Instruction/ maintenance manual of the product AQUAZONE 50PCH Carrier
Go to page of 52
Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53500094-01 Printed in U. S.A. Form 50PC-3SI Pg 1 3-11 Replaces: 50PC-2SI Installation, Star t-Up , and Ser vice Instructions CONTENTS Page SAFETY CONSIDERA T IONS .
2 Improper installation, adjustment, alteration, service, mainte- nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property dam- age. Consult a qualified installer , service agency , o r your distrib- utor or branch fo r information or assistance.
3 or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate- rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.
4 F RIGHT RETURN S TRAIGHT DI S CHARGE FRONT L N O M RIGHT RETURN FRONT LEFT/ S TRAIGHT DI S CHARGE C S P BACK DI S CHARGE CONDEN S ATE 3 / 4" FPT 3 .
5 Accessory Electric Heat (if applicable) Filter Access Return Loop Supply Loop W ater Out W ater In Integral hanger support- pre-attached in factory Field-supplied transition to minimize pressure los.
6 ACCE SS PANEL S T OP VIEW-LEFT RETURN U R S I S OMETRIC VIEW LEFT RETURN LEFT VIEW - AIR COIL OPENING T C POWER S UPPLY 3 /4" [19.1 MM] HV KNOCKOUT LOW V OLTAGE 1/2" [12.7 MM] L V KNOCKOUT LOW V OLTAGE 1/2" [12.7 MM] L V KNOCKOUT CONDEN S ATE 3 /4" FPT FRONT-VIEW K 1.
7 Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP: • Units are for indoor use only . • Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%.
8 Side to Back Discharge Conversion 1. Remove screws to free the top and discharge panels. See Fig. 5. 2. Remove the access panel and set aside. 3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.
9 Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not in- stall units with a common trap or vent. VE N T IN G — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line.
10 Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum ex- pected dew point of the pipe am bient. Insulation is required if loop water temperature drops below the dew point.
11 NO TES: 1. Compressor and bl ower moto r thermally protected internally . 2. All wiring to the unit must comply with NEC and local codes. 3. T ransformer f or 208/230 v will be connected for 208 v oper ation. F or 230 v operatio n, s witch RED wire to O RG wire.
12 NO TES: 1. Compressor ther mally protected internally . 2. All wiring to the unit must comply with NEC and local codes. 3. T ransf ormer is wired to 208-v RED lead fo r 208-3-60 units . For 230-3-60, switch RED and ORG lea ds at L1 and insulate RED lead.
13 NO TES: 1. Compressor ther mally protected i nternally . 2. All wiring to the unit must comply with NEC and local codes . 3. T ransformer is wired to 460-v BLK/ RED lead fo r 460-3-60 units or 575-v GR Y lead f or 575- 3-60 units. T ransf ormer is energy limiting or may ha v e circuit break er .
14 Fig. 16 — 50PCH,PCV Units wi th Complete C and LON Contr oll er (460 V) Compl ete C a50-8493 LEGEND AL — Ala rm Relay Contacts BM — Blower Motor BMC — Blower Mo tor Capacitor BR — Blower .
15 Deluxe D NO TES: 1. Compressor and blow er motor ther mally protected inter nally . 2. All wiring to the unit must comply with NEC and local codes . 3. T ransformer is wired to 460-v BLK/RED lead f or 460-3-60 units . T rans- fo rmer is energy limiting or ma y have ci rcuit breaker .
16 WH S P-OPEN F S D Fig. 18 — Units wi th Complete C and WS HP Open Multiple Protocol Controls A50-8697 LEGEND BM — Blo wer Motor BR — Blow er Relay CO — Cond ensate Overflow FSD — Fire S mok e De tector LW T — Leaving Water T emperature N.
17 W S HP-OPEN F S D Fig. 19 — Units with Deluxe D and WS HP O pen Multiple Protocol Controls A50-8698 LEGEND BM — Blo wer Motor BR — Blow er Rela y CO — Condensate Overflow FSD — Fire Smoke Detector LW T — Leaving W ater T e mperature N.C.
18 012207-1BT4 8 5BT LED1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CO.
19 Table 3 — 50PCH,PCV Uni t Electrical Data LEGEND *Units using 460-v and ECM (electr onically commutated motor), modulating HWR (hot water reheat), and /or internal secondary pump will require a neutral wire from the supply side in order to f eed accessory with 265-v .
20 Step 9 — Wire Field Contr ols THERMOST A T CONNECTIONS — Th e the rmo s t a t should be wired directly to th e Aquazone™ control board. See Fig. 13-20, and 22. W A TE R FREEZE PROTE CTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers.
21 WS H P OP E N W I R IN G — The WSHP Open controller will be factory wired to the Complete C or Deluxe D control board, however , the system wiring will need to be completed utilizing WSHP Open controller wiring diagrams and the Third Party Integration (TPI) Guide.
22 W iring a Supply Air T emperature (SA T) Sensor — The SA T sensor is required for reheat applications. If the cable used to wire the SA T sensor to the controller will be less than 100 ft, an unshielded 22 A WG (American W ire Gage) cable should be used .
23 Table 9 — 50PCH,PCV Blo wer Performance — Sta ndard Unit NO TES: 1. Shaded areas denote ES P (e xternal static pressure) where oper ation is not recommended. 2. Units fact ory shipped on medium speed. Other sp eeds require field selection. 3. All airflow is r ated and sho wn abov e at low est volt age if unit is dual v olt- age rated, i.
24 FIELD SELECT ABLE INPUTS Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.
25 Table 11 — DIP Switch Bloc k S2 — Accessory 1 Relay Option s LEGEND NO TE: All other DIP swi tch combinations are inv alid. Table 12 — DIP Switch Bloc k S2 — Accessory 2 Re lay Options LEGEND NO TE: All other switch combinations are in v alid.
26 Table 13 — Operating Limits — 50PCH,PCV Units LEGEND Scr oll Compressor Rotation — It is important to be certain compressor is rotatin g in the proper direction. T o determine whether or not com pressor is rotating in th e prop- er direction: 1.
27 Table 15 — 50PC006 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution. Table 16 — 50PC009 Typical Unit Operating Pressures and Temperat ures LEGEN D *Based on 15% Methanol anti freeze sol ution.
28 Table 18 — 50PC015 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution. Table 19 — 50PC018 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution.
29 Table 21 — 50PC030 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution. Table 22 — 50PC036 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution.
30 Table 24 — 50PC048 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution. Table 25 — 50PC060 Typical Uni t Operating Pressur es and Temperature s LEGEN D *Based on 15% Methanol anti freeze sol ution.
31 T o start-up a unit with WSHP Open controls: 1. T o plug in the BAC view 6 handheld display into a SPT sensor , point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.
32 Flow Regulati on — Flow regulation can be accom- plished by two methods. Most wate r control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger , the flow rate can be deter- mined. See T able 26.
33 the water loop. If an open type cooling tower is used continu- ously , chemical treatment a nd filtering will be necessary . Table 27 — Approximate Fluid Volume (gal.) per 100 Ft of Pipe LEGEND NO TE: V olume of heat e xchanger is appro ximately 1.
34 optional CO 2 IAQ (indoor air quality) sensor mounted in the space can maximize the occupa nt comfort. The WSHP Open controller has its own hardware cl ock that is automatically set when the heat pump software is downloaded to the board. Oc- cupancy types are described in the scheduling section below .
35 of capacity . Likewise, a 45-second delay is used when staging down. After a compressor is staged off, it may be restarted again after a normal time-guard period of 5 minutes and if the supply-air temperature has increased above the minimum supply-air temperature limit.
36 • The IAQ sensor reading is greater than the DCV start control set point . The control has four user adjustable set points: DCV start control set point, DCV maximum control set point, minimum damper position, and DCV maximum damper position.
37 stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step. DE H U MI D I F I CA TI O N TE S T — T ests dehumidification mode. Operates for 2 minutes. AU X I L IA RY H EA T I N G T ES T — T ests auxiliary heat.
38 Table 31 — Aquazone Deluxe D Co ntrol Current LED Status and Ala rm Relay Operations LEGEND NO TES: 1. If there is no f ault in memo ry , the F ault LED will flash code 1. 2. Codes will be displayed with a 10-second F ault LED pause . 3. Slow flash is 1 flash ev er y 2 seconds.
39 Air Coil Cleaning — Remove dirt and debris from evap- orator coil as required by condition of the coil. A 10% solution of dishwasher deter gent and water is recommended for cleaning both sides of the coil, followed by a thorough water rinse. Clean coil with a stiff brush, vacuum cleaner , or com- pressed air .
40 Air Coil Fan Motor Remo val Disconnect motor power wires from motor terminals before motor is removed from unit. 1. Shut off unit main power supp ly . 2. Loosen bolts on mounting bracket so that fan belt can be removed. 3. Loosen and remove the 2 motor mounting bracket bolts on left side of bracket.
41 Table 32 — Troubleshooting LEGEND RV — Re versing V alve F AUL T H EA TING COOLING POSSIBLE CAUSE SOLUTION Main P ower Pr oblems X X Green Statu s LED Off Check line voltage circuit breaker and disconnect. Check for line v oltage between L1 and L2 o n the contactor.
42 Table 32 — Troubleshooting ( cont) LEGEND RV — Re versing V alve F A UL T HEA TING COOLING POSSIBLE CA USE SOLUTION Only Compressor Runs X X Thermostat wir ing Check G wiring at heat pump. J umper G and R f or f an operation. Check Y and W wiring at heat pump.
43 APPENDIX A — WSHP OPEN SCREEN CONFIGURA TION LEGEND SCREEN NAME POINT NAME PA S SWO R D LEVEL EDITABLE RANG E DEFAULT NOTES Equipment Status Operating Mode No P assword Required Off, F an Only , .
44 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA S S WO RD LEVEL EDITABLE RANGE D EFAULT NOTES Unit Maintenance Operating Mode No P assw ord required Off, F an .
45 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT N AME PAS SW OR D LEVEL EDITABLE RANG E DEFAULT NOTES Configuration Set Points Occupied Heating User/Admin P assw ord .
46 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA S SWO R D LEVE L EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration F an Mode Admin P ass word lev e.
47 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS S WO RD LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Service Configuration # of F an Speeds Admin P ass wo.
48 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA S SWO R D LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Alarm Configuration SPT Occupied Alarm Hysteresis Ad.
.
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No .
CL-1 50PCH,PCV ST A RT -UP CHECKLIST CUSTOMER: ___________________________ JOB NAME: _______________________________________ MODEL NO.:___________________________ SERIAL NO.
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No .
An important point after buying a device Carrier AQUAZONE 50PCH (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Carrier AQUAZONE 50PCH yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Carrier AQUAZONE 50PCH - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Carrier AQUAZONE 50PCH you will learn all the available features of the product, as well as information on its operation. The information that you get Carrier AQUAZONE 50PCH will certainly help you make a decision on the purchase.
If you already are a holder of Carrier AQUAZONE 50PCH, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Carrier AQUAZONE 50PCH.
However, one of the most important roles played by the user manual is to help in solving problems with Carrier AQUAZONE 50PCH. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Carrier AQUAZONE 50PCH along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center