Page 1 of the FieldServer FS-8700-36 user manual — Driver Manual (Supplement to the FieldServer Instruction
Page 1 · click to enlarge
Page 1
FieldServer FS-8700-36 — Driver Manual (Supplement to the FieldServer Instruction diagram (page 1)
Fig. 1 · Driver Manual (Supplement to the FieldServer Instruc…

A Sierra Monitor Company

Driver Manual (Supplement to the FieldServer Instruction

FS-8700-36 Weigh-Tronix

APPLICABILITY & EFFECTIVITY

Effective for all systems manufactured after May 1, 2001

Instruction Manual Part Number FS-8700-36

VersionN/A

Manual) · 2/18/2004

Page 2 of the FieldServer FS-8700-36 user manual — Driver Manual (Supplement to the FieldServer Instruction
Page 2 · click to enlarge
Page 2
Page 2 of the FieldServer FS-8700-36 user manual — Driver Manual (Supplement to the FieldServer Instruction
Page 3 of the FieldServer FS-8700-36 user manual — 1.1 Hardware/Software
Page 3 · click to enlarge
Page 3

1. Weigh-Tronix Description

The Weigh-Tronix driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Weigh-Tronix protocol. The FieldServer emulates a Client only.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

Devices Supported ManufModelNotes Weigh-TronixWI 125 Weigh-TronixWI 127 Weigh-TronixWI 130 *Other devices – contact FST

1.1 Hardware/Software

Supplied by FieldServer Technologies.

FieldServerDESCRIPTION Technologies PART # FS-8915-10UTP cable (7 foot) for RS-232 use FS-8917-01RJ45 to DB25M connector adapter

PART # DESCRIPTION Weigh-Tronix Simposer Software

Cables for PC to scale to configure scale

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Page 4 of the FieldServer FS-8700-36 user manual — 2. FieldServer as a Weigh-Tronix Client
Page 4 · click to enlarge
Page 4

2. FieldServer as a Weigh-Tronix Client

2.1 Hardware Connections

FieldServer FS-8700-36 — 2. FieldServer as a Weigh-Tronix Client diagram (page 4)
Fig. 2 · 2. FieldServer as a Weigh-Tronix Client

P1 P7 R1 P2 R2 P3 P4 P5 P6 P8 N1 N2

M DB 25MTO TB6 (Weigh-tronix) Pin 2 Pin 3 Pin 6REC XMT GND

P7 P5 P6 Tx Rx Tx Tx Rx Rx

2.1.1 Setting up the Scale

Setting up the scale requires installing and executing Weigh-Tronix Surposer software. This has to be obtained from Weigh-Tronix and installed per their user manual. The procedure below is just a summary of the steps required to configure the Scale and any technical support regarding the scale should be obtained from Weigh-Tronix. a. Install Simposer b. Start Weigh-Tronix Simposer c. Editors/Configure/Serial Ports/end of message = 05

Serial port = 1 Baud = 9600 Parity = none Data Bits = 8 Handshake = none Mode = basic control d. Connect computer to scale as instructed by Weigh-Tronix e. Editors/Program

Enter the following program sub com1_message fmtprint (1) end sub getcom$(1) end sub Close editor f. Editors/print formats

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

DB25M Customer Responsibility · Weigh-Tronix

Page 5 of the FieldServer FS-8700-36 user manual — 2. FieldServer as a Weigh-Tronix Client
Page 5 · click to enlarge
Page 5

G {gross} lb \r\n T {tare} lb \r\n\ N {net} lb \r\n Select Print Format = 1 Select Port = 1 f. Close editor g. Save configuration h. Download Com 1 or Com 2

Wait for double beep Wait for single beep i. Exit WI-130 config j. Attach Model FieldServer FieldServer per dwg etc.

2.1.2 Configuration File Structure

2.1.2.1 Data Arrays

Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provides data format INT16, INT32, BIT, FLOAT Data_Array_Length Number of Data Objects 1-10,000 Example

// Data Arrays Data_Arrays Data_Array_Name, Data_Format, Data_Array_Length DA_AI, Float, 100

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Section Title Data_Arrays

Page 6 of the FieldServer FS-8700-36 user manual — P1-P8, R1-R2
Page 6 · click to enlarge
Page 6

Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer

P1-P8, R1-R2

Baud * Specify baud rate 300-9600-38400 Parity * Specify parity Even, Odd, None Data_Bits Specify data bits 7, 8 Stop_Bits Handshaking Specify hardware handshaking

Timeout Specify Timeout defaults must not be used

Weigh-Tronix 10.05

// Client Side Connections Connections Port, Baud, Timeout p8, 9600, 10.0s

2.1.2.2 Client Side Nodes

Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Protocol Specify protocol used Weigh-Tronix Timeout Specify Timeout defaults must not be used

Weigh-Tronix 10.05

// Client Side Nodes Nodes Node_Name, Protocol, Port Scale1, Weigh-Tronix, P8

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com
Show 6 more labels / short text on this page
Client Side Connections · Section Title Connections · RTS, RTS/CTS, None · Example · Section Title Nodes · Example
Page 7 of the FieldServer FS-8700-36 user manual — RDBC, WRBC, WRBX
Page 7 · click to enlarge
Page 7

2.1.2.3 Client Side Map Descriptors

Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above Function Function of Client Map Descriptor

RDBC, WRBC, WRBX

Node_Name Name of Node to fetch data from

One of the node names specified in “Client Node Descriptor” above Address Starting address of read block 0 Length Length of data array 3 Data_Array_Low_Scal e*

Scaling zero in Data Array -32767 to 32767, default 0

Scaling max in Data Array -32767 to 32767, default 100

Node_Low_Scale* Scaling zero in Connected Node

-32767 to 32767, default 0

Node_High_Scale* Scaling max in Connected Node

-32767 to 32767, default 100

// Client Side Map Descriptors Map_Descriptor Map_Descriptor_Name, Data_Array_Name, Data_Array_Location, Function, Node_Name, Address, Length wtio_MAP, DA_AI, 0, RDBC, Scale1, 0, 3,

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Section Title Map_Descriptors · Data_Array_High_Scal e* · Example

Page 8 of the FieldServer FS-8700-36 user manual — 3. Revision History
Page 8 · click to enlarge
Page 8

3. Revision History

04/22/02 1.00d 1 Revision history added 2/18/04 1.00d 2 Releasing

Visit our websitewww.fieldserver.com E-mail: support@ fieldserver.com

Date Driver Version · Document Revision · Comment

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the FieldServer FS-8700-36

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FieldServer FS-8700-36

Be the first to ask — other owners or our team will answer.

Original document

FieldServer FS-8700-36 manual PDF

8 pages·50 KB·Computer Drive·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…