Instruction/ maintenance manual of the product 2330MKII Emerson
Go to page of 50
BOOK 0958-B Series 2330MKII Single-Phase Adjustable-Speed DC Motor Controllers (1/6 – 3 H P ) Control Techniques 3750 East Market Street York, PA 17402-2798 717-751-4200, FAX 717-7 51-4263 www.
.
BOOK 0958-B SERIES 2330 MKII SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6 - 3 HP) Control Techniques 3750 E Market Street York, PA 17402-2798 USA Tel 717.
BOOK 0958-B.
BOOK 0958- B iii TABLE OF CONTENTS SECTION TITLE PAGE I .......................................... GENERAL INFORMATION ................................................................ ... 1 Introduction ................................................
BOOK 0958-B iv LIST OF TABLES TABLE TITLE PAGE 1 ................... Se rie s 2 330 MK II M od el Mat ri x ............................................................................. ..............1 2 ................... Ju mp er J 4 P os iti on ...
BOOK 0958- B v Blank Page.
BOOK 0958-B vi WARNING The following must be strictly adhered to at all times. 1. YOU AS THE O WNER OR OPERATOR OF FINCOR EQUIPMENT HAVE THE RESPONSIBILITY TO HAVE THE USERS OF THIS EQU IPMENT TRAINED IN ITS OPERATIO NS AND WARNED O F ANY POTENTIAL HAZARDS OF SERIOUS INJURY.
BOOK 0958- B 1 SECTION I GENERAL INFORMATION INTRODUCTION This manual contains installation, op eration, and mainten ance and repair in structions for Finco r Series 2330 MKII Single-Phase Adju stable-Speed DC Mot or Controllers. A part s list, ratings and specifications, and drawing s are also included.
BOOK 0958-B 2 MOTOR SELECTION Series 2330MKII Controllers control the operation of general purpose DC motors designed for use with solid-state rectified power supplies. The motor may be shunt-wound, stabilized shunt-wound, or permanent magnet. For maximum efficienc y, the motor should be rated for operation from a NEMA Code K p ower supply.
BOOK 0958- B 3 SECTION II INSTALLATION Before starting the installa tion, read this section thoroughly. In addition, a thorough re view of the Ratings an d Specifications (Section VI) is recommen ded. The followin g instal lation guidelines should be ke pt in mind wh en installi ng th e controller.
BOOK 0958-B 4 5. ISOLATION T RANSFORME R - While not required , an isolation transformer can provide the follo wing advantages: a. Reduce the risk of person al injury if high voltage drive circuits are a ccidentally touched. b. Provide a barrie r to externally generated AC supp ly transi ents.
BOOK 0958- B 5 INSTALLING TH E CONTROLLER 1. Remove the controller front co ver (if used) by removing the four cover screws. 2. Check components in the controller for ship ping damage. Report shipping damage to the carrier. 3. Check the controller and motor data labels to be sure the units are electrically compatible.
BOOK 0958-B 6 9. If the controller con tains any options that re quire external wiring, follow the wi ring instructions in the instruction sheet supplied with the option. 10. If rem o te operator control wiring and/ or sign al w irin g is requ ired , c onnec t th e co ntro ller as shown in the appropriate connection diagram (Figures 3 through 1 8).
BOOK 0958- B 7 FIGURE 1. CONTROLLER MOUNTING CONFIGURATIONS.
BOOK 0958-B 8 FIGURE 2. CONTROLLER MOU NTING DIMENSIONS.
BOOK 0958- B 9 Figure 3. Logic connection diagram, Run-Stop-Jog Switch Figure 4. Logic connection diagram, Forward-Reverse Switch and Run-Stop-Jog Switch.
BOOK 0958-B 10 Figure 5. Logic connection diagram, Run-Stop Pushbuttons and Run-Jog Switch Figure 6. Logic connection diagram, Run-Stop-Controlled Stop Pushbuttons and Run-Jog Switch.
BOOK 0958- B 11 Figure 7. Logic connection diagram, Optional Unidirectional Contactor using Run-Jog Switch Figure 8. Logic connection diagram, Optional Unidirectional Contactor using Run-Stop Pushbutt.
BOOK 0958-B 12 Figure 9. Logic connection diagram, Optional Armature Contactor Reversing using Switches Figure 10. Logic connection diagram, Optional Armature Contactor Reversing using Pushbuttons and.
BOOK 0958- B 13 Figure 11. Logic connection diagram, Line Starting with Motor Speed Potentiometer Figure 12. Signal Connection Diagram, Motor Speed Potentiometer.
BOOK 0958-B 14 Figure 13. Signal Connection Diagram, Tachometer Feedback Figure 14. Signal Connection Diagram, Current (Torque) Reference Potentiometer Figure 15.
BOOK 0958- B 15 Figure 16. Signal Connection Diagram, 4-20mA Interface Figure 17. Signal Connection Diagram, 4-20mA Transducer with Manual/Auto Switch Figure 18.
.
BOOK 0958- B 17 INITIAL STAR TUP 1. Open the controller cover (if used) by removing the four cover screws. 2. Be familiar with all options installed in the controller by re viewing the instruction sheets supplied wit h the options. 3. Be sure all wiring is corre ct and all wiring terminati ons are tightened securel y.
BOOK 0958-B 18 Blank Page.
BOOK 0958- B 19 SECTION III OPERATION POWER ON/OFF To energize the drive, turn-on the AC supply voltage to the controller. When this oc curs, the motor shunt field energizes with rated field voltage, and potentially hazardous volta ge is present at th e mo to r a r mat u re te r min a ls .
BOOK 0958-B 20 TABLE 5. DYNAMIC BRAKING CHARAC TERISTICS a RA TED HORSEPOWER COMPONENT MODEL RA TED VOLTAGE 1/6 1/4 1/3 1/2 3/4 1 1-1/2 2 3 115V 180 129 103 66 44 34 NA NA NA 2331 2335 230V NA NA 400 .
BOOK 0958- B 21 REVERSE To reverse motor rotation on controllers with rev ersing cap abilities, initiat e a Stop function and then initiat e a reversing command. Th e motor will then accelerate to th e setting of the MOTOR SPEED potentiometer or external speed reference signal, as applicable.
BOOK 0958-B 22 Blank Page.
BOOK 0958- B 23 SECTION IV MAINTENANCE AND REPAIR GENERAL 1. Keep the controller dry and free of dust, dirt, and debris. No parts require perio dic replacement. 2. Peri odically t urn-off the AC line su pply to th e controller and check all wire terminations to be sure they are tight.
BOOK 0958-B 24 MINIMUM SPEED 1. Turn the MIN SPD potentiometer fully counterclockwise (0%) f o r zero spee d. 2. Set the MOTOR SPEED potentiom eter at 0% or the exte r n al speed reference si gnal at minimum, as applicable.
BOOK 0958- B 25 TROUBLESHOOTING TABLE 6. TROUBLESHOOTING INDICATION POSSIBLE CAUSE CORRECTIVE ACTION AC line open Be sure rated AC line voltage is applied to the controller. Operator controls inoperative or c on- nected incorrectly Repair accordingly.
BOOK 0958-B 26 TABLE 6. TROUBLESHOOTING INDICATION POSSIBLE CAUSE CORRECTIVE ACTION One or more SCR‘s or Diode D1b shorted Replace shorted devices or the c ontrol board.
BOOK 0958- B 27 TABLE 6. TROUBLESHOOTING INDICATION POSSIBLE CAUSE CORRECTIVE ACTION Low line voltage Check f o r rated li ne voltage, ±10%, o n the controller line terminals. Motor overl oaded Check shunt field current. a Low shunt field current causes excessive arm ature current.
BOOK 0958-B 28 TABLE 6. TROUBLESHOOTING INDICATION POSSIBLE CAUSE CORRECTIVE ACTION 9. Line an d motor arma ture current excessive Motor overl oaded Check shunt field current. a Low shunt field current causes excessive arm ature current. If field current is adequa te, check for a mechani cal overload.
BOOK 0958- B 29 SECTION V PARTS LIST TABLE 7. PART S LIST, SERI ES 2330 MKII CONTROLLERS FINCOR PART NUMBER PART RATING MODEL 2331 2335 MODEL 2332 2336 Control Board NA 106703903 106703904 15A, 600V 3.
BOOK 0958-B 30 Blank Page.
BOOK 0958- B 31 SECTION VI RATINGS AND SPECIFICATIONS RATINGS 1. Duty ........................................................................................................................ ............................. Continuou s 2. Horsepo wer Range .
BOOK 0958-B 32 TABLE 9. OPERATING VOLTAGES AND SIGNALS OUTPUT VDC POWER SOURCE (Single- phase) Armature Field SPEED REFERE NCE SIGNAL MAGNET IC CONTROL VOLTAGE 115V, 50 or 60 Hz 0 - 90 50/100 230V, 50 or 60 Hz 0 - 180 100/200 0 -5 Vdc 0 - 10 Vd c 4 - 20Ma 24 VDC TABLE 10.
BOOK 0958- B 33 Regulation percentages are of m otor ba se speed under steady-state conditions TABLE 11. SPEED REGULA TION CHARACTERISTICS VARIABLE REGULATION METHOD Load Change (95%) Line Voltage (±.
BOOK 0958-B 34 4. MOTOR CONTACTOR - Control ler model numbers with a n ‘A’ or ‘B’ suffix, e.g. , 2331A, 2331AP0, ha ve a DC magnetic armature c ontactor, which disconnects both m otor armature leads from the contr oller. An antiplug cir cuit ensures that the contactor d oes not make or br eak DC.
BOOK 0958- B 35 SECTION VII DRAWINGS.
BOOK 0958-B 36 Figure 19. Functional Schematic, Series 2330MKII 1.
BOOK 0958- B 37 Figure 20. Series 2330MKII Control Board, 1/6 – 3HP.
BOOK 0958-B 38 Blank Page.
BOOK 0958- B 39 Index A AC LINE PROTECTION ........................................ 33 AC supply tr ansients ................................................... 4 ACCEL potentiometer .............................................. 23 ACCELERATION .....
BOOK 0958-B 40 Maximum Speed ....................................................... 33 MAXIMUM SPEED ................................................ 23 MIN SPD potentiometer ........................................... 24 Minimum Speed ..............
BOOK 0958- B 41.
www.fincor.net.
An important point after buying a device Emerson 2330MKII (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Emerson 2330MKII yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Emerson 2330MKII - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Emerson 2330MKII you will learn all the available features of the product, as well as information on its operation. The information that you get Emerson 2330MKII will certainly help you make a decision on the purchase.
If you already are a holder of Emerson 2330MKII, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Emerson 2330MKII.
However, one of the most important roles played by the user manual is to help in solving problems with Emerson 2330MKII. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Emerson 2330MKII along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center