As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety.
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application require- ment, including distributed generation applications. That’s why the 7000 Series is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
Commercial Buildings / Industrial Buildings
Web Hosting, Internet Data Centers
Process Manufacturing / Wafer Fabrication Plants /
Distributed Power / Load Management
ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
ASCO Power Transfer Switches are the first CE Marked, IEC 60947- 6-1 compliant Transfer Switches in the world which have been certified by a notified body of the European Union.
Healthcare Facilities · Telecom Central Offices

Offers the Most Advanced Transfer Switches in the World.

ASCO Power Transfer Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacity size, is achieved by a reliable, field proven solenoid operating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPSs and microprocessor based systems. 7000 Series Power Transfer Switches are available open or enclosed, in ampacity sizes from 30 through 4000 amperes with the largest selection of optional accessories offered anywhere. All switching configurations are available with an integrally mounted bypass-isolation switch and/or rated for use in service entrance applications.
rated 1600 amperes (shown with optional front
connected terminals and Power Manager).


ASCO Automatic Closed-Transition Transfer Switches feature main contacts that overlap, permitting the transfer of electrical loads without power interruption. The switch transfers in a make-before-break mode if both sources are within acceptable parameters. Control logic continuously monitors source conditions and automatically determines whether the load transfer should be open (conventional non-overlap mode) or closed transition. Available 150 through 4000 amperes.
Closed-Transition Transfer within 5 electrical degrees is achieved passively, without control of engine generator set. Therefore, no additional control wire runs are required between the ATS and engine generator set governor. Plus, protective relaying may not be required under normal operation since the contact overlap time is less than 100 milliseconds (consult your local utility on protective relay requirements).
Failure to synchronize indication and extended parallel time protection is built-in to all 7000 Series closed transition controls to prevent abnormal operation. Fig. 2: Four pole, Closed-Transition Transfer Switch rated 1000 amperes in Type 1 enclosure.

ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time. Applications include older style variable frequency drives, rectifier banks, and load management applications.
Fig. 3: Four pole, Delayed-Transition Transfer Switch rated 2000 amperes.


ASCO Non-Automatic Transfer Switches are electrically operated units which are operated with manual control switches mounted locally or at remote locations.
shown in Type 1 enclosure.

See publication 1128 for more information on withstand and close-on ratings for ASCO transfer switches.


ASCO Automatic Transfer & Bypass-Isolation Switches are available in open transition, closed transition and delayed transition designs. The bypass and isolation features allow power transfer switches to be inspected, tested, and maintained without any interruption of power to the load.
Isolation Transfer Switch Rated 1000 Amps


Transfer Switch self aligning power jaws.
optional automatic shutters.

Bypass and Isolation Handles - Simple as 1, 2, 3
Bypass to Normal
Source availability Bypass switch

Push in bypass handle and turn it counter clockwise

Not in “auto” flashing LED

Turn isolation handle counter clockwise until window shows “Test”
Mechanical bypass switch position flags
Turn isolation handle counter clockwise until window shows “Isolate”
Represents Current Flow In test position control panel remains energized to allow for electrical operation of a transfer switch.
Mechanical isolation handle position

The ASCO Service Entrance Power Transfer Switch combines automatic power switching with a disconnect and overcurrent protective device on the utility source. The power transfer switch meets all National Electric Code requirements for installation at a facility’s main utility service entrance. Service entrance rated transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source. A circuit breaker serves as the utility disconnect and links are provided to disconnect both neutral and ground connections.

This product is UL 1008 and UL 891 listed and is available up to 600V and 4000A in Standard, Delayed, Closed Transition, Soft Load, and Bypass Isolation Configurations.


ATS
Ø
GFCT - Ground Fault Current Transformer
ATS - Automatic Transfer Switch
One line diagram of a typical service entrance rated transfer switch available in Solid, Switched or Overlapping Neutral * Ground fault trip protection provided on sizes of 1000 amperes and above


UL Type 3R w/strip heater & thermostat
UL Type 4X
ASCO 5500 Series Thin Web Server for internet
connection • Additional Breaker(s) Circuit Breaker on Emergency Load Distribution Panel
ASCO 5200 Series Power Manager
Consult ASCO for additional features
To order an ASCO 7000 Series Service Entrance Power Transfer Switch, complete the following catalog number.
7 A US + B + 3 + 400 + N + 5X + C

*Note. Switches rated 150, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional). For 4 pole applications on switches rates 260 to 400 amps and 4000 amps specify overlapping switched neutral (optional). Conventional switched neutral is provided on delayed transition transfer products when specified.

The Example Catalog Number above is 7AUSB3400N5XC (X is used to specify optional accessories).
Dimensions and Weights for non-bypass configurations only in type 1 enclosures. Consult ASCO for all other product configurations.

< · Crimp lugs


The 7000 Series Microprocessor Based Controller is used with all sizes of Power Transfer Switches from 30 through 4000 amperes. It represents the most advanced digital controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power applications.
Because of severe voltage transients frequently encountered with industrial distribution systems, the microprocessor logic board is separated and isolated from the power board as shown below. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards highlighted below.
Fig. 11: 7000 Series Microprocessor Controller.

Fig.12: Microprocessor Power and Logic PC Boards.

Emission Standard - Group 1, Class A EN 55011:1991 Generic Immunity Standard, from which: EN 50082-2:1995 Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995 Radiated Electromagnetic Field Immunity ENV 50140:1993 Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995 Surge Transient Immunity EN 61000-4-5:1995 Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994


Time Delays

Control Switches and Indicating Lights for Conventional 2-Position Switches

Fig. 13: 7000 Series User Controls and Indicators.

Fig. 14: 7000 Series User Controls and Indicators.
The 7000 Series microprocessor controller is a Transfer Control Center which allows the user to easily access detailed information on: system status; power source parameters; voltage, frequency and time delay settings; optional feature settings; historical event log; and system diagnostics. A four line, (20) character LCD has a backlit display which enables easy viewing under all conditions. The user can navigate through all screens using only six buttons, which also allows selection of: (18) different source parameter settings; (16) standard time delays; (12) standard feature settings; up to seven independent engine exercise routines; and even the language (English, German, Spanish, French, etc.) which appears on the display.

Since the Transfer Control Center must be visible and operable through the enclosure door, it has been qualified for use in industrial and outdoor applications. This includes installation in Type 3R (outdoor/rainproof), 4 (weatherproof) and 12 (indoor/industrial) enclosures.
Fig. 15: 7000 Series Transfer Control Center.

Status
Source Status

Normal Source Vab=480V ABC Vbc=480V Vunbal=1% Vca=480V 60.0Hz
Displays system status in clear, concise language. Message shown indicates normal source is acceptable
Displays voltage for each phase, frequency, phase rotation and voltage unbalance for both
and the load is connected to the normal source.
normal and emergency sources.
Inphase Transfer Mode
TD.Engine.Cooldown:
-45o 0.02Hz
Active time delay status displays time
Displays the relative phase angle between sources and frequency differential to indicate the controller is awaiting an inphase condition.
remaining until next control event.
Normal Voltage Dropout 85%.408V Pickup 90%.432V
TD N>E Xfer Signal Bypass if N Fail: No Pre Xfer: 0 min 20S Post Xfer: 0 min 20S
O.V. Trip 110%.528V
Provides voltage and frequency setting values for normal and emergency sources. Voltage pick-up, dropout and trip settings are set in percentage of nominal
Provides direct reading display for setting time delays.
voltage and are also displayed in rms voltage values.
Feature Settings
P1 Engine.Exerciser Enable: Yes WLoad: Yes Start:19h30. ALL MON Run.Time: 2h15min
Seven independent programs, load/no load selection, flexible run times and daily, weekly,
Standard features can be activated with the keypad. As an
example, when enabled, the “shed load” option causes the transfer switch to transfer the load off of the specified source.
bi-weekly and monthly exercise routines.
If desired, the load shed transfer can be made inphase.
Historical Event Log
16.AUG02/95 13h10:17 Eng.Start NormFail. 15.AUG02/95 13h10:25 Xfer.N>E
Instant availability of statistical information on total number of
Displays detailed information for last 99 events,
ATS transfers, number of transfers caused by power failures
including time of occurrence, length of event,
and total days controller has been energized, plus more.
date and reason for event.

Time Delays
Neutral Conductor Options • Solid neutral, with fully-rated terminals. (AL-CU) UL Listed.
2C The standard feature one time delay is adjustable from 0 to six seconds to delay engine starting. If necessary, extended time delay on engine starting is available. Adjustable from 0 to 60 min in one second steps. Factory set at five minutes. 1G Similar to accessory 2C except using 24 volt DC external input signal.
Manual Controls for Automatic Transfer Switches
37B Six foot (6’) extension harness to increase distance between
transfer switch and control panel on open-type units.
6C Reset switch for manual retransfer to normal with automatic retransfer in the event of emergency source failure.
23B Three phase ammeter with selector switch (with current transformers and shorting blocks).
6D Selector switch for automatic/manual retransfer to normal. Automatic bypass if emergency fails.
24B Three phase voltmeter with selector switch.
voltage, frequency and power monitoring.
12 Three position engine control selector switch. Positions: 1- Stop 2- Automatic 3 - Engine Test
72A Serial communication module for remote communications to ASCO PowerQuest® products.
transfer switch according to UL 1008.
Engine controls containing “engine stop” positions should be located at the engine generator. (Consult ASCO for application assistance.)
ASCO Pulsar 450 rated 40KA
73AC1 Normal source protection. (3Ø, 4wire WYE) 73AC2 Emergency source protection. (3Ø, 4wire WYE) 73AC3 Load side protection. (3Ø, 4wire WYE)
14A/14B Additional auxiliary contact sets to indicate switch position. Two sets are standard. Specify total number of sets if more are required.
18B Two-pole, double-throw contacts operate when emergency source voltage is present at transfer switch terminals.
111A Generator - to - Generator for Standby Applications
111B Generator - to - Generator for Prime Power Applications
18G Two-pole, double-throw contacts operate when normal source voltage is present at transfer switch terminals.
99 “Push-to-Test” feature on all pilot light indicators.
Customer Control Circuits
14A1 Auy contact to close in “Bypass to Normal” position.
30A Load-shedding circuit initiated by opening of a customer-supplied contact.
14B1 Auxiliary contact to close in “Bypass to Emergency” position.
14T Auxiliary contact to close when transfer switch is in “Automatic” position.
30B Load-shedding circuit initiated by removal of customer-supplied control voltage. (Specify voltage).
14U Auxiliary contact to close when transfer switch is in “Isolate” position.
31Z Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and retransfer.
14V Auxiliary; contact to close when transfer switch is in “Test” position.
43R Terminal block for all customer control connections on 30-150 amp only (standard on all other sizes).
(Consult ASCO for guidance.)

Power Manager

POWER SYSTEM TOTAL 404 KW +1.00 PF 0 KVAR 60.00 Hz 404 KVA ATSºn NORM
The ASCO Power Manager is a microprocessor based metering device that provides real-time measurements of single and three phase power systems. The Power Manager uses digital signal processing technology to measure voltage and current per phase; real, reactive and apparent power, and bi-directional energy. All measurements can be viewed locally with a backlit liquid crystal display and/or displayed remotely with ASCO PowerQuest ® or SiteWeb™products.
Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PTs). Measures three phase currents and a fourth current input is available for measuring current in the neutral conductor. The Power Manager includes one discrete input for transfer switch position, eight general purpose discrete inputs, and four relay outputs for controlling or monitoring external devices.
Fig. 16: ASCO Power Manager.

Connected To: With Display Without Display Load Acc. 85L Acc. 75L Normal Acc. 85N Acc. 75N Emergency Acc. 85M Acc. 75M Load (BPS only) Acc. 85R* Acc. 75R*
Add suffix “A” to above designations if neutral conductor monitoring is required.
blocks and all necessary interwiring.
* Bypass & isolation switch contacts wired to discrete Power Manager inputs.

ASCO Connectivity Solutions
ASCO PowerQuest® and SiteWeb™ communications products allow for the monitoring and control of power transfer switches in your Emergency or Standby Power Distribution System. Local Area networks and Remote networks are supported with either single or multiple points of access, and web-enabled communications allow access to your power system from anywhere around the world.
ASCO 5110 (72A) Serial Modules

ASCO 5200 Power Manager ASCO 5100
ASCO PowerQuest
VPi 32.15
ASCO ATS 2
RS-485
ASCO 5110 (72A) Serial Modules
ASCO 5200 Power Manager
ASCO ATS 1
ASCO 5150 (72E) Connectivity Module

PowerQuest< is a PC based software package. When combined with the ASCO Communication Interface Module (Acc 72A), the ASCO 5120 Telephone Interface Module and ASCO 5200 Series Power Manager, as shown above, it provides the most economical communication system for monitoring and control of power transfer switches and engine generators.
The local RS-485 network allows communications with up to 32 power transfer switches and four engine generators. An analog phone connection and ASCO telephone interface module allow for direct dial up, monitoring and control of remote locations. The ASCO Power Manager not only allows you to view current power and power factor readings, but also has a programmable KW set point to initiate transfer of loads to a standby source for peak shaving operations.

Serial Module (5110) is used to allow local or remote communications with ASCO PowerQuest® or SiteWeb™communication products. The module is used to connect the 7000 Series Transfer Switches, and ASCO Power Managers to the serial network via an RS-485 interface. The module has two port connectors used for ATS & Standalone Power Manager connectivity. The serial connection is accomplished from a 5-pin terminal header/socket block. The module is designed to communicate with up to 32 devices.

Connectivity Module (5150) is used to bring several different serial devices that communicate at different baud rates and with different protocols to a common Ethernet media. The module is used to connect 7000 Series Transfer Switches, and ASCO Remote Annuciators to the standard Ethernet TCP/IP network with standard 10base T(RJ-45) connector. The module has been built in customized JAVATM
applets (program applications for an internet browser) for each monitored device that loads automatically to a standard Web Browser. The module is designed to communicate with up to 8 clients simultaneously with Web applications (web pages), PowerQuest® , or third party Modbus< devices over an Ethernet connection.

The ASCO Telephone Interface Module (TIM) allows users to dial directly into their ASCO communications network for monitoring and/or control. The TIM connects to the ASCO communication network via RS-485 and the phone port connects directly into an analog phone jack. Also, the TIM has an RS-232 connector which allows the TIM to be used as the dialing modem.
Supplied with 120 VAC to 18 VDC (nominal) UL approved, class 2 power supply. Fig. 19: Telephone

ATS 1 - 8 Summary Screen ATS 1 - 8 Summary Screen ASCO ASCO
1901 lavg 548 KW 1901 lavg 548 KW 1901 lavg 548 KW 1901 lavg 548 KW 1901 lavg 548 KW 1901 lavg 548 KW 1901 lavg 548 KW 472 lavg 136 KW
208 NVca 0 EVca
208 NVca 0 EVca
208 NVca 0 EVca
208 NVca 0 EVca
208 NVca 208 EVca
208 NVca 208 EVca
208 NVca 208 EVca
0 NVca 208 EVca
ATS 2
ATS 3
ATS 4
ATS 5
ATS 6
ATS 7
ATS 8
E L N
E L N
E L N
E L N
E L N
E L N
E L N
E L N
E N
E N
E N
E N
E N
E N
E N
E N
OTTS OTTS OTTS OTTS OTTS OTTS OTTS OTTS
ATS 9-16 Re-Scan
TD Bypass Re-Transfer Transfer Previous
Engine 1 Stopped Engine 2 Stopped Engine 3 Stopped Engine 4 Running
0 KW Total 0.00 Frequency 0.00 Power Factor 0 Vavg. 0 lavg.
0 KW Total 0.00 Frequency 0.00 Power Factor 0 Vavg. 0 lavg.
0 KW Total 0.00 Frequency 0.00 Power Factor 0 Vavg. 0 lavg.
136 KW Total 60.01 Frequency 0.82 Power Factor 208 Vavg. 472 lavg.
L N
N
< · ?

ASCO ASCO
ADDRESS
KVA
Previous Previous Relay 3
Previous Previous Relay 4
Transfer Switch Detail Screen
ATS Details Screen ATS Details Screen
Description ATS 8 Location Switch 1
Ver. ADRTST-E12
PRESENT STATE
205 NVca 0 EVca ATS1
PC
OTTS
CP
Normal Voltage Frequency Settings
Time Delay Settings [min]:[sec]
Voltage or Freq % Nom Value
6/13/99 10:02:42
Voltage P.U.
Voltage D.O.
Emerg to Norm-Src Fail
Voltage Trip Freq P.U.
Emerg to Norm-Test Xfer
Event Logging (Max. 99 Entries)
Emerg to Norm-Emerg Fail
Freq D.O.
Volt Unbal P.U.
Volt Unbal D.O.
Non - Standard TD
Time 16:05:42
ASCO ASCO
ENGINE
Previous Previous Relay 3
Previous Previous Relay 4


ASCO 5500 Thin Web Server
Ethernet Hub RS 422 Modbus
Monitoring Monitoring and Control
ASCO 5110 (72A) Serial Modules
ASCO 5150 (72E) Connectivity Modules
ASCO ATS 2
ASCOA
ASCO ATS 2
TS 1

TM is a client-server application requiring no software to be installed on the client computer. When combined with the ASCO Communication Interface Modules (Acc 72A / Acc 72E), the ASCO 5500 Series Thin Web Server and the ASCO 5200 Series Power Manager, as shown above, it provides the most comprehensive Intranet and Internet communication system for the monitoring and control of power transfer switches and engine generators located in your emergency or standby power distribution system.
TM communication system allows multiple client access, from local or remote locations, and provides for the monitoring of up to 64 power transfer switches and eight engine generators. In addition, automatic paging is provided for all alarm signals.

The ASCO Thin Web Server allows you to monitor and control transfer switches and engine generators anytime over the Internet or an Intranet from anywhere in the world. It also transmits a page message that an alarm has occurred with one or more of the transfer switches. Plus, this is possible from your home computer or anywhere that has Internet service, using the ASCO Thin Web Server single-board computer with its embedded SiteWeb™ HTML web pages.

Description Acc. Option Catalog No.
Serial Module 72A 5110
Connectivity Module 72E 5150
Telephone Interface Module for Remote Monitoring* — 5120
Power Manager with Display* — 5200D
Thin Web Server* — 5510E
Thin Web Server with Modem* — 5510M
PowerQuest VPi Software Package* — VPi 32.15
*Note: These products are available as separate items only. They can be ordered by catalog numbers shown in above chart.
Connectivity Modules

ASCO Connectivity Solution Guide
Series 5150 Connectivity Module
Vpi 32.15
Quantity of Monitored / Controlled Power Transfer Switches per LAN
Number of Monitored / Controlled Gensets
Control & Monitoring Capability
Monitor Multiple Protocols & Baud Rates (ASCO I, ASCO II, Modbus)
Monitors Dissimilar ASCO Controllers on Common LAN
Communicates with ASCO Remote Annuciators
Email / Paging Alarms
Historical Trending Option Alarms

To order an ASCO 7000 Series Power Transfer Switch, complete the following catalog number:
+ TS A A 3 400 N 5X C

Enclosure Neutral
Amperes Voltage
Grp Code
Poles
Code
2 3 A
TS
30 70 100 150 200 230 260 400 600 800 1000 1200 1600 2000 3000 4000
115 120 208 220 230 240
A
E
*
F
N
CTS
*
H
G
B
CTB
J K L M N P Q R
400 415 440 460 480 550 575 600
Type 4X enclosure (stainless steel)
DTS
K
M
DTB
Type 3R secure double door
N
Type 4 secure double door
Type 4X secure double door
Q
Type 12 secure double door
*Note: Switches rated 30-230, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional). For 4 pole applications on switches rated 260 to 400 amps and 4000 amps specify overlapping switched neutral (optional). Conventional switch neutral is provided on delayed transition transfer products when specified. 200 and 230 amp switch limited to 480 volts maximum.

(X is used to specify optional accessories).
Transfer Switch Configurations 7A TS, 7N TS, 7A DTS, 7A CTS, 7N DTS, 7N CTS Transfer/Bypass Configurations
7A TB, 7N TB, 7A DTB, 7A CTB, 7N DTB, 7N CTB
Sizes of UL-Listed Solderless Screw-Type
Terminal for Power Connections


Max # of Conductors
Range of AL-CU Conductor Sizes
Max # of Conductors
Range of AL-CU Conductor Sizes
#14 to 4/0 AWG
# 4 AWG to 600 MCM
#4 AWG to 600 MCM
# 1/0 AWG to 250 MCM
# 2 AWG to 600 MCM
#1/0 AWG to 250 MCM
#1/0 AWG to 600 MCM
# 1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
# 1/0 AWG to 600 MCM
# 2 AWG to 600 MCM
#1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
# 2 AWG to 600 MCM
Suitable for Bus Bar Connection or Lugs Can Be Field Modified
entry of normal. Optionally, the switch may be supplied with reverse source and/or bottom entry load, when specified.

2-Position Transfer Switching 7A TS, 7N TS (Non-Bypass)

Depth inches (mm) Height inches (mm) Width inches (mm) Poles Switch Rating
Enclosed UL Type 12
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral A/B/C 18 (457) 48 (1219) 13 (330) 260, 400 2, 3 or 3 with neutral A/C 22 (559) 48 (1219) 13 (330) 600, 800, 1000 2, 3 or 3 with neutral A/B/C 34 (864) 72 (1829) 20 (508) 1200 2, 3 or 3 with neutral A/B/C 38 (965) 87 (2210) 23 (584) 1600, 20001 2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 48 (1219) 30001 2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 60 (1524) 40001 2, 3 or 3 with neutral A/C 46 (1168) 91 (2311) 72 (1829)
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral B/C 10-1/4 (260) 10-1/4 (260) 5-1/2 (140) 260, 400 2 or 3 12 (305) 18-1/2 (470) 6-7/8 (175) 260, 400 2 or 3 with neutral C 14-1/2 (368) 18-1/2 (470) 6-7/8 (175) 600, 800, 1000, 1200 2, 3 or 3 with neutral B/C 27 (686) 31 (787) 12-7/8 (327) 1600, 2000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 26-1/4 (667) 3000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 30-3/4 (781) 4000 2, 3 or 3 with neutral C 41 (1041) 52 (1321) 25-1/2 (648)
2-Position Transfer Switching 7A TS, 7N TS

lb (kg) Poles Switch Rating
Open lb (kg)* Enclosed
30, 70, 100 2 67 (31) 15 (7) 30, 70, 100 3 70 (32) 18 (8) 30, 70, 100 3 with B/C 73 (33) 21 (10) 150, 200, 230 (Open) 2 69 (32) 17 (8) 150, 200, 230 (Open) 3 72 (33) 20 (9) 150, 200, 230 (Open) 3 with B/C 75 (34) 23 (11) 230, 260, 400 2 117 (53) 37 (17) 230, 260, 400 3 125 (57) 45 (21) 230, 260, 400 3 with C 133 (61) 53 (24) 600, 800, 1000 2 400 (182) 150 (68) 600, 800, 1000 3 420 (192) 170 (78) 600, 800, 1000 3 with B/C 446 (203) 196 (90) 1200 2 685 (312) 150 (68) 1200 3 705 (321) 170 (78) 1200 3 with B/C 731 (333) 196 (90) 1600, 2000 2 1110 (503) 370 (167) 1600, 2000 3 1160 (525) 420 (190) 1600, 2000 3 with B/C 1210 (548) 470 (213) 3000 2 1365 (620) 405 (184) 3000 3 1430 (649) 470 (213) 3000 3 with B/C 1495 (679) 535 (243) 4000 2 2208 (1002) 975 (443) 4000 3 2433 (1104) 1200 (545) 4000 3 with C 2533 (1149) 1300 (590)
1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.

Closed Transition and Delayed Transition Transfer Switching 7A DTS, 7A CTS, 7N DTS, 7N CTS

Depth inches (mm) Height inches (mm) Width inches (mm) Poles Switch Rating
Enclosed UL Type 13
150, 260, 4001 2, 3 or 3 with neutral A/C 24 (610) 63 (1600) 17-1/2 (445) 600, 800, 1000 2, 3 or 3 with neutral A/B 34 (864) 72 (1829) 20 (508) 1200 2, 3 or 3 with neutral A/B 38 (965) 87 (2210) 23 (584) 1600, 20002 2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 48 (1219) 30002 2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 60 (1524) 40002 2, 3 or 3 with neutral A/C 46 (1168) 91 (2311) 72 (1829)
150, 260, 400 2, 3 or 3 with neutral C 14-3/4 (375) 30 (762) 5-7/8 (149) 600, 800, 1000, 1200 2, 3 or 3 with neutral B 27 (686) 31 (787) 12-7/8 (327) 1600, 2000 2, 3 or 3 with neutral B 33-1/4 (845) 28 (711) 26-1/4 (667) 3000 2, 3 or 3 with neutral B 33-1/4 (845) 28 (711) 30-3/4 (781) 4000 2, 3 or 3 with neutral C 41 (1041) 52 (1321) 29-1/2 (749)
Closed Transition and Delayed Transition Transfer Switching 7A DTS, 7A CTS, 7N DTS, 7N CTS

lb (kg) Poles Switch Rating
150, 260, 400 2 137 (62) 45 (21) 150, 260, 400 3 145 (66) 53 (24)
150, 260, 400 3 with C 153 (69) 63 (28) 600, 800, 1000 2 420 (192) 175 (80) 600, 800, 1000 3 450 (205) 205 (94) 600, 800, 1000 3 with B 480 (219) 235 (108) 1200 2 710 (324) 175 (80) 1200 3 740 (337) 205 (94) 1200 3 with B 770 (351) 235 (108) 1600, 2000 2 1300 (590) 505 (229) 1600, 2000 3 1350 (612) 555 (252) 1600, 2000 3 with B 1400 (635) 605 (274) 3000 2 1555 (706) 540 (245) 3000 3 1620 (735) 660 (300) 3000 3 with B 1685 (765) 725 (329) 4000 2 2360 (1071) 1127 (511) 4000 3 2580 (1171) 1347 (611) 4000 3 with C 2680 (1217) 1447 (657)
1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.

Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB

Depth inches (mm) Height inches (mm) Width inches (mm) Poles Switch Rating
Enclosed UL Type 1
150, 260, 4001 2, 3 or 3 with neutral A/C 28-1/2 (724) 62-1/2 (1588) 19 (483) 600, 800(Front Connected)2, 5 2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 32 (813) 600, 800, 1000, 12002, 3 2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 48 (1219) 1600, 20002, 3 2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 60 (1524) 30002, 3 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 72 (1829) 40004 3 or 3 with neutral A/C 96-1/2 (2451) 91 (2311) 72 (1829)
150, 260, 4001 2 or 3 14-3/4 (375) 37-1/8 (946) 22-1/4 (565) 150, 260, 4001 2 or 3 with neutral C 19-3/4 (500) 61-1/2 (1553) 22-1/4 (565) 600, 800, 1000, 12002, 3 2, 3 or 3 with neutral B/C 38 (965) 72 (1829) 38 (965) 1600, 20003, 30002, 3 2, 3 or 3 with neutral B/C 38 (965) 72 (1829) 38 (965)
2. Handles extend 6-1/4 inches (159mm). 3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout). Side or rear access required. 4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout). 5. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amp. All service and load cables limited to top entry only.
Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB
lb (kg) Poles Switch Rating
150, 260, 400 2 340 (154) 135 (61) 150, 260, 400 3 350 (158) 145 (66) 150, 260, 400 3 with C 360 (163) 155 (70) 600, 800, 1000, 1200 2 1510 (685) 920 (417) 600, 800, 1000, 1200 3 1580 (717) 990 (449) 600, 800, 1000, 1200 3 with B/C 1650 (748) 1060 (481) 1600, 2000 2 2180 (989) 1300 (589) 1600, 2000 3 2360 (1070) 1550 (702) 1600, 2000 3 with B/C 2540 (1152) 1800 (815) 3000 3 2730 (1240) 1690 (768) 3000 3 with B/C 3360 (1525) 1980 (899) 4000 3 6300 (2858) – 4000 3 with C 6900 (3130) –
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.

Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB6, 7A CTB, 7N DTB6, 7N CTB

Depth inches (mm) Height inches (mm) Width inches (mm) Poles Switch Rating
Enclosed UL Type 1
150, 260, 4001, 5 2, 3 or 3 with neutral A/C 28-1/2 (724) 74 (1880) 19 (483) 600, 800 (Front Connected)2, 7 2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 32 (813) 600, 800, 1000, 12002, 3 2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 48 (1219) 1600, 20002, 3 2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 60 (1524) 30002, 3 3 or 3 with neutral A/B 38 (965) 91 (2311) 72 (1829) 40004 3 or 3 with neutral A/C 96-1/2 (2451) 91 (2311) 72 (1829)
150, 260, 4001, 5 2 or 3 14-3/4 (375) 61-1/2 (1553) 22-1/4 (565) 150, 260, 4001, 5 2 or 3 with neutral C 19-3/4 (500) 61-1/2 (1553) 22-1/4 (565) 600, 800, 1000, 12002, 3 2, 3 or 3 with neutral B 38 (965) 72 (1829) 38 (965) 1600, 20003, 30002, 3 2, 3 or 3 with neutral B 38 (965) 72 (1829) 38 (965)
2. Handles extend 6-1/4 inches (159mm). 3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout).Side or rear access required. 4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout). 5. Dimensions for 400 amp, 7A DTB and 7N DTB with neutral code B are 38(965)W x 91(2311)H x 48(1219)H. 6. Conventional switched neutral is provided on 7A DTB and 7N DTB switching arrangements when specified (optional Code B). 7. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amps. All service and load cables limited to top entry only.
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB, 7A CTB, 7N DTB, 7N CTB
lb (kg) Poles Switch Rating
150, 260, 400 2 340 (154) 145 (66) 150, 260, 400 3 350 (158) 155 (70) 150, 260, 400 3 with C 360 (163) 165 (75) 600, 800, 1000, 1200 2 1560 (708) 970 (440) 600, 800, 1000, 1200 3 1630 (739) 1040 (472) 600, 800, 1000, 1200 3 with B 1700(771) 1110(503) 1600, 2000 2 2315 (10550) 1435 (651) 1600, 2000 3 2495 (1132) 1685 (764) 1600, 2000 3 with B 2675 (1213) 1935 (878) 3000 3 2730 (1240) 1690 (768) 3000 3 with B 3360 (1525) 1980 (899) 4000 3 6300 (2858) – 4000 3 with C 6900 (3130) –
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.


ASCO Services, Inc., pro- vides a wide range of techni- cal services to users of automatic transfer switches in emergency and standby power systems. These serv- ices include comprehensive scheduled maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine genera- tors.
largest manufacturer of power transfer switching and control equipment. Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.
point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts. This customization permits centralcorporate control of costs and schedul- ing. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.
perienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls. Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs. ASCO< Services 1-800-800-ASCO.
ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unex- pected expenditures. A 35-
ASCO Services deploys more than 75 serviceperson- nel strategically located throughout the nation to provide 24-hour response in emergency situations. Each region is manned by ex-
ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power Technologies, the world’s

We Keep Your Power On
A S C O P O W E R T E C H N O L O G I E S
F L O R H A M P A R K , N E W J E R S E Y 0 7 9 3 2
8 0 0 8 0 0 A S C O
W W W . A S C O . C O M
A U S T R A L I A
C A N A D A
G E R M A N Y
J A P A N
M E X I C O
S O U T H A F R I C A
S O U T H A M E R I C A
U N I T E D A R A B E M I R A T E S
U N I T E D K I N G D O M
U N I T E D S T A T E S
Publication 3040-R7 ASCO December, 2004