Official user manual

Bryant 663C

12 pages·136 KB·Heat Pump·PDF·ENDEFRITNLJA
Bryant 663C
Table of Contents 80 sections installation and start-up instructions 12 SEER SPLIT-SYSTEM HEAT PUMP · INSTALLATION I. CHECK EQUIPMENT AND JOB SITE · OUTDOOR WALL INDOOR WALL · CAULK · … ShowHide
installation and start-up instructions 12 SEER SPLIT-SYSTEM HEAT PUMPp.1INSTALLATION I. CHECK EQUIPMENT AND JOB SITEp.1OUTDOOR WALL INDOOR WALLp.2CAULKp.2LIQUID TUBEp.2VAPOR TUBE INSULATIONp.2THROUGH THE WALLp.2JOISTp.2HANGER STRAP (AROUND VAPORp.2INSULATIONp.2VAPOR TUBEp.2DIMENSIONS (IN.)p.2MINIMUM MOUNTING PADp.2TIEDOWN KNOCKOUT LOCATIONSp.2UNIT SIZEp.2DIMENSIONSp.2A B Cp.2SUSPENSIONp.2V. ELEVATE UNITp.2II. INSTALL ON A SOLID, LEVEL MOUNTING PADp.2VI. REMOVE INDOOR CHECK-FLO-RATER® PISTON AND INSTALL TXVp.2III. CLEARANCE REQUIREMENTSp.2IV. OPERATING AMBIENTSp.2SENSING BULBp.3EQUALIZER TUBEp.3VIII. CHECK DEFROST THERMOSTATp.3IX. MAKE PIPING CONNECTIONSp.3X. MAKE ELECTRICAL CONNECTIONSp.4→ TABLE 2—ACCESSORY USAGEp.4REQUIRED FORp.4LOW-AMBIENT APPLICATIONSp.4LONG-LINE APPLICATIONS*p.4BURIED LINE APPLICATIONS†p.4ACCESSORYp.4(BELOW 55°F)p.4(OVER 50 FT)p.4XIII. START-UPp.5DISCONNECT PER N. E. C. AND/OR LOCAL CODESp.5CONTACTORp.5FIELD POWERp.5WIRINGp.5FIELD GROUNDp.5GROUND LUGp.5COOLINGp.5XI. COMPRESSOR CRANKCASE HEATERp.5HEATINGp.5XII. INSTALL ELECTRICAL ACCESSORIESp.5BRYANT PROGRAMMABLEp.6ONE OUTDOOR THERMOSTATp.6THERMOSTATp.6FA, FB, FC, FD, FF, FHp.6FAN COILp.6FA, FB, FC,p.6MODEL HPp.6FD, FF, FHp.6TWO OUTDOOR THERMOSTATSp.6FK4C FAN COILp.6OTHER HP THERMOSTATp.7IF AVAILABLEp.7BRYANT DUAL FUEL THERMOSTATp.8TWO-STAGE OR VARIABLE SPEEDp.8SINGLE-STAGEp.8MODEL DFp.8FURNACE HEAT PUMPp.8FA, FB, FC, FHp.9FA, FB, FC, FH FAN COIL WITHp.9WITH SMARTp.9SMART HEATp.9HEATp.9FAN COIL SMART HEATp.9SUPPLEMENTALp.9WIRING DIAGRAM NOTES:p.11FOR EXAMPLE: O/W2 MEANS Op.11O/W2 MEANS W2p.11LEGENDp.1124 VOLT FACTORY WIRINGp.1124 VOLT FIELD WIRINGp.11FIELD SPLICE CONNECTIONp.11OUTDOOR THERMOSTATp.11EHRp.11
Page 1 of the Bryant 663C user manual — INSTALLATION I. CHECK EQUIPMENT AND JOB SITE
Page 1 · click to enlarge
Page 1

installation and start-up instructions 12 SEER SPLIT-SYSTEM HEAT PUMP

Bryant 663C — installation and start-up instructions 12 SEER SPLIT-SYSTEM HEAT PUMP diagram (page 1)
Fig. 1 · installation and start-up instructions 12 SEER SPLIT…
CancelsII 661C-18-2 II 663C-18-1
Bryant 663C — installation and start-up instructions 12 SEER SPLIT-SYSTEM HEAT PUMP diagram (page 1)
Fig. 2 · installation and start-up instructions 12 SEER SPLIT…

SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.

Fig. 1—Model 663C

7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.) 10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation. When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion, check refrigerant charge using charging information located on control box cover. IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all residential applications including long line. IMPORTANT: Always install a liquid-line filter drier. Refer to Product Data Sheet for appropriate part number. Obtain filter drier from service parts or your distributor or branch.

→

INSTALLATION RECOMMENDATIONS NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where unit operation sounds may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit.

INSTALLATION I. CHECK EQUIPMENT AND JOB SITE

3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.

A. Unpack Unit Move to final location. Remove carton taking care not to damage unit. B. Inspect Equipment

4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.) 6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit service panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Page 2 of the Bryant 663C user manual — IV. OPERATING AMBIENTS
Page 2 · click to enlarge
Page 2

Avoid contact between tubing and structure NOTE:

Bryant 663C — OUTDOOR WALL INDOOR WALL diagram (page 2)
Fig. 3

OUTDOOR WALL INDOOR WALL

CAULK

LIQUID TUBE

VAPOR TUBE INSULATION

THROUGH THE WALL

Bryant 663C — OUTDOOR WALL INDOOR WALL diagram (page 2)
Fig. 4

JOIST

HANGER STRAP (AROUND VAPOR

INSULATION

VAPOR TUBE

DIMENSIONS (IN.)

MINIMUM MOUNTING PAD

TIEDOWN KNOCKOUT LOCATIONS

UNIT SIZE

LIQUID TUBE

DIMENSIONS

A B C

SUSPENSION

018 22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8 024–060 30 X 30 6-1/2 23-1/2 20

Fig. 3—Mounting Unit to Pad

Fig. 2—Connecting Tubing Installation

V. ELEVATE UNIT

→

II. INSTALL ON A SOLID, LEVEL MOUNTING PAD

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location.

In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.

On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

VI. REMOVE INDOOR CHECK-FLO-RATER® PISTON AND INSTALL TXV

Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind baffle construction.

For TXV kit part number and charging instructions, refer to TXV label in outdoor unit. If indoor unit (fan coil) comes factory equipped with a bi-flow hard shutoff TXV, no TXV change is required.

→

III. CLEARANCE REQUIREMENTS

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

If TXV installation is required, remove existing Check-Flo-Rater from indoor coil. Refer to Fig. 4 and 5 and install TXV kit as follows:

1. Install suction tube adapter.
2. Install liquid flare-to-sweat adapter.

On rooftop applications, locate unit at least 6 in. above roof surface.

3. Connect external equalizer tube to fitting on suction tube adapter.

IV. OPERATING AMBIENTS

4. Position sensing bulb on horizontal portion of suction tube adapter. Secure using supplied hardware.

The minimum outdoor operating ambient in cooling mode is 55˚F, and the maximum outdoor operating ambient in cooling mode is 125˚F. The maximum outdoor operating ambient in heating mode is 66˚F.

5. Insulate bulb after installation. (See Fig. 5.)
6. Leak check all connections.
Page 3 of the Bryant 663C user manual — →
Page 3 · click to enlarge
Page 3
Bryant 663C — SENSING BULB diagram (page 3)
Fig. 5
Bryant 663C — SENSING BULB diagram (page 3)
Fig. 6

SENSING BULB

EQUALIZER TUBE

7⁄8 IN. OD & SMALLER LARGER THAN 7⁄8 IN. OD

Fig. 4—Typical TXV Installation

Fig. 5—Positioning of Sensing Bulb

→

VII. CHECK OUTDOOR CHECK-FLO-RATER® PISTON Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.

  • CAUTION: To prevent damage to unit or service valves observe the following:
  • Use a brazing shield.
  • Wrap service valves with wet cloth or use a heat sink material.

→

VIII. CHECK DEFROST THERMOSTAT

Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 2 in. long. (See Fig. 6.) The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.

→

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, substan- tial capacity and performance losses can occur. Following the recommendations in the Residential Split System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field tubing equivalent line length. Refer to Table 2 for accessory requirements.

Bryant 663C — → diagram (page 3)
Fig. 7

→

For buried-line applications greater than 36 in., refer to Table 2 and Residential Split System Buried-Line Application Guideline. Buried-line applications may not exceed 100 ft.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

A. Outdoor Unit Connected to Factory-Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.

B. Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service valves. (See Table 1.) Use refrigerant grade tubing.

Fig. 6—Defrost Thermostat Location

C. Sweat Connection

IX. MAKE PIPING CONNECTIONS

Remove plastic retainer holding outdoor piston in liquid service valve and connect sweat/flare adapter provided to valve. (See Fig. 7.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code require- ments. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

→

Page 4 of the Bryant 663C user manual — (BELOW 55°F)
Page 4 · click to enlarge
Page 4

→TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

Bryant 663C — X. MAKE ELECTRICAL CONNECTIONS diagram (page 4)
Fig. 8

LIQUID VAPOR VAPOR (LONG LINE) Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3/8 3/8 5/8 5/8 5/8 3/4 024 3/8 3/8 3/4 030, 036 3/8 3/8 3/4 3/4 3/4 7/8 042 3/8 3/8 7/8 7/8 7/8 1-1/8 048, 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8

X. MAKE ELECTRICAL CONNECTIONS

Bryant 663C — X. MAKE ELECTRICAL CONNECTIONS diagram (page 4)
Fig. 9

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

→Fig. 7—Liquid Service Valve

A. Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

→

→ TABLE 2—ACCESSORY USAGE

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

LOW-AMBIENT APPLICATIONS

LONG-LINE APPLICATIONS*

BURIED LINE APPLICATIONS†

ACCESSORY

(OVER 3 FT) Crankcase Heater Yes Yes Yes Evaporator Freeze Thermostat Yes No No Accumulator No No Yes Compressor Start Assist

(BELOW 55°F)

(OVER 50 FT)

Capacitor and Relay Yes Yes Yes

or Low-Ambient Pressure Switch

Wind Baffle See Low-Ambient Instructions No No Unit Risers Recommended No No Liquid-Line Solenoid Valve

or Hard Shutoff TXV

Ball Bearing Fan Motor Yes‡ No No

* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † For buried line applications, refer to Residential Split System Buried-Line Application Guideline. ‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

Show 8 more labels / short text on this page
Low-Ambient Controller, · MotorMaster® Control, · Yes No No · See Long-Line · No · Application · Yes · Guideline
Page 5 of the Bryant 663C user manual — XII. INSTALL ELECTRICAL ACCESSORIES
Page 5 · click to enlarge
Page 5

XIII. START-UP

  • CAUTION: To prevent compressor damage or personal injury, observe the following:
  • Do not overcharge system with refrigerant.
  • Do not operate unit in a vacuum or at negative pressure.
  • Do not disable low-pressure switch. In scroll compressor applications:
  • Dome temperatures may be hot.

B. Connect Ground and Power Wires

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 8.

  • CAUTION: To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
  • Back seating service valves are not equipped with Schrader valves. Fully back seat (counter clockwise) valve stem before removing gage port cap.
  • Front seating service valves are equipped with Schrader valves.

DISCONNECT PER N. E. C. AND/OR LOCAL CODES

CONTACTOR

FIELD POWER

WIRING

FIELD GROUND

Follow these steps to properly pumpdown a system and avoid negative suction pressure.

WIRING

GROUND LUG

1. Fully back seat (open) liquid and vapor tube service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger-tight and tighten with wrench an additional 1/12 turn.

Fig. 8—Line Power Connections

C. Connect Control Wiring

3. Close electrical disconnects to energize system.

Route 24-v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 9–14.)

4. Set room thermostat to desired temperature. Be sure set point is below indoor ambient temperature.

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

5. Set room thermostat to HEAT or COOL and fan control to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge.

A. Sequence of Operation

→

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24-v/40-va minimum.

With power supplied to indoor and outdoor units, transformer is energized.

COOLING

On a call for cooling, thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes reversing valve, switching it to cooling position. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor circuit. R-G energizes indoor unit blower relay, starting indoor blower motor on high speed. When thermostat is satisfied, its contacts open, de-energizing the contactor and blower relay. Compressor and motors should stop. NOTE: If indoor unit is equipped with a time-delay relay circuit, the blower runs an additional 90 sec to increase system efficiency.

→

→

XI. COMPRESSOR CRANKCASE HEATER

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.

HEATING

On a call for heating, thermostat makes circuits R-Y and R-G. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor. Circuit R-G energizes indoor blower relay, starting blower motor on high speed. Should temperature continue to fall, R-W2 is made through second-stage room thermostat bulb. Circuit R-W2 energizes a sequencer, bringing on first bank of supplemental electric heat and

A crankcase heater is required if refrigerant tubing is longer than 50 ft.

XII. INSTALL ELECTRICAL ACCESSORIES

Refer to the individual instructions packaged with kits or acces- sories when installing.

Page 6 of the Bryant 663C user manual — BRYANT PROGRAMMABLE
Page 6 · click to enlarge
Page 6

BRYANT PROGRAMMABLE

ONE OUTDOOR THERMOSTAT

THERMOSTAT

FA, FB, FC, FD, FF, FH

BRYANT PROGRAMMABLE

FAN COIL

FA, FB, FC,

MODEL HP

THERMOSTAT

FD, FF, FH

MODEL HP

FAN COIL

Bryant 663C — BRYANT PROGRAMMABLE diagram (page 6)
Fig. 10
Bryant 663C — BRYANT PROGRAMMABLE diagram (page 6)
Fig. 11

BRYANT PROGRAMMABLE

FA, FB, FC,

TWO OUTDOOR THERMOSTATS

THERMOSTAT

FD, FF, FH

MODEL HP

FAN COIL

Bryant 663C — BRYANT PROGRAMMABLE diagram (page 6)
Fig. 12

BRYANT PROGRAMMABLE

THERMOSTAT

FK4C FAN COIL

MODEL HP

24 VAC HOT R INDOOR FAN G HEAT STAGE 2 W/W1 COOL/HEAT Y/Y2 STAGE 1 RVS COOLING O/W2 NOT USED Y1/W2 24 VAC COM C NOT USED B TROUBLE L OPTIONAL S1 OUTDOOR SENSOR CONNECTION S2RDHJ1JUMPER R W2 JUMPER Y O C G W/W1R G W1 W2 Y/Y2J2 Y/Y2 O/W2
Bryant 663C — BRYANT PROGRAMMABLE diagram (page 6)
Fig. 13

Fig. 9—Typical 24-v Circuit Connections using Bryant Model HP Thermostat with Fan Coils and No Outdoor Thermostat,

1 Outdoor Thermostat, or 2 Outdoor Thermostats

Page 7 of the Bryant 663C user manual — IF AVAILABLE
Page 7 · click to enlarge
Page 7

FA, FB, FC,

OTHER HP THERMOSTAT

FD, FF, FH

FA, FB, FC,

ONE OUTDOOR THERMOSTAT

FAN COIL

OTHER HP THERMOSTAT

FD, FF, FH

FAN COIL

Bryant 663C — FA, FB, FC, diagram (page 7)
Fig. 14
24 VAC HOT R 24 VAC COM C HEAT STAGE 2 W2 COOL/HEAT STAGE 1 Y INDOOR FAN G RVS COOLING O EMERGENCY E HEATR C * W2R C Y G O* E * W3 GW2 Y O E* IF AVAILABLE
Bryant 663C — FA, FB, FC, diagram (page 7)
Fig. 15

FA, FB, FC,

TWO OUTDOOR THERMOSTATS

OTHER HP THERMOSTAT

FD, FF, FH

FAN COIL

Bryant 663C — FA, FB, FC, diagram (page 7)
Fig. 16
24 VAC HOT R E 24 VAC COM C HEAT STAGE 2 W2 COOL/HEAT Y STAGE 1 E INDOOR FAN G RVS COOLING O EMERGENCY HEAT E* W3ODT E C W2HRR CR C Y E GHR* W2 * EW2 YODT O EEHG RGO

OTHER HP THERMOSTAT

FK4C FAN COIL

Bryant 663C — OTHER HP THERMOSTAT diagram (page 7)
Fig. 17
24 VAC COM C HEAT STAGE 2 W2 COOL/HEAT Y STAGE 1 INDOOR FAN G RVS COOLING O EMERGENCY E HEATC W1 W2J2C W2 JUMPER Y O Y/Y2 G O Y1

IF AVAILABLE

Fig. 10—Typical 24-v Circuit Connections using Other HP Thermostats with Fan Coils and No Outdoor Thermostat, 1 Outdoor

Thermostat, or 2 Outdoor Thermostats

*

Page 8 of the Bryant 663C user manual — BRYANT PROGRAMMABLE
Page 8 · click to enlarge
Page 8

BRYANT DUAL FUEL THERMOSTAT

BRYANT DUAL FUEL THERMOSTAT

TWO-STAGE OR VARIABLE SPEED

SINGLE-STAGE

MODEL DF

FURNACE HEAT PUMP

MODEL DF

FURNACE HEAT PUMP

Bryant 663C — BRYANT DUAL FUEL THERMOSTAT diagram (page 8)
Fig. 18
Bryant 663C — BRYANT DUAL FUEL THERMOSTAT diagram (page 8)
Fig. 19

Fig. 11—Typical 24-v Circuit Connections using Bryant Model DF Thermostat with Single- or 2-Stage Furnace

BRYANT PROGRAMMABLE

FK4C FAN COIL

THERMOSTAT

Bryant 663C — BRYANT PROGRAMMABLE diagram (page 8)
Fig. 20

Smart Sequencing Application: Model 2S thermostat with switch C OFF and switch D ON uses single-speed heat pump, FK4 fan coil with selected 2:1 size ratio heaters. Provides 3 stages of auxiliary heat for even heating comfort via W/W1 and Y1/W2. Refer to FK4 Installation Instructions.

Fig. 12—Typical 24-v Circuit Connections using Bryant Model 2S Thermostat

with FK4C Fan Coil and Smart Staging

Page 9 of the Bryant 663C user manual — BRYANT PROGRAMMABLE
Page 9 · click to enlarge
Page 9

BRYANT PROGRAMMABLE

FA, FB, FC, FH

FA, FB, FC, FH FAN COIL WITH

BRYANT PROGRAMMABLE

FAN COIL

WITH SMART

ONE OUTDOOR THERMOSTAT

THERMOSTAT

THERMOSTAT

MODEL HP

SMART HEAT

MODEL HP

HEAT

Bryant 663C — BRYANT PROGRAMMABLE diagram (page 9)
Fig. 21
Bryant 663C — BRYANT PROGRAMMABLE diagram (page 9)
Fig. 22

BRYANT PROGRAMMABLE

FA, FB, FC, FH

FAN COIL SMART HEAT

THERMOSTAT

MODEL HP

SUPPLEMENTAL

HEATING

Bryant 663C — BRYANT PROGRAMMABLE diagram (page 9)
Fig. 23

Fig. 13—Typical 24-v Circuit Connections using Bryant Model HP Thermostat with Smart Heat and No Outdoor Thermostat,

1 Outdoor Thermostat, or 2 Outdoor Thermostats

Page 10 of the Bryant 663C user manual — FA, FB, FC, FH
Page 10 · click to enlarge
Page 10

FA, FB, FC, FH

OTHER HP THERMOSTAT

FAN COIL SMART HEAT

FA, FB, FC, FH

OTHER HP THERMOSTAT

FAN COIL SMART HEAT

Bryant 663C — FA, FB, FC, FH diagram (page 10)
Fig. 24
Bryant 663C — FA, FB, FC, FH diagram (page 10)
Fig. 25

FA, FB, FC, FH

OTHER HP THERMOSTAT

FAN COIL SMART HEAT

Bryant 663C — FA, FB, FC, FH diagram (page 10)
Fig. 26

Fig. 14—Typical 24-v Circuit Connections using Other HP Thermostats with Smart Heat and No Outdoor Thermostat,

1 Outdoor Thermostat, or 2 Outdoor Thermostats

Page 11 of the Bryant 663C user manual — DEFROST
Page 11 · click to enlarge
Page 11

WIRING DIAGRAM NOTES:

1. BRYANT THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS BEGINNING WITH TSTAT
2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.
3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEMPERATURE SWITCH, OR 5-MINUTE COMPRESSOR CYCLE PROTECTION. CONNECT 24-V FIELD WIRING TO FACTORY-PROVIDED STRIPPED LEADS.
4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME UNITS.
5. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE COMPRESSOR CYCLE PROTECTION AND 4 CYCLES PER HR LIMIT. SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR DETAILS.
6. TO STAGE ELECTRIC RESISTANCE HEAT, CONSULT OUTDOOR THERMOSTAT INSTALLATION INSTRUCTIONS.
7. FOR DUAL FUEL THERMOSTATS, UNDERLINED LETTER ON DUAL TERMINAL INDICATES ITS USAGE.

FOR EXAMPLE: O/W2 MEANS O

O/W2 MEANS W2

OUTDOOR TEMPERATURE SENSOR MUST BE ATTACHED IN ALL DUAL FUEL INSTALLATIONS.

JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMINALS MUST BE PRESENT.

8. Y1 AND O CONNECTIONS TO 2-STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL.

LEGEND

24 VOLT FACTORY WIRING

24 VOLT FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EHR

EMERGENCY HEAT RELAY

SHR

SUPPLEMENTAL HEAT RELAY

providing electrical potential to second heater sequencer (if used). If outdoor temperature falls below setting of outdoor thermostat (field-installed option), contacts close to complete circuit and bring on second bank of supplemental electric heat. When thermostat is satisfied, its contacts open, de-energizing contactor and sequencer. All heaters and motors should stop.

3. Restart unit in heating mode, allowing frost to accumulate on outdoor coil.
4. After a few minutes in heating mode, liquid line temperature should drop below closing point of defrost thermostat (approximately 30˚F).

DEFROST

5. Short between speed-up terminals with a flat-bladed screwdriver. (See Fig. 15.) This reduces the timing sequence to 1/256th of original time. (See Table 3.)

The defrost control is a time/temperature control which includes a field-selectable (quick-connects located at board edge) time period between defrost cycles (30, 50, or 90 minutes), factory set at 90 minutes. The electronic timer and defrost cycle start only when contactor is energized and defrost thermostat is closed. Defrost mode is identical to cooling mode except that outdoor fan motor stops and second-stage heat is turned on to continue warming conditioned space. To initiate defrost, the defrost thermostat must be closed. This can be accomplished as follows:

6. When you hear reversing valve change position, remove screwdriver immediately; otherwise, control will terminate normal 10-minute defrost cycle in approximately 2 sec.
7. Unit will remain in defrost for remainder of defrost cycle time or until defrost thermostat reopens at approximately 80˚F coil temperature of liquid line.
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control board. (See Fig. 15.) Tape lead to prevent grounding.
8. Turn off power to outdoor unit and reconnect fan motor lead to OF2 on control board. (See Fig. 15.)
Page 12 of the Bryant 663C user manual — CARE AND MAINTENANCE
Page 12 · click to enlarge
Page 12

TABLE 4—REQUIRED LIQUID-LINE TEMPERATURE (°F)

Bryant 663C — TABLE 4—REQUIRED LIQUID-LINE TEMPERATURE (°F) diagram (page 12)
Fig. 27

LIQUID PRESSURE AT SERVICE VALVE

REQUIRED SUBCOOLING

TEMPERATURE

(°F) 5 10 15 20 134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79 74 187 92 87 82 77 196 95 90 85 80 205 98 93 88 83 214 101 96 91 86 223 104 99 94 89 233 107 102 97 92 243 110 105 100 95 253 113 108 103 98 264 116 111 106 101 274 119 114 109 104 285 122 117 112 107 297 125 120 115 110 309 128 123 118 113 321 131 126 121 116 331 134 129 124 119 346 137 132 127 122 359 140 135 130 125

Bryant 663C — LIQUID PRESSURE AT SERVICE VALVE diagram (page 12)
Fig. 28

O R T2 Y TI DFT C TEST 30 50 90

Fig. 15—Defrost Control

TABLE 3—DEFROST CONTROL SPEED-UP

TIMING SEQUENCE

SPEED-UP (NOMINAL) 30-minute cycle 27 33 7 sec 50-minute cycle 45 55 12 sec 90-minute cycle 81 99 21 sec 10-minute cycle 9 11 2 sec 5 minutes 4.5 5.5 1 sec

PARAMETER MINIMUM (MINUTES)

MAXIMUM (MINUTES)

B. Heating Check Chart Procedure

To check system operation during heating cycle, refer to the Heating Check Chart on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.

XIV. CHECK CHARGE

Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure. To check charge in heating mode, refer to Heating Check Chart Procedure.

→

A. Cooling Only Procedure

NOTE: If subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge Units installed with cooling mode TXV require charging with the subcooling method.

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

→

XV. FINAL CHECKS

1. Operate unit a minimum of 10 minutes before checking charge.
1. Securely fasten all panels and covers.
2. Measure liquid service valve pressure by attaching an accurate gage to service port. 3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil. 4. Refer to unit rating plate for required subcooling temperature.
2. Tighten service valve stem caps to 1/12-turn past finger tight.
3. Leave User’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
4. Fill out Dealer Installation Checklist and place in customer file.
5. Refer to Table 4. Find the point where required subcooling temperature intersects measured liquid service valve pressure.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip- ment failure, periodic maintenance must be performed on this equipment.

6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of ± 3°F.

Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.

© 1997 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —12— Printed in U.S.A. 663c181 Catalog No. 5366-300

Ask about the Bryant 663C

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 663C

Be the first to ask — other owners or our team will answer.

Original document

Bryant 663C manual PDF

12 pages·136 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…