Emerson Process Management Wireless Gateway (Express)

13 pages·511 KB·Network Card·PDF·ENDEFRITNLJA
Emerson Process Management Wireless Gateway (Express)
Table of Contents 20 sections Bristol · ® Express SCADA RTU · Features · Application Suitability · … ShowHide
Page 1 of the Emerson Process Management Wireless Gateway (Express) user manual — Website: www.EmersonProcess.com/Remote Remote Automation Solutions
Page 1 · click to enlarge
Page 1

Product Data Document 420DS-6c / D301311X012 January 29, 2009 - Page 1

Bristol

® Express SCADA RTU

Emerson Process Management Wireless Gateway (Express) — Bristol diagram (page 1)
Fig. 1 · Bristol

Bristol® ControlWave® Express SCADA RTU, from Emerson Process Management, provides excep tional performance and unique functionality for applications requiring low installation cost, very low power consumption, and space efficiency.

As an integrated RTU is a SCADA system, ControlWave Express has the unique attributes required for wide area networks, without sacrificing process control performance.

Multiple serial communication ports for network, • local and multi-vendor connectivity

Built-in BSAP, Modbus & DNP protocols for • broad network compatibility

Features

Report-By-Exception for communication • efficiency

ARM processor provides exceptional • performance and low power consumption

Modbus Store and Forward capability for • geographic flexibility with radio networks

IEC 61131-3 programming with ACCOL III • process control function block library

Ultra low power modes for solar applications • and reduced solar panel and battery costs

Optional 100/10 MB Ethernet port •

Three serial communication ports •

Wide operating temperature range for remote • outdoor locations

Flexible fixed I/O configurations •

4 Digital inputs •

Application Suitability

2 Digital outputs •

2 selectable Digital inputs/outputs •

Based on years of experience in water, gas and SCADA related industries, ControlWave Express has the technology, functional benefits and open architecture to excel in many applications.

2 selectable Digital inputs/counters •

2 selectable Digital/Pulse inputs on CPU •

3 optional Analog inputs •

Water distributionPump, tank, well and reservoir control

1 optional Analog output •

WastewaterLift station and storm water monitoring and control

Wide temperature range (-40 to +70ºC) •

Class I, Div. 2 hazardous location and CE • approval

Natural GasGas well, storage and plunger lift control

Open standards for programming, network • configuration and communication

Website: www.EmersonProcess.com/Remote Remote Automation Solutions

Page 2 of the Emerson Process Management Wireless Gateway (Express) user manual — ControlWave Designer with ACCOL III
Page 2 · click to enlarge
Page 2

Scalability

IEC 61131-3 process languages for batch, continu ous and discrete control: Function Block Diagram, Structured Text, Sequential Function Chart, Ladder Logic Diagram and Instruction List.

ControlWave Express can also be combined seam lessly with other members in the ControlWave family of products. For remote applications requiring more I/O flexibility, ControlWave Micro provides a modular RTU/PLC expandable up to 14 I/O modules.

ControlWave Designer includes an extensive library of more than 200 basic IEC 61131-3 functions and function blocks common to many IEC 61131-3 based products. These include:

For natural gas well site and measurement station automation, ControlWave single and multi-run flow computers share a common architecture with the ControlWave family of products and all meet API 21.1 requirements for multiple meter runs.

Flip-flops, Counters & Timers •

Ladder diagram functions – coils and contacts, • etc.

For in-plant control applications, ControlWave and ControlWave Micro are powerful, flexible PLCs. ControlWave offers the greatest local and remote I/O expansion to hundreds of I/O points, up to three Ethernet ports for network segmentation, plus CPU, communication and I/O redundancy capability.

Numerical, Arithmetic & Boolean functions • – Sine, Cosine, Add, Sub, Square Root, And, Or, etc.

Selection & Comparison – Min, Max, Greater • than, Equal, Less than, etc.

Type conversions – Integer to Real, Boolean to • Word, etc.

The combined benefits of the ControlWave family of products integrates your wide area network with your local area network.

ACCOL III

Open Standards For Programming, Net work Configuration and Communication

In addition to the basic functions and function blocks, ControlWave Designer brings the benefit of over twenty years of SCADA and plant control expe rience in Emerson’s Bristol ACCOL III function block library. ACCOL III includes over sixty function blocks valuable for use in oil & gas, water & waste and pro cess measurement & control applications. Further, ACCOL III is designed to take full advantage of the significant features offered by ControlWave.

Only ControlWave brings the perfect combination of industry standards to minimize learning, engineering and implementation costs.

By adhering to such industry standards as Ethernet, TCP/IP, Microsoft Windows®, COM/DCOM, FTP, OLE and ActiveX, ControlWave is able to achieve the highest degree of openness in control system architecture and bring the optimal process efficiency and productivity needed to ensure a successful system implementation.

Briefly, this library includes function blocks for:

Average, Compare, Totalize •

Scheduling & Sequencing •

PID & Lead/Lag •

ControlWave Designer with ACCOL III

AGA gas flow and liquids calculations •

To minimize your engineering and development time, we have adopted the international standard for PLC programming, IEC 61131-3. ControlWave Designer is a fully IEC 61131-3 compliant program ming environment for the ControlWave family of products. ControlWave Designer includes all five

In addition, ControlWave ensures data integrity, in the event of a communication interruption, by stor ing critical time-stamped alarm and historical data in the controller memory. This data is then securely retrieved when communication is restored.

File handling •

Page 3 of the Emerson Process Management Wireless Gateway (Express) user manual — CPU RFI
Page 3 · click to enlarge
Page 3

Specifications

Mounting base plate: 10.75” H x 5.5” H x 2.0”D • (27.3 cm x 14.0 cm x 5.0 cm)

CPU

32-bit ARM processor14 & 33 MHz CPUs •
MountingFlat or edge panel mounting, or • optional DIN mount

Sleep mode for low power applications •

Real time clock/memory battery backup9000 • hours

Operating Temperature range • : -40 to 70oC (-40 to 158oF), storage up to 85oC

Program execution and Data Memory2 MB • battery backed SRAM memory
Relative Humidity •15-95% non-condensing
Data and file storage memory8 MB Flash for • Program source, historical Archive and Audit storage
Vibration •1.0g for 10-150 Hz - 0.5g for 150Hz to 2000Hz

Optional solar power regulator •

Hazardous Area Approvals •non-incendive for operation in Class I, Division 2

LED status indicators – 6 failure status LEDs, • Watchdog and CPU Idle and communication LEDs

CPU RFI

ImmunityENV 50140 Radio-frequency •

Two RS-232 and one selectable RS-232/RS- • 485 serial communication port supporting baud rates up to 115.2 KB

electromagnetic field amplitude modulated EMC •

EmissionsEN 55022:1998 Class A ITE • emissions requirements (EU)

One optional 100/10 Base-T Ethernet port with • RJ45 connector

ICES-003 Issue 3 Class A Digital Apparatus • emissions requirements (Canada)

One RJ45 connector for interface to • ControlWave LCD display/keypads

AS/NZS3548:1995/CISPR Class A ITE • emissions requirements (Australia)

5.4 to 16 Vdc power input with 14 MHz CPU • - Surge suppression 16 V transorb

3V/m – 80 MHz to 1000Mhz (IEC 1000-4-3) •

9.0 to 30.0 Vdc power input with 33 MHz CPU • - Surge suppression 30 V transorb

14 MHz CPU0.036 watt

Power-fail detection and recovery sequencer •

33 MHz CPU w/o Ethernet0.12 watt

Battery voltage monitor •

33 MHz CPU with Ethernet1.0 watt

Reverse voltage protection •

DIO card0.018 watt
DIO plus AIO card0.021 watt
Show 5 more labels / short text on this page
Housing · Environmental Specifications · Communication · Power Input · I/O RFI Susceptibility
Page 4 of the Emerson Process Management Wireless Gateway (Express) user manual — Specifications
Page 4 · click to enlarge
Page 4

ControlWave Express Process I/O

1 second for 2 DI/PI inputs on CPU board •

Surge protectionMeets C37.90-1978 •

ControlWave Express I/O module is designed to maximize usability while minimizing installation and maintenance.

30 Vdc transorb between signal and ground •

Terminations are pluggable and accept a • maximum wire size of 16 gauge

Emerson Process Management Wireless Gateway (Express) — ControlWave Express Process I/O diagram (page 4)
Fig. 2 · ControlWave Express Process I/O

Power consumption is stated for each I/O • module type measured at the input supply and does not include loop power

Inputs located on base CPU board •

Number of pointsup to 2 non-interrupting • inputs

The I/O module (bottom card) provides a mix of analog and digital inputs and outputs that are a perfect fit for small RTU applications.

Internally sourced, dry contact single ended • inputs

2 DI/PI (on CPU) •

Scan rateOnce per second •

1 RTD input on 14 MHz CPU •

Input filter20 microSec •

4 DI •

Voltage RangeInternally sourced dry contact • input - 3.3 Vdc

2 DO •

On state>1.6 V, Off state <1.3V •

2 selectable DI or DO •

Input current200 µA for low power applications •

2 selectable DI or HSC •

Optional 3 AI or 3 AI and 1 AO •

200 µA input, all inputs ON: 0.002 watt

Used as Pulse Input:

Features

Frequency Range0-10 kHz •

Convenient pluggable local terminations •

DebounceNone •

All configuration jumpers and switches • accessible without disassembly of circuit boards

Accumulator16 bit •

Termination points for external loop power • supply

Input available on 14 MHz Ultra Low Power • CPU only

Specifications

Specifications are for the interface only, not includ ing the RTD probe or wiring

RTD Conversion Accuracy± 0.1°C, or ± 0.1% • of reading, whichever is greater
I/O access50 ms with 33 MHz CPU, 250 ms • with 14 MHz CPU

Pulse/Digital Inputs · RTD Input · All I/O

Page 5 of the Emerson Process Management Wireless Gateway (Express) user manual — ControlWave Express Process I/O
Page 5 · click to enlarge
Page 5

Ambient temperature effect on RTD • measurement: ±0.01°C / ºC max

Number points3 AI optional •

Long Term Stability at Constant Conditions: • ±0.25ºC / month max

AI Resolution14 bit •
Input ConfigurationExternally sourced. Single– • ended inputs - jumper selectable 4–20 mA or 1–5 Vdc
Number of pointsup to 4 dedicated DI and 4 • selectable DI (2 DI/DO, 2 DI/HSC)
Input Impedance1 megΩ - 1 5 Vdc; •

250 Ω - 4-20 mA

Internally sourced, dry contact single ended • inputs

Input Filtering12 Hz •
Channel Settling Time600 ms to be within • 0.01% of input signal
Input Voltage RangeInternally sourced dry • contact input - 3.3 Vdc
Input accuracy•
On state>1.6 V, Off state <1.3V •

0.1% of span at 25 oC

Input current•

0.2% of span -40 oC to 70 2 oC

4 DI selectable 60 µA for low power applications or 2 mA for in-plant noise immunity

2 DI/DO selectable 200 µA or 2.2 mA

2 DI/HSC selectable 200 µA or 2.2 mA

Input filtering15 ms time constant (contact • bounce)
Number of Channels1 AO optional •
Output configurationsSelectable externally • sourced 4-20 mA or 1-5 Vdc:
All 8 inputs ON0.005 watt

250 ohm with 12 V external source

(4 inputs @ 66 µA and 4 @ 200 µA)

650 ohm with 24 V external source

All 8 inputs ON0.075 watt

1-5 Vdc @ 5mA max., 11 to 30 Vdc external source

(4 inputs @ 2 mA and 4 @ 2.2 mA)

D/A resolution12 bit •
Accuracy•
Number of points2 dedicated, 2 selectable DO • (2 DI/DO)

0.1% of span @ 25 oC for current output; 0.1% + 3% of span @ 25 oC for voltage

Output typesolid state open drain MOSFET •

0.3% of span @ -40 to 70 oC for current 0.3% + 3% of span @ -40 to 70 oC for voltage

Operating voltage range10 - 31Vdc •
Maximum operating frequency20 Hz •
Power consumption – 1 output•

Current sink capability: 400 mA at 16 V (6 V • system), 400 mA at 30 V (12/24 V system)

Analog current output0.1 watt
Analog voltage output0.1 watt

Not applicable to DOs

Show 6 more labels / short text on this page
Analog Inputs · Digital Inputs · Non-interrupting inputs • · Not applicable · Analog Output · Digital Outputs
Page 6 of the Emerson Process Management Wireless Gateway (Express) user manual — OpenBSI
Page 6 · click to enlarge
Page 6
Number of points2 selectable as HSC or DI •

Above this communication layer are a group of ap plications known as OpenBSI Utilities. These client utilities communicate through the server to collect and manage data gathered from the network, gen erate files based on collected historical data, collect alarms, and monitor and control OpenBSI commu nications.

Frequency Range0-10 kHz •
Input Voltage Range•
Internally sourced3.3 Vdc
Externally sourced3 Vdc to 24 Vdc
On state>1.65 V, Off state <1.65 V •

Communication engine for PC applications •

Input filter20 microSec for 10 kHz • 1 ms for 300 Hz LSC

Supports ControlWave and Network 3000 serial • and IP protocols

Input current : selectable 200 µA for low • power applications or 2.2 mA for in-plant noise immunity

RS 232, Dial-line, cellular, radio, satellite, and • Ethernet connections

Provides on-line download & signal variable • changes

Accumulator16 bit •

Allows network configuration through NetView •

PC and Network communication diagnostics •

200 µA input, all inputs ON: 0.004 watt

OPC Server for interfacing to most HMI • software

2.2 mA input, all inputs ON: 0.039 watt

Harvester collects historical data on request or • scheduled basis

OpenBSI

NetView is the basic configuration and application interface for all network operations. NetView uses a tree structure for network graphical display in the

Emerson’s OpenBSI (Open Bristol System Inter face) is a set of network setup, communication diag nostic, and data viewing utilities that provide access to both ControlWave and Network 3000 controllers and RTUs. OpenBSI is the only product available in the industry to bring such unique functionality and ease of use to the network level. At the core is the communication interface, written as a Windows communication server API through which other client applications communicate with the Bristol networks.

Emerson Process Management Wireless Gateway (Express) — OpenBSI diagram (page 6)
Fig. 3 · OpenBSI

OpenBSI supports both serial BSAP protocol and Ethernet Internet Protocol communication to ControlWave and Network 3000 RTUs and control lers.

Netview - Network configuration

Windows Explorer style. Network nodes can be added on-line by simply dragging the node Icon into the tree. This invokes a configuration Wizard simpli

Show 4 more labels / short text on this page
High Speed Counters · OpenBSI Utilities · Simply Creative · and application Launchpad
Page 7 of the Emerson Process Management Wireless Gateway (Express) user manual — Real-time ActiveX Controls
Page 7 · click to enlarge
Page 7

fying network setup. Through the NetView Wizard, the necessary network parameters are entered for node and IP address, alarm and message routing, and network communication media. Once config ured, selecting any node allows direct access to the common OpenBSI utilities to reprogram, download a new application to the node, review communication statistics, view real-time data through DataViewer, and edit controller/RTU properties.

Operators have the ability to alter signal values. Multiple DataView windows may be open simultane ously.

WebBSI - WebBSI is a powerful and flexible soft ware product bringing web technology to all Bristol automation and SCADA products. WebBSI includes a set of ActiveX Controls for reading and writing real-time and historical data, trending, recipe editing and custom display generation. Through these con

Local Configuration Wizard allows local commu

Emerson Process Management Wireless Gateway (Express) — Real-time ActiveX Controls diagram (page 7)
Fig. 4 · Real-time ActiveX Controls
Emerson Process Management Wireless Gateway (Express) — Real-time ActiveX Controls diagram (page 7)
Fig. 5 · Real-time ActiveX Controls

Custom built web page interface

using a standard web browser

Configuration Wizard simplifies Network setup

trols, you can use the standard Microsoft Internet Explorer web browser to access Network 3000, TeleFlow and ControlWave products through a set of supplied HTML web pages.

nication with any attached ControlWave controller or RTU to download system flashware upgrades, configure cold download parameters, and configure IP and soft-switch parameters.

Real-time ActiveX Controls

DataView is an on-line utility used to collect and display several types of process data, including sig nal values, data array values, signal lists, and audit trail information.

One of the many benefits OpenBSI brings to you is our use of open standards such as ActiveX Con trols. AcitveX is another of the Microsoft standards, which allow plug and play with any ActiveX con tainer, using Microsoft ActiveX container technol ogy such as Visual Basic, HTML web pages, and Microsoft Excel

Emerson Process Management Wireless Gateway (Express) — Real-time ActiveX Controls diagram (page 7)
Fig. 6 · Real-time ActiveX Controls

The set of available ActiveX Controls provides the basic functions necessary to communicate and col lect data from ControlWave.

DataView for Real-time data display

Page 8 of the Emerson Process Management Wireless Gateway (Express) user manual — Historical Data Collection
Page 8 · click to enlarge
Page 8

Another important historical feature is the Audit storage and collection system. The Audit Trail is a file stored in ControlWave flash memory containing significant events and time-stamped alarms. The alarms stored in the Audit system provide a histori cal archive in addition to the real-time alarm report ing system.

Security – 56-bit encryption - allows the user to • sign on to the RTU

Signal Value – displays signal values in various • formats

Comm Statistics – works with a standard page • that displays the RTU’s communication statistics

This file is also collected through OpenBSI and presented as a text file in the PC. This functionality is extremely useful in providing an event trail during communication or PC downtime or other system problem.

Configuration Info – works with a standard page • that displays and allows the user to change RTU Configuration information

Historical • – Collect and view historical archive and audit files

Archive Collection – collection and storage to • disk of the ControlWave archive data

The IP compliant ControlWave opens the door for owner controlled access via Web Pages. Any ge neric web page builder can be employed to create user defined pages to access ControlWave. The web pages are populated with these pre-configured ActiveX controls.

Audit Collection - collection and storage to disk • of the ControlWave audit data.

Exports data files to third party, .CSV & • ODBC applications

DDE compliant for use with other popular • Windows applications

Microsoft Internet Explorer •

Bristol ActiveX controls •

With industry demand for open standards, ControlWave answers the call by embracing tech nologies that open the door for maximizing your efficiency and productivity. The OPC standard was developed by the OPC Foundation comprised of hardware and software suppliers from the process control community. OPC allows the engineer to select best in class hardware and software with con fidence in their interoperability. Our OpenBSI OPC Server was among the first to comply with the OPC Foundation alarm and event server specification.

OpenBSI LocalView or NetView •

Historical Data Collection

High Historical Data Integrity

The ControlWave Historical Data Collection sys tem offers exceptional historical data integrity by providing time-stamped historical data storage in ControlWave flash memory. The historical data is collected, through OpenBSI on a scheduled or demand basis and converted to .CSV and ODBC compliant file formats for use in spreadsheets and reports. If data is missed due to a communication failure, it is collected when the communication is reestablished and the PC historical database is backfilled with the missing data. This distributed his torical database architecture provides the greatest data reliability and integrity during communication or PC failure.

OPC Data Access 1.0a & 2.0 compatible •

Compatible with both ControlWave and Network • 3000 systems

32 bit multi-threading, multi-processor design •

Automatic database builder •

Integrated real-time data monitor •

Show 4 more labels / short text on this page
ActiveX Controls · Required Software · OPC Server · WindowsXP •
Page 9 of the Emerson Process Management Wireless Gateway (Express) user manual — Historical Data Collection
Page 9 · click to enlarge
Page 9

Supports OPC Browse interface •

BSAP meets the definition of an industry-standard, open architecture protocol because it conforms to ISO standards 2629, 1745 and 2111, it is not propri etary in that Emerson does not charge a license fee and makes the protocol and documentation avail able to anyone.

Supports both serial comm and IP Ethernet • connections

Supports COM/DCOM & OLE Automation •

Primary and Background polling scheme •

While BSAP is an open protocol, the added func tionality of the messages provide much more capa bility than is found in other networks.

OPC Alarm & Event Server support •

ControlWave Open Network Connectivity

By embracing the open system network technolo gies available through TCP/IP, Ethernet, OPC, and Microsoft DNA, as well as pseudo standards such as Modbus and Open Modbus, ControlWave can provide a total Process Automation Management Solution for in-plant LAN based networks and Wide Area Network SCADA systems.

Time-stamped Alarm reporting •

Historical archive data transfer •

Audit file transfer •

On-line program editing •

With the exceptional connectivity provided by the ControlWave network, access to real-time data and operating conditions, historical data, maintenance and performance data are all available to the global network. ControlWave provides the needed informa tion to the plant floor technician, operator, engineer, supervisor and corporate management, even exter nal customers.

Modbus is often considered a de-facto standard pro tocol because of its broad usage as either the pri mary or a secondary offering in many measurement and control related products. Even with its common use, Modbus protocol actually has many variations. Consider Modbus RTU and Modbus ASCII, Master & Slave, Serial and TCP/IP Open Modbus. In addi tion there are considerations regarding supported function codes, floating point values and byte order. Bristol products support the following:

Like all of Emerson’s Bristol products, ControlWave supports BSAP (Bristol Standard Asynchronous Protocol), Modbus, DFI, CIP, DNP3, and serial ASCII as standard functions.

Modbus serial and TCP/IP Open Modbus • (Ethernet)

These protocols are implemented in Flashware so no additional hardware is required to use any one or a combination of all protocols.

Master and Slave •

Modbus RTU and ASCII •

Modes 1 - 7, 8, 15 & 16 •

BSAP is widely accepted as providing exceptional data integrity and greatly simplifies communication between controllers. BSAP is provided with interfac es for Master/Slave, vertical networks, and Client/ Server, horizontal networks. In either case, variable lists are created in each controller that are easily passed from server to client or slave to master.

IP modes 51, 52 & 53 •

Integer and IEEE 4 byte floating point •

Show 6 more labels / short text on this page
Global time-synchronization • · Diagnostics • · Communication statistics • · Modbus Protocol · Communication Protocols · BSAP Protocol
Page 10 of the Emerson Process Management Wireless Gateway (Express) user manual — Historical Data Collection
Page 10 · click to enlarge
Page 10

ControlWave was designed to provide the optimum level of data security using a distributed database architecture. All data including time & date stamped alarms, alarm limits, and historical data are stored locally in each industrially rugged ControlWave, thereby distributing your data integrity risk. To further ensure that the data is always current and historically accurate, the historical data is stored in non-volatile flash memory within ControlWave. Historical data is even maintained during and after program downloading.

The Generic Serial Interface is a user program mable Master and Slave protocol used to send and receive messages typically with third party serial ASCII devices. This protocol can be used to inter face with such devices and message boards, card readers and many measurement devices.

Security is an essential element of any open system, particularly those with Internet access. ControlWave employs a User Name/Password ac cess system protected by a 56-bit encryption tech nique through the TCP connection. There can be up to thirty-two users, who sign-in using their name and password. Both the name and the password can be up to sixteen characters.

When historical data is collected from ControlWave, it is converted and appended to .CSV and/or ODBC compliant databases but does not destroy the origi nal historical data stored in ControlWave, thus pro viding a flexible and secure historical data system that is clearly recognized as a benefit to virtually every industrial application.

The security system provides for up to sixty-four access rights to read and write data values and files via FTP, access and configure historical and audit data information, edit configuration, run internal diagnostics, read and reset system status. It further allows the programming software to read, write and download the ControlWave.

The Bridge Between Systems

Continuing our tradition of introducing innovative new solutions while maintaining compatibility with existing systems, Emerson again provides a migra tion path for existing customers by bridging the new ControlWave system with Network 3000 systems already in place. The network bridge is enabled by employing the open architecture technologies afforded by TCP/IP and OPC in both networks. TCP/IP allows seamless Ethernet connectivity to both networks as well as the corporate Intranet so both ControlWave and Network 3000 controllers can reside and communicate on the same LAN. Emerson’s Bristol OpenBSI OPC Server facilitates the merging of the two networks for technical, engi neering and operator data access. The data source, configuration and path are completely transparent to the OPC client. Real-time data can also be passed between the two communication networks making this a total Plant Automation Management Solution.

The Secure Data Advantage

ControlWave sets a new standard for providing in telligent control at the point where control is needed. Whether you need control on the plant floor or at a remote site in the “middle of nowhere” ControlWave is the solution for control, communication and secure data to help you make the right operating decisions.

© 2009 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.

Bristol, Inc., Bristol Canada, BBI SA de CV, the Flow Computer Division, and Emerson Process Management Ltd, Remote Automation Solutions division (UK) , are wholly owned sub sidiaries of Emerson Electric Co. doing business as Remote Automation Solutions (“RAS”), a division of Emerson Process Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid are trademarks of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric Co. All other marks are property of their respective owners.

The contents of this publication are presented for informational purposes only. While every effort has been made to ensure informational accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or specifications of such products at any time without notice. All sales are governed by RAS’ terms and conditions which are available upon request. RAS does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any RAS product remains solely with the purchaser and end-user.

Emerson Process Management Remote Automation Solutions

Watertown, CT 06795 USA T 1 (860) 945-2200 Mississauga, ON 06795 Canada T 1 (905) 362-0880 Worcester WR3 8YB UK T 44 (1) 905-856950

Generic Serial Interface · Multi-user Security Access

Page 11 of the Emerson Process Management Wireless Gateway (Express) user manual — Model Specification
Page 11 · click to enlarge
Page 11

Model Specification

A - B - C D - E - F G

Model NumberCWEXP - _ - _ - _ _ - _ - _ _
Emerson Process Management Wireless Gateway (Express) — Model Specification diagram (page 11)
Fig. 7 · Model Specification
DESCRIPTIONCODE APackagingA 10Basic RTU Panel Mount1 2 Basic RTU 35 MM DIN Rail Mount BCertificationB 20UL Class I DIV II1 2 UL, CE (With Protective Cover) C DProcessor (CPU board has 2 PI/DI & 3 serial ports)C D 30Advanced CPU with gas calculationsA1 A2 A3 30Standard CPU without gas calculationsS1 S2 S3 EI/O OptionsE 40None 2 PI/DI on Base CPU Base + 2 DI/DO, 4 DI, 2 DO, 2 HSC 2 PI/DI on Base CPU Base + 2 DI/DO, 4 DI, 2 DO, 2 HSC, 3 AI 2 PI/DI on Base CPU Base + 2 DI/DO, 4 DI, 2 DO, 2 HSC, 3 AI, 1 AO0 1 2 3
Emerson Process Management Wireless Gateway (Express) — Model Specification diagram (page 11)
Fig. 8 · Model Specification
Page 12 of the Emerson Process Management Wireless Gateway (Express) user manual — Model Specification, cont’d
Page 12 · click to enlarge
Page 12

Model Specification, cont’d

A - B - C D - E - F G

Model NumberCWEXP - _ - _ - _ _ - _ - _ _
DESCRIPTIONCODE F GApplication ProgramF G 50No application program00 Stock for quick shipmentP/N Quantities of 5 or less pre-configured models below will ship within 5 days Preconfigured P/Ns: Panel mt, C1D2, 33MHz w/o ENET, DI,DO,AI CWEXP-1-1-A2-2-00 Panel mt, C1D2, 33MHz w/o ENET, DI,DO,AI, AO CWEXP-1-1-A2-3-00 Panel mt, C1D2, 33MHz with ENET, DI,DO,AI, CWEXP-1-1-A3-2-00 Panel mt, C1D2, 33MHz with ENET, DI,DO,AI, AOCWEXP-1-1-A3-3-00396857-01-9 396857-02-7 396857-03-5 396857-04-3 Note 1: 9-pin ‘D’ connector for Comm port 1 cannot have a connector hood Use P/N 392843-03-0 for cable without hood.392843-03-0 Spare partsP/N Fuse Battery DIN rail mounting kit I/O terminal cover LED board 3 pin terminal block 4 pin terminal block 5 pin terminal block 6 pin power terminal block 8 pin terminal block 9 pin terminal block395603-07-2 395620-01-5 621584-02-9-Kit 621590-01-0-Kit 400098-01-6 395710-01-0 395710-03-0 395710-04-9 395710-07-3 395710-05-7 395710-06-5
Emerson Process Management Wireless Gateway (Express) — Model Specification, cont’d diagram (page 12)
Fig. 9 · Model Specification, cont’d
Emerson Process Management Wireless Gateway (Express) — Model Specification, cont’d diagram (page 12)
Fig. 10 · Model Specification, cont’d
Page 13 of the Emerson Process Management Wireless Gateway (Express) user manual — Model Specification, cont’d
Page 13 · click to enlarge
Page 13
Emerson Process Management Wireless Gateway (Express) — Model Specification, cont’d diagram (page 13)
Fig. 11 · Model Specification, cont’d

Ask about the Emerson Process Management Wireless Gateway (Express)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Process Management Wireless Gateway (Express)

Be the first to ask — other owners or our team will answer.

Original document

Emerson Process Management Wireless Gateway (Express) manual PDF

13 pages·511 KB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…