FieldServer FS-8700-41

58 pages·2.3 MB·Computer Drive·PDF·ENDEFRITNLJA
FieldServer FS-8700-41
Table of Contents 33 sections Driver Manual (Supplement to the FieldServer Instruction Manual) · FS-8700-41 Simplex Time Recorder Company - 4100 Computer Port Protocol · APPLICABILITY & EFFECTIVITY · 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD · … ShowHide
Page 1 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 1 · click to enlarge
Page 1
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 1)
Fig. 1 · Driver Manual (Supplement to the FieldServer Instruc…

A Sierra Monitor Company

Driver Manual (Supplement to the FieldServer Instruction Manual)

FS-8700-41 Simplex Time Recorder Company - 4100 Computer Port Protocol

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Driver Version1.07 Document Revision: 8
Page 2 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 3 · click to enlarge
Page 3

FS-8700-41 Simplex Driver Manual Table of Contents

Appendix A.11. Advanced Map Descriptor Example 2. - Read Panel Time 33 Appendix A.12. Advanced Map Descriptor Example 3 - Write Panel Time 34 Appendix A.13. Advanced Map Descriptor Example 4 - Panel Revision Information 34 Appendix A.14. Advanced Map Descriptor Example 5 - AckAll 35 Appendix A.15. Advanced Map Descriptor Example 6 - Silence / Reset 35 Appendix A.16. Advanced Map Descriptor Example 7 - Acknowledge a specific point 36 Appendix A.17. Advanced Map Descriptor Example 8 - ClearAll 37 Appendix A.18. Advanced Map Descriptor Example 9 - Earths 38 Appendix A.19. Advanced Map Descriptor Example 10 - Show 39 Appendix A.20. Using Clist to Write-Through and Store point status from Unsolicited Messages 41

Appendix B. Troubleshooting Tips 42 Appendix B.1. Address Errors 42 Appendix B.2. Driver Limitations 42 Appendix B.3. Resolving Network Addresses above 255 43

Appendix C. Error Messages 44

Appendix D. Pseudo Points 49

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 4 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 4 · click to enlarge
Page 4
1. Simplex Time Recorder Company - 4100 Computer Port Protocol

The Simplex Time Recorder Company - 4100 Computer Port Protocol driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Simplex Time Recorder Company - 4100 Computer Port Protocol. This driver is designed to connect to a Simplex 4100 panel equipped to support the “4100 Computer Port Protocol” as defined in Simplex’s document 950-004 Revision E dated 28 July 2000. The implementation provides a selected subset of protocol functions and subset of functionality for each of these selected functions. It is important to note the exclusions and limitations described in this document. The driver is a capable of parsing and storing information sent by a panel in the form of unsolicited messages which are typically generated when there is a state change in the panel or one of the connected devices. The driver is also capable of polling for point and panel status data and some additional data such as the panel’s time and revision information. In addition the driver is capable of setting some control points in the panel – acknowledging and resetting alarms and writing data (where permitted) to some analog and discrete points. This is a client only driver and is not capable of emulating a Simplex Panel. Server emulation is provided for test purposes only and is not supported or documented.

1.1. Supported Panel Types

The driver has been tested against 4020, 4100 and 4100U panels. There is no difference in the protocol format between the various panels. What changes is the panel firmware version and with the firmware changes the supported function set changes.

1.2. Simplex Panel Firmware Revision vs. Supported Functionality

This driver was primarily tested against a 4020 panel with firmware revision 9.2. Beta testing against a 4100 panel with a firmware revision 10.x was also performed. A grid of firmware revision number and supported functions is provided by Simplex. This grid is available from Simplex. Request the ‘CPP Revision Compatibility’ Table. All the functions described in this manual are supported for firmware revisions 10 or higher. For revisions between 9.2 and 10, the ‘Earths’ and ‘Value’ functions described in this driver are not supported by the Simplex Panels. For revisions lower than 9.2, then functions supported need to be determined by trial and error. We are fairly confident that all the functions supported by version 9x are also supported by versions 8x of the panel firmware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 5 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 5 · click to enlarge
Page 5
2. Driver Scope of Supply

2.1. Supplied by FieldServer Technologies for this driver

FieldServer TechnologiesDescription PART # FS-8917-16Ethernet Cable with pigtail (4020 and 4100 Panels) FS-8917-07Ethernet cable with 25 pin male connector. (4100u Panels) SPA59132RS-485 connection adapter FS-8700-41Driver Manual.

2.2. Provided by Supplier of 3rd Party Equipment

To enable the 4100 Protocol, the 4100 system, supplied by the user, must have a free RS- 232 port dedicated for use with the computer device. In most cases, this is not included in the base configuration of the product provided by The Simplex Time Recorder Company, and must be added as a sales option. All 4100 systems limit the number of computer ports active at one time in a system. To determine the limit for the specific product configuration, refer to the specific product specifications, or contact a Simplex sales representative.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 6 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 6 · click to enlarge
Page 6
3. Hardware Connections

The FieldServer is connected to the Simplex Device’s RS-232 port of device type "COMPUTER", the following port attributes may be configured specifically for that particular port:

Ensure that these settings correspond to the settings described in section 4 of this document. Sim4100 Panel Setting Default Options Baud Rate 9600 75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200 Parity EVEN1 ODD, EVEN, MARK, SPACE, NONE Data Bits 8 7 or 8 Stop Bits 1 1 or 2 Sim4100U Panel Setting Default Options Baud Rate 9600 75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200 Parity NONE1 ODD, EVEN, MARK, SPACE, NONE Data Bits 8 7 or 8 Stop Bits 1 1 or 2 The following are the Simplex, recommended connections to be used in cabling between the 4100 and the FieldServer device. For the computer device, the standard EIA signal description, and the 25 pin (DB25) and 9 pin (DB9) connector assignments are shown.

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 6)
Fig. 2 · Driver Manual (Supplement to the FieldServer Instruc…
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 6)
Fig. 3 · Driver Manual (Supplement to the FieldServer Instruc…
4100 HostCableComputer 4100SignalSignalDB25PinDB9Pin PortPortDB25 Pin ATB1BTB2 812TXD→RXD22 633RXD←TXD33 724RTS2RTS47 545CTSCTS58 457GND──GND75

1 Odd or Even parity is recommended (by Simplex) to provide additional error detection at the character level. 2 Note, that if HSHAKE is not used (Simplex Device Setting), the connections between RTS and CTS are not required

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 7 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 7 · click to enlarge
Page 7

3.1. Connection to a Simplex 4020 Panel

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 7)
Fig. 4 · Driver Manual (Supplement to the FieldServer Instruc…

Card 4020/RS-232/2120 modem ready assembly.

Terminal Block Markings Port A =1-5, Port B=6-10. 1=+com(xmt). 2=+com(rts), 3=-com(rcv), 4=-com(cts), 5=gnd, 6=xmt, 7=rts, 8=rcv, 9=cts, 10=gnd,

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Communication Board · Chip 4100 RS2120

Page 8 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 8 · click to enlarge
Page 8
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 8)
Fig. 5 · Driver Manual (Supplement to the FieldServer Instruc…
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 8)
Fig. 6 · Driver Manual (Supplement to the FieldServer Instruc…
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 8)
Fig. 7 · Driver Manual (Supplement to the FieldServer Instruc…

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Serial Connection

Page 9 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 9 · click to enlarge
Page 9

3.2. Connection to a Simplex 4100 Panel

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 9)
Fig. 8 · Driver Manual (Supplement to the FieldServer Instruc…
FS-X40 FUNCTIONFROMSIMPLEX 4100 PANEL RXRJ45-01XMIT TXRJ45-08RCV GNDRJ45-04GND
P1 P2 P3 P4 P5 P6 P7 P8 R1 R2 N1 N RS232 RS485 10 Base ETHERN P1 P2 P3 P4 P5 P6 P7 P8 R1 R2 Net 1 Net 2 s m t n wr RxTxRxTxRxTxRxTxRx TxRxTxRxTxRxTxRxTxRxTxTxRxConTxRx ConSy Co Ac Ru P

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 10 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 10 · click to enlarge
Page 10

3.3. Connection to a Simplex 4100U Panel

Port A Front of 4100U Panel

Pin 3 - Blue

Pin 7 - Green

Pin 2 - White

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Port B

Page 11 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 11 · click to enlarge
Page 11
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 11)
Fig. 9 · Driver Manual (Supplement to the FieldServer Instruc…

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 12 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 12 · click to enlarge
Page 12
4. Configuring the FieldServer as a Simplex Time Recorder Company - 4100 Computer Port Protocol Client

For a detailed discussion on FieldServer configuration, please refer to the relevant instruction manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Simplex Time Recorder Company - 4100 Computer Port Protocol Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Simplex Time Recorder Company - 4100 Computer Port Protocol communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1. Data Arrays

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 12)
Fig. 10 · Driver Manual (Supplement to the FieldServer Instruc…

Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters

Provide data format. Each Data Array can only take on one format.

Number of Data Objects. Must be larger than the required data storage area.

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 12)
Fig. 11 · Driver Manual (Supplement to the FieldServer Instruc…

// Data Arrays Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length DA_AI_01, UInt16, 200 DA_AO_01, UInt16, 200 DA_DI_01, Bit, 200 DA_DO_01, Bit, 200

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Example

Page 13 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 13 · click to enlarge
Page 13

4.2. Client Side Connection Descriptions

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 13)
Fig. 12 · Driver Manual (Supplement to the FieldServer Instruc…

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R23

Baud* Specify baud rate 110 – 115200, standard baud rates only.

Parity* Specify parity Even, Odd, None, Mark, Space Data_Bits* Specify data bits 7, 8 Stop_Bits* Specify stop bits 1 Protocol Specify protocol used sim4100 Handshaking* Specify hardware handshaking RTS, RTS/CTS, None Poll Delay* Time between internal polls 0-32000 seconds, 1 second Example

// Client Side Connections Connections Port, Protocol, Baud, Parity, Handshaking, Poll_Delay P8, Sim4100, 9600, Even, None, 0.100s

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 13)
Fig. 13 · Driver Manual (Supplement to the FieldServer Instruc…

4.3. Client Side Node Descriptors

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 13)
Fig. 14 · Driver Manual (Supplement to the FieldServer Instruc…

Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters

This parameter is IGNORED. Special keywords to define the card-sub-point are described in section 4.4 Protocol Specify protocol used Sim4100

Port Specify which port the device is connected to the FieldServer P1-P8, R1-R23

Required for Simplex4100 Panels. If not specified then a Simplex 4100/4020 panel is assumed. 4020/4100 - panels with firmware version 9x or earlier. 4100U – panels with firmware version 10x or later.

3 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 14 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 14 · click to enlarge
Page 14
FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 14)
Fig. 15 · Driver Manual (Supplement to the FieldServer Instruc…

// Client Side Nodes Nodes Node_Name, PLC_Type, Protocol, Connection Device1, 4100U, Sim4100, P8

4.4. Client Side Driver Tables

A driver table is used to extend a table of values/attributes that have been hard coded into the driver. It is possible to extend the tables using CSV file parameters. Additional information on the use of these tables may be found in Appendix A.8

4.4.1. SHOW Response Attributes Driver Table

Column Title Function Legal Values

Protocol The protocol must be specified on each row of a driver table. Sim4100

The exact character sequence that must be specified. May include an equal sign.

The SHOW command response consists of a number of attributes and their current state/ values. Use this parameter to add a new attribute to the table.

If the response contains the attribute defined above, its current state/value must be stored at offset x in the associated Data Array. Use this parameter to define x. Take care to leave enough space for those attributes which have multiple values.

May not be zero.

This parameter tells the driver how to convert the current state/value for storage in the Data Array. For example, the driver cannot store the state ‘Normal’ . By specifying method 1, you tell the driver to use the state descriptor ‘Normal’ in a lookup table of attribute states to find the value associated to Normal and to store that value.

1,2,3 May not be zero.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 4 more labels / short text on this page
Example · sim4100_Attr_Name · sim4100_Attr_Offset · sim4100_Attr_Method
Page 15 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 15 · click to enlarge
Page 15

4.4.2. SHOW Response Attribute States Driver Table

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 16 · Driver Manual (Supplement to the FieldServer Instruc…

The protocol must be specified on each row of a driver table.

Use this parameter to extend this list of predefined attribute states.

Define a state word such as ‘Normal’ and associate a value using the ‘value’ parameter.

This parameter is the value to be associated with the ‘name’

4.5. Client Side Map Descriptors

4.5.1. FieldServer Specific Map Descriptor Parameters

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 17 · Driver Manual (Supplement to the FieldServer Instruc…

Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

0 to maximum specified in “Data Array” section above

Function Function of Client Map Descriptor RDBC, WRBC, WRBX

4.5.2. Driver Specific Map Descriptor Parameters

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 15)
Fig. 18 · Driver Manual (Supplement to the FieldServer Instruc…

One of the node names specified in “Client Node Descriptor” above

Length of Map Descriptor - must always be specified. If the length of the response (such as errors / earths, show, revision) is not known in advance it should be set to a value large enough to store to allow some contingency. If data cannot be stored because an array is too short the driver will produce a message in the error log.

Address Not required. The address is specified by using the card-point-sub specification described in section 4.4.2

4.5.3. Timing Parameters

Column Title Function Legal Values Scan_Interval Rate at which data is polled >0.1s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 16 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 16 · click to enlarge
Page 16

4.5.4. Protocol (Simplex Device) Specific Parameters

Column Title Function Legal Values

Further notes on these keywords are provided in Appendix A Ackall, Setd, Disable, Restart, Clistall, Clist, Time, Ctime, Ack, Xpoint, Seta, Super, Show, Earths, Value, ClearAll The Simplex Time Recorder Company - 4100 Computer Port Protocol only uses the standard 4100 address format of --. Symbolic addressing is not supported. The following keywords are used to address devices. sim4100_Card Simplex Address

A keyword which controls the function being performed or the type of data being polled / written.

Further notes and examples are provided in Appendix A

sim4100_Point Simplex Address

sim4100_Sub Simplex Address

Only appropriate when the sim4100_func=clist. Controls the write through behavior of the clist function. See Appendix A.20 for additional information. When using the default value then the write commands are done using the format SET c-p-s ON/OFF. If the parameter is set to value then writes are done using the format SET c-p-s value.

Control the ability of ‘CLIST’ map descriptors to be used to store data from unsolicited messages. Refer also to Appendix A.20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 5 more labels / short text on this page
sim4100_func · sim4100_WriteThru* · Onoff, value · Store_Unsolicited* · Yes/No
Page 17 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 17 · click to enlarge
Page 17

This Map Descriptor can be used to poll for the status of a particular point. When the response is obtained the driver sets the value

of one Data Array element to a number indicating the point’s status. The values are described in Appendix A.4. You need one such

Simplex DeviceSub-Point
Simplex DeviceCard
Simplex DevicePoint

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name Length Scan_Interval, sim4100_func sim4100_card, sim4100_point, sim4100_sub

A1, DA_AI3, 0, RDBC, Node_A, 1, 5, Clist, 1, 2, 3

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Map Descriptor for every point whose status you wish to poll. Notes in Appendix A.13 provide more information

described in Appendix A

List Status' Function to

data. The format of the

(in this case) read the

current point status of

the point specified by

supervisory, trouble

card-point-sub. This

4.5.5. Map Descriptor Example 1. - Read Point Status

must be the same

as the node name

map Descriptor.

value of zero is

this position. A

first position.

data array.

Show 24 more labels / short text on this page
Perform the 'Computer · function returns fire, · returned data is · sim4100_func=ackal · Simplex protocol · Ignored for the · unless the · l, clearall, · the port connected · described in this · used to identify · This identifier · to the Simplex · device being · equivalent to the · array starting at · written into the · The data is · extracted from · placed in this · the device is · independent · The Data · driver
Page 18 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 18 · click to enlarge
Page 18

This Map Descriptor can be used to store point status data when the FieldServer receives an unsolicited message from the Panel

containing point status information (Xpoint messages). The panel sends an Xpoint message each time a point’s status changes to

any non-normal state. Using these Map Descriptors will ensure that the FieldServer is constantly updated with the latest panel status

information. The Map Descriptor’s are passive so they can be used in a joint strategy with the clist function (section 4.4.1) to keep

One Xpoint Map Descriptor is required for storage of Xpoint messages from each card. For a given card, the driver uses a mapping

Thus for this MapDesc. If the Xpoint message is for 1-1-0

If the value is 10 then the driver uses 10 array locations

. If the Xpoint message is for 1-2-5 then the state will be

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, sim4100_card, sim4100_point, sim4100_sub, Length

When used with an Xpoint MapDesc this parameter

A1 DA_AI3, 0 passive, Node_A, xpoint, 1, 0, 10, 1000

4.5.6. Map Descriptor Example 2. - Use unsolicited messages from the Panel to determine point

then the state will be stored at location 10.

means ‘How many sub-points per point ?’

Point 2Array locations 20-29 …

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Point 1Array location 10-19
Point 0Array locations 0-9

function based on the point-subpoint address to determine the array location to store the state for the c-p-s.

stored at location 25.

for each point. Thus

Set this to zero for xpoint

for this card are stored

Simplex DeviceCard

using this MapDesc.

track of a point’s status. Notes in Appendix A provide more information

MapDesc.

Must be passive Driver stores

device is placed in

array.

Show 10 more labels / short text on this page
All point-subpoint data · unsolicited · messages · data from · xpoint · status · extracted from the · independent data · The Data · this driver
Page 19 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 19 · click to enlarge
Page 19
5. Configuring the FieldServer as a Simplex Time Recorder Company - 4100 Computer Port Protocol Server

The driver contains some server side functionality which has been developed to meet FieldServer’s continuous quality assurance efforts. However, the server side functions are not documented or supported for customer use. If you have a strong requirement for this functionality then please contact the Sales and Marketing group of FieldServer.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 20 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 20 · click to enlarge
Page 20

Appendix A. Advanced Topics

Appendix A.1. Hardware Handshaking

The driver does not support the Simplex RTS/CTS handshaking model. Therefore deselect the HSHAKE terminal flag or connect CTS to RTS with a jumper on the 4100 side.

Appendix A.2. Simplex Address Formatting – Specific Keywords

The Simplex Time Recorder Company - 4100 Computer Port Protocol only uses the standard 4100 address format of --. Symbolic addressing is not supported. The following table lists keywords which control the behavior of the FieldServer with respect to connection to a Simplex device and the permissible values determining the type of data being read/written.

This command acknowledges all card-point-sub states based on the values found in the associated arrays. The FieldServer watches the Data Array to see if we need to send an ack.

DA element Accepted 1st – ack all 2nd - ack A primary abnormal state 3rd – ack F Fire alarm 4th – ack P Priority 2 5th – ack S Supervisory 6th – ack T Trouble 7th – ack C Control Set the array element to 1 to initiate the command. The FieldServer clears the value on completion.

WRBC Do not specify c-p-s in the Map Descriptor.

This command allows the user to acknowledge a single point. The specified Data Array is inspected and the value of the single element is used to determine which device state's are ack'd. Refer to Appendix A.4

WRBC Specify c-p-s in the Map Descriptor.

RDBC Specify c-p-s in the Map Descriptor.

Clist This command returns the current point status for one point. Refer to Appendix A.4 and Appendix A.20

This function obtains earth/ground status information from the panel. Two Data Array elements are used to store the normal (=1) or abnormal (=2) for each card. The first element is for the positive ground and the second element is the negative ground. Where cards do not report both, the first element of the pair is used. The array position is obtained by multiplying the card number by two and adding the offset specified in the Map Descriptor. Set the length of this Map Descriptor to twice the value of the maximum card number.

RDBC Do not specify c-p-s in the Map Descriptor.

4 This driver function used the Simplex ‘CSHOW c-p-s CVAL’ command. It is only supported by panels with firmware revision numbers greater than 10

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 4 more labels / short text on this page
Keyword Description Function · Ackall · Ack · Earths4
Page 21 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 21 · click to enlarge
Page 21

Stores analog value(s) read from a particular devicewithout scaling or units. When more than one value is reported the driver stores the values in consecutive array elements. Ensure that the Map Descriptor’s usage of the Data Arrays is spaced appropriately.

RDBC Specify c-p-s in the Map Descriptor.

Each type of Simplex device reports a different set of attributes and attribute states/values. Refer to Appendix A.8 for more information. The driver analyses the response from the poll. When an attribute is recognized, the attribute state is evaluated. If this is recognized then the driver stores a value, corresponding to the attribute state, at an array location corresponding to the attribute. 4.4 provides additional information. The driver can only recognize attributes and attribute states that it is programmed to recognize. Using the information provided in Appendix A.8, set the length of the Map Descriptor equal to array position of highest attribute. Ensure that Map Descriptors using this function do not use overlapping areas of the Data Arrays. See example in Appendix A.19.

RDBC Specify c-p-s in the Map Descriptor.

This command allows the user to manipulate the status and/or priority of a control point The port access level must be set appropriately in the Simplex device otherwise the device returns an error.

WRBC Specify c-p-s in the Map Descriptor.

  • This command allows the user to:
  • Manipulate the status and/or priority of a control point
  • Modify the value of an analog pseudo point.
  • Set the sensitivity of a TrueAlarm sensor
  • Set the rate-of-rise threshold of a TrueAlarm heat sensor
  • Select the audio channel of a speaker circuit

WRBC Specify c-p-s in the Map Descriptor.

Point Status Change. This is an unsolicited message sent automatically by a Simplex device to report a change in point status. The card-point-sub is used to calculate an offset into the associated Data Array. Read Appendix A.4 to understand this better. The state being reported determines the value being written into the Data Array. Read Appendix A.5 to understand this better.

Passive Specify c-p-s in the Map Descriptor.

Disable Not Implemented Restart Not Implemented

This command sets and displays the time and date in "user" format. As a command it sets the hour minute second of the Simplex device by getting the values from the Data Array associated with the Map Descriptor. The first element contains the hour, the second the minute and the third contains the second. A 24 hour clock is assumed. As a query, the data is unpacked into the Data Array in the same format as described above.

RDBC (Query) or WRBC (Set) Do not specify c-p-s in the Map Descriptor.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 7 more labels / short text on this page
Keyword Description Function · Value · Show · Setd · Seta · Xpoint · Time
Page 22 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 22 · click to enlarge
Page 22

As a command it sets the hour minute second of the Simplex device by getting the values from the Data Array associated with the Map Descriptor. The first element contains the hour, the second the minute, the third element contains the second, the 4th contains the day of the week, the 5th contains the month, the 6th contains the day of the month and the 7th element of the array contains the year (value 01 indicates 2001). A 24 hour clock is assumed. As a query, the data is unpacked into the Data Array in the same format as described above.

RDBC (Query) or WRBC (Set) Do not specify c-p-s in the Map Descriptor.

Used to send a silence signal to the Simplex device. This is a triggered command. When the element in the Data Array associated with the Map Descriptor is set to 1 then the command is sent to the Simplex device. The driver will set the value to zero when the command has been acknowledged.

WRBC Do not specify c-p-s in the Map Descriptor.

Used to send a reset signal to the Simplex device. This is a triggered command. When the element in the Data Array associated with the Map Descriptor is set to 1 then the command is sent to the Simplex device. The driver will set the value to zero when the command has been acknowledged.

WRBC Do not specify c-p-s in the Map Descriptor.

Used to request revision information from the Simplex panel. Use of this Map Descriptor is recommended as it allows the driver to generate a warning if an unknown Simplex revision is encountered. Make sure that the length of the Map Descriptor is sufficient to store all the revision information. A Length of 200 is recommended.

RDBC Do not specify c-p-s in the Map Descriptor.

Passive Do not specify c-p-s in the Map Descriptor. If using RUINET to monitor the FieldServer, display the Data Array associated with this Map Descriptor in ‘String’ format so that you can read the error message easily. The driver appends information about the Map Descriptor which generated the error to make the error more easily understandable.

Use this keyword to define a Map Descriptor which tells the driver where to store error messages received from the Simplex device. The most recent message is stored in the Data Array specified. Make sure that the Data Array length is long enough to store enough meaningful information. A length of 200 is recommended.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 6 more labels / short text on this page
Keyword Description Function · Ctime · Silence · Reset · Revision · Errors
Page 23 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 23 · click to enlarge
Page 23

Map Descriptor’s which use this function do two things; Firstly, they register a c-p-s with the driver. Secondly they define a Data Array name and element range that must be set to zero when the ClearAll function is activated. Up to 4 c-p-s’s may be registered per FieldServer. These registered points are monitored each time a Clist response is obtained as well as each time the panel sends an unsolicited Xpoint message with a state change. If one of these messages reports a ‘U1’ state for a registered point then the driver processes all ‘ClearAll’ Map Descriptor’s and sets all the associated array values to zero. An example of the use of ClearAll is provided in section 6.12 example 9.

Passive Specify c-p-s in the Map Descriptor (but read the notes on the left)

Warm_Start Generates a warm restart message. Used to test the driver.

Used for simulation only.

Cold_Start Generates a cold restart message. Used to test the driver. Used for simulation only.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Keyword Description Function · ClearAll

Page 24 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 24 · click to enlarge
Page 24

Appendix A.2.1. Sim4100_Card Keyword

The FieldServer will accept any positive integer number including zero; however, not all values are valid for Simplex devices. Refer to Note (1). Many commands and output message contain system point ID fields. These fields reflect the way a 4100 point (local, external, real, pseudo), is referred to. There are two basic formats allowed, address format , and symbolic format . In the Simplex device the terminal ADDRESS flag is set (DEFAULT) so that is always used in computer messages; otherwise, the symbolic form is used. The FieldServer cannot work with symbolic (spoint) addresses.

Appendix A.2.2.

Format -- Legend: 4100 card, pseudos included, See note (1) 4100 point (sometimes slot), See note (2) 4100 sub-point (sometime point), See note (2) Examples: 0-6-6 Master trouble point (LCD trouble) 5-0-1 Typical card status point, card at address 5 3-1-0 Point 1 for card at address 3

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 24)
Fig. 19 · Driver Manual (Supplement to the FieldServer Instruc…

Notes: (1) The following ranges are valid for Simplex Devices: Card address Card type 0-119 Physical (Hardware) cards 128-143 Digital Pseudo cards 144-159 Analog Pseudo cards 160-175 List Pseudo cards (2) The range of point and sub-point fields for point addressing is very sparse and depends on the type of card at that location. Contact Simplex Time Company for details on point address ranges for specific cards.

Appendix A.2.3. Sim4100_Point Keyword

The FieldServer will accept any positive integer number including zero; however, not all the values are valid for Simplex devices - see Sections 6.3 and 6.4 for further information.

Appendix A.2.4. Sim4100_sub Keyword

The FieldServer will accept any positive integer number including zero; however, not all the values are valid for Simplex devices - see Sections 6.3 and 6.4 for further information.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 25 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 25 · click to enlarge
Page 25

Appendix A.3. How to use Data Arrays to map to/from Card-Point-Sub

Some commands derive a card-point-sub address by inspecting a FieldServer Data Array. Others receive data from a device with a card-point-sub address and modify the data in an array based on the card-point-sub address. This section explains how to make the connection between an index into a Data Array and a card-point-sub address. In a simple world the Data Array index would be Index = card * max point per card * max sub point per point + point * max sub point per point + sub Where max point per card and max sub point per point could be large numbers. As you can imagine this would require huge sparse Data Arrays. To reduce the Data Array size the FieldServer uses a mapping algorithm which can be optimized based on the addresses of the Simplex devices. The map is manipulated by using the sim4100_card/point/sub parameter values. Example: Consider the following Map Descriptor fragment. … , sim4100_func, sim4100_card, sim4100_point, sim4100_sub, data_array_offset Xpoint, 10, 5, 10, 0 If data is received for point -- = 9-0-0 This data will NOT be processed because the card number does not match the value of the sim4100-card If data is received for point -- = 10-20-0, however, the data will be processed. The array location is derived using the following formula (sim4100_sub is to be read as the “number of sub-points per point”; sim4100_card’s value will be ignored.) Location = data_array_offset + * sim4100_sub + = 0 + 20 * 10 + 0 = 200

Appendix A.4. Simplex Point Status Data Format

When a point status is obtained the FieldServer will write one byte of data to a Data Array. The byte will contain the following information. Because each point can report a number it only makes sense to use Data Arrays that are not bit arrays.

Bit Identifier Description 0 (First Bit) F Fire Alarm 1 P Priority 2 2 S Supervisory 3 T Trouble 4 U Utility 5 C Control 6 D Disable 7 A Primary state (based on point type - F if smoke detector, C if signal circuit, etc.)

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 25)
Fig. 20 · Driver Manual (Supplement to the FieldServer Instruc…

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

addresses

Page 26 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 26 · click to enlarge
Page 26

Appendix A.5. Simulation of the Xpoint command

The following notes apply only to FieldServer Technologies engineers. The sim4100_func=xpoint keyword is used to parse unsolicited point status change messages sent by Simplex devices. For simulation purposes it a wrbc version of this function has been implemented to test the response parsing ability of the slave portion of the driver.

Appendix A.6. Application Supervision Messages

  • Section 7.2 of the Simplex 4100 protocol describes unsolicited messages from a Simplex device. This sim4100_func=super wrbc command is used to test the driver's ability to parse these messages. The 4100 protocol supports a periodic application supervision message. This supervision poll is performed if the TERMINAL flag POLL is set (COMPUTER DEFAULT). The objective of the supervision poll is two-fold:
  • It is the only periodic message that can be expected to be sent by the 4100, thus establishing the basis for supervising the line.
  • To ensure that all layers of the two systems are operating properly and able to respond to messages. For example, in a PC implementation that uses a Terminate-and-StayResident (TSR) device driver to implement the protocol, the answer to the supervision poll should be done in a way such that if the program exits to DOS, the TSR will not continue to indicate to the 4100 that everything is OK, when in fact, the PC will not be able to annunciate an alarm.

Appendix A.7. Driver Stats

Appendix A.7.1. How the Driver counts bytes and messages received and transmitted.

"Ack" messages sent/received by the driver in response to read/write messages are NOT counted as messages. However, the single byte produced by these messages is included in the byte count. The driver does not count DLL layer messages as messages. The driver counts bytes at the DLL layer. The byte count includes the bytes that wrap application layer messages, acks and the port supervision and responses messages. The driver counts messages at the application layer.. This means that if you use RUINET to monitor the FieldServer and you view the Map Descriptor’s the byte count stats will always be zero. Some Map Descriptors require data in the Data Arrays to trigger a write command. An example is the "Ack" command. The driver does not count one of these messages as being sent until the array actually triggers a poll to be sent.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 27 of the FieldServer FS-8700-41 user manual — Driver Manual (Supplement to the FieldServer Instruction Manual)
Page 27 · click to enlarge
Page 27

Appendix A.7.2. Driver Exposed Stats

The driver is capable of exposing statistics about its behavior in a Data Array. It is necessary to create a Data Array with name sim4100-stats as per the example below and it will be updated by the driver. Note that the stat number corresponds to the offset. Take care not to poke any values into the 1st 10 elements of this Data Array (offsets 0 to 9). Doing so will trigger internal diagnostics and may interfere with normal operation. A different set of stats is maintained for each connection. Each connection uses 100 elements of the data array. Ensure the array length is large enough if the port number is large.

Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length sim4100-stats , UINT16 , 1000 At revision 1.07a of the driver and before, no stats had been exposed.

FieldServer FS-8700-41 — Driver Manual (Supplement to the FieldServer Instruction Manual) diagram (page 27)
Fig. 21 · Driver Manual (Supplement to the FieldServer Instruc…

10 SIM4100_STAT_XPOINT_CARD The Card in c-p-s from most recent xpoint store

11 SIM4100_STAT_XPOINT_POINT The Point in c-p-s from most recent xpoint store

12 SIM4100_STAT_XPOINT_SUB The SubPoint in c-p-s from most recent xpoint store

13 SIM4100_STAT_XPOINT_QUALIFIER The Qualifier from most recent xpoint store

The Qualifier from most recent xpoint store, stored as an enumeration – See Note1 for bit states

The reported state from most recent xpoint store. State value: 0 FALSE/Normal 1 TRUE/Abnormal

The reported ack state from most recent xpoint store. Ack state: *=needs ack, -=acked (always "-" for U or C states)

17 SIM4100_STAT_XPOINT_HOUR The Time from most recent xpoint store

18 SIM4100_STAT_XPOINT_MIN The Time from most recent xpoint store

19 SIM4100_STAT_XPOINT_SEC The Time from most recent xpoint store

20 SIM4100_STAT_XPOINT_DOW The Date from most recent xpoint store

21 SIM4100_STAT_XPOINT_DAY The Date from most recent xpoint store

22 SIM4100_STAT_XPOINT_MONTH The Date from most recent xpoint store

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 28 of the FieldServer FS-8700-41 user manual — 25 SIM4100_STAT_XPOINT_COMBO_STATE_NEW
Page 28 · click to enlarge
Page 28

Stat number Stats Description

23 SIM4100_STAT_XPOINT_YEAR The Date from most recent xpoint store

A single point could potentially be active in more than one state simultaneously. The driver tracks the combine state by building a UINT whose bits indicate the state. This is the combo state before the update. See Note 1 for bit states.

24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD

A single point could potentially be active in more than one state simultaneously. The driver tracks the combine state by building a UINT whose bits indicate the state. This is the combo state after the update. See Note 1 for bit states. Note 1 – Bit States. Qualifier: Enum=0 Qual=F Fire alarm state Enum=1 Qual=P Priority 2 alarm state Enum=2 Qual=T Trouble state Enum=3 Qual=S Supervisory state Enum=4 Qual=U Utility monitor, digital/analog pseudo state Enum=5 Qual=C Control state (non pseudo) Enum=6 Qual=D Disable Trouble state

25 SIM4100_STAT_XPOINT_COMBO_STATE_NEW

Appendix A.8. SHOW Function Attributes and Attribute States

  • The Show command provides an ASCII response formatted for printing. The driver parses these messages and converts the data to numbers which can be sent to upstream devices using another protocol. The driver performs the following tasks in analyzing the response.
  • On a line by line basis from the left, it searches for an attribute against a table of attribute strings. If an attribute string is found in the line then processing continues. Otherwise the line is discarded.
  • The attribute number is recorded. It will be used to determine the array location where the attribute state/value will be stored.
  • The attribute also determines the state/value extraction method and attempts to determine the attribute state/value using the appropriate method.
o Method 1The driver uses a table of attribute states, comparing them to the

remainder of the line. If there is a match the driver stores the value of the attribute state in the array location determined by the attribute, o Method 2: The driver looks for (up to three) analog values separated by forward

slashes. o Method 3: The driver looks for analog values preceded by an equal sign.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 29 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 29 · click to enlarge
Page 29
  • The driver stores in the first array location the number of response lines which resulted in attribute data being stored. This information can be used for trouble shooting. The following table reports the attributes that the driver recognizes. This list may be extended by changing the configuration. If, for example, the attribute ‘ENABLED STATE’ is recognized then the state of this attribute will be stored at array location 6.

Attribute Array Position Method Not Defined 0 1 PRIMARY STATUS 1 1 PHYSICAL STATE 2 1 RAW STATE 3 1 ACTIVE STATE 4 1 ARMED STATE 5 1 ENABLED STATE 6 1 UNVERIFIED 7 2 CURRENT DEVICE 8 1 DEVICE 9 1 TEST STATE 10 1 PRESENT SENSITIVITY SELECTED= 11 2 PRESENT SENSITIVITY SELECTED = 11 2 AVERAGE VALUE = 14 3 AVERAGE VALUE= 14 3 AVERAGE = 14 2 AVERAGE= 14 2 AVERAGE 14 2 VALUE = 17 2 VALUE= 17 2 PEAK= 20 2 PEAK = 20 2 TROUBLE THRESHOLD 23 1 OUTPUT STATE 24 1 OUTPUT STATUS 25 1 DETECTOR SOUNDER 26 1 ALARM TEMPERATURE SELECTED= 27 2 DETECTOR RELAY 30 1 TOTAL NUMBER OF TROUBLES 31 2 NODE MISSING 32 1 VERSION CONTROL 33 1 NODE INITIALIZATION IN PROGRESS 34 1 SIMPLEX SERVICE MODE 35 1 EARTH GROUND 36 1 AC POWER 37 1 BATTERY LOW/DISCHARGED 38 1 BATTERY CHARGE 39 1 SYSTEM PSEUDO STATUS 40 1 NETWORK CARD STATUS 41 1 CARD TROUBLE STATUS 42 1 MISCELLANEOUS STATUS 43 1 RELAY STATUS 44 1 PRIORITY 45 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 30 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 30 · click to enlarge
Page 30

Attribute Array Position Method CONTROL STATUS 46 1 CURRENT (AMPS) 47 2 CARD MISSING/FAILED 48 1 CORRECT CARD 49 1 RS-232 Interface PORT A 40 1 RS-232 Interface PORT B 41 1 2120/RS-232 PORT Broadcast Fail 42 1 CARD MISSING/FAILED 43 1

The table below reports the attribute states recognized for attribute method=1.

Attribute State Value Attribute State Value AUTOMATIC CONTROL 1 ARMED 10 OUTPUT NORMAL 2 ENABLED 11 SELF TEST NORMAL 3 ON-LINE 12 CORRECT DEVICE 4 ENABLED 13 PRIORITY 15 5 NORMAL 14 RANGE NORMAL 6 TROUBLE 15 ALARM 7 OFF 16 SHORT 8 ON 17 SHORT 9 0

Examples: PHYSICAL STATE SHORT Driver recognizes ‘Physical State’ as attribute 2 and uses method 1 to evaluate the rest of the line. Driver recognizes ‘Short’ as attribute state with value 8. Therefore, the driver stores the number 8 at location 2 in the Data Array. VALUE=77 / 0% OF ALARM / 1.0% SMOKE Driver recognizes ‘VALUE=’ as attribute 17 and uses method 2 to evaluate the rest of the line. Driver stores three values; 77, 0 and 1.0 in three consecutive locations starting at location 17. Note that there is a gap between attribute 17 and the next attribute in the table sufficient for storing up to 3 values. Note that a slash separates the three values. AVERAGE VALUE=75 / ALARM LEVEL=145 Driver recognizes ‘AVERAGE VALUE’ as attribute 14 and uses method 3 to evaluate the rest of the line. Driver stores two values; 75 and 145 in two consecutive locations starting at location 14. Note that an equal sign ‘=’ precedes each numeric value.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 31 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 31 · click to enlarge
Page 31

Appendix A.8.1. Extending the List of Show Attributes

You can extend the list of attributes and attribute states that the driver recognizes by modifying the configuration CSV file. The following example adds three attributes and 4 attribute states. If a device reports an attribute of ‘LIGHT STATE’ as ‘BRIGHT’ then the driver will load array element 32 with the value 41.

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 31)
Fig. 22

Use a digit. The three methods are described above.

Keyword starts a new section of the CSV file.

Attribute Definitions. The name will be stripped of all spaces between the last character and the comma

When allocating offsets, be mindful of the offsets already used.

Driver_Table sim4100_Attr_Name, sim4100_Attr_Offset, sim4100_Attr_Method, protocol BROKEN , 30 , 1 , sim4100 FIXED , 31 , 1 , sim4100 LIGHT STATE , 32 , 1 , sim4100 Driver_Table sim4100_Attr_State_Name, sim4100_Attr_State_value, protocol DIM , 40 , sim4100 BRIGHT , 41 , sim4100

Use values that are not allocated to the pre-defined list of states.

Appendix A.9. Synchronizing the FieldServer with the Panel

When using the Xpoint function to store point states, each time the panel does a warm-start it sets all point states to normal and then starts evaluating every single one. Thus, after a warm start, the FieldServer will receive Xpoint messages from the panel for every point not in a normal state. This provides one synchronization method. The limitation of this method is that the Simplex panels do not report when a point’s state changes back to normal. Thus to maintain the synchronization the upstream device must clear the point to zero once it has read its abnormal state, i.e. The upstream device should consider the data reported by the Xpoint function as latched data. A second method is to connect/reset the FieldServer when there are no points in an abnormal state. A third method is poll point states using the Clist function as described in Appendix A.20. This way the FieldServer states will always be updated. Polling is slow and in a system with many points it is possible that it may take several minutes to update status information for all points. Thus combining this method with the use of Xpoint Map Descriptors gives the best of both worlds. When a point changes to ‘not’ normal, then the FieldServer gets the state change from the Xpoint function immediately and at the same time synchronization is assured by the continuous polling.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 32 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 32 · click to enlarge
Page 32

A fourth method is provided too. This method allows a range of a data array to be set to zero when a user specified point reports a normal state. Refer to Appendix A.17 for more information.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 33 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 33 · click to enlarge
Page 33

If an error response is received from the panel then if a Map Descriptor similar to this one is defined, the driver will store the error

It is best to define the DA_ERRORS array as format BYTE and if you use RUINET to monitor this Data Array change the display

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 33)
Fig. 23
FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 33)
Fig. 24

message (and some information about the Map Descriptor that caused the error) in the Data Array DA_ERRORS.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Appendix A.11. Advanced Map Descriptor Example 2. - Read Panel Time

format to string so that you can read the error. Refer also to Appendix B.1.

Appendix A.10. Advanced Map Descriptor Example 1 - Errors

Page 34 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 34 · click to enlarge
Page 34

Use Ctime to set the panel time and date and use Time just to set the hour minute and seconds. If the hour is zero then the driver

It is best to define tie DA_REV_INFO array as format BYTE and if you use RUINET to monitor this Data Array change the display

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 34)
Fig. 25

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, Scan_Interval, Length

Time_Mapdesc, DA_TIME, 0, wrbc, Node_A, CTime,, 30s, 7 Time_Mapdesc, DA_TIME, 0, wrbc, Node_A, Time,, 30s, 7

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Appendix A.13. Advanced Map Descriptor Example 4 - Panel Revision Information

Appendix A.12. Advanced Map Descriptor Example 3 - Write Panel Time

format to string so that you can read the information

does not send a write message to the panel.

Page 35 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 35 · click to enlarge
Page 35

This example illustrates the use of the ‘AckAll’ function. Each time the driver uses this Map Descriptor, it checks the data in the Data

Array. If one location is non-zero then the appropriate ack message is sent to the panel. As the function is wrbx, the message is only

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 35)
Fig. 26

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, Scan_Interval, Length

AckAll_Mapdesc, DA_ACKALL, 0, wrbx, Node_A, AckAll, 1.0s, 6

Silence_Mapdesc, DA_TRIGGERS, 0, Wrbx, Node_A, Silence, 1.0s, 6 Reset_Mapdesc, DA_TRIGGERS, 1, Wrbx, Node_A Reset, 1.0s 6

Driver’s set the trigger back to zero once the

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Set the array element to 1 to initiate the command. The FieldServer clears the value on completion

Appendix A.15. Advanced Map Descriptor Example 6 - Silence / Reset

Appendix A.14. Advanced Map Descriptor Example 5 - AckAll

As the function is wrbx, the message is only sent when the value is updated.

2nd – ack A Primary Abnormal State

The 1st element of the Data Array is used to trigger the ack all

5th – ack S Supervisory

3rd – ack F Fire alarm

4th – ack P Priority 2

6th – ack T Trouble

sent when the value is updated.

received.

Page 36 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 36 · click to enlarge
Page 36

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval sim4100_Func Sim4100_Card, Sim4100_Point, Sim4100_Sub Length

The ackall function can be used to ack all points or all points that are in a particular state. What about if you wish to send an ack

message for a single point. One Map Descriptor is required for each c-p-s combination you require specific acknowledgements for.

The driver checks the array location corresponding to the Map Descriptor. If the value is non-zero then an ack message is sent. The

Ack_mapdesc1, DA_ACK, 0, Wrbx, Node_A, 1, 1.0s, Ack, 1, 2, 3, 1 Ack_Mapdesc2, DA_ACK, 1, wrbx, Node_A, 1, 1.0s, Ack, 1, 2, 4, 1

value is used to determine what kind of ack is sent. As the function is wrbx, the message is only sent when the value is updated.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Appendix A.16. Advanced Map Descriptor Example 7 - Acknowledge a specific point

Bit 1P - Priority 2 alarm state
Bit 6D - Disable Trouble State
Bit 3S - Supervisory State
Bit 0F - Fire Alarm Panel
Bit 2T - Trouble State
Bit 4U - Utility Monitor
Bit 7A - Primary Point
Bit 5C - Control State
Page 37 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 37 · click to enlarge
Page 37

normal state you may require a way of synchronizing the FieldServer data to the Panel when everything is normal. This function is

The idea behind this function assumes that there is some point(s) which when they report a state of U1 trigger the driver to clear

When you create Map Descriptor’s with the ClearAll function the driver makes a note of the c-p-s. If an Xpoint message is received

from the Panel for the specified c-p-s or you use clist to poll for the state of the c-p-s and the state is U1 then this triggers this

ClearAll action. When the action is triggered the driver sets all array point covered by all Map Descriptor’s with the clearall function to

As the Xpoint messages (unsolicited message from the panel reporting c-p-s status changes) only report when a c-p-s goes to a non-

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 37)
Fig. 27

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, sim4100_card, sim4100_point, sim4100_Sub, Length

FieldServer FS-8700-41 — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD diagram (page 37)
Fig. 28

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, sim4100_card, sim4100_point, sim4100_Sub, Length

Clear_Mapdesc1, DA_AI, 0, passive, Node_A, ClearAll, 1, 2, 3, 100 Clear_Mapdesc1, DA_2, 50, passive, Node_A, ClearAll, 1, 2, 3, 50

Clear_Mapdesc1, DA_I, 0, passive, Node_A, Ack, 1, 2, 3, 100 Clear_Mapdesc1, DA_2, 0, passive, Node_A, Ack, 1, 2, 3, 100

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

If 1-2-3 or 1-2-4 go to state U1 then

provided as an aid. Typically it is used in conjunction with a pseudo-point programmed into your panel.

Appendix A.17. Advanced Map Descriptor Example 8 - ClearAll

zero, without consideration of the c-p-s associated with the Map Descriptor.

sections of one or more Data Arrays.

Page 38 of the FieldServer FS-8700-41 user manual — 24 SIM4100_STAT_XPOINT_COMBO_STATE_OLD
Page 38 · click to enlarge
Page 38

You can only use this function if the panel firmware version is greater than or equal to revision 10.0. This function uses reads earth /

If, for example, card 3 reports information then the driver uses array elements 6 & 7 to store information for this card. Obtain the

If the card reports positive and negative earth data then the driver stores the positive earth data at location 6 and the negative earth

If the card reports earth / ground state information without the keywords ‘Positive’ or ‘Negative’ the driver stores the data at location

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval sim4100_Func Sim4100_Card

Earth_mapdesc1, DA_EARTHS, 0, rdbc, Node_A, 20, 1.0s, Earths, 1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

The driver stores a value of 1 to report normal and a value of 2 to report abnormal.

Appendix A.18. Advanced Map Descriptor Example 9 - Earths

array location by multiplying the card number by two.

ground status information from the panel.

data at location 7.

Page 39 of the FieldServer FS-8700-41 user manual — DEVICE ADDRESS: 7-10-2 TYPE: COMBO
Page 39 · click to enlarge
Page 39

One Map Descriptor is required for each point whose attributes you wish to ‘show’. The show function reads data that describes the

attributes and the state of each attribute for a single device. Every type of device has a different set of attributes. When the response

is received by the driver, it fills a number of Data Array locations with numeric values that represent the attributes and their states.

The driver will load the array DA_SHOW starting at offset zero for up to 100 elements. Using the following tables we determine what

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval sim4100_Func Sim4100_Card, Sim4100_Point, Sim4100_Sub

Show_mapdesc1, DA_SHOW, 0, rdbc, Node_A, 100, 1.0s, Show, 1, 2, 3

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

By way of example assume that point 1-2-3 is a Heat Detector and the response to the show query is as follows

You should reserve at least 100 array locations for each Map Descriptor by setting the length to 100.

UNVERIFIED 0

Appendix A.19. Advanced Map Descriptor Example 10 - Show

40 Character Custom Label Mx-y-2 HEAT DETECTOR

DEVICE ADDRESS: 7-10-2 TYPE: COMBO

PRIMARY STATUS NORMAL

CURRENT DEVICE CORRECT DEVICE

DEVICE ON_LINE

TEST STATE SELF TEST NORMAL

TROUBLE THRESHOLD RANGE NORMAL

ENABLED STATE ENABLED

ALARM TEMPERATURE SELECTED= 135 DEG F

UNIT NUMBER: 0 RUI NUMBER: LOCAL

LOCAL UNIT – MAIN PANEL

IDNET INTERFACE CARD

VALUE=0 / -41 DEG F

PEAK=0 / -41 DEG F

values you can expect for this response.

Page 40 of the FieldServer FS-8700-41 user manual — 24 OUTPUT STATE
Page 40 · click to enlarge
Page 40

Array Position Attribute Value Filled In5 Note

0 Not Defined 10 1 !

1 PRIMARY STATUS 14 (Normal) 1 #

2 PHYSICAL STATE ~

3 RAW STATE

4 ACTIVE STATE

5 ARMED STATE

6 ENABLED STATE 11 (Enabled) 1

7 UNVERIFIED 0 1

8 CURRENT DEVICE 4 (Correct Device) 1

9 DEVICE 12 (On_Line) 1

10 TEST STATE 3 (Self test normal) 1

11 PRESENT SENSITIVITY SELECTED

14 AVERAGE

17 VALUE 0 1

20 PEAK 0 1

23 TROUBLE THRESHOLD 6 (Range Normal) 1

24 OUTPUT STATE

25 OUTPUT STATUS

26 DETECTOR SOUNDER

27 ALARM TEMPERATURE SELECTED= 135 1

30 DETECTOR RELAY Notes: ! The value 10 represents the count of the number of attributes that were extracted from the response. It is not equal to the number of array locations filled in because some attributes (e.g. Value) result in more than one array location being updated. ~ The un-filled-in locations are not updated by the driver when this response is analysed because the attributes corresponding to these locations were not reported in the response to the query. * Room for up two three numbers for attributes like value, peak but in this case only two values are relevant for this device.

5 Locations marked with a 1 are updated when the driver analyses this response

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Show 4 more labels / short text on this page
18 -41 1 · 19 * · 21 -41 1 · 22 *
Page 41 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 41 · click to enlarge
Page 41

Appendix A.20. Using Clist to Write-Through and Store point status from

From version 1.05 on the functionality of the ‘clist’ Map Descriptor’s has been enhanced.

  • The ‘Clist’ Map Descriptors can
  • Read a point’s status
  • Write to a point when a Write-Through is activated
  • Store the point status when an ‘xpoint’ unsolicited message is received from the panel.

A Write-Through occurs when a Data Array value that is normally updated by a read (rdbc) Map Descriptor is updated by some other driver or by using the Ruinet application.

  • In this case the updated value is written through the read Map Descriptor and the Simplex 4100 driver writes the updated value to the panel. The value is written once only each time that the Data Array element is updated except when the value is updated by the response to the read or if the point status is updated when an unsolicited message is received from the panel. Ensure that:
  • The point is not a read only point
  • The Panel’s access level has been set appropriately. When an unsolicited message is received from the panel it would normally be stored using a Map Descriptor with the ‘xpoint’ function. (See section 4.5.6) However, if you are polling for the status of that point using a ‘Clist’ Map Descriptor and if that Map Descriptor has ‘Store_Unsolicited’ set to yes then you must omit the ‘xpoint’ Map Descriptor as the ‘Clist’ Map Descriptor can be used to store the point status when it is updated with an unsolicited message. If you have both Map Descriptor’s defined then the result will be unpredictable. A write command can be sent to a Simplex panel in one of two formats:
1. SET c-p-s ON/OFF (default) 2) SET c-p-s value Use the sim4100_WriteThru parameter in the CSV to change to the 2nd format. Even if you are writing to an analog pseudo point using format 1 is suitable because by enabling the point you force it to take its intrinsic value. By setting the point off you are setting its value to zero.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Unsolicited Messages

Page 42 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 42 · click to enlarge
Page 42

Appendix B. Troubleshooting Tips

Appendix B.1. Address Errors

  • If the driver produces BAD_ADDRESS stats then do the following
  • Read the notes on processing errors. You can see the last error response and a report of the MD's which received the error response in the error array.
  • Alternatively, take a log, open the ASCII version of the log and look for error messages. Error 2 is the response sent by the panel when it is polled for a point that doesn’t exist. Find the Error #2's n the log. Now look at the line which precedes the error. It is the poll. Look to see which point in being polled. Now you know the c-p-s of the invalid point, edit the configuration and remove the MD which polls for data at that point. When you have finished editing the configuration, download the modified file and reset the FS for the changes to take effect.

Appendix B.2. Driver Limitations

  • Other than being able to write through a Map Descriptor where the sim4100_func=’clist’ , write throughs are not supported by this driver.
  • Port expansion is not supported.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 43 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 43 · click to enlarge
Page 43

Appendix B.3. Resolving Network Addresses above 255

The Standard format for addressing a simplex point is c-p-s (Card-Point-Subpoint). Each of these components in the address supports a maximum value of 255. However, when using an NDU (Network Display Unit), addresses may be supplied in a Card-Address format where the address value could be substantially larger than 255. In these applications it will be necessary to convert the Card-Address format into c-p-s format before configuring the points in the FieldServer. The formula used to convert between the two formats is as follows: Card is the same for both formats. Network Address = ((Point-1)*256) + Sub-Point + 1 This conversion procedure is best illustrated by means of an example: Example: Card–Address point supplied = 5-2936 From this we deduce the card number to be 5. The next step is to break the address into multiples of 256 in order to determine point and sub-point. Since this is also a hex denominated calculation, an easy way to do this is to convert the value to Hex: 2936 = 0xB78 Now, break out the last two hex numbers for sub-point portion, and use the rest for point address. So we get: 0xB = 11 = (Point-1) 0x78 = 120 = Sub-Point + 1 Solving this equation, we get: Point = 12 Sub-Point = 119

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 44 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 44 · click to enlarge
Page 44

Appendix C. Error Messages

Error Message Troubleshooting Tip

The card-point-sub is being used to derive an array offset. The calculation requires division by the point & the sub and one or both of these values are zero. Sim4100:#2 RTS has been asserted for too long. Extend timer, check cable uses RTS/CTS or reconfig 4100 device to suppress hardware handshaking

Sim4100:#1 invalid for ack. Read manual.

If RTS-CTS handshaking has been used then this message is produced if the driver finds that the RTS has been asserted by the slave device for too long. The timeout is hard coded at 2.0s. Sim4100:#3 sim4100_chan_init() Init with null chan. Requires support from FieldServer Technologies.

The driver has found a value for a sim4100_func keyword that it does not recognize. Check the CSV file and read Appendix A.2 of this manual for a list of legal keywords.

Sim4100:#4 Unknown sim4100_func in csv

The sim4100_func keyword has been assigned the value 'ack' but a card-point-sub has not been specified. It would be better to use the ackall function instead. Sim4100:#6 ack/ackall/seta/setd must be a write.

Sim4100:#5 Use Ackall function.

You cannot use the rdbc function with these keywords. Use a wrbc instead.

You cannot use these keywords at the present time. If you require one of these functions implemented call FieldServer Technologies. Sim4100:#8 Func=Clistall/Clist, wrbc not allowed These keywords must be used with a rdbc instead.

Sim4100:#7 disable/restart/list not implemented

Sim4100:#9 Write ack was not expected.

Please report this error to FieldServer Technologies. Sim4100:#10 Invalid point status =(Hex)

Please report his message to FieldServer Technologies noting the values in braces.

Sim4100:#11. Error. Array too short. rqd= %d( max= %d) act= %d. MapDesc= Data Abandoned! Subsequent msgs suppressed!

Check the CSV file Data Array lengths.

Sim4100:#12 Error. Incoming data is being abandoned.

Subsequent message supressed! Check the CSV file; there was no matching Map Descriptor for a message. Sim4100:#13 FYI. Login Function not Implemented.

Please contact FieldServer Technologies if you would like this feature implemented.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 45 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 45 · click to enlarge
Page 45

Error Message Troubleshooting Tip

A write thru is defined as follows. The FieldServer reads data from a device and stores it in a Data Array. If a remote device changes the value in that Data Array, the FieldServer will write the new value to the device that is being read. This driver does not permit write thru's except when the data is being updated using CLIST. Refer also to Sections 4.5.4, 4.5.6 and Appendix A.20. In versions of the driver up to and including 1.07a a panic is produced when this message is printed. The message is printed to a maximum of 10 times and then suppressed. SIM4100:#15 FYI. Incoming abandoned. No Map Desc.

Sim4100:#14 MD=%s Addr=%d

Check the CSV file; there was no matching Map Descriptor for a message.

If the server can’t find a matching MD (i.e. the point being polled for doesn’t exist) then the driver responds with Simplex Error #2.

SIM4100:#16 FYI. No Map Desc. Respond with Error.

Check the driver manual and Simplex User Manuals. There is no driver response to the message received. SIM4100:#18 FYI. Incoming Abandoned. (%d)

SIM4100:#17 FYI. Incoming Abandoned. No Data.

Please report his message to FieldServer Technologies noting the values in braces.

No corrective action is required on your part. The message is printed for your information only. Message ‘a’ is printed when version 9 firmware is found in the panel. Message ‘b’ is printed when version 10 firmware is found in the panel. Message ‘b’ is printed when version 11 firmware is found in the panel.

Sim4100:#19a FYI. Sim4100 Firmware found (%.2f)

The firmware version found is not one that the driver explicitly supports. This does not mean the driver will not work but if a feature of the driver isn’t working correctly knowing that the firmware version is not supported may help diagnose the problem more easily. No corrective action is required on your part. If however, some you suspect that the driver is not operating correctly it is important that you mention seeing this message in the Error Buffer when reporting the problem.

Sim4100:#19d FYI. Panel Firmware Rev %.2f may be incompatible.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 46 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 46 · click to enlarge
Page 46

Error Message Troubleshooting Tip

The format of the firmware version information could not be interpreted correctly. This may mean that your panel has a firmware version that is not one that the driver explicitly supports. This does not mean the driver will not work but if a feature of the driver isn’t working correctly knowing that the firmware version is not supported may help diagnose the problem more easily. No corrective action is required on your part. If however, some you suspect that the driver is not operating correctly it is important that you mention seeing this message in the Error Buffer when reporting the problem. Sim4100:#20 FYI. Data abandoned! Array too short. MapDesc= Check the CSV file Data Array lengths.

Sim4100:#19e FYI. Panel Firmware may be incompatible.

Sim4100:#21. Error. Data abandoned! Array too short c-p-s= %d-%d-%d Check the CSV file Data Array lengths.

Polling is disabled until the port supervision message has been received. This message can be safely ignored. When the panel sends unsolicited messages to the FieldServer this message is printed. Polling remains inhibited until the unsolicited message stream end.

Sim4100:#22. FYI. Polling Inhibited.

When a stream of unsolicited messages is received from the Simplex panel then polling is inhibited until the stream ends. When the stream ends this message is printed. It may be safely ignored. Sim4100:#25. Error. Data abandoned! Array too short c-p-s= %d-%d-%d Check the CSV file Data Array lengths.

Sim4100:#23. FYI. Polling Enabled

Sim4100:#26 FYI. Data abandoned! Array too short.(%d) MapDesc= Check the CSV file Data Array lengths.

Sim4100:#27. FYI. Sequence Number reset requested & done.

Sim4100:#28. Error. Bad Sim4100_Func=%d in MD=

Check the CSV file and driver manual for valid Simplex functions.

Sim4100:#29. FYI. Length changed to 1 in MapDesc=

Check the CSV file for the correct Map Descriptor function type. Sim4100:#30. FYI. Length changed to 1 in MapDesc=

Check the CSV file for the correct Map Descriptor function type. Sim4100:#31. FYI. Length changed to 1 in MapDesc=

Check the CSV file for the correct Map Descriptor function type. Sim4100:#32. FYI. Sequence number semi-reset.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 47 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 47 · click to enlarge
Page 47

Error Message Troubleshooting Tip

Message sequence numbers incorrect. Check Simplex User Manuals, and driver manuals. Contact FieldServer Technologies for additional support.

Sim4100:#33. Error. Invalid Seq Number.

Message sequence number incorrect. Check Simplex User Manuals, and driver manuals. Contact FieldServer Technologies for additional support. Sim4100:#36. FYI. Bad sim4100_func=%d in MapDesc=

Sim4100:#34. Bad Seq. Sequence number reset.

Check the CSV file for the correct Simplex function type. Sim4100:#38. FYI. Bad sim4100_func=%d in MapDesc=

Check the CSV file for the correct Simplex function type.

Attribute was found, but State not found in driver table. Contact FieldServer Technologies for additional support. Sim4100:#40 FYI. Data abandoned! Array too short.(%d) Mapdesc= Check the CSV file Data Array lengths

Sim4100:#39 FYI. Data abandoned! State not recognized. Mapdesc=

Sim4100:#41 FYI. Data abandoned! Array too short.(%d) Mapdesc= Check the CSV file Data Array lengths

Sim4100:#43. Err. Can only monitor %d point(s) for ClearAll

Contact FieldServer Technologies for additional support. Sim4100:#44 FYI. ClearAll mapDesc's must be passive

Map Descriptor function has been changed automatically Sim4100:#45 FYI. User added SHOW attribute= offset=%d method=%d

Sim4100:#46 Err. No space. Driver rejects SHOW attribute= offset=%d method=%d

No space is available in internal driver table. Contact FieldServer Technologies for additional support. Sim4100:#47 Err. Duplicate. Driver rejects SHOW attribute= offset=%d method=%d

Duplicate found in internal driver table. Contact FieldServer Technologies for additional support.

Sim4100:#48 FYI. User added SHOW attr state= value=%d

Sim4100:#49 Err. No space. Driver rejects SHOW attr state= value=%d

No space is available in internal driver table. Contact FieldServer Technologies for additional support. Sim4100:#50 Err. Duplicate. Driver rejects SHOW attr state= value=%d

Duplicate found in internal driver table. Contact FieldServer Technologies for additional support.

sim4100:#51 Err. Length must be specified and > 0. Check the CSV file for the length fields.

Check the CSV file for node definitions, Simplex hardware, and connections. A device node appears to be offline. Contact FieldServer Technologies for additional support. Sim4100:#53. Md= Abandoned. Polling was inhibited.

SIM4100:#52 FYI. Incoming Abandoned. Node offline

Obsolete. Contact FieldServer Technologies for support.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 48 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 48 · click to enlarge
Page 48

Error Message Troubleshooting Tip

Sequence number checking was disabled. Check your password. Contact FieldServer Technologies for support. Sim4100:#55. Error. Bad Sim4100_Func=%d in MD=

Sim4100:#54. Err. SeqNumber check disabled.

Check the CSV file for the correct Simplex function type. Sim4100:#56 Not used.

The driver ignored Login messages. No corrective action is required. This message is printed for your information only. Sim4100:#58 FYI. You could have used an Array called to expose diagnostic info.

Sim4100:#57* Err. Cant parse Login message. Ignored.

This message is printed for your information only. It can safely be ignored. For additional information read section “Appendix A.7.2 Driver Exposed Stats”

An internal driver diagnostic has been triggered. You must report this error to FieldServer’s Technical Support.

Sim4100:#59 Err. Checkpoint. Report this to Tech Support.

Every Sim4100 Map Descriptor must be connected to a node. Ensure that the parameter ‘Node_Name’ has been specified on the Map Descriptor. To correct this problem, edit the CSV, make the correction, download the corrected CSV file and reset the FieldServer.

Sim4100:#60 Err. MapDesc=%s. No Node.

If you have a Map Descritor which has the sim4100_func parameter set to ‘earths’ or to ‘values’ then you must set the PLC_Type parameter on the node to 4100U. (See section 0 Client Side Node Descriptors ). It is only appropriate to do so if the firmware version of your panel is 10.x or later. You can create a map descriptor to read the version information if you are not sure. You can also use the menu system on the Panel to read the version number. To correct this problem, edit the CSV, make the correction, download the corrected CSV file and reset the FieldServer.

Sim4100:#61 Err. PLC_Type=4100u rqd for 'values'/'earths'

This message is printed when the input buffer overflows. This usually occurs when the panel sends lots of messages and they are not being processed by the driver fast enough. A panic is printed immediate after this message. The driver will clear the buffer and start capturing new bytes as they arrive. Messages may have been lost. We advise that you re-synch the panel. This error has only been seen once. It occurred when a panel was connected to the driver with the wrong connection settings.

Sim4100:#62 Err. Input Buffer Overflow.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 49 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 49 · click to enlarge
Page 49

Appendix D. Pseudo Points

It is beyond the scope of the driver manual to describe the full functionality of the Simplex Panels. However, we have found it useful to provide the following data to customers. The following information is not maintained and updated therefore you should use it for reference only and should always consult with the vendor of your Simplex system before implementing any project decisions or actions based on the information provided in this section. Pseudo points are points that report states or attributes based on how the Simplex system has been installed, configured and programmed. They are often programmed to groups, devices, zones or other logic groupings. For example, a pseudo point may be programmed to report if and only if more than one sensor in a particular area is reporting smoke. Every Simplex system has a number of default pseudo points programmed into the firmware supplied with the panel. These default points depend only on the firmware revision number and are generally unaffected by the configuration programmed for a particular site. Although the 4100 card number can range from 0-250 in theory, only the following ranges are presently used in the system:

Card address Card type 0-119 Physical (Hardware) cards 128-143 Digital Pseudo cards 144-159 Analog Pseudo cards 160-175 List Pseudo cards Digital Pseudo’s: There are 250 fixed pseudo's in the 4020 panel and 511 in the 4100 and 4100U. The numbering sequence is simple, 128 starts the first block of 256 (0 to 255), so the first point is 128-0-0, the second is 128-1-0, and so on. The next block starts at 129 and follows the same sequence, then 130 and so on up to 143. In the 4100 the first user definable pseudo is P-256, in the 4100U it's P-512.

P0 SYSTEM RESET KEY UTILITY 128-0-0 P1 ALARM SILENCE KEY UTILITY 128-1-0 P2 FRONT PANEL LAMPTEST CONTROL (ANNUNC. 0) UTILITY 128-2-0 P3 FIRE ALARM DETECT UTILITY 128-3-0 P4 GLOBAL ACKNOWLEDGE ENABLE UTILITY 128-4-0 P5 SET SERVICE PSEUDO VALUES UTILITY 128-5-0 P6 ALARM SILENCE UTILITY 128-6-0 P7 EXTRA CARD IN THE SYSTEM TROUBLE128-7-0 P8 KEYPAD ACTIVE UTILITY 128-8-0 P9 SYSTEM OUT OF CQB'S TROUBLE128-9-0 P10 CODED INPUT ACTIVE UTILITY 128-10-0 P11 UNACKNOWLEDGED FIRE ALARM EXISTS UTILITY 128-11-0 P12 UNACKNOWLEDGED SUPERVISORY EXISTS UTILITY 128-12-0 P13 UNACKNOWLEDGED TROUBLE EXISTS UTILITY 128-13-0 P14 SYSTEM DISABLED - PROGRAMMER DOWNLOAD TROUBLE128-14-0 P15 CFIG RAM WRITE PROTECT MISSING (SW1-1) TROUBLE128-15-0 P16 SMPL PROGRAM 0 - SYSTEM DEFAULT UTILITY 128-16-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 50 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 50 · click to enlarge
Page 50

P17 SMPL PROGRAM 1 - DEFAULT AUDIO UTILITY 128-17-0 P18 SMPL PROGRAM 2 - SYSTEM OPTIONS (CODING) UTILITY 128-18-0 P19 SMPL PROGRAM 3 - USER CUSTOM CONTROL UTILITY 128-19-0 P20 SMPL PROGRAM 4 - USER CUSTOM CONTROL UTILITY 128-20-0 P21 SMPL PROGRAM 5 - USER CUSTOM CONTROL UTILITY 128-21-0 P22 SMPL PROGRAM 6 - USER CUSTOM CONTROL UTILITY 128-22-0 P23 SMPL PROGRAM 7 - USER CUSTOM CONTROL UTILITY 128-23-0 P24 CODING GROUP 0 ACTIVE UTILITY 128-24-0 P25 CODING GROUP 1 ACTIVE UTILITY 128-25-0 P26 CODING GROUP 2 ACTIVE UTILITY 128-26-0 P27 CODING GROUP 3 ACTIVE UTILITY 128-27-0 P28 CODING GROUP 4 ACTIVE UTILITY 128-28-0 P29 CODING GROUP 5 ACTIVE UTILITY 128-29-0 P30 CODING GROUP 6 ACTIVE UTILITY 128-30-0 P31 CODING GROUP 7 ACTIVE UTILITY 128-31-0 P32 COLD START TROUBLE128-32-0 P33 WARM START TROUBLE128-33-0 P34 CITY DISCONNECT TROUBLE128-34-0 P35 MANUAL EVACUATION SWITCH INPUT UTILITY 128-35-0 P36 ELEVATOR BYPASS TROUBLE128-36-0 P37 DOORHOLDER BYPASS TROUBLE128-37-0 P38 CONTROL POINT BYPASS TROUBLE128-38-0 P39 SYSTEM EXECUTING FROM RAM TROUBLE128-39-0 P40 AUTOMATIC DETECTOR RESET UTILITY 128-40-0 P41 MASTER FIRE ALARM ACK KEY UTILITY 128-41-0 P42 MASTER SUPERVISORY ACK KEY UTILITY 128-42-0 P43 MASTER TROUBLE ACK KEY UTILITY 128-43-0 P44 CODING BUS DISABLE SWITCH UTILITY 128-44-0 P45 DRILL SWITCH INPUT UTILITY 128-45-0 P46 DOOR HOLDER TRIGGER UTILITY 128-46-0 P47 SIGNALS/VISUALS ACTIVE UTILITY 128-47-0 P48 MANUAL EVACUATION FIRE 128-48-0 P49 SYSTEM AT ACCESS LEVEL 1 OR GREATER UTILITY 128-49-0 P50 SYSTEM AT ACCESS LEVEL 2 OR GREATER UTILITY 128-50-0 P51 SYSTEM AT ACCESS LEVEL 3 OR GREATER UTILITY 128-51-0 P52 SYSTEM AT ACCESS LEVEL 4 UTILITY 128-52-0 P53 SYSTEM LIST OVERFLOW - WARM START NEEDED TROUBLE128-53-0 P54 NETWORK MIKE KEYED UTILITY 128-54-0 P55 CRT KEYPAD INACTIVITY TIMER DISABLE UTILITY 128-55-0 P56 CITY CIRCUIT STD TROUBLE RELAY OPERATION UTILITY 128-56-0 P57 KEYPAD INACTIVITY TIMER DISABLE UTILITY 128-57-0 P58 SYSTEM TIME/DATE INVALID OR NOT SET TROUBLE128-58-0 P59 ALARM VERIFICATION TALLY LIMIT EXCEEDED TROUBLE128-59-0 P60 ALARM VERIFICATION GROUP 0 ACTIVE UTILITY 128-60-0 P61 ALARM VERIFICATION GROUP 1 ACTIVE UTILITY 128-61-0 P62 ALARM VERIFICATION GROUP 2 ACTIVE UTILITY 128-62-0 P63 ALARM VERIFICATION GROUP 3 ACTIVE UTILITY 128-63-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 51 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 51 · click to enlarge
Page 51

P64 ALARM VERIFICATION GROUP 4 ACTIVE UTILITY 128-64-0 P65 ALARM VERIFICATION GROUP 5 ACTIVE UTILITY 128-65-0 P66 ALARM VERIFICATION GROUP 6 ACTIVE UTILITY 128-66-0 P67 ALARM VERIFICATION GROUP 7 ACTIVE UTILITY 128-67-0 P68 FIRST STAGE TIMER EXPIRED UTILITY 128-68-0 P69 THE EVAC MESSAGE HAS PLAYED UTILITY 128-69-0 P70 WALK TEST GROUP 0 ENABLED TROUBLE128-70-0 P71 WALK TEST GROUP 1 ENABLED TROUBLE128-71-0 P72 WALK TEST GROUP 2 ENABLED TROUBLE128-72-0 P73 WALK TEST GROUP 3 ENABLED TROUBLE128-73-0 P74 WALK TEST GROUP 4 ENABLED TROUBLE128-74-0 P75 WALK TEST GROUP 5 ENABLED TROUBLE128-75-0 P76 WALK TEST GROUP 6 ENABLED TROUBLE128-76-0 P77 WALK TEST GROUP 7 ENABLED TROUBLE128-77-0 P78 ALARM SILENCE/ALARM CUTOUT PSEUDO UTILITY 128-78-0 P79 RESET SPKRS WHEN AUDIO CODING COMPLETE UTILITY 128-79-0 P80 MASTER MICROPHONE KEYED UTILITY 128-80-0 P81 REMOTE MICROPHONE 1 KEYED UTILITY 128-81-0 P82 REMOTE MICROPHONE 2 KEYED UTILITY 128-82-0 P83 REMOTE MICROPHONE 1 READY TO TALK UTILITY 128-83-0 P84 REMOTE MICROPHONE 2 READY TO TALK UTILITY 128-84-0 P85 VTG 1 - ACTIVE UTILITY 128-85-0 P86 VTG 2 - ACTIVE UTILITY 128-86-0 P87 EVACUATION MESSAGE ON UTILITY 128-87-0 P88 EVACUATION MESSAGE OFF UTILITY 128-88-0 P89 EVACUATION MESSAGE LED UTILITY 128-89-0 P90 ALERT MESSAGE ON UTILITY 128-90-0 P91 ALERT MESSAGE OFF UTILITY 128-91-0 P92 ALERT MESSAGE LED UTILITY 128-92-0 P93 DRILL MESSAGE ON UTILITY 128-93-0 P94 DRILL MESSAGE OFF UTILITY 128-94-0 P95 DRILL MESSAGE LED UTILITY 128-95-0 P96 ALL CLEAR MESSAGE ON UTILITY 128-96-0 P97 ALL CLEAR MESSAGE OFF UTILITY 128-97-0 P98 ALL CLEAR MESSAGE LED UTILITY 128-98-0 P99 AUX MSG 1 ON UTILITY 128-99-0 P100 AUX MSG 1 OFF UTILITY 128-100-0 P101 AUX MSG 1 LED UTILITY 128-101-0 P102 AUX MSG 2 ON UTILITY 128-102-0 P103 AUX MSG 2 OFF UTILITY 128-103-0 P104 AUX MSG 2 LED UTILITY 128-104-0 P105 PHONE PAGING ON UTILITY 128-105-0 P106 PHONE PAGING OFF UTILITY 128-106-0 P107 PHONE PAGING LED UTILITY 128-107-0 P108 AUDIO OVERRIDE ON UTILITY 128-108-0 P109 AUDIO OVERRIDE OFF UTILITY 128-109-0 P110 AUDIO OVERRIDE TROUBLE TROUBLE128-110-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 52 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 52 · click to enlarge
Page 52

P111 ALL SPEAKERS MINUS ON UTILITY 128-111-0 P112 ALL SPEAKERS MINUS OFF UTILITY 128-112-0 P113 ALL SPEAKERS MINUS LED UTILITY 128-113-0 P114 ALL SPEAKERS CHANNEL 1 ON UTILITY 128-114-0 P115 ALL SPEAKERS CHANNEL 1 OFF UTILITY 128-115-0 P116 ALL SPEAKERS CHANNEL 1 LED UTILITY 128-116-0 P117 ALL SPEAKERS CHANNEL 2 ON UTILITY 128-117-0 P118 ALL SPEAKERS CHANNEL 2 OFF UTILITY 128-118-0 P119 ALL SPEAKERS CHANNEL 2 LED UTILITY 128-119-0 P120 ALL SPEAKERS CHANNEL 3 ON UTILITY 128-120-0 P121 ALL SPEAKERS CHANNEL 3 OFF UTILITY 128-121-0 P122 ALL SPEAKERS CHANNEL 3 LED UTILITY 128-122-0 P123 LOCAL SPEAKER EVAC ON UTILITY 128-123-0 P124 LOCAL SPEAKER EVAC OFF UTILITY 128-124-0 P125 LOCAL SPEAKER EVAC LED UTILITY 128-125-0 P126 LOCAL SPEAKER ALERT ON UTILITY 128-126-0 P127 LOCAL SPEAKER ALERT OFF UTILITY 128-127-0 P128 LOCAL SPEAKER ALERT LED UTILITY 128-128-0 P129 ALL SPEAKERS TALK ON UTILITY 128-129-0 P130 ALL SPEAKERS TALK OFF UTILITY 128-130-0 P131 ALL SPEAKERS TALK LED UTILITY 128-131-0 P132 ANALOG SENSOR ALMOST DIRTY LOG ENABLE TROUBLE128-132-0 P133 LOG ANALOG SENSOR PEAK VALUE ENABLE UTILITY 128-133-0 P134 CLEAR ANALOG SENSOR PEAK VALUE TROUBLE128-134-0 P135 ALL ALERT UTILITY 128-135-0 P136 ALL EVAC UTILITY 128-136-0 P137 ALL ALERT LED UTILITY 128-137-0 P138 MASTER MIKE PRETONE PLAYING ON VTG2 UTILITY 128-138-0 P139 REMOTE MIKE 1 PRETONE PLAYING ON VTG2 UTILITY 128-139-0 P140 REMOTE MIKE 2 PRETONE PLAYING ON VTG2 UTILITY 128-140-0 P141 MANUAL AUDIO EVAC ON UTILITY 128-141-0 P142 MANUAL AUDIO EVAC OFF UTILITY 128-142-0 P143 MANUAL AUDIO EVAC LED UTILITY 128-143-0 P144 DISABLE SUPERVISION ON VTG 1 (2120 APPL) UTILITY 128-144-0 P145 DISABLE SUPERVISION ON VTG 2 (2120 APPL) UTILITY 128-145-0 P146 EMPTY AUDIO SERVICE QUEUE UTILITY 128-146-0 P147 EVAC MSG PLAYING WHEN MICROPHONE KEYED UTILITY 128-147-0 P148 SYSTEM OUT OF AQB'S TROUBLE128-148-0 P149 SPEAKER SWITCH OFF AUTO TROUBLE128-149-0 P150 AUDIO CODING GROUP 1 ACTIVE UTILITY 128-150-0 P151 AUDIO CODING GROUP 2 ACTIVE UTILITY 128-151-0 P152 VTG 1 - AUDIO SUPERVISION ACTIVE UTILITY 128-152-0 P153 VTG 2 - AUDIO SUPERVISION ACTIVE UTILITY 128-153-0 P154 PHONE TALK LINE RELAY FEEDBACK UTILITY 128-154-0 P155 PHONE NETWORK RELAY FEEDBACK UTILITY 128-155-0 P156 LOCAL MASTER PHONE HANDSET OFF HOOK UTILITY 128-156-0 P157 PHONE TALK LINE RELAY CONTROL INPUT UTILITY 128-157-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 53 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 53 · click to enlarge
Page 53

P158 PHONE NETWORK RELAY CONTROL INPUT UTILITY 128-158-0 P159 PHONE TALK LINE RELAY CONTROL UTILITY 128-159-0 P160 PHONE NETWORK RELAY CONTROL UTILITY 128-160-0 P161 MASTER PHONE OFFHOOK SUPERVISION TROUBLE128-161-0 P162 MASTER MIKE PRETONE PLAYING ON VTG1 UTILITY 128-162-0 P163 REMOTE MIKE 1 PRETONE PLAYING ON VTG1 UTILITY 128-163-0 P164 REMOTE MIKE 2 PRETONE PLAYING ON VTG1 UTILITY 128-164-0 P165 AMPS SWITCHED TO BATTERY UTILITY 128-165-0 P166 ENABLE RM PHONE TO RM PHONE CONVERSATIONUTILITY 128-166-0 P167 ALERT MSG PLAYING WHEN MICROPHONE KEYED UTILITY 128-167-0 P168 MICROPHONE TO EVAC IN EFFECT UTILITY 128-168-0 P169 MICROPHONE TO ALERT IN EFFECT UTILITY 128-169-0 P170 MICROPHONE TO TALK (CHANNEL 3) IN EFFECT UTILITY 128-170-0 P171 BACKGROUND MUSIC RELAY CHANNEL 1 UTILITY 128-171-0 P172 BACKGROUND MUSIC RELAY CHANNEL 2 UTILITY 128-172-0 P173 BACKGROUND MUSIC RELAY CHANNEL 3 UTILITY 128-173-0 P174 VTG 1 CODE'S PRECODE PLAYING UTILITY 128-174-0 P175 VTG 1 CODE'S AFTER CODE PLAYING UTILITY 128-175-0 P176 AFTER CODE START - VTG 1 UTILITY 128-176-0 P177 VTG 1 'QUIET' MESSAGE PLAYING UTILITY 128-177-0 P178 VTG 2 CODE'S PRECODE PLAYING UTILITY 128-178-0 P179 VTG 2 CODE'S AFTER CODE PLAYING UTILITY 128-179-0 P180 AFTER CODE START - VTG 2 UTILITY 128-180-0 P181 VTG 2 'QUIET' MESSAGE PLAYING UTILITY 128-181-0 P182 (2120 APPL) VTG1 CODE START UTILITY 128-182-0 P183 (2120 APPL) STOP VTG1 QUEUE UTILITY 128-183-0 P184 (2120 APPL) VTG2 CODE START UTILITY 128-184-0 P185 (2120 APPL) STOP VTG2 QUEUE UTILITY 128-185-0 P186 MIKE DISABLE UTILITY 128-186-0 P187 VTG & AMPLIFIER TROUBLE DISABLE UTILITY 128-187-0 P188 VTG SUPERVISION TONE NOT ACTIVE TROUBLE128-188-0 P189 SATELLITE PHONE TIMEOUT DISABLE UTILITY 128-189-0 P190 NETWORK MIKE PRETONE PLAYING UTILITY 128-190-0 P191 MASTER MIKE KEYED UTILITY 128-191-0 P192 REMOTE MIKE 1 KEYED UTILITY 128-192-0 P193 REMOTE MIKE 2 KEYED UTILITY 128-193-0 P194 MIKES ARE READY TO PAGE UTILITY 128-194-0 P195 S21 SWITCH ACTIVATED UTILITY 128-195-0 P196 RAM BATTERY MISSING/FAILED TROUBLE128-196-0 P197 2120 1 COMM LOSS UTILITY 128-197-0 P198 INHIBIT SONALERT UTILITY 128-198-0 P199 INHIBIT ALARM DEFAULT UTILITY 128-199-0 P200 FORCE COLD START UTILITY 128-200-0 P201 AC VOLTAGE FAILURE/BROWNOUT UTILITY 128-201-0 P202 DETECTOR RESET UTILITY 128-202-0 P203 LCD ANNUNCIATORS OVERRIDE KEYSWITCH UTILITY 128-203-0 P204 SIGNALS SILENCED UTILITY 128-204-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 54 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 54 · click to enlarge
Page 54

P205 TRUEALARM SENSITIVITY MODIFIED TROUBLE128-205-0 P206 PRINT QUEUE OVERFLOW TROUBLE128-206-0 P207 NETWORK DIAGNOSTIC MODE TROUBLE128-207-0 P208 OUT OF NQB'S TROUBLE128-208-0 P209 COMMUNICATIONS SHORT CIRCUIT TROUBLE TROUBLE128-209-0 P210 NETWORK DETECTOR RESET UTILITY 128-210-0 P211 NETWORK SYSTEM RESET UTILITY 128-211-0 P212 DETECTOR/SYSTEM RESET UTILITY 128-212-0 P213 4120 NETWORK CARD CONFIGURED UTILITY 128-213-0 P214 CLEAR VERIFICATION TALLIES TROUBLE128-214-0 P215 PRIORITY 2 ALARM DETECT UTILITY 128-215-0 P216 PRIORITY 2 ALARM RESET REQUEST UTILITY 128-216-0 P217 NETWORK SIGNAL SILENCE UTILITY 128-217-0 P218 UNACKNOWLEDGED PRIORITY 2 ALARM EXISTS UTILITY 128-218-0 P219 MASTER PRIORITY 2 ALARM ACK KEY UTILITY 128-219-0 P220 NETWORK PRIORITY 2 RESET UTILITY 128-220-0 P221 SIGNALS ACTIVE - OFF ON SILENCE UTILITY 128-221-0 P222 REMOTE DOWNLOAD ENABLED TROUBLE128-222-0 P223 MASTER MICROPHONE READY TO TALK UTILITY 128-223-0 P224 NETWORK INITIALIZATION INCOMPLETE TROUBLE128-224-0 P225 NETWORK OPERATING IN DEGRADED STYLE-7 TROUBLE128-225-0 P226 NETWORK INITIALIZATION IN PROGRESS TROUBLE128-226-0 P227 SDACT DATABASE VERSION MISMATCH TROUBLE128-227-0 P228 PREVENT TIME/DATE LOGGING UTILITY 128-228-0 P229 TRUEALERT SILENT TEST ACTIVE TROUBLE128-229-0 P230 TRUEALERT DEVICE TEST MODE ACTIVE TROUBLE128-230-0 P231 EXTRA NODE ON NETWORK TROUBLE128-231-0 P232 NETWORK POINT LABEL UPDATING INHIBITED TROUBLE128-232-0 P250 ENABLE END PAIR AND MONITOR LOGGING UTILITY 128-250-0 Analog Pseudo's do not have alarm states, they have physical values such as the day, date, time, number of fire events, number of troubles and so on. A0 NUMBER OF SYSTEM FIRE ALARMS ANALOG 144-0-0 A1 NUMBER OF SYSTEM SUPERVISORIES ANALOG 144-1-0 A2 NUMBER OF SYSTEM TROUBLES ANALOG 144-2-0 A3 NUMBER OF OLD (UNCLEARED) FIRE ALARMS ANALOG 144-3-0 A4 NUMBER OF OLD (UNCLEARED) SUPERVISORIES ANALOG 144-4-0 A5 NUMBER OF OLD (UNCLEARED) TROUBLES ANALOG 144-5-0 A6 CURRENT HOUR ANALOG 144-6-0 A7 CURRENT MINUTE ANALOG 144-7-0 A8 CURRENT SECOND ANALOG 144-8-0 A9 CURRENT DAY ANALOG 144-9-0 A10 CURRENT MONTH ANALOG 144-10-0 A11 CURRENT YEAR ANALOG 144-11-0 A12 CURRENT ACCESS LEVEL ANALOG 144-12-0 A13 ACCESS LEVEL TIMEOUT TIMER 144-13-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 55 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 55 · click to enlarge
Page 55

A14 SYSTEM RESET WINDOW TIMER TIMER 144-14-0 A15 SYSTEM RESET WINDOW TIMER SETPOINT ANALOG 144-15-0 A16 DETECTOR RESET PULSE TIMER TIMER 144-16-0 A17 4-WIRE RESET RELAY PULSE TIMER TIMER 144-17-0 A18 FIRE ALARM CLEAR DELAY TIMER TIMER 144-18-0 A19 FIRE ALARM CLEAR DELAY TIMER SETPOINT ANALOG 144-19-0 A20 FIRE ALARM CLEAR PULSE TIMER TIMER 144-20-0 A21 SYSTEM RESET PULSE TIMER TIMER 144-21-0 A22 ALARM SILENCE INHIBIT TIMER TIMER 144-22-0 A23 ALARM SILENCE INHIBIT TIMER SETPOINT ANALOG 144-23-0 A24 FIRE ALARM CUTOUT TIMER TIMER 144-24-0 A25 FIRE ALARM CUTOUT TIMER SETPOINT ANALOG 144-25-0 A26 FIRE ALARM CUTOUT SILENCE PULSE TIMER TIMER 144-26-0 A27 TROUBLE REMINDER CYCLE TIMER TIMER 144-27-0 A28 TROUBLE REMINDER OFF-TIME SETPOINT ANALOG 144-28-0 A29 TROUBLE REMINDER ON-TIME SETPOINT ANALOG 144-29-0 A30 DOOR HOLDER ALARM DROP TIMER TIMER 144-30-0 A31 DOOR HOLDER ALARM DROP TIMER SETPOINT ANALOG 144-31-0 A32 DOOR HOLDER BROWNOUT DROP TIMER TIMER 144-32-0 A33 DOOR HOLDER BROWNOUT DROP TIMER SETPOINT ANALOG 144-33-0 A34 SYSTEM STARTUP PULSE TIMER TIMER 144-34-0 A35 FIRE ALARM AUDIBLE SIGNAL OPERATION ANALOG 144-35-0 A36 FIRE ALARM VISUAL SIGNAL OPERATION ANALOG 144-36-0 A37 ALARM VERIFICATION - RETARD TIME ANALOG 144-37-0 A38 ALARM VERIFICATION - RESET TIME ANALOG 144-38-0 A39 ALARM VERIFICATION - CONFIRMATION TIME ANALOG 144-39-0 A40 ALARM VERIFICATION - TALLY LIMIT ANALOG 144-40-0 A41 WALK TEST ABORT TIMEOUT SETPOINT ANALOG 144-41-0 A42 WALK TEST REACTIVATE DELAY SETPOINT ANALOG 144-42-0 A43 MONITOR ZONE ENABLE DELAY SETPOINT ANALOG 144-43-0 A44 CODED INPUT TIMEOUT SETPOINT ANALOG 144-44-0 A45 OFF TIME AFTER PNIS (NON-CONT.) CODES ANALOG 144-45-0 A46 CITY CIRCUIT CONFIGURATION ANALOG 144-46-0 A47 ALERT TONE/MSG AFTER MICROPHONE UNKEYED ANALOG 144-47-0 A48 TOTAL AUDIO CHANNELS ANALOG 144-48-0 A49 CHANNEL 1 ROUTING ANALOG 144-49-0 A50 CHANNEL 2 ROUTING ANALOG 144-50-0 A51 CHANNEL 3 ROUTING ANALOG 144-51-0 A52 LOCAL ROUTING ANALOG 144-52-0 A53 EVAC TONE/MSG AFTER MICROPHONE UNKEYED ANALOG 144-53-0 A54 SUPERVISION MSG# ANALOG 144-54-0 A55 EVACUATION MSG# ANALOG 144-55-0 A56 ALERT MSG# ANALOG 144-56-0 A57 DRILL MSG# ANALOG 144-57-0 A58 ALL CLEAR MSG# ANALOG 144-58-0 A59 AUX 1 MSG# ANALOG 144-59-0 A60 AUX 2 MSG# ANALOG 144-60-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 56 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 56 · click to enlarge
Page 56

A61 MICROPHONE PRETONE MSG# ANALOG 144-61-0 A62 PHONE OFFHOOK TIMER TIMER 144-62-0 A63 PHONE CALLBACK TIMER TIMER 144-63-0 A64 PHONE TIMEOUT TIMER TIMER 144-64-0 A65 REMOTE MASTER PHONE TIMEOUT TIMER TIMER 144-65-0 A66 SPEAKER SWITCH OFF AUTO COUNT ANALOG 144-66-0 A67 AUDIO RESET PULSE TIMER TIMER 144-67-0 A68 VTG 1 PRIORITY ANALOG 144-68-0 A69 VTG 2 PRIORITY ANALOG 144-69-0 A70 CHANNEL 1 ROUTING PRIORITY ANALOG 144-70-0 A71 CHANNEL 2 ROUTING PRIORITY ANALOG 144-71-0 A72 CHANNEL 3 ROUTING PRIORITY ANALOG 144-72-0 A73 LOCAL SPEAKER ROUTING PRIORITY ANALOG 144-73-0 A74 AUDIO SUPERVISION PULSE TIMER VTG1 TIMER 144-74-0 A75 AUDIO SUPERVISION PULSE TIMER VTG2 TIMER 144-75-0 A76 ENABLE/DISABLE STATISTIC GROUP ANALOG 144-76-0 A77 ENABLE/DISABLE STATISTIC OUTPUT PORT ANALOG 144-77-0 A78 5 SEC TIMER FOR REMOTE MASTER PHONES TIMER 144-78-0 A79 CLEAR PEAK PULSE ANALOG 144-79-0 A80 PRECODE MESSAGE NUMBER - VTG 1 ANALOG 144-80-0 A81 AFTER CODE MESSAGE NUMBER - VTG 1 ANALOG 144-81-0 A82 PRECODE MESSAGE NUMBER - VTG 2 ANALOG 144-82-0 A83 AFTER CODE MESSAGE NUMBER - VTG 2 ANALOG 144-83-0 A84 ' QUIET' MESSAGE NUMBER ANALOG 144-84-0 A85 2 SECOND TIMER - VTG 1 TIMER 144-85-0 A86 2 SECOND TIMER - VTG 2 TIMER 144-86-0 A87 MIKE INHIBIT TIMER TIMER 144-87-0 A88 MIKE INHIBIT TIMER SETPOINT ANALOG 144-88-0 A89 PHONE CALLBACK TIMER SETPOINT ANALOG 144-89-0 A90 PHONE TIMEOUT TIMER SETPOINT ANALOG 144-90-0 A91 VTG & AMPLIFIER TROUBLE DISABLE TIMER TIMER 144-91-0 A92 SUPERVISION NOT ACTIVE - TBL DELAY TIMER TIMER 144-92-0 A93 4 WIRE DETECTOR RESET EXTEND TIMER TIMER 144-93-0 A94 ACTIVE MESSAGE NUMBER - VTG 1 ANALOG 144-94-0 A95 ACTIVE MESSAGE NUMBER - VTG 2 ANALOG 144-95-0 A96 ACTUAL CHIPSET PLUGGED INTO VTG 1 ANALOG 144-96-0 A97 ACTUAL CHIPSET PLUGGED INTO VTG 2 ANALOG 144-97-0 A98 BATTERY TROUBLE COUNTER COUNTER 144-98-0 A99 AC POWER FAIL COUNTER COUNTER 144-99-0 A100 SYSTEM TYPE ANALOG 144-100-0 A101 FIRST STAGE TIMER ANALOG 144-101-0 A102 FIRST STAGE TIMER SETPOINT ANALOG 144-102-0 A103 MASTER MIKE 5 SECOND UNKEY DELAY ANALOG 144-103-0 A104 REMOTE MIKE 1 5 SECOND UNKEY DELAY ANALOG 144-104-0 A105 REMOTE MIKE 2 5 SECOND UNKEY DELAY ANALOG 144-105-0 A106 MASTER MIKE'S PRETONE TIMER ANALOG 144-106-0 A107 MASTER MIKE'S PRETONE SETPOINT ANALOG 144-107-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 57 of the FieldServer FS-8700-41 user manual — 2 PHYSICAL STATE ~
Page 57 · click to enlarge
Page 57

A108 REMOTE MIKE 1'S PRETONE TIMER ANALOG 144-108-0 A109 REMOTE MIKE 1'S PRETONE SETPOINT ANALOG 144-109-0 A110 REMOTE MIKE 2'S PRETONE TIMER ANALOG 144-110-0 A111 REMOTE MIKE 2'S PRETONE SETPOINT ANALOG 144-111-0 A112 GROUND TROUBLE COUNTER COUNTER 144-112-0 A113 PAGING CHANNEL ANALOG 144-113-0 A114 TRUEALARM MODIFICATION COUNTER COUNTER 144-114-0 A115 EXCESSIVELY DIRTY (OUT OF RANGE) ANALOG 144-115-0 A116 DIRTY SENSOR COUNTER COUNTER 144-116-0 A117 ALMOST DIRTY COUNTER COUNTER 144-117-0 A118 ALARMS SILENCED DELAY TIMER TIMER 144-118-0 A119 NUMBER OF LOCAL SYSTEM POINTS' TROUBLES COUNTER 144-119-0 A120 SYSTEM PAGING STATUS ANALOG 144-120-0 A121 KEYPAD INACTIVITY TIMEOUT SETPOINT ANALOG 144-121-0 A122 NUMBER OF SYSTEM PRIORITY 2 ALARMS ANALOG 144-122-0 A123 NUMBER OF OLD (UNCLEARED) PRI2 ALARMS ANALOG 144-123-0 A124 PRI2 RESET WINDOW TIMER TIMER 144-124-0 A125 PRI2 RESET WINDOW TIMER SETPOINT ANALOG 144-125-0 A126 PRI2 ALARM CLEAR DELAY TIMER TIMER 144-126-0 A127 PRI2 ALARM CLEAR DELAY TIMER SETPOINT ANALOG 144-127-0 A128 PRI2 ALARM CLEAR PULSE TIMER TIMER 144-128-0 A129 PRIORITY 2 RESET PULSE TIMER TIMER 144-129-0 A130 PRIORITY 2 RESET START TIMER TIMER 144-130-0 A131 SUPERVISION DELAY SETPOINT CHL1 ANALOG 144-131-0 A132 SUPERVISION DELAY SETPOINT CHL2 ANALOG 144-132-0 A133 SUPERVISION NOT ACTIVE DELAY SETPOINT ANALOG 144-133-0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Page 58 of the FieldServer FS-8700-41 user manual — THIS PAGE INTENTIONALLY LEFT BLANK
Page 58 · click to enlarge
Page 58

THIS PAGE INTENTIONALLY LEFT BLANK

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-41

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-41

Be the first to ask — other owners or our team will answer.