7000 Series ADTS Automatic Delayed–Transition Transfer Switches

Operator’s

Manual

E–design 150–400A, F–design 600–800A, G–design 1000–4000A, F–design 3000–4000A,

TABLE OF CONTENTS

INSTALLATION 1-1 Mounting and Line Connections 1-1 Auxiliary Circuits and Harness 1-2 Engine Starting Contacts 1-2 Functional Test 1-2, 1-3, 1-4, 1-5

of possible personal injury.

TESTING & SERVICE 2-1 Transfer Test 2-1 Preventive Maintenance 2-1 Disconnecting the Controller 2-1 Manual Load Transfer 2-2 Trouble-Shooting 2-2

of possible equipment damage.

Refer to Group 5 Controller User’s Guide 381333–126 for ATS status display messages, time delays, pickup & dropout settings, and adjustments.

INDEX back cover

An experienced licensed electrician must install the ADTS.

Refer to the outline and wiring drawings provided with your 7000 Series ADTS for all installation and connection details and accessories.

Emerson FDESIGN 600800A — TABLE OF CONTENTS diagram (page 1)
Fig. 1
Emerson FDESIGN 600800A — TABLE OF CONTENTS diagram (page 1)
Fig. 2

G design 4000 A

G design 2000 A

381333–129 C 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com

ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3

section-page

Page 2 of the Emerson FDESIGN 600800A user manual — H 380
Page 2 · click to enlarge
Page 2

Catalog Number Identification Typical 7000 Series catalog no. for G–design switched neutral, 3 pole, 2000 A, 480 V, ADTS in Type 1 enclosure:

7ADTS B 3 2000 N 5 C

Neutral Phase Poles Amperes A – solid 2 – single Ø 150 1000 B 3 260 1200 – switched – three Ø 400 1600 600 2000 blank – none 800 3000 4000 Amperes 150 260 400 600 8001000 1200 1600 2000 3000 4000

A 115

J 400

5. standard

C – type 1

K 415

F – type 3R

G – type 4

L – type 12

D 220

M 460

E 230

N 480

M –type 3R secure

G 277 F 240

Q 575 P 550

N –type 4 secure P –type 4X secure Q –type 12 secure

H 380

R 600

blank – open type

Emerson FDESIGN 600800A — H 380 diagram (page 2)
Fig. 3

field connections terminal block TB

G–design 2000 ampere size in typical enclosure with location of customer connections

Show 9 more labels / short text on this page
accessories · ordered · Group 5 Controller · power connections · Transfer · Control & lights · Transfer · Switch · power connections
Page 3 of the Emerson FDESIGN 600800A user manual — Rating Label
Page 3 · click to enlarge
Page 3

Rating Label

Nameplate The Transfer Switch nameplate includes data for each specific 7000 Series ADTS. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is shown on the previous page with its elements explained.

Each automatic delayed–transition transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.

Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.

Emerson FDESIGN 600800A — Rating Label diagram (page 3)
Fig. 4 · Rating Label

field connections terminal block TB

G–design 4000 ampere size in typical enclosure with location of customer connections

Transfer · Switch · Group 5 Controller

Page 4 of the Emerson FDESIGN 600800A user manual — Line Connections
Page 4 · click to enlarge
Page 4

SECTION 1 INSTALLATION

ASCO Series 7000 Automatic Delayed–Transition Transfer Switches are factory wired and tested. Field installation simply requires mounting and connection of service cables, and auxiliary control circuits (if required).

De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.

Remove the Shipping Skid

For large switches, open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.

Testing Power Conductors

Supporting Foundation

Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.

The supporting foundation for the enclosure must level and straight. Refer to the applicable enclosure outline drawing included with the ADTS for all mounting details including door opening space.

If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.

Connecting Power Conductors

After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the switch. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.

Mounting

Refer to the outline and mounting diagram provided with the ADTS; it shows all mounting details and instructions.

Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the automatic switch switch.

Mount the ADTS vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the switch.

Do not run cables in front of or behind the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum for 150-400 amps, 1 inch minimum over 400 amps.

The controller is mounted on the cabinet door. An add-on DIN rail is provided for some optional accesso- ries and is mounted below controller on the door.

Auxiliary Cable Boxes

It is not necessary to remove the barriers from the transfer switches to install the cables. If you do remove them,however, be sure to reinstall the barriers carefully.

For 1000 & 1200 amp. sizes, an auxiliary cable box is required for all (normal, emergency, & load)bottom or top entry. Order ASCO part no. 609027 if required.

Bus Connections

For large switches use grade 5 hardware to connect bus to appropriate terminal plates. Wipe off the bus surfaces before they are joined. If the bus is very dirty, gently clean the surfaces with a non---flammable solvent. Avoid touching the cleaned surfaces.

On 1000 & 1200 amp. be sure to install auxiliary cable box if both service and load cables are en- tering through the top or bottom of enclosure.

Line Connections

A Wiring Diagram is furnished with the ASCO Series 7000 ADTS (separate from this manual). Refer to this drawing. All wiring must be made in accordance with the National Electrical Code and local codes.

Do not breathe cleaning solvent vapors.

Page 5 of the Emerson FDESIGN 600800A user manual — Functional Test
Page 5 · click to enlarge
Page 5

Tighten bolted joints to the torque specified in Table A.

Engine Starting Contacts The engine control contact connections (if used) are located on the transfer switch. Connect signal wires to appropriate terminals as specified in Table B and shown in Figure 1---1.

The reliablility of the connection depends

on how clean and how tight the joint is.

Table B. Engine start connections

Table A. Tightening torque values for bolted joints

When normal source failsTerminals on transfer switch contact closesTB1 and TB2 contact opensTB1 and TB3
Bolt Diameter in inchesTightening Torque in foot pounds 1/47 5/1612 3/820 1/250 5/895 3/4155
Emerson FDESIGN 600800A — 129c1 diagram (page 5)
Fig. 5 · 129c1

Controller Ground

A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the control panel by a plug-in harness (two plugs).

Auxiliary Circuits

Connect auxiliary circuit wires to appropriate terminals on the transfer switch. Note the control features that are furnished on this switch. Make the necessary auxiliary connections by referring to the Wiring Diagram.

Figure 1-1. Customer terminal block

on the top right side of enclosure.

Functional Test

The Functional Test consists of three checks:

Read all instructions on the Wiring Diagram and labels affixed to the ADTS. Note the control features that are provided and review their operation before proceeding.

V 1 — Manual Operation Test, page 1–3

V 2 — Voltage Checks, page 1–4

Continue to 1 – Manual Operation Test on next page.

V 3 — Electrical Operation, page 1–5

Do these checks in the order presented

to avoid damaging the ATS.

Show 4 more labels / short text on this page
(Grade 5 hardware) · engine start connections · on customer · terminal block TB
Page 6 of the Emerson FDESIGN 600800A user manual — 1 – Manual Operation
Page 6 · click to enlarge
Page 6
Emerson FDESIGN 600800A — 129c1 diagram (page 6)
Fig. 6 · 129c1
Emerson FDESIGN 600800A — 129c1 diagram (page 6)
Fig. 7 · 129c1
Emerson FDESIGN 600800A — 129c1 diagram (page 6)
Fig. 8 · 129c1

Figure 1-2. Figure 1-3. Figure 1-4 150 – 400 A (3 pole) 600 & 800 A (& 4 pole 400 A) 3000 & 4000 A E–design switches F–design switches F–design transfer switches

1 – Manual Operation

1000 through 4000 A G–design See Figure 1-5. Install the hub (with pin) onto the shaft and insert the manual firmly into the side hole in the hub. Push in or pull out hub to engage opposite source contacts.

A detachable manual operator handle is provided on the Transfer Switches for maintenance purposes only. Manual operation of both CN and CE transfer switches must be checked before they are operated electrically.

3000 and 4000 A F–design See Figure 1-4. Insert the manual handle into the hole in the weight.

2. Move the handle as shown to manually operate the Transfer Switch. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris. Repeat the manual operation check on the other Transfer Switch.

Do not manually operate the transfer switch

until both power sources are disconnected:

open both circuit breakers.

1. Select the appropriateswitch amperagesize aboveand follow the directions for installing the handle:
3. Return the CN Transfer Switch to the C (closed) position. Return the CE Transfer Switch to the O (open) position. Remove manual operator handle and store it on the Transfer Switch in the place provided.

150 through 400 A E–design See Figure 1-2. Insert the manual handle into the hole in the shaft, left side of the operator.

600 and 800 A F–design See Figure 1-3. Attach the manual handle onto the pivot shaft extension, left side of the operator.

Verify that the maintenance handle has been removed and stored properly before proceeding!

Now continue to 2 – Voltage Checks on next page.

Turn counterclockwise to OPEN contacts.

into hole (spring fully compressed)

Emerson FDESIGN 600800A — 1 – Manual Operation diagram (page 6)
Fig. 9 · 1 – Manual Operation

Grasp handle firmly with both hands

Turn clockwise to CLOSE contacts.

Slide the hub onto the shaft and insert the pin.

counterclockwise DOWN OPENS the contacts Pull out shaft to open Emergency source contacts (upper) Push in shaft to open Normal source contacts (lower)

clockwise DOWN OPENS the contacts Pull out shaft to close Emergency source contacts (upper) Push in shaft to close Normal source contacts (lower)

contact position indicators (left side)

Figure 1-5. 1000 – 4000 ampere G–design transfer switches.

Show 9 more labels / short text on this page
handle · shafts · handle · handle · Insert handle · Emergency contacts · window indicators · OPEN or CLOSED · Normal contacts
Page 7 of the Emerson FDESIGN 600800A user manual — 2 – Voltage Checks
Page 7 · click to enlarge
Page 7
Emerson FDESIGN 600800A — 129c1 diagram (page 7)
Fig. 10 · 129c1
Emerson FDESIGN 600800A — 129c1 diagram (page 7)
Fig. 11 · 129c1

GREEN

RED

RED GREEN

AMBER

Figure 1-6. Standard controls and indicators.

1Close the normal source circuit breaker. The Transfer Switch Connected To Normal and the Normal Source Accepted lights should come on.Load Disconnect Active 2Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch normal source terminals. 3Close the emergency source circuit breaker. (Start generator, if necessary.) The Transfer Switch Connected To Normal & Emergency Source Accepted lights should come on.Load Disconnect Active 4Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch emergency source terminals.* 5Use a phase rotation meter to check phase rotation of emergency source; it must be the same as the normal source.A B C 6Shut down the engine–generator, if applicable. The Emergency Source Accepted light should go off. Then put the starting control selector switch (on the generator set) in the automatic position. Close enclosure door.Load Disconnect Active
Emerson FDESIGN 600800A — GREEN diagram (page 7)
Fig. 12

2 – Voltage Checks

First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.

Before energizing the switch check to be sure that both normal and emergency contacts are not left in the closed position.

Emerson FDESIGN 600800A — 2 – Voltage Checks diagram (page 7)
Fig. 13 · 2 – Voltage Checks

Verify that the feeders have been connected to the proper lugs.

Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–6.

Q Black square means light is on.

S White square means light is off.

* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switch will respond only to the rated voltage specified on the Transfer Switch nameplate.

Emerson FDESIGN 600800A — 2 – Voltage Checks diagram (page 7)
Fig. 14 · 2 – Voltage Checks

Now continue to 3 – Electrical Operation on next page.

observe these lights

Page 8 of the Emerson FDESIGN 600800A user manual — Transfer Test
Page 8 · click to enlarge
Page 8

GREEN

RED

RED GREEN

AMBER

Figure 1-7. Standard controls and indicators.

1Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs (within 15 sec.). The Emergency Source Accepted light should come on.Load Disconnect Active 2Transfer switch CN opens and the Transfer Switch Connected to Normal light should go off and the Load Disconnect Active light should come on. Both CN & CE contacts are now open.Load Disconnect Active 3After the delay transition time delay, the CE Transfer switch will operate to the Emergency position. The Transfer Switch Connected To Emergency light should come on and Load Disconnect Active light goes off.Load Disconnect Active 4Transfer switch will operate back to Normal position after Feature 3A time delay. For immediate retransfer turn Transfer Control counterclockwise to Retransfer Delay Bypass. The Transfer Switch Connected To Normal light should come on; Transfer Switch Connected to Emergency light should go off.Load Disconnect Active 5The engine–generator will stop after the Feature 2E time delay (unloaded running engine cooldown). The Emergency Source Accepted light should go off.Load Disconnect Active
Emerson FDESIGN 600800A — GREEN diagram (page 8)
Fig. 15

3 --- Electrical Operation

This procedure will check the electrical operation of the Automatic Delayed–Transition Transfer Switch. See Figure 1---7.

Emerson FDESIGN 600800A — 3 --- Electrical Operation diagram (page 8)
Fig. 16 · 3 --- Electrical Operation

Close the enclosure door first !

Transfer Test

Emerson FDESIGN 600800A — Transfer Test diagram (page 8)
Fig. 17 · Transfer Test

Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.

Perform steps 1 through 5 at the right. Observe the status lights.

Q Black square means light is on.

Emerson FDESIGN 600800A — Transfer Test diagram (page 8)
Fig. 18 · Transfer Test

S White square means light is off.

Emerson FDESIGN 600800A — Transfer Test diagram (page 8)
Fig. 19 · Transfer Test

This completes the Functional Test of the ADTS.

observe these lights · operate this switch

Page 9 of the Emerson FDESIGN 600800A user manual — REPLACEMENT PARTS
Page 9 · click to enlarge
Page 9

SECTION 2 TESTING & SERVICE

TRANSFER TEST

DISCONNECTING THE CONTROLLER

Operate the 7000 Series ADTS at least once a month by following the five–step Electrical Operation Transfer Test procedure on page 1–5.

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the control panel must be isolated, follow these steps:

PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ADTS. An annual preventive maintenance program is recom- mended.

Do not unplug the controller until steps 1a or 1b is completed.

ASCO Services, Inc. (ASI) is ASCO Power Technologies’ national service organization. ASI can be contacted at 1-800-800-2726 for information on preventive maintenance agreements.

1. Observe the position of the transfer switch. a. If the transfer switch is in the Normal position,

place standby engine starting control in the off position. Then open the emergency source circuit breaker.

Checklist for Yearly Inspection

b. If the transfer switch is in the Emergency

position, open the normal source circuit breaker. Place the engine starting control in the test or run position.

Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal – Emergency power sources before performing inspections!

2. Separate the two quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.

j Clean the ADTS enclosure. Brush and vacuum

away any excessive dust accumulation. Remove any moisture with a clean cloth. j Check the transfer switch contacts. Remove

Do not unplug the controller until steps 1a or 1b is completed.

transfer switch barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully. j Maintain transfer switch lubrication. If switch is

1. Observe the position of the transfer switch. a. If the transfer switch is in the Normal position,

subjected to severe dust or abnormal operating conditions, renew factory lubrication on all move- ments and linkages. Relubricate solenoid operator if TS coil is replaced. Don’t use oil; order lubrica- tion kit 75-100. j Check all cable connections & retighten them.

be sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open. b. If the transfer switch is in the Emergency

position, normal source circuit breaker still should be open.

2. The two harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until both latches click.

REPLACEMENT PARTS

Replacement parts are available in kit form. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch nameplate. Contact your local ASCO Power Technolo- gies Sales Office or ASI:

3. Restore the opposite source as follows: a. If the transfer switch is in the Normal position,

place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker. b. If the transfer switch is in the Emergency

call 1 – 800 – 800 – ASCO ( 2726 )

position, close the normal source circuit breaker.

Disconnecting the Plugs · Reconnecting the Plugs

Page 10 of the Emerson FDESIGN 600800A user manual — TROUBLE-SHOOTING
Page 10 · click to enlarge
Page 10

TESTING & SERVICE

MANUAL LOAD TRANSFER

2. Use manual handle to manually operate transfer switch to the opposite source. First open the closed transfer switch, then close the other transfer switch.

This procedure will manually transfer the load if the control panel is disconnected.

3. Thenremovethemaintenancehandle. See page1–3.

Do not manually operate the transfer switch until both power sources are disconnected (all conductors deenergized).

Verify that the maintenance handle has been removed before proceeding!

1. Deenergize both the normal and emergency source conductors (remove fuses or open circuit breakers).
4. If the transfer switch is in the Emergency position manually start the engine generator and then install emergency source fuse or close the circuit breaker.

TROUBLE-SHOOTING

Hazardous voltage capable of causing shock, burns, or death is used in this switch. Do not touch the power or load terminals of the transfer switch!

Table 2-1. Trouble-Shooting Checks.

CHECK IN NUMERICAL SEQUENCE PROBLEM1 OPERATION2 GEN-SET3 VOLTAGE Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails.Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting.Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.--- Transfer switch does not transfer the load to the emergency source after the engine–generator set starts.Wait for Feature 2B time delay to time out.Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (57 Hz for a 60 Hz system.) *Voltmeter should read at least 90% of nominal phase to phase voltage between terminals EA and EC (or EL1 and EL2 for 2 pole switches)* Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.Wait for Feature 3A time delay to time out.---Voltmeter should read at least 90% of nominal phase to phase voltage between terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches). Gen. does not stop after load retransfer to normal source.Wait for Feature 2E time delay to time out.Starting control must be in the automatic position.---

* These are factory settings. Refer to Controller User’s Guide. If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI at 1–800–800–2726. Furnish the Serial No. and Catalog No. from the transfer switch nameplate.

(continued)

Page 11 of the Emerson FDESIGN 600800A user manual — 129c2
Page 11 · click to enlarge
Page 11
Page 11 of the Emerson FDESIGN 600800A user manual — 129c2
Page 12 of the Emerson FDESIGN 600800A user manual — HELP
Page 12 · click to enlarge
Page 12

INDEX

A

O operation

auxiliary cable box, 1–1

electrical, 1–5 manual, 1–3

illustration of, 1–3 warning, 1–3 sequence of, 2–1 optional accessories

B

see Controller User’s Guide

P parts, 2–1 phase rotation check, 1–4 problem, 2–2

engine start contacts, 1–2 rating, cover

lugs, 1–2 preparation, 1–2

R

rating label, cover replacement parts, 2–1

Load Disconnect Active light, 1–5

S settings

see Controller User’s Guide

disconnecting, 2–1 see Controller User’s Guide

M

T test, functional, 1–2, 1–3, 1–4, 1–5 time delays, 2–1

E

see Controller User’s Guide Transfer Control selector switch

manual load transfer, 3–2

Retransfer Delay Bypass, 1–5 Transfer Test, 1–5 Transfer Switch Connected to

Emergency Source Accepted light, 1–5

F

Emergency light, 1–5 Transfer Switch Connected to Normal

light, 1–4, 1–5 transfer test, 1–5 transfer to emergency, 1–5 transfer to normal, 1–5, 2–1 trouble–shooting, 2–2

functional test, 1–2, 1–3, 1–4, 1–5

H

N

V voltage checks, 1–4 voltage, pickup and dropout settings

HELP

customercare@asco.com 800–800–ASCO

Normal Source Accepted light, 1–5

see Controller User’s Guide

Printed in U.S.A. E ASCO Power Technologies, L.P. 2009

Show 21 more labels / short text on this page
inspection, 3–1 · auxiliary circuits, 1–2 · installation, 1–1 · barriers, 1–1 · labels, · cable · lights, 1–4, 1–5 · catalog number, cover · cleaning, 2–1 · connections · line, 1–1 · lubrication, 2–1 · controller, 1–1 · maintenance, preventive, 3–1 · electrical operation, 1–5 · manual operation, 1–3 · illustration of, 1–3 · frequency, generator, 2–2 · harness, 1–2 · disconnect plugs, 2–1 · nameplate, cover
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson FDESIGN 600800A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson FDESIGN 600800A

Be the first to ask — other owners or our team will answer.

Original document

Emerson FDESIGN 600800A manual PDF

12 pages·2.7 MB·Switch·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…