To prevent electrical shock and/or equipment dam- age, disconnect electric power to system at main fuse or circuit breaker box prior to installation or service.
The control has a user selection for changing the setpoint to be either the Cut In or the Cut Out setting. The user must be careful to understand how this effects the “range” in which the control will operate when the differential value is entered. If entered values are incorrect, the control could operate outside the user’s intended settings due to set-up error. See section titled "Operation".
Where failure of this control may result in personal injury and/or property damage, additional alarms or limit controls must be installed.
This control is a temperature control and is not to be used as a temperature limit control.


TEMPERATURE UNITS INDICATOR (°F or °C)
HEATING MODE INDICATOR ( )
BINARY INPUT INDICATOR LIT WHEN UNIT IS IN “SETBACK” MODE REFER TO PAGE 6
STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED (ON). (SEE NOTE)
MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 & 5
Switch SW1 must be set for system mode as shown:
SW1
TEMPERATURE “DOWN” BUTTON
NOTE: Green Status Indicator LED and display backlight operation It may be observed from time to time that the green status indicator LED and display back-light will briefly turn off during a call for heating or cooling. During this time, the control is performing a self-check lasting up to 15 seconds. This is normal operation of the control and the load power will be maintained
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW REAR VIEW

1.58”
4.19”
5.59”
.85”

Fig. 3 Line Voltage Application
(Power Stealing)
Switch Settings Switch SW2 must be set for applications as shown:
Alarm Output For optional connection to customer alarm equipment

(See "Special Note" in "Operation Section" for Alarm)
Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to connect a neutral line to power the control. The control receives power from the unit it is control- ling. Power Stealing saves time and money by often eliminat- ing the labor to run a neutral wire to the control for power. See compatibility chart below for certain limitations.
Power Stealing Compatibility Chart

Alarm Output For optional connection to customer alarm equipment

(Non-Power Stealing)
Alarm Output For optional connection to customer alarm equipment
display will be blank because power has been interrupted to the control. All menu settings and setpoint will be restored when power is returned.

Binary Input (Gold Plated Contacts)
24 VAC TH - Thermostat Hot TR - Thermostat Return NC contact operates opposite
of load contact * NTC – Negative Temperature Coefficient PTC – Positive Temperature Coefficient
PTC* Temperature Sensor · NTC* Temperature Sensor

USER MENU OPERATION SETTINGS: The control has user Menu settings that will determine how the control operates. The unit is shipped with factory de- fault settings. The user must change any of the settings as required for the application. To reset all settings to factory defaults, press and hold all 3 buttons simultaneously ( , , and buttons) for approximately 5 seconds.
Each press of results in forward movement to the next Menu item. If you need to change an item “passed”, you must repeatedly press , return to the operating mode, then press and hold for 5 seconds to re-enter the Menu mode. Then repeatedly, momentarily press until the desired Menu item is again displayed.
To store any changes made to any Menu items, the Menu must be exited by pressing when the last item is displayed. If no buttons are pressed for ten minutes while in the menu, the control will return to operating mode and any changes that were made will be lost.
To view Menu items, press and hold for 5 seconds. The unit will display the first Menu item on the left side of the display. The right side of the display indicates the Menu item settings. To change the setting, momentarily press the or key.
The following table shows the menu items, default settings and optional settings.
A momentary press of the key advances the display to the next Menu item, and continues, till the last menu item is displayed. Pressing the key one more time with the last menu item, (aL) displayed returns the control to the operating mode.

This control is a temperature control and is not to be used as a temperature limit control.
If control is in Cool mode, and Set Point is selected as the Cut Out: Temperature Operating = Setpoint + Differential Range Temperature (plus)
To prevent scald injury, do not use this control to heat water for bathing, washing, hot tub or similar applications.
Example:
The factory default setpoint for this control is 45°F (7°C) for Cool and 120°F (49°C) for Heat. Setpoint temperature can be adjusted using the or keys. A power loss does not lose the settings. All menu item selections and setpoint set- ting are stored in a permanent memory.
45° SW1 = Cool Set Point (SP) = Cut Out Differential = 5 Setpoint temperature = 40°
40° Setpoint (Cut Out)
The user determines the temperature operating range. To determine the temperature range, the user must select the Set Point (SP) as the Cut Out or Cut In temperature, Dif- ferential (dFF) and enter a set point temperature. Cut out is when the load is turned off and cut in is when the load is turned on.
HEAT To use as a Heating control, SW1 must be set to Heat. The flame ( ) icon will display.
If control is in Heat mode, and Set Point is selected as the Cut Out: Temperature Operating = Setpoint – Differential Range Temperature (minus)
COOL/REFRIGERATION To use as a Cooling control, SW1 must be set to Cool. The snowflake ( ) icon will display.
Example:
SW1 = Heat Set Point (SP) = Cut Out Differential = 5 Setpoint temperature = 100°
100° Setpoint (Cut Out)
If control is in Cool mode, and Set Point is selected as the Cut In: Temperature Operating = Setpoint – Differential Range Temperature (minus)
If control is in Heat mode, and Set Point is selected as the Cut In: Temperature Operating = Setpoint + Differential Range Temperature (plus)
Example:
40° Setpoint (Cut In)
SW1 = Cool Set Point (SP) = Cut In Differential = 5 Setpoint temperature = 40°
Example:
105° SW1 = Heat Set Point (SP) = Cut In Differential = 5 Setpoint temperature = 100°
100° Setpoint (Cut In)

Lock Panel (LP) The keypad can be locked to prevent unwanted tampering with the control settings. In the User Menu, change the menu item LP selection to On. When the menu is exited and set- tings are stored, the or , and keys will be disabled from normal use. To unlock the keypad, press and hold for 5 seconds. The display will change to show LP On. Momentarily press
Temperature out of range – If the temperature is more than 5° from the setpoint, continuously for the length of time set in AL, the alarm relay output will close. The delay should be set to allow for conditions that will cause the temperature to vary, such as defrost cycle, opening door for stock removal or replacement or Set Back changes. When setting the AL time, consideration should be given to these events to prevent a false alarm.
or to change to Off and then momentarily press . The control will return to normal operation and the keypad will be unlocked.
If the control set back feature is used to change the setpoint, the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm.
Binary Input (bIn) and Set Back (Sb) Binary Input is an option to allow the setpoint temperature to set back to conserve energy or for other reasons as determined by the user. Set Back determines the number of degrees the setpoint temperature will be changed.
Power Loss – If the temperature control experiences an input power failure, the control will close the alarm relay before total power of the control is lost. The delay time is not used in this event, and the alarm relay will close within seconds of a power failure. In addition, the load relay contact change state per the Sensor Operation Failure (SOF) setting.
An external switch or N.O. relay can be connected to the BIN and GND terminals of the control. With bIn set to On, when the switch is closed, the control will change the setpoint tem- perature by the number of degrees set in Sb. In Heat mode, setpoint temperature will change lower or cooler. In Cool mode, setpoint temperature will change higher or warmer.
When power returns, the alarm contacts will open. The load relay will remain in the SOF position the length of time set in Anti Short-Cycle Delay (ASd) after power resumption. The display will blink the flame or snowflake icon for this time to indicate the load is “locked” out. This is to help protect the user’s equipment from damage by short cycle switching.
During the time that the switch is closed, bIn will appear in the lower left corner of the display. If an alarm is connected be sure that the alarm delay time is set long enough to allow for the temperature change to avoid a “false” alarm.
Sensor Operation Failure (SOF) – If in operation, the sen- sor wiring should become open or shorted, the temperature control will begin blinking SOF with SH for shorted or SO for sensor open. However, the control will wait approximately 1 minute before closing the alarm output relay - indicating sensor operation failure. If during the 1 minute, the sensor “resumes” normal operation, the time is reset and the control returns to normal display. The load relay will operate as se- lected in sensor operation failure (SOF).
SPECIAL
Using the Alarm Output and power stealing in combination – When using power stealing mode and the alarm output, it is important for the installer to review the wiring circuit of the installation to insure no device is present that could interrupt electrical power to the temperature control. Such a device could be a defrost timer, as one example, that may be used in some refrigeration applications.
Multiple Sensors The 16E09 is normally operated with one sensor. If an aver- age temperature of an area is required, 4 sensors may be used and wired in the method shown below. If 4 sensors are used, they must all be of the same model.
If a device is in the system wiring that can periodically disrupt power to the load and the temperature control, the power stealing mode of the control cannot be used. A neutral wire must be connected to the control and select the non power stealing mode for the control. This keeps power to the control during power interruptions to the load and avoids a “false” alarm output.
This control has an alarm relay that will provide an output to alert of a malfunction. The alarm relay output must be con- nected to an external light, audible alarm or other device as needed by the user. If AL is set to 0, the alarm relay will not provide any alarm output. If AL is set to a value greater than 0, the alarm relay output provides indication of three error conditions: Temperature Out of Range, Power Loss and Sen- sor Operation Failure. Although AL must be set to a value greater than 0 for any alarm output to be provided, the value selected is the time delay, in minutes, before a Temperature Out of Range alarm is set. The alarm time delay does not apply to Power Loss or Sensor Operation Failure.

Load Output Relay: Ratings (Maximum): 120VAC 208VAC 240VAC Full Load Amps NC & Load 16 A 9.2 A 8 A Locked Rotor Amps NC & Load 96 A 55.2 A 48 A Non-Inductive Amps NC & Load 16 A 16 A 16 A Horsepower NC & Load 1 hp 1 hp 1 hp
Operating Ambient Ratings (Control Enclosure): Operating Temperature: -29°F to 140°F (-34° to 60°C)
Storage Shipping Ambient Ratings: Storage Temperature: -40°F to 185°F (-40° to 85°C) Operating Humidity: 0 to 95% Relative Humidity, Non-Condensing Maximum Dew Point: 85°F (29°C)
Temperature Set-Point Range: Set-Point Range: -40° to 220°F (-40° to 104°C) Differential Range: 1 to 30 (Degrees F or Degrees C)
Temperature Probes:
NTC The control is shipped with an NTC (Negative Temperature Coefficient) sensor, with a cable length of 7½ feet. Cable length can be extended up to 400 feet by appropriately splic- ing and adding additional cable (22 AWG or larger diameter)
as needed – polarity is not important. When extending cable length, verify temperature accuracy and use the menu Ambi- ent Temperature Offset (OFS) settings to compensate accord- ingly if required.

PTC The control may be connected to an existing PTC (Positive Temperature Coefficient) sensor. Make sure the PTC sensor meets the specifications tables below. Failure to do so will result in temperature inaccuracies. The PTC input may not be
extended more than 50 feet, and the wire gauge should be 18 AWG wire or larger diameter. Be sure the probe attached matches the resistance vs. temperature tables or temperature inaccuracies may occur.


LCD display, display back-light and green status indica- tor LED turn off in Power Stealing mode: This “off” condition is normal for the control in power stealing mode when wired with a defrost timer or other device that interrupts electrical power to the control.
Temperature differential is wider than set: - Temperature change of customer's unit is fast, and the Anti Short Cycle delay setting may be overriding the “call” to activate the heat or cool. Solution – lower Anti Short Cycle delay.
No control settings will be lost during this time, however, the installer must ensure that applications requiring power steal- ing are suitable for the control to be off during these periods.
Installation and Power Up: False alarm sounds, temperature has not yet reached set- point setting. CUSTOMER must disable alarm (AL = 0), until setpoint temperature is reached, then set alarm delay time. Customer Changes Setpoint Temperature: False alarm sounds. CUSTOMER must disable alarm (AL = 0), while unit is adjusting to new temperature. CUS- TOMER must then set the alarm delay time when tempera- ture is reached.
Please note: if the built-in alarm feature of the control is to be used on systems that may interrupt power to the control, the control must be wired with a neutral wire and set in non- power stealing mode. This will keep the control continuously powered unless there is an actual power interruption or loss. In this case, the control will be able to signal an alarm for system power loss.
Bin/Set Back False alarm sounds. CUSTOMER must set the delay time with sufficient delay time to assure the Set Back temperature is reached before the alarm delay time has expired.
Display indicates “CaL” on power up. Control was not calibrated. Return control for replacement.
Unit does not turn on, (LCD does not display anything): - Check that wiring is correct. - Make sure power is turned on. - Check that wiring is under terminal blocks correctly. - Make sure both switches inside control are set to proper position. - If in Power Steal mode, - Make sure the load draws a minimum of 2.5 amp AC. If not, wire per the Non-Power Stealing diagram. - Make sure nothing "breaks/opens the load line, such as a defrost timer or any other device, with the alarm feature enabled. This would cause a false alarm. If the alarm function is enabled, wire per the Non-Power Stealing diagram.
Alarm Sounds, Reason Unknown: CUSTOMER should make sure the Alarm (AL) delay time is great enough to cover other conditions when the unit tem- perature may not be able to stay within 5 degrees. - Loading or unloading of stock and the doors are open. (Add sufficient delay time to the alarm delay). - Power is lost to the control if the line is broken/open by a defrost timer or other device. (Wire control per the Non Power Stealing line voltage schematic and connect/add a neutral line connection).
White-Rodgers is a division of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
www. emerson.com
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.