EN
Ajax logo
Official user manual

Ajax FireProtect (FireProtect / FireProtect Plus)

19 pages·164 KB·Detector·PDF·ENDEFRITNLJA
Ajax FireProtect (FireProtect / FireProtect Plus)
Table of Contents 20 sections FireProtect / FireProtect Plus User Manual · Functional Elements · Operating Principle · Connecting the Detector to the Ajax Security System · … ShowHide
Page 1 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — FireProtect / FireProtect Plus User Manual
Page 1 · click to enlarge
Page 1

FireProtect / FireProtect Plus User Manual

Updated December 10, 2020

Ajax FireProtect (FireProtect / FireProtect Plus) — FireProtect / FireProtect Plus User Manual diagram (page 1)
Fig. 1 · FireProtect / FireProtect Plus User Manual

FireProtect (FireProtect Plus) is a wireless indoor âre detector with an in-built buzzer and a battery, ensuring up to 4 years of autonomous operation. FireProtect can detect smoke and rapid temperature increase.

Aside from these functions, FireProtect Plus additionally can alert of dangerous CO level. Both detectors can function independently from the hub.

Connecting to the Ajax security system via a secured radio protocol, FireProtect (FireProtect Plus) communicates with the at a distance of up to 1,300 m in line of sight.

The detector can be a part of third-party security systems, connecting to them via the or integration module.

Ajax uartBridge Ajax ocBridge Plus

Buy âre detector with carbon monoxide sensor FireProtect Plus

Jeweller · hub

Page 2 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Operating Principle
Page 2 · click to enlarge
Page 2

The detector is set up via the for iOS, Android, macOS, and Windows. The system notiâes the user of all events through push notiâcations, SMS, and calls (if activated).

The Ajax security system can be connected to a central monitoring station of a security company.

Buy âre detector FireProtect

Functional Elements

Ajax FireProtect (FireProtect / FireProtect Plus) — Functional Elements diagram (page 2)
Fig. 2 · Functional Elements
1. Siren hole
2. Light indicator (acts as the sensor and Test button)
3. Smoke chamber hole with the temperature detector behind the net
4. SmartBracket attachment panel
5. Power button
6. Tamper button
7. QR code

Operating Principle

Ajax apps

Page 3 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Functional Elements
Page 3 · click to enlarge
Page 3

When smoke penetrates the detector chamber, it distorts infrared light between the emitter and photoelectric receiver. This distortion triggers a smoke alarm. When the temperature exceeds 60°С or rises by 30°С during 30 minutes (not necessary to reach 60°С), the detector registers temperature increase, which triggers a âre alarm.

FireProtect Plus has an additional sensor to detect a dangerous CO level. If the concentration of CO in the air exceeds a certain level, the detector generates an alarm.

The detector is triggered:

within 60–90 min at carbon oxide concentration 50 ppm / 0.005%

within 10–40 min at CO concentration 100 ppm / 0.01%

within 3 min at carbon oxide concentration 300 ppm / 0.03%.

In case of alarm, the detector activates the built-in buzzer (the siren sound can be heard from afar) and blinks with the light indicator. When connected to a security system, both the user and the security company are notiâed of the alarm.

The siren of the device can be turned off using three ways:

1. By pressing the Ajax logo on the device lid (there is a touch button under the logo).
Ajax FireProtect (FireProtect / FireProtect Plus) — Functional Elements diagram (page 3)
Fig. 3 · Functional Elements
Page 4 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Connecting the Detector to the Ajax Security System
Page 4 · click to enlarge
Page 4
2. Through the Ajax app. In case of âre alarm, you will see a pop-up message in Ajax app suggesting to turn off the built-in sirens.
3. Using the . To turn off the built-in sirens in case of âre alarm, press the “*” button on the KeyPad.
Ajax FireProtect (FireProtect / FireProtect Plus) — Connecting the Detector to the Ajax Security System diagram (page 4)
Fig. 4 · Connecting the Detector to the Ajax Security System

Please note that for this to work you need to priorly select Mute alarm command for this button in the KeyPad settings.

If smoke and/or temperature levels do not restore to normal values, in 10 minutes, the FireProtect/FireProtect Plus turns on the siren again.

Connecting the Detector to the Ajax Security System

Connecting to the hub

Before starting connection:

1. Following the hub user guide, install the . Create the account, add the hub, and create at least one room.

KeyPad · Ajax app

Page 5 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Connecting the Detector to the Ajax Security System
Page 5 · click to enlarge
Page 5
2. Switch on the hub and check the internet connection (via Ethernet cable and/or GSM network).
3. Make sure that the hub is disarmed and does not update by checking its status in the Ajax app.

Only users with administrator rights can add the device to the hub

Pairing the detector with hub:

1. Select Add Device in the Ajax app.
2. Name the device, scan or type the QR Code (located on the detector body and packaging), and select the location room.
Ajax FireProtect (FireProtect / FireProtect Plus) — Connecting the Detector to the Ajax Security System diagram (page 5)
Fig. 5 · Connecting the Detector to the Ajax Security System
3. Tap Add — the countdown will start.
4. Switch on the device.
Page 6 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Connecting to Third Party Security Systems
Page 6 · click to enlarge
Page 6
Ajax FireProtect (FireProtect / FireProtect Plus) — Connecting to Third Party Security Systems diagram (page 6)
Fig. 6 · Connecting to Third Party Security Systems

To make sure that the detector is on, press the on/off button — the logo will light up red for a second.

For detection and pairing to occur, the detector should be located within the coverage area of the wireless network of the hub (at a single protected object). The connection request is transmitted for a short time: at the moment of switching on the device.

If pairing with the hub fails, the detector operates autonomously; switch off the detector for 5 seconds and retry.

The detector connected to the hub is displayed in the list of devices in the app. The update of the detector status in the list depends on the device inquiry time set in the hub settings (the default value is 36 seconds).

Connecting to Third Party Security Systems

To connect the detector to a third party security central unit using the

Ajax uartBridge Ajax ocBridge Plus

or integration module, follow the recommendations in the manual of the respective device.

The smoke detector always operates in the active mode. When connecting FireProtect to third party security systems, it is appropriate to place it in a permanently active protection zone.

Page 7 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — States
Page 7 · click to enlarge
Page 7

States

1. Devices
2. FireProtect | FireProtect Plus
ParameterState TemperatureTemperature of the device. Measures on the device processor and changes gradually Jeweller Signal StrengthSignal strength between the hub and the detector ConnectionConnection status between the hub and the device Battery ChargeBattery level of the device. Two states available: ОК Battery discharged How battery charge is displayed in Ajax apps LidThe tamper state of the device — reacts to the detachment Routed Through ReXDisplays the status of using the ReX range extender SmokeShows if smoke is detected Temperature threshold exceededThe state of temperature threshold exceeded alarm Rapid temperature riseThe state of rapid temperature increase alarm High CO Level (FireProtect Plus only)The state of dangerous CO level alarm Backup Battery ChargeBackup battery level of the device Smoke sensorThe state of the smoke detector Smoke sensor dust levelThe dust level in the smoke chamber

Temporary Deactivation Shows the status of the device: active, completely disabled by the user, or only notiâcations about

Page 8 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Settings
Page 8 · click to enlarge
Page 8

triggering of the device tamper button are disabled

FirmwareDetector ârmware version Device IDDevice identiâer

Settings

1. Devices
2. FireProtect | FireProtect Plus
3. Settings
SettingValue First âeldDevice name, can be edited RoomSelecting the virtual room to which the device is assigned Dangerous CO Level Alarm (FireProtect Plus only)If active, the detector alerts of exceeding the limits of carbon monoxide concentration High temperature alarmIf active, the detector reacts when the temperature is 60°C and higher Rapid temperature rise alarmIf active, the detector reacts to rapid temperature increase (30°С for 30 minutes or less) Alert with a siren if smoke is detectedIf active, sirens added to the system are activated in case of smoke alarm Alert with a siren if temperature threshold exceededIf active, sirens added to the system are activated in case if temperature threshold exceeded Alert with a siren if rapid temperature rise detectedIf active, sirens added to the system are activated in case if rapid temperature rise detected Alert with a siren if CO detected (FireProtect Plus only)If active, sirens added to the system are activated in case if CO concentration is dangerous

Jeweller Signal Strength Test Switches the device to the signal strength test

Page 9 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Interconnected FireProtect Alarms Setup
Page 9 · click to enlarge
Page 9
Starts FireProtect selftest Temporary DeactivationAllows the user to disconnect the device without removing it from the system. Two options are available: Deactivate entirely — the device will not execute system commands or participate in automation scenarios, and the system will ignore device alarms and other notiâcations Deactivate lid notiâcations — the system will ignore only notiâcations about the triggering of the device tamper button Learn more about temporary deactivation of devices Note that a disabled device does not trigger an interconnected alarm of âre detectors. But if smoke is detected, the built-in siren will sound User GuideOpens the detector User Guide Unpair DeviceDeletes device and its settings

Interconnected FireProtect Alarms Setup

The function activates built-in sirens of all âre detectors if at least one of them is triggered. Sirens are activated within the hub–detector ping interval according to the Jeweller settings.

To enable Interconnected Alarms:

1. Open the Devices tab in the 2. Select a hub 3. Go to its Settings by pressing 4. Select the Service item 5. Go to the Fire detectors settings menu and activate the Interconnected FireProtect Alarms option

mode · Ajax app

Page 10 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Interconnected FireProtect Alarms Setup
Page 10 · click to enlarge
Page 10

Interconnected alarms are supported by FireProtect and FireProtect Plus detectors with ârmware versions 3.42 and later. Please note that when you turn on the interconnected alarms, you cannot set the hub–detector ping interval (Jeweller settings) of more than 48 seconds.

6. If necessary, set the Delay of Interconnected Alarms from 0 to 5 minutes (in 1minute increments). The option allows you to postpone the interconnected alarm for a speci âed period of time.

When this option is inactive, the interconnected alarm is sent to all âre detectors within a minute.

The function works as follows:

1. One of the FireProtect/FireProtect Plus detectors detects an alarm. 2. Delay of Interconnected Alarms starts. 3. The built-in siren of the âre detector informs the alarm. Users receive notiâcations in the Ajax app (if are enabled). At the object, are activated (if the are enabled).

appropriate notiâcations Ajax sirens corresponding settings

Ajax FireProtect (FireProtect / FireProtect Plus) — Interconnected FireProtect Alarms Setup diagram (page 10)
Fig. 7 · Interconnected FireProtect Alarms Setup
Page 11 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Interconnected FireProtect Alarms Setup
Page 11 · click to enlarge
Page 11
4. An alarm con ârmation event is sent to the monitoring station and security system users, and the system starts the interconnected alarm for âre detectors if:

The interconnected alarm delay time has passed, and the triggered detector is still registering an alarm.

00:00 00:14

During the delay of the interconnected alarms, the triggered detector reports a different type of alarm (for example, the detector report the exceeding of the temperature threshold after a smoke alarm).

00:00 00:13

Page 12 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Interconnected FireProtect Alarms Setup
Page 12 · click to enlarge
Page 12

During the interconnected alarm delay, another âre detector in the system raised an alarm.

00:00 00:11

To give more time to eliminate the cause of false triggering of the detector, the user can delay the propagation of the interconnected alarm for another 10 minutes:

Through Ajax apps.

Ajax FireProtect (FireProtect / FireProtect Plus) — Interconnected FireProtect Alarms Setup diagram (page 12)
Fig. 8 · Interconnected FireProtect Alarms Setup

By pressing the KeyPad function button (if enabled).

Page 13 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Indication
Page 13 · click to enlarge
Page 13

By pressing the Button in the âre alarm muting mode.

By eliminating the cause of the alarm (âre detectors at the facility no longer detect an alarm).

By pressing the touch button of the triggered âre detector.

If a triggered detector does not return to a normal state within 10 minutes after the user postponed the interconnected alarm, another âre detector reports an alarm, or a triggered detector reports an alarm of another type (for example, temperature and smoke), the system will send an alarm conârmation and activate interconnected alarm for âre detectors.

7. If necessary, activate the Ignore First Alarm option. This setting is recommended for premises with potential sources of false alarms. For example, if the device is installed in a place where dust or steam can get into the detector.

The option functions as follows:

1. The detector reports a smoke alarm. 2. The built-in 30-second timer of the detector starts. 3. If after 30 seconds the detector still detects a threat, an alarm is sent to the hub.

Indication

Detector switching on The logo lights up green for 1 second

Detector switching off The logo blinks red three times and the device switches off

Registration failed The logo blinks green for a minute, then the device switches to the autonomous mode

Smoke or temperature increase detected The siren switches on, the logo lights red during the âre/smoke alarm

One short sound signal per 90 sec — main

Event Indication · Battery low

Page 14 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Installation
Page 14 · click to enlarge
Page 14

Two short sound signals per 90 sec — backup battery low (CR2032)

Three short sound signals per 90 sec — both batteries low

Performance testing

The Ajax security system allows conducting tests for checking the functionality of connected devices.

The tests do not start straight away but within a period of 36 seconds when using the standard settings. The test time start depends on the settings of the detector scanning period (the paragraph on “Jeweller” settings in hub settings).

Jeweller Signal Strength Test

According to the requirements of EN50131 standard, the level of the radio signal sent by wireless devices is decreased during the test mode.

Detector Testing

Before installing the detector, check the smoke sensor. To test it, switch on the detector and press the sensor button (the logo center) for a few seconds – the detector will test the smoke chamber with electronic simulation of smoke generation and then will switch on the siren for 6 seconds.

You will receive the notiâcation in the Ajax app regarding the test result and detector status.

Installation

batteries low (CR2) · FireProtect Self Test · Attenuation Test

Page 15 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Installation procedure
Page 15 · click to enlarge
Page 15

Selecting the Location

The location of the detector depends on its remoteness from the hub, and obstacles hindering the radio signal transmission: walls, ãoors, large objects inside the room.

The device developed only for indoor use.

If the signal level is low (one bar), we cannot guarantee the stable operation of the detector. Take all possible measures to improve the quality of the signal. At least, move the detector: even a 20 cm shift can signiâcantly improve the quality of signal reception.

Check the Jeweller signal level at the installation location

If the detector has low or unstable signal strength even after moving, use a

ReX radio signal range extender

Install the detector at the ceiling in the highest point where hot air and smoke are concentrated in case of âre.

If there are any beams at the ceiling, protruding by 30 or more centimeters from the ceiling level, install the detector between every two beams.

Where and how to install FireProtect Plus

Installation procedure

Before installing the detector, make sure that you have selected the optimal location that follows the guidelines of this manual!

Page 16 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Autonomous Use of the Detector
Page 16 · click to enlarge
Page 16
1. Fix the SmartBracket panel on the ceiling using bundled screws. If you use any other attachment tools, make sure that they do not damage or deform the attachment panel.

Use double-side adhesive tape only for temporary attachment of the detector. The tape runs dry with time, which can cause falling, false triggering, and detector malfunction.

2. Put the detector on the attachment panel by turning it clockwise on SmartBracket. When the detector is âxed in SmartBracket, it blinks with LED, signaling that the tamper is closed.

If LED doesn’t blink after âxing in SmartBracket, check the status of the tamper in the and then the âxing tightness of the panel.

If someone detaches the detector from the surface or takes it off the attachment panel, the security system notiâes you.

Do not install the detector:

1. outside the premises (outdoors);
2. nearby any metal objects or mirrors causing attenuation or screening of the signal;
3. at any places with fast air circulation (air fans, open windows or doors);
4. closer than a meter to the cooking surface;
5. inside premises with the temperature and humidity beyond the range of permissible limits;
6. closer than 1 m to the hub.

Autonomous Use of the Detector

The detector can be used autonomously, without connecting to a security system.

Ajax app

Page 17 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Maintenance and Battery Replacement
Page 17 · click to enlarge
Page 17
1. Switch on the detector by pressing the on/off button for 3 seconds (the logo will light up green for 1 second) and conduct the smoke test.
2. Select the optimal location of the detector following the recommendations in the second part of the section of this manual. Selecting the location
3. Install the detector as described in the section . Installation procedure

In case of autonomous use, the detector notiâes of the detected âre/smoke with the siren sound and light of the logo. To switch off the siren, press the logo (there is a sensor button) or eliminate the cause of the actuated alarm.

Maintenance and Battery Replacement

Check the operational capability of the detector regularly. Clean the detector body from dust, spider web, and other contaminants as they appear. Use soft dry napkin suitable for tech equipment.

Do not use any substances containing alcohol, acetone, gasoline, and other active solvents to clean the detector.

To a certain level, the detector ignores the dust in the smoke chamber. When the chamber becomes too dusty, the detector notiâes the user of the need to clean it via the app (and beeps every minute and a half). Such maintenance is compulsory for the detector to operate correctly.

How to clean up the smoke chamber

Pre-installed batteries ensure up to 4 years of autonomous operation. If the batteries are discharged, the security system sends the respective notiâcations and the detector signal with a sound every 90 seconds:

if the main batteries are low — a single short signal;

if the backup battery is low — two short signals;

if both batteries are low — three short signals.

How long Ajax devices operate on batteries, and what affects this

Page 18 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Tech Specs
Page 18 · click to enlarge
Page 18

Tech Specs

Smoke-sensitive element Photoelectric sensor

Temperature sensitive element Thermocouple

Sound notiâcation volume 85 dB at a distance of 3 m

Alarm threshold at the temperature +59°С ±2°С

Frequency band 868.0 – 868.6 MHz or 868.7 – 869.2 MHz depending on the region of sale

hubs range extenders ocBridge Plus uartBridge

Operates independently or with all Ajax ,

Maximum RF output power Up to 20 mW

Radio signal modulation GFSK

Radio signal range Up to 1,300 m (any obstacles absent)

Power supply 2 × CR2 (main batteries), CR2032 (backup battery), 3 V

Battery life Up to 4 years

Operating temperature range From 0°С to +65°С

Operating humidity Up to 80%

Show 5 more labels / short text on this page
Battery Replacement · Tamper protection Yes · , , · Compatibility · Installation method Indoors
Page 19 of the Ajax FireProtect (FireProtect / FireProtect Plus) user manual — Warranty
Page 19 · click to enlarge
Page 19

Overall dimensions 132 × 132 × 31 mm

Complete Set

1. FireProtect ( FireProtect Plus )
2. SmartBracket mounting panel
3. Batteries CR2 (pre-installed) — 2 pcs
4. Battery CR2032 (pre-installed) — 1 pcs
5. Installation kit
6. Quick Start Guide

Warranty

Warranty for the “AJAX SYSTEMS MANUFACTURING” LIMITED LIABILITY COMPANY products is valid for 2 years after the purchase and does not apply to the pre-installed battery.

If the device does not work correctly, you should ârst contact the support service — in half of the cases, technical issues can be solved remotely!

The full text of the warranty

Technical support:

[email protected]

Weight 220 g · User Agreement

Ask about the Ajax FireProtect (FireProtect / FireProtect Plus)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Ajax FireProtect (FireProtect / FireProtect Plus)

Be the first to ask — other owners or our team will answer.

Original document

Ajax FireProtect (FireProtect / FireProtect Plus) manual PDF

19 pages·164 KB·Detector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…