Bryant BW3
Table of Contents 70 sections Gas and Oil-Fired Water and Gas Fired Steam Boilers · Form No. PDS BS1A.75.3 · MODEL NUMBER NOMENCLATURE · BW9AAN000075AAAA · … ShowHide
Page 1 of the Bryant BW3 user manual — Gas and Oil-Fired Water and Gas Fired Steam Boilers
Page 1 · click to enlarge
Page 1
Bryant BW3 — Gas and Oil-Fired Water and Gas Fired Steam Boilers diagram (page 1)
Fig. 1 · Gas and Oil-Fired Water and Gas Fired Steam Boilers

Gas and Oil-Fired Water and Gas Fired Steam Boilers

Form No. PDS BS1A.75.3

Page 2 of the Bryant BW3 user manual — BOILER ACCESSORIES
Page 2 · click to enlarge
Page 2

MODEL NUMBER NOMENCLATURE

BW9AAN000075AAAA

B W 9 A A N 000 075 A A AA

Variations AA — Standard

Type of System W — Water S i— Steam

Series A i— Original

Combustion/Ignition 1 — Natural Draft/Standing Pilot 2 — Natural Draft/Electronic 3 — Induced Draft/Electronic 4 — Oil Burner/Without Tankless Coil 5 — Oil Burner/With Tankless Coil 9 — 90% Direct Vent/Sealed Combustion

Labeling A — Common Unit G — Canada Only (oil)

Heating Size Btu Input (x 1000) Electrical A 110 to 125 60 Hz

Fuel H — Heating Oil N — Natural Gas P — Propane

BOILER ACCESSORIES

BW1/BW2 DESCRIPTIONPART NO. Filtrol Package (Up to 75,000 Btuh Input)KBAFP0101DNK Filtrol Package (Up to 150,000 Btuh Input)KBAFP0201DNK Filtrol Package (Over 150,000 Btuh Input)KBAFP0301DNK High Limit ControlKBAHL0101DNK Combustible Floor Base (2 thru 6 section models)KBASB0301DNK Combustible Floor Base (7 thru 9 section models)KBASB0401DNK Zoning Valve 3/4 in.KBAZV0101DNK Zoning Valve 1 in.KBAZV0201DNK Gas Conversion Kit Natural to Propane (After 1799V)KBANP0201DNK Gas Conversion Kit Propane to NaturalKBAPN0201DNK NOTE: There was never a Natural to Propane conversion kit for BW/BS boiler prior to 1799V. BW3 DESCRIPTIONPART NO. Filtrol Package (Up to 75,000 Btuh Input)KBAFP0101DNK Filtrol Package (Up to 150,000 Btuh Input)KBAFP0201DNK Filtrol Package (Over 150,000 Btuh Input)KBAFP0301DNK High Limit ControlKBAHL0101DNK Combustible Floor Base (2 thru 6 section models)KBASB0301DNK Combustible Floor Base (6 thru 7 section models)KBASB0401DNK Zoning Valve 3/4 in.KBAZV0101DNK Zoning Valve 1 in.KBAZV0201DNK Gas Conversion Kit Natural to Propane (After 1799V)KBANP0201DNK Gas Conversion Kit Propane to NaturalKBAPN0201DNK NOTE: There was never a Natural to Propane conversion kit for BW/BS boiler prior to 1799V. BS1/BS2 DESCRIPTIONPART NO. Combustible Floor Base (2 thru 6 section models)KBASB0301DNK

See notes on page 3.

B — Boiler · Model Code · Cooling

Page 3 of the Bryant BW3 user manual — BOILER ACCESSORIES (CONT.)
Page 3 · click to enlarge
Page 3

BOILER ACCESSORIES (CONT.)

Combustible Floor Base (6 thru 7 section models)KBASB0401DNK Gas Conversion Kit Natural to Propane (3 section, BS1/2-075)KBANP0301DNK Gas Conversion Kit Natural to Propane (4 section, BS1/2-112)KBANP0401DNK Gas Conversion Kit Natural to Propane (5 section, BS1/2-150)KBANP0501DNK Gas Conversion Kit Natural to Propane (6 section, BS1/2-187)KBANP0601DNK Gas Conversion Kit Natural to Propane (7 section, BS1/2-225)KBANP0701DNK Gas Conversion Kit Natural to Propane (8 section, BS1/2-262)KBANP0801DNK Gas Conversion Kit Natural to Propane (9 section, BS1/2-299)KBANP0901DNK NOTE: There was never a Natural to Propane conversion kit for BW/BS boilers prior to 1799V. BW4/BW5 DESCRIPTIONPART NO. Filtrol Package (Includes Air Purge Extrol Tank and Fill Valve)KBAFP0201DNK KBAFP0301DNK Zone Valve - 3/4 in.KBAZV0101DNK Zone Valve - 1 in.KBAZV0201DNK High-Limit Control - Manual Reset*KBAHL0101DNK Tankless Water Heater KitKBATH0101IDNK Combustible Floor BaseKBASB0301DNK Low Fire Rate Kit - 3 Section BW4/BW5KBALF0101DNK Low Fire Rate Kit - 4 Section BW4/BW5KBALF0201DNK BW9 DESCRIPTIONPART NO. Concentric Vent Termination Kit (Single Pipe) - 2 in.KGAVT0501CVT Concentric Vent Termination Kit (Single Pipe) - 3 in.KGAVT0601CVT Filtrol Package (Up to 75,000 Btuh Input)KBAFP0101DNK Filtrol Package (Up to 150,000 Btuh Input)KBAFP0201DNK Zoning Valve 3/4 in.KBAZV0101DNK Zoning Valve 1 in.KBAZV0201DNK Gas Conversion Kit Natural to Propane (BW9-050)KBANP1101DNK Gas Conversion Kit Natural to Propane (BW9-075)KBANP1201DNK Gas Conversion Kit Natural to Propane (BW9-100)KBANP1301DNK Gas Conversion Kit Propane to Natural (BW9-050)KBAPN1101DNK Gas Conversion Kit Propane to Natural (BW9-075)KBAPN1201DNK Gas Conversion Kit Propane to Natural (BW9-100)KBAPN1301DNK

* 2–6 Section Models on BS1, BS2, BW1, and BW2; 2–5 Section Models on BW3. † 7–9 Section Models on BS1, BS2, BW1, and BW2; 6–7 Section Models on BW3. Note: Accessory High Limit Control is a strap-on aquastat used as an auxiliary limit or reverse acting circulator control.

Page 4 of the Bryant BW3 user manual — CERTIFIED
Page 4 · click to enlarge
Page 4

CIRCULATOR CURVE

WATER FLOW M 3 /H

2 3 4 5

TOTAL HEAD METERS

TOTAL HEAD FEET

8 12 16 20 24

WATER FLOW GPM

WATER BOILER CIRCULATOR CURVE

ELECTRICAL DATA

ALL MODELS Voltage—Hertz—Phase115 — 60 — 1 Minimum Branch Circuit Wire Size (AWG)14 Maximum Fuse Size (Amps)15 Control Circuit Power Available40va–@ 24v STANDARD BOILER WARRANTIES (Yrs) MODELBW1BW2BW3BW4BW5BW9BS1BS2 Circulator Pump333333—— Vent Damper55————55 Heat Exchanger Section Assembly (Non-prorated)2020202020151212 Oil Burner———33———

CERTIFIED

ama

®

ASME

®

Page 5 of the Bryant BW3 user manual — PROPANE CONVERTIBLE
Page 5 · click to enlarge
Page 5

MODELS BW9

The BW9 is a gas fired direct vent condensing hot water boiler with cast aluminum heat exchanger sections. A revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boiler, which results in higher efficiency. The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing condensation. Sealed combustion, premix gas burner, and low flame temperature means drastically reduced CO and NOx emissions, which contribute to a cleaner and healthier environment.

The BW9, unlike normal residential atmospheric and induced draft boilers, takes its combustion air directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh air. Sealed combustion (also known as “direct vent”) is the safest and best way to obtain plenty of clean combustion air. The induced draft fan draws in the outside combustion air, then takes the cooler flue gases from the heat exchanger and provides a positive removal of the flue gases from the building through inexpensive and readily available PVC and CPVC pipes.

RANGE OF CAPACITIES

—Three sizes ranging from 50,000 through 100,000 Btuh input.

—Each boiler is completely assembled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas piping, room thermostat, and electrical power connections as shipped. Circulator is shipped pre-wired with 6 ft bx conduit for easy installation for supply side pumping.

VENTING

—This boiler is direct vented with PVC and CPVC pipe. See the Installation Instructions for common venting requirements.

ALUMINUM SECTIONS

—These sections speed heat transfer to the boiler water. With faster thermal response, greater comfort and economy are achieved.

PRE-MIX BURNER

—Provides quiet operation and improved combustion efficiency.

—Integrated Boiler Control provides safe, dependable operation of burners. Factory-installed safety components provide maximum safety against overheating, pressure buildup, and low-water operation.

—Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.

PROPANE CONVERTIBLE

—With factory approved conversion kit accessory.

—The aluminum sections are covered by a limited 15-year warranty on the entire assembly. Circulator pump is covered by a limited 3-year warranty. All other parts are covered by a 1-year limited warranty.

UNIT SIZE050075100 Sections1 GAS CONTROLS Gas ValveHoneywell Inlet Size In.1/2 IgnitionHot Surface Ignition Burner—Stainless/Titanium Alloy1 Burner Orifice No.0.0615#48#44 CONTROLS Limit Control Range °F100-200 Pressure Relief Valve Setting Psig30 Integrated Boiler ControlUTEC factory installed CIRCULATOR Taco Model007 Full Load Amps2.0 AMPS/330 WATTS Flange Size FPT In.1-1/4
Page 6 of the Bryant BW3 user manual — MODELS BW9
Page 6 · click to enlarge
Page 6
Bryant BW3 — MODELS BW9 diagram (page 6)
Fig. 2

ALTERNATE SUPPLY & RETURN OPENINGS (1-1/4" NPT (31.75mm) CONNECTIONS PROVIDED INSIDE BOILER CABINET)

JUNCTION BOX FOR 120 V POWER, 120 V CIRCULATOR BEADS, AND 24 V THERMOSTAT LEADS

ALTERNATE BOILER WATER SUPPLY AND RETURN (31.75mm) CONNECTIONS (1-1/4" NPT BOILER CABINET) PROVIDED INSIDE

STANDARD BOILER WATER SUPPLY & RETURN OPENINGS (1-1/4" NPT (31.75mm) CONNECTIONS PROVIDED INSIDE BOILER CABINET)

CLEARANCES UNITCOMBUSTIBLE (in.) ACCESSIBILITY/CLEANING (in.)SERVICING (in.) TOP188 LEFT SIDE12424 RIGHT SIDE8—— BASE1—— FRONT02424 BACK1—— INTAKE/VENT PIPING0—— NEAR BOILER HOT WATER PIPING1—— *Service clearance requirement 24-in.
UNITGAS M TYPEAX INPUT HEATING (BTUH) CAPACITY (BTUH)AFUE %NET RATING Btuh†BOILER WATER CAPACITY (GALLONS)APPROX SHIP. WT (Lb) BW9AAN050Natural50,000 45,0009039,0002.6220 BW9AAN075Natural75,000 68,0009059,0002.6220 BW9AAN100Natural 100,000 90,0009078,0002.6220
Bryant BW3 — MODELS BW9 diagram (page 6)
Fig. 3

Gas input ratings are for elevations up to 2000 ft. In the USA, for elevations above 2000 ft., reduce input per the charts supplied in the high altitude derate kits. In Canada, boilers may be used at high altitude by using a certified field conversion kit.

*

Page 7 of the Bryant BW3 user manual — INTERGRAL DRAFT
Page 7 · click to enlarge
Page 7

MODELS BS1 and BS2

Models BS1 and BS2 Gas-Fired Steam Boilers provide fast heat quietly and economically to assure the finest in hydronic heating. These boilers provide quality design in a small, compact unit easily installed in a basement, garage, or utility room. They can be installed on a combustible floor when an optional combustible floor base is used. The model BS1 and BS2 design is CSA and A.G.A. certified for use with natural and is convertible to propane gas with accessory kit.

RANGE OF CAPACITIES

—Sizes 75,000 through 299,000 Btuh input are available.

—Each boiler is completely assem- bled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas, water, room thermostat, and electrical connections as shipped.

THERMAL-PIN, CAST-IRON SECTIONS

—These sections speed heat transfer from the flue gases to the boiler water, with faster ther- mostat response, providing greater comfort and economy. Max- imum heat is produced at a lower level on the thermal-pin sections, leading to peak efficiency.

TITANIUM COMPOSITE BURNERS

—Provide quiet operation, corrosion resistance and improved combustion efficiency. Propane convertible – with accessory kit.

—An automatic gas valve and continuous pilot or intermittent pilot provide quiet, dependable operation of the burners. Factory-installed safety components assure protection against overheating, pressure buildup, and low-water operation.

INSULATED CASING

—The casing is fully insulated with fiber- glass for maximum operating efficiency and economy.

AUTOMATIC VENT DAMPER

—The Model BS1 and BS2 is designed with automatic vent damper to recover chimney loss during off cycle.

—Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. Maximum allowable working pressure is 50 psig. The maximum allowable pressure is 15 psig for steam boilers.

INTERGRAL DRAFT

—These boilers incorporate an integral draft system to simplify installation. No external draft diverter is needed.

—The cast-iron sections are covered by a non- prorated 12-year warranty on the entire assembly. Vent damper covered by 5-year warranty. All other parts are covered by a 1-year limited warranty.

Bryant BW3 — INTERGRAL DRAFT diagram (page 7)
Fig. 4
UNIT SIZE075112150187225262299 GENERAL DATA Sections—Fine Grain Cast Iron No.3456789 Burners—Stainless/Titanium Alloy No.2345678 Burners—Orifice Drill Size Natural34343434343434 GAS CONTROLS — STANDING PILOT (BS1) Gas ValveHoneywell Inlet Size In.1/2 FPT3/4 FPT Pilot AssemblyHoneywell GAS CONTROLS — INTERMITTENT PILOT (BS2) Gas ValveHoneywell Inlet Size In.1/2 FPT3/4 FPT Pilot AssemblyHoneywell Spark GeneratorHoneywell/UTEC CONTROLS Low-Water CutoffMcDonnell Miller Pressuretrol Psig0—15 Pressure Relief Valve Setting15 Psig Capacity400 lb/hr Pressure Retard Gage Range Psig0–30 Drain Cock In.3/4 Vent Damper* In.567

Factory authorized and listed, field installed.

*

Page 8 of the Bryant BW3 user manual — *
Page 8 · click to enlarge
Page 8
DIMENSIONS MODELS BS1 and BS2 VENT DAMPER PRESSURE GAGE 26 1⁄2″ RELIEF VALVE 4 3⁄4″ 2 1⁄2″ TRANSFORMER GLASS PRESSURE GAGE LIMIT CONTROL WATER 2 1⁄2″ N.P.T. LOW WATER LINE CUT-OFF 29″ 36 3⁄8″ L CO UW OW FA FT E PR 2 1⁄2″ 24″ TROBE S86 12 1⁄4″ GAS VALVE GAS LINE A LEFT SIDE FRONT RIGHT SIDE DIMENSIONS (In.) CLEARANCES (In.) UNIT SIZE A VENT DIAMETER RIGHT SIDE 6* 075 11-1/4 5 LEFT SIDE 6* 112 14-1/2 6 TOP 6* 150 17-3/4 6 BACK 6* 187 21 7 FRONT 6* 225 24-1/4 7 * Service clearance requirement 24 in. 262 27-1/2 7 299 30-3/4 7 DIMENSIONS (In.)CLEARANCES (In.) UNIT SIZEAVENT DIAMETERRIGHT SIDE6* 07511-1/45LEFT SIDE6* 11214-1/26TOP6* 15017-3/46BACK6* 187217FRONT6* 22524-1/47* Service clearance requirement 24 in. 26227-1/27 29930-3/47

*

UNITGAS TYPENUMBER OF SECTIONSMAX INPUT (BTUH)HEATING CAPACITY (BTUH)NET RATINGAFUE % (WITH DAMPER)APPROX SHIP. WT (Lb) BtuhSq Ft BS1AAN075Natural375,00062,00047,00019681.1256 BS1AAN112Natural4112,50091,00068,00028378.8404 BS1AAN150Natural5150,000122,00092,00038379.2483 BS1AAN187Natural6187,500153,000115,00047979.6564 BS1AAN225Natural7225,000183,000137,00057180.1649 BS1AAN262Natural8262,500214,000161,00067180.5719 BS1AAN299Natural9299,000245,000184,00076780.9800 BS2AAN075Natural375,00062,00047,00019682.7256 BS2AAN112Natural4112,50091,00068,00028380.4404 BS2AAN150Natural5150,000122,00092,00038380.6483 BS2AAN187Natural6187,500153,000115,00047980.9564 BS2AAN225Natural7225,000183,000137,00057581.1649 BS2AAN262Natural8262,500214,000161,00067181.3719 BS2AAN299Natural9299,000245,000184,00076781.6800

Ratings are for altitudes to 2000 ft. Ratings for units for altitudes over 2000 ft are 4% less for each 1000 ft above sea level. Ratings in sq ft are computed at 240 Btuh/sq ft for steam boilers.

*

Page 9 of the Bryant BW3 user manual — AUTOMATIC VENT DAMPER
Page 9 · click to enlarge
Page 9

MODELS BW1 and BW2

Models BW1 and BW2 Gas-Fired Hot Water Boilers provide fast heat quietly and economically to assure the finest in hydronic heating. These boilers provide quality design in a small, compact unit easily installed in a basement, garage, or utility room. They can be installed on a combustible floor when an optional combustible floor base is used. The models BW1 and BW2 design is CSA and A.G.A. certified for use with natural and is convertible to propane gas with accessory kit.

RANGE OF CAPACITIES

—Sizes 37,500 through 280,000 Btuh are available.

—Each boiler is completely assembled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas, water, room thermostat, and electrical connections as shipped.

THERMAL-PIN, CAST-IRON SECTIONS

—These sections speed heat transfer from the flue gases to the boiler water with faster thermostat response, providing greater comfort and economy. Maximum heat is produced at a lower level on the thermal-pin sections, leading to peak efficiency.

INTEGRAL DRAFT

—These boilers incorporate an integral draft sys- tem to simplify installation. No external draft diverter is needed.

TITANIUM COMPOSITE BURNERS

—Provide quiet operation, corrosion resistance and improved combustion efficiency. Propane convertible – with accessory kit.

—An automatic gas valve and continuous pilot or inter- mittent pilot provide quiet, dependable operation of the burners. Factory-installed safety components assure protection against overheating, pressure buildup, and low-water operation.

INSULATED CASING

—The casing is fully insulated with fiberglass for maximum operating efficiency and economy.

AUTOMATIC VENT DAMPER

The Model BS1 and BS2 is designed with automatic vent damper to recover chimney loss during off cycle

Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.

—The cast-iron sections are covered by a non-prorated 20-year warranty on the entire assembly. Vent damper covered by 5- year warranty. Circulator pump covered by 3-year warranty. All other parts are covered by a 1-year limited warranty.

Bryant BW3 — AUTOMATIC VENT DAMPER diagram (page 9)
Fig. 5

Burners—Stainless/Titanium Alloy No. 1 2 3 4 5 6 7 8 Burners—Orifice Drill Size Natural 34

Full Load Amps 0.70 Flange Size FPT In. 1-1/4

Factory authorized and listed, field installed. † A 4-in. vent damper is supplied. A 4-in. to 3-in. reducer is also furnished.

*

Page 10 of the Bryant BW3 user manual — *
Page 10 · click to enlarge
Page 10
Bryant BW3 — MODELS BW1 and BW2 diagram (page 10)
Fig. 6 · MODELS BW1 and BW2

1 1⁄4″ RETURN 1 1⁄4″ NPT

DIMENSIONS (In.) UNIT SIZEAVENT CONNECTION 03783 07011-1/45 10514-1/26 14017-3/46 175217 21024-1/47 24527-1/27 28030-3/47
CLEARANCES (In.) RIGHT SIDE6 (2-5 Section)* 24 (6-9 Section)* LEFT SIDE6 (2-5 Section) 24 (6-9 Section) TOP6 BACK6 FRONT6* * Service clearance requirement 24 in.

*

BW1, BW2GAS TYPENUMBER OF SECTIONSMAX INPUT (BTUH)HEATING CAPACITY (BTUH)NET RATING (BTUH)AFUE % BW1 BW2APPROX SHIP. WT (Lb) BW2 AAN037Natural237,50030,00026,00080.081.4227 AAN070Natural370,00057,00050,00080.481.6285 AAN105Natural4105,00085,00074,00080.481.5350 AAN140Natural5140,000113,00098,00080.381.3421 AAN175Natural6175,000142,000124,00080.281.1488 AAN210Natural7210,000170,000148,00080.181.0564 AAN245Natural8245,000198,000172,00080.081.6626 AAN280Natural9280,000226,000197,00080.080.7689
Bryant BW3 — * diagram (page 10)
Fig. 7

Ratings are for altitudes to 2000 ft. Unit ratings for altitudes over 2000 ft are 4% less for each 1000 ft above sea level.

*

Page 11 of the Bryant BW3 user manual — UNIT CONVERTIBLE
Page 11 · click to enlarge
Page 11

MODEL BW3

Model BW3 Gas-Fired Induced-Combustion Water Boilers are the answer to energy-efficient residential hydronic heating. They provide fast, almost instant, heat quietly and economically. These boilers provide quality design in a small, compact unit easily installed in a basement, garage, or utility room. They can be installed on a combustible floor when an optional combustible floor kit is used. The design of model BW3N is CSA and A.G.A. certified for use with natural gas and is convertible to propane gas with accessory kit.

FEATURES RANGE OF CAPACITIES

—Six sizes ranging from 42,500 through 225,000 Btuh input.

—Each boiler is completely assembled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas, water, room thermostat, and electrical power connections as shipped.

VENTING

—This boiler can be vented into any approved chimney or Type B-1 vent. Common-venting with an existing water heater is acceptable in vertical vent systems. See the Installation Instructions for common venting requirements. The induced-combustion design also eliminates the need for a vent damper.

THERMAL-PIN CAST-IRON SECTIONS

—These sections speed heat transfer from the flue gases to the boiler water, with faster ther- mostat response, providing greater comfort and economy.

TITANIUM COMPOSITE BURNERS

—Provide quiet operation, corrosion resistance, and improved combustion efficiency. Propane convertible with accessory kit.

—An automatic gas valve and intermittent pilot provide quiet, dependable operation of the burners. Factory-installed safety components provide maximum safety against overheating, pressure buildup, and low-water operation.

INSULATED CASING

—Fully insulated with fiberglass for maximum operating efficiency and economy.

Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.

UNIT CONVERTIBLE

—The Boiler is listed for power venting with field controls power venting kit.

—The cast-iron sections are covered by a non-prorated 20-year warranty on the entire assembly. Circulator pump covered by 3-year warranty. All other parts are covered by a 1-year limited warranty.

UNIT SIZE042075112150187225 Sections—Fine Grain Cast-Iron No. 234567 GAS CONTROLS — INTERMITTENT PILOT Gas ValveHoneywell Inlet Size In. 1/2 FPT Pilot AssemblyHoneywell Spark GeneratorHoneywell Burners—Stainless/Titanium Alloy No. 123456 Burner Orifice—Drill Size Natural 323434343434 CONTROLS Limit Control Range °F 180–240 Pressure/Temperature Gage Psi °g 0–60 F 60–260 Pressure Relief Valve Setting Psig 30 Circulator Relay—AquastatHoneywell (Factory Installed) CIRCULATOR Taco Model 007 Full Load Amps0.70 Flange Size FPT In. 1-1/4
Bryant BW3 — UNIT CONVERTIBLE diagram (page 11)
Fig. 8
Page 12 of the Bryant BW3 user manual — *
Page 12 · click to enlarge
Page 12
Bryant BW3 — MODEL BW3 diagram (page 12)
Fig. 9

5 5⁄8″ 5 5⁄8″

UNIT SIZEA 04211 07514-1/4 11217-1/2 15020-3/4 18724 22527-1/4

*

UNITGAS TYPEMAX INPUT (BTUH)RATINGS HEATING CAPACITY‡N AFUE %ET RATINGBOILER WATER CAPACITY (GALLONS)APPROX SHIP. WT (Lb) BtuhBtuh† BW3AAN042Natural42,50036,00084.431,0001.75211 BW3AAN075Natural75,00063,00083.455,0003.00263 BW3AAN112Natural112,50094,00083.082,0004.25320 BW3AAN150Natural150,000125,00082.7109,0005.50369 BW3AAN187Natural187,500155,00082.3135,0006.75418
Bryant BW3 — * diagram (page 12)
Fig. 10

Gas input ratings are for elevations up to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. † Selection factors providing for piping loss and starting load are those recommended by the Institute of Boiler and Radiator Manufacturers. Net water boiler

ratings are based on an allowance of 1.15. ‡ In accordance with U.S. Government test procedures.

*

Page 13 of the Bryant BW3 user manual — OIL BURNER
Page 13 · click to enlarge
Page 13

MODELS BW4 and BW5

The modern design and attractive appearance of the models BW4 and BW5 Oil-Fired Water Boilers make them ideal for installation in any area. The boilers are shipped fully assembled and wired, including all controls (except barometric draft regulator). The compact 22-gage steel cabinet has a baked-on enamel paint finish for durability. A 1-in. layer of thermal insulation is applied inside the jacket for protection and thermal efficiency. The flame retention head burner

provides efficient fuel usage. A wet base cast iron block with thermal pins surrounds the combustion area for better heat transfer from flue gases to water.

BAROMETRIC DRAFT CONTROL

—The factory supplied barometric draft control can easily be installed in the vent pipe for optimum draft and combustion efficiency.

—Factory-wired controls on units with tankless hot water coil include a triple aquastat relay with high/low limit protection and circulator control.

COMBINATION TRANSFORMER AQUASTAT

—A 24-v transformer is combined with the aquastat assembly. The transformer will supply power efficient to power a 3-zone system on BW5 models. Factory installed combination pressure/ temperature gage and a pressure relief valve.

COIL OPTIONS

—Units are available with or without tankless heater coil. The coil provides a supply of hot water for normal domestic purposes or an accessory tankless heater coil can be added later.

FACTORY INSTALLED FEATURES

—A factory-installed drain is provided should the boiler ever need to be drained. Oil primary control prevents boiler in operation in the event of flame loss.

—Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.

EASE OF INSTALLATION

—Circulator is shipped pre-wired with 6 ft bx conduit for easy installation for supply side pumping.

—The cast-iron sections are covered by a non- prorated 20-year warranty on the entire assembly. Oil burner and circulator pump covered by 3-year warranty. All other parts are covered by a 1-year limited warranty.

SOLENOID OIL VALVE

—This provides cleaner burning and quieter operation. Valve is included on all burner types.

SWING BURNER DOOR

—This unique design offers uninhibited access for set-ups, service, and maintaining the burner. Routine cleaning is also much easier.

GENERAL DATA

Water Capacity Gal 9.6 11.6 13.7

Combustion Chamber Target Wall Ceramic Fiber

OIL BURNER

Type Manufacturer/Model Beckett/Model AFG Flame Retention Head Burner

Oil Pump Single Stage

Fuel Type No. 1 or 2 Fuel Oil Rated Load Amps 3 Amps

Combination Control Without Heater High Limit, Circulator Relay, & Cad. Cell Relay

With Heater High & Low Limit, Circulator Relay, & Cad. Cell Relay

Pressure/Temperature Gage Psig 0–60

F 60–260 ASME Pressure Relief Valve Psig 30

Full Load Amps 0.70 Flange Size FPT In. 1-1/4

Draft Regulator Furnished · °

Page 14 of the Bryant BW3 user manual — WITH TANKLESS
Page 14 · click to enlarge
Page 14

MODELS BW4 and BW5

GAGE

1 1 ⁄ 4 ″ SUPPLY

C B

CONTROL

1 1 ⁄ 4 ″ RETURN

TANKLESS HEATER 1⁄2″ N.P.T.

3 ⁄ 4 ″ ASME RELIEF

VALVE

FRONT SIDE REAR

UNIT SIZE A B C

140 17-3/4 6 9-3/4

210 21 6 11-3/8

280 24-1/4 6 13

FLUE 18 *

* Clearance 18 in. for BW5. † Service clearance requirement 24 in.

RATINGS AND PERFORMANCE

**HEATING CA-

NET I=B=R RATING

FIRING

INPUT

PACITY

RATE +GPH A.F.U.E. ++

MINIMUM CHIMNEY

BOILER MODEL NO. NO. SEC.

*MBH

*MBH

*MBH

SIZE/ HEIGHT DIMENSIONS - IN.

WITH TANKLESS

WITHOUT TANKLESS

COIL

COIL A B C

BW5BAH091 BW4BAH091 3 91 80 70 0.65 86.3 8-in. x 8-in. x 15 ft 14-1/2 6 8

BW5BAH105 BW4BAH105 3 105 92 80 0.75 85.2 8-in. x 8-in. x 15 ft 14-1/2 6 8

BW5BAH140 BW4BAH140 3 140 119 103 1 83.4 8-in. x 8-in. x 15 ft 14-1/2 6 8

BW5BAH126 BW4BAH126 4 126 111 97 0.9 86.0 8-in. x 8-in. x 15 ft 17-3/4 6 9-5/8

BW5BAH175 BW4BAH175 4 175 150 130 1.25 83.9 8-in. x 8-in. x 15 ft 17-3/4 6 9-5/8

BW5BAH210 BW4BAH210 4 210 178 155 1.5 82.4 8-in. x 8-in. x 15 ft 17-3/4 6 9-5/8

BW5BAH168 BW4BAH168 5 168 147 128 1.2 86.5 8-in. x 8-in. x 15 ft 21 6 11-1/2

BW5BAH245 BW4BAH245 5 245 209 182 1.75 83.6 8-in. x 8-in. x 15 ft 21 6 11-1/2

BW5BAH280 BW4BAH280 5 280 236 205 2 82.0 8-in. x 8-in. x 20 ft 21 6 11-1/2

* MBH = 1,000 BTU per hour / BTU = British Thermal Unit. ** Heating Capacity is based on a 13 percent C02 with a –0.02 in. wc and a #1 smoke or less. Testing was done in accordance with the D.O.E. (Department of Energy) test procedure. +GPH = Gallons per hour oil at 140,000 BTU per gallon. ++A.F.U.E. = Annual Fuel Utilization Efficiency based upon D.O.E. test procedure. As an Energy Star Partner, the manufacturer has determined that this product meets Energy Star guidelines for Energy Efficiency.

36″ · 9″

Page 15 of the Bryant BW3 user manual — GAGE
Page 15 · click to enlarge
Page 15
Page 15 of the Bryant BW3 user manual — GAGE
Page 16 of the Bryant BW3 user manual — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Page 16 · click to enlarge
Page 16

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

CancelsPDS BSIA.75.2

© 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A Catalog No. 12BS-1A1 3-01

Ask about the Bryant BW3

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant BW3

Be the first to ask — other owners or our team will answer.

Original document

Bryant BW3 manual PDF

16 pages·358 KB·Boiler·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…