Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-52 Notifier AM6000

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Instruction Manual Part Number FS-8700-52

5/22/2002

Page 2 of the FieldServer FS-8700-52 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer FS-8700-52 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 of the FieldServer FS-8700-52 user manual — 1. Notifier AM6000 Description
Page 3 · click to enlarge
Page 3

1. Notifier AM6000 Description

The Notifier AM6000 driver is a seial driver. It allows the FieldServer to transfer data from a Notifier AM6000 panel over either RS232 or RS485 using Notifier AM6000 protocol. There are eight RS232 and two RS485 ports standard on the FieldServer. The FieldServer can only a passive Client.

The driver receives messages intended for a system printer, interprets these messages by filling in data arrays in the FieldServer. This data is available for other devices or PLC's to read.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 4 of the FieldServer FS-8700-52 user manual — 2. Driver Scope of Supply
Page 4 · click to enlarge
Page 4

2. Driver Scope of Supply

2.1 Supplied by FieldServer for this driver

FieldServerDESCRIPTION Technologies PART # 8915-10UTP cable (7 foot) for RS232 use UTP cable (7 foot) for Ethernet connection 8917-02RJ45 to DB9F Connector adapter 8917-01RJ45 to DB25M connection adapter SPA59132RS485 connection adapter Driver Manual.
Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 5 of the FieldServer FS-8700-52 user manual — 3. Hardware Connections
Page 5 · click to enlarge
Page 5

3. Hardware Connections

Configure the Notifier AM6000 according to manufacturer’s instructions.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 6 of the FieldServer FS-8700-52 user manual — 4.1 Data Arrays
Page 6 · click to enlarge
Page 6

4. Configuring the FieldServer as a Notifier AM6000 Client

For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Notifier AM6000 Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Notifier AM6000 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

4.1 Data Arrays

Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provide data format. Each data array can only take on one format.

FLOAT, BIT, UInt16, SInt16, Packed_Bit, Byte, Packed_Byte, Swapped_Byte Data_Array_Length Number of Data Objects. Must be larger than the data storage area required for the data being placed in this array.

// Data Arrays // Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length DA_AI_01, UInt16, 200 DA_AO_01, UInt16, 200 DA_DI_01, Bit, 200 DA_DO_01, Bit, 200

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Section Title Data_Arrays · 1-10,000 · Example

Page 7 of the FieldServer FS-8700-52 user manual — 4.3 Client Side Nodes
Page 7 · click to enlarge
Page 7

4.2 Client Side Connections

FieldServer FS-8700-52 — 4.2 Client Side Connections diagram (page 7)
Fig. 2 · 4.2 Client Side Connections

Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer

Baud* Specify baud rate 2400 (Only baud rate supported by the Notifier port) Parity* Specify parity Even Data_Bits* Specify data bits 7 Stop_Bits* Specify stop bits 1 Protocol Specify protocol used AM6000 Handshaking* Specify hardware handshaking None Poll Delay* Time between internal polls 0-32000 seconds default 1 second Example // Client Side Connections Connections Port, Baud, Parity, Protocol, Data_bits, Handshaking, Poll_Delay P8, 2400, Even, AM6000, 7, None, 0.100s

FieldServer FS-8700-52 — 4.2 Client Side Connections diagram (page 7)
Fig. 3 · 4.2 Client Side Connections

4.3 Client Side Nodes

FieldServer FS-8700-52 — 4.3 Client Side Nodes diagram (page 7)
Fig. 4 · 4.3 Client Side Nodes

Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Node_ID Modbus station address of physical server node

Protocol Specify protocol used Modbus_RTU, Modbus/TCP, etc. Port Specify which port the device is connected to the FieldServer

FieldServer FS-8700-52 — 4.3 Client Side Nodes diagram (page 7)
Fig. 5 · 4.3 Client Side Nodes

// Client Side Nodes Nodes Node_Name, Protocol, Port Panel1, AM6000, P8

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Example

Page 8 of the FieldServer FS-8700-52 user manual — 4.4 Client Side Map Descriptors
Page 8 · click to enlarge
Page 8

4.4 Client Side Map Descriptors

4.4.1 FieldSe rver Specific Map Descriptor Parameters

FieldServer FS-8700-52 — 4.4 Client Side Map Descriptors diagram (page 8)
Fig. 6 · 4.4 Client Side Map Descriptors

Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above Data_Array_Location Starting location in Data Array 0 to maximum specified in “Data Array” section above Function Function of Client Map Descriptor Passive

4.4.2 Driver Specific Map Descriptor Parameters

Column Title Function Legal Values Node_Name Name of Node to fetch data from One of the node names specified in “Client Node Descriptor” above Data_Type Data type Register, Coil, AI, DI Length Length of Map Descriptor. This value is important when a 'Block Ack' message is received as it tells the driver how much of the data array to zeroise.

1. 1000

Address Loop/Device Address In the format mmnn where mm is the loop number and nn is the device number. Together they forma a composite device number.

AM6000 Driver specific parameters & keywords.

Am6000_typeID Used to differentiate between device and system type messages.

Device-only, System_trbl, device&type. system-Styl2, catch-all Additional notes are provided in section 5.1 Am6000_Status Allows direction of alarm or trouble states to different data arrays.

Any, Alarm, trouble, erase, on , eraseon Additional notes are provided in section 5.2 AM6000_Ackable Tells the driver that the data area of this mapdesc must be Zeroised when a block ack is received.

Additional notes are provided in section 5.3 Am6000_simulation Provided for debugging and test purposes only. Tells the driver which debug message to send. This parameter is for use by FieldServer Technologies only.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

501, 302

Page 9 of the FieldServer FS-8700-52 user manual — 4.4 Client Side Map Descriptors
Page 9 · click to enlarge
Page 9

4.4.3 Timing Parameters

Column Title Function Legal Values Scan_Interval Rate at which data is polled >0.1s

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 10 of the FieldServer FS-8700-52 user manual — 4.4 Client Side Map Descriptors
Page 10 · click to enlarge
Page 10

4.4.4 Map Descriptor Example.

Name of the data array that will be updated when this map descriptor is used.

The position in the data array that corresponds to device whose number is equal to the Address Parameter. In this example device 500's state will be strored in the 0th element of the data array called DEVICE_STATES_LOOP1

The range of device address is determined by this parameter. Because address is 500 and length is 100 in this example all devices 500 to 599 will be

All map descriptors for the AM6000 Notifier driver must be passive.

Map_block_Name, scan_interval, Data_Array_Name, Data_Array_Offset, Function, node_name, AM6000_TypeID, Address , Length , am6000_Ackable DEVICES_100_199, 1.0s, DEVICE_STATES_LOOP1, 0, passive, node_a, device-only, 500 , 100 , Yes

Connects this map descriptor to a node whose name is 'node_a' and thus connects the map descriptor to a port.

When a Block Acknowledge or System Reset message is received the driver will set the portion of the data array DEVICE_STATES_LOO P1 starting at Data_Array_Offset for Length number of elements to zero.

The device address of the first device to be processed by this map descriptor. Devices are allocated to loops. The device address consists of a mmnn format where mm is the loop number and nn is the device number. In this example the address is set to 500 this indicated that the first device to be processed by this map desc. Is on loop 5 and is device zero.

This keyword indicates that this map descriptor will only be used to process device state messages. This makes the address and length parameters very important.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 11 of the FieldServer FS-8700-52 user manual — 4.4 Client Side Map Descriptors
Page 11 · click to enlarge
Page 11

Name of the data array that will be updated when this map descriptor is used.

All map descriptors for the AM6000 Notifier driver must be passive.

When a Block Acknowledge or System Reset message is received the driver will set the portion of the data array DEVICE_STATES_LO OP1 starting at Data_Array_Offset for Length number of elements to zero.

Map_block_Name,scan_interval, Data_Array_Name, Data_Array_Offset, Function, node_name, AM6000_TypeID, Length , am6000_Ackabl MD1, 1.0s, SYSTEM_TROUBLES2, 5, passive, node_a, system-styl2, 50 , Yes

System Trouble Messages are processed using this map descriptor. Only one map descriptor like this is necessary for a whole system. This indicates Style2 is being used. Thus when system trouble message number n is processed the nth element of data array starting at location 5 (this example) will be set to 1.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 12 of the FieldServer FS-8700-52 user manual — 5. Driver Notes
Page 12 · click to enlarge
Page 12

5. Driver Notes

5.1 Map Descriptor Keywords

5.1.1 AM6000_TypeID

This keyword sets up a category of messages. If you are interested in device state's use the keyword device-only. If you are interested in system trouble messages use the keyword system- trbl (An alternate method for reporting system trouble messages is provided using the keyword system-styl2. ) device-only Only device based messages are processed using map descriptors with this keyword. The Address and Length parameters define the range of devices processed using the map descriptor. A device address consists of a loop and device number. This driver treats the two parts as a single device address. Thus loop 5 device 2 becomes address 502 for this driver and a map descriptor with an address of 500 and a length of 100 would process a message from device 2 on loop 5. system-trbl System Trouble messages are processed a numeric value is stored in the first element of the map descriptor's data array. If a new system trouble message is processed then the value is overwritten with the new value. system-styl2 This is an alternate style for processing System Trouble messages. If system trouble message whose index in the list below is n is received then the nth element of the data array is set to one. Make sure the length parameter is set to at least 50. Catch-all The use of this keyword is described in section 5.2

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 13 of the FieldServer FS-8700-52 user manual — 5. Driver Notes
Page 13 · click to enlarge
Page 13

5.1.2 AM6000_Status

Device state messages report a number of different states for the device. These states are refered to as the device status. The following are possible values of this parameter. Any, alarm, trouble, on, erase, eraseon. If you do not use this parameter in a device-only map descriptor then the driver uses the default value of Any. This means that any device state message will result in the same data array being updated. Thus a trouble/on/alarm message will result in the array being set to a 1. If you want to maintain separate array's for each state the you use this parameter. For one device address range you would have multiple map descriptors, each with a different AM6000_Status keyword. You should note that the keyword, erase, results in the data array value being set to zero when a message reports the device state as 'ERASE'. The keyword eraseon sets the value to one, when the same message is received.

5.1.3 AM6000_Ackable

This parameter tells the driver that the data array portion associated with this map descriptor can be set to zero when a Block Acknowledge or System Reset message is received. You set this parameter to one of the following legal keywords: yes, no. The Data_Array_Location and Length parameters are used to determine what portion of the associated data array must be set to zero.

5.1.4 AM6000_Simulation

This keyword is for used by FieldServer Technologies Engineers and is used for testing this driver.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 14 of the FieldServer FS-8700-52 user manual — 5.2 Statistics
Page 14 · click to enlarge
Page 14

5.2 Statistics

This driver does not keep statistics for each map descriptor. Statistics are maintained for the connection to the Am6000 Notifier device.

Count of received messages and bytes. A complete received message is 82 bytes long and thus if all messages are received correctly the byte count should be a multiple of 82.

This indicates the number of times a 'Block Ack' or 'System Reset' message have been applied. If you have 5 'Ackable' map descriptors and one 'Block Ack' message was received a count of 5 would be reported. (One message applied 5 times). You will need to count the number of 'ackable' map descriptors to use this statistic meaningfully.

FieldServer FS-8700-52 — 5.2 Statistics diagram (page 14)
Fig. 7 · 5.2 Statistics
Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 15 of the FieldServer FS-8700-52 user manual — 5.2 Statistics
Page 15 · click to enlarge
Page 15
FieldServer FS-8700-52 — 5.2 Statistics diagram (page 15)
Fig. 8 · 5.2 Statistics

This statistic indicates the number of messages that were received but were ignored by the driver. Messages are ignored for one of two reasons. Firstly, the driver might not understand the message and secondly because the driver doesn't know what to do with the data from the message.

Ignored Messages Ignored messages are very important since they do not result in the data arrays being updated. Messages are ignored for one of two reasons. Firstly, the driver might not understand the message and secondly because the driver doesn't know what to do with the data from the message. The message t may contain a keyword or be formatted in a way that cannot be understood.. It may be the case that the equipment manufacturer adds new features to the protocol. FieldServer Technologies needs to be informed of any such messages so that this driver can be updated. Secondly, you may have omitted to define a map descriptor which tells the driver what to do with the data from an incoming message. For example, say a map descriptor is defined for address 501 with a length of 50 but a message is received from device 575. Clearly the map descriptor's device address range does not extend ass far as 575 and thus the driver doesn't know where to store device 575's data.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 16 of the FieldServer FS-8700-52 user manual — 5.2 Statistics
Page 16 · click to enlarge
Page 16

Catching Ignored Messages To assist you catch and monitor ignored messages the driver provides a special map descriptor keyword. Make a map descriptor and set the parameter AM6000_TypeID 's value to Catch-All. Make sure that this is the last map descriptor in the csv file. The map descriptor requires a data length of at least 82 and when using RUI_Debug you should view the data array in tring mode. The driver will place any ignored messages in this buffer. You will be able to read the message in tring mode an make a decision on the necessary corrective action. If there are multiple messages being ignored the buffer will be overwritten. You could use your PLC / control device / Scada to monitor the first byte of this data array and generate an alarm if the value is non-zero. Thus, even though a message has been ignored you system will know about it.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 17 of the FieldServer FS-8700-52 user manual — 5.3 Listing of System Trouble Messages
Page 17 · click to enlarge
Page 17

5.3 Listing of System Trouble Messages

0 !!! ILLEGAL !!! 1 MAINS TROUBLE 2 POWER LOW ON MAIN SUPPLY 3 POWER LOW ON AUXILIARY SUPPLY 4 POWER LOW ON BATTERY-CHARGER 5 POWER OVERVOLTAGE ON MAIN SUPPLY 6 POWER OVERVOLTAGE ON BATTERY-CHARGER 7 FAILURE OR OVERLOAD ON MAIN SUPPLY 8 FAILURE OR OVERLOAD ON AUXIL. SUPPLY 9 FAILURE ON BATTERY-CHARGER 10 DISCONNEC. BATT. OR FUSE FAILURE 11 BATTERY EXHAUSTED 12 BATTERY CHARGER UNBALANCED 13 AUX. SUPPLY DISCONNECTED 14 AUX. SUPPLY USER FUSE 15 MAIN SUPPLY USER FUSE 16 SIREN FUSE 17 EARTH TROUBLE 18 SIREN SUPERV.LINE INTERRUPTED 19 BATTERY FAILURE 20 WIRE CUT ON LINE 21 SHORT CIRCUIT ON LINE 22 PRINTER: OFF LINE/BUFFER FULL/PAPER END 23 COMMUNICATION ERROR ON 24 LOW VOLTAGE ON LINE 25 SIDE A OPEN ON LINE 26 SIDE B OPEN ON LINE 27 SYSTEM KEYPAD TROUBLE 28 INTERNAL PROGR.ENABLING JUMPER :ENABLED 29 SYSTEM START UP 30 CPU RESET OR WATCH-DOG FAILURE 31 CRT-TERMINAL : OFF-LINE 32 FLASH MEMORY ERROR ON 33 SIREN SUPERV.LINE 34 LINE 35 ANNUNC.

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Msg Index Message

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-52

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-52

Be the first to ask — other owners or our team will answer.

Original document

FieldServer FS-8700-52 manual PDF

17 pages·307 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…