EN
Bryant logo
Official user manual

Bryant 698B

16 pages·328 KB·Heat Pump·PDF·ENDEFRITNLJA
Bryant 698B
Table of Contents 80 sections OUTDOOR WALL INDOOR WALL · LIQUID TUBE · JOIST · INSULATION · … ShowHide
OUTDOOR WALL INDOOR WALLp.2LIQUID TUBEp.2JOISTp.2INSULATIONp.2VAPOR TUBEp.2(2) PLACES IN BASEPANp.2MINIMUM MOUNTING PADp.2TIEDOWN KNOCKOUTp.2LOCATIONSp.2UNIT SIZEp.2DIMENSIONSp.2INSTALLATIONp.2I. CHECK EQUIPMENT AND JOB SITEp.2A. UNPACK UNITp.2B. INSPECT EQUIPMENTp.2II. INSTALL ON A SOLID, LEVEL MOUNTING PADp.2IV. OPERATING AMBIENTp.2V. ELEVATE UNITp.2COILp.3SENSING BULBp.3EQUALIZER TUBEp.3THERMOSTATIC EXPANSION VALVEp.3VI. CHECK INDOOR EXPANSION DEVICEp.3A. FURNACE COILSp.3PROCEDURE 1—INSTALLING TXV IN PLACE OF PISTONp.3INLETp.4E BULB INSULATIONp.4TAPE Cp.4TABLE 1—REFRIGERANT CONNECTIONS ANDp.4RECOMMENDED LIQUID AND VAPOR TUBEp.4DIAMETERS (IN.)p.4UNIT LIQUID VAPOR VAPOR (LONG-LINE)p.4VII. MAKE PIPING CONNECTIONSp.4A. OUTDOOR UNIT CONNECTED TO FACTORYAPPROVED INDOOR UNITp.4B. INSTALL ADAPTER TUBEp.4TABLE 2—ACCESSORY USAGEp.5REQUIRED FOR LONG-LINEp.5REQUIRED FOR SEA-COASTp.5ACCESSORYp.5APPLICATIONS *p.5(OVER 50 FT)p.5C. REFRIGERANT TUBING AND FILTER DRIERp.5TABLE 3—REQUIRED LIQUID-LINE TEMPERATURE (°F)p.5LIQUID PRESSURE ATp.5REQUIRED SUBCOOLING TEMPERATUREp.5SERVICE VALVEp.5(PSIG)p.5E. LEAK CHECKINGp.5STRAPp.5SUCTIONp.5TUBEp.58 O'CLOCK 4 O'CLOCKp.5MICRONSp.6DEEP VACUUM METHODp.6TRIPLE EVACUATION METHODp.6G. FINAL TUBING CHECKp.6CONTACTORp.7FIELD POWERp.7WIRINGp.7FIELD GROUNDp.7WIRING GROUND LUGp.7B. CONNECT GROUND AND POWER WIRESp.7C. CONNECT CONTROL WIRINGp.7IX. INSTALL ELECTRICAL ACCESSORIESp.7X. MAKE AIRFLOW SELECTIONSp.7PROGRAMMABLEp.8FV4 FK4 FAN COILp.8THERMIDISTATp.8THERMOSTATp.8TWO-SPEEDp.8CONTROL MODEL RHp.8SINGLE-STAGEp.8MODEL 2Sp.8HEAT PUMPp.8FURNACEp.8NON-PROGRAMMABLEp.8DUAL FUEL THERMOSTATp.8MODEL DFp.8TWO-STAGEp.8FV4/FK4 FAN COILp.8
Page 1 of the Bryant 698B user manual — installation and start-up instructions TWO-SPEED PURON® PLUS HEAT PUMP WITH PURON® REFRIGERANT
Page 1 · click to enlarge
Page 1

installation and start-up instructions TWO-SPEED PURON® PLUS HEAT PUMP WITH PURON® REFRIGERANT

Bryant 698B — installation and start-up instructions TWO-SPEED PURON® PLUS HEAT PUMP WITH PURON® REFRIGERANT diagram (page 1)
Fig. 1 · installation and start-up instructions TWO-SPEED PUR…
CancelsII 698B-24-3 II 698B-24-4
Bryant 698B — installation and start-up instructions TWO-SPEED PURON® PLUS HEAT PUMP WITH PURON® REFRIGERANT diagram (page 1)
Fig. 2 · installation and start-up instructions TWO-SPEED PUR…

SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Fig. 1—Model 698B

4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.)
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)

10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation. When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion, check refrigerant charge using charging information located on control box cover or in the Check Charge section of this instruction. IMPORTANT: Maximum liquid-line size is 3/8–in O.D. for all residential applications.

INSTALLATION RECOMMENDATIONS NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit. 3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
Page 2 of the Bryant 698B user manual — V. ELEVATE UNIT
Page 2 · click to enlarge
Page 2

Avoid contact between tubing and structure NOTE:

Bryant 698B — OUTDOOR WALL INDOOR WALL diagram (page 2)
Fig. 3

OUTDOOR WALL INDOOR WALL

Bryant 698B — OUTDOOR WALL INDOOR WALL diagram (page 2)
Fig. 4

LIQUID TUBE

JOIST

INSULATION

VAPOR TUBE

8 3⁄16″ 3⁄8 IN. DIA TIEDOWN KNOCKOUTS

(2) PLACES IN BASEPAN

LIQUID TUBE

MINIMUM MOUNTING PAD

TIEDOWN KNOCKOUT

LOCATIONS

UNIT SIZE

DIMENSIONS

Support Feet Snow Stand A B 024 19 X 24 26 X 32 2-13/16 6-15/16 036-060 26 X 32 31 X 35 4 9-3/4

Fig. 2—Connecting Tubing Installation

INSTALLATION

Fig. 3—Mounting Unit to Pad

I. CHECK EQUIPMENT AND JOB SITE

A. UNPACK UNIT

Bryant 698B — I. CHECK EQUIPMENT AND JOB SITE diagram (page 2)
Fig. 5

Move to final location. Remove carton, taking care not to damage unit.

B. INSPECT EQUIPMENT

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit.

II. INSTALL ON A SOLID, LEVEL MOUNTING PAD

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location. On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Fig. 4—Accessory Support Feet

IV. OPERATING AMBIENT

Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Application Guideline and Service Manual for Residential Split System Air Conditioners and Heat Pumps using Puron® Refrigerant for wind baffle construction NOTE: Unit must be level to within ±2° (±3/8 in./ft) per compressor manufacturer specifications.

The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is 125°F.

V. ELEVATE UNIT

III. CLEARANCE REQUIREMENTS When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit. On rooftop applications, locate unit at least 6 in. above roof surface.

Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of the unit. Fig. 4 shows unit with accessory support feet installed. Use accessory snow stand in areas where prolonged freezing temperatures are encountered. Refer to separate Installa- tion Instructions packaged with accessories.

Page 3 of the Bryant 698B user manual — PROCEDURE 1—INSTALLING TXV IN PLACE OF PISTON
Page 3 · click to enlarge
Page 3
8. Install vapor elbow (See Fig. 6B) with equalizer adapter to suction tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male flare connector for attaching equalizer tube.

COIL

9. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter.

SENSING BULB

EQUALIZER TUBE

10. Attach TXV bulb to horizontal section of suction line using bulb strap provided. (See Fig. 6C.) Insulate bulb with factory-supplied insulation tape. (See Fig. 6E.) See Fig. 7 for correct positioning of sensing bulb.
11. Proceed with remainder of unit installation.

THERMOSTATIC EXPANSION VALVE

B. FAN COILS Indoor unit (fan coil) comes factory equipped with a bi-flow shut-off TXV specifically designed for Puron® two-speed. No TXV changeout is required. PROCEDURE 2—REPLACING R-22 TXV OR NON-BALANCE PORT PURON® TXV

Fig. 5—TXV Installed

VI. CHECK INDOOR EXPANSION DEVICE

1. Remove any existing refrigerant and ensure coil has not been exposed to atmospheric pressure for more than 15 minutes.
2. Remove coil access panel and fitting door from cabinet.
3. Remove and save TXV support clamp using a 5/16-in nut driver.

A. FURNACE COILS

4. Remove TXV using a backup wrench on flare connections to prevent damage to tubing.

Puron® furnace coils come factory equipped with bi-flow, hard shutoff TXV s specifically designed for Puron® two-speed units. No changeout is required. Remove existing Check-Flo-Rater™piston from indoor coil and install field accessory TXV. Install TXV kit to indoor coil as follows: IMPORTANT: The TXV should be mounted as close to the indoor coil as possible and in a vertical, upright position. Avoid mounting the inlet tube vertically down. Valve is more susceptible to malfunction due to debris if inlet tube is facing down. A factory-approved filter drier must be installed in the liquid line.

5. Using wire cutters, cut equalizer tube off flush with vapor tube inside cabinet.
6. Remove bulb from vapor tube inside cabinet.
7. Braze equalizer stub-tube closed. Use protective barrier as necessary to prevent damage to drain pan.
8. Install TXV (Fig. 6A) with 3/8-in. copper inlet tube through small hole in service panel. Use wrench and backup wrench, to avoid damage to tubing valve.

PROCEDURE 1—INSTALLING TXV IN PLACE OF PISTON

9. Reinstall TXV support clamp (removed in item 3).
1. Ensure coil has not been exposed to atmospheric pressure for more than 15 minutes. 2. Remove indoor coil inlet tube at piston body inlet. Use back-up wrench to prevent damage. 3. Remove piston retainer, being careful not to damage sealing surface of O-ring. 4. Remove and discard factory-installed piston. Replace retainer if O-ring is damaged. NOTE: If the piston is not removed from the body, TXV will not function properly.
10. Attach TXV bulb to vapor tube inside cabinet in same location as original was removed using supplied bulb straps. (See Fig. 6C.) Insulate bulb with factory-supplied insulation tape. (See Fig. 6E.) See Fig. 7 for correct positioning of sensing bulb.
11. Route equalizer tube through suction connection opening (large hole) in fitting panel and install fitting panel in place.
12. Sweat inlet of TXV, marked “IN,” to liquid line. Avoid excessive heat which could damage valve.
13. Install vapor elbow (See Fig. 6B) with equalizer adapter to vapor line of line set and vapor connection to indoor coil. Adapter has a 1/4-in. male flare connector for attaching equalizer tube. (See Fig. 6B.)
5. Reinstall piston retainer in piston body. 6. Replace indoor coil inlet tube. Use back-up wrench to prevent damage.
14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter. Use backup wrench to prevent damage to equalizer fitting.
15. Proceed with remainder of unit installation.
7. Sweat swivel adapter (See Fig. 6D) to inlet of indoor coil and attach to TXV (See Fig. 6A) outlet. Use backup wrench to avoid damage to tubing or valve. Sweat inlet of TXV, marked “IN,” to liquid line. Avoid excessive heat which could damage valve.

C. Long-Line Applications, Install Liquid-Line Solenoid Valve (LSV) For refrigerant piping arrangements with equivalent lengths greater than 50 ft or when elevation difference between indoor and/or outdoor unit is greater than ± 20 ft, follow all requirements

Page 4 of the Bryant 698B user manual — B. INSTALL ADAPTER TUBE
Page 4 · click to enlarge
Page 4

INLET

D

COIL

E BULB INSULATION

TAPE C

Fig. 6—TXV Kit Contents

of the Long-Line Guideline section in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant. If required by Long-Line Application Guideline, install LSV kit Part No. KHALS0401LLS specifically designed for Puron® Heat Pumps. LSV should be installed between filter drier and indoor coil as close as possible to filter drier. Follow the Installation Instructions included with accessory kit.

TABLE 1—REFRIGERANT CONNECTIONS AND

RECOMMENDED LIQUID AND VAPOR TUBE

DIAMETERS (IN.)

UNIT LIQUID VAPOR VAPOR (LONG-LINE)

Tube Diameter 024 3/8 3/8 5/8 5/8 5/8 3/4 036 3/8 3/8 3/4 3/4 3/4 7/8 048 3/8 3/8 7/8 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8

VII. MAKE PIPING CONNECTIONS

moisture in the system. Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Al- ways keep ends of tubing sealed during installation.

A. OUTDOOR UNIT CONNECTED TO FACTORYAPPROVED INDOOR UNIT

These outdoor units are carefully evaluated and listed with specific indoor coils for proper system performance. IMPORTANT: Do not apply indoor coils which are not factory approved to these units. IMPORTANT: For 036 size units matched with the FV/FK005 or FV/FK006 and the 698BNX048 matched with the FV/FK006, a piston change is required. Refer to the KHAPX0201BPA Instal- lation Instructions for details.

B. INSTALL ADAPTER TUBE

1. Remove plastic retainer holding outdoor piston in liquid service valve.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50 ft For tubing requirements beyond 50 ft, substantial capacity and performance losses can occur. Follow the recommendations in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant to minimize losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

2. Check to be sure outdoor piston is properly installed in liquid service valve.
3. Locate plastic bag taped to unit containing adapter tube.
4. Remove Teflon washer from bag and install on open end of liquid service valve. (See Fig. 8.)
5. Remove adapter tube from bag and connect threaded nut to liquid service valve. Tighten nut finger tight and then with wrench an additional 1/2 turn (15 ft-lb). DO NOT OVER TIGHTEN!

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and

Show 8 more labels / short text on this page
SIZE Connection · Tube Diameter · Connection · Tube Diameter · Connection · Diameter · Diameter · Diameter
Page 5 of the Bryant 698B user manual — SENSING BULB
Page 5 · click to enlarge
Page 5

TABLE 2—ACCESSORY USAGE

REQUIRED FOR LONG-LINE

REQUIRED FOR SEA-COAST

ACCESSORY

APPLICATIONS *

APPLICATIONS *

(WITHIN 2 MILES) Coastal Filter No Yes Support Feet No Recommended Puron® Hard Shutoff TXV Yes† Yes† Puron® Liquid-Line Solenoid Valve for Heating LHALS0401LLS No

(OVER 50 FT)

* For tubing line sets between 50 and 175 ft, or more than 20 ft vertical differential refer to Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron® Refrigerant. † Required for all applications.

C. REFRIGERANT TUBING AND FILTER DRIER

TABLE 3—REQUIRED LIQUID-LINE TEMPERATURE (°F)

Connect vapor tubing to fittings on outdoor unit vapor service valve. Connect liquid tubing to filter drier. (See Table 1 and Fig. 9.) Use refrigerant grade tubing. Connect other end of filter drier to adapter tube on liquid service valve. D. SWEAT CONNECTION

LIQUID PRESSURE AT

REQUIRED SUBCOOLING TEMPERATURE

SERVICE VALVE

(°F) 5 10 15 20 174 56 51 46 41 181 58 53 48 43 188 61 56 51 46 195 63 58 53 48 202 65 60 55 50 209 67 62 57 52 216 69 64 59 54 223 71 66 61 56 230 73 68 63 58 237 75 70 65 60 244 77 72 67 62 251 79 74 69 64 258 81 76 71 66 265 82 77 72 67 272 84 79 74 69 279 86 81 76 71 286 88 86 78 73 293 89 84 79 74 300 91 86 81 76 307 93 88 83 78 314 94 89 84 79 321 96 91 86 81 328 97 92 87 82 335 99 94 89 84 342 100 95 90 85 349 102 97 92 87 356 103 98 93 88 363 105 100 95 90 370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 398 112 107 102 97 405 113 108 103 98 412 114 109 104 99 419 115 110 105 100 426 117 112 107 102 433 118 113 108 103 440 119 114 109 104 447 120 115 110 105 454 122 117 112 107 461 123 118 113 108 468 124 119 114 109 475 125 120 115 110 482 126 121 116 111 489 127 122 117 112 496 129 124 119 114 503 130 125 120 115 510 131 126 121 116 517 132 127 122 117 524 133 128 123 118 531 134 129 124 119 538 135 130 125 120 545 136 131 126 121 552 137 132 127 122 559 138 133 128 123 566 139 134 129 124 573 140 135 130 125 580 141 136 131 126 587 142 137 132 127 594 143 138 133 128 601 144 139 134 129 608 145 140 135 130

(PSIG)

Wrap service valves and filter drier with a wet cloth or heat- sinking material. Braze connections using either silver bearing or non-silver bearing brazing material. Do not use soft solder (materials which melt below 800°F). Consult local code require- ments.

  • CAUTION: To prevent damage to unit or service valves, observe the following:
  • Use a brazing shield.
  • Wrap service valves with wet cloth or use a heat sink material.

E. LEAK CHECKING

Leak test all joints in indoor, outdoor, and refrigerant tubing. F. EVACUATE REFRIGERANT TUBING AND INDOOR COIL

Refrigerant tubes and indoor coil must be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. IMPORTANT: Never open system under vacuum to atmosphere without first breaking it open with nitrogen.

SENSING BULB

STRAP

SUCTION

TUBE

8 O'CLOCK 4 O'CLOCK

Fig. 7—Positioning of Sensing Bulb

Page 6 of the Bryant 698B user manual — G. FINAL TUBING CHECK
Page 6 · click to enlarge
Page 6

2500 3000 3500 4000 4500 5000

Bryant 698B — MICRONS diagram (page 6)
Fig. 6
Bryant 698B — MICRONS diagram (page 6)
Fig. 7

MICRONS

MINUTES 0 1 2 3 4 5 6 7

Fig. 10—Deep Vacuum Graph

Bryant 698B — MICRONS diagram (page 6)
Fig. 8

Fig. 8—Liquid Service Valve with Sweat Adapter Tube

DEEP VACUUM METHOD

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 10.)

TRIPLE EVACUATION METHOD

The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury and system does not contain any liquid water. Refer to Fig. 11 and proceed as follows:

1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system, absorbing moisture.

Fig. 11—Triple Evacuation Method

G. FINAL TUBING CHECK

5. Repeat this procedure as indicated in Fig. 11. System will then contain minimal amounts of contaminants and water vapor.
Bryant 698B — G. FINAL TUBING CHECK diagram (page 6)
Fig. 9

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device. NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits. NOTE: Use copper wire only between disconnect switch and unit.

Fig. 9—Filter Drier with Sweat Adapter Tube and Liquid

1000 1500 · Tube

Page 7 of the Bryant 698B user manual — X. MAKE AIRFLOW SELECTIONS
Page 7 · click to enlarge
Page 7

recommended airflow and for adjustments to the manual switches labeled SW1, A/C and CF on the control board refer to the furnace Installation, Start-Up, and Operating Instructions. The 315AAV/315JAV utilizes a control center that allows the install- ing technician to select the proper airflows. The A/C switch determines the airflow during high speed compressor operation. Airflow for high and low speed can be calculated at either 350 CFM per ton or 400 CFM per ton based on the positions of SW1-5. B. AIRFLOW SELECTION FOR 355MAV FURNACES The 355MAV Condensing Variable-Speed Furnaces provide high- and low-speed blower operation to match the capacities of com- pressor at high and low speeds. To select recommended airflow, refer to the 355MAV Installation Instructions. The 355MAV utilizes a control center that allows the installing technician to select proper airflow. For adjustments to the manual switches labeled A/C and CF and recommended switch positions, refer to Furnace Installation Instructions for setting required airflow. High-speed airflow is determined by the position of the A/C switches, and low-speed airflow is determined by the position of the CF switches. C. AIRFLOW SELECTION FOR FK4 OR FV4 FAN COILS The FK4 and FV4 provide high- and low-speed blower operation to match the capacities of compressor at high and low speeds. To select recommended airflow, refer to the FK4 or FV4 Installation Instructions. The FK4 and FV4 utilize an EASY SELECT control board that allows the installing technician to select proper airflow. The ORANGE SYSTEM TYPE JUMPER wire should be set to HP–EFF or HP–COMFORT. The BLUE AC/HP SIZE JUMPER is used to select airflow to match the outdoor unit nominal size in tons of cooling. The BLACK AC/HP CFM ADJUST jumper is used to make slight adjustments to the selected airflow tonnage. See the fan coil Installation Instructions for setting required airflow. This fan coil has an adjustable blower off delay factory set at 90 sec for high- and low-speed blower operation. XI. START-UP

DISCONNECT PER N. E. C. AND/ OR LOCAL CODES

CONTACTOR

FIELD POWER

WIRING

→

FIELD GROUND

WIRING GROUND LUG

Fig. 12—Line Power Connections

A. ROUTE GROUND AND POWER WIRES Remove access panel and control box cover to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box. Size wires per NEC but not smaller than minimum wire size shown in Product Data Sheet.

→

B. CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for safety. Connect power wiring to leads provided as shown in Fig. 12.

  • CAUTION: To prevent compressor damage or personal injury, observe the following:
  • Do not overcharge system with refrigerant.
  • Do not operate unit in a vacuum or at negative pressure.
  • Do not disable low-pressure switch.

C. CONNECT CONTROL WIRING

Route 24v control wires through control wiring grommet and connect to leads provided in control box. (See Fig. 13.) Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop. All wiring must be NEC Class 1 and must be separated from incoming power leads. The outdoor unit requires a minimum of 27va, 24v control power.

D. FINAL WIRING CHECK IMPORTANT: Check factory wiring and wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

IX. INSTALL ELECTRICAL ACCESSORIES

A. GENERAL Refer to the individual instructions packaged with kits or acces- sories when installing. The liquid line solenoid valve accessory is available on these units. See Fig. 14 for wiring diagram. See Fig. 13 for typical accessory wiring diagrams.

Follow these steps to properly start up the system:

1. The outdoor unit is equipped with a crankcase heater which operates when the compressor is OFF. Energize crankcase heater 24 hr before starting unit. To energize heater only, set indoor thermostat to OFF position and close power discon- nect to unit. 2. Fully back seat (open) liquid and vapor tube service valves. 3. Unit is shipped with valve stem(s) front seated and caps installed. Replace stem caps after system is opened to refrigerant flow (back seated). Replace caps finger tight and tighten additional 1/12 turn (20 ft-lb torque) with wrench.

X. MAKE AIRFLOW SELECTIONS

A. AIRFLOW SELECTION FOR 315AAV/315JAV FUR- NACES The 315AAV/315JAV Non-Condensing Variable Speed Furnaces provide high- and low-speed blower operation to match the capacities of the compressor at high and low speeds. To select the

Page 8 of the Bryant 698B user manual — TWO-STAGE
Page 8 · click to enlarge
Page 8

PROGRAMMABLE

FV4 FK4 FAN COIL

THERMIDISTAT

THERMOSTAT

TWO-SPEED

CONTROL MODEL RH

SINGLE-STAGE

TWO-SPEED

MODEL 2S

HEAT PUMP

FURNACE

HEAT PUMP

24 VAC HOT RDH RJ1 JUMPER R FAN G COOL/HEAT STAGE 1 Y1/W2 RVS COOLING O/W2 COOL/HEAT Y/Y2 STAGE 2 HEAT STAGE 3 W/W1 24 VAC COMM C N/A B OUTDOOR S1 SENSOR CONNECTION S2G Y1/W2G Y1 O/W2 Y/Y2O Y/Y2 W1 W2J2 JUMPE C B S1 S2
Bryant 698B — PROGRAMMABLE diagram (page 8)
Fig. 10
Bryant 698B — PROGRAMMABLE diagram (page 8)
Fig. 11

See notes 1, 2, and 3

See notes 1, 2, 3, 7, 8, 9, 10, and 11

NON-PROGRAMMABLE

FV4 FK4 FAN COIL

THERMOSTAT

TWO-SPEED

PROGRAMMABLE

MODEL 2S

HEAT PUMP

DUAL FUEL THERMOSTAT

SINGLE-STAGE

TWO-SPEED

Bryant 698B — NON-PROGRAMMABLE diagram (page 8)
Fig. 12

MODEL DF

FURNACE

HEAT PUMP

Bryant 698B — MODEL DF diagram (page 8)
Fig. 13

See notes 1, 2, 3, and 4

See notes 1, 2, 3, 7, 8, and 12

TWO-STAGE

THERMIDISTAT

FV4/FK4 FAN COIL

TWO-SPEED

THERMIDISTAT

FURNACE WITH PSC BLOWER MOTOR

CONTROL MODEL RH

HEAT PUMP

CONTROL MODEL RH

TWO-SPEED

HEAT PUMP

Bryant 698B — TWO-STAGE diagram (page 8)
Fig. 14
Bryant 698B — TWO-STAGE diagram (page 8)
Fig. 15

See notes 1, 2, 3, 6, 9, and 10

See notes 1, 2, 3, 5, 7, 8, 9, 10, and 11

Fig. 13—Typical 24V Circuit Connections

Page 9 of the Bryant 698B user manual — →
Page 9 · click to enlarge
Page 9

THERMIDISTAT

VARIABLE-SPEED

PROGRAMMABLE

VARIABLE

CONTROL MODEL RH

CONDENSING

TWO-SPEED

DUAL FUEL THERMOSTAT

SPEED CONDENSING

TWO-SPEED

FURNACE

HEAT PUMP

MODEL DF

FURNACE

HEAT PUMP

Bryant 698B — THERMIDISTAT diagram (page 9)
Fig. 16
Bryant 698B — THERMIDISTAT diagram (page 9)
Fig. 17
HEAT STAGE 3 W/W1 C STO AO GL E/H 2EAT Y/Y2 FAN G 24 VAC HOT R DEHUMIDIFY DHUM 24 VAC COMM C HUMIDIFY HUM N/A B OUTDOOR S1 SENSOR CONNECTION S2W/W1 Y/Y2 G R DHUM COM HUMW1 Y2 R C HUMIDIFIER (24 VAC) OUTDOOR SENSOR S1 S2S1SENSOR

See notes 1, 2, 3, 5, 7, 8, 9, 10, 11, and 13

See notes 1, 2, 3, 5, 7, 8, and 12

VARIABLE SPEED 80% NON-CONDENSING FURNACE

PROGRAMMABLE

TWO-STAGE

TWO-SPEED

DUAL FUEL THERMOSTAT

FURNACE

HEAT PUMP

THERMIDISTAT

CONTROL MODEL RH

TWO-SPEED

Bryant 698B — VARIABLE SPEED 80% NON-CONDENSING FURNACE diagram (page 9)
Fig. 18

HEAT PUMP

Bryant 698B — HEAT PUMP diagram (page 9)
Fig. 19
HEAT STAGE 3 W/W1 HEA ST T/ AC GO EO 2L Y/Y2 FAN G 24 VAC HOT R 24 VAC COM C DEHUMIDIFY DHUM DH HUMIDIFY HUM N/A B OUTDOOR S1 SENSOR CONNECTIONS S2W/W1 Y/Y2 GW1 Y2 R C R COM HUM UM PL9-10 HUMIDIFIER (24 VAC) OUTDOOR SENSOR

See notes 1, 2, 3, 5, 7, 8, 9, 10, and 11

SUGGESTED DIP SWITCH SETTINGS

VARIABLE SPEED 80% NON-CONDENSING FURNACE

See notes 1, 2, 3, 5, 7, 8, and 12

PROGRAMMABLE

DUAL FUEL THERMOSTAT

TWO-SPEED

HEAT PUMP

MODEL DF

Bryant 698B — PROGRAMMABLE diagram (page 9)
Fig. 20
Bryant 698B — PROGRAMMABLE diagram (page 9)
Fig. 21

RELAY SPDT, PILOT DUTY 24-V COIL (HN61KK324) OR EQUIVALENT

See notes 1, 2, 3, 5, 7, 8, and 12

A01222 Fig. 13—Typical 24V Circuit Connections (Cont) and Wiring Diagram Legend

→

Page 10 of the Bryant 698B user manual — FK4/FV4 FAN COIL
Page 10 · click to enlarge
Page 10

WIRING DIAGRAM NOTES:

1. Wiring must conform to NEC or local codes.
2. Underlined letter on thermostat terminal indicates its usage. For example: O/W2 means O is energized in cooling mode.
3. Refer to indoor unit Installation Instructions for any additional features and wiring information.
4. Non-Programmable Model 2S01–B, when used in heat pump installations (jumper R19 NOT cut), uses O/W2 to control reversing valve.
5. Furnace must control its own second-stage operation via furnace control algorithms. Refer to furnace Installation Instructions for proper setup.
6. To activate dehumidify function on FK4 or FV4, remove J1 jumper at fan coil control board.
7. Heat pump MUST have a high-pressure switch for dual fuel applications.
8. Outdoor air temperature sensor must be attached in all dual fuel applications.
9. Thermidistat Dip Switch No. 1 should be set in ON position for heat pump installations.
10. Thermidistat Dip Switch No. 2 should be set in the ON position for dual capacity compressor operation.
11. Thermidistat Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
12. Dual Fuel Dip Switch–D (no. 4) must be set in the ON position for dual capacity compressor operation.
13. The DE jumper located next to the DHUM terminal must be removed to enable the DEHUM input. NOTE: If unit has not operated within the past 12 hr or following a unit power-up, upon the next thermostat highor low-speed demand, unit operates for a minimum of 5 minutes on high speed.
4. Close electrical disconnects to energize system.

XII. CHECK CHARGE

5. Set room thermostat at desired temperature. Be sure the set point is below indoor ambient and is set low enough to energize desired speed.
6. Set room thermostat to COOL or HEAT and fan control to AUTO or ON as desired. Wait for appropriate time delay(s). Operate unit for 15 minutes. Check refrigerant charge.

NOTE: Bryant electronic thermostats are equipped with a 15 minute staging timer. This timer prevents the dual capacity system from operating at high capacity until unit has been operating in low capacity for 15 minutes unless there is at least a 5°F difference between room temperature and thermostat set point. To force high capacity, adjust the set point at least 5° below room ambient for cooling or 5° above room ambient for heating.

A. UNIT CHARGE

Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure. To charge in heating mode, weigh the charge in.

FK4/FV4 FAN COIL

TWO-SPEED

HEAT PUMP

DH

J1 JUMPER

24 VAC HOT

LLS

24 VAC COM

FAN

G

G

COOL/HEAT STAGE 2

Y/Y2

Y/Y2

W/W2

HEAT STAGE 3

J2 JUMPER

RVS COOLING

O/W2

COOL/HEAT STAGE 1

N/A

OUTDOOR SENSOR

CONNECTION

Fig. 14—Typical Solenoid Valve Wiring

Page 11 of the Bryant 698B user manual — YEL
Page 11 · click to enlarge
Page 11

Adjust charge in both heating and cooling by following procedure shown on charging tables located on pink charging label on back side of access panel. NOTE: Unit is to be charged in high capacity only. Charging in low capacity may cause compressor chattering and possible damage to the compressor. B. COOLING ONLY PROCEDURE

NOTE: In heating mode, check refrigerant charge only when pressures are stable. If accessory vapor pressure switch is applied and operating conditions cause vapor pressure switch and thereby outdoor fan to cycle, check refrigerant charge in cooling or lower indoor dry bulb temperature. If in doubt, remove charge and weigh in correct refrigerant charge. NOTE: When charging is necessary during heating season, charge must be weighed in accordance with unit rating plate ±0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge.

1. Operate unit a minimum of 15 minutes before checking charge. 2. Measure liquid service valve pressure by attaching an accurate gage to service port. 3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil. 4. Refer to charging label for required subcooling tempera- tures. 5. Refer to Table 3. Find the point where required subcooling temperature intersects measured liquid service valve pres- sure. 6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line tempera- ture is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of ± 3°F. C. HEATING CHECK CHARGE PROCEDURE

XIII. SYSTEM FUNCTIONS AND SEQUENCE OF OP- ERATION The outdoor unit control system has special functions. The following is an overview of the two-speed control functions:

A. COOLING OPERATION This product utilizes a 2-stage cooling indoor thermostat. With a call for first stage cooling (Yl), the outdoor fan and low capacity compressor are energized. If low capacity cannot satisfy cooling demand, high capacity is energized (Yl and Y2 or just Y2) by the second stage of indoor thermostat. After second stage is satisfied, the unit returns to low-capacity operation until first stage is satisfied or until second stage is required again. When both one stage and two stage cooling are satisfied, the compressor will shut off. NOTE: Outdoor fan motor will continue to operate for one minute after compressor shuts off, when outdoor ambient is greater than 100°F.

To check system operation during heating cycle, refer to the Heating Pump Charging Instructions on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.

CEBD430439-03A

HP/AC

SEV

RVS

SS0ID

HI

LO

R38 R33

C2 R9

J1

PL1 PL2

OCT OAT HPS LPS

C31 R61

PL3

PL4

FORCED DEFROST

PL5

PWM2

DEFROST TIME (MIN)

R39 R44 R42

PWM1

BRN

CCH L2 ODF VH VC

BLU

BLK

CEPL130439-01 C O M M S TAT U S

YEL

D51 D52

K1

RED

A B C D

R87 R86

C E S O 1 3 0 0 7 8 - 0 0

Fig. 15—Control Board

Page 12 of the Bryant 698B user manual — TABLE 5—DEFROST DIP SWITCH SETTINGS
Page 12 · click to enlarge
Page 12

D. STATUS FUNCTION LIGHTS A system control STATUS function light is located on the outdoor unit control board. (See Fig. 15). The STATUS light provides signals for several system operations. See Table 4 for codes and definitions. Table 4 also provides the order of signal importance. NOTE: Only one code will be displayed on the outdoor unit control board (the most recent, with the highest priority). E. FACTORY DEFAULTS Factory defaults have been provided in the event of failure of outdoor air thermistor and/or outdoor coil thermistor. Refer to Table 6 for default and function. F. COMPRESSOR OPERATION When the compressor operates in two-capacity operation, the motor rotates clockwise. Both the lower and upper pistons are eccentric with the rotating crankshaft, and both compress refrig- erant. When the compressor operates in single capacity the motor reverses direction (rotates counterclockwise). The lower piston becomes idle and the upper piston compresses refrigerant. During single-capacity operation the “start” and “run” windings are reversed. G. CRANKCASE HEATER OPERATION The two-speed control energizes the compressor crankcase heater during unit’s off cycle. H. OUTDOOR FAN MOTOR OPERATION

B. ONE MINUTE SPEED CHANGE TIME DELAY

When compressor changes speeds from high to low or low to high, there is a 1-minute time delay before compressor restarts. The outdoor fan motor remains running.

C. HEATING OPERATION

This product utilizes a 3-stage heating indoor thermostat. With a call for first stage heating (Y1), the outdoor fan and low capacity compressor are energized. If low capacity cannot satisfy heating demand, high capacity is energized (Y1 and Y2) by the second stage of the indoor thermostat. Auxiliary or back up heat is controlled by third stage (W1). After second stage of heat is satisfied, the unit returns to low capacity operation until first stage is satisfied or until second stage is required again. When both one stage and two stage heating are satisfied, the compressor will shut off. See thermostat Installation Instructions for more staging information.

The two-speed control energizes outdoor fan any time compressor is operating. The outdoor fan remains energized during the 1-minute speed change time delay and if a pressure switch or compressor overload should trip. Outdoor fan motor will continue to operate for one minute after the compressor shuts off when the outdoor ambient is greater than 100°F.

THERMISTOR CURVE

TABLE 4—LED CONTROL FUNCTION LIGHT CODE

CODE DEFINITION * Constant flash

RESISTANCE (KOHMS)

1 flash w/pause Low-speed operation 9

2 flashes w/pause High-speed operation 8

3 flashes w/pause Outdoor ambient thermistor failure 7

4 flashes w/pause Outdoor coil thermistor failure 6

3 flashes pause 4 flashes Thermistor out of range† 5

0 20 40 60 80 100 120 TEMPERATURE (DEG. F)

5 flashes pause 1 flash Low pressure switch trip 4

Fig. 16—Resistance Values Versus Temperature

5 flashes w/pause 2 flashes High pressure switch trip 3

6 flashes w/pause Compressor VC/VH trip 2

Control Box Side of Unit

* Function light signal order of importance in case of multiple signal request; 1 is most important. † Check both thermistors to determine which is faulty.

THERMISTOR PLACED UNDERNEATH BASE PAN (ATTACHED TO BASE PAN WITH ADHESIVE)

TABLE 5—DEFROST DIP SWITCH SETTINGS

TIME DIP SWITCH #1 DIP SWITCH #2 30 up down 60 down up 90 down down 120 up up

Fig. 17—View from Top of Base Pan

Show 7 more labels / short text on this page
No demand · No pause · Stand by 10 · Constant light · No pause · Board failure 1 · No flash
Page 13 of the Bryant 698B user manual — TABLE 6—FACTORY DEFAULTS
Page 13 · click to enlarge
Page 13

After termination of a defrost cycle, the outdoor fan delays come on for 20 sec. This allows refrigerant system to recover outdoor coil heat and minimize the “steam cloud” effect.

3. Display the appropriate error code on the status light (see Table 4). 4. After a 15 minute delay, if Yl or Y2 inputs are on and the LPS or HPS is reset, energize appropriate compressor contactor, either low or high. 5. If LPS or HPS has not closed after 15 minute delay, outdoor fan is turned off. If the open switch closes anytime after the 15-minute delay, then resume operation on call for Y1 and/or Y2.

I. DEFROST TIME SELECTION The defrost interval can be field selected, dependent on local or geographical requirements. It is factory set at 90 minutes but can be changed to either 30, 60, or 120 minutes. To select defrost time, set dip switches located on the left side of the unit board (See Fig. 15). See Table 5 for Defrost Dip Switch Settings.

N. MAJOR COMPONENTS

J. DEFROST The dual capacity control logic for defrost function is the standard time and temperature initiated, time or temperature terminated. Defrost only occurs at outdoor temperatures less than 50°F. The control initiates defrost when outdoor coil thermistor is 30°F (±2°) or less, and selected defrost time (interval) has been accumulated during unit operation. Termination occurs when coil thermistor reaches 80°F (±5°) or defrost period reaches a maximum of 10 minutes. Defrost will occur at the compressor capacity that is being called for. During defrost, unit operates in high or low capacity, energizes reversing valve O and auxiliary heat W2, and de- energizes outdoor fan. Upon termination, there is a 20-sec delay in outdoor fan being energized.

  • TWO-SPEED CONTROL The two-speed control board controls the following functions:
  • Lowand high-compressor contactor operation
  • Outdoor fan motor operation
  • Crankcase heater operation
  • Compressor protection
  • Pressure switch monitoring
  • Time delays
  • Time/temperature defrost
  • Defrost interval selection
  • Electric heat operation during defrost mode

K. FIELD-INITIATED FORCED DEFROST

FIELD CONNECTIONS

By placing a jumper across forced defrost terminals (See Fig. 15) for a minimum of 5 sec and then removing it, a defrost cycle can be initiated. The cycle occurs only if outdoor ambient is less than 50°F, regardless of outdoor coil temperature. The cycle terminates when coil thermistor reaches 80°F (±5°) or defrost period reaches a maximum of 10 minutes.

The two-speed dual capacity control received 24v low-voltage control system inputs through the screw connections on the left side of the control board.

TWO-SPEED DUAL CAPACITY COMPRESSOR

The two-speed dual capacity compressor contains motor windings that provide 3500 RPM operation. Refer to Table 7 for correct winding resistance.

L. COMPRESSOR VOLTAGE FAILURE (6 FLASHES)

The control senses the voltage of the compressor run winding. If compressor voltage (Vc) is less than 90v when control board is calling for compressor operation, control shuts compressor off for 15 minutes with outdoor fan running. After 15 minutes (provided there is a call for Y1 or Y2), control attempts to start compressor. During this time, a code of 6 flashes appears at control board. If Vc trip occurs 3 consecutive times during a Y1 request, then low capacity operation is locked out and control responds to Y2 requests until a reset occurs. If 3 consecutive trips occur in a combination of Yl and Y2 or all Y2 requests, then both low and high capacity operation will be locked out. The compressor voltage failure (6 flashes) can be caused by:

COMPRESSOR INTERNAL RELIEF

The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when differen- tial between suction and discharge pressures exceeds 525 psi. The compressor is also protected by an internal overload attached to motor windings.

COMPRESSOR CONTROL CONTACTORS

Low and High capacity contactor coils are 24 volts. The electronic control board controls the operation of the low speed (C-L) and the high speed (C-H) contactors.

O. TEMPERATURE THERMISTORS

  • compressor internal overload trip (refer to Table 7 for correct winding)

Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor ambient and coil temperature. Refer to Fig. 16 for resistance values versus temperature. If the outdoor ambient thermistor or coil thermistor should fail, a fault code appears at electronic control. The crankcase heater is turned on during all off cycles. IMPORTANT: OUTDOOR AIR THERMISTOR PLACEMENT Mount outdoor air thermistor underneath unit base pan lip on control box side of unit as shown in Fig. 17. Attach to base pan with adhesive tape or other field expedient means. IMPORTANT: If outdoor air thermistor is nor properly placed underneath base pan, unit may have nuisance thermistor out of range faults.

  • no 208/230 volt power supply to outdoor unit
  • failed compressor contactor(s)
  • failure of start relay to pick-up properly.
  • improper wiring.

M. PRESSURE SWITCH PROTECTION The outdoor unit is equipped with high- and low-pressure switches. If the control senses the opening of the high or low pressure switch, it will respond as follows:

1. De-energize the compressor hi or low speed contactor,
2. Keep the outdoor fan operating for 15 minutes,

TABLE 6—FACTORY DEFAULTS

FAILED COMPONENT FUNCTION DEFAULT

Ambient Thermistor Defrost Initiation Defrost is initiated based on coil

temperature and time.

Outdoor Coil Thermistor Defrost Initiation and Termination Defrost occurs at each time interval, but

terminate after 5 minutes

Page 14 of the Bryant 698B user manual — PROGRAMMABLE
Page 14 · click to enlarge
Page 14
XIV. FINAL CHECKS IMPORTANTBefore leaving job, be sure to do the following:
2. Tighten service valve stem caps to 1/12-turn past finger tight.
1. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers.
3. Leave User’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
4. Fill out Dealer Installation Checklist and place in customer file.

TABLE 7—TWO-SPEED COMPRESSOR (WINDING RESISTANCE AT 70°F ± 20°)

CARE AND MAINTENANCE For continuing high performance and to minimize possible equip- ment failure, periodic maintenance must be performed on this equipment. Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.

WINDING 2 TON 3 TON 4 TON 5 TON Start (S-C) 2.280 1.850 1.459 0.740 Run (R-C) 0.770 0.745 0.552 0.356

Page 15 of the Bryant 698B user manual — PROGRAMMABLE
Page 15 · click to enlarge
Page 15
Bryant 698B — PROGRAMMABLE diagram (page 15)
Fig. 22

→ Fig. 18—Wiring Diagram—024, 036, 048

Page 16 of the Bryant 698B user manual — PROGRAMMABLE
Page 16 · click to enlarge
Page 16
Bryant 698B — PROGRAMMABLE diagram (page 16)
Fig. 23

→Fig. 19—Wiring Diagram—060

© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —16— Printed in U.S.A. 698b244 Catalog No. 5369-812

Ask about the Bryant 698B

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 698B

Be the first to ask — other owners or our team will answer.

Original document

Bryant 698B manual PDF

16 pages·328 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…