Rosemount 3095 MultiVariable™ Mass Flow Transmitter with HART® or FOUNDATION™ Fieldbus Protocol
Product Discontinued



© 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307, F (952) 949-7001 T (International) (952) 906-8888
Emerson Process Management GmbH & Co. OHG Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172 Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 T (65) 6777 8211, F (65) 6777 0947
Beijing Rosemount Far East Instrument Co., Limited No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233, F (86) (10) 6422 8586
This installation guide provides basic guidelines for the Rosemount 3095 MultiVariable Mass Flow Transmitter (reference manual document number 00809-0100-4716). It also provides the basic electronics guidelines for the 3095MFA (reference manual document number 00809-0100-4809), the 3095MFC (reference manual document number 00809-0100-4810) and the 3095MFP (reference manual document number 00809-0100-4686). It does not provide instructions for configuration, diagnostics, maintenance, service, or troubleshooting. Refer to the appropriate reference manual for more instruction. These manuals are also available electronically on www.rosemount.com
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Process leaks may cause harm or result in death.
Electrical shock can result in death or serious injury.





Figure 1. Using a Mounting Bracket

(1) Panel bolts are customer supplied.
Liquid Flow Applications · Gas Flow Applications

To improve field access or to better view the optional LCD display:
Housing Rotation Set Screw (9/64-inch)
a.Install the flange or flange/adapter bolt finger-tight. b.Torque bolts to initial torque value using a cross pattern (see Table 1). When
installing to a mounting bracket, torque bolts to 125 in./lb (169 N/m)
Table 1. Torque Cross Pattern
Bolt Material Initial Value Final Value Carbon Steel (CS) 300 in./lb (34 N/m) 650 in./lb (73 N/m) Stainless Steel (SST) 150 in./lb (17 N/m) 300 in./lb (34 N/m)

STEP 2 CONTINUED...
Figure 2. Alarm Jumper Location

4. Set the Simulate Jumper (FOUNDATION fieldbus devices), which is located on the front of the electronics board inside the electronics housing cover. The jumper is used to simulate the measurement and is used as a lock-out feature for the AI function block. To enable the simulate feature, insert the jumper across ENABLE while the transmitter is powered. The default position for the Simulate Jumper is DISABLE. Enable the simulate feature after power is applied to the device. Simulate is automatically disabled regardless of jumper position if power is cycled.
Figure 3. Armored Shielded RTD Cable

3/4 to 1/2-14 NPT Adapter Bushing

STEP 2 CONTINUED...
Figure 4. Shielded RTD Cable
Cable Adapter 1/2–14 NPT
Figure 5. ATEX/IECEx Flameproof RTD Cable
RTD Cable Gland CM20

Black Cable Connector/ RTD Connector
Black Cable Connector · Cable Adapter

STEP 2 CONTINUED...
If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 6 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 6. Common Transmitter Assemblies

4 x 1.75-in. (44 mm) 4 x 1.50-in. (38 mm)
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Figure 7. If bolt material is not shown in Figure 7, contact the local Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt. 2. Finger-tighten the bolts. 3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 7 for initial torque value. 4. Torque the bolts to the final torque value using the same crossing pattern. See Figure 7 for final torque value. 5. Verify that the flange bolts are protruding through the isolator plate before applying pressure.


Figure 7. Torque values for the flange and flange adapter bolts
WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring
that is designed for its specific flange adapter, as shown below.

Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the o-rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring.

The 3095 Engineering Assistant (EA) for HART and 3095 Engineering Assistant (EA) for FOUNDATION Fieldbus software programs can be installed on the same computer. The applications cannot be open simultaneously.
a.Place the CD-ROM in the drive and run setup.exe from Windows NT, 2000, or XP. b.After installing the software, install the HART Modem (see “Installing the HART
Modem” on page 11). 2. Upgrade the previous versions of Engineering Assistant program (if required)
a.Place the CD-ROM disk 2 into the drive and run the EAUpgrade.exe from Windows
98, NT, 2000, or XP. To properly install, the program will first uninstall Engineering Assistant from the computer. (Upgrades also are available at www.rosemount.com) b.Remove the installation disk and reboot the computer to complete installation. c.To install the upgraded program, run the EAupgrade.exe from Windows 95,98, or
NT again. 3. Connect the computer to the 3095 transmitter.
a.Connect the HART modem cable to the computer using the 9-pin serial or USB
communications port on the computer. b.Open the cover above the side marked Field Terminals, and connect the
mini-grabbers to the two 3095 terminals marked COMM. 4. Select Engineering Assistant for HART from the program menu. On-Line Mode: EA communicates directly with the 3095 through AMS.
a.In AMS Explorer view or AMS Connection view, right-mouse click on a 3095 device
tag or icon. b.Select SNAP-ON/Linked Apps > Engineering Assistant. Off-Line Mode: Engineering Assistant does not communicate directly with the 3095. Instead, the EA configuration is sent to a 3095 later when Engineering Assistant is in on-line mode. In the off-line mode a future device needs to be created in order to launch Engineering Assistant.
a.In AMS Explorer view or AMS Device Connection view, left click on Plant Database
to the Area folder. b.Left click on Area to the Unit folder. c.Left click on Unit to the Equipment Module folder. d.Left click on Equipment Module to the Control Module folder. e.right-mouse click on Control Module to the pop-up context menu. f. Select Add Future Device. g.Select 3095MV Template and click OK. h.Right-mouse click on Future device to pop-up context menu. i. Select SNAP-ON/Linked Apps > Engineering Assistant.

STEP 3 CONTINUED...
After installing the 3095 Engineering Assistant, the HART modem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may be installed manually with the following procedure.
a.Place CD-ROM disk 2 into the drive. b.Browse and select 3095 Engineering Assistant for FOUNDATION Fieldbus software
application from Windows NT, 2000, or XP c.Open the ReadMe.txt file and follow the instructions provided. 2. Install the FOUNDATION Fieldbus communication card.
a.Insert either the PCMCIA card or PCI card into the computer, following the
instructions provided with the communications card. 3. Connect the 3095 transmitter to computer and establish communications.
a.Connect the 9-pin communications cable into the FOUNDATION Fieldbus card port
located in the computer. b.Connect communication wiring to connection ports labeled “D+” and “D-”. c.Open the transmitter cover on the side marked “Field Terminals” and connect the
communication wires to the two 3095 transmitter terminals labeled “Fieldbus Wiring”. 4. Select the 3095 Engineering Assistant for FOUNDATION Fieldbus from the program menu or use the 3095 EA FOUNDATION fieldbus shortcut icon.

STEP 4: CONNECT WIRING AND POWER UP (HART) STEP 4: CONNECT WIRING AND POWER UP (HART)
Use the following steps to wire the transmitter:
Figure 8 shows wiring connections necessary to power a 3095 and enable communications with a hand-held HART communicator.
Figure 8. Transmitter Wiring Diagrams (4–20 man Power Supply)

Installation of the transient protection terminal block does not provide transient protection unless the 3095 case is properly grounded.
The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included. Figure 9. Load Limitation
Max. Loop Resistance = Power Supply Voltage-11.0

16.5(2)
(1) For CSA approval, power supply must not exceed 42.4 Vdc. (2) HART protocol communication requires a loop resistance value between 250-1100 ohms, inclusive.
24 Vdc Supply · Load (Ohms) · Power Supply

Use the following steps to wire the transmitter:
To operate and provide complete functionality, the transmitter requires the supply voltage to be within the ranges shown below.
Approval Option Code Supply Voltage B, D, F, J, K, L, N, 2, 4, 9 9-30 Vdc A, C, E, G, H, P, R, 0, 3, 5, 7, 8 9-32 Vdc T, U, V, W, Y, 6 9-17.5 Vdc
A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.
Signal wiring of the fieldbus segment can not be grounded. Grounding out one of the signal wires will shut down the entire fieldbus segment.
To protect the fieldbus segment from noise, grounding techniques for shield wire usually requires one and only one grounding point for shield wire to avoid creating a ground loop. The ground point is typically at the power supply.
For every fieldbus segment a terminator should be installed at the beginning and at the end of each segment.

Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual.
Use the following steps to send the configuration to the transmitter. All previous transmitter information will be overwritten when the information is sent.
Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default.
Table 2. HART Communicator Fast Key Sequence
Function/Variable Fast Key Sequence
% rnge 1, 1, 2 % rnge 1, 1, 5, 1, 3 4V is 1, 1, 5, 4, 1 AO Alrm typ 1, 4, 1, 1, 1 AO1 1, 1, 3 AO1 3 AP Damping 1, 4, 2, 5, 2 AP Sens Trim 1, 2, 2, 1, 2 AP Units 1, 3, 2, 2 Absolute (AP) 1, 1, 4, 2 Atm Press Cnfg 1, 4, 2, 3 Burst mode 1, 4, 1, 2, 4, 2 Burst option 1, 4, 1, 2, 4, 1 Change PV Assgn 1, 1, 5, 1, 5 Change SV Assgn 1, 1, 5, 2, 3 Change TV Assgn 1, 1, 5, 3, 3 Change 4V Assgn 1, 1, 5, 4, 3 D/A trim 1, 2, 2, 2, 1 DP Low Flow Cutoff 1, 4, 6 DP LRV 4

Function/Variable Fast Key Sequence
DP Sens Trim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV 5 DP units 1, 3, 2, 1 Date 1, 3, 4, 4 Descriptor 1, 3, 4, 2 Diff pres damp 1, 4, 2, 4 Diff pres 1, 1, 1 Diff pres 2 Fld dev rev 1, 3, 4, 9, 2 Flo rate 1, 1, 4, 5 Flow Rate Special Units 1, 4, 5, 1 ✓Flow Units 1, 3, 2, 5 GP Damping 1, 4, 2, 5, 4 GP Sens Trim 1, 2, 2, 1, 3 GP Units 1, 3, 2, 4 Gage (GP) 1, 1, 4, 4 Hardware rev 1, 3, 4, 9, 4 LCD Settings 1, 4, 3 Loop test 1, 2, 1, 1 Message 1, 3, 4, 3 Num req preams 1, 4, 1, 2, 2 Num resp preams 1, 4, 1, 2, 3 PV is 1, 1, 5, 1, 1 Poll addr 1, 4, 1, 2, 1 Process temp unit 1, 3, 2, 3 Process temp 1, 1, 4, 3 RS type 1, 3, 5, 10 ✓RTD Config 1, 4, 2, 2 ✓Range values 1, 3, 3 Reset 1, 2, 1, 3 SP Snsr Range 1, 3, 5, 2 SP Type 1, 3, 5, 3 SV is 1, 1, 5, 2, 1 Scaled D/A trim 1, 2, 2, 2, 2 Status group 1 1, 6 Totalizer 1, 4, 4 Totalizer Special Units 1, 4, 5, 2 TV is 1, 1, 5, 3, 1 ✓Tag 1, 3, 1 Temp Sens Trim 1, 2, 2, 1, 4 Temp damp 1, 4, 2, 5, 3 Universal rev 1, 3, 4, 9, 1 View status 1, 2, 1, 2 Write protect 1, 3, 4, 8 Xmtr Var Slot Assn 1, 4, 1, 2, 4, 3

Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features.
Use the following block examples to do basic configuration to the transmitter. For more advanced configurations including configuring the 3095 Mass Flow transducer block, see the 3095 Manual (00809-0100-4716).
Use the following steps to create and send the mass flow configuration to the Mass Flow Transducer Block.
AI Block configuration parameters
Parameters Enter Data Channel 1 = Pressure 2 = Static Pressure 3 = Process Temperature 4 = Device Temperature 5 = Mass Flow L_Type Direct, Indirect, or Square Root XD_Scale Scale and Engineering Units (Note: Only select the units that are supported by the device.)
Pressure: Pa bar inH20 @ 68°F psi inHg @ 0°C kPa mbar mmH20 @ 68°F g/cm2 mmHg @ 0°C mPa atm ftH20 @ 68°F kg/cm2 mmH20 @ 4°C torr inH20 @ 4°C Temperature: °C °F K
Mass Flow Rate: lbm/sec lbm/min lbm/hr lbm/day kg/sec kg/min kg/hour g/sec g/min g/hr StdCuFt/sec StdCuFt/min StdCuFt/hr StdCuFt/day StdCuM/sec StdCuM/min StdCuM/hr StdCuM/day Out_Scale Scale and Engineering Units

A zero trim is a single-point adjustment used for compensating mounting position effects and line pressure effects. When performing a zero trim, ensure the low side block valve is closed, the equalize valve is open, the high side block valve is open, and all wet legs are filled to the correct level.
Using the Field Communicator
Fast Keys Steps 1, 2, 2, 1, 1 Trim DP Offset (Zero) 1, 2, 2, 1, 2 Trim SP Offset (Zero), (AP, GP)
Using the Foundation Fieldbus AI Block
For zero errors greater than the allowable zero trim, compensate for the offset by using the XD_Scaling, Out_Scaling and Indirect L_Type.
Using the Foundation Fieldbus Host System
Perform a Zero Trim method if the host system supports methods associated with the TRANSDUCER 1400 block. Otherwise, if the host system does not support methods see the 3095 Manual (00809-0100-4716).

Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co., Limited – Beijing, China
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com A hard copy may be obtained by contacting our local sales office.
ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
3095F_2/3,4/D and 3095M_2/3,4/D Flow Transmitters — QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity Assessment All other 3095_ Transmitters/Level Controller
— Sound Engineering Practice Transmitter Attachments: Process Flange - Manifold
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (2004/108/EC)
3095 Flow Transmitters — EN 61326-1:1997 – A1, A2, and A3
Ordinary Location Certification for Factory Mutual As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
FM Approvals A Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Enclosure Type 4X. Factory Sealed. Provides nonincendive RTD connections for Class I, Division 2, Groups A, B, C, and D. J Intrinsically Safe for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G hazardous outdoor locations. Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code T4. Factory Sealed. For input parameters and installation see control drawing 03095-1020.
North American Certifications

Canadian Standards Association (CSA) C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-1024. Approved for Class I, Division 2, Groups A, B, C, and D. K Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. when installed in accordance with Rosemount drawing 03095-1021. Temperature Code T3C. For input parameters and installation see control drawing 03095-1021.
F ATEX Intrinsic Safety Certificate Number: BAS98ATEX1359X II 1 G Ex ia IIC T5 (Tamb = –45 °C to 40 °C) Ex ia IIC T4 (Tamb = –45 °C to 70 °C)
Table 3. Connection Parameters (Power/Signal Terminals)
Ui = 30V Ii = 200 mA Pi = 1.0 W Ci = 0.012 µF Li = 0
Table 4. Temperature Sensor Connection Parameters
Uo = 30V Io = 19 mA Po = 140 mW Ci = 0.002 µF Li = 0
Table 5. Connection Parameters for Temperature Sensor Terminals
Co = 0.066 F Gas Group IIC Co = 0.560 F Gas Group IIB Co = 1.82 F Gas Group IIA Lo = 96 mH Gas Group IIC Lo = 365 mH Gas Group IIB Lo = 696 mH Gas Group IIA Lo/Ro = 247 H/ohm Gas Group IIC Lo/Ro = 633 H/ohm Gas Group IIB Lo/Ro= 633 H/ohm Gas Group IIA
Special Conditions for Safe Use The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulation test required by EN 60079-11, Clause 6.3.12. This condition must be accounted for during installation.
European Certifications

G ATEX Type n Certificate Number: BAS98ATEX3360X II 3 G Ex nL IIC T5 (Tamb = –45 °C to 40 °C) Ex nL IIC T4 (Tamb = –45 °C to 70 °C) Ui = 55V
The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD) Special Conditions for Safe Use The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulation test required by EN60079-15 Clause 6.8.1. This condition must be accounted for during installation. H ATEX Flameproof Certificate Number: KEMA02ATEX2320X II 1/2 G Ex d IIC T5 (-50°C Tamb 80°C)
T6 (-50°C Tamb 65°C) 1180 Special Conditions for Safe Use (x): The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. P ATEX Dust Certificate Number: KEMA02ATEX2321 II 1 D Ex tD A20 T 90°C(-40°C Tamb 80°C) V = 55 Vdc MAX I = 23 mA MAX IP66
4 IECEx Intrinsic Safety Certificate Number: IECEx BAS06.0070X Ex ia IIC T4 (-45°C Ta 70°C) Ex ia IIC T5 (-45°C Ta 40°C)
Table 6. Input Parameters
HART I.S.
Ui = 30Vdc
Ii = 200 mAdc
Pi = 1.0 W
Ci = 12 nF
Li = 0
IECEx Certifications (HART)

Table 7. RTD Terminals Entity Parameters
Uo = 30Vdc Io = 19 mAdc Po = 140 mW
The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values:
Group Capacitance (F) Inductance (mH) or L/R Ratio
H/Ohm IIC 0.066 96 247 IIB 0.56 365 633 IIA 1.82 696 633
NOTE 1. The external circuit contains no combined lumped inductance and capacitance greater than 1% of the above values. Or 2. The inductance and capacitance are distributed as in a cable. Or 3. The external circuit contains only lumped inductance or only lumped capacitance in combination with a cable. In all other situations e.g. combined lumped inductance and capacitance, up to 50% of each of L and C values is allowed.
Conditions of Certification (X): When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.3.12 of IEC 60079-11. This must be taken into account during installation. 5 IECEx Type n Certificate Number: IECEx BAS06.0071X Ex nA nL IIC T4 (-45°C Ta 70°C) Ex nA nL IIC T5 (-45°C Ta 40°C) Ui = 55V dc max Conditions of Certification (X): When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.8.1 of IEC 60079-15. This must be taken into account during installation. 7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C Ta 65°C) Zone 0/1 Ex d IIC T5 (-20°C Ta 80°C) Vmax = 55 Vdc Imax = 23 mAdc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP66
E INMETRO Flameproof BR-Ex d IIC T6/T5
INMETRO Certifications

2 China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x):
Ci 0 Li 0
6. The terminals for connection to power supply of transmitter should be connected to associated apparatus certified by NEPSI in accordance with GB3836.1-2000 and GB3836.4-2000 to establish intrinsic safety system, it has to fulfill the following requirements: UoUi __IoIi __PoPi __CoCc+Ci __LoLc+Li Note: Cc, Lc the distributed capacitance and inductance of the cables Uo, Io, Po maximum output parameters of associated apparatus Co, Lo, maximum external parameters of associated apparatus
7. The terminals for connection to sensor of transmitter should be connected to intrinsic safety sensor certified by NEPSI in accordance with GB3836.1-2000 and GB3836.4-2000 to establish intrinsic safety system, it has to fulfill the following requirements: Ui Uo __Ii Io __Pi Po __Ci Co-Cc __Li Lc+Lo Note: Cc, Lc the distributed capacitance and inductance of the cables Ui, Ii, Pi maximum input parameters of intrinsic safety sensor Ci, Li, maximum internal parameters of intrinsic safety sensor
10.End users is not permitted to change any components insides.
China (NEPSI) Certifications

11.When installation, use and maintenance transmitter, observe the following standards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines): GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
3 China Flameproof Ex d II B+H2T4~T6 Special conditions for safe use (x):
Process Medium (°C) Temperature Class
10.When installation, use and maintenance of transmitter, observe following standards. GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
R TIIS Flameproof Consult factory for availability
Maximum Temperature of

Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
B A and J combination D C and K combination L F, G, H, and P combination 9 4, 5, 7, and 8 combination Rosemount 3095 with Fieldbus
Rosemount Inc. — Chanhassen, Minnesota USA
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com A hard copy may be obtained by contacting our local sales office.
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
3095F_2/3,4/D and 3095M_2/3,4/D Flow Transmitters
— QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity Assessment
All other 3095_ Transmitters/Level Controller
— Sound Engineering Practice
— Sound Engineering Practice
— See appropriate Primary Element QIG
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

North American Certifications
A Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Enclosure type NEMA 4X. Factory Sealed. Provides nonincendive RTD connections for Class I, Division 2, Groups A, B, C, and D. J Intrinsically Safe for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G hazardous outdoor locations. Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing 03095-1020. V FISCO for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G hazardous outdoor locations. Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing 03095-1020.
Canadian Standards Association (CSA)
C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Factory Sealed. CSA enclosure Type 4X for indoor and outdoor hazardous locations. Suitable for Class I, Division 2, Groups A, B, C, and D. Install in accordance with Rosemount Drawing 03095-1024. K Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. When installed in accordance with Rosemount Drawing 03095-1021. Temperature Code T3C. W FISCO Field Device. Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
When installed in accordance with Rosemount Drawing 03095-1021. Temperature Code T3C.
F/T ATEX Intrinsic Safety Certificate Number:
II 1 G EEx ia IIC T5 (Tamb = -45°C to 40°C) EEx ia IIC T4 (Tamb = -45°C to 70°C)
Table 8. Connection Parameters (Power/Signal Terminals)
Fieldbus (F Option) FISCO (T Option) Ui = 30V Ui = 17.5V Ii = 300 mA Ii = 380 mA Pi = 1.3 W Pi = 5.32 W Ci = 3.3 nF Ci < 5 nF Li = 0 Li = 10 µH
FM Approvals · European Certifications · Baseefa 05ATEX0022X

Table 9. Temperature Sensor Connection Parameters
Uo = 30V Io = 19 mA Po = 140 mW
Table 10. Connection Parameters for Temperature Sensor Terminals
Co = 0.066 F Gas Group IIC Co = 0.560 F Gas Group IIB Co = 1.82 F Gas Group IIA Lo = 96 mH Gas Group IIC Lo = 365 mH Gas Group IIB Lo = 696 mH Gas Group IIA Lo/Ro = 247 H/ohm Gas Group IIC Lo/Ro = 633 H/ohm Gas Group IIB Lo/Ro= 633 H/ohm Gas Group IIA
Special conditions for safe use (x): Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when installing the apparatus. G ATEX Type N Certificate Number: Baseefa05ATEX0023X
II 3 G EEx nA nL IIC T5 (Tamb = –45 °C to 40 °C) EEx nA nL IIC T4 (Tamb = –45 °C to 70 °C) Ui = 55V RTD Terminals - The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD). Special Conditions for Safe Use Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 8.1 of EN 60079-15:2003. This must be taken into account when installing the apparatus. H ATEX Flameproof Certificate Number: KEMA02ATEX2320X
II 1/2 G EEx d IIC T5 (-50°C Tamb 80°C)
T6 (-50°C Tamb 65°C) Vmax = 55 Vdc MAX Imax = 23 mA MAX IP66
Special conditions for safe use (x): The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

II 1 D T90°C (-50°C Tamb 80°C) Vmax = 55 Vdc Imax = 23 mA IP66
4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C Ta 70°C) Ex ia IIC T5 (-45°C Ta 40°C)
Table 11. Input Parameters
Fieldbus I.S. FISCO Ui = 30Vdc Ui = 17.5Vdc Ii = 300 mAdc Ii = 380 mAdc Pi = 1.3 W Pi = 5.32 W Ci = 3.3 nF Ci 5 nF Li = 0 Li 10 mH
Table 12. RTD Terminals Entity Parameters
Uo = 30Vdc Io = 19 mAdc Po = 140 mW
The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values:
H/Ohm IIC 0.066 96 247 IIB 0.56 365 633 IIA 1.82 696 633
Conditions of Certification (X): When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.4.12 of IEC 60079-11: 1999. This must be taken into account during installation. 5 IECEx Type n Certificate Number: IECEx BAS05.0024X Ex nC IIC T4 (-45°C Ta 70°C) Ex nC IIC T5 (-45°C Ta 40°C) Ui = 55V dc max Conditions of Certification (X): When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 8 of IEC 60079-15: 1987. This must be taken into account during installation.

7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C Ta 65°C) Zone 0/1 Ex d IIC T5 (-20°C Ta 80°C) Vmax = 55 Vdc Imax = 23 mAdc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP66
Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
B A and J combination D C and K combination L F, G, H, and P combination 6 T, G, H, and P combination 9 4, 5, 7, and 8 combination