SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol
. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
Fig. 1—Model 663C
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.) 10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation. When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion, check refrigerant charge using charging information located on control box cover. IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all residential applications including long line. IMPORTANT: Always install a liquid-line filter drier. Refer to Product Data Sheet for appropriate part number. Obtain filter drier from service parts or your distributor or branch.
INSTALLATION RECOMMENDATIONS NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
A. Unpack Unit Move to final location. Remove carton taking care not to damage unit. B. Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit service panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Avoid contact between tubing and structure NOTE:

CAULK
LIQUID TUBE
VAPOR TUBE INSULATION
THROUGH THE WALL

HANGER STRAP (AROUND VAPOR
INSULATION
VAPOR TUBE
DIMENSIONS (IN.)
MINIMUM MOUNTING PAD
TIEDOWN KNOCKOUT LOCATIONS
UNIT SIZE
LIQUID TUBE
DIMENSIONS
A B C
SUSPENSION
018 22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8 024–060 30 X 30 6-1/2 23-1/2 20
Fig. 3—Mounting Unit to Pad
Fig. 2—Connecting Tubing Installation
→
II. INSTALL ON A SOLID, LEVEL MOUNTING PAD
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location.
In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.
On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind baffle construction.
For TXV kit part number and charging instructions, refer to TXV label in outdoor unit. If indoor unit (fan coil) comes factory equipped with a bi-flow hard shutoff TXV, no TXV change is required.
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
If TXV installation is required, remove existing Check-Flo-Rater from indoor coil. Refer to Fig. 4 and 5 and install TXV kit as follows:
On rooftop applications, locate unit at least 6 in. above roof surface.
The minimum outdoor operating ambient in cooling mode is 55˚F, and the maximum outdoor operating ambient in cooling mode is 125˚F. The maximum outdoor operating ambient in heating mode is 66˚F.



EQUALIZER TUBE
7⁄8 IN. OD & SMALLER LARGER THAN 7⁄8 IN. OD
Fig. 4—Typical TXV Installation
Fig. 5—Positioning of Sensing Bulb
VII. CHECK OUTDOOR CHECK-FLO-RATER® PISTON Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 2 in. long. (See Fig. 6.) The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, substan- tial capacity and performance losses can occur. Following the recommendations in the Residential Split System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field tubing equivalent line length. Refer to Table 2 for accessory requirements.

For buried-line applications greater than 36 in., refer to Table 2 and Residential Split System Buried-Line Application Guideline. Buried-line applications may not exceed 100 ft.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
A. Outdoor Unit Connected to Factory-Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.
B. Refrigerant Tubing
Connect tubing to fittings on outdoor unit vapor and liquid service valves. (See Table 1.) Use refrigerant grade tubing.
Fig. 6—Defrost Thermostat Location
C. Sweat Connection
Remove plastic retainer holding outdoor piston in liquid service valve and connect sweat/flare adapter provided to valve. (See Fig. 7.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code require- ments. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

→TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

LIQUID VAPOR VAPOR (LONG LINE) Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3/8 3/8 5/8 5/8 5/8 3/4 024 3/8 3/8 3/4 030, 036 3/8 3/8 3/4 3/4 3/4 7/8 042 3/8 3/8 7/8 7/8 7/8 1-1/8 048, 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
→Fig. 7—Liquid Service Valve
A. Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
REQUIRED FOR
REQUIRED FOR
REQUIRED FOR
LOW-AMBIENT APPLICATIONS
LONG-LINE APPLICATIONS*
BURIED LINE APPLICATIONS†
ACCESSORY
(OVER 3 FT) Crankcase Heater Yes Yes Yes Evaporator Freeze Thermostat Yes No No Accumulator No No Yes Compressor Start Assist
(OVER 50 FT)
Capacitor and Relay Yes Yes Yes
or Low-Ambient Pressure Switch
Wind Baffle See Low-Ambient Instructions No No Unit Risers Recommended No No Liquid-Line Solenoid Valve
or Hard Shutoff TXV
Ball Bearing Fan Motor Yes‡ No No
* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † For buried line applications, refer to Residential Split System Buried-Line Application Guideline. ‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

B. Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 8.
CONTACTOR
FIELD POWER
WIRING
Follow these steps to properly pumpdown a system and avoid negative suction pressure.
GROUND LUG
Fig. 8—Line Power Connections
C. Connect Control Wiring
Route 24-v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 9–14.)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.
A. Sequence of Operation
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24-v/40-va minimum.
With power supplied to indoor and outdoor units, transformer is energized.
On a call for cooling, thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes reversing valve, switching it to cooling position. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor circuit. R-G energizes indoor unit blower relay, starting indoor blower motor on high speed. When thermostat is satisfied, its contacts open, de-energizing the contactor and blower relay. Compressor and motors should stop. NOTE: If indoor unit is equipped with a time-delay relay circuit, the blower runs an additional 90 sec to increase system efficiency.
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
On a call for heating, thermostat makes circuits R-Y and R-G. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor. Circuit R-G energizes indoor blower relay, starting blower motor on high speed. Should temperature continue to fall, R-W2 is made through second-stage room thermostat bulb. Circuit R-W2 energizes a sequencer, bringing on first bank of supplemental electric heat and
A crankcase heater is required if refrigerant tubing is longer than 50 ft.
Refer to the individual instructions packaged with kits or acces- sories when installing.

ONE OUTDOOR THERMOSTAT
THERMOSTAT
FA, FB, FC, FD, FF, FH
BRYANT PROGRAMMABLE
FAN COIL
FA, FB, FC,
MODEL HP
THERMOSTAT
FD, FF, FH
MODEL HP
FAN COIL


FA, FB, FC,
TWO OUTDOOR THERMOSTATS
THERMOSTAT
FD, FF, FH
MODEL HP
FAN COIL

THERMOSTAT
FK4C FAN COIL
MODEL HP

Fig. 9—Typical 24-v Circuit Connections using Bryant Model HP Thermostat with Fan Coils and No Outdoor Thermostat,
1 Outdoor Thermostat, or 2 Outdoor Thermostats

OTHER HP THERMOSTAT
FD, FF, FH
FA, FB, FC,
ONE OUTDOOR THERMOSTAT
FAN COIL
OTHER HP THERMOSTAT
FD, FF, FH
FAN COIL


TWO OUTDOOR THERMOSTATS
OTHER HP THERMOSTAT
FD, FF, FH
FAN COIL

FK4C FAN COIL

Fig. 10—Typical 24-v Circuit Connections using Other HP Thermostats with Fan Coils and No Outdoor Thermostat, 1 Outdoor
Thermostat, or 2 Outdoor Thermostats
*

BRYANT DUAL FUEL THERMOSTAT
TWO-STAGE OR VARIABLE SPEED
SINGLE-STAGE
MODEL DF
FURNACE HEAT PUMP
MODEL DF
FURNACE HEAT PUMP


Fig. 11—Typical 24-v Circuit Connections using Bryant Model DF Thermostat with Single- or 2-Stage Furnace
FK4C FAN COIL
THERMOSTAT

Smart Sequencing Application: Model 2S thermostat with switch C OFF and switch D ON uses single-speed heat pump, FK4 fan coil with selected 2:1 size ratio heaters. Provides 3 stages of auxiliary heat for even heating comfort via W/W1 and Y1/W2. Refer to FK4 Installation Instructions.
Fig. 12—Typical 24-v Circuit Connections using Bryant Model 2S Thermostat
with FK4C Fan Coil and Smart Staging

FA, FB, FC, FH
FA, FB, FC, FH FAN COIL WITH
BRYANT PROGRAMMABLE
FAN COIL
WITH SMART
ONE OUTDOOR THERMOSTAT
THERMOSTAT
THERMOSTAT
MODEL HP
SMART HEAT
MODEL HP
HEAT


FA, FB, FC, FH
FAN COIL SMART HEAT
THERMOSTAT
MODEL HP
SUPPLEMENTAL
HEATING

Fig. 13—Typical 24-v Circuit Connections using Bryant Model HP Thermostat with Smart Heat and No Outdoor Thermostat,
1 Outdoor Thermostat, or 2 Outdoor Thermostats

OTHER HP THERMOSTAT
FAN COIL SMART HEAT
FA, FB, FC, FH
OTHER HP THERMOSTAT
FAN COIL SMART HEAT


OTHER HP THERMOSTAT
FAN COIL SMART HEAT

Fig. 14—Typical 24-v Circuit Connections using Other HP Thermostats with Smart Heat and No Outdoor Thermostat,
1 Outdoor Thermostat, or 2 Outdoor Thermostats

O/W2 MEANS W2
OUTDOOR TEMPERATURE SENSOR MUST BE ATTACHED IN ALL DUAL FUEL INSTALLATIONS.
JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMINALS MUST BE PRESENT.
24 VOLT FIELD WIRING
FIELD SPLICE CONNECTION
OUTDOOR THERMOSTAT
EHR
EMERGENCY HEAT RELAY
SHR
SUPPLEMENTAL HEAT RELAY
providing electrical potential to second heater sequencer (if used). If outdoor temperature falls below setting of outdoor thermostat (field-installed option), contacts close to complete circuit and bring on second bank of supplemental electric heat. When thermostat is satisfied, its contacts open, de-energizing contactor and sequencer. All heaters and motors should stop.
The defrost control is a time/temperature control which includes a field-selectable (quick-connects located at board edge) time period between defrost cycles (30, 50, or 90 minutes), factory set at 90 minutes. The electronic timer and defrost cycle start only when contactor is energized and defrost thermostat is closed. Defrost mode is identical to cooling mode except that outdoor fan motor stops and second-stage heat is turned on to continue warming conditioned space. To initiate defrost, the defrost thermostat must be closed. This can be accomplished as follows:


REQUIRED SUBCOOLING
TEMPERATURE
(°F) 5 10 15 20 134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79 74 187 92 87 82 77 196 95 90 85 80 205 98 93 88 83 214 101 96 91 86 223 104 99 94 89 233 107 102 97 92 243 110 105 100 95 253 113 108 103 98 264 116 111 106 101 274 119 114 109 104 285 122 117 112 107 297 125 120 115 110 309 128 123 118 113 321 131 126 121 116 331 134 129 124 119 346 137 132 127 122 359 140 135 130 125

O R T2 Y TI DFT C TEST 30 50 90
Fig. 15—Defrost Control
TIMING SEQUENCE
SPEED-UP (NOMINAL) 30-minute cycle 27 33 7 sec 50-minute cycle 45 55 12 sec 90-minute cycle 81 99 21 sec 10-minute cycle 9 11 2 sec 5 minutes 4.5 5.5 1 sec
MAXIMUM (MINUTES)
B. Heating Check Chart Procedure
To check system operation during heating cycle, refer to the Heating Check Chart on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.
Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure. To check charge in heating mode, refer to Heating Check Chart Procedure.
A. Cooling Only Procedure
NOTE: If subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge Units installed with cooling mode TXV require charging with the subcooling method.
To calculate additional charge required for a 25-ft line set:
25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge
For continuing high performance and to minimize possible equip- ment failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.
© 1997 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —12— Printed in U.S.A. 663c181 Catalog No. 5366-300