Rosemount 2051 Pressure Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol
Rosemount 2051CF Series Flowmeter Transmitter with HART 4-20 mA and HART 1-5 Vdc Low Power Protocol


© 2010 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001
Emerson Process Management GmbH & Co. OHG Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390 F49 (8153) 939172 Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743
Beijing Rosemount Far East Instrument Co., Limited No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586

This installation guide provides basic guidelines for Rosemount 2051 transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the 2051 reference manual (document number 00809-0100-4101) for more instruction. This manual is also available electronically on www.emersonprocess.com/rosemount
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2051 reference manual for any restrictions associated with a safe installation.
Process leaks may cause harm or result in death.
Electrical shock can result in death or serious injury.
Conduit/Cable Entries




Liquid Flow Applications · Gas Flow Applications · Steam Flow Applications

STEP 1 CONTINUED...
When installing the transmitter to one of the optional mounting brackets, torque the bracket bolts to 125 in.-lbs. (0,9 N-m).

(1) Panel bolts are customer supplied.

STEP 1 CONTINUED...
If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 1. Common Transmitter Assemblies

4 x 1.75-in. (44 mm) 4 x 1.50-in. (38 mm)
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Figure 2. If bolt material is not shown in Figure 2, contact the local Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt. 2. Finger-tighten the bolts. 3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 2 for initial torque value. 4. Torque the bolts to the final torque value using the same crossing pattern. See Figure 2 for final torque value. 5. Verify that the flange bolts are protruding through the isolator plate before applying pressure.


Figure 2. Torque values for the flange and flange adapter bolts

Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring
that is designed for its specific flange adapter, as shown below.
Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the o-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring.

The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3.)
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the contaminants can drain away.
Figure 3. Inline Gage Transmitter

To improve field access to wiring or to better view the optional LCD display:
Housing Rotation Set Screw
If alarm and security jumpers are not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off.
(5/64-inch)

Figure 4. 2051 Transmitter Electronics Board

4-20 mA HART Without LCD Meter With LCD Display
1-5 Vdc HART Low Power Without LCD Meter With LCD Display

Use the following steps to wire the transmitter:
Figure 5. 4–20 mA HART Transmitter Wiring Diagrams

Figure 6. 1-5 Vdc HART Low Power Transmitter Wiring

Figure 7. Wiring


Transmitter operates on 10.5 - 42.4 Vdc. The dc power supply should provide power with less than two percent ripple.
Figure 8. Load Limitation
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
0 10.5 20 30 42.4
The Field Communicator requires a minimum loop resistance of 250 for communication.
The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
Low power transmitters operate on 9–28 Vdc. The dc power supply should provide power with less than two percent ripple. The Vout load should be 100 kW or greater.


A zero trim is a single-point adjustment used for compensating mounting position effects. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.
There are two methods to compensate for mounting effects:
Using the Field Communicator
If zero offset is within 3% of URL, follow the “Using the Field Communicator” instructions below. This zero trim will affect the 4-20 mA value, the HART PV, and the display value.
HART Fast Keys Steps 1, 2, 3, 3, 2 1. Equalize or vent the transmitter and connect Fieldbus communicator. 2. At the menu, input the Fast Key sequence. 3. Follow the commands to perform a zero trim.
Using the Transmitter Zero Adjustment Buttons
Using the Transmitter Zero Adjustment Buttons, the Lower Range Value (LRV) will be set to the pressure applied to the transmitter. This adjustment will affect the 4-20 mA value only. Perform the following steps to perform a rerange using the zero adjustment buttons.
Figure 9. Zero and Span buttons


The following section applies to 2051 transmitters used in SIS applications.
DCS or safety logic solver must be configured to match transmitter configuration. Figure 10 identifies the two alarm level available and their operation values. Position the alarm switch to the required HI or LO alarm position.
No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal.
The loop must be designed so the terminal voltage does not drop below 10.5 Vdc when the transmitter output is 22.5 mA.
Position the security switch to the “ON” position to prevent accidental or deliberate change of configuration data during normal operation.
Use any HART-compliant master to communicate with and verify configuration of the 2051.
User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value + response time must not exceed the loop requirements.
Figure 10. Alarm Levels

(1) Transmitter Failure, hardware alarm in LO position. (2) Transmitter Failure, hardware alarm in HI position.

Proof Test and Inspection
The following proof tests are recommended. Proof test results and corrective actions taken must be documented at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm in the event that an error is found in the safety functionality.
Use "Table 1: Field Communicator Fast Key Sequence" to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the 2051 reference manual (00809-0100-4101) for additional information.
This proof test will detect 99% of DU failures not detected by the 2051 automatic diagnostics. 1. Conduct a Loop Test. On HART host/communicator enter the Fast Key Sequence 1, 2, 2. a. Enter the milliampere value representing a high alarm state b. Check the reference meter to verify the mA output corresponds to the entered value. c. Enter the milliampere value representing a low alarm state d. Check the reference meter to verify the mA output corresponds to the entered value. 2. Perform a minimum two point sensor calibration check using the 4-20mA range points as the calibration points. a. If necessary, use one of the “Trim” procedures available in the 2051 reference manual
to calibrate.
Visual Inspection Not required.
Special Tools Not required
Product Repair All failures detected by the transmitter diagnostics or by the proof-test must be reported. Feedback can be submitted electronically at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm.
The 2051 is repairable by major component replacement. Follow the instructions in the 2051 reference manual (document number 00809-0100-4101) for additional information.
The 2051 must be operated in accordance to the functional and performance specifications provided in the 2051 reference manual.
The FMEDA report includes failure rates and common cause Beta factor estimates. This report is available at www.emersonprocess.com/rosemount
Proof Test · Specifications · Failure Rate Data

2051 Safety Failure Values
Safety response time- 1.5 sec
50 years – based on worst case component wear-out mechanisms – not based on wear-out process wetted materials
Emerson Process Management - Rosemount Inc. — Chanhassen, Minnesota, USA Emerson Process Management — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Emerson Process Management — Beijing, China Emerson Process Management — Daman, India European Directive Information
The EC declaration of conformity can be found on page 20. The most recent revision can be found at www.emersonprocess.com
Ordinary Location Certification for Factory Mutual As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
(1) A 2% variation of the transmitter mA output is allowed before a safety trip. Trip values in the DCS or Safety
Logic Solver should be derated by 2%.
Product Life

Hazardous Locations Certifications
FM Approvals E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for
Class II, Division 1, Groups E, F, and G. Dust-Ignition-Proof for Class III, Division 1. T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4X I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount drawing 02051-1009; Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code:T4 (Ta = 70 °C), Enclosure Type 4X For input parameters see control drawing 02051-1009.
Canadian Standards Association (CSA) All CSA hazardous approved transmitters are certified per ANSI/ISA 12.27.01-2003.
E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for
Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X, factory sealed. Single Seal. I6 Intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawing 02051-1008. Temperature Code T3C. Class I Zone 1 Ex ia IIC T3C. Single Seal.
I1 ATEX Intrinsic Safety Certification No. Baseefa08ATEX0129X II 1 G Ex ia IIC T4 (–60 Ta +70 °C) IP66 IP68
Table 2. Input Parameters for 4-20 mA
Ui = 30V Ii = 200 mA Pi = 1.0W Ci = 0.012 µF
Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of EN60079-11. This must be taken into account when installing the apparatus.
North American Certifications · European Certifications

N1 ATEX Type n
Certification No. Baseefa08ATEX0130X II 3 G Ex nAnL IIC T4 (–40 Ta +70 °C) Ui = 42.4 Vdc max IP66
Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated. E1 ATEX Flame-Proof
Certification No. KEMA 08ATEX0090 X II 1/2 G Ex d IIC T6 (–50 Ta 65 °C) Ex d IIC T5 (–50 Ta 80 °C) IP66
1180 Vmax = 42.4 V dc Special Conditions for Safe Use (X):
1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints. ND ATEX Dust
Certification No. Baseefa08ATEX0182X II 1 D Dust Rating: Ex tD A20 T115 °C (–20 Ta 85 °C) Vmax = 42.4 V dc A = 22 mA
1180 Special Conditions for Safe Use (X):
1. The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 60079-1. 2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66. 4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

I7 IECEx Intrinsic Safety Certification No. IECExBAS08.0045X Ex ia IIC T4 (–60 Ta +70 °C)
Table 3. Input Parameters
Ui = 30V Ii = 200 mA Pi = 1.0W Ci = 0.012 µF
Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus. E7 IECEx Explosion-Proof (Flame-Proof)
Certification No. IECExKEM08.0024X Ex d IIC T6 (–50 Ta 65 °C) Ex d IIC T5 (–50 Ta 80 °C)
1180 Vmax = 42.4 V dc Special Conditions for Safe Use (X):
1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints. N7 IECEx Type n
Certification No. IECExBAS08.0046X Ex nAnL IIC T4 (–40 Ta +70 °C) Ui = 42.4 Vdc max
Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated.
IECEx Certifications

Ex d IIC T6
BR-Ex d IIC T6/T5 I2 Intrinsic Safety BR-Ex ia IIC T4 GOST (Russia) Certifications
Ex ia IIC T4 EM Flame-Proof
Ex d IIC T5/T6 China (NEPSI) Certifications E3 Flame-Proof
Certificate No: GYJ081230 Ex d IIC T5/T6 I3 Intrinsic Safety Certificate No: GYJ081231X Ex ia IIC T4
Loop / Power Groups Ui = 30V HART / FOUNDATION fieldbus / Remote Display / Quick Connect / HART Diagnostics Ui = 17.5 V FISCO Ii = 300 mA HART / FOUNDATION fieldbus / Remote Display / Quick Connect / HART Diagnostics Ii = 380 mA FISCO Pi = 1.0 W HART / Remote Display / Quick Connect / HART Diagnostics Pi = 1.3 W FOUNDATION fieldbus Pi = 5.32 W FISCO Ci = 0.012 µF HART Ci = 0 FOUNDATION fieldbus / FISCO Li = 0 FOUNDATION fieldbus Li = 10 µH HART

Ex d IIC T5 or T6 IW Intrinsic Safety
Ex ia IIC T4

Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
K1 E1, I1, N1, and ND combination
K4 E4 and I4 combination
K5 E5 and I5 combination
K6 I6 and E6 combination
K7 E7, I7, and N7 combination
KA E1, I1, E6, and I6 combination
KB E5, I5, E6, and I6 combination
KC E1, I1, E5, and I5 combination
KD E1, I1, E5, I5, E6, and I6 combination
Combinations of Certifications