INTEGRATED FURNACE
50A55 INTEGRATED FURNACE CONTROL MODULE Qualified Serviceman’s Troubleshooting Guide
If the light on the module is on continuously, the fault is likely to be internal to the module. To make sure, interrupt line or 24 volt thermostat power for a few seconds and then restore. If internal fault is indicated again, and flame sensor is not shorted to ground, replace control. A flashing light indicates the problem is most likely in the external components or wiring. Proceed as follows:
Turn power off before any troubleshooting or servicing begins.
Line voltage (120 VAC) could be present on the surface of the ignitor, if the sys- tem is not correctly wired. Such voltage can cause serious injury or death.
Failure to read and follow all instructions carefully before in- stalling or operating this control, could cause personal injury and/ or property damage.
The following steps must be performed first before any troubleshooting begins. 1) Disconnect electric power to system at main fuse or circuit breaker. 2) Visually inspect equipment for apparent damage. Check wiring for loose connections. 3) Check for proper grounding and reversed polarity. A. Check continuity for C terminal on module to electrical service ground and connection at the furnace junction box. If ground connection is open, check module ground connection and the electrical service ground connection. Repair and retest. B. Re-connect electric power to system. C. Check for voltage between the line neutral terminal and furnace ground. If voltage exists, the main power supply lines are improperly connected to the furnace (REVERSED POLARITY). Again disconnect electric power to system; then reverse incoming supply leads to furnace. Repeat step. D. Recheck system for proper operation.
If neither apparent damage, loose connection nor reversed polarity is the problem, proceed to troubleshooting chart or fault index chart that is suggested by the actual condition.

No manual fan 1A - 1K Power supply and voltage 1C - 1G No fan at cooling speed 2A - 2L No induced draft motor 3A - 3H LED flashing 2X without inducer 3E LED flashing 3X with inducer 3I - 3O Ignitor does not glow 4A - 4D Burner does not stay lit 4E - 4N Gas supply problem 4F - 4K No outlet pressure 4H - 4J Gas valve does not energize 4L - 4N Flame sensor fault 5A - 5P Burner ground 5K Polarity check 5L - 5M Ignitor stays on after burner ignition 5B - 5C

TROUBLESHOOTING
GUIDE

Place thermostat fan switch in
Does indoor blower run at HEAT speed?
switch to AUTO position.
the ON position.
Does LED flash 1 time when disconnect
Is 24V present at
Is 24V present at
Indoor blower fault. Repair or replace. Check
ON?
R & C?
G & C?
NEUTRAL?
Repair wiring from control to thermostat. Check
Is 24V present across 12-pin connector pins TH
Is 120V present across control terminals
Is 120V present across primary of control
Is 24V present across
XFMR & XFMR
& TR on the
NEUTRAL?
Correct 120V power supply. Check
Repair wiring to transformer. Check
Replace transformer. Check
and/or plug connection. Check

INTEGRATED FURNACE
2A 2B
system switch in cooling mode and fan
Does indoor blower energize
switch in AUTO position. Lower temperature selection
at cooling fan speed?
setting.
lever to call for a cooling cycle. R & Y
contacts close.
Is thermostat terminal Y connected to furnace
With door switch closed, jumper control
Repair low voltage wiring to thermostat. Check
energize at heating fan
energize at cooling fan
R & Y.
Correct wiring from thermostat terminal Y to Y on
Indoor blower fault. Repair or
replace motor. Check operation.
furnace. Check
NEUTRAL?
Is 24V present across control terminals
2K 2J
NO Is 24V present at control terminals
Replace transformer. Check operation.
at primary of transformer?
G & C?
YES YES
Repair wiring between control and
transformer primary. Check
NEUTRAL?
Repair low voltage wiring from transformer to
Repair low voltage wiring to
Correct 120V power supply to
thermostat. Check operation.
control. Check
control. Check

TROUBLESHOOTING
GUIDE
3A 3F
Call for heat.
Is induced draft motor energized?
Is diagnostic LED flashing 3
contacts R & W close.
3B
Is diagnostic LED flashing 2
switch.
at fuse or circuit breaker.
Place incline manometer in
Test for continuity across
series with pressure switch
pressure switch.
tubing.
3J
Is pressure greater than pressure switch
wiring. If OK, repair or replace
Is pressure switch welded
switch. Check
inducer motor. Check operation.
switch. Energize
system. Check
flue collar.
Is pressure greater than pressure switch
or incorrectly installed vent. Check operation.
Repair leaks in inducer assembly or
replace induced draft motor. Check

INTEGRATED FURNACE
Main Burner Ignition Check.
Does ignitor warm up and
Inducer ON.
4B
4F
Turn power OFF to furnace.
Unplug ignitor from wire harness. Connect voltmeter
Is gas valve manual
to ON position. Check operation.
control. Energize
system.
Turn manual knob to OFF position. Connect
manometer to outlet pressure tap. Turn knob
air. Energize system. Check
to ON position. Energize system.
Is outlet pressure detected after
Refer to service facts or installer’s
Replace ignitor. Check operation.
Is 120V present at ignitor leads?
guide for proper pressure settings.
4K
to required pressure setting. Check operation.
defective wiring. Check operation.
to gas valve leads. Energize
Restore gas supply at source. Check operation.
system.
4N
Is 24V detected across gas valve leads after
Is 24V present across control MV terminals after
module. Check
Replace gas valve. Energize
Repair or replace broken leads to gas valve.
system. Check
Check operation.

TROUBLESHOOTING
GUIDE
Is blower at heat speed within 1 minute of burner ignition?
Does main burner remain
energized with flame present?
properly.
5E
5D
De-energize system.
Disconnect 12-pin connector. Connect ohmmeter from flame
Repair wiring and/or replace
sensor pin FP to burner GROUND.
NEUTRAL?
motor. Check
module. Check
5F
5M
system at main fuse or circuit breaker. Connect
Disconnect flame sensor from wire. Measure continuity from
Reverse 120V LINE & NEUTRAL
less than 50 megohms (50,000,000
Is 120V present at burner ground?
voltmeter from control terminal LINE NEUTRAL
wires. Energize
wire end to FP pin on 12-pin connector.
system. Check
to BURNER GROUND.
Energize module.
5N
5J
5K
Is control ground wire connected to
Disconnect lead from flame sensor. Connect ohmmeter
in series with flame
Clean surface of flame sensor with
Is sensor lead good?
sensor and sensor lead. Energize system. Measure current when
fine steel wool. Reinstall. Check
from sensor to burner ground.
burner ignites.
5O
5P
Connect ground wire from burner to
Repair or replace wire. Energize system. Check operation.
sensor. Does sensor have carbon or
12-pin connector terminal GROUND.
Check operation.
less than 50 megohms?
Replace sensor. Energize system. Check operation.
Replace flame sensor lead. Check