24 r Control Temperature 1 0x0432 1 25 r Cool Stage 1 0x043F 1 26 r Cooling Control Status 1 0x044A 1 27 r Dew Point Temperature 1 0x042F 1 28 r Duct Static Pressure #1 1 0x0435 1 29 r Duct Static Pressure #2 1 0x0434 1 30 r Economizer Enable 1 0x045A 1 31 r Economizer Operating Hours 2 0x08C4 1 33 r Economizer Position 1 0x042E 1 34 r Entering Water Temperature 1 0x042C 1
9 See Appendix A.1.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

35 r Fan - High Speed Operating Hours 2 0x08AC 1 37 r Fan - Low Speed Operating Hours 2 0x08A9 1 39 r Fan Operation 1 0x0462 1 40 r Fan Speed 1 0x0436 1 41 r Heat Stage 1 0x043E 1 42 r Heating Control Status 1 0x044C 1 43 r Heating Operating Hours 2 0x08C1 1 45 r Leaving Water Temperature 1 0x042D 1 46 r Mixed Air Temperature 1 0x042B 1 47 r Motor Amps 1 0x0436 1 48 r Motor Speed 1 0x04BB 1 49 r Network Communications Status 1 0x0470 1 50 r Outdoor Air Damper Status 1 0x045F 1 51 r Outdoor Air Temperature 1 0x0429 1 52 r Override Hours 2 0x08C7 1 54 r Refrigerant Pressure 1 0x0431 1 55 r Relative Humidity 1 0x0431 1 56 r Return Air Temperature 1 0x0428 1 57 r Space Temperature 1 0x042A 1 58 r Supply Air Temperature 1 0x0427 1 59 r Supply Fan Status 1 0x045E 1 60 r Unit Enabled Status 1 0x0488 1 61 r Unit Status 1 0x043D 1 62 r Variable Inlet Vane Position 1 0x0436 1 63 r Water Flow Required 1 0x0445 1 64 r Water Flow 1 0x045B 1 65 r Water Pump Start/Stop 1 0x0461 1 66 b Building Static Pressure Setpoint 1 0x0923 1 67 b Clear Alarm 1 0x04CE 1 68 b Clear Alarm Buffer 1 0x048A 1 69 b Control Mode 1 0x044F 1 70 b Control Temperature Source 1 0x0926 1 71 b Cooling Control Deadband 1 0x088D 1 72 b Cooling Control Setpoint 1 0x0907 1 73 b Cooling Supply Deadband 1 0x0878 1 74 b Cooling Supply Setpoint 1 0x090E 1 75 b Dew Point Deadband 1 0x094E 1 76 b Dew Point Sensor Type 1 0x0949 1 77 b Dew Point Setpoint 1 0x094D 1 78 b Duct Static Pressure Setpoint 1 0x0917 1 79 b Duct Static/Building Static Pressure Deadband 1 0x089B 1 80 b Economizer (Air) Changeover Differential 1 0x0932 1 81 b Economizer (Air) Changeover Temperature Setpoint 1 0x0931 1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

82 b Economizer (Air) Method 1 0x083B 1 83 b Economizer (Water) Changeover Temperature Offset 1 0x091A 1 84 b Fan On Heating Setpoint 1 0x0939 1 85 b Head Pressure Deadband 1 0x08E1 1 86 b Head Pressure Setpoint 1 0x093A 1 87 b Heating Control Deadband 1 0x0894 1 88 b Heating Control Setpoint 1 0x0905 1 89 b Heating Supply Deadband 1 0x0871 1 90 b Heating Supply Setpoint 1 0x0914 1 91 b Humidity Control Type 1 0x0947 1 92 b Humidity Deadband 1 0x094C 1 93 b Humidity Setpoint 1 0x094B 1 94 b Low Entering H20 Comp. Lockout Differential 1 0x092C 1 95 b Low Entering Water Compressor Lockout Setpoint 1 0x092B 1 96 b Min Vane Position/Fan Speed 1 0x0951 1 97 b Minimum Outdoor Air Damper Position 1 0x0934 1 98 b Minimum Supply Air Temperature Control 1 0x0919 1 99 b Unoccupied Cooling Space Differential 1 0x0904 1 100 b Unoccupied Cooling Space Setpoint 1 0x0903 1 101 b Unoccupied Heating Space Differential 1 0x0902 1 102 b Unoccupied Heating Space Setpoint 1 0x0901 1 103 b Water Flow Signal 1 0x0444 1
Appendix A.3. McQuay Equipment Types recognized by the driver.

Code Description 200CFC 200 Series Centrifugal Chiller 100CFC 100 Series Centrifugal Chiller 001ASC Air Screw Chiller 000SCU Self Contained Unit 0050RPC Reciprocating Chiller
Appendix A.4. Direct Addressing
Direct addressing allows data to be read from the McQuay device when the field name is unknown. McQuay specifies the addresses in hexadecimal notation but they must be specified in the CSV file in decimal format. For example, to read McQuay address 0x0400, the address in the CSV file must be entered as 1024. If reading multiple addressing at once (i.e. if the length is greater than 1) it may be necessary to adjust the timeout for the Map Descriptor. It is possible to read multiple addresses using one Map Descriptor; however, it is only possible to write to a single address. The following Map Descriptor parameters will need to be defined in addition to those described in section 4.4.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

5.3.6. Driver Related Map Descriptor Parameters
Normally this field is set to 1 or omitted.
Address* The address in the McQuay device that contains the data of interest.
This parameter is used with direct addressing. When reading, up to 4 consecutive address locations in the McQuay device can be combined and stored in a single Data Array element. When writing, one value from the Data Array may be sent to up to 4 consecutive address locations in the McQuay device.
Refer to examples on the following pages.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Bytes_Per_Field* · 1,2,3,4


Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Node_Name ,Address ,Length ,Bytes_per_Field ,Scan_Interval ,Function
Chiller1_emulation ,DA_CHILLER1 ,0 ,Chiller1 ,4096 ,1 ,4 ,1.0s ,Rdbc
This example reads 10 data elements from a McQuay device starting at address 4096 (= 0x1000). The 10 values obtained are stored in
This example reads a McQuay device starting at address 4096 (= 0x1000) to 4099 incl. Before storing the data from the responses, the
When the 4th address has bee read, the driver calculates Total_Value = v0 + v1 * 0x100 + v2 * 0x10000 + v3 * 0x1000000. The Total_Value is

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Appendix A.6. Advanced Map Descriptor Example 2 – Controlling Bytes per Field – Reading
FieldServer combines the 4 values into a single value and stores this single value in a single Data Array element.
Appendix A.5. Advanced Map Descriptor Example 1– Reading direct address.
The driver reads address 4096 and gets a value. Call this value v0.
The driver reads address 4097 and gets a value. Call this value v1.
The driver reads address 4098 and gets a value. Call this value v2.
The driver reads address 4099 and gets a value. Call this value v3.
DA_CHILLER1 starting at offset zero.
stored in the Data Array.

Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Node_Name ,Address ,Length ,Bytes_Per_Field ,Scan_Interval ,Function
Chiller1_emulation ,DA_CHILLER1 ,0 ,Chiller1 ,4096 ,1 ,2 ,1.0s ,Wrbc
This example writes to a McQuay device starting at address 4096 (= 0x1000) to 4097incl. The value written to each address location is based on
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Appendix A.7. Advanced Map Descriptor Example 3 – Controlling Bytes per Field – Writing
A value from 1 to 4 -tells the
extracted from offset 0 in the
written to each address is
based on the single value
write to The data value
address in decimal Length must be
The value v1 = (value_extracted_from_DA shift right by 8) AND 0xff
set to 1 when
specified.
a single value extracted from the FieldServer’s Data Arrays.
The value v0 = (value_extracted_from_DA) AND 0xff
The driver writes value v0 to address 4096.
The driver writes value v1 to address 4097.

Appendix A.8. Statistics
The driver reports statistics according to the FieldServer standards. The following notes describe some aspects of standard statistic reporting which are peculiar to this driver.
NAK Each time a negative acknowledgement message is received. CHECKSUM Each time that a message is received that contains a non-ASCII character. NOISE An acknowledgement message contains an unrecognized code. NO START Each time a message is received that doesn’t begin with a space. PROTOCOL All other errors are reported as protocol errors In addition to the standard FieldServer communication statistics described above and in the FieldServer User’s Manual, this driver can also expose some driver statistics by writing data to a Data Array. A special Map Descriptor is required. The driver recognizes the Map Descriptor by its name which must be "McQuay-stats”.
The driver stores the following data. The location in the Data Array is obtained by multiplying the port number by 50 and then using the location offset indicated in the table below.
Location Statistic 0 MCQ_STAT_PASSWORD 10 MCQ_STAT_NAK 11 MCQ_STAT_NOISE 12 MCQ_STAT_NOISE_CODE 13 MCQ_STAT_NON_ASCII_CHARS 14 MCQ_STAT_BAD_START_BYTE 15 MCQ_STAT_OTHER_CMPLT_ERR 16 MCQ_STAT_CLIENT_BYTES_RCVD 17 MCQ_STAT_CLIENT_FRAGS_RCVD 18 MCQ_STAT_CLIENT_MSGSS_RCVD 19 MCQ_STAT_CLIENT_BYTES_SENT 20 MCQ_STAT_CLIENT_FRAGS_SENT 21 MCQ_STAT_CLIENT_MSGSS_SENT 22 MCQ_STAT_SERVER_BYTES_SENT 23 MCQ_STAT_SERVER_MSGSS_SENT 24 MCQ_STAT_SERVER_NAKS_SENT The following example shows how this special Map Descriptor can be configured. You can copy this section of text directly into your CSV file.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

When the driver sees this Map Descriptor it uses the Data Array DA_MCQ_STATS (in this example) to store driver specific statistics. Only one of
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

these Map Descriptors may be specified per FieldServer.

Appendix B. Error Messages
Those messages marked with an * are only printed once even if they occur repeatedly.
The length of the Map Descriptor used to expose driver statistics is too short. Set the length to at least 1000. You can ignore this message – the driver will abandon excess statistics. McQuay:#2 FYI. You could have used a MapDesc called to expose diagnostic info.
McQuay:#1 FYI. The MapDesc called is too short
You can safely ignore this message. It is a prompt. Refer to Appendix A.8.
This is a reminder that a password is expected when a node is defined. Refer to sections 4.3 or 5.2. Even though password checking is not enforced when the driver is configured as a Server, the driver expects one to be defined for every node. McQuay:#4 Err. Node list if full. Max=%d
McQuay:#3 FYI. Normally passwords are defined for each node.
A maximum of 100 McQuay device nodes can be configured per FieldServer. If the limit is reached, call support.
A node has been provided with two passwords. This is either a configuration error or two nodes with the same address are connected to different ports. The driver can only store one password per node address and cannot use the port number to differentiate them. Re-program the McQuay devices to have the same passwords if they have the same addresses.
McQuay:#5 Err. Node=%d has more than one password.
Device Scaling is being applied and the driver doesn’t know how to scale a variable. Please submit your configuration file with your request for support.
*McQuay:#9 FYI. Device scaling method unknown.
The driver doesn’t recognize the equipment type specified using the PLC_Type parameter in the configuration file. Refer to Appendix A.3 for a list of valid equipment types.10 McQuay:#11 Err. Node=%s. Equip. Type not specified. Refer to Sections 4.3, 5.2. and Appendix A.310
McQuay:#10 Err. Node=%s. Equip. type not recognized.
McQuay:#13 Err. MapDesc=%s. Field Name unknown.
Refer to Appendix A.2 for a list of valid field names. Refer also to Sections 4.4 or 5.3.
McQuay:#14 Err. MapDesc=%s. Max Len=1 for Writes with direct addr.
Corrective action is required. When writing to a McQuay device using direct addressing the length may only be 110
McQuay:#15 Err. MapDesc=%s. Field Name/Address Required.
Neither a field name nor an address was specified. The driver does not know what location to read. Specify a field name from Appendix A.2.10 McQuay:#16 Err. MapDesc=%s. No Node.
Each Map Descriptor must be connected to a node. This is done by specifying a node name. 10 McQuay:#17 Err. MapDesc=%s. Md too short.
The offset added to the length of the Map Descriptor extends beyond the Data Array. Increase the Data Array length. 10 McQuay:#18 Err. MapDesc=%s. Cannot write 'Everything'.
When using ‘everything’ as a field name the Map Descriptor function must be Rdbc or Rdb as this is a read only function.10
McQuay:#19 do diagnostic 3 McQuay:#20 do diagnostic 1 McQuay:#21 do diagnostic 2
Call FieldServer Technical Support. A developer diagnostic has been called and should not have been.
10 Correct the configuration by editing the CSV file and downloading it to the FieldServer, then reset the FieldServer for the changes to take effect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com
Error Message Action

Error Message Action McQuay:#22 Err. Illegal Node_ID [%d] - Set to 1 Check configuration file, a Node_ID is out of range. 11
If the Node_ID is greater than 255 then this message is printed. In versions of the driver prior to 1.02 this was permitted and these configurations will operate correctly. In versions since 1.02a the route parameter is used to provide the routing device’s address. Convert the Node_ID as follows. Divide the old Node_ID by 256. Set the Node_ID equal to remainder and set the route equal to the quotient. Example; Old Node_ID = 834. 834 div 256 = 3 remainder 66. Therefore Route=3 and Node_ID=66.
McQuay:#23 FYI. Config requires non-critical update. Read Manual.
If the Node_ID is > 255 and the Route is specified too then this error is printed. The Node_ID should be a number in the range 0 to 255.Error! Bookmark not defined. McQuay:#25 Err. Max Len=1 when Bytes_Per_Field > 1. MD=%s.
McQuay:#24 Err. Illegal Node_ID/Route
The length parameter must be set to 1 when a Map Descriptor has the Bytes_Per_Field parameter specified10
McQuay:#26 Err. Max Bytes_Per_Field=4. MD=%s.
Legal values for the Bytes_Per_Field parameter are whole numbers in the range 1 to 4 inclusive. 10
This message is printed if a NAK response is received in the first few polls to a node. The driver guesses that the reason is that the Node_ID/route or password has been incorrectly specified in the configuration file. Verify these settings. The message is printed once and suppressed for subsequent occurrences. Refer to Appendix C.2
McQuay:#27* Err. Response=NAK. Read Manual. Maybe password or Node_ID
The message is printed and then suppressed for subsequent occurrences, but the NAK stat is incremented for each occurrence. The driver is reporting that the McQuay device responded with a NAK under different circumstances from msg#27 which is printed if the NAK is received during the first few polls. The message indicates that the McQuay device could not respond. If the NAK's are occasional, assume that noise has corrupted an occasional message. If they occur frequently assume a systematic or connection error. Refer to Error! Reference source not found. and Appendix C.2.
McQuay:#28* Err. Device responded with a NAK.
11 Correct the configuration by editing the CSV file and downloading it to the FieldServer, then reset the FieldServer for the changes to take effect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com

Appendix C. Troubleshooting
Appendix C.1. Connection Problems
Appendix C.2. Negative Acknowledgement - NAK
Appendix C.3. Node ID problems
If the Node is incorrectly specified, the FieldServer will not get a response from the McQuay unit. The ID used to communicate with the McQuay unit needs to be determined. This may not be the same as shown on the Rotary switches of the unit. Note that McQuay uses Hexadecimal notation for addressing, therefore, if connection to the Unit is with address 0201, this is in Hex and the Node ID for the FieldServer configuration needs to be 513.
Appendix C.4. Server Side Configuration – Consecutive Addresses
Some variables have their values stored in two consecutive address locations. When the Client polls for the value it actually sends two read messages – one for each address. When configuring the Server side, therefore, it is necessary to define two Map Descriptors for variables which require two consecutive addresses.
Map_Descriptors Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Address ,Length Supply Fan Status ,DA_AI_01 ,01 ,Passive ,Node_A ,1118 ,1 Supply Temp ,DA_AI_01 ,02 ,Passive ,Node_A ,1063 ,1 Space Temp ,DA_AI_01 ,03 ,Passive ,Node_A ,1066 ,1 Control Temp Part 1 ,DA_AI_01 ,04 ,Passive ,Node_A ,1074 ,1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com