HRVBBLHU HRVBBSVC
HRVBBLVU
Heat Recovery Ventilators
The Heat Recovery Ventilation (HRV) system offered by Bryant is the finest unit on the market today. The HRVB provides efficient and cost-effective heat recovery during the heating season when needed most.
As temperatures drop below 23°F (–5°C), indoor air is recirculated periodically through the heat exchanger core to prevent frost from forming. Competitors’ methods of supplementary electric defrost waste energy. Unlike rotary wheel heat exchangers which mix air streams, these cross flow or counterflow heat exchangers ensure that there is no mixing of the stale air stream with the fresh outdoor air stream.
A filter installed on the incoming outdoor air stream removes large airborne particles from the intake air stream before they enter the heat exchanger and reduces the maintenance required.
The units’ acoustically engineered design makes them the quietest on the market and ensures that comfort is felt, not heard.
Unlatching 2 suitcase style latches allows easy removal of the filters and core for cleaning.
HRVBBLVU
Form No. PDS HRV.71.1

Maximum Capacity (CFM) 150 CFM 200 CFM 250 CFM 330 CFM Electrical Supply:
1 — 115 volts
Descriptor:
LHU — Large Horizontal Unit SVU — Small Vertical Unit LVU — Large Vertical Unit Brand:
Bryant Equipment Type:

DIVISION OF AMCA
Climate Map for Energy and Heat Recovery Ventilators
Sacramento Salt Lake City
Washington D.C.
ERV Recommended w/HRV or ERV Wall Control


Allows the user to manually set fan speed to low or high as required to maximize comfort.
Offers automatic dehumidistat control and the option to select continuous or intermittent fan operation. Setting the wall control to low will activate the continuous mode.
In addition to the features found with standard control, this package offers a recirculation mode. These controls may only be used to operate stand-alone units with the defrost option which enables the recirculation feature.
* All defrost times are in the standard mode (as shipped) † Time between defrost when within specified temperature range

15" (381.0)
5 7 / 8 " DIA (149.2)
4 PLCS
3.STALE AIR FROM HOUSE TO HRV
4.STALE AIR FROM HR TO OUTSIDE
F
1.FRESH AIR FROM OUTSIDE
E
G
167/8" (428.6)
25/16" (58.7)
181/8" (460.4)
301/4" (768.3)
4 PLCS 1" (25.4)
20" (508.0)
23/16" (56.2)
43/4" (120.6)
D




DIMENSIONS (continued)
18 5⁄16″ [465.1] 2 3⁄16″ [55.6]
19 1⁄16″ [484.2] 8 3⁄16″ [208.0]


2000 sq ft with 8 ft ceiling 0.35 air changes per hr (AC/h)
(2000 sq ft x 8 ft ceiling x 0.35 AC/h) / 60 min/h = 93.3 CFM
2 people 2 baths 1 kitchen
(2 x 15) + (2 x 20) + 25 = 95 CFM
ADDITIONAL HEATING AND COOLING LOAD CHARTS
Although the ventilators process the outside air before it enters the home, additional heating and cooling loads need to be considered.
The heating load chart shows the heating loads in Btuh for a range of winter design temperatures for each model of ventilator.
The heating design temperature for Milwaukee, WI is –4°F. At –5°F, the additional heating load of the HRVBBLHU1250 is 8417 Btuh. This additional load should be taken into consideration when sizing the heating equipment.

The cooling load chart shows loads in Btuh as well. To use the cooling load chart, first find the design enthalpy from a psychrometric chart using the design dry bulb and wet bulb temperatures. (See psychrometric chart on p. 11.) The cooling load can then be found for a range of enthalpies for each ventilator.
The cooling design dry bulb temperature for Milwaukee, WI is 87°F and the average wet bulb at that temperature is 73°F. On the psychrometric chart the enthalpy is about 37.7 Btu/lb of dry air which will round up to 38 Btu/lb of dry air. In the left column, at 38 Btu/lb the HRVBBLHU1250 would have an additional cooling load of 6428 Btuh. This additional load should be taken into account when sizing the air cooling equipment.


0 45 50 55 60 65 70 75 80 85 90 95 100 105 110
Enthalpy at saturation, Btu per pound of dry air
Below 32˚F, properties and enthalpy deviation lines are for ice.


UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
© 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 12HR-VBO 3-00