INSTALLATION

To prevent electrical shock and/or equipment dam- age, disconnect electric power to system at main fuse or circuit breaker box prior to installation or service.

The control has a user selection for changing the setpoint to be either the Cut In or the Cut Out setting. The user must be careful to understand how this effects the “range” in which the control will operate when the differential value is entered. If entered values are incorrect, the control could operate outside the user’s intended settings due to set-up error. See section titled "Operation".

Where failure of this control may result in personal injury and/or property damage, additional alarms or limit controls must be installed.

This control is a temperature control and is not to be used as a temperature limit control.

Fig. 1 Control Front View and Description

Emerson Temperature Controller (16E09-101) — Fig. 1 Control Front View and Description diagram (page 2)
Fig. 1 · Fig. 1 Control Front View and Description
Emerson Temperature Controller (16E09-101) — Fig. 1 Control Front View and Description diagram (page 2)
Fig. 2 · Fig. 1 Control Front View and Description

TEMPERATURE UNITS INDICATOR (°F or °C)

SETPOINT TEMPERATURE

HEATING MODE INDICATOR ( )

BINARY INPUT INDICATOR LIT WHEN UNIT IS IN “SETBACK” MODE REFER TO PAGE 6

COOLING MODE INDICATOR ( )

STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED (ON). (SEE NOTE)

MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 & 5

Switch SW1 must be set for system mode as shown:

TEMPERATURE “UP” BUTTON

SW1

TEMPERATURE “DOWN” BUTTON

NOTE: Green Status Indicator LED and display backlight operation It may be observed from time to time that the green status indicator LED and display back-light will briefly turn off during a call for heating or cooling. During this time, the control is performing a self-check lasting up to 15 seconds. This is normal operation of the control and the load power will be maintained

Fig. 2 Control Dimensions and Mounting Information

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW REAR VIEW

Emerson Temperature Controller (16E09-101) — Fig. 2 Control Dimensions and Mounting Information diagram (page 2)
Fig. 3 · Fig. 2 Control Dimensions and Mounting Information

1.58”

4.19”

5.59”

.85”

BOTTOM VIEW

Show 4 more labels / short text on this page
Circuit Board · Inside Cover · Refrigeration Cool · Heating Heat
Page 3 of the Emerson Temperature Controller (16E09-101) user manual — Fig. 5 24 VAC Applications
Page 3 · click to enlarge
Page 3

WIRING

Wiring Instruction Notes

Fig. 3 Line Voltage Application

(Power Stealing)

Switch Settings Switch SW2 must be set for applications as shown:

Alarm Output For optional connection to customer alarm equipment

SW2 Line Voltage (Power Stealing) Line Voltage (Non Power Stealing)PS Non PS 24 VAC (Non Power Stealing)Non PS
PTC* Temperature ALARM Sensor PTC GND BIN NTC Bina (Gol NTC* Con Temperature PS Sensor SW2 NON PS 24 VAC 24 VA TH TR NC NEUT LINE LOAD Voltage Input TH - TR - 120 VAC 208/240 VAC Hot L1 Neutral L2 Voltage Input 120 VAC208/240 VAC HotL1 NeutralL2
Emerson Temperature Controller (16E09-101) — Wiring Instruction Notes diagram (page 3)
Fig. 4 · Wiring Instruction Notes

(See "Special Note" in "Operation Section" for Alarm)

Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to connect a neutral line to power the control. The control receives power from the unit it is control- ling. Power Stealing saves time and money by often eliminat- ing the labor to run a neutral wire to the control for power. See compatibility chart below for certain limitations.

Power Stealing Compatibility Chart

Fig. 4 Line Voltage Application

ApplicationPower StealingNon-Power Stealing Line Voltage, replacing existing control that has a common wireYesYes Line Voltage, with load greater than 2.5 amps, without Defrost timer or other power interruption circuit, with or without alarmYesYes Line Voltage, with load greater than 2.5 amps, with Defrost timer of other power interruption circuit, no alarmSee Note 1Yes Line Voltage with load greater than 2.5 amps, with Defrost timer or other power Interruption circuit, with alarmNoYes Line Voltage with load less than 2.5 ampsNoYes 24 VAC ApplicationNoYes
Emerson Temperature Controller (16E09-101) — Fig. 4 Line Voltage Application diagram (page 3)
Fig. 5 · Fig. 4 Line Voltage Application

(Non-Power Stealing)

Alarm Output For optional connection to customer alarm equipment

PTC* Temperature ALARM Sensor PTC GND BIN NTC Bina (Go NTC* Con Temperature PS Sensor SW2 NON PS 24 VAC 24 V NEUT LINE LOAD TH TR TH NC Voltage Input TR 120 VAC 208/240 VAC Hot L1 Neutral L2 Voltage Input 120 VAC208/240 VAC HotL1 NeutralL2
Emerson Temperature Controller (16E09-101) — (Non-Power Stealing) diagram (page 3)
Fig. 6 · (Non-Power Stealing)

Fig. 5 24 VAC Applications

(Non-Power Stealing)

Alarm Output For optional connection to customer alarm equipment

display will be blank because power has been interrupted to the control. All menu settings and setpoint will be restored when power is returned.

Emerson Temperature Controller (16E09-101) — Fig. 5 24 VAC Applications diagram (page 3)
Fig. 7 · Fig. 5 24 VAC Applications

Binary Input (Gold Plated Contacts)

24 VAC TH - Thermostat Hot TR - Thermostat Return NC contact operates opposite

of load contact * NTC – Negative Temperature Coefficient PTC – Positive Temperature Coefficient

PTC* Temperature Sensor · NTC* Temperature Sensor

Page 4 of the Emerson Temperature Controller (16E09-101) user manual — USER MENU
Page 4 · click to enlarge
Page 4

USER MENU

USER MENU OPERATION SETTINGS: The control has user Menu settings that will determine how the control operates. The unit is shipped with factory de- fault settings. The user must change any of the settings as required for the application. To reset all settings to factory defaults, press and hold all 3 buttons simultaneously ( , , and buttons) for approximately 5 seconds.

Each press of results in forward movement to the next Menu item. If you need to change an item “passed”, you must repeatedly press , return to the operating mode, then press and hold for 5 seconds to re-enter the Menu mode. Then repeatedly, momentarily press until the desired Menu item is again displayed.

To store any changes made to any Menu items, the Menu must be exited by pressing when the last item is displayed. If no buttons are pressed for ten minutes while in the menu, the control will return to operating mode and any changes that were made will be lost.

To view Menu items, press and hold for 5 seconds. The unit will display the first Menu item on the left side of the display. The right side of the display indicates the Menu item settings. To change the setting, momentarily press the or key.

The following table shows the menu items, default settings and optional settings.

A momentary press of the key advances the display to the next Menu item, and continues, till the last menu item is displayed. Pressing the key one more time with the last menu item, (aL) displayed returns the control to the operating mode.

Menu ItemDescriptionFactory DefaultOptions Press or to selectComments CFTemperature ScaleFC or FSelects temperature display in Fahrenheit or Celsius dFFDifferential51 to 30Selects the range between Cut In and Cut Out. SPSet Point Mode Cool HeatCl COCO or CI CI or COSelects how the set point temperature will operate the load terminal. CI indicates the setpoint temperature will be the Cut In temperature. CO indicates the temperature will be the Cut Out temperature. See Operation section. SOFSensor Operation Failure Cool Heat1 00 or 1 NoneCooling - Selects the operation of the Control Load relay in the event of a sensor failure in Cool mode. 1 (default) will cause the load contacts of the relay to close and remain closed if the sensor either opens or shorts. 0 causes the load contacts of the relay to open and remain open. Heating has no optional selection. Sensor failure in Heating will result in the relay contacts opening. dLDisplay LightOffOn or OffSelects the LCD display light Off or On. With this selected Off, the display light will illuminate any time a keypad button is pressed to provide better viewing in low lighting conditions, and go off after 10 seconds. If On is selected, the display light will be On continuously. ASdAnti Short-Cycle DelayCool 1 Heat 00 to 12Selects the minimum time (in minutes) that the load contacts will remain open after a cycle before closing again. This will prevent the compressor or other load from being damaged by cycling too soon. A blinking Snowflake or Flame icon indicates that the control has a demand to energize the load, but is waiting for the delay time to elapse. A setting of 0 indicates no time and the feature is disabled. SW1 must be set to the proper position before checking this setting. LPLock Front Panel KeypadOffOn or OffWhen selected Off, the keypad can be used as normal. When selected On, prevents unauthorized access to the control settings by locking out all keys. To unlock the control when it is locked, press and hold the Menu key for 5 seconds. OFSAmbient Temperature Offset0-4, -3, -2, -1, 0, 1, 2, 3, 4This control is calibrated at the factory, but the “sensed" temperature may read different because of mounting/installation, or other factors. This item allows the displayed temperature to be shifted the number of degrees set to compensate for this difference
Page 5 of the Emerson Temperature Controller (16E09-101) user manual — OPERATION
Page 5 · click to enlarge
Page 5

USER MENU

Menu ItemDescriptionFactory DefaultOptions Press or to selectComments bInBinary InputOffOn or OffThe default setting of Off will have no affect on the operation of the thermostat. When set to On, it allows an external binary input (switch or relay) to start a temperature set back. See Set Back (Sb). SbSet Back00 to 50Selects the number of degrees the thermostat will change the setpoint temperature when the external binary input signal is received. 0 will cause no temperature change to occur. See Binary Input (bin). ALAlarm00 to 99Selects the time delay (in minutes) before a Temperature Out of Range alarm output is sent. A setting of 0 disables the alarm relay.

OPERATION

This control is a temperature control and is not to be used as a temperature limit control.

If control is in Cool mode, and Set Point is selected as the Cut Out: Temperature Operating = Setpoint + Differential Range Temperature (plus)

To prevent scald injury, do not use this control to heat water for bathing, washing, hot tub or similar applications.

Example:

The factory default setpoint for this control is 45°F (7°C) for Cool and 120°F (49°C) for Heat. Setpoint temperature can be adjusted using the or keys. A power loss does not lose the settings. All menu item selections and setpoint set- ting are stored in a permanent memory.

45° SW1 = Cool Set Point (SP) = Cut Out Differential = 5 Setpoint temperature = 40°

40° Setpoint (Cut Out)

The user determines the temperature operating range. To determine the temperature range, the user must select the Set Point (SP) as the Cut Out or Cut In temperature, Dif- ferential (dFF) and enter a set point temperature. Cut out is when the load is turned off and cut in is when the load is turned on.

HEAT To use as a Heating control, SW1 must be set to Heat. The flame ( ) icon will display.

If control is in Heat mode, and Set Point is selected as the Cut Out: Temperature Operating = Setpoint – Differential Range Temperature (minus)

COOL/REFRIGERATION To use as a Cooling control, SW1 must be set to Cool. The snowflake ( ) icon will display.

Example:

SW1 = Heat Set Point (SP) = Cut Out Differential = 5 Setpoint temperature = 100°

100° Setpoint (Cut Out)

If control is in Cool mode, and Set Point is selected as the Cut In: Temperature Operating = Setpoint – Differential Range Temperature (minus)

If control is in Heat mode, and Set Point is selected as the Cut In: Temperature Operating = Setpoint + Differential Range Temperature (plus)

Example:

40° Setpoint (Cut In)

SW1 = Cool Set Point (SP) = Cut In Differential = 5 Setpoint temperature = 40°

Example:

105° SW1 = Heat Set Point (SP) = Cut In Differential = 5 Setpoint temperature = 100°

100° Setpoint (Cut In)

Show 10 more labels / short text on this page
Temperature · Range · Temperature · Range · 95° · Temperature · Range · 35° · emperature · an e
Page 6 of the Emerson Temperature Controller (16E09-101) user manual — NOTE
Page 6 · click to enlarge
Page 6

OPERATION

Lock Panel (LP) The keypad can be locked to prevent unwanted tampering with the control settings. In the User Menu, change the menu item LP selection to On. When the menu is exited and set- tings are stored, the or , and keys will be disabled from normal use. To unlock the keypad, press and hold for 5 seconds. The display will change to show LP On. Momentarily press

Temperature out of range – If the temperature is more than 5° from the setpoint, continuously for the length of time set in AL, the alarm relay output will close. The delay should be set to allow for conditions that will cause the temperature to vary, such as defrost cycle, opening door for stock removal or replacement or Set Back changes. When setting the AL time, consideration should be given to these events to prevent a false alarm.

or to change to Off and then momentarily press . The control will return to normal operation and the keypad will be unlocked.

If the control set back feature is used to change the setpoint, the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm.

Binary Input (bIn) and Set Back (Sb) Binary Input is an option to allow the setpoint temperature to set back to conserve energy or for other reasons as determined by the user. Set Back determines the number of degrees the setpoint temperature will be changed.

Power Loss – If the temperature control experiences an input power failure, the control will close the alarm relay before total power of the control is lost. The delay time is not used in this event, and the alarm relay will close within seconds of a power failure. In addition, the load relay contact change state per the Sensor Operation Failure (SOF) setting.

An external switch or N.O. relay can be connected to the BIN and GND terminals of the control. With bIn set to On, when the switch is closed, the control will change the setpoint tem- perature by the number of degrees set in Sb. In Heat mode, setpoint temperature will change lower or cooler. In Cool mode, setpoint temperature will change higher or warmer.

When power returns, the alarm contacts will open. The load relay will remain in the SOF position the length of time set in Anti Short-Cycle Delay (ASd) after power resumption. The display will blink the flame or snowflake icon for this time to indicate the load is “locked” out. This is to help protect the user’s equipment from damage by short cycle switching.

During the time that the switch is closed, bIn will appear in the lower left corner of the display. If an alarm is connected be sure that the alarm delay time is set long enough to allow for the temperature change to avoid a “false” alarm.

Sensor Operation Failure (SOF) – If in operation, the sen- sor wiring should become open or shorted, the temperature control will begin blinking SOF with SH for shorted or SO for sensor open. However, the control will wait approximately 1 minute before closing the alarm output relay - indicating sensor operation failure. If during the 1 minute, the sensor “resumes” normal operation, the time is reset and the control returns to normal display. The load relay will operate as se- lected in sensor operation failure (SOF).

Alarm (AL)

SPECIAL

Using the Alarm Output and power stealing in combination – When using power stealing mode and the alarm output, it is important for the installer to review the wiring circuit of the installation to insure no device is present that could interrupt electrical power to the temperature control. Such a device could be a defrost timer, as one example, that may be used in some refrigeration applications.

NOTE

Multiple Sensors The 16E09 is normally operated with one sensor. If an aver- age temperature of an area is required, 4 sensors may be used and wired in the method shown below. If 4 sensors are used, they must all be of the same model.

If a device is in the system wiring that can periodically disrupt power to the load and the temperature control, the power stealing mode of the control cannot be used. A neutral wire must be connected to the control and select the non power stealing mode for the control. This keeps power to the control during power interruptions to the load and avoids a “false” alarm output.

This control has an alarm relay that will provide an output to alert of a malfunction. The alarm relay output must be con- nected to an external light, audible alarm or other device as needed by the user. If AL is set to 0, the alarm relay will not provide any alarm output. If AL is set to a value greater than 0, the alarm relay output provides indication of three error conditions: Temperature Out of Range, Power Loss and Sen- sor Operation Failure. Although AL must be set to a value greater than 0 for any alarm output to be provided, the value selected is the time delay, in minutes, before a Temperature Out of Range alarm is set. The alarm time delay does not apply to Power Loss or Sensor Operation Failure.

Show 4 more labels / short text on this page
Sensor 1 · Sensor 3 · Sensor 2 · Sensor 4
Page 7 of the Emerson Temperature Controller (16E09-101) user manual — PTC TEMPERATURE VERSUS RESISTANCE TABLES
Page 7 · click to enlarge
Page 7

SPECIFICATIONS

Load Output Relay: Ratings (Maximum): 120VAC 208VAC 240VAC Full Load Amps NC & Load 16 A 9.2 A 8 A Locked Rotor Amps NC & Load 96 A 55.2 A 48 A Non-Inductive Amps NC & Load 16 A 16 A 16 A Horsepower NC & Load 1 hp 1 hp 1 hp

Operating Ambient Ratings (Control Enclosure): Operating Temperature: -29°F to 140°F (-34° to 60°C)

Storage Shipping Ambient Ratings: Storage Temperature: -40°F to 185°F (-40° to 85°C) Operating Humidity: 0 to 95% Relative Humidity, Non-Condensing Maximum Dew Point: 85°F (29°C)

  • 24 VAC NC & Load 100 VA, 30 VAC Max (Class 2) Pilot Duty NC & Load 125 VA, 24 to 240 VAC
  • Minimum Load Rating: 1 Amp @ 24 VAC
  • Note: the above minimum current/voltage is specified to assure proper operation.

Temperature Set-Point Range: Set-Point Range: -40° to 220°F (-40° to 104°C) Differential Range: 1 to 30 (Degrees F or Degrees C)

CaseNEMA 1 Enclosure, Flammability Rating: UL94VO
Alarm Relay Ratings (Maximum)N.O. contact: 1 Amp, 5 to 24 V, AC or DC

Temperature Probes:

NTC The control is shipped with an NTC (Negative Temperature Coefficient) sensor, with a cable length of 7½ feet. Cable length can be extended up to 400 feet by appropriately splic- ing and adding additional cable (22 AWG or larger diameter)

as needed – polarity is not important. When extending cable length, verify temperature accuracy and use the menu Ambi- ent Temperature Offset (OFS) settings to compensate accord- ingly if required.

NTC TEMPERATURE VERSUS RESISTANCE TABLES

Emerson Temperature Controller (16E09-101) — NTC TEMPERATURE VERSUS RESISTANCE TABLES diagram (page 7)
Fig. 8
Temperature (°F) (°C)Resistance (KΩ) -40 -40328.29 -31 -35236.83 -22 -30172.90 -13 -25127.65 -4 -2095.23 5 -1571.74 14 -1054.56 23 -541.85 32 032.37 41 525.23
Temperature (°F) (°C)Resistance (KΩ) 50 1019.82 59 1515.67 68 2012.48 77 2510.00 86 308.07 95 356.55 104 405.34 113 454.38 122 503.61 131 552.99
Temperature (°F) (°C)Resistance (KΩ) 140 602.49 149 652.09 158 701.76 167 751.48 176 801.26 185 851.07 194 900.92 203 950.79 212 1000.68 221 1050.59

PTC The control may be connected to an existing PTC (Positive Temperature Coefficient) sensor. Make sure the PTC sensor meets the specifications tables below. Failure to do so will result in temperature inaccuracies. The PTC input may not be

extended more than 50 feet, and the wire gauge should be 18 AWG wire or larger diameter. Be sure the probe attached matches the resistance vs. temperature tables or temperature inaccuracies may occur.

PTC TEMPERATURE VERSUS RESISTANCE TABLES

Emerson Temperature Controller (16E09-101) — PTC TEMPERATURE VERSUS RESISTANCE TABLES diagram (page 7)
Fig. 9
Temperature (°F) (°C)Resistance (KΩ) -40 -40613 -31 -35640 -22 -30668 -13 -25697 -4 -20727 5 -15758 14 -10789 23 -5822 32 0855 41 5889
Temperature (°F) (°C)Resistance (KΩ) 50 10924 59 15960 68 20997 77 251035 86 301074 95 351113 104 401153 113 451194 122 501236 131 551279
Temperature (°F) (°C)Resistance (KΩ) 140 601323 149 651368 158 701413 167 751459 176 801506 185 851554 194 901602 203 951652 212 1001702 221 1051753
Page 8 of the Emerson Temperature Controller (16E09-101) user manual — www.white-rodgers.com
Page 8 · click to enlarge
Page 8

TROUBLESHOOTING

LCD display, display back-light and green status indica- tor LED turn off in Power Stealing mode: This “off” condition is normal for the control in power stealing mode when wired with a defrost timer or other device that interrupts electrical power to the control.

Temperature differential is wider than set: - Temperature change of customer's unit is fast, and the Anti Short Cycle delay setting may be overriding the “call” to activate the heat or cool. Solution – lower Anti Short Cycle delay.

No control settings will be lost during this time, however, the installer must ensure that applications requiring power steal- ing are suitable for the control to be off during these periods.

Installation and Power Up: False alarm sounds, temperature has not yet reached set- point setting. CUSTOMER must disable alarm (AL = 0), until setpoint temperature is reached, then set alarm delay time. Customer Changes Setpoint Temperature: False alarm sounds. CUSTOMER must disable alarm (AL = 0), while unit is adjusting to new temperature. CUS- TOMER must then set the alarm delay time when tempera- ture is reached.

Please note: if the built-in alarm feature of the control is to be used on systems that may interrupt power to the control, the control must be wired with a neutral wire and set in non- power stealing mode. This will keep the control continuously powered unless there is an actual power interruption or loss. In this case, the control will be able to signal an alarm for system power loss.

Bin/Set Back False alarm sounds. CUSTOMER must set the delay time with sufficient delay time to assure the Set Back temperature is reached before the alarm delay time has expired.

Display indicates “CaL” on power up. Control was not calibrated. Return control for replacement.

Unit does not turn on, (LCD does not display anything): - Check that wiring is correct. - Make sure power is turned on. - Check that wiring is under terminal blocks correctly. - Make sure both switches inside control are set to proper position. - If in Power Steal mode, - Make sure the load draws a minimum of 2.5 amp AC. If not, wire per the Non-Power Stealing diagram. - Make sure nothing "breaks/opens the load line, such as a defrost timer or any other device, with the alarm feature enabled. This would cause a false alarm. If the alarm function is enabled, wire per the Non-Power Stealing diagram.

Alarm Sounds, Reason Unknown: CUSTOMER should make sure the Alarm (AL) delay time is great enough to cover other conditions when the unit tem- perature may not be able to stay within 5 degrees. - Loading or unloading of stock and the doors are open. (Add sufficient delay time to the alarm delay). - Power is lost to the control if the line is broken/open by a defrost timer or other device. (Wire control per the Non Power Stealing line voltage schematic and connect/add a neutral line connection).

tech support help line: 1-888-725-9797

White-Rodgers is a division of Emerson Electric Co.

The Emerson logo is a trademark and service mark of Emerson Electric Co.

www.white-rodgers.com

www. emerson.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson Temperature Controller (16E09-101)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Temperature Controller (16E09-101)

Be the first to ask — other owners or our team will answer.

Original document

Emerson Temperature Controller (16E09-101) manual PDF

16 pages·2.4 MB·Refrigerator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…