Nameplate The Transfer Switch nameplate includes data for each specific 7000 Series ADTB. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is shown below with its elements explained.
Typical 7000 Series ADTB catalog no. for overlapping neutral, 3 pole, 600 amp, 480 V, ATS in Type 1 enclosure:
Amperes Voltage Controller Enclosure
J 400
C – type 1 F – type 3R
B – switched 5X – if
G – type 4
L – type 12
M 460
blank – open type
Q 575 P 550
R 600
H 380


ASCO 7000 Series Automatic Delayed–Transition Transfer & Bypass–Isolation Switches (7ADTBs) are factory wired and tested. Field installation requires mounting and connection of service cables, and auxiliary control circuits (if required).
Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.
Open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the shipping skid.
Protect the switch from construction grit and metal chips to prevent malfunction or
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the switch for all mounting details including door opening space.
shortened life of the 7ADTB switch.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
After the power cables have been tested, connect them to the appropriate terminal lugs on the bypass switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solder- less screw type and will accept the wire sizes listed on the drawings provided with the 7ADTB. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Refer to the applicable enclosure outline drawing fur- nished with this switch and mount the automatic transfer switch according to details and instructions shown on diagram.
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Refer to the Wiring Diagram provided with the switch. All wiring must be made in accordance with the National Electrical Code and local codes.
Do not remove the interphase barriers from the transfer switch. Always protect the transfer switch, bypass switch, and isolation contacts and mechanisms from construc- tion grit and metal chips when cabling.
The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.

All customer connections, including the engine control contact connections, are located on terminal block TB which is mounted on the top right side of the enclosure. Refer to the wiring diagram provided with the automatic transfer switch and connect the engine start wires to the appropriate terminals. See Figure 1–1 and Table A.

Table A. Engine start connections.
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this automatic transfer switch.
Figure 1-1. Customer terminal block on the top right
side of the enclosure.
The Functional Test consists of two checks:
Read all instructions on the Wiring Diagram and labels affixed to the automatic transfer & bypass–isolation switch. Note the control features that are provided and review their operation before proceeding.
❐1 — Voltage Checks, page 1–3
❐2 — Electrical Operation, page 1–4
Continue to 1 – Voltage Checks on next page.
Do these checks in the order presented
to avoid damaging the 7ADTB.
engine start connections · on customer · terminal block TB



RED
RED GREEN
AMBER
Figure 1-2. Standard controls and indicators.

Read all instructions on the Wiring Diagrams and labels affixed to the 7ADTB. Note the control features that are provided and review their operation before proceeding.
After installing the 7ADTB check the following:
– Bypass Handle should be in the NORMAL position. – Isolation Handle should be in the CONN position. – CN transfer switch should be C (closed) – CE transfer switch should be O (open)

If handles are not in correct positions, follow instructions for Bypassing and Isolating the automatic transfer switch in Section 3. Do not force the handles. Electrical interlocks prevent a wrong sequence of operation.
First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.
Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1–6 at the right. Observe the status lights. See Figure 1–2.

* If necessary, adjust voltage regulator on generator per the manufacturer’s recommendations. The 7ADTB will respond only to rated voltage specified on the nameplate.
Now continue to 2 – Electrical Operation on next page.
observe these lights

RED
RED GREEN
AMBER
Figure 1-3. Standard controls and indicators.

This procedure checks electrical operation of the ADTS.
Close enclosure door before proceeding to prevent personal injury in case of electrical system fault.

The ATS should still be bypassed. Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started; put engine starting control in automatic position. The Transfer Switch Connected to Normal light and the Normal Source Accepted light should be on.



This completes the Functional Test of the 7ADTB.
operate this switch · observe these lights

REPLACEMENT PARTS
Test the Automatic Transfer Switch portion of the 7000 Series 7ADTB at least once a month. This procedure checks the electrical operation of the Transfer Switchand Controller. Put the engine–generator starting control (at the engine–generator set) in automatic mode.
Replacement parts are available in kit form. When or- dering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch name- plate. Contact your local ASCO Power Technologies Sales Office or ASI:
In the following test the generator will start, the load will be transferred to the Emergency source, then back to the Normalsource. Aninterruptiontothe loadwill occur, un- less the the Transfer Switch contacts are bypassed before the test. See pages 3–1 through 3–4 for bypassing & iso- lating instructions if no interruption of load is required.
call 1 – 800 – 800 – ASCO ( 2726 )
call 1 – 888 – 234 – ASCO ( 2726 )
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:
Be sure to close the enclosure door before proceeding to prevent personal injury
in case of electrical system fault.
Perform the five–step Electrical Operation – Transfer Test procedure on page 1–4.
Bypass–Isolation Switch is energized! Do not touch isolation contact fingers;
PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series 7ADTB. An annual preventive maintenance program is recom- mended.
shock, burns, or death could result!
ASCO Services, Inc. (ASI) is ASCO Power Technologies’s national service organization. In the US ASI can be contacted at 1-800-800-2726 for in- formation on preventive maintenance agreements.
Checklist for Yearly Inspection
Hazardous voltage capable of causing shock,
burns, or death is used in this switch. Deenergize both Normal – Emergency power
sources before performing inspections!
❐Clean the 7ADTB enclosure.
Brush and vacuum away any excessive dust accumu- lation. Remove any moisture with a clean cloth. ❐Check the transfer switch contacts.
This procedure manually transfers load to other source if the Transfer Switch or Controller are out of service.
Bypass, isolate, and withdraw the transfer switch. Then remove the transfer switch interphase barriers andcheckthe conditionof thecontacts. Replacecon- tacts when pitted or worn excessively. Reinstall the interphase barriers carefully. See page 3–4. ❐Maintain transfer switch lubrication.
Close enclosure doors to prevent personal
injury in case of electrical system fault.
If switch is subjected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and linkages. Relubricate solenoid operator if TS coil is replaced. Don’t use oil; order lubrication kit 75-100. ❐Check all cable connections & retighten them.
Disconnecting the Plugs · Reconnecting the Plugs

Hazardous voltage capable of causing shock,
burns, or death is used in this switch. Do not touch the power or load terminals
of the bypass switch or transfer switch!
Table B. Trouble-Shooting Checks.
* These are factory settings. Refer to Controller’s User’s Guide.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI: in the United States, call 1–800–800–2726 or in Canada call 1–888–234–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.
both upper and lower contact shafts. Observe the window indicators (right side). Remove the mainte- nance handle and store it on the lower left side.
Bypass and isolate the Transfer Switchbefore using the maintenance handle! See pages 3–1 through 3–4. Remove the maintenance handle after using it; store it inside.
window indicators O is open C is closed
contact position indicators (right side)
Figure 2–1. Contact position indicators.



UP opens the Emergency source contacts
DOWN closes the Emergency source contacts
Figure 2–2. Maintenance handle operation for Emergency source contacts (upper shaft).
UP closes the Normal source contacts
DOWN opens the Normal source contacts
Figure 2–3. Maintenance handle operation for Normal source contacts (lower shaft).
Table C. Maintenance handle positions. ALL POWER MUST BE OFF !
* Link between contact shafts prevents closing both N and E contacts. The shaft extension and contact shaft turn in opposite directions through a cam–follower mechanism. If Normal and Emergency connectios are reversed this operation is also reversed.


BYPASSING THE ATS* This procedure explains how to Bypass the closed transfer switch contacts. Bypassing is required before the Transfer Switch can be tested or isolated. The Bypass Switch Handle must be in the OPEN position (green window indicator) and the Isolation Handle must be in the CONN [connected] position (window indicator). The TS Connected light must be on. See Figures 3–1, 3–2, 3–3.
You can only bypass to the same source
that the Transfer Switch is connected. Solenoid interlock prevents incorrect operation.

Window indicator shows yellow when ATS is bypassed to Emergency.
Window indicator shows green when the ATS is not bypassed.
Figure 3–1. Status lights and Engine Control.

Upper green light is on if Transfer Switch is on Normal.
Window indicator shows yellow when ATS is bypassed to Normal.
Lower red light is on if Transfer Switch is on Emergency.
Figure 3–4. Bypass Handle and three position window indicators.
Figure 3–2. Status lights for Transfer Switch main
contact position.

TS CONNECTED Upper amber light should be on.
Allowable Positions of the Bypass Switch in relation to Positions of the Transfer Switch
(with Isolation Handle in the Conn [connected]
position and TS Connected light on)
Figure 3–3. Status lights for Transfer Switch isolation
contact position.

To Bypass Normal Source* To Bypass Emergency Source* (Load connected to Normal Source) The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.
(Load connected to Emergency Source) The Transfer Switch Connected To Emergency light is on
and Transfer Switch Connected To Normal light is off.
Push in the handle and turn it counterclockwise.* Turn the handle clockwise.*
Push in* the Bypass Handle all the way, then turn it counterclockwise until Bypass Switch Position shows closed on NORMAL (yellow window indicator). The green light Bypassed to Normal will come on and the amber light Not In Automatic will flash.
Turn* the Bypass Handle clockwise until Bypass Switch Position shows closed on EMERGENCY (yellow window indicator). The red lightBypassed toEmergency willcome on and the amber light Not In Automatic will flash.
Push in Bypass Handle
Bypass Switch Turn Bypass Handle clock- wise.
and turn it counter- clockwise.
ATS
Figure 3–5. Bypass to Normal diagram.
Figure 3–7. Bypass to Emergency diagram.


Upper green light comes on
BYPASSED TO NORMAL
Lower red light comes on
BYPASSED TO EMERGENCY

Upper window indicator EMERGENCY shows yellow
Lower window indicator NORMAL shows yellow
Figure 3–6. Status light and window indicator for
Figure 3–8. Status light and window indicator for
Bypassed to Emergency Source. The automatic transfer switch can now be put in the TEST or OPEN position. See ISOLATING on page 3–3.
Bypassed to Normal Source.
* NOTE: When Accessory 40*B (reversed Normal & Emergency connections) is specified, the handle operation is reversed. Follow instructions on the door.

Isolating is required before any service work can be performed on the automatic transfer switch (ATS). Refer to Figures 3–9, 3–10, 3–11, and 3–12.
Hazardous voltage capable of causing
electrical shock, burns, or death; do not touch any control circuit terminals.
Turn crank counter- clockwise until window shows ISOLATE.
Turn crank counter- clockwise until window shows TEST.
Figure 3–11. TEST to ISOLATE position.
Figure 3–9. CONNECTED to TEST position.


TS CONNECTED Middle amber light should be on.
TS TEST
TS TEST
Lower amber light should be on.
TS ISOLATED

CONN
TEST ISOLATE
TEST ISOLATE
out the transfer switch
out the transfer switch
Figure 3–10. Isolation Handle turned to TEST.
Figure 3–12. Isolation Handle turned to ISOLATE.

1. Deenergize transfer switch (pages 3–1 thru 3–4) Bypass, isolate, and withdraw transfer switch. Use a voltmeter to verify that no electrical power is present at the transfer switchterminals. 2. Use the maintenance handle (page 2–2). Open the contacts that will be inspected by using the detachable maintenance handle. 3. Remove the barrier (Figure 3–14). Use a phillip screwdriver to loosen (ccw) four or six captive round–head screws holding the barrier to the arc chutes. Then pull the barrier straight outward to remove it.
Hazardous voltage capable of causing
electrical shock, burns, or death; do not touch any control circuit terminals.


right rail left rail
Figure 3–13.Transfer switch isolated
and pulled out for inspection. See page 2–2 for maintenance handle use. A lifting yoke 812053 is available to facilitate lifting by using an overhead crane or similar equipment. See WARNING.
The Transfer Switch weighs about 150 lbs. depending upon the number of poles. Use lifting device 812053 or other device capable of lifting this weight to avoid personal injury or equipment damage. Two persons are recommended.
Contact condition should be checked annually. Discoloration is normal. Do not file contacts because it wastes material. Instead use light emery paper to clean up the contact surfaces. The non–replaceable main contacts are designed to last the life of the transfer switch.
To prevent the possibility of fatal electrical shocks and burns, bypass, isolate, and withdraw the transfer switch before working on it.
Figure 3–14. Barrier removal.
tab handles

This procedure explains how to return the automatic transfer switch (ATS) to service after inspection and maintenance. Observe the Bypass Switch Position indica- tor and lights).
TS CONNECTED Middle amber light should come on.
TS ISOLATED

position window TEST clockwise – draws in
the transfer switch Figure 3–17. Isolation Handle turned to TEST. 3. TheATScan betested nowwithout loadinterruption (see page 2–1).
right rail left rail
Figure 3–15.Transfer switch isolated
Solenoid interlock prevents you from closing
and pulled out for inspection.
the isolation contacts until the ATS is in the
same position as the Bypass Switch.
Close the enclosure door to prevent personal
injury in case of electrical system fault.
Turn crank clockwise until window shows TEST.
Operate to NORMAL Operate to EMERGENCY Turn Transfer Control switch to Retransfer Delay Bypass.
Turn Transfer Control switch to Transfer Test (hold 15 seconds).* Connected To Normal light should come on.
Connected To Emergency light should comes on.
* If Feature 2B time delay is used, there will be a delay before transfer to Emergency.
Figure 3–16. ISOLATE to TEST position.
tab handles · Automatic Transfer Switch

Do not close the isolation contacts unless
the Transfer Switch (ATS) and Bypass
Switch are in the same position!
Turn crank clockwise until window shows TEST.
Figure 3–18. TEST to CONN (connected) position.
TS CONNECTED Upper amber light should be on.
TS ISOLATED

position window CONN clockwise – draws in
Figure 3–19. Isolation Handle turned to CONN.
Automatic Transfer Switch · the transfer switch

RETURN TO SERVICE continued*
Window indicator shows yellow when ATS is bypassed to Emergency.
This procedure explains how to return the Bypass Switch Handle to the OPEN position. The Bypass Handle must be in the CLOSED position (yellow indicator on NOR- MAL or EMERGENCY) and the Isolation Handle must be in the CONN position (window). See Figures 3–20, 3–21, and 3–22.
Window indicator shows green when the ATS is not bypassed.
You can only bypass to the same source
that the ATS is connected. Solenoid interlock prevents incorrect operation.
1 Observe which Bypass Switch Position indicator is yellow (NORMAL or EMERGENCY) at the Bypass Switch Handle. This indicates the source connected to the load. 2 Un–Bypass to same source as the Bypass Switch Position as follows (select Normal or Emergency).
Window indicator shows yellow when ATS is bypassed to Normal.
Figure 3–20. Bypass Handle and position indicators.
To Un–Bypass Normal Source* To Un–Bypass Emergency Source* (Load connected to Normal Source) The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.
(Load connected to Emergency Source) The Transfer Switch Connected To Emergency light is on
and Transfer Switch Connected To Normal light is off.
Turn the handle clockwise.* Turn the handle counterclockwise.*
Turn* the Bypass Handle clockwise until the Bypass Switch Position shows OPEN (green window indicator). The Bypassed to Normal light should go off and the Not In Automatic light should go off.
Turn* the Bypass Handle counterclockwise until the Bypass Switch Position shows OPEN (green window indicator). The Bypassed to Emergency light should go off and the Not In Automatic light should go off.
Bypass Switch Turn Bypass Handle counter- clockwise.
Turn Bypass Handle clockwise.
ATS
Figure 3–21. Un–Bypass Normal diagram.
Figure 3–22. Un–Bypass Emergency diagram.
The Automatic Transfer & Bypass–Isolation Switch should be left in this position.
* NOTE: When Accessory 40*B (reversed Normal & Emergency connections) is specified, the handle push–pull operation is reversed. Follow instructions on the door.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 1 OPERATION | p.8 | ||
| Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails. | Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting. | p.8 | |
| Transfer switch does not transfer the load to the emergency source after the engine–generator set starts. | Wait for Feature 2B time delay to time out. | p.8 | |
| Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released. | Wait for Feature 3A time delay to time out. | p.8 | |
| Gen. does not stop after load retransfer to normal source. | Wait for Feature 2E time delay to time out. | p.8 | |
| Load Disconnect Active light comes on. | Wait for load disconnect time delay to time out. | p.8 | |
| Load Disconnect Active light stays on longer than 6 min. | Check load disconnect time delay setting. Call ASI. | p.8 |