Instruction/ maintenance manual of the product Powerware 9130 Eaton
Go to page of 120
Eaton 9130 UPS 700–3000 VA User's Guide ®.
Class A EMC Statements (Low Voltage Models over 1500 VA) FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Class B EMC Statements (Low Voltage Models up to 1500 VA and High Voltage Models up to 3000 VA) FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: IEC 61000-3-12 S EU Directives: 7.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Warnings 3 .
TABLE OF CONTENTS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com ii Retrieving the Event Log 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com iii 9 Warranty 107 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two-Year Limited Warranty (US and Canada) 107 .
TABLE OF CONTENTS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com iv.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 1 Chapter 1 Introduction The Eaton ® 9130 uninterruptible power system (UPS), part of the Powerware ® series, .
INTRODUCTION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 2 Figure 1 shows the Eaton 9130 rackmount UPS, and Figure 2 shows the optional rackmount EBM. Figure 1. The Eaton 9130 Rackmount UPS Figure 2. The Eaton 9130 Rackmount EBM Figure 3 shows the Eaton 9130 tower UPS and optional EBM.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 3 Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 4 C A U T I O N S Batteries can present a risk of electrical shock or burn from high short-circuit current.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 5 A D V A R S E L S Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj kortslutningsstrøm. Overhold gældende forsigtighedsregler.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 6 S De uitgangsoverstroombeveiliging en de stroomonderbreker moeten door derden worden geleverd.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 7 S Pienennä tulipalon vaaraa kytkemällä vain piiriin, jossa on 100 ampeerin maksimihaarapiirin ylivirtasuoja kansallisen sähkölainsäädännön (ANSI/NFPA 70) mukaan.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 8 S Afin de réduire les risques d'incendie, ne raccordez qu'à un circuit muni d&apos.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 9 A C H T U N G S Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene Energiequelle (Batterien). Der USV-Ausgang kann Spannung führen, auch wenn das USV nicht an eine Wechselstromquelle angeschlossen ist.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 10 P E R I C O L O La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 11 Viktig Sikkerhetsinformasion VIKTIGE SIKKERHETSINSTRUKSJONER GJEM DISSE INSTRUKSJONENE Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og vedlikehold av UPS-enheten og batteriene.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 12 Regulamentos de Segurança INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES Este manual contém instruções importantes que devem ser seguidas durante a instalação e manutenção do no-break e das baterias.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 13 Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòè ÂÀÆÍÛÅ ÓÊÀÇÀ.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 14 Î Ñ Ò Î Ð Î Æ Í Î S Âûñîêîå íàïðÿæåíèå, âûçâàííîå êîðî.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 15 S La protección contra sobrecorriente de salida y el conmutador de desconexión debe suministrarse por parte de terceros.
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 16 S För att reducera faran för brand får anslutning endast utföras till en krets som skyddas med överbelastningsskydd på maximalt 100 ampere i enlighet med NEC, ANSI/NFPA 70.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 17 Chapter 3 Installation This section explains: S Equipment inspection S Unpacking the cabinet S Checking the a.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 18 Unpacking the Cabinet C A U T I O N S Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and on the cabinet.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 19 Rackmount Installation The Eaton 9130 rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic rackmount configuration with square and round mounting holes.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 20 Rackmount Setup C A U T I O N S The cabinet is heavy (see page 78).
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 21 2. Select the proper holes in the rack for positioning the UPS in the rack (see Figure 5). The rails occupy four positions on the front and rear of the rack.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 22 NOTE There are two sets of four mounting holes on each side of the UPS: a forward position and a middle position. Choose the position that meets your configuration needs.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 23 13. Optional. Insert a rear stop bracket through the inside of each rail behind the UPS. Rotate each bracket and slide the bracket until it fits tightly against the UPS's rear panel.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 24 NOTE A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. NOTE Leave ribbon cable connected. Figure 9.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 25 Up to 1500 VA Models 2000–3000 VA Models Figure 10. Connecting the UPS Internal Batteries 3. If you are installing EBMs, see the following section, “Connecting the EBM(s),” before continuing with the UPS installation.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 26 Connecting the EBM(s) To install the optional EBM(s) for a UPS: 1. On the bottom of the UPS right front cover, remove the EBM cable knockout (see Figure 11).
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 27 Bottom EBM Cable Knockout (underneath cover) Top EBM Cable Knockout EBM Cover Hook Figure 12. Removing the EBM Front Cover 3. For the bottom (or only) EBM, remove the EBM cable knockout on the top of the EBM front cover.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 28 C A U T I O N A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 29 7. Replace the EBM front cover. To replace the cover, verify that the EBM cables are routed thro.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 30 Tower Wiring Installation This section explains: S Installing the UPS, including connecting t.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 31 C A U T I O N A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 32 6. If you are installing power management software, connect your computer to one of the communication ports or optional connectivity card (see page 53).
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 33 1000–1500 VA Models 2000–3000 VA Models Remove cable retention clip. Plug in EBM cable. Rotate clip. Reinstall cable retention clip. Figure 16.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 34 UPS Initial Startup To start up the UPS: NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 35 10. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads are powered. The UPS should be in Normal mode.
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 36.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 37 Chapter 4 Operation This chapter contains information on how to use the Eaton 9130, including front panel ope.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 38 Table 1 shows the indicator status and description. Table 1. Indicator Descriptions Indicator Status Description Green On The UPS is operating normally.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 39 Table 2 shows the basic menu structure. Table 2. Menu Map for Display Functions Main Menu Submenu D.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 40 User Settings The following table displays the options that can be changed by the user.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 41 Table 3. User Settings (continued) Default Setting Available Settings Description Frequency Converter [Enabled] [Disabled] If Enabled, the UPS operates as a frequency converter, with bypass operation and all bypass-related alarms disabled.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 42 Table 3. User Settings (continued) Default Setting Available Settings Description Site Wiring Fault Alarm [Enabled] [Disabled] An active site wiring fault alarm prevents startup or, if operating, forces operation to Battery mode and disables bypass.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 43 Table 3. User Settings (continued) Default Setting Available Settings Description Predictive Mainte.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 44 If battery capacity becomes low while in Battery mode, the indicator flashes slowly and the audible alarm beeps once every second. If the “Battery Low” alarm is set, the indicator also illuminates solid.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 45 Standby Mode When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. The indicator is off, indicating that power is not available to your equipment.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 46 5. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See “Troubleshooting” on page 101.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 47 UPS Shutdown To shut down the UPS: 1. Press the button on the front panel for three seconds. The UPS starts to beep and shows a status of “UPS off pending.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 48 Setting Power Strategy On the High Efficiency setting, the UPS operates normally on Bypass, transfers to inverter in less than 10 ms when utility fails, and transfers back to Bypass in 1 minute after utility returns.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 49 You can prohibit Bypass (”Never”) or always allow Bypass with no specification checking (”Always”). For “Always on UPS Fault,” transfer to Bypass is always made on UPS fault; otherwise, operation proceeds as with the default setting.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 50 To set the restart and shutdown delay times for each load segment: 1. Press any button to activate the menu options, then select SETTINGS, USER SETTINGS and AUTOMATIC START DELAY.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 51 Configuring Battery Settings Set the UPS for the number of EBMs installed, whether to run automatic battery tests, and automatic restart configuration.
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 52 Running Automatic Battery Tests Automatic battery tests run approximately every 30 days, unless disabled. During the test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds under the existing load.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 53 Chapter 5 Communication This section describes the: S Communication ports (RS-232 and USB) S Connectivity car.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 54 Installing Communication Options and Control Terminals To install the communication options and control terminals: 1. Install the appropriate connectivity card and/or necessary cable(s) and connect the cables to the appropriate location.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 55 When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 56 Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 57 NOTE For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 58 Relay Output Contacts The UPS incorporates three programmable relay outputs with potential free contacts for remote alarm indications: a standard relay port and two outputs in the RS-232 communication port.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 59 Programmable Signal Inputs The UPS incorporates four programmable signal inputs: one RS-232 input, two connectivity card inputs, and one REPO terminal input.
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 60 Modem Operation To configure the UPS and modem handling features for remote monitoring and service, contact your service representative.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 61 Chapter 6 UPS Maintenance This section explains how to: S Care for the UPS and batteries S Replace the UPS in.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 62 Storing the UPS and Batteries If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility power.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 63 S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be extremely toxic. S Determine if the battery is inadvertently grounded.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 64 NOTE Leave ribbon cable connected. Figure 23. Removing the UPS Right Front Cover 2. Disconnect the internal battery connector (see Figure 24). 3.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 65 5. Carefully pull the handle on the battery tray and slide the battery package slowly out onto a flat, stable surface; use two hands to support the battery package.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 66 Replacing Tower UPS Internal Batteries C A U T I O N The UPS internal batteries are heavy (see page 78). Use caution when handling the heavy batteries.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 67 2. Remove and retain the two screws holding the internal battery connector. Disconnect the internal battery connector. See Figure 26. Battery Cover Plate Internal Battery Connector Battery Tray Handle Figure 26.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 68 6. Replace the battery cover plate into the slots at left, threading the battery connector through the access slot. Reinstall the retained screws.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 69 Replacing Rackmount EBMs C A U T I O N The EBM is heavy (see page 78). Lifting the cabinet into the rack requires a minimum of two people. To replace the EBMs: 1.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 70 2. Unplug the EBM cable from the UPS. If additional EBMs are installed, unplug the EBM cable from the battery connector on each EBM. 3. If not already installed, install the supplied mounting brackets on the new EBM(s).
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 71 10. Replace the EBM front cover. To replace the cover, verify that the EBM cables are routed .
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 72 5. For each cable retention clip removed, rotate the clip and install it under each EBM cable connection using the retained screws.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 73 Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS.
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 74.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 75 Chapter 7 Specifications Model Specifications This section provides the following specifications: S Communication options S Model lists S Weights and dimensions S Electrical input and output S Environmental and safety S Battery Table 8.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 76 Table 10. UPS Model List (Rackmount Models) Model Power Level Rear Panel Diagram PW9130L700R-X.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 77 Table 11. UPS Model List (Tower Models) Model Power Level Rear Panel Diagram PW9130L700T-XL 70.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 78 Table 12. Weights and Dimensions (Rackmount Models) Model (Rackmount UPS) Dimensions (H W D) Weight PW9130L700R-XL2U PW9130L1000R-XL2U PW9130G1000R-XL2U PW9130i1000R-XL2U PW9130G1000R-XL2UEU PW9130G1000R-XL2UAU 86.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 79 Table 13. Weights and Dimensions (Tower Models) Model (Tower UPS) Dimensions (H W D) Weight PW9130L700T-XL PW9130i700T-XL PW9130G700T-XLAU 231* 160 354 mm (9.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 80 Table 15. Electrical Input (Rackmount Models) Model Default Input (Voltage/Current) Selectable Input Voltages Voltage Range at 100% Load PW9130L700R-XL2U 120V / 5.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 81 Table 16. Electrical Input (Tower Models) Model Default Input (Voltage/Current) Selectable Input Voltages Voltage Range at 100% Load PW9130L700T-XL 120V / 5.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 82 Table 17. Electrical Input Connections (Rackmount Models) Model Input Connection Input Cable P.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 83 Table 18. Electrical Input Connections (Tower Models) Model Input Connection Input Cable PW913.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 84 Table 19. Electrical Output (All Models) All Models Normal Mode Battery Mode Voltage Regulation ±2% Nominal output voltage ±3% Efficiency >95% (High Efficiency mode), >88% >79.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 85 Table 20. Electrical Output Connections (Rackmount Models) Model Output Connections Output Cab.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 86 Table 21. Electrical Output Connections (Tower Models) Model Output Connections Output Cables .
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 87 Table 22. Environmental and Safety (All Models) 120 Vac Models 208/230/240 Vac Models Surge Suppression ANSI C62.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 88 Table 23. Battery Runtimes (in Minutes) at 100% Load (Rack Models) Model Internal Batteries + .
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 89 Table 24. Battery Runtimes (in Minutes) at 100% Load (Tower Models) Model Internal Batteries +.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 90 Table 25. Battery Internal Batteries EBMs Rackmount Configuration 700–1000 VA models: 36 Vdc.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 91 Rear Panels This section shows each model's rear panel. Receptacles in Load Segment 1 are shaded. Table 10 on page 76 lists the rackmount models.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 92 Figure 31. Model PW9130G1000R-XL2UAU Figure 32.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 93 Figure 35. Model PW9130L2000R-XL2U Figure 36.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 94 Figure 39. Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Figure 40. Models PW9130G2500R-XL2U, PW9130G3000R-XL2U Figure 41. Models PW9130G2500R-XL2UEU, PW9130i3000R-XL2U, PW9130G3000R-XL2UEU Figure 42.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 95 Figure 43. Model PW9130L700T-XL Figure 44. Model PW9130L1000T-XL Figure 45.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 96 Figure 47. Model PW9130L3000T-XL Figure 48. Model PW9130G1000T-XL Figure 49.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 97 Figure 51. Model PW9130i700T-XL Figure 52. Model PW9130G1000T-XLEU and PW9130i1000T-XL Figure 53.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 98 Figure 55. Models PW9130G3000T-XLEU and PW9130i3000T-XL Figure 56.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 99 Figure 59. Model PW9130G2000T-XLAU Figure 60.
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 100.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 101 Chapter 8 Troubleshooting The Eaton 9130 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected.
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 102 To check the Event Log for a history of conditions: 1. Press any button on the front panel display to activate the menu options. 2. Press the button until EVENT LOG displays.
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 103 Action Possible Cause Alarm or Condition Overload LED is on. 1 beep every second. Power requirements exceed the UPS capacity (greater than 100% of nominal; see page 84 for specific output overload ranges).
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 104 Action Possible Cause Alarm or Condition The UPS does not start. The power cord is not connected correctly. Check the power cord connections. The Remote Emergency Power-off (REPO) switch is active or the REPO connector is missing.
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 105 Silencing the Alarm Press any button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition.
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 106.
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 107 Chapter 9 Warranty Two-Year Limited Warranty (US and Canada) Powerware UPS Models: 3105, 9120, 9125, 9130, 9140, and FERRUPS ® up to 3.1 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc.
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 108 WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caus.
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 109 COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services .
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 110 WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caus.
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 111 OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any).
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 112 WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User's equipment does not include reimbursement for or restoration of any data loss.
An important point after buying a device Eaton Powerware 9130 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Eaton Powerware 9130 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Eaton Powerware 9130 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Eaton Powerware 9130 you will learn all the available features of the product, as well as information on its operation. The information that you get Eaton Powerware 9130 will certainly help you make a decision on the purchase.
If you already are a holder of Eaton Powerware 9130, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Eaton Powerware 9130.
However, one of the most important roles played by the user manual is to help in solving problems with Eaton Powerware 9130. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Eaton Powerware 9130 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center