A Sierra Monitor Company
FS-8700-78 Dart
Effective for all systems manufactured after January 18, 1999
Instruction Manual Part Number FS-8700-78
2/20/2003



The Dart Driver is designed for connection to a Data Air Coporation Dart Device. The Dart device is a active element on a network of Data Air devices such as DAP panels. It manages the devices and provides co-ordination and supervision. In performing these duties the Dart device polls all the devices on the network for all the data. The Dart is capable of ‘echoing’ the responses from these devices on one of its RS232 ports. This driver is designed to listen passively to these echoes and store device data. In addition the driver can send messages (containing set point data, for example,) directly to individual devices on the network. The FieldServer is connected to the RS232 serial port of the Dart. The Fieldserver can read and write but active polling must be minimized as in reduces the amount of time that the DART spends controlling the networked devices. The driver operates primarily as a passive client listening to echoes of the data being polled by the DART. The DART must be set to ‘Echo’ mode on the front panel of the Dart for the driver to operate correctly. There is no alternative to this essential but manual setup-step. The driver may be configured very simply (See example 1 in section 4 of the manual). In addition a number of advanced configurations are possible. The manual is divided to separate the basic and advanced topics. The driver supports the common message formats for common Data Aire devices. A list of the supported messages is provided in the manual. The driver cannot be used to configure or read the status of a DART device itself. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.
Several factors outside FieldServer’s control make for slow communications with Data Aire devices. The Data Aire communications is based on a very low baud rate. In addition inter- message timing constraints and overhead requirements for active messages in a Dart configuration add significant time to each transaction. When a used with a DART device, writing to a set point (or other variable) may take up to 8 seconds to complete the transaction. The results of the write will not be seen until the DART has timed-out back into control mode and echoes the new data to the Fieldserver. This could take several minutes if there are many devices on the loop and will take at least 30 seconds. When writing continuously, with DART configurations, the minimum time interval between successive writes is 2 minutes and with non-DART configurations is 1.8 seconds.

2.1 Supplied by Sierra Monitor for this driver
RS485 connection adapter Driver Manual.
Data Aire Dart and documentation RS232 cable for the loop network

Hardware

When a DART device is connected to the Data Aire field devices then the Fieldserver is connected to the serial port of the DART. The DART must be set to ‘Echo’ mode. This is done on the front panel of the DART.

For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette). The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Dart Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. The Dart Serial Driver cannot be configured as a data server. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provide data format. Each data array can only take on one format.
FLOAT, BIT, UInt16, SInt16, Packed_Bit, Byte, Packed_Byte, Swapped_Byte Data_Array_Length Number of Data Objects. Must be larger than the data storage area required for the data being placed in this array.
// Data Arrays // Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length DA_AI_01, UInt16, 200 DA_AO_01, UInt16, 200 DA_DI_01, Bit, 200 DA_DO_01, Bit, 200
Section Title Data_Arrays · 1-10,000

Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer This is the port connected to the DART’s RS232 port.
P1-P8, R1-R2 (P1-P8) requires 232/485 converter.
Secondary_Port* Using a Dart ? Do not specify this parameter.
P1-P8, R1-R2 (R1-R2) requires 232/485 converter. Baud* Specify baud rate 2400 (Others available but Daire only operates at 2400 baud.) Parity* Specify parity None Data_Bits* Specify data bits 8 Stop_Bits* Specify stop bits 1 Protocol Specify protocol used Either keyword may be used.
Handshaking* Specify hardware handshaking None Poll Delay* Time between internal polls 0-32000 seconds default 1 second

// Client Side Connections Connections Port, Parity, Data_Bits, Stop_Bits, Protocol, Poll_Delay P1, 2400 , None, 8, 1, Dart , 0.100s
Section Title Connections · Dart

Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Node_ID This is not the node address of the Dart device ! Specify the node address of the DAP device whose data you wish to monitor.
Protocol Specify protocol used Dart Port Specify which port the Dart is connected to the FieldServer
Example
// Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Port Unit1, 1, Dart , P1
Section Title Nodes

4.4.1 FieldServer Specific Map Descriptor Parameters

Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer
One of the Data Array names from “Data Array” section above Data_Array_Location Starting location in Data Array 0 to maximum specified in “Data Array” section above Function Function of Client Map Descriptor The use of the WRBX keyword is recommended for DART configurations as communications are minimized.
Column Title Function Legal Values Scan_Interval Rate at which data is polled >0.1s
Column Title Function Legal Values Node_Name Name of Node to fetch data from
One of the node names specified in “Client Node Descriptor” above Length Length of Map Descriptor 1 The length must always be set to one. Address Starting address of read block Not required for client configuration. This parameters is used in simulation configuration only. The following parameters apply only to the Dart Driver. DA_Func* Tell the driver to poll the device for all the data that is available. The data is device specific. Other uses of this parameter are permitted. These uses are discussed in the Advanced Topics section of this manual.
Everything See table 4.4.3.1 for a map of how the data is stored in the Fieldserver data arrays

DA_Field Only required when the function is a write (wrbc) or when the map descriptor is associated with a write by means of the DA_Assoc parameter value. This is the name of the data field whose value you wish to set in the device. Other uses of this parameter are permitted. These uses are discussed in the Advanced Topics section of this manual.
See Table 4.4.3.3 for a list of permitted values.
DA_Assoc Use to associate passive map descriptors with an active map descriptor. Using this parameter you associate multiple fields with one wrbc map descriptor, thus reducing writing multiple values to one device using just one message.
Any positive integer.


Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Func Read_Node_01, DA_01 , 0 , passive , Unit1 , 0 , 1300 , Everything
The driver waits passively for the Dart to echo data from the devices.
No Scan Interval. The driver will process data as fast as the Dart can serve it.

4.4.5 Map of How Data Aire Device Data is stored in a Data Array
In the example of 4.4.1 the Fieldserver listens passively for all possible data from the device called ‘unit1’ and stores the data in an array called ‘DA_01’. The data that is obtained from ‘unit1’ is dependent on the type of device. Irrespective of the device type the arrangement of data, stored in DA_01, is fixed. If a data field cannot be obtained from ‘unit1’ then the array is left with a zero value for that data field. Table 4.4.5.1: Array Locations of ‘Everything’ In the following table the array location indicates the offset in the data array at which a data field can be found. (This offset is relative to the offset specified in the map descriptor.) The columns headed 2,3 … indicate the unit types for which the data fields are available. For example: The field ‘d_temp’ can be read from unit types 2,5,6,7,9 but not from any of the other unit types. It is beyond the scope of this manual to describe each field and to indicate valid ranges. Such information should be obtained from the Data Aire Corporation. ‘x’ Indicates Read only ‘X’ Indicates a point that can be read & written. ‘w’ Indicates a write only point.
Num Elements Data Field 2 3 4 5 6 7 8 9 14 15 Message Type 1 1 1 Zone w Dap-Config 2 1 1 Inhibit w Dap-Config 3 4 1 unitType x Dap-Unit 4 2 1 temp x Dap-Stat 5 2 1 hum x Dap-Stat 6 2 1 d_temp x Dap-Stat 7 3 8 mode x Dap-Stat 23 3 8 hold x Dap-Stat 39 1 1 cs_on x Dap-Stat 40 1 1 hs_on x Dap-Stat 41 1 1 valvePCT x Dap-Stat 42 1 1 hVlvPCT x Dap-Stat 43 4 14 errors x Dap-Stat 57 2 1 hiTemp x Dap-Stat 58 2 1 loTemp x Dap-Stat 59 2 1 hiHum x Dap-Stat 60 2 1 loHum x Dap-Stat 61 1 1 chilled_water x Dap-Stat 62 1 1 compressor_config x Dap-Stat
Array Location Method

487 1 1 chilled_water X X X Dap-Menu 488 1 1 compressor_config X X X Dap-Menu 489 1 1 c_mode X X X Dap-Menu 490 2 1 fire_lim X X X Dap-Menu 491 1 1 heat_strip_config X X X Dap-Menu 492 1 1 hi_cal X X X Dap-Menu 493 1 1 hi_h_cal X X X Dap-Menu 494 2 1 hi_t_lim X X X Dap-Menu 495 1 1 humid_config X X X Dap-Menu 496 1 1 h_calib X X X Dap-Menu 497 1 1 lead_lag X X X Dap-Menu 498 1 1 loc_h_deadband X X X Dap-Menu 499 1 1 loc_h_setpt X X X Dap-Menu 500 2 1 loc_t_dband X X X Dap-Menu 501 2 1 loc_t_setpt X X X Dap-Menu 502 1 1 lo_cal X X X Dap-Menu 503 1 1 lo_h_lim X X X Dap-Menu 504 2 1 lo_t_lim X X X Dap-Menu 505 1 1 main_int X X X Dap-Menu 506 1 1 passwd_a X X X Dap-Menu 507 1 1 passwd_b X X X Dap-Menu 508 1 1 rst_mode X X X Dap-Menu 509 1 1 s_delay X X X Dap-Menu 510 2 1 t_calib X X X Dap-Menu 511 1 1 voice X X X Dap-Menu 512 1 1 vvrg X X X Dap-Menu 513 1 1 cat1 X X X Dap-Menu 514 1 1 cat2 X X X Dap-Menu 515 1 1 cat3 X X X Dap-Menu 516 2 1 d_calib X X X Dap-Menu 517 2 1 lo_d_lim X X X Dap-Menu 518 1 1 ptc X X X Dap-Menu 519 2 1 supplyT x x x Chiller-Stat 520 2 1 returnT x x x Chiller-Stat 521 4 1 coolOn1 x x x Chiller-Stat 522 4 2 coolOn2 x x x Chiller-Stat 523 4 2 coolOn3 x x x Chiller-Stat 524 2 1 valvePct x x x Chiller-Stat 525 4 1 pumpsOn x x x Chiller-Stat 526 4 1 condOn x x x Chiller-Stat 527 4 1 modFail x x x Chiller-Stat 528 2 1 hiSupT x x x Chiller-Stat 529 2 1 loSupT x x x Chiller-Stat 530 2 1 hiRetT x x x Chiller-Stat 531 2 1 loRetT x x x Chiller-Stat 532 1 1 csUtilPct1 x x x Chiller-Stat

533 1 1 csUtilPct2 x x x Chiller-Stat 534 1 1 csUtilPct3 x x x Chiller-Stat 535 1 1 valveUtilPct x x x Chiller-Stat 536 3 48 errors x x x Chiller-Stat 584 1 1 mode x x x Chiller-Stat 585 6 11 runtimes x x x Chiller-Xtra 596 3 80 errold x x x Chiller-Xtra 676 6 10 errage x x x Chiller-Xtra 854 4 1 adjust_rate x x x Chiller-Menu 855 4 1 auto_ack X X X Chiller-Menu 856 2 1 aux_setpt X X X Chiller-Menu 857 4 1 backup_mods X X X Chiller-Menu 858 2 1 backup_setpt X X X Chiller-Menu 859 4 1 cmota X X X Chiller-Menu 860 4 1 comp_type X X X Chiller-Menu 861 4 1 ptc X X X Chiller-Menu 862 2 1 hi_r_lim X X X Chiller-Menu 863 2 1 hi_s_lim X X X Chiller-Menu 864 4 1 LL_policy X X X Chiller-Menu 865 2 1 lo_r_lim X X X Chiller-Menu 866 2 1 lo_s_lim X X X Chiller-Menu 867 1 1 main_int X X X Chiller-Menu 868 4 1 mods_configd X X X Chiller-Menu 869 1 1 network_ID X X X Chiller-Menu 870 1 1 op_1_delay X X X Chiller-Menu 871 1 1 op_2_delay X X X Chiller-Menu 872 4 1 op_1_message X X X Chiller-Menu 873 4 1 op_2_message X X X Chiller-Menu 874 1 1 password X X X Chiller-Menu 875 4 4 relay_mask_0 X X X Chiller-Menu 879 4 4 relay_mask_1 X X X Chiller-Menu 883 4 4 relay_mask_2 X X X Chiller-Menu 887 4 1 restart_mode X X X Chiller-Menu 888 4 1 reverse_valve X X X Chiller-Menu 889 4 1 sc_alarm_on X X X Chiller-Menu 890 1 1 start_delay X X X Chiller-Menu 891 1 1 supply_dband X X X Chiller-Menu 892 2 1 supply_setpt X X X Chiller-Menu 893 4 1 temp_scale X X X Chiller-Menu 894 4 1 valve_voltage X X X Chiller-Menu 895 4 1 voice X X X Chiller-Menu 896 4 1 water_valve X X X Chiller-Menu 897 1 1 return_cal X X X Chiller-Menu 898 1 1 supply_cal X X X Chiller-Menu

899 4 1 adj_rate X Dap80-Menu 900 1 1 alrm_delay_1 X Dap80-Menu 901 1 1 alrm_delay_2 X Dap80-Menu 902 1 1 alrm_delay_3 X Dap80-Menu 903 1 1 alrm_delay_4 X Dap80-Menu 904 4 1 alrm_select_1 X Dap80-Menu 905 4 1 alrm_select_2 X Dap80-Menu 906 4 1 alrm_select_3 X Dap80-Menu 907 4 1 alrm_select_4 X Dap80-Menu 908 4 1 ant-enable X Dap80-Menu 909 4 1 autoflush_time X Dap80-Menu 910 4 1 auto_ack X Dap80-Menu 911 4 1 comp_config X Dap80-Menu 912 4 1 control_type X Dap80-Menu 913 4 1 c_mode X Dap80-Menu 914 4 1 da_volts X Dap80-Menu 915 4 1 dehum_on X Dap80-Menu 916 2 1 d_calib X Dap80-Menu 917 4 1 esaver_supp_comp X Dap80-Menu 918 2 1 fire_lim X Dap80-Menu 919 4 1 heater_config X Dap80-Menu 920 1 1 hi_h_lim X Dap80-Menu 921 2 1 hi_t_lim X Dap80-Menu 922 4 1 humid_config X Dap80-Menu 923 2 1 h_calib X Dap80-Menu 924 1 1 h_dband X Dap80-Menu 925 4 1 lead_lag X Dap80-Menu 926 2 1 lo_d_lim X Dap80-Menu 927 1 1 lo_h_lim X Dap80-Menu 928 2 1 lo_t_lim X Dap80-Menu 929 2 1 main_int X Dap80-Menu 930 1 1 network_id X Dap80-Menu 931 2 1 nom_h_setpt X Dap80-Menu 932 1 1 password X Dap80-Menu 933 4 1 ptc X Dap80-Menu 934 3 16 relay_1_mask_0 X Dap80-Menu 950 3 16 relay_1_mask_1 X Dap80-Menu 966 3 16 relay_1_mask_2 X Dap80-Menu 982 3 16 relay_2_mask_0 X Dap80-Menu 998 3 16 relay_2_mask_1 X Dap80-Menu 1014 3 16 relay_2_mask_2 X Dap80-Menu 1030 3 16 relay_3_mask_0 X Dap80-Menu 1046 3 16 relay_3_mask_1 X Dap80-Menu 1062 3 16 relay_3_mask_2 X Dap80-Menu 1078 4 1 reverse_valve X Dap80-Menu 1079 4 1 rst_mode X Dap80-Menu 1080 4 1 sc_alarms X Dap80-Menu

1081 1 1 s_delay X Dap80-Menu 1082 2 1 t_calib X Dap80-Menu 1083 1 1 t_dband X Dap80-Menu 1084 2 1 t_setpt X Dap80-Menu 1085 4 1 valve_config X Dap80-Menu 1086 4 1 voice X Dap80-Menu 1100 1 1 sensor_1_name x x Dap80-Analog 1101 1 1 sensor_1_units x x Dap80-Analog 1102 1 1 sensor_1_type x x Dap80-Analog 1103 1 1 sensor_1_min_val x x Dap80-Analog 1104 1 1 sensor_1_max_val x x Dap80-Analog 1105 1 1 sensor_1_cal x x Dap80-Analog 1106 1 1 sensor_2_name x x Dap80-Analog 1107 1 1 sensor_2_units x x Dap80-Analog 1108 1 1 sensor_2_type x x Dap80-Analog 1109 1 1 sensor_2_min_val x x Dap80-Analog 1110 1 1 sensor_2_max_val x x Dap80-Analog 1111 1 1 sensor_2_cal x x Dap80-Analog 1112 1 1 sensor_1_input x x Dap80-Channels 1113 1 1 sensor_2_input x x Dap80-Channels 1114 1 1 sensor_3_input x x Dap80-Channels
When the driver reads everything from a device it must first obtain the device’s unit type so that it can determine what other data is available. Once the unit type is obtained then the driver updates the ‘Unit-Type’ field visible on the node screen of the RUIDebug program. The unit type is also available in the data array defined in table 4.4.5.1. The following table lists the unit type that can be processed by this driver.
Unit Type Numeric Unit Type Description
"1" 1 044 data logger
"2" 2 046 expanded DAP
"3" 3 046 2 mod chiller
"4' 4 046 3 mod chiller
"5" 5 048 DAP, 80-character display
"6" 6 049 DAP, 16-character display
"-" 0 Unknown/unavailable/un-initialized

"7" 7 080 DAP II, no relay expansion
"8" 8 080 Chiller II
"9" 9 080 DAP II, with relay expansion
"10" 10 Not Defined
"11" 11 Not Defined
"12" 12 Not Defined
"13" 13 Not Defined
"E" 14 080 DAP II, with analog module
"F" 15 080 DAP II, with relay and analog

4.4.7 Map Descriptor: Example 2 – Writing a Set-Point .
A Data Aire device cannot be written to until it has been read. This is a limitation of the Data Aire protocol. This means that you configuration cannot consist only of wrbc map descriptors. It should consist of a at least a map descriptor like example 1for every unit that you wish to write to. Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Field , Scan_Interval Write_SP_01 , DA_SETPOINTS , 0 , wrbc , unit1 , 0 , 1 , nom_h_setpt, 120.0s
The setpoint is obtained from this data array.
Always leave the address set to zero and the length as one.
Specify the data field you wish to write. Pick from table 4.5.1. Ensure that the keyword can be written to the unit type identified as unit1. Example. If unit1 is a Chiller then the above map descriptor will not function correctly as it can only be used to write to unit types 7,9,14,15.
This is how often the data will be written to the device. Slow the scan interval down. The dart will only take control of the devices when the network has been idle for at least 50 seconds. If you generate polls too often then the dart will never exercise control.
Reccomendation Use wrbx instead of wrbc. This causes the driver to generate the command message only when the setpoint changes which in turn minimizes communications. Using this method the DART’s control mode is interrupted the least.

4.4.8 Map Descriptor: Example 3 – Writing multiple points using one message.
Map_Descriptor_Name, Data_Array_Name , Data_Array_Offset, Function, node_name, Address, Length, DA_Field , DA_Assoc, Scan_Interval Write_MapDesc_1, DA_ SETPOINTS, 0 , wrbc, unit1 , 0 1 , nom_h_setpt , 2 , 120.0s Write_MapDesc_1, DA_SETPOINTS , 1 , passive, unit1 , 0 1 , t_setpt , 2
A 'Write' and a passive to the same node. This write will update two fields, the nom_h_setpt and the t_setpt. The write MapDesc. Must precede the passive. This method is only appropriate if you plan to continuosly write to the devices. If you intend to write on change using the wrbx function then use multiple map descriptors that are not associated and give each one a wrbx.
Associate the passive map descriptor to the active (wrbc) map descriptor. In this way the driver will use only one message to write to the device. The message will be built using both map descriptors. This method reduces the communication load. The association is made using the DA_Assoc parameter. Use unique positive integers. Omitting the DA_Assoc parameter when using ‘passive’ map descriptors will produce ambiguous results.

This Chapter is blank.



6.1 Additional Driver Specific Map Descriptor Parameters
What happens if you want to poll for one specific type of data more frequently than others ? What if you want more control of the location of where data is stored ? What happens if you want to do diagnostic polls … ? To be able to achieve solutions to any of these types of questions the driver offers advanced configuration by adding to and extending the map descriptors specific to the Dart Serial Driver.
Column Title Function Legal Values DA_Func* Specifies the Data Aire Command/Query function to be used. Use a function appropriate to the type of slave (DAP/Chiller/DAP80) and the type of data required.
Numeric/Text. See section 6.1.1 for a list of possible values.
DA_Field* Specifies the data field to be retrieved from the slave device. Salves are only capable of responding with a data composite consisting of many data fields. You use this parameter to specify which parameter is you wish to have extracted from the data composite. Note1.
This is a text field. See section 6.1.2 for a list of possible values as well as Table 4.4.5.1
DA_Assoc* Use to associate passive map descriptors with an active map descriptor. In some case you may have a read (rdbc) addressing the same node as a write (wrbc). Both the read and write may have associated map descriptors. This field is used to make the association. Give the rdbc & passives map descriptors associated with the rdbc the same value (any number) and give the wrbc and its passive map descriptors
Any positive integer.

another value for DA_Assoc. Da_Freq Used only for connection to DART’s. Specify in milliseconds the interval at which you want a wrbc/rdbc map descriptor to be executed. When using wrbc/rdbc’s to a dart device set the scan interval to 5.0s and set this parameter to a number greater than 180000 (3 minutes). An interval of 300000 (5 minutes is recommended).
DA_MethodΨ Specifies the extraction method. Such as Hex-ASCII to decimal number in 10's of a degree,
See section 6.3 for a list of possible values.
DA_BytcntΨ Specifies the number of bytes that are to be processed by the method specified above. For method#6 which processes an array of elements the DA_Bytcnt specifies the number of bytes that constitute each element of the array.
DA_OffsetΨ An offset into the data composite that is returned when the slave is polled. The offset is the number of bytes from the first data byte.
0 to the length of the data composite. No validation is performed.
DA_ElecntΨ Number of elements that are produces by the extraction method.
Ψ: These parameters are only required for custom data extractions not provided for with DA_Field parameter.
6.1.1 DA_Func Parameter - Permitted values.
The driver supports a limited subset of the Dart Poll & Response Functions. The selection of the sub-set is based on the identification of useful & practical functions.
>= 1 · >= 1

IN addition to the ‘Everything’ keyword indicated in chapter 4 the following specific query functions are implemented. Func. Description Driver Parameter Protocol Id. ‘1’ DART Config Query DA_Func = dart-config 49 ‘2’ Dart Psswd Query DA_Func = dart-password 50 '3' DAP Config Command DA_Func = dap-config 51 '4' DAP Log Query DA_Func = dap-log 52 '5' DAP Unit-Type Query DA_Func = dap-unit 53 '6' DAP Stat Query DA_Func = dap-stat 54 '7' DAP Xtra Query DA_Func = dap-xtra 55 '8' DAP Menu Query DA_Func = dap-menu 56 'A' Chiller Stat Query DA_Func = chiller-stat 65 'B' Chiller Xtra Query DA_Func = chiller-xtra 66 'C' Chiller Menu Query DA_Func = chiller-menu 67 ‘D” Dart Status DA_Func = dart-status 68 'E' DAP80 Menu Query DA_Func = dap80-menu 69 'G' DAP Analog Query DA_Func = dap80-analog 71 'H' DAP Channels Query DA_Func = dap80_channles 72 Each of the above queries returns a complex set of data consisting of many sub-fields. Contact Data-Aire for a complete listing of the data composite returned. The following special / diagnostic functions are also implemented. Driver Parameter Protocol Id. DA_Func = All-Listen 11 DA_Func = Ack 6 DA_Func = Dart-Transparant 2 DA_Func = Dart-Opaque 3 DA_Func = Test-Echo 16 DA_Func = Test-No-Echo 15 DA_Func = Unit-Talk 13 With the exception of the Unit-Talk command, these are nodeless commands. When using any of these special commands no other DA_* fields need be specified. The operation of these functions is as follows ; All-Listen instructs the all units in the network to switch their relays to the listen position. Those units already in the listen position will do nothing. Those in the talk position will first echo the all-listen command and then switch their relays to the listen position. A pause of 0.15 seconds is required after the transmission of this command, to allow the units time to switch their mechanical relays.
6.1.2 DA_Field Parameter - Permitted values.
Legal values depend on the value of DA_Func.

Description Data Format DA_Func
All The whole data record returned by the slave is stored in the data array byte for byte. The number of bytes written is dependent of the DA_Func. DA_Func=dart-password Bytes =231 DA_Func=dart-config Bytes =41 DA_Func=dap-config Bytes =4 DA_Func=dap-log Bytes =240 DA_Func=dap-unit Bytes =1 DA_Func=dap-stat Bytes =68 DA_Func=dap-xtra Bytes =124 DA_Func=dap-menu Bytes =103 DA_Func=chiller-stat Bytes =54 DA_Func=chiller-xtra Bytes =104 DA_Func=chiller-menu Bytes =89 DA_Func=dap80-menu Bytes =138 DA_Func=dart-status Bytes = 9 DA_Func=dap80-analog Bytes =36 DA_Func=dap80-channels Bytes=12
Special Indicates that a user defined extraction is specified in the map descriptor. When this value is specified as the DA_Field value then DA_Method,DA_Bytcnt,DA_Offset,DA_ Elecnt must also be specfied.
See Table 4.4.5.1 for all other keywords.
Bytes

The DA_Method specifies a method for interpreting a range of bytes when the DA_Field=special.
Each byte is valid when its contains only one of the following ASCII characters.
{ 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F }
Each byte being parsed is considered to be a hexadecimal digit. The most significant digit is the left most byte.
Thus the four bytes 30 31 32 33 (hex) are interpreted by regarding the ASCII value of each byte as a hexadecimal digit. Thus we interpret the 4 bytes as the hexadecimal number 0123 and the decimal value is equal to 291.
This method is the same as method one but is used for humidity's and temperatures which are transmitted as the number of tenths of a unit.
Thus in the example of method 1. The 4 bytes yield the decimal number 29.1 °F/%.
Each byte is regarded as containing a hexadecimal digit in ASCII format.
Example: incoming byte contains 41(hex). -> regard as the hexadecimal digit 'A' in ASCII format.
The method then converts the hex digit to a series of 8 bits. In this example the bits are 00001010 with the msb being the left most.
Each byte is regarded as containing a hexadecimal digit in ASCII format.
Example: incoming byte contains 41(hex). -> regard as the hexadecimal digit 'A' in ASCII format. The decimal value of the this digit is written to the data array. In this example the number 10 would be written to the data array. Method 5
There is no translation. The raw bytes are written to the data array.
Processes an array of elements using method 1 translation. The raw data being parsed is considered to consist of DA_elecnt elements each consisting of DA_bytecnt bytes. Method 1 is applied to each cluster of bytes.

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Func, DA_Field, Scan_Interval A1, DA_AI3, 0, rdbc, Node_A, 0, 1 , dap-stat, temp ,5 A2, DA_AI3, 1, passive, Node_A, 0, 1 , dap-stat, hum ,5 A3, DA_AI3, 2, passive, Node_A, 0, 1, dap-stat, d_temp ,5 A4, DA_AI3, 3, passive, Node_A, 0, 1 , dap-stat, hiTemp ,5 A5, DA_AI3, 4, passive, Node_A, 0, 1 , dap-stat, loTemp ,5 A6, DA_AI2, 0, passive, Node_A, 0, 1 , dap-stat, cs_on ,5 A7, DA_AI2, 1, passive, Node_A, 0, 1 , dap-stat, hs_on ,5
It would be sensible for DA_AI3 to be an array of FLOATs because the temps and humidity’s return real numbers with one digit after the decimal point. DA_AI2 could be any type of array other than BIT because the values returned for these
All these map descriptors address Node_a therefore only one map descriptor needs to read (rdbc) the node. The remaining map descriptors can be passive (thus optimizing communications.)
All these map descriptors read their data from the same slave.
Slave is a DAP and we are reading status information.
These parameters need to be typed in exactly as specified in this manual. They are case sensitive. The format of the data extracted depends on the parameter.
The scan time is only important for the active map descriptor.

The DAP-II Status query returns 14 bytes of errors & status information. The arrangement and meaning of these bytes is defined by the Data Aire Corporation and is also dependent on the type of DAPII module being polled. Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Func, DA_Field, Scan_Interval A1, DA_AI1, 0, rdbc, Node_A, 0, 1 , dap-stat, errors ,5 A2, DA_DI1, 1, passive, Node_A, 0, 1 , dap-stat, bitErrors ,5
The 'errors' key word returns 14 bytes, thus we DA_AI1 should be a BYTE array. Each byte will have values 0-15 to represent the value of the bits in each byte. The bitErrors extracts the same data from the DAP but presents it as a series of 14x8 bits. Thus make
Slave is a DAP and we are reading status information.
BitErrors is a synonym for errors. The data is extracted using a different data format.
Data arrangement and meaning of each error is defined by Data Aire Corp. Example: Bit 24 is a LOW TEMP WARNING for DAPII-044/8/9 units. Example: Bit 09 is a HUMIDITY SENSOR PROBLEM for a DAPII-080 unit.

6.1.6 Advanced Map Descriptor: Example 3 - Using the 'special' parameter.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Func, DA_Field, DA_Method ,DA_Bytcnt, DA_Offset, DA_Elecnt Scan_Interval A1, DA_AI3, 0, rdbc, Node_A, 0, 1 , dap-stat, special, 1 4, 10, 1, 5
It would be sensible for DA_AI3 to be an array of FLOATs because extraction method(=1) returns a floating point number.
You can use specials as rdbc and passive map descriptors.
Performs a DAP status query
From the data bytes returned by the slave, extract 4 bytes starting at byte 10 and apply method 1 to convert the bytes before writing them to the FieldServer data
Once you use the parameter 'special' you must specify the additional parameters.
See table 6.3 for descriptions on how these extraction methods work.

6.1.7 Advanced Map Descriptor: Example 4 - Using the 'DA_Assoc' parameter.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, node_name, Address, Length, DA_Func, DA_Field, DA_Assoc, Scan_Interval A1, DA_AI3, 0, rdbc, Node_A, 0, 1 , dap80-menu, All , 1 ,5 A2, DA_AI3, 1, passive, Node_A, 0, 1 , dap80-menu, alrm_delay_1, 1 ,5 A3, DA_AI3, 2, passive, Node_A, 0, 1, dap80-menu, alrm_delay_2, 1 ,5 A4, DA_AI3, 3, passive, Node_A, 0, 1 , dap80-menu, alrm_delay_3, 1 ,5 A8, DA_AI4, 0, wrbc, Node_A, 0, 1 , dap80-menu, nom_h_setpt, 2 ,5 A9, DA_AI4, 1, passive, Node_A, 0, 1 , dap80-menu, t_setpt , 2, 5
A 'Read' and some passive map descriptors to extract other data fields from the same read. (optimizes communications) Read must precede the passive's.
DA_Assoc associates the passives with the correct active map descriptor. Thus Map Descriptors A2,3,4 are associated with A1 because the value of DA_Assoc=1 for all these map descriptors. Thus Map DescriptorsA89is associated with A8 because the value of DA_Assoc=2 for both these map descriptors.
A 'Write' and a passive to the same node. This write will update two fields, the nom_h_setpt and the t_setpt. The write map desc. Must precede the passive.
Potential confusion for the FieldServer because the node and the DA_Func's are the same for all the map descriptors. Solve this problem using DA_Assoc.

6.1.8 Map Descriptor: Example 5 - Using a special / diagnostic command.
Map_Descrip tor_Name, Scan_Interval, Data_Array_Name , Data_Array_Offset, Function, node_name, Address, Length, DA_Func, A1, 1.0s, UNUSED_ARRAY, 0 , wrb , No_node, 0, 1 , All-Listen,
A data array must be associated with the map descriptor even though it will not be used. It may be any data type.
This command is sent only once. If you need to do this periodically then change this to a wrbc.
Must connect this map descriptor to a node whose node_id is zero. For example. Nodes Node_Name, Node_ID, Protocol, Port Unit1, 0, Daire, R1
This is a special / dianostic command. It causes a one byte message to be sent.


The driver as specified in this manual is based on Data Aire Poll and Response Protocol Revision 3.2 dated 4 Nov 1997. The driver is compliant with a later release of the specification Revision 3.7 - 21 JUN 00.
6.3.1 Bad Values
In the event that the driver cannot correctly decode the raw bytes it will generally write an value which indicates bad data. In most cases the indicating value is -1 or 65535 (depending on data type). When setting bits for status fields the driver will not write new data to the array if the incoming byte is invalid. Look in the error log for indication of this type of problem.
Example. Valid ASCII digits are 0..9,A..F. If a byte is being parsed and an hex digit is expected but not found then the driver considers this an errors and writes the bad value indication OR produces an error message when the bad value indication cannot be used.
When a node is absent or dies it is possible that the Dart may go idle and stop communicating with all other nodes. This problem is not related to the driver but to the Data Aire devices.
The driver reports ignored messages. These are messages sent by a DAP/DART for which the driver cannot find a map descriptor to store the message. This does not mean the driver is not working. It means that a message which contains data that the driver/you are not interested in is being discarded. The current version of the driver ignores a few messages relating to the status of the DART device. Later versions of the driver will be capable of storing these messages and the number of ignored messages will decrease.

The variables in a DAP device are not individually addressable. When a DAP device is read a data composite is returned. The driver extracts the data you require. When data is written to a DAP device it is not possible to write a value to one individual data element such as a temperature setpoint. Rather, the DAP devices requires the complete data composite (all its variables, states, settings) be written at once. This makes the setting of a setpoint a complex operation for the driver. It involves the following steps
i. Read the device, obtain a complete set of data and store (internally in the driver.). ii. Use this stored data to form the basis for a write. Modify the data with the data
the user wishes to set. iii. Write the modified data composite back to the DAP device. You can see that to complete a 'write' operation successfully, we must first read the device successfully. If the read has not been completed then the write operation will be abandoned. The driver prints messages to the error logs and records a NODE_OFFLINE stat each time that it attempts to write but is unable to. The DAP-Config command is an exception to the above notes. A read is not required. The Dap Config command is used to turn off/on DAP units. The Command uses two consecutive array elements. The first is the zone, the second is the inhibit command. Valid zones are 0-63. If any inhibit bit (bits 0-5) is set then the unit will not run. If bits 0 to 5 are off then the unit will run. Bits 6& 7 are used for display only on the DAP panel. 0x01 - Inhibit Cooling 0x02 - Inhibit Heating 0x04 - Inhibit Humid 0x08 - Inhibit Dehumidification 0x10 - Inhibit fan 0x20 - Reserved 0x40 - Network Standby - Display on panel (only has no effect on unit) 0x80 - Network off inhibit is active - display only - no effect on operation This function should be used as a wrbc/x. When the driver encounters this command it reads the associated data array, loads the two elements found at the array offset into the message and transmits the message. The driver does not set any data array elements to confirm that the command concluded successfully.

Indicates Driver release this release of the manual corresponds to.
Revisions to the manual. Each time that the driver release number changes the manual revision is set to zero.
This is the first release of this driver since its separation from a combined Dart/Dap driver. Previously this manual was identified as the “Data Aire user Manual Rev1.05a Rev2”