Application For two position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft or jackshaft 3/8” to 1.05” in diameter by means of its universal clamp. A crank arm and mounting brackets are available if the actuator cannot be direct coupled to the jackshaft or damper shaft.
Square footage of damper operated will depend on make and model of damper. Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S applications.
Operation The FSAF series actuators provide true spring return operation for reliable fail-safe application and positive close-off on UL555S dampers. The spring return system provides constant torque to the damper with, and without, power applied to the actuator.
The FSAF series provides 95° of rotation and is provided with a graduated position indicator showing 0 to 95°. The FSAF has a manual positioning mechanism which allows the setting of any damper position within its 95° of rotation.
The actuator is shipped in the zero fail-safe position to provide automatic compression against damper gaskets for tight shut-off. When power is applied, the manual mechanism is released and the actuator drives toward the open position where it stops rotating.
The manual override can also be released physically by the use of a crank supplied with the actuator.

SAFETY NOTE Screw a conduit fi tting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable fl exible conduit. Properly terminate the conduit in a suitable junction box.
FSAF24-S US, FSAF120-S US Auxiliary Switch 2xSPST 7A resistive, 2.5A inductive at 120V or 250V, UL Approved, double-insulated, one switch at 10°, one adjustable from 30° to 90°
![Page 2 of the 321 Studios FSAF24 user manual — On/Off, Spring Return, Meets 250°F [121°C] for Half Hour, 75 Seconds](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/page-2.webp?w=400)
![321 Studios FSAF24 — On/Off, Spring Return, Meets 250°F [121°C] for Half Hour, 75 Seconds diagram (page 2)](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/fig-2-1.webp)
2 CAUTION Equipment Damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.
4 No ground connection required. Double insulated.
5 For end position indication, interlock control, fan startup, etc., the FSAF24- S US and FSAF120-S US incorporates two built-in auxiliary switches: 2 x SPST, 7A resistive, 2.5 inductive @120/250 VAC, UL Approved, one switch is fi xed at 10, one is adjustable from 30 to 90.
Meets UL requirements without the need of an electrical ground connection. Meets cULus or UL and CSA Standard requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! G During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo- nents could result in death or serious injury.
![321 Studios FSAF24 — On/Off, Spring Return, Meets 250°F [121°C] for Half Hour, 75 Seconds diagram (page 2)](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/fig-2-2.webp)
Large combination fi re and smoke dampers are to be operated by Belimo FSAF series actuators. Manufacturer shall provide 5 year warranty.
Actuators shall draw no more than 11VA at 120V or 24V.
Where auxiliary switches are required for signaling, starting fans, or position indica- tion, -S model actuators, damper blade, or proximity switches shall be provided.
Smaller dampers shall employ Belimo FSLF or FSNF actuators per damper manufac- turer recommendations.
![Page 3 of the 321 Studios FSAF24 user manual — On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/page-3.webp?w=400)
Torque min. 133 in-lb, for control of air dampers
Application For two position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft or jackshaft 3/8” to 1.05” in diameter by means of its universal clamp. A crank arm and mounting brackets are available if the actuator cannot be direct coupled to the jackshaft or damper shaft.
Square footage of damper operated will depend on make and model of damper. Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S applications.
Operation The FSAF series actuators provide true spring return operation for reliable fail-safe application and positive close-off on UL555S dampers. The spring return system provides constant torque to the damper with, and without, power applied to the actuator.
The FSAF series provides 95° of rotation and is provided with a graduated position indicator showing 0 to 95°. The FSAF has a manual positioning mechanism which allows the setting of any damper position within its 95° of rotation.
The actuator is shipped in the zero fail-safe position to provide automatic compression against damper gaskets for tight shut-off. When power is applied, the manual mechanism is released and the actuator drives toward the open position where it stops rotating.
The manual override can also be released physically by the use of a crank supplied with the actuator.
![321 Studios FSAF24 — On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds diagram (page 3)](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/fig-3-1.webp)
SAFETY NOTE Screw a conduit fi tting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable fl exible conduit. Properly terminate the conduit in a suitable junction box.
FSAF230-S US Auxiliary Switch 2xSPST 7A resistive, 2.5A inductive at 120V or 250V, UL Approved, double-insulated, one switch at 30° to 90°
![Page 4 of the 321 Studios FSAF24 user manual — On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/page-4.webp?w=400)
![321 Studios FSAF24 — On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds diagram (page 4)](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/fig-4-1.webp)
2 CAUTION Equipment Damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.
4 No ground connection required. Double insulated.
5 For end position indication, interlock control, fan startup, etc., the FSAF230-S US incorporates two built-in auxiliary switches: 2 x SPST, 7A resistive, 2.5 inductive @120/250 VAC, UL Approved, one switch is fi xed at 10°, one is adjustable from 30° to 90°.
Meets UL requirements without the need of an electrical ground connection. Meets cULus or UL and CSA Standard requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! G During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo- nents could result in death or serious injury.
![321 Studios FSAF24 — On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds diagram (page 4)](/cdn/reader/fa/fa45dddad7f94182e69b3787e80615d6b0858d3b104c283588bfc20507390d5a/images/fig-4-2.webp)
Large combination fi re and smoke dampers are to be operated by Belimo FSAF series actuators. Manufacturer shall provide 5 year warranty.
Actuators shall draw no more than 12VA at 230V or 10 VA at 24V.
Where auxiliary switches are required for signaling, starting fans, or position indica- tion, -S model actuators, damper blade, or proximity switches shall be provided.
Smaller dampers shall employ Belimo FSLF or FSNF actuators per damper manufac- turer recommendations.

FSAF24-SR(-S) US Proportional, Spring Return, 24 V, 2 to 10 VDC or 4 to 20 mA control signal Operation at 250°F for limited time per UL555S testing
Application For proportional modulation of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft or jackshaft up to 1.05” in diameter by means of its universal clamp. A crank arm and mounting brackets are available if the actuator cannot be direct coupled to the jackshaft or damper shaft.
The actuator operates in response to a 2 to 10 VDC, or with the addition of a 500 Ω resistor, a 4 to 20 mA control input from an electronic controller or positioner. A 2 to 10 VDC feedback signal is provided for position indication or master-slave applications. See Application Bulletin for details.
Operation The FSAF series actuators provide spring return operation. There is no reversing switch on the FSAF24-SR. It is direct acting only. A reverse acting signal is required if it must spring open while 2V signal drives it closed. The torque is asymmetrical giving 180 in-lb drive and 133 in-lb spring.
Technical Data FSAF24-SR(-S) US Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Power consumption running 7 W, 11 VA
The FSAF resets after being driven or springing closed to the 0 position. There is a possible hysteresis of 1° every 1000 changes in signal. This can cause a position shift. It is recommended that power or signal be reset once a week.
A manual override winder and locking mechanism is provided. If the manual winder is used when the actuator is powered, the actuator will release and drive closed to reset the 0 degree position.
holding 3 W, 5 VA Transformer sizing 15 VA (class 2 power source) Electrical connection
The actuator may not be mechanically parallelled or “piggybacked.” Each damper section should be controlled by a separate actuator.
FSAF24-SR 3 ft, 18 GA, 4 color coded leads (24V) 1/2” conduit connector FSAF24-SR-S 3 ft, 18 GA appliance cable 1/2” conduit connector Overload protection electronic throughout 0 to 95° rotation Operating range 2 to 10 VDC, 4 to 20mA Input impedance 100 kΩ (0.1 mA), 500 Ω Feedback output U 2 to 10 VDC (max. 0.5 mA) for 95° Angle of rotation mechanically limited to 95° Torque 133 in-lb [15 Nm] constant Direction of rotation spring reversible with cw/ccw mounting
The wire 5 feedback can be used to parallel up to five additional actuators. If less than 2.1 V or greater than 9.9V is given wire 3, actuator drives all the way to the respective end stop.
The FSAF uses a DC motor which is controlled by a microchip The actuator may be stalled anywhere during its rotation without damage. If power is removed, the damper will spring closed. Interlocks must be provided as necessary for life safety functions and to shut down fan if required.

SAFETY NOTE Screw a conduit fi tting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable fl exible conduit. Properly terminate the conduit in a suitable junction box.
The control direction switch is not present. Direct acting only. 2 VDC=Fail-safe position. Position indication visual indicator, 0° to 95° (0° spring return position) Manual override 3mm hex crank (shipped w/actuator) Running time motor
normal duty -22°F to 122°F [-30°C to 50°C]
safety duty 3 on/off cycles after 30 minutes at ambient
temperature of 250°F [121°C] Storage temperature -40°F to 176°F [-40°C to 80°C] Housing NEMA type 2 / IP40 Housing material zinc coated metal Agency listings† cULus to UL873 and CSA C22.2 No. 24-93 Noise level (max) running 45 db (A) Servicing maintenance free Quality standard ISO 9001, 5 year Belimo warranty Weight 6.0 lbs (2.7 kg.)
FSAF24-SR-S US Auxiliary switch 2 x SPDT 7A resistive, 2.5A inductive at 120/250VAC. UL Approved, double-insulated, one set at =+10°, one adjustable 30° to 90°

FSAF24-SR(-S) US Proportional, Spring Return, 24 V, 2 to 10 VDC or 4 to 20 mA control signal
Operation at 250°F for limited time per UL555S testing
4 No ground connection required. Double insulated.
5 Only connect common to neg. (–) leg of control circuits.
6 For end position indication, interlock control, fan startup, etc., FSAF24-SR-S US incorporates two built-in auxiliary switches: 2 x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL Approved, one switch is fi xed at 10°, one is adjustable 30° to 90°.
Meets UL requirements without the need of an electrical ground connection. The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
WARNING Live Electrical Components! G During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo- nents could result in death or serious injury.

Proportional smoke, and combination fi re and smoke dampers, shall be controlled by Belimo FSAF24-SR actuators. The control signal shall provide proportional damper control in response to a 2 to 10 VDC or, with the addition of a 500 Ω resistor, a 4 to 20 mA control input from an electronic controller or positioner. The actuators must be designed so that they may be used for either clockwise or counter clockwise fail-safe operation. Actuator shall open damper in
The number one “equal or better” requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements since UL has stated that they do not regulate replacements.

2 CAUTION Equipment Damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.

FSAF24-BAL(-S) US Spring Return, 24 V, 3-Position, 100% Open Override Operation at 250°F for limited time per UL555S testing

Application For 3-position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s tests. In the absence of other information, use 10 in-lb of torque per square foot of area for opposed blade and 14 in-lb for parallel blade fire and smoke dampers at 1000 fpm air velocity.
The FSAF24-BAL is specifically designed to balance the air flow in ducts and simultaneously provide control of fire and smoke dampers. 0V = spring closed. 24V on wire 2, not 3 = drive to the potentiometer position (balanced flow). 24V on wire 3, regardless of the status of wire 2 = drive full open (smoke control extraction or pressurization). See Application Bulletin for details.
Operation For 3-position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s tests. In the absence of other information, use 10 in-lb of torque per square foot of area for opposed blade and 14 in-lb for parallel blade fire and smoke dampers at 1000 fpm air velocity.
The FSAF24-BAL is specifically designed to balance the air flow in ducts and simultaneously provide control of fire and smoke dampers. 0V = spring closed. 24V on wire 2, not 3 = drive to the potentiometer position (balanced flow). 24V on wire 3, regardless of the status of wire 2 = drive full open (smoke control extraction or pressurization).
Technical Data FSAF24-BAL(-S) US Power supply 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Power consumption running AC 9.5 VA 6.5W
DC 6W holding AC 5 VA 3W

SAFETY NOTE The actuator contains no components which the user can replace or repair.
DC 3W Transformer sizing 10 VA (class 2 power source 24V only) Electrical connection 3 ft, 18 GA, 1/2” conduit connector Overload protection electronic throughout 0 to 95° rotation Control signal 24 VAC/DC 3-position Angle of rotation 20° to 95°, pot adjustable Torque 133 in-lb [15 Nm] Direction of rotation spring reversible with cw/ccw mounting Position indication visual indicator, 0° to 95° (0° spring return position) Manual override 3mm hex crank (shipped w/actuator) Running time motor
FSAF24-BAL-S US Auxiliary switch 2 x SPDT 7A resistive, 2.5A inductive at 120/250VAC. UL listed, double-insulated, one switch is set at 10°, one is adjustable 30° to 90°

FSAF24-BAL(-S) US Spring Return, 24 V, 3-Position, 100% Open Override Operation at 250°F for limited time per UL555S testing

2 CAUTION Equipment Damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.
4 Only connect Hot, Wire 2 to Wire 3 override control
For end position, interlock control, fan start-up, etc., FSAF24-BAL-S incorporates two built-in auxiliary switches: 2 x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL listed, one switch is fi xed at 10°, one adjustable 30° to 90°
6 For end position indication, interlock control, fan startup, etc., FSAF24-SR-S US incorporates two built-in auxiliary switches: 2 x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL Approved, one switch is fi xed at 10°, one is adjustable 30° to 90°.
6 Meets UL requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! G During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo- nents could result in death or serious injury.
Where indicated on drawings, combination fi re and smoke and balancing dampers shall be controlled by Belimo FSAF24-BAL or equal actuators. The actuators must be designed so that they may be used for either clockwise or counter clockwise failsafe operation. Actuator shall open damper in

Actuator shall have an adjustable Maximum Opening Potentiometer which shall be used by the TAB contractor to adjust fl ow to that portion of the system fed by the damper.
4 OVERRIDE CONTROL See Wiring Diagrams on following pages for typical methods.
The actuator shall spring closed if either the smoke detector or alarm system removes power from it. Actuator shall spring closed if the primary temperature thermodisc opens due to high ambient of >165°F or as otherwise indicted on drawings.
The actuator shall drive full open if either the smoke control system 100% open override or Fire Fighters Smoke Control Station override is activated. Damper shall spring closed again if the thermodisc of a combination fi re and smoke damper opens due to high temperature (typically 250°F).
7 Double insulated