Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-60 Gardner Denver Auto Sentry

ES/RS2000

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Page 2 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 3 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 3 · click to enlarge
Page 3
1. Gardner Denver Auto Sentry ES/RS2000 Description

The Gardner Denver Auto Sentry ES/RS2000 driver allows the FieldServer to transfer data from devices over either RS-232 or RS-485 using Gardner Denver Auto Sentry ES/RS2000 protocol. The driver can be configured to communicate with ES Controllers with software versions V2.0X, V2.1X and RS2000 Controllers with software versions V4.0X

The client driver implements the following functionality:

  • Polls controllers for service and maintenance data.
  • Polls controllers for operating mode data.
  • Polls controllers for operating data. The driver can poll up to 8 units connected to one ES/RS2000 Controller. It always sets the active unit on the ES/RS2000 Controller before polling for data even if consecutive polls are for the same unit. This is done to prevent synchronization problems. Gardner Denver ES/RS2000 Controllers implements three message types for which the driver can poll. The driver does not validate the message data fields for correct values although it does validate data field lengths For example, shutdown codes reported by V2.1 ES Controllers range from 0 to 27. If a code of 28 is reported, the driver will not flag it as an error since codes have to be interpreted by the operator. However, a message length longer than 2 digits will be reported as an error.

Max Nodes Supported FieldServer Mode Nodes Comments

Client 1 A client node can communicate with up to 8 units connected to a ES/RS2000 Controller

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 4 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 4 · click to enlarge
Page 4
2. Driver Scope of Supply
FieldServer TechnologiesDescription PART # FS-8915-10UTP cable (7 foot) for RS-232 use FS-8917-03RJ45 to DB9M connector adapter FS-8700-60Driver Manual

1.02 Provided by the Supplier of 3rd Party Equipment

2.1.1. Required 3rd Party Hardware

Part #Description -ES/RS2000 controller

2.1.2. Required 3rd Party Software

None.

2.1.3. Required 3rd Party Configuration

The ES/RS2000 Controller must be set up in the correct mode to support either RS-232 or RS-485 communications to an external monitoring system. Please refer to manufacturer’s setup instructions.

2.1.4. Optional Items

PART #Vendor/ManufacturerDescription 485LDRCB&B ElectronicsRS-232/RS-485 converter

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 5 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 5 · click to enlarge
Page 5
3. Hardware Connections

The FieldServer is connected to the ES/RS2000 Controller as shown in the connection drawing below: Configure the ES/RS2000 Controller according to manufacturer’s instructions.

FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 5)
Fig. 2 · FS-8700-60 Gardner Denver Auto Sentry

1.03 Hardware Connection Tips / Hints If inter-controller communications are set up for the controller, connect to the RS-232 port only. If inter-controller communications are not used, connect to either the RS- 232 or RS-485 port of the Controller.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 6 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 6 · click to enlarge
Page 6
4. Configuring the FieldServer as a Gardner Denver Auto Sentry ES/RS2000 Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Gardner Denver Auto Sentry ES/RS2000 Controller.

1.04 Data Arrays/Descriptors The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Gardner Denver Auto Sentry ES/RS2000 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters

Provide data format. Each Data Array can only take on one format.

Float, UInt16, Uint32, Byte, Packed_Byte, Swapped_Byte

Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.

// Data Arrays Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length, DA_Service_Data, Uint32, 38 DA_Oper_Mode, UInt16, 3 DA_Oper_Data, Uint16, 5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 5 more labels / short text on this page
Section Title Data_Arrays · Data_Array_Format · Data_Array_Length · 1-10,000 · Example
Page 7 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 7 · click to enlarge
Page 7
FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 7)
Fig. 3 · FS-8700-60 Gardner Denver Auto Sentry

Specify which port the device is connected to the FieldServer

Protocol Specify protocol used Gardner_Denver Baud* Specify baud rate 1200, 9600 (match to Controller) Parity* Specify parity None Data_Bits* Specify data bits 7 Stop_Bits* Specify stop bits 1

Poll_Delay* Time between internal polls > = 0.2s Timeout* Time to wait for response > = 0.6s

FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 7)
Fig. 4 · FS-8700-60 Gardner Denver Auto Sentry

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Example

Page 8 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 8 · click to enlarge
Page 8
FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 8)
Fig. 5 · FS-8700-60 Gardner Denver Auto Sentry

Node_Name Provide name for node Up to 32 alphanumeric characters

Node_ID Unit number connected to an ES/RS2000 controller 1-8

Connection Specify which port the device is connected to the FieldServer P1-P8, R1-R21

Sets the protocol to be used for different Controller software versions

FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 8)
Fig. 6 · FS-8700-60 Gardner Denver Auto Sentry

// Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Connection Node_1, 1, Gardner_Denver, P1 Node_2, 2, Gardner_Denver, P1

1.07 Client Side Map Descriptors

4.1.1. FieldServer Related Map Descriptor Parameters

FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 8)
Fig. 7 · FS-8700-60 Gardner Denver Auto Sentry

Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

0 to maximum specified in “Data Array” section above

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 9 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 9 · click to enlarge
Page 9

4.1.2. Driver Related Map Descriptor Parameters

ColumnFunctionLegal Values Title Node Name _Name of Node to fetch data fromOne of the node names specified in “Client Node Descriptor” above Gar cmd _Data poll commandsService Data, Operating Mode, _ _ Operating Data Gar data _Data fields in a data poll command response message. Can be used to poll for all or specific data or just isolate specific items in a “All” poll._ Available with Service Data: All, _ Advisories, Shutdown codes, _ Hourmeter shutdown, _ Hourmeter total, _ Hourmeter loaded, _ Hourmeter temp, _ Hourmeter tmp st, Last maint A, Last maint B, Oilage _ _ Available with Operating Mode: _ All, Oper mode, Seq number, _ _ Oper state _ Available with Operating Data: All, _ System pressure, Filter pressure, _ _ Discharge temp, Reservoir temp, _ _ Motor current

4.1.3. Timing Parameters

Column TitleFunctionLegal Values Scan Interval _Rate at which data is polled. Note that the Poll Delay Connection parameter affects the _ effective scan interval.≥0.1s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 10 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 10 · click to enlarge
Page 10
FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 10)
Fig. 8 · FS-8700-60 Gardner Denver Auto Sentry
FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 10)
Fig. 9 · FS-8700-60 Gardner Denver Auto Sentry

GD_MBA1, DA_Service_Data, 0, RDBC, Node_1, Service_Data, All, 1.0s GD_MBA2, DA_Oper_Mode, 0, RDBC, Node_1, Operating_Mode, All, 1.0s GD_MBA3, DA_Oper_Data, 0, RDBC, Node_1, Operating_Data, All, 1.0s

37 Oilage Unknown, see ES/RS2000 controller spec

2 Discharge temperature divide by 16 for temperature in degrees F

3 Reservoir temperature divide by 16 for temperature in degrees F

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

0 Advisories see ES/RS2000 Controller spec

1-20 10x (Shutdown code / Hourmeter reading) pairs see ES/RS2000 Controller spec

0 Operating mode indication see ES/RS2000 Controller spec

1 Sequence number2 see ES/RS2000 Controller spec

2 Unit operating state3 see ES/RS2000 Controller spec

0 System pressure divide by 16 for pressure in psig

1 Filter pressure divide by 16 for pressure in psig

4.1.4. Map Descriptor Example 1 – Polling all available Controller Data

21 Current total runtime hourmeter reading Hours

22 Current loaded runtime hourmeter reading Hours

23-28 6x Current temp hourmeters [H1] – [H6] Hours

29-34 6x Stored temp hourmeters [OH1] – [OH6] Hours

35 Last maintenance A Hours

36 Last maintenance B Hours

2 ES V2.0X Controllers do not respond with this field 3 ES V2.0X Controllers do not respond with this field

function responsible for polling the Controller.

Data will be stored as follows:

Show 4 more labels / short text on this page
Offset Description Units · Operating mode data · DA_Service_Data · Operating data
Page 11 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 11 · click to enlarge
Page 11
FieldServer FS-8700-60 — FS-8700-60 Gardner Denver Auto Sentry diagram (page 11)
Fig. 10 · FS-8700-60 Gardner Denver Auto Sentry

“Discharge_temp” is isolated here by

still using the same Gar_cmd as the

active map descriptor.

Map Descriptor Name,Data Array Name,Data Array Offset,Function,Node Name,Gar cmd,Gar data,Scan Interval _ _ GD MBA1,_ _ DA Service Data,_ _ 0,RDBC,_ Node 1,_ Service Data,_ All,_ 1.0s _ GD MBA2,_ _ DA Oilage,0,Passive Client,_ Node 1,_ Service Data,Oilage,- _ GD MBA3,_ DA Hourmeter,0,_ Passive Client,_ Node 1,_ Service Data,Hourmeter total,- ______ GD MBA4,DA Oper Mode,0,RDBC,Node 1,Operating Mode,All,1.0s _ GD MBA5,_ _ DA Oper State,0,Passive Client,_ Node 1,_ Operating Mode,Oper state,- __ _____ GD MBA6,DA Oper Data,0,RDBC,Node 1,Operating Data,All,1.0s _ GD MBA7,_ _ DA Disch Temp,0,Passive Client,_ Node 1,_ Operating Data,Discharge temp,- Note the use of the passive map descriptor function. This map descriptor Note, the Gar cmd Note that a specific data item, _ does not poll but receives data from the active map descriptor since the indicates polling for “Discharge temp” is isolated here by _ Gar cmd and Node Name fields match. Operating data. still using the same Gar cmd as the _ _ _ active map descriptor.

4 RS2000 V4.0X Controllers set this field to zero

Gar_cmd and Node_Name fields match.

Controller.

Page 12 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 12 · click to enlarge
Page 12

Appendix 1. Advanced Topics

Appendix 1.1. Can I use only Passive Client mapdescs ?

No. A passive client map descriptor must be used after an active RDBC map descriptor. The driver uses the active map descriptors to poll the Controller and then searches for Passive Client map descriptors with matching Node_Name and Gar_Cmd fields. It then stores the data items as specified by the Gar_data field from the data collected by the preceding active map descriptor.

Appendix 1.2. Data length of specific polls versus “All” data polls

The length of the data packet retrieved from the Controller during a poll is always fixed for each of the three types of data polls. When specifying a specific Gar_data item on a RDBC active map descriptor, the driver still gets all data of Gar_cmd type from the controller in a single poll, but only stores the data item in question.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 13 of the FieldServer FS-8700-60 user manual — FS-8700-60 Gardner Denver Auto Sentry
Page 13 · click to enlarge
Page 13

Appendix 2. Revision History

Date Resp Format Driver

Doc. Rev. Comment

Ver.

9/2/02 JDM 1.00a 1 Applying new template. 4/12/04 DR DR 1.02b 2 Updated 7/12/04 DR DR 1.03a 3 Updated connection diagram

7/16/04 Meg Meg 1.03a 4 Redrew connection diagram. Reformatted document.

8/24/04 Meg Meg 1.03a 5 Replaced connection diagram with original created by Deon. 12/29/04 JD 1.03a 6 Releasing

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-60

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-60

Be the first to ask — other owners or our team will answer.

Original document

FieldServer FS-8700-60 manual PDF

13 pages·119 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…