Serial communications permits largeamounts of informationto be processed over afew wires.In theserial communications systems used by ASCO,each individual device in the system --- automatic transfer switch, bypass-isolation switch, ATS annunciator, etc. --- has a unique code, or address, that is assigned to it through DIP switches in the devices. According to the established ASCO serial communications rules, or protocol, each ATS annunciator and/or the network supervisor on the communication link “talks” to all automatic transfer switches and other elements being monitored on the link at the same time. They all “hear” what is being said, but only the device that is addressed responds.

Sending and receiving requests and commands is done over the same pair of twisted wires linked in anetwork fashionfrom onedevice to another to form the communication link, or highway. This physical configuration comprises a network in which only the addressed device is permitted to go on line and respond to an inquiry. With this serial communications system, a minimum number of wires can be used to link the elements together. Without serial communications, it would take considerably more wires to accomplish the same thing.

INSTALLATION

The ATS Annunciator has been tested and is ready to use. Installation simply requires mounting, connecting power and communication wiring, and setting DIP switches. When unpacking the unit, locate theloose partswhich aresupplied in a separate kit. The kits contain the following parts:

Emerson 214A404 — INSTALLATION diagram (page 2)
Fig. 1
Master Kit 401091Slave Kit 401092 label holder labels & 2 resistorslabel holder labels, 2 resistors, & ribbon cable

The Master ATS Annunciator can be readily identified by the front mounted key switch (to prevent unauthorized operation). You will find the key taped inside the back panel. Up to two Slave ATS Annunciators can be mounted directly above or below the Master. All three ATS Annun- ciators are then interconnected by means of ribbon cables. All external wiring for power and serial communication line connects to the Master ATS Annunciator. Observe the requirements of the National Electrical Code (especially Articles 725 and 800) and any local codes when interwiring.

Mounting An Outline and Installation drawing (JS 387797) is included in the back of this manual. The two---part enclosure, which measures 10I wide x 6I high and 2I deep, is designed for mounting to the standard wall boxes listed on the drawing. After removing the front cover the hinged circuit board opens to the right to expose the mounting holes in the base.

Figure 1. Cover removal.

power wires, insulated ground wire, and communication cable hinged circuit board

Emerson 214A404 — INSTALLATION diagram (page 2)
Fig. 2

Loosen four screws to remove the cover as shown in Figure 1. Remove four screws and remove the face plate. Then remove the two left standoffs and swing the hinged circuit board to the right as shown in Figure 2. You will find the key taped to the back panel. Run the power wires (and insulated ground wire) and communication cable (twisted pairs) through the center hole in the back of the enclosure, then to the right through the notch in the circuit board. Attach the ATS Annunciator to the wall box by using the mounting holes that line up. Swing the circuit board closed again. Reinstall the two standoffs and tighten them securely. Reinstall the face platewith fourscrews.

Connecting Slave ATS Annunciators Connect the Slave ATS Annunciator(s), when used, to the Master. Remove the adhesive labels from the slotted openings as shown in Figure 2.

Then run the ribbon cable between ATS Annunciators and plug each end into the adjacent sockets. Two Slaves may be connected to one Master either by above and below arrangement or two below arrangement. See the Outline and Installation drawing for details.

slotted opening for ribbon cable and removable label

Figure 2. Hinged circuit board (Master).

Show 4 more labels / short text on this page
Serial Communications · face plate screws · cover cover screws · face plate standoff
Page 3 of the Emerson 214A404 user manual — Networks for Interconnecting ATS Annunciators and ATSs
Page 3 · click to enlarge
Page 3

INSTALLATION (continued) Power Wiring The Master ATS Annunciator can be powered by either an ac or dc source (but not both) as shown onthe Outline and Installation drawing 387797 and in Figure 3. For ac wiring use a Class 2 bell transformer with a 120 V ac primary and a 16 V ac secondary (12 VA minimum). Connect the ac wiring to terminals 9 and 10; connect the ground to terminal 1. For dc wiring connect a 12 or 24 V dc power source (750 ma) to terminals 7 (---) and 8 (+).

Emerson 214A404 — T+ diagram (page 3)
Fig. 3

T+

Standard 80˚ C

T---

R+

R--- resistor on Master 1 only

Belden 9842 Belden 9829 Alpha 6202C Alpha 6222C

Belden 82729 Alpha 58902

To prevent damage do not energize the circuit at this time.

Communication Wiring

Figure 3. Terminal block (Master). Located on right side of circuit board.

Connect one end of the transmit and receive commu- nication cable (twisted pairs) to terminals 3 through 6 on the Master ATS Annunciator as shown on the Outline and Installation drawing 387797 and in Figure 3. Refer to the Daisy Chain and Star configuration hook up drawings for typical arrangements. Use communication cable specified in Figure 3. This cable has two twisted pairs (4 wires) and an overall shield. All twisted pair shields must be connected to terminal 2 for grounding. The earth ground is connected to terminal 1 and internally jumpered to terminal 2. Two resistors are supplied. Connect one resistor (390 Ohm, 1/4 Watt, 5%) between terminals 5 and 6 on Master 1 only. See Figure 3. (The other resistor will be con- nected at the automatic transfer switch furthest away.) Two twisted pairs can be connected to the ATS Annunciator terminal block. Use a separate terminal block (not supplied) mounted in a separate wall box if more connections are necessary, as shown in Figure 4.

Emerson 214A404 — Communication Wiring diagram (page 3)
Fig. 4 · Communication Wiring

Figure 4. Typical separate terminal block.

Networks for Interconnecting ATS Annunciators and ATSs

Refer to Drawing JS 401900 Sheets 1 through 4 for typical interconnection schemes. The Daisy Chain configuration utilizes a single run of communication cable with all of the equipment connectedin parallel as shown on Sheet No. 1. This type of network utilizes the least amount of cable and is probably the most popular approachwhenlongline runs are anticipated.Depend- ing on the desired reliability of the system, some consideration should be given to the effect of a cable break. If the cable is broken all ATSs beyond the break will lose their communication. It should be kept in mind that annunciator lamps will flash if a disconnec- tion occurs. Also, a disconnection of the communica- tions cable will in no way impair the operation of the automatic transfer switch.

Star networks can be used as an alternate configu- ration as shown on Sheet No. 2. With this approach, greater reliability can be achieved because a discon- nect of the cable between the junction box and the ATS will only impair one switch.

Depending on location of this equipment it may sometimes be advantageous to use combinations of Daisy Chain and Star networks. Typical configurations are shown on Sheets No. 3 and 4.

Show 6 more labels / short text on this page
Acceptable Communication Cable · shield gnd · Belden 1419A · Plenum Rated · ! · Belden 89729
Page 4 of the Emerson 214A404 user manual — Set Number of Masters and Master Address
Page 4 · click to enlarge
Page 4

SETTING UP THE ATS ANNUNCIATORS

Catalog 214A400, 214A404 Master ATS Annunciators Catalog 214A401 Slave ATS Annunciator

Emerson 214A404 — SETTING UP THE ATS ANNUNCIATORS diagram (page 4)
Fig. 5
Emerson 214A404 — SETTING UP THE ATS ANNUNCIATORS diagram (page 4)
Fig. 6
Emerson 214A404 — SETTING UP THE ATS ANNUNCIATORS diagram (page 4)
Fig. 7

Master ATS Annunciator factory default settings Slave ATS Annunciator factory default settings Figure 5. DIP switches in Master. Figure 6. DIP switches in Slave. Before applying power to the ATS Annunciators, the DIP switches must be set to select the number of Masters and Slaves, Master Address, and the addresses of each automatic transfer switch connected. Refer to Figures 5 and 6 for the location of DIP switches. See Charts 1, 2, 3, and 4 for position of actuators for each setting.

5 Controller menu selection for the serial communica- tion baud rate must be set to 9600.

Set Number of Slaves DIP switch S1 shown in Figure 6, (on the left side of each Slave) selects the number of the Slave (either 1 or 2). Refer to Chart 3. For example, if only one Slave is used, depress the actuators shown in the top figure (setting for Slave 1). If two Slaves are used, set one to the setting for Slave 1 and on the other Slave depress the actuators shown in the lower figure (setting for Slave 2).

Set Number of Masters and Master Address

ASCOBUS I communication protocol supports single– and multi–master, daisy chain, and star confi- gurations. Group 7/7A and 5 Controllers can be connected on the same network. In this case the Group 5 menu item selecting the serial communication baud rate must be set to x9600.

Setting the ATS Address Number DIP switches S2, S3, S4, and S5 on the ATS Master (Figure 5) and Slave Annunciators (Figure 6) are usedto set the unique address number for each ATS. Up to 32 ATSs can be accommodated on a system utilizing three Masters and five Slaves.

When more than one Master is being used, one Master must be selected as the Lead Master. Then the Lead Master must be told how many other masters there are. DIP switch S6 shown in Figure 5 on the Master ATS Annunciator selects how many Masters are being used (up to seven) and their addresses. Actuators 1 through 3 set the number of Masters (Chart 1 ) and actuators 4 through 6 set their addresses (Chart 2). For example, if only one Master is used, actuators 1 through 6 should be down (off). If more than one Master is used, select one as a Lead Master and set all other Masters to different address.

Actuator 1 must be on (up) for each address being used.

Refer to Chart 4 for selecting a unique address number for each ATS. One DIP switch is used for each ATS. For example, ATS 1 would use address 00 so set DIP switch S2 (on the Master) with actuators 2---6 down (off). ATS2 would use address 01 so set DIP switch S3 (on the Master) with actuator 6 up (on). Remember to move actuator 1 up (on) for each DIP switch being used! Refer to Table D at the back of this manual.

To select the ASCOBUS II communication proto- col, the DIP switches S6 actuators 1,2,3 must be set to ON position (ATS Annunciator must be deenergized). With ASCOBUS II protocol selected, Group 1 and 5 Controllers canbe connectedon the same network and the only configuration supported is the daisy chain configuration with single master annunciator and upto 2 slaves (see drawing 401900). In this case the Group

ATS Label Holder The ATS Annunciator is labeled for ATS1, ATS2, ATS3, and ATS4. Included with each ATSAnnunciator is an adhesive–backed label holder with labels for ATS5---12 and some blank labels. Label each ATS Annunciator with the ATS numbers that are addressed in it. Fill in Table D at the back of this manual.

Page 5 of the Emerson 214A404 user manual — SETTING UP THE ATS ANNUNCIATORS
Page 5 · click to enlarge
Page 5

SETTING UP THE ATS ANNUNCIATORS

Emerson 214A404 — SETTING UP THE ATS ANNUNCIATORS diagram (page 5)
Fig. 8
Page 6 of the Emerson 214A404 user manual — SETTING UP THE ATS ANNUNCIATORS
Page 6 · click to enlarge
Page 6

SETTING UP THE ATS ANNUNCIATORS

Emerson 214A404 — SETTING UP THE ATS ANNUNCIATORS diagram (page 6)
Fig. 9
Page 7 of the Emerson 214A404 user manual — HOW TO TEST AN AUTOMATIC TRANSFER
Page 7 · click to enlarge
Page 7

OPERATION

Catalog 214A400, 214A404, and 214A401 ATS Annunciators communicate with ASCO automatic transfer switches to report their status. Eachautomatic transfer switch is continuously polled and reports its status back to the ATSAnnunciator. Lightsonthefront indicate which automatic transfer switches are connected to the normal source or emergency source. Source availability is also reported.

to control their operation. A key switch prevents unauthorized operation. The Transfer Test push button simulates a normal source outage and transfers the individual load to the emergency source, if available. When the same push button is pressed again, it signals the automatic transfer switch to retransfer back to normal immediately. A Time Delay Active push button bypasses any transfer time delay in process (Feature 2B or 3A). Lights above each push button indicate that the automatictransfer switchis inthe test mode andinatime delay mode.

In addition, the ATS Annunciators can send commands to individual automatic transfer switches

HOW TO TEST AN AUTOMATIC TRANSFER

SWITCH FROM THE ATS ANNUNCIATOR

1. Insert the switch key and turn it clockwise to the Unlock position as shown in Figure7. 2. Select the number of the automatic transfer switch you want to test and find the Transfer Test push button below the ATS number on the bottom row. 3. Press and hold the Transfer Test push button until the amber light above it starts flashing. 4. Observe that the Emergency Source Available red light comes on indicating that the generator has started. 5. Observe that the LoadConnectedto Emergency red light comes on (Normal light off) indicating that the ATS has transferred.

6. Press the Transfer Test push button again to end the test. The flashing amber light goes off.
7. Observe that the Load Connected to Normal green light comes on (Emergency light off) indicating that the ATS has retransferred.
8. When testing is completed, turn the key switch counterclockwise to the Lock position and remove the key.
Emerson 214A404 — HOW TO TEST AN AUTOMATIC TRANSFER diagram (page 7)
Fig. 10

Transfer test push button

Figure 7. ATS Annunciator (Master)

Show 8 more labels / short text on this page
status lights · Load connected to · Source available · Time delay active · key switch · Time delay bypass · push button · Transfer test
Page 8 of the Emerson 214A404 user manual — TROUBLE-SHOOTING
Page 8 · click to enlarge
Page 8

TROUBLE-SHOOTING

Table A. Trouble Shooting the ATS Annunciator

ProblemProbable CauseCorrective Action 1. Normal and Emergency lights flash alternately on all ATS Annunciators.No communication made. Incorrect, broken, or shorted wiring between ATSs and ATS Annunciators.Recheck wiring; check for shorted or open circuits. Be sure correct twisted pairs are connected. 2. Normal and Emergency lights flash alternately on only one Annunciator.No communication made. Addresses on ATSs do not correspond to addresses on ATS Annunciator.Recheck address settings in ATS Annunciator and ATS Control Panels. They must be the same. 3. Normal and Emergency lights flash for only one ATS column (not alternately)Communication lost to that ATS due to no power to ATS location.Check power and communication lines at all ATSs. 4. Normal and Emergency lights flash for all ATS columns (not alternately)Communication lost due to power failure at all ATSs, or broken or shorted communication line.Check power and communication lines at all ATSs. 5. When Transfer Test is pressed amber light does not flash.Key switch on Master ATS Annunciator in Lock position.Insert key and turn it to Unlock position. 6. When Time Delay Bypass is pressed amber light does not go off.Key switch on Master ATS Annunciator in Lock position. Key switch was turned to Lock before test completed.Insert key and turn it to Unlock position.

If corrections do not resolve the problem, call your local ASCO Power Technologies or Authorized Representative Office, or ASI. Furnish the Serial No. and Catalog No. from the transfer switch nameplate.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
1. Normal and Emergency lights flash alternately on all ATS Annunciators.No communication made. Incorrect, broken, or shorted wiring between ATSs and ATS Annunciators.Recheck wiring; check for shorted or open circuits. Be sure correct twisted pairs are connected. p.8
2. Normal and Emergency lights flash alternately on only one Annunciator.No communication made. Addresses on ATSs do not correspond to addresses on ATS Annunciator.Recheck address settings in ATS Annunciator and ATS Control Panels. They must be the same. p.8
3. Normal and Emergency lights flash for only one ATS column (not alternately)Communication lost to that ATS due to no power to ATS location.Check power and communication lines at all ATSs. p.8
4. Normal and Emergency lights flash for all ATS columns (not alternately)Communication lost due to power failure at all ATSs, or broken or shorted communication line.Check power and communication lines at all ATSs. p.8
5. When Transfer Test is pressed amber light does not flash.Key switch on Master ATS Annunciator in Lock position.Insert key and turn it to Unlock position. p.8
6. When Time Delay Bypass is pressed amber light does not go off.Key switch on Master ATS Annunciator in Lock position. Key switch was turned to Lock before test completed.Insert key and turn it to Unlock position. p.8

Ask about the Emerson 214A404

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson 214A404

Be the first to ask — other owners or our team will answer.

Original document

Emerson 214A404 manual PDF

8 pages·621 KB·Switch·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…