FALCON® ELECTRIC, INC.
700-1000VA

FALCON® ELECTRIC, INC.
5106 Azusa Canyon Road Irwindale, CA 91706
Tel. 626-962-7770 Fax. 626 962-7720

800.842.6940
OM48031-SUP, 01/09/04, Rev A.


SAVE THESE INSTRUCTIONS
This manual contains important instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference.
All of the models presented herein are designed for installation and use in a controlled environment free of contamination.
This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble. This unit contains no user replaceable parts. Refer all servicing to Falcon Electric, Inc.
This UPS is not intended to be used in conjunction with life support or operating room equipment.
Always unplug this UPS prior to cleaning and never apply liquid or spray detergent on the UPS.
Never attempt to service batteries. High voltage exists within the unit, which could cause electrical shock. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unau- thorized personnel away from batteries. When replacing the UPS batteries, use the same number and type of batteries.
Allow at least 24 hours, after the UPS is first installed and turned on, to fully charge the internal battery and assure the maximum backup time is available.
DO NOT plug this UPS into its own output as this may damage the UPS.
DO NOT remove or unplug the input cord when the UPS is turned on. This removes the safety ground from the UPS and the equipment connected to the UPS.
This UPS contains its own energy source (batteries). The output receptacles may carry live voltage even when the UPS is not connected to an AC source.

® SMP Series - Overview
The FALCON® SUP Series UPS has the unique ability to operate from either 120Vac domestic or 230Vac international utility power, while providing 120Vac domestic output power. The SUP does not perform frequency conversion, however it is the ideal solution for the international traveller requring voltage conversion.
The Line-interactive or Automatic Voltage Regulator (AVR) feature provides output voltage regulation, while the UPS is operating from the utility power. This keeps the connected equipment's operating voltage within reasonable limits during abnormal utility power conditions such as brown-outs, high line voltages and surges.
All SUP models are microprocessor controlled. A Liquid Crystal Display (LCD) is conveniently located on the front panel. This display gives immediate and detailed UPS and power information without having to connect an expensive monitoring computer. An intelligent RS-232 computer interface port is also located on the UPS rear panel in the event remote monitoring or unattended computer shutdown is required. An optional external SNMP/HTTP agent is available, giving the ability to manage the UPS remotely across a LAN, WAN or via the Internet.
Unlike many other line-interactive UPSs on the market, the SUP models produce a sinewave output voltage, just like the incoming utility power. This assures your delicate electronic equipment will always receive the sinewave power it was designed for.
All models have an advanced two-stage battery charger providing safe, fast battery recharging while yielding a longer battery life.
All models have advanced surge protection circuitry to prevent damaging power line transients from reaching your equipment. Additional surge protect- ed, RJ11 telephone jacks are provided on the UPS rear panel.

If any FALCON® equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to the Falcon® Service Department.
THE BATTERY CONNECTION JUMPER MUST BE INSTALLED PRIOR TO PLUGGING IN AND ATTEMPTING TO TURN ON THE UPS.
5. If you are connecting the UPS to a PC Computer, you may want to install the supplied UPSilon shutdown and management software on your computer after connection the UPS interface cable to the RS-232 interface connector located on the UPS rear panel. Then connect the mating end of the cable to an unused serial port located on the computer rear panel. Before the UPS will be able to communicate properly with your computer, install the supplied computer monitoring and shutdown software.
Installation · Inspecting the Equipment · UPS Setup

The UPS provides both a contact closure and a true RS-232 computer interface.
The definition and setup for RS-232 is as follows:
Baud Rate : 2400 bps Data Length : 8 bits Stop Bit : 1 bit Parity : None
Pin #6: RS-232 data Tx out Pin #7: Common for Pin #6 and Pin #9 Pin #9: RS-232 data Rx In
The definition and setup for DB9 (optional) is as follows:
Pin #2: AC Power Failure Pin #4: Common GND of Pin #2 & Pin #5 Pin #5: UPS Battery Low Pin #6: Turn off UPS Pin #7: GND for Pin 6
The computer interface pin-out is stated above for reference only. Use Pin #4 as the common for Pins #2 and #5. Pins #2 and #4 are normally closed and will open when the utility fails. Pins #5 and #4 are normally open and will close at the low battery indication.
The UPS will shut down when a 5-12 Vdc voltage is applied across Pins #6 and #7 for three seconds, while the UPS is on battery mode.
Communications Interface

Controls, Displays & Functions
B
A
A. Main Control Button - This button is used to turn the UPS on and off, to perform a UPS self test, or to reset and silence an audible alarm. Refer to page 10 for operation instructions.
B. A Liquid Crystal Display (LCD) is provided. Please reference the number designation for the display function and the function descriptions referenced in this manual. Refer to pages 6-8 in this manual.
C. Two LCD metering function select buttons are provided. The upper button scrolls the display through the metering functions in an upward direction, the lower button in a downward direction. Refer to “LCD Metering Display Modes” referenced on page 8 of this manual.






Remove some of the load from the UPS to correct this condition.
remaining.
exceeds 30 watts and disappears when the load is under 25%.
UPS is operating normally from the utility line. Battery Mode - The sinewave and battery symbols will blink when
the UPS is operating on its internal battery. Test Mode - The sinewave symbol will display steadily and the
battery symbol will blink during a UPS self test.
the UPS output voltage due to a high utility voltage condition. The sinewave symbol is also displayed to indicate that the UPS is operating normally from the utility line.

6 Boost Mode - The AVR is increasing the UPS output voltage due to
a low utility voltage condition or "Brown-out". The sinewave symbol is also displayed to indicate that the UPS is operating normally from the utility line.
conditions: a) The UPS has been programmed to automatically turn on or off using the supplied remote monitoring software. b) The green mode is enabled and the UPS output load is under 25 watts. The UPS will turn off after a 30 second delay.
55ºC. If the end-user does not reduce the UPS output load or correct the cause of the UPS overheating, the temperature will continue to rise and upon reaching 60ºC the UPS will shutdown to prevent damage due to excessive overheating.
only.
during backup mode, briefly depress the control button.
control button and holding it for ten seconds. If the UPS resets and operates normally, no further action is required. If the UPS fault indicator is still displayed, the UPS has failed and must be repaired.
will be displayed inside the battery normal symbol.
indicates a charged battery.
segments will be dark. As the battery discharges, the segments will disappear starting from the top segment and end with the bottom segment.

the LCD display indicates the AC output voltage initially. Depressing the downward scroll button will indicate the following each time it is depressed:
LCD Metering Display Modes (use display scroll buttons to change modes; modes are in descending order)
JUMPER SLOT 2
JUMPER
following procedure. a) Using a #1 Phillips screwdriver remove the two screws securing
the battery disconnect cover. b) Remove the battery disconnect jumper plug from the plastic bag. c) Press the disconnect jumper into the socket visible through the
hole exposed after removal of the cover. A small popping sound may occur; this is normal.


found on all domestic (120V) models. IEC type receptacles will be found on international (230V) models.

1. Turning The UPS On and Off Depending on how the UPS was turned off, it may automatically turn on when the input plug is plugged in. If it does not turn on automatically, depress the control button located on the front panel for four seconds until the UPS turns on. To turn the UPS off press and hold the control button for five seconds or until the UPS turns off. UPS batteries will still continue to recharge after the UPS has turned off.
3. UPS Overload Condition To ensure that your computer equipment will be protected during a utility failure, it is important to make sure that the maximum power required from the equipment is not over the rated capacity of the UPS. The LCD overload indicator will be displayed and an audible alarm will sound if the load is over 120% of the UPS's rated output. If the over load is greater than120% , the UPS will shut down immediately to protect the itself. After three seconds, if the overload is removed the UPS will automatically turn on again. If the overload is still present the UPS will turn off and stay off, requiring the UPS be manually restarted. Always correct any overload condition immediately.
4. DC Start, Cold Start To start the UPS when utility power is not available, press and hold down the control button twice for one second each time. The UPS will start up and run on its internal battery until discharged. If you do not depress the control button to turn the UPS off during battery operation, the UPS will automatically restart when utility voltage is reapplied. The UPS batteries should not be left discharged for long periods of time or battery damage may occur.
Always reconnect the UPS to a utility source, turn the UPS on and allow the batteries to recharge for eight hours after the batteries have been fully discharged due to DC operation.
Operation

6. Battery Charging This UPS is shipped from the factory with its batteries fully charged. However, some charge may be lost due to the self discharge characteristics of the internal sealed lead-acid battery. Always allow the UPS to recharge for 24 hours prior to use. To recharge, simply connect the UPS line cord to a powered receptacle. The UPS does not have to be turned on for batteries to recharge. During normal use, the UPS will self recharge should the battery be depleted due to a loss of utility power.
7 UPS Reset In the event the UPS will not accept commands and appears to be locked up, depress the control button for and hold for ten seconds. The UPS CPU will be reset.
The load will be turned off according to the shutdown and start up schedule set in the software, which is then transferred and stored in the UPS memory. During the period of turn off to the next turn on, the status LCD "time entered" symbol will blink.

Maintenance & Technical Support
Never attempt to service batteries. High voltage exists within the unit, which could cause electrical shock. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing the UPS batteries, use the same number and type of batteries.
A. NEVER dispose of batteries in a fire, as batteries will explode. B. NEVER dispose of used batteries or the UPS in the trash or landfill as it is
against federal and state laws. The UPS and Batteries must be recycled. For UPS and battery recycling information, please contact our service department for the name and address of the nearest battery recycling facility.
A. Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic. B. A battery can present a risk of electrical shock and high short circuit current.
REFER ALL BATTERY SERVICING OR REPLACEMENT TO A QUALIFIED SERVICE TECHNICIAN. NEVER ATTEMPT TO REPLACE THE BATTERIES.

The following precautions should be observed by a qualified technician when working with batteries:
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correcting the interference by one or more of the following measures:
a. Reorient or relocate the receiving antenna. b. Increase the separation between the equipment and the receiver. c. Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected. d. Consult the dealer or an experienced radio/television technician for
assistance.

Your FALCON® Electric SUP Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service.
FALCON ELECTRIC, INC. 5106 Azusa Canyon Road Irwindale, CA. 91706 Voice 626.962.7770 Fax 626.962.7720 Service 800.842.6940 Email: service@falconups.com WWW.FALCONUPS.COM
Should service be desired, you must first obtain a Return Material Authorization number (RMA) and return shipping instructions from our customer service department. Please have your UPS model, serial numbers and date of purchase on hand prior to the call. (This information is located on the identification label on the rear panel of the unit.) The information is essential in retrieving your unit's historical records.
The RMA number issued must appear on the outside of the shipping carton. The original shipping container must be used when returning any SUP Series product. Falcon® Electric will not assume any responsibility for shipping damage. In the event of shipping damage you will be charged for repairs due to the damage.
All units must be returned prepaid. The address and shipping instructions will be given to you at the time the RMA is issued.
You may request technical information or support by email or telephone.
Please send your technical or support questions by email to:
You may contact a FALCON support engineer directly by calling the FALCON support line between 9:00 am and 4:00 pm PST.
626.962.7770

® hereby warrants parts shipped under this Agreement to be free from defective workmanship for a period of one year following date of shipment. Accidental damage, misuse or normal wear and tear shall not be construed as a defect. 1.2 The date of shipment as used herein will be the date on the Bill of Lading. If no Bill of Lading is issued, the date of shipment shall be shown on seller's shipping document. 1.3 No provision of this warranty shall cover equipment which has been altered or modified from the originally specifications manufactured unless authorized in writing. 1.4 No provision of this warranty shall cover batteries. However, battery manufacturer's warranties will be passed through to the customer whenever applicable.
2. LIMITS OF "IN WARRANTY" SERVICE LIABILITY: 2.1 FALCON® is obligated during the in-warranty period to provide service and/or adjustments to equipment returned to the factory at the expense of buyer (the term "factory" as used here-in shall also include any field service centers which may be established by FALCON ®) and to repair or replace any part(s) thereof which in the opinion of authorized FALCON ® personnel are found to have been defective during the warranty period. 2.2 Equipment requiring in-warranty services must be returned to the factory with all transportation charges prepaid, clearly tagged, stating the nature of the trouble experienced, and the disposition of the equipment after repair. The equipment will be returned freight collect by FALCON ® to the location specified via the best and least expensive carrier available or via customer's shipping instructions. 2.3 During the in-warranty period, no service charges shall be payable by the buyer for service performed other than for service necessitated by accident, misuse, theft, abnormal line or source voltage fluctuations, abnormal conditions of operation, damage by the elements or damage resulting from adjustments, repairs, modifications made by anyone other than FALCON ® authorized personnel, or the buyer's failure to reasonably maintain the equipment.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IS GIVEN AND ACCEPTED IN LIEU OF ANY AND ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE REMEDIES OF BUYER SHALL BE LIMITED TO THOSE PROVIDED HEREIN. IN NO EVENT WILL SELLER BE LIABLE FOR COLLATERAL OR CONSEQUENTIAL DAMAGES. No person is authorized to assume on behalf of FALCON ® any obligation or liability in connection with the sale, warranty or service policy of any products manufactured and/or marketed by FALCON
® beyond the warranty description on the face hereof.
® ELECTRIC reserves the right to make changes, additions, and/or improvements in its products without incurring any obligation to install them on its products previously sold. This Warranty is valid for FALCON
® product as sold.

Model Number SUP700-1C SUP1.0K-1C Nominal VA 700 1000 Electrical Input Nominal AC Voltage 120V or 230V 120V or 230V Current-Amps 7 (120V), 3.6 (230V) 10 (120V), 5.2 ( 230V) AC Voltage Window -21% to 25% Frequency 50/60 Hz (Auto – Tracking) Frequency Range 47 – 63Hz UPS is designed for use on 120V domestic or 230V international utility power with neutral, line and ground connections. Electrical Output Watts 490 650 Nominal AC Voltage 120V 120V Frequency 50/60 Hz (Auto-Tracking) On-Line Voltage Regulation ± 8% On Battery Voltage Regulation ± 8% Typical (prior to low battery warning) Waveform True Sinewave Surge Protection 125 Joules MOV Unit Protection Short Circuit, Overload & Over Temperature Efficiency AC to AC (Typical) 97% (120Vac Input), 90% (230Vac Input) Battery DC Voltage 24V 24V Type 12V, 7AH x 2 Lead Acid Maintenance-Free
12V, 9AH x 2 Lead Acid Maintenance-Free Back Up Time @ Full Load @ 1/2 Load
5 Minutes 12 Minutes 4.5 Minutes 11 Minutes Recharge Time 5 Hours to 90% Battery times are approximate. Transfer Time Bypass to Inverter Black-out, 3ms / Brown-out, 0ms Inverter to Bypass 0ms Electrical Connections Input 1 - 6’ Cord with 5-15P & 1 – 6’ Cord with Schuko 1 - 6’ Cord with 5 -15P & 1 – 6’ Cord with Schuko Output (3) 5-15R (3) 5-15R Environmental Operating Temperature 0º C - 40º C (32º F to 104º F) Altitude 7,000 Feet Humidity 10% to 95% Non – Condensing Cooling Low Velocity Forced Air Fans Audible Noise @ 1 meter < 45dBA Controls and Indicators Control One Main Control Button – UPS On/Off, Self Test, Reset & Silence Alarms Selection Control Two LCD Metering Scroll Function Select Buttons LCD Display
AC Input Voltage, AC Output Voltage, Output Frequency, DC Battery Voltage, Internal UPS
Temperature, Timer – Minutes to Shutdown, Hours to Restart, Battery – Remaining Battery Time LCD Operational Symbols Overload, Load Level, UPS is Loaded, Normal Mode, Buck Mode, Boost Mode, Timer Enabled,
High Temperature, Fan Off, Alarm Off, UPS Fault, Battery Low, Battery Level Audible Alarms Low Battery, Defective Battery, Low Battery, Overload, Over Temperature, AC Out of Range Communications RS-232 Serial Port and Contact Closure Signal interface (Bundled UPSilon 2000 Software) Mechanical Dimensions H x W x D Inches (mm)
7.9 x 7.1 x 14.2 (200 x 180 x 360) Weight lb. (kg) 33.1 (15) 33.1 (15) Agency Listing UL1778, CUL, FCC Class A Note: The UPS will go to Green Mode whenever the output load is under 30 watts.
©2004 Falcon® Electric, Inc. All rights reserved. Falcon® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. All other brand names and trademarks are the property of their respective owners. The information and specifications stated in this document are subject to change without notice. 01-07-04 MD44034-A
Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720
www.falconups.com - email:sales@falconups.com