160/200/300/400kVA
User Manual
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Copyright © 2008 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
E-mail: [email protected]



This manual contains information concerning the installation and operation of the HIPULSE U single module (expandable) UPS of Emerson Network Power Co., Ltd. (Emerson for short).
All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or its agent) before being put into service. Failure to observe this condition will invalidate any implied warranty.
The HIPULSE U UPS has been designed for commercial or industrial use only, and is not for use in any life support application.



This equipment complies with the following requirements: Normative references: Uninterruptible Power System (UPS). z IEC60950-1, IEC62040-1-1 — General and safety requirements for use in operator access area z IEC/EN62040-2 — EMC requirements z IEC62040-3 — Performance requirements and test methods Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. This equipment must be earthed in accordance with local electrical codes.
Upstream power distribution protection device of the UPS must be selected according to local electrical codes.
If any internal fuse of the UPS is damaged, it must be replaced by professionals with a new one of the same specifications.
This equipment is fitted with radio frequency interference (RFI) suppression filters. Earth leakage current exceeds 3.5mA and is less than 1000mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breaker (RCCB) or residual current detector (RCD) devices. RCCBs must be selected insensitive to DC unidirectional pulses (Class A) and transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This system has a signal available for use with an automatic device, externally located, to protect against backfeeding voltage through the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass circuit, a label must be added at the switchgear to advise service personnel that the circuit is connected to a UPS system. The text is the following or equivalent:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these voltages is minimized as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
Conformity and standards · General

Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
The warning triangle indicates all the personal safety instructions.
Batteries









Chapter 1 General Description 1
This chapter briefly introduces the features, design concept and operation mode of the HIPULSE U UPS.
The HIPULSE U UPS is connected between a critical load, such as a computer, and its 3-phase mains power supply. Being designed to furnish a well regulated 3-phase output power supply under all rated load and input supply conditions, the system offers the user the following advantages:
z increased power quality
The UPS has its own internal voltage and frequency regulators which ensure that its output is maintained within close tolerances independent of voltage and frequency variations on the mains power lines.
z increased noise rejection
By rectifying the input AC power to DC power, and then converting it back to AC power, any electrical noise present on the input mains supply line is effectively isolated from the UPS output, therefore the critical load sees only clean power.
z power blackout protection
If the mains power fails, the UPS continues to power the critical load from its battery source, leaving the load immune from power disturbances.
This section describes the operating principle of an individual module. The UPS basically operates as an AC-DC-AC converter (see Figure 1-1). The first conversion stage (from AC to DC) uses a 3-phase, fully controlled silicon-controlled resistor (SCR) bridge rectifier to convert the incoming mains supply into a regulated DC busbar.
Rectifier Inverter Static switch
Figure 1-1 Single module block diagram
The DC busbar produced by the rectifier provides both battery charging power – being equipped with a temperature compensated battery charging system, to prolong battery life – and power to the inverter section – which utilizes the latest integrated gate bipolar transistor (IGBT) switching space vector pulse width modulation (SVPWM) design – and provides the second conversion phase, that is, reconverting the DC busbar voltage back into an AC voltage waveform.
During normal operation, both the rectifier and inverter sections are active and provide regulated load power whilst simultaneously charging the battery. In the event of a mains power failure, the rectifier becomes inoperative and the inverter is powered solely from the battery. Critical load power is maintained under these conditions until the battery is fully discharged, whereupon the UPS shuts down. The end of battery discharge is assumed when the battery voltage falls below a preset value (that is, 330Vdc for a 400Vac system).
The period for which the load can be maintained following a mains power failure is known as the system’s “Autonomy Time” and is dependent upon both the battery A/Hr capacity and the applied percentage load.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

2 Chapter 1 General Description
The circuit block annotated “Static switch” in Figure 1-2 contains an electronically controlled switching circuit, which enables the critical load to be connected either to the inverter output or to a bypass power source through the static bypass line. During normal system operation, the load is connected to the inverter, and the inverter-side of the static switch is closed. But in the event of a UPS overload or inverter failure, it is automatically transferred to the static bypass line.

Figure 1-2 UPS power switches configuration
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the static switch activates connecting the load to the bypass supplies. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from the mains (bypass) supply while the UPS is shut down for routine maintenance.
During normal operation, that is, when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker (BCB) is also closed and the battery is therefore permanently float charged at the DC busbar voltage level.
(“1+N” parallel UPS system) Note: As the unit outputs are connected in parallel, the system checks that the inverter control circuits are perfectly synchronized with one another and with the bypass mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronization is in progress.
A module's static switch cannot close until these conditions are satisfied.
If the power mains has a failure or is out of tolerance the rectifier will go off automatically, while the inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not returned within this time, the inverter will go off automatically and an alarm message will appear on the operator control and display panel of the UPS.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Bypass mains supply · Input mains · supply

Chapter 1 General Description 3
When the mains returns within the required tolerance, the rectifier will start up again automatically and gradually (power walk-in), supplying power to the inverter and recharging the battery at the same time. There will be no interruption of the critical load.
If the battery system only is taken out of service for maintenance, it is disconnected from the rectifier/charger and inverters by means of (an) external disconnect breaker(s). The UPS shall continue to function and meet all of the specified steady-state performance criteria, except for the power outage back-up time capability.
In the event of an inverter fault, the static transfer switch will automatically transfer the load onto the bypass mains with no interruption. In such an event, seek technical assistance from Emerson local customer service center.
(“1+N” parallel UPS system) In the event of a fault in a unit, the unit’s static transfer switch will automatically exclude the unit from the system. If the system is still capable of providing the required load, the remaining units will continue to supply the load with no interruption. When the units still present in the system are no longer capable of fulfilling power requirements, the load will automatically be transferred onto the bypass mains.
In the event of an overload at the inverter output which lasts longer than the typical time/current (refer to table 8-6), the inverter will shut down and the static transfer switch will automatically transfer the load onto the bypass mains with no interruption. If the overload falls within the typical time/current that has been specified, the load will be returned to the inverters when the power drops to a level which can be supported by the number of active units in the system (parallel “1+N”).
In the event of a short circuit in the output, the load will normally be transferred onto the bypass mains, which will cause the inverter to shut down. This switch is determined above all by the features of the protective devices in use in the system.
In either case, an alarm message will appear on the operator control and display panel of the UPS.
(“1+N” parallel UPS system) The control logic system constantly monitors load requirements and controls the power supplied by the UPS modules. In the event that an overload condition is sustained for greater than a preset time, the load will transfer to the bypass mains supply, when the number of active modules is unable to satisfy load requirements. The load returns to the inverter supply if the power is reduced to a value that can be sustained by the number of active modules in the system.
A second bypass circuit contained in the UPS cabinet, identified as the maintenance bypass line, is included to enable a raw mains supply to be made available to the load while facilitating a safe working environment for carrying out scheduled UPS system maintenance or trouble shooting. The circuit is manually selected by the maintenance bypass switch in the OFF position.
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel. CAUTION: If an automatic circuit breaking device is not present in the input distribution panel, there remains a dangerously high voltage at the output busbars and also on the input busbars of the UPS module that is switched off.
In ECO mode, the system prefers to put the load on the bypass mains, with the inverter on stand-by. The load is switched over to the inverter when the mains goes outside of standard frequency and voltage values (settable).
The ECO mode configuration requires a different setup in the default menu configuration.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

4 Chapter 1 General Description
Operating procedures in ECO mode are the same as those described in Chapter 5 Operating Instructions, except that the load is normally on the bypass mains, the Inverter LED is normally off, and the corresponding alarm message Bypass mode will appear on the LCD.
In ECO mode the load is not protected against mains distortion.
Figure 1-2 illustrates the HIPULSE U UPS module in what is known as the split bypass configuration. In the split bypass configuration, the static bypass line is connected by a separate power switch to a dedicated bypass power source which also feeds the maintenance bypass line. Where a separate power source is not available the bypass (Q2) and rectifier (Q1) input supply connections would be linked together.
With the exception of the maintenance bypass switch, all the switches shown must be closed during normal UPS operation.
The battery should be connected to the DC busbar through a circuit breaker fitted inside the battery cabinet — or located adjacent to the batteries where a battery cabinet is not used. This circuit breaker is closed manually, but it contains an undervoltage release coil which enables it to be tripped from the UPS control electronics following certain detected faults. It also has a magnetic trip facility for overload protection.
HIPULSE U UPS system offers a battery temperature compensation circuit. As the temperature inside the battery cabinet/area rises, the DC busbar voltage reduces in order to sustain the battery at its optimum charge voltage. This must be used in conjunction with the battery temperature sensing device.
If necessary, a single module system can be expanded to cater for an increased load requirement by adding additional modules — up to a maximum of six UPS modules can be connected in parallel.
System expansion requires a change in the SETUP of the operator control and display panel of each UPS module.
The UPS permits operation in the following alternative modes:
The UPS inverter continuously supplies the critical AC load. The rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously float or boost charging its associated backup battery.
Upon failure of the AC mains input power, the critical AC load is supplied by the inverter, which obtains power from the battery. There is no interruption in power to the critical load upon failure or restoration of the AC mains input power after which the Normal mode operation will continue without the necessity of user intervention.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 1 General Description 5
The battery becomes exhausted following an extended AC mains failure. The inverter shuts down when the battery reaches the end-of-discharge voltage (EOD). The UPS can be programmed to Auto Recovery after EOD after a set variable delay time. This mode and any delay time are programmed by the commissioning engineer.
The load power is supplied though the mains static bypass line. This may be considered as an intermediate operating condition being utilized for the purpose of load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.
The UPS is shut down but the load is connected to the unprotected mains through the maintenance bypass supply line.
The UPS has the capability of fully supporting their critical load while limiting the amount of power taken from the incoming AC mains supply. Any balance of power required is supplied by the UPS battery. This feature is useful, for example, in applications where peak-hour tariffs apply or where a generator smaller than needed feeds the UPS during mains outages. The Source Share mode is user-activated and the ratio of the mains AC input power is programmable from 20% to 100% of the rated UPS power.
All power switches and the BCB are closed, the system prefers to put the load on the bypass mains, with the inverter on stand-by; only when the voltage and/or frequency of the bypass supply are beyond pre-defined and adjustable limits is the critical AC load transferred to the inverter.
For higher capacity or higher reliability or both, the outputs of up to six UPS modules can be programmed for directly paralleling while a built-in parallel controller in each UPS ensures automatic load sharing.
The UPS can be programmed into Frequency Converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 45Hz to 65Hz. In this mode, it is required to open the bypass switch to disable the static bypass operation, and the battery becomes optional depending on any requirement to operate in Battery mode.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

6 Chapter 2 Mechanical Installation
This chapter briefly introduces the mechanical installation of the HIPULSE U UPS, including the notes, environmental considerations, mechanical considerations, preliminary checks and installation drawings.
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.
Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. 1. Eye protection should be worn to prevent injury from accidental electrical arcs. 2. Remove rings , watches and all metal objects. 3. Only use tools with insulated handles. 4. Wear rubber gloves. 5. If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations. 6. If electrolyte comes into contact with the skin the affected area should be washed immediately with water.
The UPS system can be connected to an isolated neutral (IT) power system. This chapter describes the environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide as to the general procedures and practices that should be observed by the installing engineer.
The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Table 8-2).
All models in the HIPULSE U UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located in the cabinet roof. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS through the floor void. If necessary, a system of extractor fans should be installed to aid cooling-air flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 2 Mechanical Installation 7
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote figures for an operating temperature of 20°C. Operating above this temperature will reduce the battery life, and operation below this temperature will reduce the battery capacity. On a normal installation the battery temperature is maintained between 15°C and 25°C. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Keep batteries away from main heat sources or main air inlets, and so on.
The batteries can be mounted in a purpose-built battery cabinet, which is positioned adjacent to the UPS module. Pedestals are required for the battery cabinets when they are located on raised floors, in the same way as for the UPS cabinets If the batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a BCB must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible.
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements, for example, UPS cabinet, battery cabinet. The 300kVA UPS (12-pulse rectifier) and 400kVA UPS comprise a main cabinet and a side cabinet. In general, all the cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form an aesthetically appealing equipment suit.
Ensure that any lifting equipment that used in moving the UPS cabinet has sufficient lifting capacity. Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. See Table 8-3 for UPS weight details.
The UPS cabinet can be moved by fork lift. Before moving the UPS cabinet, it is necessary to remove both the front, rear (or side) grille panels located at the base of the cabinet.
In the eventuality that the equipment cannot be moved by fork lift, then rollers should be used.
As HIPULSE U UPS has no ventilation grills at either the sides or the rear, no clearances are required. However, where space permits, a clearance of approximately 600mm at the back will ease access to magnetic component parts. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened.
Before the equipment is in place, remove the transportation restraints that hold the output transformer in place. For procedures, refer to Appendix 1 Transportation Restraints Removing Procedures.
Cables can enter for HIPULSE U UPS and battery cabinet either from below or through either side.
Side entry is made possible by removing blanking pieces fitted in the side panel to reveal the cable entry holes.
This cable entry method allows the equipment to be positioned on a solid floor without the need for cable trenching and allows cables to pass from one module to the other when positioned side-by-side.
Optionally a top cable entry extension may be used.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

8 Chapter 2 Mechanical Installation
Before you install the UPS hardware you should carry out the following preliminary checks:
The following drawings illustrate the key mechanical characteristics of the various UPS system cabinets.
Front view Side view


Removable grille - if using side cable entry (2 pcs in 628*102) 87 3
Removable grille for lifting with fork-lift truck (1 pcs in 1201*116, 2 pcs in 484*102)

Removable grille for lifting with fork-lift truck (1 pcs in 1201*116, 2 pcs in 484*102)
Figure 2-1 Front, side, top, back views of 160kVA/200kVA UPS (6-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 2 Mechanical Installation 9


14 holes for securing unit to floor (if required)
Grille for air entry from the bottom
Surface loading of UPS4× 104cm , 2.7Kg\cm 2 2
Figure 2-2 Top, base views of 160 kVA/200kVA UPS (6-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

10 Chapter 2 Mechanical Installation
Front view Side view

Removable grille - if using side cable entry (2 pcs in 628*102)
Removable grille for lifting with fork-lift truck (1 pcs in 1591*116, 2 pcs in 607*102)
Removable grille for lifting with fork-lift truck (1 pcs in 1591*116, 2 pcs in 607*102)
Figure 2-3 Front, side, top, back views of 160 kVA/200kVA UPS (12-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 2 Mechanical Installation 11

14 holes for securing unit to floor (if required)
Grille for air entry from the bottom
Surface loading of UPS 8× 104cm ,2.0Kg\cm 2 2
Figure 2-4 Top, base views of 160 kVA/200kVA UPS (12-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Top view

12 Chapter 2 Mechanical Installation

可拆卸 板 栅 1591*116 1件(卸下 板可 栅 用于叉 搬运 车 ,安装后可用于防 通 护 风)
Removable grille (1 pcs in 1591*116, for lifting with fork-lift truck after being removed, for protection and ventilation after being installed)
Removable grille (1 pcs in 1591*116, for lifting with fork-lift truck after being removed, for protection and ventilation after being installed)
Figure 2-5 Front, side, top, back views of 300kVA UPS (6-pulse rectifier) (unit in mm)

Cable entry holes Holes for securing unit to floor
Figure 2-6 Base view of 300kVA UPS (6-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 2 Mechanical Installation 13

Removable grille (1 pcs in 1591*116, 1 pcs in 631*116,for lifting with fork-lift truck after being removed, for protection and ventilation after being installed)
可拆卸 板 栅 1591*116 1件, 631*116 1件 (卸下 板可用于叉 搬运 栅 车 ,安装后可用于防 通 护 风)
Figure 2-7 Front, side, top, back views of 300kVA UPS (12-pulse rectifier) and 400kVA UPS (6/12-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

14 Chapter 2 Mechanical Installation

Figure 2-8 Base view of 300kVA UPS (12-pulse rectifier) and 400kVA UPS (6/12-pulse rectifier) (unit in mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 3 Electrical Installation 15
This chapter introduces the electrical installation of the HIPULSE U UPS, including the procedures or methods for power cabling and control cabling, and the distance from floor to connection point.
The UPS requires both power cabling and control cabling once it has been mechanically installed. All control cables, whether screened or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected.

BEFORE CABLING UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS SUPPLY TO THE MAINS DISTRIBUTION PANEL. CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY Warning SIGNS TO PREVENT THEIR INADVERTENT OPERATION. For cable entry, refer to 2.3.5 Cable Entry.
The power cables of the system must be size with respect to the following description:
The input cables must be sized for the maximum input current, including the maximum battery recharge current, given in the Table 3-1, with respect to the module rating and the input AC voltage.
The bypass and output cables must be sized for the nominal output current, given in the Table 3-1, with respect to the module rating and the output AC voltage.
Each UPS module has its own battery which is connected using two cables, one positive and one negative. The battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 3-1 with respect to the module rating.
The power cables can be sized to suit the UPS module rating according to Table 3-1.
Table 3-1 UPS module power cable rating

(subtract 5% for 12-pulse) Bypass/output at full load Input/output
160 341 324 312 243 231 222 464 M10 11 M10 bolt 26
200 426 405 390 304 289 278 580 M10 11 M10 bolt 26
300 634 602 572 456 434 413 870 M12 13 M12 bolt 50
400 848 803 772 607 578 556 1160 M12 13 M12 bolt 50
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

16 Chapter 3 Electrical Installation
The following are guidelines only and superseded by local regulations and codes of practice where applicable:
The rectifier input, bypass, output and battery power cables (all require lug type terminations) are connected to busbars situated below the power isolator switches, as shown in Figure 3-2 and Figure 3-3.
A terminal block X3 is used for connecting the control cables to the battery circuit breaker (BCB). These are female spade type connections (fast-on 6.3*0.8) and are described later in 3.3.2 Battery Control.
The safety earth busbar is located near the input and output power supply connections as shown in Figure 3-2 and Figure 3-3. The safety earth cable must be connected to the earth busbar and bonded to each cabinet in the system.
All cabinets and cable trunking should be earthed in accordance with local regulations. The earth cable should be bound with binding strips onto the metallic column for cabling so as to prevent the fixing screw of the earth cable from loosening in the case the earth cable is pulled.
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK HAZARD TO PERSONNEL, OR THE RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.
For safety reasons, it is necessary to install, external to the UPS system, circuit breaking protective devices in the input AC supply and towards the battery. Given that every installation has its own characteristics, this chapter provides general useful information for qualified installation engineers, with knowledge of operating practices, of regulatory standards, and of the equipment to be installed.
These inputs must be protected, installing suitable protective devices at the distribution panel of the incoming mains supply, considering that the protection should discriminate with overload capacity of the system (see Table 8-6 and Table 8-7).
In the case of a split bypass being used, separate protective devices should be installed in the incoming mains distribution panel. The protective devices must be selected for the nominal input current, with respect to the UPS rating and the input AC supply voltage as given in Table 3-1.
In the event of a residual current detector (RCD) device being installed upstream of the input supply, one must take into account the transient and steady state earth leakage currents that are produced during start-up of the UPS.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 3 Electrical Installation 17
The presence of a radio frequency interference (RFI) suppression filter inside the UPS determines a residual earth current greater than 3.5mA and less than 1000mA.
Residual current circuit breakers (RCCBs) must be sensitive to DC unidirectional pulse (Class A) in the network and insensitive to transient current pulses. They are identified by the symbols respectively:
Figure 3-1 Symbols of residual current circuit breaker (RCCB)
These isolators must have an average sensitivity, possible adjustable between 0.3A and 1A.
It is recommended that the selectivity with every RCD be verified both upstream of the input distribution board and downstream (towards the load).
The UPS Battery is protected by means of a control circuit that operates the tripping mechanism of an automatic circuit breaking device (having a variable trip setting). The tripping mechanism using an undervoltage release coil that operates on a present minimum voltage level.
The circuit breaker is essential for maintenance of the battery and is normally located near to the battery installation.
In the eventuality that an external distribution panel is used for load distribution, the selection of protective device must provide discrimination with those that are use at the input to the UPS module.
Once the equipment has been finally positioned and secured, refer to Figure 3-2 and Figure 3-3 to connect the power cables as described in the following procedures:
Ensure that any links (*) fitted between rectifier input and bypass busbars are removed. But do not remove those between the
neutral terminals. See Figure 3-2 and Figure 3-3.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

18 Chapter 3 Electrical Installation

If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that the system output cables are safely isolated at their ends.
Do not close the BCB before the equipment has been commissioned. 8. Refit the lower protective cover.


Figure 3-2 Power cable connections for 160/200kVA UPS
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 3 Electrical Installation 19

注:如采用分离旁路, 拆 请 除旁路和整流器 入之 的 输 间 三个横向跨接母线(*)
W2 V1 W1 V3 U3 N3 W3 V2 U2
池 接 电 连 整流器 接 连 旁路 接 连 出 接 输 连 接地
Figure 3-3 Power cable connections for 300/400kVA UPS
The distances from floor to connection points are provided in Table 3-2.
Table 3-2 Distance from floor to connection point

Minimum distance (mm) UPS 160/200kVA 300kVA 400KVA Rectifier AC input supply 247.5 273 273 Bypass AC input supply 247.5 273 273 UPS AC output 247.5 267.5 273 Battery power 244 300 305
Battery control and temperature compensation 325 350 350 Ground 247.5 270 274
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

20 Chapter 3 Electrical Installation
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system, communicate with a personal computer or provide alarm signaling to external devices or for remote Emergency Power Off (EPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. As shown in Figure 3-4, it provides the following ports:
z dry contact input ports (X3)
z dry contact output ports (X1)
z emergency Power Off (EPO) input port (X2)
z auxiliary DC power output port (X5)

MODEM / SNMP 卡 电
SNMP
RS232-1
J16
源
RS232-2
黑方 块 ( )代表引脚 1 X1
) on each slot The black square (
indicates Pin 1.
Figure 3-4 Ports of the monitoring board
The dry contact input ports (X3) include a battery environment, battery ground fault and generator supply detection port (J4) and a maintenance bypass cabinet port (J26, J30), as shown in Figure 3-5.

Figure 3-5 Dry contact input port
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
PWR Modem · card

Chapter 3 Electrical Installation 21
The battery environment, battery ground fault and generator supply detection port is described in Table 3-3.
Table 3-3 Description of battery environment, battery ground fault and generator supply detection port

Position Name Description J4.1 ENV3 Battery environment detection (NC) J4.2 BtG Battery ground fault detection (NC)
Note: 1. Must be configured by configuration software before becoming active. 2. When activated, the charger current can be limited, through software, to a percentage of the full charger current (0~100%). 3. Activating this feature will limit the battery charging The UPS accepts external signaling from voltage-free (dry) contacts connected to finger-proof, push-in terminal J4. Subject to prior software programming, the signaling is accepted by the UPS when connection between the relevant terminal and the +12V terminal of J4 is altered. Cables connected to J4 must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5 to 1mm2
cross-section area for maximum runs between 25 and 50 meters, respectively.
J26 and J30 are the maintenance bypass cabinet (MCB) port. The ports are described in Table 3-4.
Table 3-4 Description of maintenance bypass cabinet port

Position Name Description J26.1 T_IT* Input transformer overtemperature (NC) J26.2 AUX_I (Reserved)
J26.4 GND Power ground J30.1 FUSE (Reserved) J30.2 F_FAN Fan fail alarm (NC)
J30.3 T_OT* Output transformer overtemperature (NC) J30.4 AUX_O (Reserved) Note*: Must be configured by software before becoming active
All auxiliary cables must be double insulated. Wire should be 0.5~1.5mm2 stranded.
There are three output dry contact relays at the X1 slot, see Figure 3-6 and Table 3-5.

Figure 3-6 Dry contact output port
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

22 Chapter 3 Electrical Installation
Table 3-5 Description of dry contact output port
J13.2 BFP_O Bypass feedback protection relay (NO) J13.3 BFP_S Bypass feedback protection relay center J13.4 BFP_C Bypass feedback protection relay (NC) J21.2 INV_O On inverter dry contact relay (NO) J21.3 INV_S On inverter dry contact relay center J21.4 INV_C On inverter dry contact relay (NC)
J25.2 ACF_O Main input voltage or frequency fault relay (NO) J25.3 ACF_S Main input voltage or frequency fault relay center J25.4 ACF_C Main input voltage or frequency fault relay (NC)
All auxiliary cables must be double insulated. Wire should be 0.5~1.5mm2 stranded.
The UPS has an Emergency Power Off (EPO) function that operates by a button on the UPS door or by a remote contact provided by the user.
The X2 slot, shown in Figure 3-7, is the remote EPO input port, which is described in Table 3-6.

Figure 3-7 EPO input port
Table 3-6 Description of EPO input port
Position Name Description J28.1 EPO_NC EPO activated when opened to J28.2 J28.2 EPO_NC EPO activated when opened to J28.1 J28.3 EPO_NO EPO activated when shorted to J28.4 J28.4 EPO_NO EPO activated when shorted to J28.3 The remote EPO facility is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable. If this function is not used, terminals J28: 3&4 must be opened and J28: 1&2 must be closed.


The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated. Normally closed EPO–J28: 1, 2, these terminals are supplied factory-linked on the monitor board.
The auxiliary DC power output port X5 provides auxiliary DC power for optional SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.
The communication ports include the serial ports RS232-1 and RS232-2, Intellislot intelligent communication ports.
RS232-1 provides serial data and is intended for direct use with Emerson UPSitePlusTM UPS monitoring software.
RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Position Name Description

Chapter 3 Electrical Installation 23
There are three intelligent communication ports (Intellislot 1, Intellislot 2, and Intellislot 3) available for installing optional SNMP card, UPS JBUS/MODBUS adapter, and relay card.
The serial ports RS232-1, RS232-2, and the Intellislot intelligent communication ports share the same communication resources, as described in Table 3-7.
Table 3-7 Communication port resource deployment table

On the UPS LCD screen, under Settings, controlled by:
SNMP card 9600 JBUS/MODBUS adapter Any Intellislot 2 Comm 1
SNMP card 9600 JBUS/MODBUS adapter Any Intellislot 1 Comm 2
SNMP card 9600 JBUS/MODBUS adapter Any Intellislot 3 Comm 3
RS232-1 Comm 1 UPSitePlusTM UPS monitoring software 9600 -
RS232-2 Comm 2 Commissioning and service software (only for use by authorized commissioning and service personnel) 9600 Not simultaneous with the three Intellislot ports
The BCB is controlled by the BCB control board. Both are located within the BCB box. This board controls the circuit breaker's undervolts release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control logic.
All connections between the BCB control board and the UPS module are made through the auxiliary terminal block X3 located on the base of the UPS Cabinet. X3 is shown in Figure 3-8 and described in Table 3-8.
GND
OL
+12V
TMP_T
Battery temperature sensing 1
LM355+
Battery temperature sensing 2
DRV
DRV_GND
NC
12 Figure 3-8 Auxiliary terminal block X3
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

24 Chapter 3 Electrical Installation
Table 3-8 Description of auxiliary terminal block X3
X3 terminal reference Reference label Description
1 FB BCB normally open auxiliary contact 2 GND Signal ground 3 OL Cable detection 4 +12V Power positive 5 TMP_T Temperature sensing terminal 6 GND Temperature sensing signal ground
7 LM355+ LM335 detection positive 8 LM355+GND LM335 signal ground 9 DRV BCB drive 10 DRV_GND Drive ground Note: 1. The auxiliary cables of the battery must be screened and double insulated. 2. The screen is connected to the earth of the battery cabinet or supporting rack. 3. Use multiple-core shielded cables with a section of 0.5 to 1 mm 2. 4. Connect the cables with the fast-on 6.3*0.8 mm terminals (female) Connect the BCB control and temperature compensation cables between the UPS auxiliary terminal block X3 and BCB control board. For details, refer to Figure 6-5. These cable must be shielded, shield should be connected at protective earth of battery cabinet or battery breaker, not of UPS.
If battery temperature compensation is needed, this function must be activated by the commissioning engineer.
The 300kVA UPS (12-pulse rectifier) and 400kVA UPS comprise a main cabinet and a side cabinet.. In installation, you need to make electrical connection between the main cabinet and side cabinet.
The power cable connections between the main cabinet and side cabinet of the 300kVA UPS (12-pulse rectifier) and 400kVA UPS are shown in Figure 3-9 to Figure 3-11. The installation engineer should make cable connection in strict accordance with these figures.

Nut M10 Spring w asher 10
Figure 3-9 Power cable connection between main cabinet and side cabinet of 300kVA UPS (12-pulse rectifier)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Main cabinet

Chapter 3 Electrical Installation 25

Figure 3-10 Power cable connection between main cabinet and side cabinet of 400kVA UPS (6-pulse rectifier)

W6( red) W5( green) W4( yellow )
Figure 3-11 Power cable connection between main cabinet and side cabinet of 400kVA UPS (12-pulse rectifier)
You need not connect signal cables between the main cabinet and side cabinet of the 300kVA UPS (12-pulse rectifier).
When you connect signal cables between the main cabinet and side cabinet of the 400kVA UPS, you should connect the signal cables from the main cabinet to the corresponding ports on the ULW366SA8 board of the side cabinet. The connection relationship is shown in Table 3-9, you just need to connect the J2, J4, J6, J7 and J10 ports. The positions of the ports on the ULW366SA8 board are shown in Figure 3-12.
Table 3-9 Signal cable connection between main cabinet and side cabinet of 400kVA UPS
Port (side cabinet) Cable No. (main cabinet) Meaning J2 W98-12 Fan power J4 W98-13 Fan power J6 W45 Rectifier current detection J7 W41-5 Fuse fault detection J10 W58 Rectifier drive

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

26 Chapter 3 Electrical Installation
F1/F2/F3
T20 T19
I1-J9
I1-J9
I1-J1
W45-5 W45-4
W41-5
W302
W302 W302
J10
J5
J6
J7
J1
J11
W303-1
A2(1)-X7
W301
FAN12
J2
W98-12
A5(1)-J3
A2(2)-X7 ULW36CSA8
J12
W303-2
FAN15 FAN14 FAN13 J3
W300-1
W300-3 W300-2
J4
A5(1)-J5
W98-13
Figure 3-12 Signal cable connection between main cabinet and side cabinet of 400kVA UPS
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 4 Operator Control And Display Panel 27
This chapter expounds the functions and use of the components on the operator control and display panel of the HIPULSE U UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm message list
The operator control and display panel is located on the front door of the UPS. The panel is the access point for operator control and monitoring of all measured parameters, UPS and battery status and of event and alarm logs.
The operator control and display panel is divided into three functional areas: mimic power flow chart, graphic LCD monitor with menu keys, control buttons, as shown in Figure 4-1.
Mimic power flow chart Control buttons

Vphase V Iphase A Freq. Hz Vline V P. F.
Input Breaker Closed 10-12 12:28:16 Manual Turn On 10-12 12:30:06 UPS in Normal Mode 10-22 12:30:16
Alarm LED LCD menu keys Figure 4-1 Operator control and display panel
The six LEDs mounted on the mimic flow chart represent the various power paths of the UPS, and indicate the current UPS operational status and alarm status by color (red, green, yellow) and state (ON, OFF, flashing), as described in Table 4-1.
Table 4-1 Description of LED indicators
LED State Description Steady green Rectifier in normal operation Flashing green Input AC normal, but rectifier not operating
Steady red Rectifier f failed Rectifier LED
OFF Rectifier not operating, input ac not available or out of normal range Steady green Load on bypass power Steady red Bypass not available, out of normal range or static bypass switch fault Bypass LED
OFF Bypass normal, load not on bypass power Steady green Battery normal, but discharging and powering the load
Flashing green Battery end-of-discharge pre-warning Steady red Battery abnormal (failed, absent or polarity reversed) or battery circuit breaker abnormal Battery LED
OFF Battery and battery circuit breaker normal, battery charging Steady green Inverter normal and powering the load Flashing green Inverter ON, starting up, synchronizing, or standing by (ECO mode) Steady red Inverter failed Inverter LED
OFF Inverter not operating
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

28 Chapter 4 Operator Control And Display Panel

LED State Description Steady green UPS output ON and normal Steady red UPS output ON and overloaded Load LED
Steady green Normal operation Steady yellow UPS warning (for example, AC input failure) Alarm LED (STATUS)
Steady red UPS fault (for example, fuse or hardware failure)
The operator control and display panel provides a buzzer. UPS activity is accompanied by the following sounds.
Table 4-2 Audible alarm description
Single beep Direct access key acknowledgement One beep per second UPS warning. For example, AC input failure Continuous beep Fault. For example, fuse or hardware failure
The operator control and display panel provides four control buttons, as described in Table 4-3.
Table 4-3 Description of control buttons
INVERTER ON Pushing this button turns on the inverter. Note: If the inverter is not ready, pushing this button cannot turn on the UPS INVERTER OFF During UPS operation, pushing this button turns off the inverter and transfers the load to the bypass
FAULT CLEAR In case the UPS shuts down due to fault, after eliminating the alarm conditions, pushing this button clears the fault
When an alarm is active, pushing this button silences the audible alarm. When a new alarm occurs afterwards, the buzzer will give audible alarm again. When there is no audible alarm, pushing this button initiates the audible alrm test
To activate the above control buttons, you are required to press and hold the buttons for approximately 2 seconds until a beeping sound is heard.
The operator control and display panel provides an LCD and five menu keys (F1, F2, F3, F4, HELP). The menu keys are described in Table 4-4.
Table 4-4 Menu key icons and their meaning

The user-friendly and menu-driven LCD allows you to easily browse through the input, output, load and battery parameters, learn current UPS status and alarm information, perform functional setting and control operation. The LCD also stores up to 512 historical records that can retrieve for reference and diagnosis.
As shown in Figure 4-2, the LCD primary screen is divided into five windows: system information window, menu window, UPS data window, and current record window. Pressing the F1 key scrolls through the user-operable windows.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Control button Description

Chapter 4 Operator Control And Display Panel 29

Input breaker closed 10-12 12:28:16 Manual turn on 10-12 12:30:06 UPS in normal mode 10-22 12:30:16
Figure 4-2 LCD primary screen
The description that follows refers to the LCD primary screen shown on Figure 4-2.
The system information window displays current time and date and identifies the UPS, its configuration and its status. For details, see Table 4-5.
Table 4-5 System information window

No. Item Explanation 1 HIPULSE U UPS family name 2 2006-01-01 Current date
Single: single unit ECO: single unit operating in ECO mode Unit # 1: of max 6 units in a parallel system
Normal: UPS in normal operation, load on inverter, no alarm Warning: system attention required Fault: serious UPS fault existing
The menu window provides the menus of the STS data window. The UPS data window displays the items of the menu selected in the menu window. UPS parameters can be browsed and functions can be set through the menu window and UPS data window. Details are provided in Table 4-6.
Table 4-6 Menu window and UPS data window

No. Menu Item Explanation L-L voltage (V) Line voltage 1 Mains Frequency (Hz) Input frequency
L-N voltage (V) Phase voltage Frequency (Hz) Bypass frequency 2 Bypass
L-L voltage (V) Line voltage L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) Output frequency
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

30 Chapter 4 Operator Control And Display Panel
No. Menu Item Explanation Sout (kVA) Apparent power Pout (kW) Active power Qout (kVAR) Reactive power
Loadlevel (%) The percentage of the UPS rating load
Crest factor Output current crest factor Sout (kVA) Apparent power Pout (kW) Active power Qout (kVAR) Reactive power 5 System
Single system, no parallel data When configured as a single unit, UPS has only native load, no system load Battery voltage (V) Battery bus voltage Battery current (A) Battery bus current
Battery temperature (°C) Internal battery temperature °C Battery remain time (Min.) Battery run time remaining Battery boost charging Battery is boost charging Battery float charging Battery is float charging
Battery is not connected Battery is not connected
…… Inverter output abnormal 20-01-2006 11:30:02 22-01-2006 13:38:06 Battery maintained 22-01-2006 13:38:02 22-01-2006 13:38:36 ……
Displays up to 512-event history log indicating system status with start/stop date and time stamp for each event. You may scroll through the history log. Refer to Table 4-8 for a complete list of UPS alarm messages
Selects display in Chinese or English. Use F1, up and down arrow keys (F2, F3) to select this menu item, and press the Enter key (F4). Use left and right arrow keys (F2, F3) to reach desired language and press the Enter key (F4)
8 Language 中文/English
Adjusts the graphic LCD monitor contrast for best viewing. Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt this setting. Press the Enter key (F4). Select setting with left and right arrows (F2, F3) and press the Enter key (F4)
YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be selected. Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt this setting. Press the Enter key (F4). Select setting with left and right arrows (F2, F3) and press the Enter key (F4)
Adjusts time (in 24-hr format) and Date format (in user defined format previously set). Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt this setting. Press the Enter key (F4). Enter each date or time digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered
Comm1 baud rate (Monitoring board RS232-1, Intellislot 2) Comm2 baud rate (Monitoring board RS232-2, Intellislot 1) Comm3 baud rate (Monitoring board Intellislot 3)
Adjusts the transmission speed of any of the 3 UPS communication ports available. Available settings are - 9600bps (default setting, SNMP card supports this baud rate only) - 4800bps - 2400bps Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt the desired port and baud rate. Press the Enter key (F4)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 4 Operator Control And Display Panel 31
No. Menu Item Explanation
This setting applies to RS485 communication and the “one-to-multiple points” communication mode of parallel system. It is required to set the parameter Host communication mode of COM1 in parallel system to Multipoint to point using background software before setting the communication address of each UPS module
Communication mode Reserved modem function. No need to change the default setting “RS232” Callback times (reserved) Phone No.1 (reserved) Phone No.2 (reserved) Phone No.3 (reserved)
Modifies password for the Command menu. Use the Shift key (F1) to highligt Command Password, press the Enter key (F4). Enter each old password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered. Follow prompts and repeat the process for new password
Manually initiates battery maintenance test, which will lead to the battery being partly discharged, for rough assessment of the battery capacity. The Load must exceed 20% and be less than 80% of rated UPS capacity, and the battery must have been float charging for 5 hours or more. Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt the desired test. Press the Enter key (F4). Enter each password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered
Manually initiates battery capacity test, which will lead to the battery being completely discharged, for accurate assessment of the battery capacity. The Load must exceed 20% and be less than 80% of rated UPS capacity, and the battery must have been float charging for 5 hours or more. Use the Shift key (F1) and up and down arrow keys (F2, F3) to highligt the desired test. Press the Enter key (F4). Enter each password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered
Manually initiates the system test. The user actives this function, after 5 seconds, a pop window will appear to show the result of this diagnosis: Rectifier, Inverter, Monitor OK or Fault
Stop testing Manually stop the test, including maintenance test, capacity test and system test
Manually initiates freshening charge, when the battery is not in boost charge state. Use the Shift key (F1) and up and down arrow keys (F2, F3) to highlight this item. Press the Enter key (F4). Enter each password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered
Stop freshening charge Manually stop the freshening charge
Displays UPS firmware versions, including inverter, rectifier, monitoring board firmware versions 11 Version
UPS model Displays UPS model information; for example, 380V-50Hz
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

32 Chapter 4 Operator Control And Display Panel
Keeps a log of current alarms, ignores transient conditions that have been resolved. Use F1, F2 and F3 to read the alarm messages.
For a complete history log, refer to the Records menu in Table 4-6.
Refer to Table 4-8 for a complete list of UPS alarm messages.
The function of menu keys F1 to F4 and HELP is shown by a self-explanatory icon as appropriate for the particular window.
As shown in Figure 4-3, the UPS door provides an emergency power off (EPO) button. It is housed beneath a safety cover to prevent inadvertent operation. After the EPO button has been pressed and hold for 2 seconds, it disables the static switch block entirely (so removing load power). It also disables the rectifier and inverter, and trips the battery circuit breaker. Under normal circumstances it does not remove UPS input power since this is applied through a manually controlled external isolator; however, if the UPS input supply is connected through circuit breaker having an electrical trip facility, the EPO switch can be used to drive the external circuit breaker’s trip circuit so as to remove the UPS input power.

Emergency power off (EPO) button
Figure 4-3 Emergency power off button
Upon UPS start, the UPS executes system test, and the start screen will appear and remains approximately 15 seconds, as shown in Figure 4-4.

Figure 4-4 Start screen
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 4 Operator Control And Display Panel 33
After the UPS starts and finishes system test, the primary screen will appear, as shown in Figure 4-5. For details about the primary screen, refer to 4.1.5 Detailed Description Of Menu Items.
200kVA-3X3 HIPULSE U 2006-01-01
12:30:36 Unit #1 Normal
B(BC)
C(CA)
Vphase V Iphase A Freq. Hz
220 20.5 50.1 380 0.99
220 20.5 50.1 380 0.99
220 20.5 50.1 380 0.99
P. F.
Input Breaker Closed 10-12 12:28:16 Manual Turn On 10-12 12:30:06 UPS in Normal Mode 10-22 12:30:16
Figure 4-5 Primary screen
During UPS operation, if there is neither an alarm nor a keypad operation within two minutes, the default screen will appear, as shown in Figure 4-6. Two minutes later, the LCD backlight will turn off. When an alarm occurs or a key is pressed, the primary screen will return, and the LCD backlight will turn on.
The LCD will also return to the primary screen when pressing any menu key at the default screen.
HIPULSE U 2006-01-01 12:30:36 200kVA-3X3 Unit #1 Normal

Press any key, back to main menu.
Figure 4-6 Default screen
At the primary screen, use the HELP key to display the help screen, as shown in Figure 4-7. This screen describes current meanings of the menu keys to help you with the menu operation. Pressing the HELP key exits the help screen and returns to the primary screen.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

34 Chapter 4 Operator Control And Display Panel

Figure 4-7 Help screen
Operation of the HELP key:
A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command. The prompts are provided in Table 4-7.
Table 4-7 Prompts and meanings
No. Prompt Meaning
1 Transfer with interrupt, confirm or cancel
Inverter and Bypass supplies are not synchronized and any load transfer between the supplies will cause a brief load interruption
2 The load is too high to be transferred with interrupt
The total load must be less than the capacity of one unit to allow a parallel system to perform an interrupted transfer from bypass to inverter
3 This operation leads to output shutdown, confirm or cancel
No alternative supply is available and any Inverter Off operation will cause the load to be de-energised
4 This operation leads to inverter overload, confirm or cancel
Turning off this inverter will lead to the overload of remaining inverter(s) in a parallel system
5 Turn on more UPS to carry current load
The number of paralleled inverters already turned on is insufficient to carry the existing load
Battery capacity test discharges the battery 100%. This prompt apears to require your confirmation. Cancelling the test will ends the test and transfers the UPS to Normal mode
6 Battery will be depleted, confirm or cancel
7 System selftest finished, everything is ok No action required
8 System selftest finished, please check the current warnings Check the current record window
9 Enter control password Required for battery or UPS test (default: 12345)
10 Battery selftest condition is low, please check battery state and loadlevel
Battery test condition is not met. Please check whether the battery is in boost charge state and the load level meet the battery test conditions. To initiate the battery test, the load must range between 20% and 80%
11 Freshening charge condition is low, please check battery settings and state
This prompt appears when you select the freshening charge command while the freshening charge condition is not met (such as no battery, charger failure)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 4 Operator Control And Display Panel 35
Table 4-8 provides the complete list of UPS alarm messages supported for display either on the Records menu (historical data) or in the current record window (prevailing data) as described in 4.1.5 Detailed Description Of Menu Items.
Table 4-8 UPS alarm message list
Rectifier comm. fail Internal RS485 communication failure between monitor and rectifier
Mains volt. abnormal Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input line-to-neutral voltage amplitude of rectifier
Mains undervoltage Mains voltage is undervoltage. Check the input line voltage
Mains freq. abnormal Mains frequency is out of limit range and results in rectifier shutdown. Check the input voltage and frequency
Battery fuse fail Battery fuse flowout led to BCB tripping Rectifier block Rectifier detected faulty. Rectifier shuts down. Battery discharges
Rectifier overtemp. The temperature of heat sink is too high to keep the rectifier running. The UPS can recover automatically. Check the environment and ventilation Input fuse fail Input fuse blowout led to rectifier turning off Control power 1 fail UPS operates but Control Power is not available Control power 2 fail UPS operates but Redundant Control Power is not available Mains phase reversed Rectifier AC input phase sequence is reversed Rectifier current limit Rectifier overcurrent led to power limiting operating
Soft start fail Rectifier could not start due to low DC bus voltage Input filter fault Filter inductor overtemperature led to filter contactor tripping Filter contactor fault Filter contactor operation abnormal
Filter overcurrent Mains power outside the normal voltage or frequency range of the input passive filter results in filter overcurrent. Please find out the reason for the mains power abnormality REC drive cirtuit fault Rectifier being off due to improper connection of rectifier drive cable or rectifier type setting error REC input Ph. missing Rectifier input phase missing. Check the input power connection or if the mains power is abnormal
DC bus over voltage Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a fault in rectifier side
Bus capacitor overvolt Bus capacitor voltage exceeds 350V, rectifier is off. Check the voltages of the two groups of bus capacitors EPO Emergency Power Off direct access key pressed or external command received Input disconnect open Rectifier input switch open Input disconnect closed Rectifier input switch closed Normal mode Load supplied from inverter output through double conversion of the AC mains input supply
Source share mode Load supplied from inverter output through shared double conversion of the AC mains input supply and of the Battery supply PPF online Reactive input filter connected
PPF disconnecting Reactive input filter disconnected Battery mode Load supplied from inverter output through battery
No battery Check the battery and the battery wiring; check whether the BCB is closed and the BCB dry contact is connected
Auto start After UPS was shutdown at EOD, inverter auto starts when utility restore Generator connected The generator has been connected to the UPS BCB open Battery Circuit Breaker status (open) BCB closed Battery Circuit Breaker status (closed) Battery float charging Battery status (Float charge mode) Battery boost charging Battery status (Boost charge mode)
Battery discharging Battery status (discharge mode) Battery period testing Automatic periodic battery maintenance discharge test (20% capacity discharge) Batt. capacity testing User initiated battery capacity discharge test (100% capacity discharge) Batt. maint. testing User initiated maintenance discharge test (20% capacity discharge) UPS system testing User initiated system test Inverter in setting Inverter starting up and synchronizing
Rectifier in setting Rectifier starting up and synchronizing Battery Room Alarm Environment in Battery Room Needs Attention
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Alarm message Description

36 Chapter 4 Operator Control And Display Panel
Alarm message Description REC FLASH UPDATE Ongoing update of rectifier firmware INV FLASH UPDATE Ongoing update of inverter firmware MONITOR FLASH UPDATE Ongoing update of monitor firmware
Unit off confirm Prompt to press the Enter key (F4) to acknowledge that the UPS will be disconnected from other paralleled UPS modules
System off confirm Prompt to press the Enter key (F4) to acknowledge that the all paralleled UPS will be disconnected from the load Fault reset FAULT CLEAR direct access key pressed Alarm silence SILENCE ON/OFF direct access key pressed
Turn on fail Inverter failed to turn on when INVERTER ON direct access key was pressed. This may be as a result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready Alarm reset FAULT CLEAR or SILENCE ON/OFF direct access key pressed
Transfer confirm Prompt to press the Enter key (F4) to acknowledge that an interrupted load transfer to bypass will happen Transfer cancel Prompt to press the ESC key (F4) to avoid that an interrupted load transfer to bypass will happen Manual turn on Manual Turn On through operator control and display panel Manual turn off Manual Turn Off through operator control and display panel
Battery ground fault Battery leakage to ground detected (option) Protocol version clash Firmware incompatibility between Monitor Board and Digital Signal Processor Board Setting save error History records not saved. (Reserved) Battery overtemp. The Battery temperature is over limit. Check the battery temperature and ventilation Ambient overtemp. The Ambient temperature is over limit. Check the ventilation of UPS room Battery fault Battery detected faulty (Reserved)
Battery maintained Battery test failed, Battery should be replaced
Before the end of discharge, battery undervoltage pre-warning should occur. After this pre-warning, battery should have the capacity for 3 minutes discharging with full load. The time is user-configured from 3 to 60 minutes. Shut down the load in time Battery end of discharge Inverter turned off due to low battery voltage. Check the utility failure and try to recover it Inverter comm. fail Internal RS485 communication failure between monitor and inverter
The CAN communication between different UPSs within a parallel system fails. 1.Check if there are some UPSs not powered on in the parallel system. If so, power on these UPSs and check if the alarm disappears. 2. Press the FAULT CLEAR push button
Parallel comm. fail
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% rating. This alarm automatically resets once the bypass voltage goes normal. 1. First verify that the bypass voltage and frequency displayed on the operator control and display panel is within the selected range. Note here the rated voltage and frequency are specified by the system voltage level and output frequency level respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to be faulty
Bypass unable to trace
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal. First check if there are some relevant alarms such as Bypass disconnect open, Bypass phase reverse. If they appear, solve them first. 1. Then verify that the bypass voltage and frequency displayed on the operator control and display panel is within the bypass limit. Note here the rated voltage and frequency are specified by the system voltage level and output frequency level respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger through the configuration software according to the customer’s agreement
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition is no longer true. 1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so, solve it first. 2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek any possible measurements Inverter output abnormal Inverter output voltage beyond limits. Load transfers to bypass
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Battery low pre-warning · Bypass abnormal · Inverter asynchronous

Chapter 4 Operator Control And Display Panel 37
The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true, then check for and verify: 1. high ambient air temperature. 2. blocked cooling airway. 3. any fan failure. 4. prolonged inverter overload Fan fault At least one of the cooling fans has failed
Inverter overtemp.
Inverter STS fail At least one of the static switches of inverter side is open or short circuit. This fault is locked until power off
Bypass STS fail At least one of the static switches of bypass side is open or short circuit. This fault is locked until power off Operation invalid This record is registered following an incorrect operation
The UPS is confirmed to be overload when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the load percent indicated on the LCD to determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm
The UPS parallel system is confirmed to overload when the total load arises above 105% nominal rating for the set basic number of UPSs. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the system load percent indicated on the LCD to determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm
The UPS is confirmed to overload and the overload times out. Note 1: the highest loaded phase will indicate overload timing-out first. Note 2: When the timer is active then alarm “unit overload” should also be active as the load is above nominal. Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred to bypass. The inverter shutdown and will restart after 10 seconds. Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to inverter mode. Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an overload is indicated then check the load, and investigate any additional load connected prior to the alarm (if applicable)
Unit over load timeout
Byp. abnormal shutdown Both bypass and inverter voltages unavailable. Load interruption Inverter over current Inverter pulse width modulation module overloaded
The phase sequence direction of bypass voltage is reversed. Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C lags 120 degrees behind phase B. Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it is found to be in error
Load impact transfer A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverter
Transfer time-out The load is on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour Load sharing fault UPS modules within a parallel system are not sharing the load current equally DC bus abnormal DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass
System transfer The whole paralleled UPS system transferred to bypass at the same time. This message will appear on the UPS which passive transfer to bypass
Parallel board fault Malfunction of the paralleling control circuits of this UPS module. Can cause system transfer to bypass
The parallel cables are not connected correctly in a parallel system. Reset the fault by pressing the FAULT CLEAR button, then restart the inverter by pressing the INVERTER ON button Bypass over current Bypass current is over limit above 135% rating. The UPS just alarms and does nothing
LBS Active Load Bus Synchronization is active. The UPS is acting as an LBS master or slave in a dual bus configuration
LBS abnormal UPS set to LBS mode (master or slave), but no LBS signal on LBS bus. Check the LBS bus connection Byp. induct overtemp. Bypass load sharing inductor overtemperature. Check the environment and ventilation Static Sw. overtemp. Overtemperature of static switch on bypass or inverter side. Check the environment and ventilation
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

38 Chapter 4 Operator Control And Display Panel
UPS feeds output voltage back to the mains grill through bypass due to shortcircuit of static switch on bypass side during mains failure. In this case, lack of protective bypass switch or improper connection of switch auxiliary contact will endanger the user safety. Special attention should be paid to this INV drive circuit fault Improper connection of inverter drive cable, or equipment type setting error Bypass disconnect closed Bypass switch closed
Byp. feedback fault
Bypass disconnect open Bypass switch open Maint. disconnect closed Maintenance bypass switch closed
Maint. disconnect open Maintenance bypass switch open Output disconnect closed Output switch closed Output disconnect open Output switch open Check UPS output The UPS is off and has no output
If the UPS auto-recovery after EOD function is disabled, after UPS shutdown due to battery discharge to EOD (end-of-discharge) voltage, when the mains power is restored, the UPS will not restart automatically, and the LCD will display this alarm message Normal mode The UPS is in Normal mode Battery mode The UPS is in Battery mode Source share mode The UPS is in Source Share mode Bypass mode The UPS is in Bypass mode
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Alarm message Description · Output disabled

Chapter 5 Operating Instructions 39
This chapter provides detailed operating notes and instructions of the HIPULSE U UPS.
Only after an authorized engineer has conducted the initial power-on and finished the UPS configuration is the user allowed to operate the UPS. No user accessable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. Hazardous voltages are always present at the UPS input and output terminals. If the UPS is fitted with an internal Class A filter, the filter carries hazardous voltages too. 1. All the user controls and indicators (LED) mentioned in these procedures are identified in Chapter 4 Operator Control And Display Panel.
3. The HIPULSE U UPS system incorporates an optional automatic boost charge facility, which can be used in systems containing conventional flooded lead-acid batteries. If this type of battery is used in your installation you may notice that the battery charger voltage may be greater than its nominal (432Vdc for 380Vac, 446Vdc for 400Vac and 459Vdc for a 415Vac system) when the mains supply returns from a prolonged outage. This is the normal response of the boost charge facility: the charger voltage should return to normal after a few hours.
The UPS can be separated by means of power switches, mounted inside the cabinet and accessible after opening the front door, which has a key. The location of the UPS power switches is shown in Figure 5-1 and Figure 5-2.
The UPS module power switches are:
Q1 — input switch: Connects the UPS with the mains supply.
Q2 — bypass switch: Connects the UPS with the bypass supply.
Q3 — maintenance bypass switch (padlocked): Permits supply of the load directly by the bypass line for maintenance of the UPS module.
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
Q5 — output switch: Connects the output of the UPS to the load.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

40 Chapter 5 Operating Instructions

修插座 维 :用于 工程 行 维护 师进 UPS 使用 维护时 ,不可用作其它用途 Service socket: Designed for use in UPS service, cannot be used for other purposes Figure 5-1 Power switch location of 160/200kVA UPS

修插座 维 :用于 工程 行 维护 师进 UPS 使用 维护时 ,不可用作其它用途 Service socket: Designed for use in UPS service, cannot be used for other purposes
Figure 5-2 Power switch location of 300/400kVA UPS
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 5 Operating Instructions 41
This procedure must be followed when turning on the UPS from a fully powered down condition, that is, where the load is not being initially supplied at all or where supplied by the maintenance bypass switch. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
This procedure results in mains voltage being applied to the UPS output terminals. Isolate and attach warning labels to any downstream load connections, as applicable. 1. Open the UPS door to gain access to the power switches. 2. Close the bypass switch Q2 and output switch Q5. Close also any external output isolation switches, where used.
The LCD display becomes active and after initialization, the UPS output is powered from the bypass. At this point, the status of the LEDs is as described in Table 5-1.
Table 5-1 LED status
Bypass LED Steady green
Load LED Steady green
Battery LED Steady red
Alarm LED Steady yellow 3. Close the input switch Q1.
The rectifier LED flashes during the startup of rectifier and becomes steady green once the rectifier reaches normal operation state after about 15s.
The inverter will start up and the inverter LED flashes while it synchronizes to the bypass voltage frequency.
After the inverter is ready, the UPS transfers from bypass to inverter, the bypass LED turns off, and the inverter LED becomes steady green.
Table 5-2 LED status
Rectifier LED Steady green
Inverter LED Steady green
Load LED Steady green
The UPS is now operating in Normal mode
Apply only to a single module UPS and when programmed by the commissioning engineer to perform ECO mode control of the power delivered to the load.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

42 Chapter 5 Operating Instructions
Follow previous 5.2 Start-UP Procedure (Into Normal Mode) and observe at the end of the procedure that bypass LED on the operator control and display panel remains green (indicating that the load is supplied by the bypass mains).
The UPS is now operating in ECO mode
The Battery test mode procedures transfer the UPS into shared source mode wherein approximately 15% of the load power is supplied by the battery and the balance by the AC input mains.
z Battery maintenance test: verifies the battery integrity and leads to the battery being partly discharged (20%).
Battery low prewarning alarm)
z The load must be between 20% and 80% of rated UPS capacity.
z The battery must have been float charging for 5 hours or more.
The battery test procedures are password controlled and menu driven. The test is immediately terminated in the event of a battery or a mains failure and the total load power is supported from the remaining source without interruptions.
Use the right or left arrow key to navigate to the Command menu.
Use the Shift key (F1), up and down arrow keys (F2, F3) to highlight the desired test. Press the Enter key (F4).
When prompted, enter each password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered.
This test updates the battery information, including the battery autonomy time (battery discharge duration during AC input failure) and the battery aging coefficient (battery capacity percentage when compared to a new battery).
If required, the test may be stopped before completion by selecting Stop testing on the Command menu.
The UPS test procedure checks the control functions of the UPS, the mimic flow chart LEDs and the audible alarm. This self-test is password controlled and menu driven. It can be carried out from the operator control and display panel by the operator and takes 5 seconds.
Test procedure:
Use the right or left arrow key to navigate to the Command menu.
Use the Shift key (F1) and up and down arrow keys (F2, F3) to highlight the desired test. Press the Enter key (F4).
When prompted, enter each password digit with up arrow (F2) and use right arrow (F3) to access next field. Press the Enter key (F4) when all digits have been entered.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 5 Operating Instructions 43
After five seconds, a pop window will appear to showing the result of this diagnosis: rectifier, inverter, monitor OK or fault.
If required, the test may be stopped before completion by selecting Stop testing on the Command menu.
The following procedure transfers the load supply from being protected by the UPS into being connected directly to the AC input bypass supply though a maintenance bypass switch.
Except in emergency situations, so as not to risk a short interruption in powering the load, before initiating this bypass procedure, confirm that no warning status is displayed in the top right corner of the LCD screen. If a warning status is displayed, the operator will be prompted to confirm or cancel any action that can lead to load interruption. 1. Press the INVERTER OFF button on the operator control and display panel.
The UPS inverter will shut down and the load is supplied through the static bypass supply. At this point, the inverter LED extinguishes, and the alarm LED turns on.
The maintenance bypass supply is now in parallel with the UPS static switch supply, and the LCD shows messages reflecting the actions taken (that is, maintenance bypass closed, etc.).
This ends the bypass procedure. The load is now powered directly from the maintenance bypass supply.
The load equipment is not protected from AC supply aberration. Proceed with following steps if rectifier and battery shutdown is also required.
This will disable further rectifier, inverter, static switch and battery operation, but will not affect the maintenance bypass switch.
Before carrying out this step, verify that the EPO contact is not connected to any external switch or device. 5. Open the input switch Q1 and the bypass switch Q2.
All LED indications and messages on the operator control and display panel will extinguish as the mains driven internal power supplies decay.
The load is now powered from the maintenance bypass supply and the UPS is completely shut down.
This procedure must be followed to completely power down the UPS and load. All power switches, isolators and circuit breakers will be opened and power will be removed from the load.
The following procedure will switch off all power to the load equipment.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

44 Chapter 5 Operating Instructions
All LED indications and messages on the operator control and display panel will extinguish as the mains driven internal power supplies decay.
The UPS provides an EPO button on the UPS door. The EPO button is designed to switch off the UPS in emergency conditions (that is, fire, flood, etc.). To achieve this, just press and hold the EPO button for two seconds, and the system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS control circuit will remain active; however, the output will be turned off. To remove all power from the UPS, the external feeder breaker should be opened.
Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the LCD, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: inverter overtemperature, cut-off overload, battery overvoltage, excessive switching, etc.
After confirming that the fault is cleared and there is no EPO signal:
The rectifier restarts, and the bypass supplies power to the load. When the rectifier starts, the rectifier LED flashes. When the rectifier is in normal operation (about 15s later), the rectifier LED turns steady green. 2. Press and hold the INVERTER ON button for two seconds.
Five minutes after the overtemperature signal disappears, that is, when the overgemperature fault is eliminated, the rectifier will automatically start. After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely. When input utility is returned, if the bypass switch Q2 and output switch Q5 are closed, the UPS will start up on Bypass. There will be power at the output terminals of the UPS.
If the maintenance bypass switch Q3 is closed and the mains input is available, the UPS has output.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 5 Operating Instructions 45
When the mains power fails, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.
The UPS will automatically restart and enable output power:
z After the mains power is restored.
z If the Auto Recovery after EOD Enabling feature is enabled.
z After the Auto Recovery after EOD Delay Time expires (the default delay is 10 minutes) During the auto
recovery delay, the UPS will be charging its batteries to provide a safety margin for equipment shutdown if input power fails again.
If the Auto Recovery after EOD Enabling feature is disabled, the user may restart the system manually by pressing the FAULT CLEAR button.
The LCD menus and data display are available in two languages: Chinese, English.
To select a different language than the one being displayed:
To change the system date and time:
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

46 Chapter 6 Battery
This chapter introduces the battery, including the battery safety points, installation, maintenance, and the battery protection function, as well as the connections of the optional battery circuit breaker (BCB) box and battery temperature sensor.
The UPS battery consists of battery blocks connected in series to provide a nominal DC input voltage for the UPS inverter. The required autonomy time (the time that the battery can maintain supply to the load in the event of a mains failure) is limited by the ampere-hour size of the individual battery blocks and in some cases this could mean several strings are connected in parallel.
It must be possible to disconnect the battery from the UPS module when undertaking maintenance or service procedures. This is facilitated by means of a suitably rated circuit breaker which must be located as close as possible to the battery terminals, and the power and control cables connected to the UPS using the most direct route possible.
If multiple sets of batteries connected in parallel are used to increase battery autonomy, the extension must be fitted with a sectioning device to permit work to be performed on one set of batteries while the others remain in service.
For external battery assembly, Emerson offers an optional battery circuit breaker (BCB) box, the features of which depend on the size of the UPS. Normally, you must select a corresponding BCB box for each UPS, in order to disconnect the battery from the UPS when the UPS requires maintenance or repair. The BCB box includes a BCB control board. This box is designed to be either wall-mounted or assembled on a frame, and is connected between the UPS and the battery. Refer to 6.9 BCB Box (Optional) for more information.
Special care should be taken when working with the batteries associated with the HIPULSE U UPS. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to physically isolate the battery installation from all but appropriately qualified maintenance personnel; which is best achieved by locating the cells in a key-lockable cabinet or a purpose-designed, dedicated battery room.
The following general battery safety precautions and warnings should be observed at all times: 1. A battery can present risk of electric shock or burn from high short circuit currents. 2. When connected in a string the voltage could be 460Vdc, this voltage is potentially lethal always observe high voltage precautions. 3. Only qualified personnel should install or service batteries. 4. Eye protection should be work to prevent injury from accidental electrical arcs. 5. Remove rings, watches, necklaces, bracelets and all metal objects. 6. Only use tools with insulated handles. 7. Wear rubbers gloves and a rubber apron when handling batteries. 8. If a battery leaks electrolyte, or is otherwise physically damaged, it should be placed in a container resistant to sulphuric acid and disposed of in accordance with local regulations. 9. If electrolyte comes into contact with the skin the affected area should be washed with plenty of clean water immediately. 10. Batteries must always be disposed of according to local environmental laws.
It is common practice in UPS installations to use valve-regulated cells. The term ‘valve regulated’ is used currently in place of either ‘sealed’ or ‘maintenance free’ both of which have been used in the past.
Valve-regulated cells are not ‘sealed,’ and will vent, particularly on overcharge. The amount of gas given off is less than for a flooded cell but when considering the design of the battery installation allowances must be made for
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 6 Battery 47
adequate ventilation and heating of the cells. Boost charging must not be applied to valve regulated cells as this will cause them to overcharge and subsequently vent.
Similarly, valve-regulated cells cannot be regarded as maintenance-free as they must be kept clean and their connections checked periodically for tightness and lack of corrosion. Specific inspection instrument can also be used to check each battery cell periodically to learn about the variation in capacity.
Batteries are fully charged before delivery; however, storage and transportation times mean that, inevitably, some charge is lost by the time the battery is commissioned. All the cells forming the battery should be brought to the same state of charge and be recharged within 6 months of the factory charge.
It is especially important that the battery is fully charged before attempting a witness test of the autonomy time. This may require several days to complete; therefore any witness test concerning the batteries should take place only after the battery has been on uninterrupted float charge for at least one week.
Cell performance typically improves after a few weeks in service or after two or three discharge and recharge cycles.
Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to key considerations which must be taken into account during the installation design process and might affect the design outcome depending on localized conditions.
Battery performance depends on the ambient battery temperature. Capacity and autonomy times are quoted for a new battery operating at 20°C. Battery capacity is increased by 1% for every 1°C increase in temperature up to 25°C. If a battery is used at temperatures above 25°C, its life is reduced; consequently its capacity and UPS autonomy time will reduce more rapidly over a period of time. Operating below 20°C will reduce the battery capacity by approximately 1% to 1.5% per 1°C. For example, if a battery discharge test is attempted during the middle of winter when the ambient temperature is 5°C the battery capacity will be only 77.5% of its design value and will not satisfy its specified autonomy time.
Ambient temperature, ventilation, spacing, float voltage and ripple current all affect the battery temperature. Uneven temperature distribution through the battery string will cause the voltage distribution to be uneven which can also lead to problems — it is therefore important to maintain an even temperature across the whole battery chain.
Valve-regulated cells are very sensitive to temperature and should be operated at a temperature between 15°C and 25°C. To help sustain this operating temperature range the battery is normally float charged at 2.25V/cell.
When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS. That is, in the case of valve-regulated cells, the ambient room temperature should be kept between 15°C and 25°C, and not between 0°C and 40°C (which is the specified main equipment operating temperature range). Temperature excursions are permissible for short periods of time provided the average temperature does not exceed 25°C.
The nominal DC bus voltage, and therefore battery float voltage, is set according the module’s rated input and output voltages, and usually set to 432Vdc (380Vac), 446Vdc (400Vac) or 459V (415Vac). Given that the desired cell float voltage is 2.25V, this means that a different number of cells are required in each case (see Table 6-1).
Table 6-1 Battery population
Parameter 380V 400V 415V
Number of cells used (standard) 192 pcs 198 pcs 204 pcs
End-of-discharge voltage 320V 330V 340V
Float voltage 432V 446V 459V
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

48 Chapter 6 Battery
The battery is connected to the UPS through a BCB which is manually closed and electronically tripped through the UPS control circuitry. If the cells are rack-mounted (or located remote from the main UPS cabinet), the BCB must be mounted as near as possible to the batteries themselves, and the power and control cables connected to the UPS using the most direct route possible.
Features of the BCB include:
z Isolation from battery to achieve safety and reliability
z Automatic opening in the event of inverter lockup due to battery undervoltage to prevent battery damage caused
z Tripping by remote emergency power off (EPO) button if installed
z Operation error protection
To achieve the required autonomy time, it may be necessary to parallel battery strings. In which case, the battery circuit breaker should be placed downstream of all parallel battery strings.
Whatever the type of mounting system selected, the following conditions should be noted (see Figure 6-1):
X Layout of cells:
Whatever battery mounting system is used, the batteries should be laid out in such a manner as to make simultaneous contact with two exposed live parts having a potential greater than 150V impossible. Where this is not possible, insulated terminal shields must be installed and insulated cables must be used for connections.
Y Service platform:
The service platform (or duckboard) must be slip-proof, insulated from the floor and be at least one meter wide.
Z Connections:
All connections must be as short as possible.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
z Shortcircuit protection · by overdischarge

Chapter 6 Battery 49
A BCB is generally installed in an enclosure on the wall close to the battery installation. The connection of BCB box available for the HIPULSE U UPS is described in the following section.

Figure 6-1 Battery room design
The battery circuit breaker (BCB) box of 160/200kVA UPS adopts wall mounting, while that of the 300/400kVA UPS can adopt both wall mounting and floor mounting. The installation hole dimensions are shown in Figures 6-2 to 6-4.

Figure 6-2 Installation hole dimensions for wall mounting of BCB box of 160/200kVA UPS (unit: mm)

Figure 6-3 Installation hole dimensions for wall mounting of BCB box of 300/400kVA UPS (unit: mm)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

50 Chapter 6 Battery
4-Ф13 Knockout Figure 6-4 Installation hole dimensions for floor mounting of BCB box of 300/400kVA UPS (unit: mm)
The battery circuit breaker (BCB) box contains a BCB and a BCB control board (ULK366SC1).
The BCB box is fitted as close as possible to the battery and connected to the UPS, as illustrated in Figure 6-5.


TMP12Z
TMP12Z
TMP12Z
Figure 6-5 BCB box connection
Note: The control cables from the UPS to the BCB control board must be made using the accessory cable of the BCB, which is a shielded cable located in a separate conduit to that containing the battery power cables. The cable shield must be earthed to prevent induced noise affecting the control operation, and a separate safety earth must be connected between the UPS and BCB box.
A battery temperature sensor (model: TMP12Z) supplied separately from the BCB is connected with the UPS logic through the BCB control board. For the connection, see Figure 6-5.
With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as to be inversely proportional to the ambient temperature of the battery cabinet or battery room. This prevents the battery being over charged at high ambient temperatures.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
BCB control board

Chapter 7 “1+N” System 51
This chapter introduces the installation procedures, operating instructions of the “1+N” system, and the installation of the dual bus system, of the HIPULSE U UPS.
The system can comprise of up to 6 UPS modules of the same power rating and connected in parallel without the need for a centralized mains static bypass. Instead the bypass static switches of each UPS share the load when the system transfers to the mains bypass supply.
From a ‘power’ viewpoint, each module is internally identical to the ‘single module’ configuration. A “1+N” system requires inter-module control signals to manage the load sharing, synchronizing and bypass switching. The control signals are connected through the parallel cables, which are multi-way ribbon cables connected between the units of the system to form a ring.
When three or more modules are to be connected in parallel it is recommended that inductance should be inserted in the static bypass line. This can be installed internal to the UPS as an option.
The basic installation procedure of a parallel system comprising two or more UPS modules is the same as that of single module system. This section only introduces the installation procedures specific to the parallel system. The installation of a parallel UPS must follow the installation procedure for a single UPS module with the additional requirements detailed in this section.
Be sure that a parallel kit is present and fitted in each of the modules, and that the modules are of the same rating and with the same software and hardware release.
To achieve coordinated operation of the modules in the parallel system, it is required to configure each module separately using background configuration software. This must be done by Emerson service & support trained personnel.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

52 Chapter 7 “1+N” System
Place the UPS modules side by side and interconnect as shown in Figure 7-1.


Maintenance bypass switch Q3
Rectifier Inverter Static switch
Input switch Q1 Input mains
并机 电缆
Ext. Sw out
Battery 1 BCB 1
Maintenance bypass switch Q3
Rectifier Inverter Static switch
Q5
J5
并机 电缆
BCB 2
Ext. Sw out
Ext. Sw out
Figure 7-1 “1+N” system block diagram
Refer to the instructions supplied in 3.1.6 Protective Devices.
Refer to the instructions supplied in 3.1 Power Cabling.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 7 “1+N” System 53
Shielded and double insulated control cables available in length up to 20 meters must be must be interconnected in a ring configuration between UPS modules as shown in Figure 7-2. Specifically, connect the two parallel cables from X1-1 and X2-2 on the parallel board of the first module respectively to X1-2 and X2-1 on the parallel board of the second module, and so on.
The parallel board is mounted on the inner door of each UPS module. The ring configuration ensures high reliability of the control.

Parallel board Parallel board Parallel board Parallel board Parallel board Parallel board
Figure 7-2 Connection of “1+N” system parallel cables
Refer to the EPO input port (X2) part in 3.3.1 Monitoring Board Ports.
Refer to 3.3.2 Battery Control.
EXT-Maint (X3-1&2) on UPS parallel board M3 (leave open if no external bypass switch is used) provides external maintenance bypass interlock protection for the UPS. Short circuit means external bypass closed.
EXT-Out (X3-3&4) on UPS parallel board M3 (leave shorted if no external output switch is used) provides external output interlock protection for paralleled UPS modules. Short circuit means external output switch closed.
UPS parallel board M3 is located behind protective covers accessible aftr opening the UPS front door — removal of this barrier requires the use of a tool and is restricted to service personnel. Jumper JP1 (located next to X3) needs to be removed for X3: 3&4 to work properly.
If residual current detectors (RCDs) are used on UPS unit inputs, use a common device only on the system’s bypass mains. At the instant of electrical connection, the current may not be split instantaneously and this may cause the residual current circuit breakers (RCCBs) to trip separately. These operations must be performed one at a time, progressing to the next step only after having completed the previous step on both UPS modules.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

54 Chapter 7 “1+N” System
This procedure must be followed when turning on the UPS from a fully powered down condition, that is, where the load is not being initially supplied at all or where supplied by the maintenance bypass switch. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
Refer to 5.2 Start-Up Procedure (Into Normal Mode).
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel. Refer to 5.6 Maintenance Bypass Procedure (And UPS Shut Down).
7.3.3 Switching OFF And Isolating One UPS While The Other Remains In Service
To completely isolate the UPS, open the AC power supply circuit breaker (both circuit breakers if separate supplies are provided for the rectifier and the bypass supply) and the output circuit breaker on the power distribution switchboard.
If individual UPS output isolation circuit breaker (and its auxiliary contacts) are not installed on the power distribution switchboard, remember that voltage supplied by the others UPS which remains in service will still be present on the output terminals of the shutdown UPS.
If individual UPS output isolation circuit breaker are not installed on the power distribution switchboard, remember that voltage supplied by the others UPS which remains in service will still be present on the output terminals of the shutdown UPS. Warning: Wait five minutes for the internal d.c bus bar capacitors to discharge.
This procedure is indicated to re-integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 7 “1+N” System 55
Table 7-1 LED status
Rectifier LED Steady green
Inverter LED Steady green
Load LED Steady green
Refer to 5.7 Shutdown Procedure (Complete UPS And Load Shutdown).
As shown in Figure 7-3, the dual bus system consists of two independent UPS configurations each consisting of one or more UPS modules. Dual bus systems are high availability configurations suitable for loads with multiple input terminals. For single input loads an optional static transfer switch (STS) may be added.
The objective of the dual bus system is to keep the output of two independent UPS systems (or parallel systems) in synchronization using optional load bus synchronization (LBS) cable. One system is designated as the master; the other is designated as the slave. The operating modes covered comprise master and or slave operating inverter or bypass mode.
In installation, place the UPS modules side by side and interconnect as described in the following sections.

Input rectifier Input rectifier
Input rectifier Input rectifier
Figure 7-3 Typical dual bus system (using STS and LBS cable)
Refer to 3.1.6 Protective Devices.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

56 Chapter 7 “1+N” System
The wiring of power cables is similar to that of single module system. Refer to 3.1 Power Cabling.
The bypass and the main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point.
If the dual bus system consists of two single units, use the optional 9-core LBS cable to connect between the LBS interfaces (X4 socket on parallel board) of the two single units, and use another optional LBS cable to connect between any two 25-core interfaces (X2-1 or X2-2) of the two single units, as shown in Figure 7-4.
Although the dedicated 25-core LBS cable looks like the parallel cable, it is absolutely not the parallel cable, and cannot be replaced by it. Otherwise, UPS system chaos may occur.
04116319 20m DB9-DB9 04115338 10m DB9-DB9 04115339 15m DB9-DB9
X2-1 X2-2
X1-2 X1-1
X1-2 X1-1
UPS unit 1 UPS unit 2
Figure 7-4 Control cable connection of dual bus system consisting of two single units
Control cable connection of dual bus system consisting of a single unit and a parallel system
Figure 7-5 shows the control cable connection of the dual bus system consisting of a single unit and a parallel system composed of two or more single units. Use the optional 9-core LBS cable to connect from the LBS interface (X4 socket on parallel board) of the single unit to the LBS interface of any single unit in the parallel system; and use another optional LBS cable to connect from any 25-core interface (X2-1 or X2-2) of the single unit to the LBS interface of any single unit except for the aforesaid one in the parallel system, note that this LBS cable has a 9-core end and a 25-core end, respectively connecting the X4 interface of the parallel system and the 25-core interface of the single unit.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 7 “1+N” System 57

04116319 20m DB9-DB9 04115338 10m DB9-DB9 04115339 15m DB9-DB9
Figure 7-5 Control cable connection of dual bus system consisting of a single unit and a parallel system
For the dual bus system consisting of two parallel systems respectively composed of two or more single units, you must form a ring connection between the two parallel systems with the optional 9-core LBS cables. The connection interfaces are the X4 sockets on the parallel boards, as shown in Figure 7-6.
04115338 10m DB9-DB9 04116319 20m DB9-DB9
Parallel board Parallel board Parallel board Parallel board

Figure 7-6 Control cable connection of dual bus system consisting of two parallel systems
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
04115339 15m DB9-DB9

58 Chapter 8 Specifications
This chapter provides the specifications of the HIPULSE U UPS.
Table 8-1 Conformity and standard
Description Year Normative references Safety requirements 1999 IEC60950-1, IEC62040-1-1, UL1778
EMC 2005 IEC/EN62040-2 Design and test methods 1999 IEC62040-3
Table 8-2 Environmental requirements

Power rating (kVA) Item Unit 160 200 300 400 Operating Temperature °C 0~40 Maximal temperature for 8hr day °C 40°C (derate power by 1.5% per °C between 40°C and 50°C Mean Temperature for 24hr °C Maximally 35 Relative humidity - ≤95% at 20°C Altitude of operation m ≤1000m asl (derate power by 1% per 100m between 1000m and 2000m)
Storage temperature and transport temperature °C -25 to 70
Table 8-3 Mechanical characteristics

400 (12-pulse) Height mm 1900 Width mm 1250 1640 1250 1640 1640 2280 2280 2280 Depth mm 875 Weight kg 1200 1725 1350 2000 1600 2200 2100 2750 Ventilation - By internal intake fans
Airflow m3/h 2590 2750 2750 2910 5350 5350 6150 6150 Cable entry - Bottom or either side (top optional)
Table 8-4 Electrical characteristics (input rectifier)

400 (12-pulse) Rated mains voltage Vac 380, 400, or 415
Supply - Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally, from 290Vac to 498Vac)
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 8 Specifications 59
Power rating (kVA) Item Unit 160 (6-pulse)
400 (12-pulse) Rated input power 2 kVA 197 191 245 236 365 354 488 469 Rated input current2 A 298 289 371 358 551 535 739 708 Maximal input Power3 kVA 246 239 306 295 420 407 609 584 Maximal input current3 A 373 362 464 447 634 616 931 885
Duration of progressive power walk-in4
Note: 1. With mains at -15% and suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2. IEC62040-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3. IEC62040-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4. Set by dedicated background software
Table 8-5 Electrical characteristics (DC intermediate circuit)

Power rating (kVA) Item Unit 160 200 300 400
Recommended number of lead-acid cells 1,2 pcs
Maximum voltage on manual charge 2.40 V/el.1 Vdc
471 (380Vac) 485 (400Vac) 500 (415Vac) Max boost charge duration 3 min 480~1800 Freshening charge duration3 h 1~36
Boost-float threshold current 3 A 0.001C~0.025C Ripple voltage superimposed 4 % ≤1 Note: 1. (According to rated voltage). 2. Factory set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3. Set by software. 4. Battery disconnected, RMS percentage value referred to DC voltage
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

60 Chapter 8 Specifications
Table 8-6 Electrical characteristics (inverter output)
Power rating (kVA) Item Unit 160 200 300 400 Rated mains voltage1 Vac 380, 400, or 415
Supply - Three phase with neutral Frequency2 Hz 50 or 60
Rated Power at cos = 0.9 kVA 160 200 300 400 Rated Power at cos = 1 kW 144 180 270 360
60, 1.10 10, 1.25 1, 1.5 Maximal non linear load allowed4 - 100%Pn
Three-phase transient overload3 Min,
Voltage stability, steady State test3 % ±1 Voltage stability, transient test 5 % ±5 Maximum rate of charge of frequency6 Hz/s 0.1 Note: 1. Factory set 380V 400 or 415 voltages with software setting. 2. Factory set at 50Hz 60 Hz with software setting. 3. IEC62040-3 (5.3.2). 4. IEC62040-3 (ANNEX E). 5. IEC62040-3 (5.3.1), also for 0~100~0%, load transient, restore time 20 ms to 1%. 6. Factory set at 0.1Hz/s; up to 1Hz/s with software setting
Table 8-7 Electrical characteristics (bypass input mains)
Power rating (kVA) Item Unit 160 200 300 400 Rated mains voltage1 Vac 380, 400, or 415
Supply - Three phase with neutral
Rated current 380Vac 400Vac 415Vac
243 304 456 607 231 289 433 577
222 278 416 554 Bypass voltage tolerance2 % Default upper limit: 15%; default lower limit: -20% Delay time to recognise bypass voltage returned to window s 2
Inverter output voltage window % ±5 Frequency3 Hz 50 or 60
Input frequency tolerance 4 % ±5 Maximum frequency slew rate Hz/s 1
Current rating of neutral cable - 1.3In
Protection, bypass line - The bypass line should be protected using an external device in the input distribution system. This device should be sized to discriminate with the load protection
10 14.3 20 12.6 50 11.0 100 10.0 200 9.0 500 8.0 1000 7.1 2000 6.6 5000 5.7 Note: 1. Factory set 380V. 400 or 415 voltages with software setting. 2. Other values in -20%~15% with software setting. 3. Factory set at 50Hz 60 Hz with software setting. 4. Other values -5%~5%with software setting
Transient overload ms I/In
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
I/In

Chapter 8 Specifications 61
Table 8-8 Electrical characteristics (system performance)

No load losses kW 2.75 3.30 3.50 4.15 3.90 4.65 4.70 6.51 Full load losses (100%) kW 9.63 11.89 11.12 13.91 19.33 21.8 28.2 31.6
Table 8-9 Electrical characteristics (ECO mode)

400 (12-pulse) Full load losses (100%) kW 2.97 3.52 3.55 4.20 5.23 5.91 7.10 8.96
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

62 Chapter 9 Service & Maintenance
Regular service and maintenance are required during the long term operation of the UPS system (including the associated battery). The battery maintenance is expounded in chapter 6. This chapter deals with the life characteristics of the key components of the UPS, and provides recommendation for the regular check and service of the key components. Proper service and maintenance of the UPS system can extend the UPS life and reduce the risk of system malfunction.
The daily patrol check of the UPS system can be conducted by trained personnel, while the check and replacement of the UPS components should be done by authorized professionals.
During the UPS operation, some UPS components’ lives are shorter than the UPS life due to wear and tear in working. To ensure the safe power supply of the UPS system, regular check and replacement of these components are required. This section introduces the key components of the HIPULSE U series UPS and their reference working lives. For systems working in different conditions (environment, load, and so on), you may ask professionals to assess the components and provide advices whether to replace the components by referring to the information provided in this section.
The design life of the magnetic components is 20 years. The key factors affecting the life of the magnetic components are the interwinding isolation system and the temperature increase in operation. The HIPULSE U series UPS adopts H-level isolation system and can withstand up to 220°C working temperature. Normally, the UPS works in forced air cooling condition.
The power semiconductor devices include SCR (silicon-controlled rectifier) and IGBT (insulated gate bipolar transistor). In normal UPS working condition, there is no rated life of the power semiconductor devices. The SCR and IGBT failures are always caused by other problems, as they do not have the problem of life expiration. However, in system service and maintenance, you should check on an annual basis the appearances of the power semiconductor devices for erosion and damage. If you spot any risk of failure , replace the device.
The life of the electrolytic capacitors depend on the DC bus voltage and ambient temperature of the UPS.
To ensure safe and stable UPS operation, it is recommended to check the operation status of the electrolytic capacitors on an annual basis. The electrolytic capacitors must be replaced before their life expires, advisably, within 5 to 6 years of operation.
It is recommended to replace the AC capacitors within 5 to 6 years of continuous operation, and to check the AC capacitors on a half year basis. Replace the AC capacitor if spotting any deformation.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Chapter 9 Service & Maintenance 63
The key components listed in Table 9-1 are used in the UPS. To prevent system malfunction caused by failure of key components due to wear and tear during working, you are recommended to check them regularly, and replace them within their life expectancy.
Table 9-1 Lifves and recommended replacement time of key components
Key components Life expectancy Recommended replacement time Recommended check period
AC capacitor ≥7 years (~62,000hr) 5~6 years 6 months
Electrolytic capacitor ≥7 years (~62,000hr) 5~6 years 1 year
Fan ≥7 years (~62,000hr) 5~6 years 1 year Air filter 1~3 years 1~2 years 3 months Valve-regulated lead-acid battery ( 5 years of life) 5 years 3~4 years 6 months
Valve-regulated lead-acid battery ( 10 years of life) 10 years 6~8 years 6 months
When replacing the fuse on the high-voltage interface board or the fuse in the fuse box, use a fuse of the same model, avoid being misled by the parameter screenprint on the fuse box.
380V systems can use both 380V/4A fuse and 500V/4A fuse, while 400V/415V systems can use 500V/4A fuse only.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

64 Appendix 1 Transportation Restraints Removing Procedures
1. 160kVA&200kVA UPS Transportation Restraints Removing
Procedures
A A 放大 处 图
A
Figure 1 Removing the installation hole cover
M10 bolt M12 bolt
固定件
出 器 输 变压
A A amplified view A
Figure 2 Removing the output transformer transportation restraints
3. There is a transportation restraint respectively in the front and at the back at the bottom of the output transformer. The one at the back is shown in Figure 2. Remove the fixing bolts of the one at the back, including two M10 bolts in the middle and two M12 bolts at sides; then, remove the fixing bolts, including two M10 bolts in the middle and two M12 bolts at sides, of the transportation restraint in the front through the installation hole revealed in step 1.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Appendix 1 Transportation Restraints Removing Procedures 65

Figure 3 Removing the transformer transportation restraints
There are two transportation restraints respectively in the front and at the back, totally four, at the bottom of the phase-shifting transformer. Remove the two M10 bots at both sides and one M12 bolt in the middle of each transportation restraint, as shown in Figure 3. Remove the four transportation restraints, and then reinstall the four M12 bolts in their original positions.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

66 Appendix 1 Transportation Restraints Removing Procedures
The removing procedures of the output transformer transportation restraints of 300kVA UPS with 12-pulse rectifier are the same as those of 300kVA UPS with 6-pulse rectifier. The removing procedures of the transportation restraints of the phase-shifting transformer are as follows:


移相 器 变压 移相 器 变压 Phase-shifting transformer
Open the front door Open the back door Remove the back panel Figure 5 Opening the front door and removing the back panel
打 前 板 开 门 打 后 板 开 门

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Appendix 1 Transportation Restraints Removing Procedures 67

Installation hole covers Figure 7 Removing the installation hole covers

Figure 8 Removing the two transportation restraints at the back
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

68 Appendix 1 Transportation Restraints Removing Procedures

Figure 9 Removing the two transportation restraints in the front
The removing procedures of the output transformer transportation restraints of 400kVA UPS with 12-pulse rectifier are the same as those of 400kVA UPS with 6-pulse rectifier. The removing procedures of the transportation restraints of the phase-shifting transformer are as follows:

Remove the tw o bolts fixing the transportation restraint
Figure 10 Removing the two transportation restraints in the front
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Appendix 1 Transportation Restraints Removing Procedures 69

Remove the tw o bolts fixing the transportation restraint
Figure 11 Removing the two transportation restraints at the back
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual