Rosemount 2051 Pressure Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol

Rosemount 2051CF Series Flowmeter Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol

Emerson Process Management Rosemount 2051CF — Rosemount 2051 Pressure Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol diagram (page 1)
Fig. 1 · Rosemount 2051 Pressure Transmitter with HART 4-20 m…

www.rosemount.com ¢00825-0100-4101¤

Page 2 of the Emerson Process Management Rosemount 2051CF user manual — WARNING
Page 2 · click to enlarge
Page 2

© 2010 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.

Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001

Emerson Process Management GmbH & Co. OHG Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390 F49 (8153) 939172 Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743

Beijing Rosemount Far East Instrument Co., Limited No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586

Emerson Process Management Rosemount 2051CF — Rosemount 2051 Pressure Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol diagram (page 2)
Fig. 2 · Rosemount 2051 Pressure Transmitter with HART 4-20 m…

This installation guide provides basic guidelines for Rosemount 2051 transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the 2051 reference manual (document number 00809-0100-4101) for more instruction. This manual is also available electronically on www.emersonprocess.com/rosemount

WARNING

Explosions could result in death or serious injury:

Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2051 reference manual for any restrictions associated with a safe installation.

  • Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
  • In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.

Process leaks may cause harm or result in death.

  • To avoid process leaks, only use the o-ring designed to seal with the corresponding flange adapter.

Electrical shock can result in death or serious injury.

  • Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
  • Unless marked, the conduit/cable entries in the transmitter housing use a 1 / 2 -14 NPT thread form. Only use plugs, adapters, glands or conduit with a compatible thread form when closing these entries.

Conduit/Cable Entries

Page 3 of the Emerson Process Management Rosemount 2051CF user manual — A. Applications
Page 3 · click to enlarge
Page 3

S TEP 1: M OUNT THE T RANSMITTER

A. Applications

Emerson Process Management Rosemount 2051CF — A. Applications diagram (page 3)
Fig. 3 · A. Applications
1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
Emerson Process Management Rosemount 2051CF — A. Applications diagram (page 3)
Fig. 4 · A. Applications
1. Place taps in the top or side of the line. 2. Mount beside or above the taps.
Emerson Process Management Rosemount 2051CF — A. Applications diagram (page 3)
Fig. 5 · A. Applications
1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Fill impulse lines with water.

Liquid Flow Applications · Gas Flow Applications · Steam Flow Applications

Page 4 of the Emerson Process Management Rosemount 2051CF user manual — B. Optional Mounting Brackets
Page 4 · click to enlarge
Page 4

STEP 1 CONTINUED...

B. Optional Mounting Brackets

When installing the transmitter to one of the optional mounting brackets, torque the bracket bolts to 125 in.-lbs. (0,9 N-m).

Emerson Process Management Rosemount 2051CF — B. Optional Mounting Brackets diagram (page 4)
Fig. 6 · B. Optional Mounting Brackets

(1) Panel bolts are customer supplied.

Page 5 of the Emerson Process Management Rosemount 2051CF user manual — C. Bolting Considerations
Page 5 · click to enlarge
Page 5

STEP 1 CONTINUED...

C. Bolting Considerations

If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.

Figure 1. Common Transmitter Assemblies

Emerson Process Management Rosemount 2051CF — C. Bolting Considerations diagram (page 5)
Fig. 7 · C. Bolting Considerations

4 x 1.75-in. (44 mm) 4 x 1.50-in. (38 mm)

Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Figure 2. If bolt material is not shown in Figure 2, contact the local Emerson Process Management representative for more information.

Use the following bolt installation procedure:

1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt. 2. Finger-tighten the bolts. 3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 2 for initial torque value. 4. Torque the bolts to the final torque value using the same crossing pattern. See Figure 2 for final torque value. 5. Verify that the flange bolts are protruding through the isolator plate before applying pressure.

Page 6 of the Emerson Process Management Rosemount 2051CF user manual — D. O-rings with Flange Adapters
Page 6 · click to enlarge
Page 6
Emerson Process Management Rosemount 2051CF — Step 1: Mount the Transmitter diagram (page 6)
Fig. 8 · Step 1: Mount the Transmitter

Figure 2. Torque values for the flange and flange adapter bolts

Bolt MaterialHead MarkingsInitial TorqueFinal Torque Carbon Steel (CS)B7M300 in.-lbs. 650 in.-lbs.

D. O-rings with Flange Adapters

Emerson Process Management Rosemount 2051CF — D. O-rings with Flange Adapters diagram (page 6)
Fig. 9 · D. O-rings with Flange Adapters

Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring

that is designed for its specific flange adapter, as shown below.

Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the o-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring.

Page 7 of the Emerson Process Management Rosemount 2051CF user manual — S TEP 3: S ET T HE J UMPERS
Page 7 · click to enlarge
Page 7

E. Inline Gage Transmitter Orientation

The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3.)

Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the contaminants can drain away.

Figure 3. Inline Gage Transmitter

Emerson Process Management Rosemount 2051CF — E. Inline Gage Transmitter Orientation diagram (page 7)
Fig. 10 · E. Inline Gage Transmitter Orientation

S TEP 2: C ONSIDER H OUSING R OTATION

To improve field access to wiring or to better view the optional LCD display:

1. Loosen the housing rotation set screw. 2. First rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit).
3. Retighten the housing rotation set screw.

Housing Rotation Set Screw

S TEP 3: S ET T HE J UMPERS

If alarm and security jumpers are not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off.

1. If the transmitter is installed, secure the loop, and remove power. 2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Reposition the jumper. Avoid contact with the leads and the terminals. See Figure 4 for the location of the jumper and the ON and OFF positions.
4. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements.

(5/64-inch)

Page 8 of the Emerson Process Management Rosemount 2051CF user manual — Step 2: Consider Housing Rotation
Page 8 · click to enlarge
Page 8

Figure 4. 2051 Transmitter Electronics Board

Emerson Process Management Rosemount 2051CF — Step 2: Consider Housing Rotation diagram (page 8)
Fig. 11 · Step 2: Consider Housing Rotation

4-20 mA HART Without LCD Meter With LCD Display

1-5 Vdc HART Low Power Without LCD Meter With LCD Display

Page 9 of the Emerson Process Management Rosemount 2051CF user manual — S TEP 4: C ONNECT THE W IRING AND P OWER
Page 9 · click to enlarge
Page 9

S TEP 4: C ONNECT THE W IRING AND P OWER

Use the following steps to wire the transmitter:

1. Remove the housing cover on the FIELD TERMINALS side. 2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the “–” terminal.

Figure 5. 4–20 mA HART Transmitter Wiring Diagrams

Emerson Process Management Rosemount 2051CF — S TEP 4: C ONNECT THE W IRING AND P OWER diagram (page 9)
Fig. 12

Figure 6. 1-5 Vdc HART Low Power Transmitter Wiring

P S Voltmeter e transient protection terminal block does not provide transient protection unle
  • 3. Ensure proper grounding. It is important that the instrument cable shield:
  • be trimmed close and insulated from touching the transmitter housing.
  • be connected to the next shield if cable is routed through a junction box.
  • be connected to a good earth ground at the power supply end.
Page 10 of the Emerson Process Management Rosemount 2051CF user manual — Step 4: Connect the Wiring and Power
Page 10 · click to enlarge
Page 10

Figure 7. Wiring

Emerson Process Management Rosemount 2051CF — Step 4: Connect the Wiring and Power diagram (page 10)
Fig. 13 · Step 4: Connect the Wiring and Power
4. Plug and seal unused conduit connections.
5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
6. Replace the housing cover.
Page 11 of the Emerson Process Management Rosemount 2051CF user manual — Power Supply for 1-5 Vdc HART Low Power
Page 11 · click to enlarge
Page 11

Power Supply for 4-20 mA HART

Transmitter operates on 10.5 - 42.4 Vdc. The dc power supply should provide power with less than two percent ripple.

Figure 8. Load Limitation

Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)

0 10.5 20 30 42.4

The Field Communicator requires a minimum loop resistance of 250 for communication.

The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.

Power Supply for 1-5 Vdc HART Low Power

Low power transmitters operate on 9–28 Vdc. The dc power supply should provide power with less than two percent ripple. The Vout load should be 100 kW or greater.

Show 4 more labels / short text on this page
Load (Ohms) · Operating · Region · Voltage (V dc)
Page 13 of the Emerson Process Management Rosemount 2051CF user manual — Zero Trim
Page 13 · click to enlarge
Page 13

S TEP 6: T RIM THE T RANSMITTER

Zero Trim

A zero trim is a single-point adjustment used for compensating mounting position effects. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.

There are two methods to compensate for mounting effects:

  • Field Communicator
  • Transmitter Zero Adjustment Buttons Select the appropriate method and follow instructions below.

Using the Field Communicator

If zero offset is within 3% of URL, follow the “Using the Field Communicator” instructions below. This zero trim will affect the 4-20 mA value, the HART PV, and the display value.

HART Fast Keys Steps 1, 2, 3, 3, 2 1. Equalize or vent the transmitter and connect Fieldbus communicator. 2. At the menu, input the Fast Key sequence. 3. Follow the commands to perform a zero trim.

Using the Transmitter Zero Adjustment Buttons

Using the Transmitter Zero Adjustment Buttons, the Lower Range Value (LRV) will be set to the pressure applied to the transmitter. This adjustment will affect the 4-20 mA value only. Perform the following steps to perform a rerange using the zero adjustment buttons.

1. Loosen the certifications label screw and slide the label to expose the zero adjustment buttons. See Figure 9. 2. Set the 4 mA point by pressing the zero button for 2 seconds. Verify that the output is 4 mA. The optional LCD will display ZERO PASS.

Figure 9. Zero and Span buttons

Emerson Process Management Rosemount 2051CF — Zero Trim diagram (page 13)
Fig. 14 · Zero Trim
Page 14 of the Emerson Process Management Rosemount 2051CF user manual — Configuration
Page 14 · click to enlarge
Page 14

S AFETY I NSTRUMENTED S YSTEMS

The following section applies to 2051 transmitters used in SIS applications.

DCS or safety logic solver must be configured to match transmitter configuration. Figure 10 identifies the two alarm level available and their operation values. Position the alarm switch to the required HI or LO alarm position.

Installation

No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal.

The loop must be designed so the terminal voltage does not drop below 10.5 Vdc when the transmitter output is 22.5 mA.

Position the security switch to the “ON” position to prevent accidental or deliberate change of configuration data during normal operation.

Configuration

Use any HART-compliant master to communicate with and verify configuration of the 2051.

User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value + response time must not exceed the loop requirements.

Figure 10. Alarm Levels

Emerson Process Management Rosemount 2051CF — Configuration diagram (page 14)
Fig. 15 · Configuration

(1) Transmitter Failure, hardware alarm in LO position. (2) Transmitter Failure, hardware alarm in HI position.

Page 15 of the Emerson Process Management Rosemount 2051CF user manual — Reference
Page 15 · click to enlarge
Page 15

Operation and Maintenance

Proof Test and Inspection

The following proof tests are recommended. Proof test results and corrective actions taken must be documented at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm in the event that an error is found in the safety functionality.

Use "Table 1: Field Communicator Fast Key Sequence" to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the 2051 reference manual (00809-0100-4101) for additional information.

This proof test will detect 99% of DU failures not detected by the 2051 automatic diagnostics. 1. Conduct a Loop Test. On HART host/communicator enter the Fast Key Sequence 1, 2, 2. a. Enter the milliampere value representing a high alarm state b. Check the reference meter to verify the mA output corresponds to the entered value. c. Enter the milliampere value representing a low alarm state d. Check the reference meter to verify the mA output corresponds to the entered value. 2. Perform a minimum two point sensor calibration check using the 4-20mA range points as the calibration points. a. If necessary, use one of the “Trim” procedures available in the 2051 reference manual

to calibrate.

Visual Inspection Not required.

Special Tools Not required

Product Repair All failures detected by the transmitter diagnostics or by the proof-test must be reported. Feedback can be submitted electronically at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm.

The 2051 is repairable by major component replacement. Follow the instructions in the 2051 reference manual (document number 00809-0100-4101) for additional information.

Reference

The 2051 must be operated in accordance to the functional and performance specifications provided in the 2051 reference manual.

The FMEDA report includes failure rates and common cause Beta factor estimates. This report is available at www.emersonprocess.com/rosemount

Proof Test · Specifications · Failure Rate Data

Page 16 of the Emerson Process Management Rosemount 2051CF user manual — Approved Manufacturing Locations
Page 16 · click to enlarge
Page 16

2051 Safety Failure Values

Safety accuracy2% (1)

Safety response time- 1.5 sec

50 years – based on worst case component wear-out mechanisms – not based on wear-out process wetted materials

P RODUCT C ERTIFICATIONS

Approved Manufacturing Locations

Emerson Process Management - Rosemount Inc. — Chanhassen, Minnesota, USA Emerson Process Management — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Emerson Process Management — Beijing, China Emerson Process Management — Daman, India European Directive Information

The EC declaration of conformity can be found on page 20. The most recent revision can be found at www.emersonprocess.com

Ordinary Location Certification for Factory Mutual As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

(1) A 2% variation of the transmitter mA output is allowed before a safety trip. Trip values in the DCS or Safety

Logic Solver should be derated by 2%.

Product Life

Page 17 of the Emerson Process Management Rosemount 2051CF user manual — HART Protocol
Page 17 · click to enlarge
Page 17

HART Protocol

Hazardous Locations Certifications

FM Approvals E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for

Class II, Division 1, Groups E, F, and G. Dust-Ignition-Proof for Class III, Division 1. T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4X I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount drawing 02051-1009; Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code:T4 (Ta = 70 °C), Enclosure Type 4X For input parameters see control drawing 02051-1009.

Canadian Standards Association (CSA) All CSA hazardous approved transmitters are certified per ANSI/ISA 12.27.01-2003.

E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for

Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X, factory sealed. Single Seal. I6 Intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawing 02051-1008. Temperature Code T3C. Class I Zone 1 Ex ia IIC T3C. Single Seal.

I1 ATEX Intrinsic Safety Certification No. Baseefa08ATEX0129X II 1 G Ex ia IIC T4 (–60 Ta +70 °C) IP66 IP68

Table 2. Input Parameters for 4-20 mA

Ui = 30V Ii = 200 mA Pi = 1.0W Ci = 0.012 µF

Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of EN60079-11. This must be taken into account when installing the apparatus.

North American Certifications · European Certifications

Page 18 of the Emerson Process Management Rosemount 2051CF user manual — Product Certifications
Page 18 · click to enlarge
Page 18

N1 ATEX Type n

Certification No. Baseefa08ATEX0130X II 3 G Ex nAnL IIC T4 (–40 Ta +70 °C) Ui = 42.4 Vdc max IP66

Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated. E1 ATEX Flame-Proof

Certification No. KEMA 08ATEX0090 X II 1/2 G Ex d IIC T6 (–50 Ta 65 °C) Ex d IIC T5 (–50 Ta 80 °C) IP66

1180 Vmax = 42.4 V dc Special Conditions for Safe Use (X):

1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints. ND ATEX Dust

Certification No. Baseefa08ATEX0182X II 1 D Dust Rating: Ex tD A20 T115 °C (–20 Ta 85 °C) Vmax = 42.4 V dc A = 22 mA

1180 Special Conditions for Safe Use (X):

1. The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 60079-1. 2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66. 4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

Page 19 of the Emerson Process Management Rosemount 2051CF user manual — Product Certifications
Page 19 · click to enlarge
Page 19

I7 IECEx Intrinsic Safety Certification No. IECExBAS08.0045X Ex ia IIC T4 (–60 Ta +70 °C)

Table 3. Input Parameters

Ui = 30V Ii = 200 mA Pi = 1.0W Ci = 0.012 µF

Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus. E7 IECEx Explosion-Proof (Flame-Proof)

Certification No. IECExKEM08.0024X Ex d IIC T6 (–50 Ta 65 °C) Ex d IIC T5 (–50 Ta 80 °C)

1180 Vmax = 42.4 V dc Special Conditions for Safe Use (X):

1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints. N7 IECEx Type n

Certification No. IECExBAS08.0046X Ex nAnL IIC T4 (–40 Ta +70 °C) Ui = 42.4 Vdc max

Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated.

IECEx Certifications

Page 20 of the Emerson Process Management Rosemount 2051CF user manual — Product Certifications
Page 20 · click to enlarge
Page 20

Ex d IIC T6

BR-Ex d IIC T6/T5 I2 Intrinsic Safety BR-Ex ia IIC T4 GOST (Russia) Certifications

Ex ia IIC T4 EM Flame-Proof

Ex d IIC T5/T6 China (NEPSI) Certifications E3 Flame-Proof

Certificate No: GYJ081230 Ex d IIC T5/T6 I3 Intrinsic Safety Certificate No: GYJ081231X Ex ia IIC T4

Loop / Power Groups Ui = 30V HART / FOUNDATION fieldbus / Remote Display / Quick Connect / HART Diagnostics Ui = 17.5 V FISCO Ii = 300 mA HART / FOUNDATION fieldbus / Remote Display / Quick Connect / HART Diagnostics Ii = 380 mA FISCO Pi = 1.0 W HART / Remote Display / Quick Connect / HART Diagnostics Pi = 1.3 W FOUNDATION fieldbus Pi = 5.32 W FISCO Ci = 0.012 µF HART Ci = 0 FOUNDATION fieldbus / FISCO Li = 0 FOUNDATION fieldbus Li = 10 µH HART

Emerson Process Management Rosemount 2051CF — Product Certifications diagram (page 20)
Fig. 16 · Product Certifications

Ex d IIC T5 or T6 IW Intrinsic Safety

Ex ia IIC T4

Show 7 more labels / short text on this page
TIIS Certifications · E4 TIIS Flame-Proof · Inmetro Certifications · E2 Flame-Proof · IM Intrinsic Safety · CCoE Certifications · EW Flame-Proof
Page 21 of the Emerson Process Management Rosemount 2051CF user manual — Product Certifications
Page 21 · click to enlarge
Page 21

Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.

K1 E1, I1, N1, and ND combination

K4 E4 and I4 combination

K5 E5 and I5 combination

K6 I6 and E6 combination

K7 E7, I7, and N7 combination

KA E1, I1, E6, and I6 combination

KB E5, I5, E6, and I6 combination

KC E1, I1, E5, and I5 combination

KD E1, I1, E5, I5, E6, and I6 combination

Combinations of Certifications

Page 22 of the Emerson Process Management Rosemount 2051CF user manual — EC Declaration of Conformity
Page 22 · click to enlarge
Page 22
Emerson Process Management Rosemount 2051CF — EC Declaration of Conformity diagram (page 22)
Fig. 17 · EC Declaration of Conformity
Page 23 of the Emerson Process Management Rosemount 2051CF user manual — EC Declaration of Conformity
Page 23 · click to enlarge
Page 23
Emerson Process Management Rosemount 2051CF — EC Declaration of Conformity diagram (page 23)
Fig. 18 · EC Declaration of Conformity
Page 24 of the Emerson Process Management Rosemount 2051CF user manual — EC Declaration of Conformity
Page 24 · click to enlarge
Page 24
Emerson Process Management Rosemount 2051CF — EC Declaration of Conformity diagram (page 24)
Fig. 19 · EC Declaration of Conformity
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson Process Management Rosemount 2051CF

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Process Management Rosemount 2051CF

Be the first to ask — other owners or our team will answer.

Original document

Emerson Process Management Rosemount 2051CF manual PDF

24 pages·2.7 MB·Carbon Monoxide Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…