CM5A/CM5B COILS KMABA BLOWERS

For Manufactured Homes

4THE CM5A/CM5B INDOOR COIL

THE KMABA BLOWER

To complete your cooling or heating system, the model CM5A or CM5B Coil is installed inside your Evcon/Coleman, Nor- dyne/Miller/Intertherm or AirPro gas or electric downflow fur- nace. Both coils are uncased, and designed for installation within the manufactured home furnace casing or inside a fac- tory-installed plenum. These indoor coils are designed to be used in conjunction with blower kits and other accessories. The CM5A and CM5B coils are designed for quick and easy in- stallation by a qualified service technician. The CM5A comes with factory-installed mechanical connec- tions. The CM5B comes with factory-installed sweat connec- tions. Both coils utilize a Check-Flo-Rater® piston for refrig- erant flow control. Both coils can be used in cooling-only applications or as part of a heat pump system. When heating in conjunction with a heat pump, the outdoor heat pump unit recovers heat from the outdoor air, and trans- mits it to the CM5A or the CM5B indoor coil for distribution to the living space. The CM5A and CM5B coils are not activated when heating in conjunction with a furnace without a heat pump in the system. Built-in drainage assembly ensures leak-free condensate re- moval. Periodic cleaning of filter and drainage sections is rec- ommended to avoid possible sediment blockage. The A-shape design of the coil provides maximum cooling-heating transfer surface and ease of handling at installation. Four coil sizes are available from 024 though 048, covering a wide range of cool- ing-heating capacities to meet varying manufactured home re- quirements.

KMABA Blower Kits and Accessories are designed and built to meet the needs of the manufactured housing market. The kits are used to upgrade Nordyne and Evcon gas and electric fur- naces (see note). For cooling and heat pump duty, kits avail- able include blowers for up to 4 tons of air conditioning, control boxes, insulation kits, filter kits, and evaporator coil shelves. Blower kits for gas furnaces are shipped without controls. Order the control box from accessory usage chart. Blower kits for elec- tric furnaces are shipped with or without controls. See acces- sory usage chart for details. All control box kits are designed to operate with a minimum 4-wire thermostat. Quick connect wire harnesses are shipped with the appro- priate blower kit or control box for ease of installation. Sheet metal adapter plates also are included with the blower kits that are needed to adapt the blower with the furnace.

Form No. PDS CM5A.24.2

Page 2 of the Bryant Air Conditioner Coil (CM5A) user manual — CM5A SPECIFICATIONS
Page 2 · click to enlarge
Page 2

CM5A DIMENSIONS

Bryant Air Conditioner Coil (CM5A) — CM5A DIMENSIONS diagram (page 2)
Fig. 1

3⁄8″ DIA LIQUID FITTING "B" DIA VAPOR FITTING

UNIT SIZESERIESUNIT DIMENSIONS (In.)NUMBER OF ROWSSHIPPING WEIGHT (Lb) ABC 024A145/8330 036A163/4332 042A183/4335 048A183/4437
Bryant Air Conditioner Coil (CM5A) — CM5A DIMENSIONS diagram (page 2)
Fig. 2

NOTE:

Series designation is the 14th position of unit model number.

CM5A SPECIFICATIONS

UNIT SIZE-SERIES024-A036-A042-A048-A Operating Weight (Lb)21232628 REFRIGERANT ControlCheck-Flo-Rater® Piston COIL TypeUncased A-Type with Aluminum Fins Rows-Fins/In.3–153–153–154–13 Face Area (Sq Ft)3.113.564.003.56 Nominal CFM800120012001200 CONNECTIONS TypeMechanical Vapor (In. ID)5/83/4 Liquid (In. ID)3/8 OPTIONAL EQUIPMENT TXV (Hard Shutoff)KSATX0801HSOKSATX0901HSO
Bryant Air Conditioner Coil (CM5A) — CM5A SPECIFICATIONS diagram (page 2)
Fig. 3
Page 3 of the Bryant Air Conditioner Coil (CM5A) user manual — CM5B SPECIFICATIONS
Page 3 · click to enlarge
Page 3

CM5B DIMENSIONS

Bryant Air Conditioner Coil (CM5A) — CM5B DIMENSIONS diagram (page 3)
Fig. 4
UNIT SIZESERIESUNIT DIMENSIONS (In.)NUMBER OF ROWSSHIPPING WEIGHT (Lb) ABC 024A145/8330 036A163/4332 042A187/8335 048A187/8437
Bryant Air Conditioner Coil (CM5A) — CM5B DIMENSIONS diagram (page 3)
Fig. 5

NOTE:

Series designation is the 14th position of unit model number.

CM5B SPECIFICATIONS

UNIT SIZE-SERIES024-A036-A042-A048-A Operating Weight (Lb)21232628 REFRIGERANT ControlCheck-Flo-Rater® Piston COIL TypeUncased A-Type with Aluminum Fins Rows—Fins/In.3–153–153–154–13 Face Area (Sq Ft)3.113.564.003.56 Nominal CFM800120012001200 CONNECTIONS TypeSweat Vapor (In. ID)5/83/47/8 Liquid (In. ID)3/8 OPTIONAL EQUIPMENT TXV (Hard Shutoff)KSATX0801HSOKSATX0901HSO
Bryant Air Conditioner Coil (CM5A) — CM5B SPECIFICATIONS diagram (page 3)
Fig. 6
Page 4 of the Bryant Air Conditioner Coil (CM5A) user manual — NOTE:
Page 4 · click to enlarge
Page 4
Bryant Air Conditioner Coil (CM5A) — KMABA SPECIFICATIONS diagram (page 4)
Fig. 7
BLOWER MODELABCD KMABA01013TG17-3/415-1/47-3/89-5/8 KMABA02014TG7-1/210 KMABA03013TE7-3/89-5/8 KMABA04014TE7-1/210 KMABA05013TE7-3/89-5/8 KMABA06014TE7-1/210
Bryant Air Conditioner Coil (CM5A) — KMABA SPECIFICATIONS diagram (page 4)
Fig. 8

KMABA SPECIFICATIONS

BLOWER MODEL01013TG02014TG03013TE04014TE05013TE06014TE Shipping Weight (Lb)303833393541 ELECTRICAL Volts—Phase115/1115/1208–230/1208–230/1208–230/1208–230/1 Operating Voltage Range104–127104–127187–253187–253187–253187–253 Full Load Amps7.209.003.004.303.004.30 BLOWER MOTOR Motor Hp (PSC)1/21/21/23/41/23/4 RPM—Speeds1075/3 Blower TypeDirect Drive BLOWER WHEEL Diameter (In.)10-1/211-1/210-1/211-1/210-1/211-1/2 Width (In.)8 Air DischargeDownflow Maximum Cooling Capacity3 Ton4 Ton3 Ton4 Ton3 Ton4 Ton ACCESSORIES Control Box KitKMACC02014WGKMACC0401E14KMACC0601FE4 Filter KitN/AKMAFK0101NFK Insulation KitN/AKMAIK0101E1IN/A Coil Shelf KitN/AKMACR0101CRI
Bryant Air Conditioner Coil (CM5A) — KMABA SPECIFICATIONS diagram (page 4)
Fig. 9

NOTE:

Refer to Accessory Usage chart for exact kit application. N/A—Not applicable

Page 5 of the Bryant Air Conditioner Coil (CM5A) user manual — NOTES:
Page 5 · click to enlarge
Page 5

PERFORMANCE DATA

GROSS COOLING CAPACITIES (MBH)

INDOOR COIL AIRSATURATED TEMPERATURE LEAVING EVAPORATOR (°F) 3035404550 CFMEWB (°F)TCGSHGBFTCGSHGBFTCGSHGBFTCGSHGBFTCGSHGBF CM5A/CM5B024 6007250.424.20.0045.821.80.0040.919.40.0035.316.90.0928.814.30.06 6741.524.80.0837.022.40.0632.019.90.0526.217.30.0519.914.70.06 6233.725.40.0529.122.90.0524.120.40.0618.517.50.0814.814.80.19 8007261.929.40.0056.726.80.0050.824.10.0044.021.10.1136.017.90.08 6751.630.90.1046.228.10.0839.925.10.0732.722.00.0724.918.70.08 6242.132.10.0736.429.10.0730.126.00.0823.222.40.1119.019.00.22 10007271.533.80.0065.430.90.0058.627.80.0051.124.70.1242.221.20.10 6759.736.00.1253.733.00.1046.729.80.0938.426.20.0929.222.30.10 6249.238.10.0942.734.70.0935.431.10.1027.626.90.1322.922.90.25 CM5A/CM5B036 10007274.835.40.0068.732.50.0061.729.30.0054.026.10.1144.822.50.09 6762.637.70.1056.434.70.0949.231.40.0840.827.70.0731.323.70.09 6251.339.70.0844.736.30.0837.532.70.0929.128.30.1223.923.90.24 12007283.439.40.0076.936.30.0069.233.00.1960.429.40.1250.525.60.10 6770.142.60.1163.139.30.1055.335.70.0946.231.80.0935.727.40.10 6257.645.40.0950.541.80.0942.537.80.1033.432.80.1427.827.80.26 14007290.642.80.0083.639.70.0075.536.20.1765.932.40.1355.428.40.12 6776.346.90.1268.943.50.1160.339.60.1150.835.60.1039.630.90.12 6262.950.50.1055.446.70.1146.942.50.1237.437.10.1631.531.50.29 CM5A/CM5B042 10007277.436.70.0071.533.80.0064.730.70.0056.827.40.1147.823.80.08 6765.239.20.0959.036.10.0851.632.70.0743.329.00.0633.625.00.07 6254.241.60.0747.438.10.0739.934.40.0731.229.90.0925.525.50.21 12007285.940.60.0079.837.70.0072.134.40.2063.330.70.1153.627.00.10 6772.844.20.1065.540.70.0957.937.20.0948.933.30.0838.228.80.09 6260.447.20.0853.343.70.0845.139.60.0935.734.70.1129.729.70.23 14007293.144.00.0086.641.10.0078.537.60.1669.133.90.1258.529.80.11 6779.048.50.1171.545.00.1063.141.20.1053.637.20.0942.332.50.10 6265.752.40.0958.148.70.1049.644.40.1039.939.20.1333.633.60.25 CM5A/CM5B048 12007286.440.90.0079.237.40.0071.233.80.0062.029.90.1151.325.70.09 6772.343.50.1164.939.80.0956.535.80.0846.731.50.0736.027.10.09 6259.645.80.0851.541.60.0842.737.20.0934.232.80.1128.628.60.20 14007294.544.60.0086.840.90.0077.837.00.0068.033.00.1456.628.50.12 6779.147.80.1371.244.00.1262.139.80.1151.635.20.1039.830.30.11 6265.150.60.1056.946.50.1047.441.80.1138.337.20.1232.432.40.22 160072101.047.60.0093.143.90.0083.739.90.0073.135.60.1661.231.00.14 6784.951.60.1576.347.50.1467.043.30.1355.938.60.1243.233.40.13 6270.055.10.1261.550.90.1251.546.00.1342.441.60.1436.036.00.25

BF

3. Direct interpolation is permissible. Do not extrapolate. 4. SHC is based on 80°F db temperature of air entering coil. Below 80°F db, subtract (Correction Factor x CFM) from SHC. Above 80°F db, add (Correction Factor x CFM) to SHC 5. All data points are based on 10°F superheat leaving coil. SHC CORRECTION FACTOR BYPASS FACTORENTERING AIR DRY-BULB TEMPERATURE (°F) 7978777675Under 75 8182838485Over 85 Correction Factor 0.10 0.20 0.300.98 0.87 0.761.96 1.74 1.532.94 2.62 2.293.92 3.49 3.054.91 4.36 3.82Use formula shown below. Interpolation is permissible. Correction Factor = 1.09 x (1 – BF) x (db – 80)

CFM

— Cubic Ft per Minute

EWB

— Entering Wet Bulb (

F)

SHG

— Gross Sensible Capacity 1000 Btuh

TCG

— Gross Cooling Capacity 1000 Btuh

NOTES:

1. Contact manufacturer for cooling capacities at conditions other than shown in table. 2. Formulas:

sensible heat cap.

Leaving db = entering db —

1.09 x CFM

Leaving wb = wb corresponding to enthalpy of air leaving coil (h

4.5 x CFM

= enthalpy of air entering coil.

Show 11 more labels / short text on this page
— Bypass Factor · ° · ) · lwb · total capacity (Btuh) · h · lwb · = h · ewb · where h · ewb
Page 6 of the Bryant Air Conditioner Coil (CM5A) user manual — COIL STATIC PRESSURE DROP (IN. WC)
Page 6 · click to enlarge
Page 6

COIL STATIC PRESSURE DROP (IN. WC)

UNIT SIZEBULBAIR QUANTITY (CFM) 024WET DRY6007008009001000 0.11 0.090.14 0.120.19 0.150.23 0.190.27 0.22 036WET DRY10001100120013001400 0.22 0.190.28 0.230.32 0.270.37 0.310.42 0.36 042WET DRY11001200130014001500 0.24 0.200.28 0.240.32 0.290.38 0.330.43 0.39 048WET DRY12001300140015001600 0.30 0.270.35 0.290.40 0.330.45 0.380.51 0.43
Page 7 of the Bryant Air Conditioner Coil (CM5A) user manual — ACCESSORY USAGE
Page 7 · click to enlarge
Page 7

ACCESSORY USAGE

ACCESSORY KIT NO.USED WITH Evcon/Coleman/AirProNordyne/Miller/Intertherm Gas FurnacesElectric FurnacesGas FurnacesElectric Furnaces DGRT—A 7900DGRT—B DGAT3400 3400A 3500A8—EB—BMGHAMGBAMGBBMGHBE1EBE1EHFEBA FEBBFEH2 FEHB BLOWER PACKAGES KMABA01013TGX*X†——X——X†———— KMABA02014TGX*X‡——XX‡X‡X‡———— KMABA03013TE—————————X**—— KMABA04014TE—————————X**—— KMABA05013TE——X**———————X**X** KMABA06014TE——X**———————X**X** CONTROL BOXES KMACC02014WGX———XX—————— KMACC0401E14—————————X††—— KMACC0601FE4——————————X††X†† FILTER KIT KMAFK0101NFK————————XXXX INSULATION KITS KMAIK0101E1I————————XX—— COIL SHELF KIT KMACR0101CRI——XX————————

* Requires additional control box kit. † Only required on high static 3-ton applications. ‡ Only required on 3-1/2-ton and 4-ton applications. ** Blower package comes with necessary control box. Additional control box kit not required. †† Only required if using existing furnace blower. X—Indicates recommended use of product.

Page 8 of the Bryant Air Conditioner Coil (CM5A) user manual — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Page 8 · click to enlarge
Page 8

SERVICE TRAINING

  • Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
  • Unit Familiarization
  • Maintenance
  • Installation Overview
  • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-962-9212

[ ] Packaged Service Training [ ] Classroom Service Training

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

CancelsPDS CM5A.24.1

© 1997 Bryant Heating and Cooling Systems, 7310 W. Morris St., Indianapolis, IN 46231 PRINTED IN U.S.A. Catalog No. 12CM-5A1 5-97

Ask about the Bryant Air Conditioner Coil (CM5A)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant Air Conditioner Coil (CM5A)

Be the first to ask — other owners or our team will answer.

Original document

Bryant Air Conditioner Coil (CM5A) manual PDF

8 pages·128 KB·Blower·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…