Table of Contents 80 sections installation, start-up, · 583B 683B 602B 702B · and operating instructions · ICM FIOP INSTALLATION INSTRUCTIONS · … ShowHide
installation, start-up,p.1583B 683B 602B 702Bp.1and operating instructionsp.1ICM FIOP INSTALLATION INSTRUCTIONSp.1TABLE OF CONTENTSp.1SAFETY CONSIDERATIONS.....................................................1p.1INTRODUCTION..........................................................................2p.1RECEIVING AND INSTALLATION ..........................................2p.1ICM FIOP PRE-START-UP..........................................................2p.1ICM FIOP START-UP ................................................................10p.1ELECTRICAL DATA & SCHEMATICS—ICM FIOP.............12p.1CARE AND MAINTENANCE...................................................12p.1TROUBLESHOOTING ...............................................................13p.1START-UP CHECKLIST............................................................13p.1SAFETY CONSIDERATIONSp.1HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)p.2POWER SUPPLYp.2INTRODUCTIONp.2FIELD-SUPPLIED FUSED DISCONNECTp.2GND CONTROL BOXp.2BLK(DH)p.2DHUMp.2YEL(Y)p.2THERMOSTAT (TYPICAL)p.2GRN(G)p.2LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)p.2RED(R)p.2BRN(C)p.2W1 WHI(W1)p.2SPLICE BOXp.2RECEIVING AND INSTALLATIONp.2ICM FIOP PRE-START-UPp.2I. ELECTRICAL CONNECTIONSp.2DHUM BLK (DH)p.2W/W1 WHT(W1)p.2THERMOSTAT (THERMIDISTAT ™ )p.2Y/Y2p.2ORN(O)p.2O/W2p.2SPECIAL PROCEDURES FOR 208–V OPERATIONp.2HIGH AIRFLOWp.3GRA(W2)p.3W2p.3TIME DELAY PROFILEp.3WHEN THERMOSTAT IS SET ON CONTINUOUS FANp.3W2 ORN(0)p.3HUMIDISTATp.4HUM 1p.424-VACp.4TO HUMIDIFIERp.4HUM 2p.4(G)p.4HUMIDIFIER WIRINGp.4A95317p.4EASY SELECT BOARD TERMINALp.4BLOCKp.4D H J1p.4REMOVEp.4JUMPERp.4A95316p.49 PIN CONNECTORp.512 PIN CONNECTORp.5THERMIDISTAT ™p.6THERMIDISTATp.6THERMIDISTAT™CONNECTIONp.6CAPABILITIESp.7SIZE OF ELECTRIC HEATER INSTALLEDp.7TIONp.7702B & 602Bp.9HUMIDISTAT CONNECTIONp.9(1.) FAN OPERATION—p.10(2.) COOLING MODE—p.10(3.) HEAT PUMP HEATING—p.11(4.) GAS HEAT MODE—p.11(5.) AUTOMATIC CHANGE-OVER—p.11III. 702B: START-UP (ICM FIOP)p.11TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583Bp.121 REFRIGERANT (R-410A)p.12REFRIGERANT METERING DEVICEp.12CONDENSER COILp.12
Page 1 of the Bryant 683B user manual — Table of Contents
Page 1 · Contents
Contents

Contents

installation, start-up,p.1583B 683B 602B 702Bp.1and operating instructionsp.1ICM FIOP INSTALLATION INSTRUCTIONSp.1TABLE OF CONTENTSp.1SAFETY CONSIDERATIONS.....................................................1p.1INTRODUCTION..........................................................................2p.1RECEIVING AND INSTALLATION ..........................................2p.1ICM FIOP PRE-START-UP..........................................................2p.1ICM FIOP START-UP ................................................................10p.1ELECTRICAL DATA & SCHEMATICS—ICM FIOP.............12p.1CARE AND MAINTENANCE...................................................12p.1TROUBLESHOOTING ...............................................................13p.1START-UP CHECKLIST............................................................13p.1SAFETY CONSIDERATIONSp.1HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)p.2POWER SUPPLYp.2INTRODUCTIONp.2FIELD-SUPPLIED FUSED DISCONNECTp.2GND CONTROL BOXp.2BLK(DH)p.2DHUMp.2YEL(Y)p.2THERMOSTAT (TYPICAL)p.2GRN(G)p.2LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)p.2RED(R)p.2BRN(C)p.2W1 WHI(W1)p.2SPLICE BOXp.2RECEIVING AND INSTALLATIONp.2ICM FIOP PRE-START-UPp.2I. ELECTRICAL CONNECTIONSp.2DHUM BLK (DH)p.2W/W1 WHT(W1)p.2THERMOSTAT (THERMIDISTAT ™ )p.2Y/Y2p.2ORN(O)p.2O/W2p.2SPECIAL PROCEDURES FOR 208–V OPERATIONp.2HIGH AIRFLOWp.3GRA(W2)p.3W2p.3TIME DELAY PROFILEp.3WHEN THERMOSTAT IS SET ON CONTINUOUS FANp.3W2 ORN(0)p.3HUMIDISTATp.4HUM 1p.424-VACp.4TO HUMIDIFIERp.4HUM 2p.4(G)p.4HUMIDIFIER WIRINGp.4A95317p.4EASY SELECT BOARD TERMINALp.4BLOCKp.4D H J1p.4REMOVEp.4JUMPERp.4A95316p.49 PIN CONNECTORp.512 PIN CONNECTORp.5THERMIDISTAT ™p.6THERMIDISTATp.6THERMIDISTAT™CONNECTIONp.6CAPABILITIESp.7SIZE OF ELECTRIC HEATER INSTALLEDp.7TIONp.7702B & 602Bp.9HUMIDISTAT CONNECTIONp.9(1.) FAN OPERATION—p.10(2.) COOLING MODE—p.10(3.) HEAT PUMP HEATING—p.11(4.) GAS HEAT MODE—p.11(5.) AUTOMATIC CHANGE-OVER—p.11III. 702B: START-UP (ICM FIOP)p.11TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583Bp.121 REFRIGERANT (R-410A)p.12REFRIGERANT METERING DEVICEp.12CONDENSER COILp.12
Page 2 of the Bryant 683B user manual — SPECIAL PROCEDURES FOR 208–V OPERATION
Page 2 · click to enlarge
Page 2

C. Easy Select™—583B

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

POWER SUPPLY

INTRODUCTION

FIELD-SUPPLIED FUSED DISCONNECT

GND CONTROL BOX

BLK(DH)

DHUM

YEL(Y)

Y

THERMOSTAT (TYPICAL)

GRN(G)

LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

G

These instructions cover the installation of a Bryant Small Pack- aged Product with ICM motor-factory installed option (FIOP). This option can be selected as a FIOP on gas heating/electric cooling (583B), dual fuel–electric heat pump with gas heat back-up (683B), electric cooling (702B) or electric heat pump (602B) units with Puron®.

RED(R)

R

BRN(C)

W1 WHI(W1)

SPLICE BOX

RECEIVING AND INSTALLATION

LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring

Refer to unit Installation Instructions.

Fig. 2—583B High- and Control-Voltage

ICM FIOP PRE-START-UP

I. ELECTRICAL CONNECTIONS

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

A. Control Voltage Connections

POWER SUPPLY

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35 C minimum) wires.

FIELD-SUPPLIED FUSED DISCONNECT

GND CONTROL BOX

DHUM BLK (DH)

W/W1 WHT(W1)

YEL(Y)

THERMOSTAT (THERMIDISTAT ™ )

LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

Y/Y2

GRN(G)

B. Standard Connection

G

RED(R)

R

Remove knockout hole located in the heat section panel adjacent to the service access panel (See unit installation package). Remove the rubber grommet from the installer’s packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel. Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box. Locate 18-gage wires leaving control box. These low-voltage connection leads can be identified by colors (See Fig. 2, 3, 4 or 5). Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Route leads through hole in bottom of control box and make low-voltage connections (See Fig. 2, 3, 4 or 5). Secure all cut wires, so that they do not interfere with operation of unit.

BRN(C)

ORN(O)

O/W2

SPLICE BOX

FIELD CONTROL - VOLTAGE WIRING FIELD HIGH - VOLTAGE WIRING

Fig. 3—683B High- and Control-Voltage

EASY SELECT™CONFIGURATION TAPS FOR 583B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a

SPECIAL PROCEDURES FOR 208–V OPERATION

Connections · Connections

Page 3 of the Bryant 683B user manual — SPLICE BOX
Page 3 · click to enlarge
Page 3

Factory selected gas heat size should correspond to unit label. b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

Factory selected air conditioner size should correspond to capacity of unit installed. Installer should verify air conditioner size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes. c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED

POWER SUPPLY

FIELD-SUPPLIED FUSED DISCONNECT

Factory selected on 583B for AC-Air conditioner. For Gas Heat/Electric Cool Unit–AC must be selected. d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR

GND CONTROL BOX

BLK(DH)

DHUM

HIGH AIRFLOW

YEL(Y)

Y

The AC/HP CFM Adjust select is factory set to the High-HI (NOM for 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 8, D as indicated). e. ON/OFF DELAY—SELECT DESIRED

GRN(G)

THERMOSTAT (TYPICAL)

LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

G

RED(R)

R

BRN(C)

W1 WHI(W1)

GRA(W2)

W2

SPLICE BOX

LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring

TIME DELAY PROFILE

Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 8, E as indicated). Selection options are: (1.) The standard 90 sec off delay (Factory Setting) at 100

Fig. 4—702B High- and Control-Voltage

percent airflow in cooling mode. In heating mode, IGC will control 45 sec on delay with no airflow and 45 sec off delay.

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at

POWER SUPPLY

100 percent airflow profile is used when it is desirable to allow system coils time to cool-down in conjunction with the airflow in heating mode.

(3.) A no delay option used for servicing unit or when a

thermostat is utilized to perform delay functions in cooling mode. In heating mode IGC will control 45 sec on delay with no airflow and 45 sec off delay.

FIELD-SUPPLIED FUSED DISCONNECT

GND CONTROL BOX

BLK(DH)

(4.) Not recommended for 583B

DHUM

YEL(Y)

Y

f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED

THERMOSTAT (TYPICAL)

WHEN THERMOSTAT IS SET ON CONTINUOUS FAN

GRN(G)

LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

G

RED(R)

(1.) LO speed—Factory setting, 50 percent cooling mode

R

BRN(C)

airflow.

(2.) MED speed—Move connector to MED, 65 percent cooling

W1 WHI(W1)

mode airflow.

GRA(W2)

W2 ORN(0)

(3.) HI speed—Move connector to HI, 100 percent cooling

O

mode airflow (See Fig. 8, F as indicated).

g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE

The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol. h. BASIC UNIT CONFIGURATION

SPLICE BOX

LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring

Fig. 5—602B High- and Control-Voltage

The following basic configuration of the indoor motor will provide ARI rated performance of the 583B. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required, or if system enhancements such as super dehumidify are not needed. (1.) HEAT-Factory selected to match heat input size.

pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8). a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE

(2.) AC/HP Size-Factory selected to match system size, please

verify.

Connections · Connections

Page 4 of the Bryant 683B user manual — A95316
Page 4 · click to enlarge
Page 4

(3.) SYSTEM TYPE-Factory selected on 583B system AC-

KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating. c. HUMIDIFIER/HUMIDISTAT CONNECTIONS

AIR CONDITIONER.

(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM

for 036 & 060, and LO for 024 & 030..

Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat (See Fig. 6). These terminals are energized with 24-v. when G thermostat signal is present (See Fig. 6 & 7). Alternately, the 24-v. signal may be sourced from the W and C on the 9 pin connector. When using a Thermidis- tat™Control, Zone Perfect Plus or Comfort Zone II, the 24-v. signal may be sourced directly from the Thermidistat™HUM terminal (See Fig. 6, 7 & 8).

(5.) ON/OFF DELAY-Factory selected 0/90 profile.

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

mostat is set to continuous fan. i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick

The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super- Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort. This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published ARI SEER efficiency. During cool-to-dehumidify call, it provides maximum dehumidification by reducing airflow to a minimum. The actual super dehumidify command from Thermidistat™control to the indoor unit is a “Y” signal without a “G” signal in addition to dehumidify signal. The indoor unit responds to this combination by reducing the airflow to a minimum. All other characteristics of cool to dehumidify are the same. The following system configuration is recommended for maxi- mum cooling/dehumidifying comfort (See Fig. 8).

HUMIDISTAT

HUM 1

24-VAC

TO HUMIDIFIER

HUM 2

(G)

HUMIDIFIER WIRING

A95317

Fig. 6—Humidifier Wiring-583B

EASY SELECT BOARD TERMINAL

BLOCK

D H J1

(1.) HEAT-Factory selected to match gas heat size of unit

HUMIDISTAT

installed.

REMOVE

R

(2.) AC/HP Size-Factory selected to match system size, please

JUMPER

verify.

(3.) SYSTEM TYPE-Factory selected on 583B system AC-

A95316

AIR CONDITIONER.

Fig. 7—Humidistat Wiring for

(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).

(5.) ON/OFF DELAY-Select ENH profile.

d. DEHUMIDIFY CAPABILITY WITH STANDARD

HUMIDISTAT CONNECTION Latent capacities for this unit are better than average systems. If increased latent capacity is an application requirement, the ICM board provides connection terminals for use of a standard humidistat. The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode, remove jumper J1 and wire in a standard humidistat (See Fig. 7).

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

mostat is set to continuous fan.

(7.) DEHUMIDIFY MODE-Remove J1 jumper to activate.

(8.) LOW VOLTAGE CONNECTIONS-Make connections as

shown in ELECTRICAL CONNECTIONS section.

(9.) CONFIGURE THERMIDISTAT™-Follow Thermidis- tat™(or capable zoning system) installation instructions for Super Dehumidify operation. ACCESSORY INSTALLATION

e. DEHUMIDIFY AND SUPER DEHUMIDIFY

a. AUXILIARY TERMINALS

CAPABILITIES This model unit is capable of responding to a signal from indoor system control (Thermidistat™or capable zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.

The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 6). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of this operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.

D. 583B Sequence of Operation

b. ELECTRONIC AIR CLEANER CONNECTIONS

a. CONTINUOUS FAN

The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N.

(1.) Thermostat closes circuit R to G—The Blower runs at

continuous fan airflow b. COOLING MODE

Reference Guide) · De-Humidify Mode-583B

Page 5 of the Bryant 683B user manual — TIME DELAY PROFILE
Page 5 · click to enlarge
Page 5

(1.) If indoor temperature is above temperature set point and

9 PIN CONNECTOR

humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers single speed cooling airflow. c. COOLING MODE-DEHUMIDIFICATION

Bryant 683B — 9 PIN CONNECTOR diagram (page 5)
Fig. 1

(1.) If indoor temperature is above temperature set point and

humidity is above humidity set point, thermostat or Ther- midistat™closes circuits R to G, R to Y/Y2, R to O and humidistat or Thermidistat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system. d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (SEE QUICK REFERENCE GUIDE)

A

B

DH R W1 W2 Y1 Y/Y2 G O C

D

E

F

(1.) If the indoor temperature is below the temperature set

point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and closes circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0–v.) for Super Dehu- midify mode, the motor delivers reduced airflow to maxi- mize the humidity removal of the system while minimizing over cooling.

12 PIN CONNECTOR

Fig. 8—Detail of SPP Printed-Circuit Board

moval 2. HP-EFF (factory selected) Provides equal airflow for heating and cooling modes to increase overall heat pump efficiency. Provides approximately 400 CFM/ton.

e. GAS HEATING MODE

(1.) Thermostat closes circuit R to W/W1—The unit delivers

the selected gas heat airflow. The IGC will control a 45 sec. blower “On” delay and a 45 sec. “Off” delay.

d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR

E. Easy Select™—683B

HIGH AIRFLOW

The AC/HP CFM Adjust select is factory set to the High-HI (NOM for 036, 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 8, D as indicated).

EASY SELECT™CONFIGURATION TAPS FOR 683B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8).

e. ON/OFF DELAY—SELECT DESIRED

TIME DELAY PROFILE

Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 8, E as indicated). Selection options are:

a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE

Factory selected gas heat size should correspond to unit label.

(1.) The standard 90 sec off delay (Factory Setting) at 100

percent airflow in cooling or heat pump heating mode. In gas heating mode, IGC will control a 45 sec “On” delay and a 45 sec “Off” delay.

b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED

Factory selected air conditioner size should correspond to capacity of unit installed. Installer should verify air conditioner size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes.

(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at

100 percent airflow profile is used when it is desirable to allow system coils time to cool-down/heat-up in conjunc- tion with the airflow in cooling or heat pump heating mode.

c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED

Factory selected on 683B for HP-EFF. SELECT OPTIONS 1. HP-COMFORT provides approximately 315 CFM/ton for higher normal heating air temperature and provides approxi- mately 350 CFM/ton cooling airflow for good humidity re-

(3.) A no delay option used for servicing unit or when a

thermostat is utilized to perform delay functions. In gas heating mode IGC will control 45 sec on delay with no airflow and 45 sec off delay.

Page 6 of the Bryant 683B user manual — THERMIDISTAT™CONNECTION
Page 6 · click to enlarge
Page 6

(4.) ENH (enhanced) selection provides a 30 sec. cooling &

(8.) CONFIGURE THERMIDISTAT™-Follow Thermidis- tat™installation instructions for Super Dehumidify opera- tion. ACCESSORY INSTALLATION a. AUXILIARY TERMINALS

heat pump on delay with no airflow, plus 150 seconds at 70 percent airflow and no off delay for added comfort. This will minimize cold blow in heat pump operation and could enhance system efficiency. f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED

WHEN THERMOSTAT IS SET ON CONTINUOUS FAN

The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 9). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of this operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.

(1.) LO speed—Factory setting, 50 percent cooling mode

airflow.

(2.) MED speed—Move connector to MED, 65 percent cooling

mode airflow.

(3.) HI speed—Move connector to HI, 100 percent cooling

mode airflow (See Fig. 8, F as indicated). g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE

b. ELECTRONIC AIR CLEANER CONNECTIONS

The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N. KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating.

The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol. h. BASIC UNIT CONFIGURATION

c. HUMIDIFIER / THERMIDISTAT™CONNECTIONS

Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard Thermidistat™(See Fig. 9). These terminals are energized with 24-v. when G thermostat signal is present (See Fig. 10). Alternately, the 24-v. signal may be sourced from the W and C on the 9 pin connector. When using a Thermidis- tat™Control the 24-v. signal may be sourced directly from the Thermidistat™HUM terminal (See Fig. 8, 9 & 10).

The following basic configuration of the indoor motor will provide ARI rated performance of the 683B. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required. (1.) HEAT-Factory selected to match heat input size.

(2.) AC/HP Size-Factory selected to match system size, please

verify.

(3.) SYSTEM TYPE-Factory selected on 683B system for

HP-EFF.

THERMIDISTAT ™

(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM

for 036 & 060, and LO for 024 & 030.

HUM 1

24-VAC

TO HUMIDIFIER

(5.) ON/OFF DELAY-Factory selected 0/90 profile.

HUM 2

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

(G)

mostat is set to continuous fan.

HUMIDIFIER WIRING

i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick

Fig. 9—Humidifier Wiring-683B

The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super- Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort. This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published ARI SEER efficiency. The following system configuration is recommended for maxi- mum cooling/dehumidifying comfort (See Fig. 8). (1.) HEAT-Factory selected to match gas heat size of unit

EASY SELECT BOARD TERMINAL

BLOCK

D H J1

THERMIDISTAT

JUMPER

R

installed.

(2.) AC/HP Size-Factory selected to match system size, please

Fig. 10—Thermidistat™Wiring for

verify.

(3.) SYSTEM TYPE-Factory selected on 683B system for

d. DEHUMIDIFY CAPABILITY WITH STANDARD

HP-EFF.

THERMIDISTAT™CONNECTION

(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).

Latent capacities for this unit are better than average systems. If increased latent capacity is an application requirement, the ICM board provides connection terminals for use of a Thermidis- tat™. The unit will detect the Thermidistat™contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls

(5.) ON/OFF DELAY-Select ENH profile.

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

mostat is set to continuous fan.

(7.) LOW VOLTAGE CONNECTIONS-Make connections as

shown in ELECTRICAL CONNECTIONS section.

Reference Guide) · De-Humidify Mode-683B

Page 7 of the Bryant 683B user manual — TION
Page 7 · click to enlarge
Page 7

to a level which causes the Thermidistat™to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode wire in Thermidistat™see jumper in Fig. 10.

NOTE: The Thermidistat™is capable of providing Super Com- fort Heat operation mode and must be configured as outlined in its installation instructions. The system must be installed with appro- priate outdoor temperature sensor. Consult Thermidistat™litera- ture for configuration instructions. Consult sensor instructions for sensor installation details. If the outdoor temperature is in the range of 12° to 40° F, the Thermidistat™closes circuit R to Y/Y2 and opens circuit R to G. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full heating requested value. If circuit R to G is open (0-v.) for maximum heating comfort, the motor delivers reduced airflow to maximize the temperature and minimize the draft effect of the heated air leaving the unit.

e. DEHUMIDIFY AND SUPER DEHUMIDIFY

CAPABILITIES

This model unit is capable of responding to a signal from Thermidistat™to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with Thermidistat™to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.

G. Easy Select™—702B & 602B

F. 683B Sequence of Operation

9 PIN CONNECTOR

Bryant 683B — 9 PIN CONNECTOR diagram (page 7)
Fig. 2

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G—The Blower runs at

continuous fan airflow b. COOLING MODE

(1.) If indoor temperature is above temperature set point and

A

humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers single speed cooling airflow.

B

c. COOLING MODE-DEHUMIDIFICATION

DH R W1 W2 Y1 Y/Y2 G O C

(1.) If indoor temperature is above temperature set point and

humidity is above humidity set point, Thermidistat™ closes circuits R to G, R to Y/Y2, R to O and Thermidis- tat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system.

D

E

d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (SEE QUICK REFERENCE GUIDE)

F

12 PIN CONNECTOR

(1.) If the indoor temperature is below the temperature set

point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and closes circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling.

Fig. 11—Detail of SPP Printed-Circuit Board

EASY SELECT™CONFIGURATION TAPS FOR 702B & 602B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used. a. AUX HEAT kW/CFM—SELECT HEATER RANGE FOR

e. GAS HEATING MODE

(Occurs if outdoor temperature is below outdoor temperature change over setpoint.)

(1.) Thermostat closes circuit R to W/W1—The unit delivers

SIZE OF ELECTRIC HEATER INSTALLED

the selected gas heat airflow. The IGC will control 45 sec. on delay with no airflow and 45 sec. off delay. f. HEAT PUMP HEATING MODE

Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked with a range of heaters for which airflow (also marked), is approved. For increased comfort, select the narrowest kW range matching the heater size, for example, 0–10 for 10–kW heater. This airflow must be greater than the minimum for CFM for electric heater application with the size system installed for safe and continuous operation. (See Tables 16, 17 & 18 for airflow delivery and minimum CFM.) Note that airflow marked is the

(Occurs if outdoor temperature is above outdoor temperature change over setpoint.)

(1.) Thermidistat™closes circuit R to G and R to Y/Y2–The

unit delivers selected heat pump heating airflow. g. HEATING MODE—SUPER COMFORT HEAT OPERA-

TION

Page 8 of the Bryant 683B user manual — WHEN THERMOSTAT IS SET ON CONTINUOUS FAN
Page 8 · click to enlarge
Page 8

airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ICM will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved (See Fig. 11, A as indicated).

(2.) MED speed—Move connector to MED, 65 percent cooling

mode airflow.

(3.) HI speed—Move connector to HI, 100 percent cooling

mode airflow (See Fig. 11, F as indicated). g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE

The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol.

b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED

The factory setting for air conditioner or heat pump size is the size which matches the model of packaged unit installed. Installer should verify air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes (See Fig. 11, B as indicated).

h. BASIC UNIT CONFIGURATION

The following basic configuration of the indoor motor will provide ARI rated performance of the System. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required, or if system enhancements such as super dehumidify are not needed.

c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED

The type of system will be factory selected (see below for details):

(1.) AUX HEAT kW/CFM-Select the heater range for the size

of electric heater installed (skip this step if no heater is installed).

(1.) AC-Air conditioner (Factory Selected for 702B)

(2.) HP-COMFORT—Heat Pump Comfort provides approxi-

mately 315 CFM per ton for higher normal heating air delivery temperature and provides approximately 350 CFM per ton cooling airflow for good humidity removal.

(2.) AC/HP SIZE-Factory selected to match system size in-

stalled, please verify.

(3.) SYSTEM TYPE-Factory selected AC (702B) or HP-EFF

(602B).

(3.) HP-EFF (Factory Selected for 602B)— Heat Pump Effi-

ciency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton.

(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM

for 036 & 060, and LO for 024 & 030.

(5.) ON/OFF DELAY-Select 0/90 profile.

d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

HIGH AIRFLOW

mostat is set to continuous fan.

The AC/HP CFM Adjust select is factory set to the High-Hi (NOM for 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. CFM Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 11, D as indicated).

i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick

The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort: This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published HSPF or ARI SEER efficiency. The following system configuration is recommended for maxi- mum heating and cooling/dehumidifying comfort (See Fig. 11).

e. ON/OFF DELAY—SELECT DESIRED

TIME DELAY PROFILE

Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 11, E as indicated). Selection options are:

(1.) The standard 90 sec off delay (Factory Setting) at 100

(1.) AUX HEAT kW/CFM-Select the narrowest heater range to

match size of electric heater installed (skip this step if no heater is installed).

percent airflow in cooling or heat pump heating mode.

(2.) A 30 sec cooling delay with no airflow/90 sec off delay at

(2.) AC/HP Size-Factory selected to match system size in-

100 percent airflow profile is used when it is desirable to allow system coils time to heat-up/cool-down in conjunc- tion with the airflow in cooling or heat pump heating mode.

stalled, please verify.

(3.) SYSTEM TYPE-Select system type HP-COMFORT (for

heat pump system) or AC (for air conditioner system).

(3.) A no delay option used for servicing unit or when a

(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).

thermostat is utilized to perform delay functions.

(5.) ON/OFF DELAY-Select ENH profile.

(4.) ENH, enhanced selection, provides a 30 sec cooling on

(6.) CONTINUOUS FAN-Select desired fan speed when ther-

delay with no airflow/ plus 150 sec at 70 percent airflow/ no off delay for added comfort. This will minimize cold blow in heat pump operation (602B only) and could enhance system efficiency.

mostat is set to continuous fan.

(7.) DEHUMIDIFY MODE-Remove J1 jumper to activate.

(8.) LOW VOLTAGE CONNECTIONS-Make connections as

f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED

shown in ELECTRICAL CONNECTIONS section.

WHEN THERMOSTAT IS SET ON CONTINUOUS FAN

(9.) CONFIGURE THERMIDISTAT™(or capable zoning

(1.) LO speed—Factory setting, 50 percent cooling mode

system)-Following its installation instructions for Super Dehumidify and Super Comfort Heat operation.

airflow.

Reference Guide)

Page 9 of the Bryant 683B user manual — HUMIDISTAT CONNECTION
Page 9 · click to enlarge
Page 9

This configuration provides the following comfort enhance- ments:

EASY SELECT BOARD TERMINAL

BLOCK

(a.) A 30 sec blower on delay with 150 sec at 70 percent

airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100 percent airflow reducing the cold blow sensation at start up in heating and allowing the indoor coil to more quickly reach wet coil operating conditions in cooling.

D H J1

HUMIDISTAT

REMOVE

R

(b.) A no blower off delay eliminates cold blow which may

JUMPER

be associated with running the blower after shut down of the compressor and avoids re-evaporation of con- densed moisture after cooling/dehumidifying opera- tion.

A95316

Fig. 13—Humidistat Wiring for De-Humidify Mode-for

702B & 602B

(c.) Lower airflow while the compressor is running to

reduce draft effects and increase heating air tempera- ture and improved humidity control during cooling operation.

standard humidistat. The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode, remove jumper J1 and wire in a standard humidistat ( See Fig. 13).

ACCESSORY INSTALLATION a. ACCESSORY ELECTRIC HEATERS

Electric heaters may be installed with the 702B & 602B units per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits.

b. AUXILIARY TERMINALS

f. DEHUMIDIFY AND SUPER DEHUMIDIFY CAPABILITIES

The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 12). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of the operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.

these models are capable of responding to a signal from indoor system control (thermostat, Thermidistat™, zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.

H. 702B & 602B Sequence Of Operation

c. ELECTRONIC AIR CLEANER CONNECTIONS

a. CONTINUOUS FAN

The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating.

(1.) Thermostat closes circuit R to G—The Blower runs at

continuous fan airflow.

b. COOLING MODE-LOW HUMIDITY

(1.) If indoor temperature is above temperature set point and

d. HUMIDIFIER/HUMIDISTAT CONNECTIONS

humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers cooling airflow.

Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat (See Fig. 12). These terminals are energized with 24-v. when G thermostat signal is present. (See Fig. 11, 12 & 13). Alternately, the 24-v. signal may be sourced from the W and C circuit board connections. When using a Thermidistat™Control, Zone Perfect Plus or Comfort Zone II, the 24-v. signal may be sourced directly from the Thermidis- tat™HUM terminal.

c. COOLING MODE-DEHUMIDIFICATION

(1.) If indoor temperature is above temperature set point and

humidity is above humidity set point, thermostat or Ther- midistat™closes circuits R to G, R to O, and R to Y/Y2 and humidistat or Thermidistat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system. d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (see

HUMIDISTAT

HUM 1

24-VAC

TO HUMIDIFIER

HUM 2

(G)

HUMIDIFIER WIRING

A95317

Fig. 12—Humidifier Wiring for 702B & 602B

(1.) If the indoor temperature is below the temperature set

e. DEHUMIDIFY CAPABILITY WITH STANDARD

point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested

HUMIDISTAT CONNECTION

Latent capacities for these units are better than average systems. If increased latent capacity is an application requirement, the circuit board provides connection terminals for use of a

quick reference guide)

Page 10 of the Bryant 683B user manual — (2.) COOLING MODE—
Page 10 · click to enlarge
Page 10

value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling. e. ELECTRIC HEATING MODE

I. 583B START-UP (ICM FIOP) CHECKING COOLING CONTROL OPERATION-Start and check the unit for proper cooling control operation as follows:

(1.) Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position. Note fan delay time setting selected on the Easy Select™board. (See Easy Select Section.)

(1.) Thermostat closes circuit R to W/W1, or W2—The unit

delivers the selected electric heat airflow. There are no on or off delays. f. HEAT PUMP HEATING MODE (602B only)

(2.) Place SYSTEM switch in COOL position and FAN switch

(1.) Thermostat closes circuits R to G and R to Y/Y2—The unit

in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the time setting selected on Easy Select™board. (See Easy Select Section.)

delivers selected heat pump heating airflow. g. HEAT PUMP HEATING WITH AUXILIARY

ELECTRIC HEAT (602B only)

(1.) Thermostat closes circuits R to G, R to Y/Y2 and R to

W/W1 or W2 (and R to O in the case of defrost). In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.

(3.) When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO position. Observe that unit operates in heating mode when tempera- ture control is set to “call for heating” (above room temperature) and operates in cooling mode when tempera- ture control is set to “call for cooling” (below room temperature).

AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges. The heating operation airflow must produce a temperature rise that falls with in the approved range. Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required. CHECK HEATING CONTROL-Start and check the unit for proper heating control operation as follows. (see furnace lighting instructions located inside burner or blower access panel.):

h. HEATING MODE—SUPER COMFORT HEAT OPERA-

TION

NOTE: The indoor control used, such as a Thermidistat™, must be capable of providing Super Comfort Heat operation mode and control must be configured as outlined in its installation instruc- tions. The system must be installed with appropriate outdoor temperature sensor. Consult indoor control literature to determine if control is capable and for configuration instructions. Consult indoor control instructions and sensor instructions for sensor installation details.

If the outdoor temperature is in the range of 12° to 40° F, the Thermidistat™closes circuit R to Y/Y2 and opens circuit R to G. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full heating requested value. If circuit R to G is open (0-v.) for maximum heating comfort, the motor delivers reduced airflow to maximize the temperature and minimize the draft effect of the heated air leaving the unit.

(1.) Place room thermostat SYSTEM switch in the HEAT

position and the FAN switch in the AUTO position.

(2.) Set the heating temperature control of the thermostat above

room temperature.

(3.) The induced-draft motor will start.

ICM FIOP START-UP ICM General Start Up CHECKING AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with Puron® (R-410A) refrigerant, and is tested and factory sealed. NOTE: Adjustment of the refrigerant charge is not required UNLESS the unit is suspected of not having the proper R-410A charge. The charging label and the tables shown refer to system tempera- tures and pressures. The temperatures and pressures are calculated at rated airflow. When charging unit, set to rated airflow. A refrigerant charging chart label is attached to the outside of the compressor access door. The chart includes the required suction line temperature at given suction line pressures and outdoor ambients. An accurate superheat, thermocouple- or thermistor-type thermometer, and gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement IMPORTANT: When evaluating the refrigerant charge, an indi- cated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insuf- ficient airflow across either one or both coils.

(4.) After a call for heating, the main burner should light with

in 5 sec. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the lockout control, break the 24-v. power to W.

(5.) The indoor fan will turn on 45 sec after the flame has been

established. The indoor fan will turn off according to time delay selected on the Easy Select™board (See Easy Select Section) after the thermostat has been satisfied.

II. 683B START-UP (ICM FIOP) Also refer to the Thermidistat™instructions for start up and check out of the system.

(1.) FAN OPERATION—

The fan button on Thermidistat™switches fan icon between AUTO and ON. While ON is displayed, output will be on, turning fan on. Allow up to 10 sec. after button is pressed for fan to turn on and off. the fan will continue to run for the time setting selected on the Easy Select™ board after AUTO icon is displayed.

(2.) COOLING MODE—

Press MODE button on the Thermidistat™until COOL icon is displayed. Cooling begins within 10 sec. and

Page 11 of the Bryant 683B user manual — III. 702B: START-UP (ICM FIOP)
Page 11 · click to enlarge
Page 11

remains on for 4 minutes. Observe that compressor, outdoor fan and indoor blower motors start after the call for Cooling. At the end of 4 minutes, the cooling cycle stops and the MODE reverts back to OFF. The Indoor Blower continues to run for the time selected on the Easy Select™board after OFF icon is displayed.

(3.) When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in heating mode when tempera- ture control is set to ‘‘call for heating’’ (above room temperature) and operates in cooling mode when tempera- ture control is set to ‘‘call for cooling’’ (below room temperature). NOTE: Once the compressor has started and then has stopped, it will not start again until 5 minutes have elapsed. (The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit between ther- mostat terminal R to terminals Y and G.) These open circuits de-energize contactor coil C and ICM board. The condenser and compressor motors stop. After the time delay setting selected on the Easy Select™board (See Easy Select Section) , the blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat.

(3.) HEAT PUMP HEATING—

Press MODE button on the Thermidistat™until HEAT icon is displayed. Heat pump heating begins within 10 sec. and remains on for 4 minutes. Observe that the compres- sor, outdoor fan and indoor blower come on. At the end of the 4 minutes, heating cycle stops and the MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™Board after the OFF icon is displayed. Heating maybe turned off anytime during the 4 minute cycle by pressing MODE button until OFF is displayed.

(4.) GAS HEAT MODE—

IV. 602B: START-UP (ICM FIOP) CHECKING COOLING AND HEATING CONTROL OPERA- TION– Start and check the unit for proper control operation as follows:

Press MODE button until E-HEAT(Emergency Heat or Back-Up Heat) icon is displayed. Gas heating begins within 10 sec. and remains on for 4 minutes. The induced draft motor should start immediately. The burners should light within 5 sec. of E-HEAT call. The indoor blower will turn on 45 sec. after the flame has been established. Gas heating stops at the end of 4 minutes and MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™Board after the OFF icon is displayed.

(1.) Place room thermostat SYSTEM switch or MODE control

in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down according to time delay selected on the Easy Select™ board (See Easy Select Section) when FAN MODE switch is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (through unit wire G) across the 24-v. secondary of transformer (TRAN). Thermidistat™or Thermostat and Humidistat: When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O, DH, and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (though unit wire G) across the 24-v. secondary of transformer (TRANS).

(5.) AUTOMATIC CHANGE-OVER—

To test AUTO CHANGE-OVER function between COOL and HEAT: Enable the AUTO CHANGE-OVER mode during Thermi- distat™set-up. Refer to the Thermidistat™literature for details. Observe that the unit operates in cooling when in COOL MODE (when setting is below room temperature) and HEAT MODE (when setting is above room tempera- ture).

AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges. The heating operation airflow must produce a temperature rise that falls with in the approved range. Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required.

(3.) Place system switch or MODE control in HEAT position.

Set control above room temperature. Observe that com- pressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down according to time delay selected on the Easy Select™board (See Easy Select Section) when control setting is satisfied.

(4.) When using an automatic changeover room thermostat,

place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to “call for Cooling” (below room temperature), and unit operates in Heating mode when temperature control is set to “call for Heating” (above room temperature). NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit between thermostat terminal R to terminals Y and G. These open circuits de-energize contactor coil C and ICM board. The con- denser and compressor motors stop. After the time delay setting selected on the Easy Select™board (See Easy Select Section) , the

III. 702B: START-UP (ICM FIOP)

CHECKING COOLING CONTROL OPERATION–Start and check the unit for proper cooling control operation as follows:

(1.) Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.

(2.) Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the selected off delay.

Page 12 of the Bryant 683B user manual — CARE AND MAINTENANCE
Page 12 · click to enlarge
Page 12

TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 583B 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 290 290 313 313 321 321 382 382 COMPRESSORS

1 REFRIGERANT (R-410A)

Quantity (lb.) 5.0 5.0 5.5 5.5 6.9 6.9 9.0 9.0

REFRIGERANT METERING DEVICE

Orifice ID (in.) Check-Flo-Rater™Piston

.057 .065 .065 .070 .070

CONDENSER COIL

Rows...Fins/in. Face Area (sq ft)

1...17 10.9 1...17 10.9 1...17 12.7 1...17 12.7 2...17 9.1 2...17 9.1 2...17 12.3 2...17 12.3

CONDENSER FAN

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

Nominal Cfm Diameter (in.) Motor HP (Rpm)

EVAPORATOR COIL

Rows...Fins/in. Face Area (sq ft)

3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 4.7 3...15 4.7

EVAPORATOR BLOWER

800 10 X 10 1/2

800 10 X 10 1/2

1000 10 X 10 1/2

1000 10 X 10 1/2

1200 11 X 10 3/4

1200 11 X 10 3/4

1400 11 X 10 3/4

1400 11 X 10 3/4

Size (in.) Motor (HP)

FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)

2...44 2...50 2...38 2...46 2...44 2...50 2...38 2...46 2...38 2...46 3...38 3...46 2...38 2...46 3...38 3...46

Natural Gas Burner Orifice No. (Qty...Drill Size)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-

PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat. The 5 minute compressor delay also applies to heat pump heating mode.

ELECTRICAL DATA & SCHEMATICS—ICM FIOP

I. PHYSICAL DATA & ELECTRICAL SCHEMATICS Use the Physical Data and Electrical Tables on the following pages for information that applies to Bryant Puron® units with the ICM indoor motor FIOP.

To clean the blower motor and wheel:

AIRFLOW & TEMPERATURE RISE TABLES—ICM FIOP

1. 1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

II. TABLES FOR SYSTEM SET-UP Use the Airflow and Temperature Rise Tables on the following pages for information that applies to Bryant Puron® units with the ICM indoor motor FIOP.

b. Carefully pivot blower access panel outward towards the

electrical box. Route wiring above blower access panel.

c. Disconnect the 5 and 16 pin plugs at the blower motor.

d. On all units, remove blower assembly from unit. Re-

move screws securing blower to vertical partition and slide assembly out. Be careful not to tear insulation in blower compartment.

CARE AND MAINTENANCE

Indoor Blower and Motor NOTE: All motors are pre-lubricated. Do not attempt to lubricate these motors. For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.

e. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

Show 8 more labels / short text on this page
Scroll · Quantity · Nominal Airflow (Cfm) · Propane Gas · HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 13 of the Bryant 683B user manual — TROUBLESHOOTING
Page 13 · click to enlarge
Page 13

TABLE 2—ICM FIOP PHYSICAL DATA—UNIT 583B (CONTINUED)

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 583B 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 4 4 4 5 5 5 OPERATING WEIGHT (lb.) 421 421 421 468 468 468 COMPRESSORS

1 REFRIGERANT (R-410A)

Quantity (lb.) 9.5 9.5 9.5 10.0 10.0 10.0

REFRIGERANT METERING DEVICE

Orifice ID (in.) Check-Flo-Rater™Piston

.073 .073 .073 .086 .086 .086

CONDENSER COIL

Rows...Fins/in. Face Area (sq ft)

2...17 12.3 2...17 12.3 2...17 12.3 2...17 16.4 2...17 16.4 2...17 16.4

CONDENSER FAN

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

Nominal Cfm Diameter (in.) Motor Hp (Rpm)

EVAPORATOR COIL

Rows...Fins/in. Face Area (sq ft)

4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7

EVAPORATOR BLOWER

1600 11 X 10 3/4

1600 11 X 10 3/4

1600 11 X 10 3/4

2000 11 X 10 1.0

2000 11 X 10 1.0

2000 11 X 10 1.0

Size (in.) Motor (HP)

FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)

3...38 3...46 3...33 3...42 3...31 3...41 3...38 3...46 3...33 3...42 3...31 3...41

Natural Gas Burner Orifice No. (Qty...Drill Size)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

TABLE 3—583B WITH ICM FIOP ELECTRICAL DATA

VOLTAGE

RANGE COMPRESSOR OUTDOOR FAN

INDOOR FAN

MOTOR POWER SUPPLY

UNIT SIZE 583B V-PH-HZ

MOTOR

MIN MAX RLA LRA FLA FLA MCA MAX FUSE OR CKT. BKR. 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 22.1 30 030 208/230–1–60 187 253 14.7 73.0 0.9 4.3 23.6 30 036 208/230–1–60 187 253 15.4 83.0 0.9 6.8 27.0 35 042 208/230–1–60 187 253 18.6 105.0 0.9 6.8 31.0 40 048 208/230–1–60 187 253 20.5 109.0 1.6 6.8 34.0 40 060 208/230–1–60 187 253 27.6 158.0 1.6 9.2 45.2 60

f. Loosen set-screw that secures wheel to motor shaft,

d. Reassemble wheel into housing.

remove screws that secure motor mount brackets to blower housing, and slide motor and motor mount out of blower housing.

e. Reassemble motor into housing. Be sure set-screw(s) are

tightened on motor shaft flats and not on round part of shaft.

2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation.

f. Pivot blower access panel back into place. Adjust wire

assemblies so that wiring follows proper pathways.

g. Reinstall unit access panel.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.

3. Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.

TROUBLESHOOTING

START-UP CHECKLIST

Show 8 more labels / short text on this page
Scroll · Quantity · Nominal Airflow (Cfm) · Propane Gas · HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 14 of the Bryant 683B user manual — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B
Page 14 · click to enlarge
Page 14
Bryant 683B — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B diagram (page 14)
Fig. 3

Fig. 14—ICM FIOP Electric Schematic—Unit 583B

Page 15 of the Bryant 683B user manual — LOSS-OF-CHARGE/LOW-
Page 15 · click to enlarge
Page 15

TABLE 4—ICM FIOP PHYSICAL DATA—UNIT 683B

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 024040 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 310 324 324 321 321 380 380 COMPRESSORS

1 REFRIGERANT (R-410A)

Quantity (lb.) 7.0 8.9 8.9 9.3 9.3 9.5 9.5

REFRIGERANT METERING DEVICE

Orifice Indoor (in.) Check-Flo-Rater™Piston

0.061 0.061 0.061 0.067 0.067 0.073 0.073

REFRIGERANT METERING DEVICE

Orifice Outdoor (in.) Check-Flo-Rater™Piston

0.032 (2) 0.040 (2) 0.040 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.038 (2)

OUTDOOR COIL

2...17 8.5 2...17 10.3 2...17 10.3 2...17 10.3 2...17 10.3 2...17 13.5 2...17 13.5

Rows...Fins/in. Face Area (sq ft)

OUTDOOR FAN

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2500 22 1/4 (1100)

2500 22 1/4 (1100)

2350 22 1/8 (825)

2350 22 1/8 (825)

Nominal Cfm Diameter (in.) Motor Hp (Rpm)

INDOOR COIL Rows...Fins/in. Face Area (sq ft)

3...15 3.7 3...15 3.7 3...15 3.7 4...15 3.7 4...15 3.7 3...15 4.7 3...15 4.7

INDOOR BLOWER Nominal Airflow (Cfm)

800 10 X 10 1/2

1000 10 X 10 1/2

1000 10 X 10 1/2

1200 11 X 10 3/4

1200 11 X 10 3/4

1400 11 X 10 3/4

1400 11 X 10 3/4

Size (in.) Motor (HP)

FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)

2...44 2...50 2...44 2...50 2...38 2...46 2...38 2...46 3...38 3...46 2...38 2...46 3...38 3...46

Natural Gas Burner Orifice No. (Qty...Drill Size)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-

PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

Show 7 more labels / short text on this page
Scroll · Quantity · Propane Gas · HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 16 of the Bryant 683B user manual — TABLE 6—683B WITH ICM FIOP ELECTRICAL DATA
Page 16 · click to enlarge
Page 16

TABLE 5—ICM FIOP PHYSICAL DATA—UNIT 683B (CONTINUED)

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 4 4 4 5 5 5 OPERATING WEIGHT (lb.) 409 409 409 504 504 504 COMPRESSORS

1 REFRIGERANT (R-410A)

Quantity (lb.) 10.6 10.6 10.6 12.4 12.4 12.4

REFRIGERANT METERING DEVICE

Orifice Indoor (in.) Check-Flo-Rater™Piston

.076 .076 .076 .088 .088 .088

REFRIGERANT METERING DEVICE

Orifice Outdoor (in.) Check-Flo-Rater™Piston

0.046 (2) 0.046 (2) 0.046 (2) 0.052 (2) 0.052 (2) 0.052 (2)

OUTDOOR COIL

2...17 13.5 2...17 13.5 2...17 13.5 2...17 15.4 2...17 15.4 2...17 15.4

Rows...Fins/in. Face Area (sq ft)

OUTDOOR FAN

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

Nominal Cfm Diameter (in.) Motor Hp (Rpm)

INDOOR COIL Rows...Fins/in. Face Area (sq ft)

4...15 4.7 4...15 4.7 4...15 4.7 4...15 5.7 4...15 5.7 4...15 5.7

INDOOR BLOWER Nominal Airflow (Cfm)

1600 11 X 10 3/4

1600 11 X 10 3/4

1600 11 X 10 3/4

1750 11 X 10 1.0

1750 11 X 10 1.0

1750 11 X 10 1.0

Size (in.) Motor (HP)

FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)

3...38 3...46 3...33 3...42 3...31 3...41 3...38 3...46 3...33 3...42 3...31 3...41

Natural Gas Burner Orifice No. (Qty...Drill Size)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

TABLE 6—683B WITH ICM FIOP ELECTRICAL DATA

VOLTAGE

RANGE COMPRESSOR OUTDOOR FAN

INDOOR FAN

MOTOR POWER SUPPLY

UNIT SIZE 683B V-PH-HZ

MOTOR

MIN MAX RLA LRA FLA FLA MCA MAX FUSE OR CKT. BKR. 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 22.1 30 030 208/230–1–60 187 253 15.9 73.0 0.9 4.3 25.1 35 036 208/230–1–60 187 253 16.9 83.0 1.6 6.8 29.5 40 042 208/230–1–60 187 253 22.4 105.0 0.9 6.8 35.7 50 048 208/230–1–60 187 253 21.3 109.0 1.6 6.8 35.0 50 060 208/230–1–60 187 253 27.6 158.0 1.6 9.2 45.3 60

Show 7 more labels / short text on this page
Scroll · Quantity · Propane Gas · HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 17 of the Bryant 683B user manual — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B
Page 17 · click to enlarge
Page 17
Bryant 683B — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B diagram (page 17)
Fig. 4

Fig. 15—ICM FIOP Electric Schematic—Unit 683B

Page 18 of the Bryant 683B user manual — LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
Page 18 · click to enlarge
Page 18

TABLE 7—ICM FIOP PHYSICAL DATA—UNIT 702B

THIS DATA APPLIES TO 702B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb) 270 291 299 321 326 399 COMPRESSOR Scroll REFRIGERANT (R-410A)

Quantity (lb) 5.0 5.5 6.9 9.0 9.5 10.0

Check-Flo-Rater™Piston .057 .057 .065 .070 .073 .086 CONDENSER COIL

REFRIGERANT METERING DEVICE

Orifice ID (in.)

1...17 10.9 1...17 12.7 2...17 9.1 2...17 12.3 2...17 12.3 2...17 16.4

Rows...Fins/in. Face Area (sq. ft.)

CONDENSER FAN

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

2350 22 1/8 (825)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

Nominal Cfm Diameter (in.) Motor Hp (Rpm)

EVAPORATOR COIL

3...15 3.7 3...15 3.7 3...15 3.7 3...15 4.7 4...15 4.7 4...15 4.7

Rows...Fins/in. Face Area (sq. ft.)

EVAPORATOR BLOWER

Size (in.) Motor (HP)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

Show 11 more labels / short text on this page
800 10x10 1/2 · 1000 10x10 1/2 · 1200 10x10 3/4 · 1400 11x10 3/4 · 1600 11x10 3/4 · 2000 11x10 1 · Nominal Airflow (Cfm) · HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 19 of the Bryant 683B user manual — TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA
Page 19 · click to enlarge
Page 19

TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA

VOLTAGE

OUTDOOR

INDOOR

ELECTRIC

SINGLE POINT POWER SUPPLY

RANGE COMPRESSOR

FAN MOTOR

FAN MOTOR

UNIT SIZE 702B V-PH-HZ

HEAT

MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP

-/- 3.8/5.0 5.4/7.2 7.5/10.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7

22.1/22.1 27.9/31.4 37.8/42.9 50.5/57.5

30/30 30/35 40/50 60/60

–

024 208/230–1–60 187 253 13.5 61.0 0.9 4.3

-/- 3.8/5.0 5.4/7.2 7.5/10.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7

23.5/23.5 27.9/31.4 37.8/42.9 50.5/57.5

30/30 30/35 40/50 60/60

–

030 208/230–1–60 187 253 14.7 73.0 0.9 4.3

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5

27.0/27.0 31.1/34.5 40.9/46.0 53.6/60.6 76.2/86.6

35/35 35/40 50/50 60/– –

–/70 80/90

036 208/230–1–60 187 253 15.4 83.0 0.9 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

31.0/31.0 31.1/34.5 40.9/46.0 53.6/60.6 76.2/86.6 98.8/112.7

40/10 40/40 50/50 60/– – –

–/70 90/90 100/125

042 208/230–1–60 187 253 18.6 105.0 0.9 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

34.0/34.0 34.0/34.5 40.9/46.0 53.6/60.6 76.2/86.6 98.8/112.7

40/40 40/40 50/50 60/- – –

–/70 90/90 100/125

048 208/230–1–60 187 253 20.5 109.0 1.6 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

45.2/45.2 45.2/45.2 43.8/48.9 56.5/63.5 79.1/89.5 101.6/115.5

60/60 60/60 50/50 60/- – –

–/70 90/90 110/125

060 208/230–1–60 187 253 27.6 158.0 1.6 9.1

* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer to Multiplication FactorsTable 23.

Page 20 of the Bryant 683B user manual — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B
Page 20 · click to enlarge
Page 20
Bryant 683B — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B diagram (page 20)
Fig. 5

Fig. 16—ICM FIOP Electrical Schematic—702B

Page 21 of the Bryant 683B user manual — LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
Page 21 · click to enlarge
Page 21

TABLE 9—ICM FIOP PHYSICAL DATA—UNIT 602B

THIS DATA APPLIES TO 602B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 602B024 602B030 602B036 602B042 602B048 602B060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 299 320 328 350 355 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REFRIGERANT R-410A REFRIGERANT METERING DEVICE Check-Flo-Rater™ Refrigerant (R-410A) Quantity (lb.) 7.0 8.9 9.3 9.5 10.6 12.4 ORIFICE ID (in.) 0.061 0.061 0.067 0.073 0.076 0.088 ORIFICE OD (in.) 0.032 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.046 (2) 0.052 (2) OUTDOOR COIL

2...17 8.5 2...17 10.3 2...17 10.3 2...17 13.5 2...17 13.5 2...17 15.4

Rows... Fins/in. face area (sq. ft.)

OUTDOOR FAN Nominal Airflow (CFM)

2350 22 1/8 (825)

2350 22 1/8 (825)

2800 22 1/4 (1100)

2500 22 1/8 (825)

3300 22 1/4 (1100)

3300 22 1/4 (1100)

Diameter Motor HP (RPM)

INDOOR COIL Rows... Fins/in. face area (sq. ft.)

3...15 3.7 3...15 3.7 4...15 3.7 3...15 4.7 4...15 4.7 4...15 5.7

INDOOR BLOWER Nominal Airflow (CFM)

800 10 X 10 1/2

1000 10 X 10 1/2

1200 10 X 10 3/4

1400 11 X 10 3/4

1600 11 X 10 3/4

2000 11 X 10 1

Size (in.) Motor (HP)

610 ± 15 420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

20 ± 5 45 ± 10

RETURN-AIR FILTERS (in.)

throwaway 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

Show 4 more labels / short text on this page
HIGH-PRESSURE SWITCH (psig) · Cutout Reset (Auto) · (Liquid Line) (psig) · Cutout Reset (Auto)
Page 22 of the Bryant 683B user manual — TABLE 10—602B WITH ICM FIOP ELECTRICAL DATA
Page 22 · click to enlarge
Page 22

TABLE 10—602B WITH ICM FIOP ELECTRICAL DATA

VOLTAGE

OUTDOOR

INDOOR

ELECTRIC

SINGLE POINT POWER SUPPLY

RANGE COMPRESSOR

FAN MOTOR

FAN MOTOR

UNIT SIZE 602B V-PH-HZ

HEAT

MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP

-/- 3.8/5.0 5.4/7.2 7.5/10.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7

22.1/22.1 44.6/48.1 54.5/59.6 67.2/74.2

30/30 50/50 60/– –

– – –/70 70/80

024 208/230–1–60 187 253 13.5 61.0 0.9 4.3

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5

25.1/25.1 47.6/51.1 57.4/62.6 70.2/77.2 92.8/103.2

30/30 60/60 – – –

– – 70/70 80/80 100/110

030 208/230–1–60 187 253 15.9 73.0 0.9 4.3

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5

29.5/29.5 52.1/55.6 61.9/67.0 74.7/81.6 97.2/107.7

40/40 60/60 – – –

– – 70/80 80/90 100/110

036 208/230–1–60 187 253 16.9 83.0 1.6 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

35.7/35.7 58.3/61.7 68.1/73.2 80.8/87.8 103.4/113.0 126.0/139.9

50/50 –

– 70/70 80/80 90/90 110/125 150/150

042 208/230–1–60 187 253 22.4 105.0 0.9 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

35.0/35.0 57.6/61.1 67.4/72.5 80.2/87.1 102.7/113.2 125.3/139.2

50/50 –

– 70/70 80/80 90/90 110/125 150/150

048 208/230–1–60 187 253 21.3 109.0 1.6 6.8

-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0

-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3

45.1/45.1 67.7/71.1 77.7/82.8 90.2/97.2 112.8/123.2 135.4/149.3

60/60 –

– 80/80 90/90 100/110 125/125 150/150

060 208/230–1–60 187 253 27.6 158.0 1.6 9.2

* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer to Multiplication FactorsTable 23.

Page 23 of the Bryant 683B user manual — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B
Page 23 · click to enlarge
Page 23
Bryant 683B — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B diagram (page 23)
Fig. 6

Fig. 17—ICM FIOP Electrical Schematic—602B

Page 24 of the Bryant 683B user manual — TABLE 13—583B & 683B GAS HEATING ICM AIRFLOW
Page 24 · click to enlarge
Page 24

TABLE 11–583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY)

DRY COIL ICM AIRFLOW

SMALL CABINET

CFM ADJUST

PIN SELECT LO PIN NOM PIN HI PIN

UNIT SIZE

EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0

COOLING † 745 675 – 835 750 690 940 880 815 COOLING DEHUMIDIFY 675 625 – 675 650 600 755 730 705

HEAT PUMP COMFORT (683B Only) 670 605 – 740 690 635 845 795 735

COOLING † 940 860 785 1020 965 895 1185 1100 1010 COOLING DEHUMIDIFY 820 785 735 820 800 770 955 920 880

HEAT PUMP COMFORT (683B Only) 850 780 745 935 905 845 1055 1040 955

COOLING † 1025 935 – 1145 1085 1005 1320 1260 1180 COOLING DEHUMIDIFY 925 885 – 925 900 870 1060 1040 1010

HEAT PUMP COMFORT (683B Only) 955 880 – 1075 990 920 1220 1180 1125

† On 683B Only Heat Pump Efficiency and Cooling pin selections deliver equal airflow

TABLE 12—583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY)

DRY COIL ICM AIRFLOW

LARGE CABINET

CFM ADJUST

PIN SELECT LO PIN NOM PIN HI PIN

UNIT SIZE

EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0

COOLING † 1100 1225 1410 COOLING DEHUMIDIFY 980 980 1125

HEAT PUMP COMFORT (683B Only) 990 1100 1265

COOLING † 1260 1400 1610 COOLING DEHUMIDIFY 1120 1120 1290

HEAT PUMP COMFORT (683B Only) 1135 1260 1450

COOLING † 1575 1750 2010 COOLING DEHUMIDIFY 1400 1400 1610

HEAT PUMP COMFORT (683B Only) 1415 1575 1810

† On 683B Only Heat Pump Efficiency and Cooling pin selections deliver equal airflow

TABLE 13—583B & 683B GAS HEATING ICM AIRFLOW

SMALL CABINET

EASY SELECT™ BOARD SETTING (CFM) 700 800 1100 1250

Static Pressure 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0

024 040 – – – 855 770 710 – 060 – 1020 890 835 – – –

030 040 – – – 880 840 805 – 060 – 1030 970 910 – – –

036 060 – 1035 995 955 – – – 090 – 1170 1110 1025

External · Unit Size · Gas Heat Size

Page 25 of the Bryant 683B user manual — SMALL CABINET
Page 25 · click to enlarge
Page 25

TABLE 14—583B & 683B GAS HEATING ICM AIRFLOW

LARGE CABINET

EASY SELECT™ BOARD SETTING (CFM) 1000 1250 1600 1750 1800

Static Pressure 0.0–1.0

042 060 1000 – 090 – 1250 – – –

048 090 – 1250 – – – 115 – – 1600 – – 130 – – – 1750 –

060 090 – 1250 – – – 115 – – 1600 – – 130 – 1800

TABLE 15—583B & 683B ICM AIR FLOW VS. TEMPERATURE RISE CHART

RATED GAS INPUT RATE

AIRFLOW SETTING

CALCULATED TEMPERATURE

MIN. TEMP

MAX TEMP

MAX DISCH.

UNIT COOLING

SIZE

EASY SELECT™

(X 1000)

(SCFM)

RISE

RISE

RISE

TEMP

024 40 800 36.5 20 50 175 60 (583B Only) 1100 40 35 65 165

030 40 800 36.5 20 50 175 60 1100 40 35 65 165

036 60 1100 40 25 55 165 90 1200 54 45 75 175

583B & 683B

042 60 1000 44 20 50 165 90 1250 53 35 65 170

048 90 1250 53 25 55 165 115 1600 53 35 65 170 130 1750 54 40 70 175

060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175

TABLE 16—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW

SMALL CABINET

CFM ADJUST

PIN SELECT LO PIN NOM PIN HI PIN

UNIT SIZE

EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0

COOLING † 800 725 – 885 805 730 990 930 855 COOLING DEHUMIDIFY 715 670 – 715 695 645 795 775 745

HEAT PUMP COMFORT (602B Only) 720 660 – 790 745 685 890 850 785

COOLING † 1010 920 825 1105 1030 930 1255 1160 1050 COOLING DEHUMIDIFY 890 845 795 890 865 825 1010 980 925

HEAT PUMP COMFORT (602B Only) 945 850 765 1020 965 895 1140 1105 995

COOLING † 1110 1025 970 1235 1175 1115 1400 1355 1280 COOLING DEHUMIDIFY 990 960 910 990 975 940 1125 1110 1085

HEAT PUMP COMFORT (602B Only) 1035 975 910 1160 1080 1020 1305 1275 1220

† Heat Pump Efficiency and Cooling pin selections deliver equal airflow

External · Unit Size · Gas Heat Size

Page 26 of the Bryant 683B user manual — LARGE CABINET
Page 26 · click to enlarge
Page 26

TABLE 17—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW

LARGE CABINET

CFM ADJUST

PIN SELECT LO PIN NOM PIN HI PIN

UNIT SIZE

EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0

COOLING † 1100 1225 1410 COOLING DEHUMIDIFY 980 980 1125

HEAT PUMP COMFORT (602B Only) 990 1100 1265

COOLING † 1260 1400 1610 COOLING DEHUMIDIFY 1120 1120 1290

HEAT PUMP COMFORT (602B Only) 1135 1260 1450

COOLING † 1575 1750 2010 COOLING DEHUMIDIFY 1400 1400 1610

HEAT PUMP COMFORT (602B Only) 1415 1575 1810

† Heat Pump Efficiency and Cooling pin selections deliver equal airflow

TABLE 18—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)

UNIT SIZE 024 030 036 042 048 060

602B 750 1025 1250 1285 1710 1800 702B 750 750 1250 1205 1500 1800

TABLE 19—ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)

SMALL CABINET

STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0.00 0.02 0.04 0.06 0.07 7.5 kW 0.00 0.02 0.03 0.05 0.07 0.08 0.09 10 kW 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.11 15 kW 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 20 kW 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19

TABLE 20— ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)

LARGE CABINET

STATIC CFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 5 kW 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 7.5 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 10 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 15 kW 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 20 kW 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16

Page 27 of the Bryant 683B user manual — TABLE 23—ELECTRIC HEATER MULTIPLICATION FACTORS
Page 27 · click to enlarge
Page 27

TABLE 21—ICM FIOP WET COIL PRESSURE DROP (IN. WG)

UNIT SIZE

STANDARD CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 024 0.005 0.007 0.010 0.012 0.015 – 030 – 0.007 0.010 0.012 0.015 0.018 0.021 0.024 – 036 – – – 0.019 0.023 0.027 0.032 0.037 0.042 0.047 – 042 – 0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043 – – – 048 – 0.027 0.032 0.036 0.041 0.046 0.052 0.057 0.063 0.068 – 060 – 0.029 0.032 0.036 0.040 0.045 0.049 0.053

TABLE 22—FILTER PRESSURE DROP TABLE (IN. WG)

FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — 20 X 24 X 1 — 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — 24 X 30 X 1 — 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18

TABLE 23—ELECTRIC HEATER MULTIPLICATION FACTORS

HEATER KW

VOLTAGE DISTRIBUTION

MULTIPLICATION

RATING

FACTOR

200 .69 208 .75 230 .92 240 1.00

Example: 15.0 kW (at 240-v.) heater on 208-v. = 15.0 (.75 mult. factor) = 11.25 capacity at 208-v.

Page 28 of the Bryant 683B user manual — 12 PIN CONNECTOR
Page 28 · click to enlarge
Page 28

QUICK REFERENCE GUIDE SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES

AND SUPER HUMIDITY CONTROL IN COOLING

EASY SELECT BOARD

9 PIN CONNECTOR

1. Configuration Taps (See Installation Instructions, for detailed description.)

ICM PRINTED CIRCUIT BOARD

A. AUX HEAT - Set for heater size (Ex: 0-10 for 10 kw) B. AC/HP SIZE - Set for size of outdoor unit C. SYSTEM TYPE - Select "HP COMFORT" D. AC/HP CFM ADJUST - Select "LO" E. ON/OFF DELAY - Select "ENH" F. CONTINUOUS FAN - Select desired speed 2. Remove Jumper J1 to activate all dehumidify modes. 3. Complete wiring and install outdoor temperature sensor according to Installation Instructions.

SEC1 SEC2

J1

EASY SELECT

TM

AUX HEAT KW/CFM 0-30 1075

0-20 875 0-10 725

A

VIO

AC/HP SIZE

036 030 024 018

B

BLU

SYSTEM TYPE

DH R W1 W2 Y1 Y/Y2 G O C

AC HP-COMFORT HP-EFF

THERMIDISTAT™ CONTROL SETTINGS

ORN

AC/HP CFM ADJUST

D

NOM HI

LO

1. Set "DIP Switches" - Set the dip switches (back of Thermidistat Control Board) appropriately for specific system being installed.

BLK

ON/OFF DELAY

2. Thermidistat Control Configurations (See Thermidistat™ Control Installation Instructions for detailed description.)

0 90 30 90 0 0

J2

E

ENH

WHT

  • Option 5 (Variable Speed Motors) - set to ON
  • Option 7 (Super Dehumidify) - set to ON
  • Option 12 (Heaters during Defrost) - setting "2" is suggested for all heaters
  • Option 16 - Heat pump systems set to ON for warmer heat below 40 ° F.
  • Option 17 - Select programmable or non-programmable mode.

CONTINUOUS FAN

AUX1 HUM1

F

MED HI YEL LO

HUM2 YEL

AUX2

24VAC

HEATER/MOTOR

GRY

3. Set desired humidity level on front of Thermidistat (50 to 55% RH recommended). For dehumidification in cooling, both "dhu" and "cool" must be displayed.

12 PIN CONNECTOR

ICM QUICK REFERENCE GUIDE

TABLE 24—TROUBLESHOOTING CHART

Bryant 683B — 12 PIN CONNECTOR diagram (page 28)
Fig. 7

Blower wheel not secured to shaft Inspect and properly tighten blower wheel to shaft Insufficient voltage at motor Determine cause and correct Power connectors not properly seated Connectors should snap easily; do not force

0-5 625

Page 29 of the Bryant 683B user manual — AC HP Size
Page 29 · click to enlarge
Page 29

START-UP CHECKLIST (Remove and Store in Job File) I. Preliminary Information MODEL NO.: SERIAL NO.: DATE: TECHNICIAN:

II. PRE-START-UP (Insert checkmark in box as each item is completed) ( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE) ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS ( ) MAKE SURE THAT - ON 060 SIZE PURON HEATPUMP, ONLY-THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED.

III. START-UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR (EVAPORATOR) FAN AMPS TEMPERATURES OUTDOOR (CONDENSER) AIR TEMPERATURE DB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB HEAT PUMP SUPPLY AIR GAS HEAT SUPPLY AIR ELECTRIC HEAT SUPPLY AIR PRESSURES GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE IN. WG REFRIGERANT SUCTION PSIG SUCTION LINE TEMP* REFRIGERANT DISCHARGE PSIG DISCHARGE TEMP† ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TEMPERATURE RISE TEMPERATURE RISE (LITERATURE) RANGE MEASURED TEMPERATURE RISE *Measured at suction inlet to compressor †Measured at liquid line leaving condenser.

EASY SELECT

Heat Settings

IV. EASY SELECT SETTINGS FULL UNIT MODEL NUMBER: ENTER AVAILABLE HEATSETTINGS ENTER AVAILABLE AIRFLOW HEAT AIR PIN CONNECTION SETTING ENTER AVAILABLE SIZES SIZE PIN CONNECTION SETTING TYPE PIN CONNECTION SETTING ADJUST PIN CONNECTION SETTING DELAY PIN CONNECTION SETTING (0/0 or 0/90 for gas/electric models) CONTINOUS FAN PIN CONNECTION SETTING

AC HP Size

System Type AC HP-Comfort HP.Eff AC/HP CFM Adjust Norm Lo Hi On/Off Delay

0⁄90 30⁄90 0⁄0 ENH Continous Fan Lo Med Hi

Page 30 of the Bryant 683B user manual — TABLE 1—ICM FIOP PHYSICAL DATA—UNIT 583B
Page 30 · click to enlarge
Page 30

© 2001 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —30— Printed in U.S.A. ii583b243 Catalog No. 5358-308

Ask about the Bryant 683B

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 683B

Be the first to ask — other owners or our team will answer.

Original document

Bryant 683B manual PDF

30 pages·809 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…