installation and start-up instructions 10 SEER SPLIT-SYSTEM HEAT PUMP

Bryant 661C — installation and start-up instructions 10 SEER SPLIT-SYSTEM HEAT PUMP diagram (page 1)
Fig. 1 · installation and start-up instructions 10 SEER SPLIT…
CancelsII 661C-18-6 II 661C-18-7
Bryant 661C — installation and start-up instructions 10 SEER SPLIT-SYSTEM HEAT PUMP diagram (page 1)
Fig. 2 · installation and start-up instructions 10 SEER SPLIT…

SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor- oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Fig. 1—Models 661C

Bryant 661C — installation and start-up instructions 10 SEER SPLIT-SYSTEM HEAT PUMP diagram (page 1)
Fig. 3 · installation and start-up instructions 10 SEER SPLIT…

INSTALLATION RECOMMENDATIONS NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.

Fig. 2—Models 661G and 661S

1. Locate unit away from windows, patios, decks, etc. where unit operation sounds may disturb customer.
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing. (See Fig. 3.)
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
4. Leave some slack between structure and unit to absorb vibration.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 3.)
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 3.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
Page 2 of the Bryant 661C user manual — V. ELEVATE UNIT
Page 2 · click to enlarge
Page 2

Avoid contact between tubing and structure NOTE:

Bryant 661C — LIQUID TUBE diagram (page 2)
Fig. 4
Bryant 661C — LIQUID TUBE diagram (page 2)
Fig. 5

LIQUID TUBE

JOIST

INSULATION

VAPOR TUBE

DIMENSIONS (IN.)

MINIMUM MOUNTING PAD

TIEDOWN KNOCKOUT LOCATIONS

UNIT SIZE

DIMENSIONS

A B C

LIQUID TUBE

SUSPENSION

018—030 22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8 042—060 30 X 30 6-1/2 23-1/2 20

Fig. 4—Mounting Unit to Pad

Fig. 3—Connecting Tube Installation

When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion, check refrigerant charge using charging information located on control box cover. IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all residential applications including long line. IMPORTANT: Always install a liquid-line filter drier. Refer to Product Data Sheet for appropriate part number. Obtain filter drier from service parts or your distributor or branch.

III. CLEARANCE REQUIREMENTS

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

INSTALLATION I. CHECK EQUIPMENT AND JOB SITE

On rooftop applications, locate unit at least 6 in. above roof surface.

IV. OPERATING AMBIENTS The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is 125°F. The maximum outdoor operating ambient in heating mode is 66°F.

A. Unpack Unit Move to final location. Remove carton taking care not to damage unit. B. Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit service panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications. II. INSTALL ON A SOLID, LEVEL MOUNTING PAD If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 4 to determine base pan size and knockout hole location. On rooftop applications, mount on level platform or frame 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications. Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind baffle construction.

V. ELEVATE UNIT

In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.

VI. CHECK INDOOR AND OUTDOOR CHECK-FLO- RATER® PISTON Check indoor coil piston to see if it matches the required piston shown on outdoor unit rating plate. If it does not match, replace indoor coil piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination.

Page 3 of the Bryant 661C user manual — VIII. MAKE PIPING CONNECTIONS
Page 3 · click to enlarge
Page 3

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

LIQUID VAPOR VAPOR (LONG LINE) Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018, 024 3/8 3/8 5/8 5/8 5/8 3/4 060, 036 3/8 3/8 3/4 3/4 3/4 7/8 042, 048 3/8 3/8 7/8 7/8 7/8 1-1/8 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8

UNIT SIZE

  • CAUTION: To prevent damage to unit or service valves observe the following:
  • Use a brazing shield.
  • Wrap service valves with wet cloth or use a heat-sink material.

Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft in length or 20 ft vertical differential, substantial capacity and performance losses can occur. Following the recommendations in the Residen- tial Split System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field tubing equivalent line length.

VII. CHECK DEFROST THERMOSTAT

Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 2 in. long. (See Fig. 5.) The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

FEEDER TUBE

A. Outdoor Unit Connected to Factory-Approved In- door Unit

STUB TUBE

Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.

B. Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service valves. (See Table 1.) Use refrigerant grade tubing. Refer to appropriate section below for type of service valves installed on unit.

DEFROST THERMOSTAT

C. Sweat Connection

Fig. 5—Defrost Thermostat Location

Remove plastic retainer holding outdoor piston in liquid service valve and connect sweat/flare adapter provided to valve. (See Fig. 6.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code require- ments. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

VIII. MAKE PIPING CONNECTIONS

D. Final Tubing Check IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Page 4 of the Bryant 661C user manual — XIII. START-UP
Page 4 · click to enlarge
Page 4

PISTON BODY

PISTON

PISTON RETAINER

B. Connect Ground and Power Wires

STRAINER

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 7.

SWEAT/FLARE ADAPTER

C. Connect Control Wiring

Route 24v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 8 and 9.)

Fig. 6—Liquid Service Valve with Sweat Adapter Tube

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.

DISCONNECT PER N.E.C. AND/OR LOCAL CODES

CONTACTOR

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory trans- former for control power, 24v/40va minimum.

FIELD POWER

WIRING

BLUE 3 PHASE ONLY

FIELD GROUND

WIRING

GROUND LUG

D. Final Wiring Check

Fig. 7—Line Power Connections

X. COMPRESSOR CRANKCASE HEATER

IX. MAKE ELECTRICAL CONNECTIONS

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 50 ft.

XI. COMPRESSOR CRANKCASE HEATER

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 50 ft.

XII. INSTALL ELECTRICAL ACCESSORIES

Refer to the individual instructions packaged with kits or acces- sories when installing.

XIII. START-UP

  • CAUTION: To prevent compressor damage or personal injury, observe the following:
  • Do not overcharge system with refrigerant.
  • Do not operate unit in a vacuum or at negative pressure.
  • Do not disable low-pressure switch. In scroll compressor applications:
  • Dome temperatures may be hot.

A. Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

Page 5 of the Bryant 661C user manual — ODT
Page 5 · click to enlarge
Page 5

BRYANT PROGRAMMABLE

BRYANT PROGRAMMABLE

FA, FB, FC,

ONE OUTDOOR THERMOSTAT FA, FB, FC, FD, FF, FH

THERMOSTAT

FD, FF, FH

HEAT PUMP

THERMOSTAT

HEAT PUMP

MODEL HP

FAN COIL

FAN COIL

MODEL HP

Bryant 661C — THERMOSTAT diagram (page 5)
Fig. 6
24 VAC HOT R INDOOR FAN G HEAT STAGE 2 W/W1 COOL/HEAT Y/Y2 STAGE 1 RVS COOLING O/W2 NOT USED Y1/W2 24 VAC COM C NOT USED B TROUBLE L OPTIONAL S1 OUTDOOR SENSOR CONNECTION S2W3 RR W2 G W/W1 Y/Y2G W2 O/W2 Y1/W2E CY O C
Bryant 661C — THERMOSTAT diagram (page 5)
Fig. 7

when installing outdoor thermostat.

energized when requesting supplemental heat.

BRYANT PROGRAMMABLE

BRYANT PROGRAMMABLE

THERMOSTAT

FK4C FAN COIL

HEAT PUMP

MODEL HP

FA, FB, FC,

TWO OUTDOOR THERMOSTATS

THERMOSTAT

FD, FF, FH

HEAT PUMP

MODEL HP

FAN COIL

24 VAC HOT R INDOOR FAN G HEAT STAGE 2 W/W1 COOL/HEAT Y/Y2 STAGE 1 RVS COOLING O/W2 NOT USED Y1/W2 24 VAC COM C NOT USED B TROUBLE L OPTIONAL S1 OUTDOOR SENSOR CONNECTION S2DH RJ1JUMPER R W2 JUMPER Y O C GG W/W1 Y/Y2 O/W2W1 W2 Y/Y2J2 O
Bryant 661C — BRYANT PROGRAMMABLE diagram (page 5)
Fig. 8

ODT

Bryant 661C — ODT diagram (page 5)
Fig. 9

when installing outdoor thermostats.

energized when requesting supplemental heat.

Fig. 8—Typical 24v Circuit Connections using Bryant Model HP Thermostat with Fan Coils and No Outdoor Thermostat, 1

Outdoor Thermostat, or 2 Outdoor Thermostats

Page 6 of the Bryant 661C user manual — IF AVAILABLE *
Page 6 · click to enlarge
Page 6

FA, FB, FC,

FA, FB, FC,

ONE OUTDOOR THERMOSTAT

OTHER HP THERMOSTAT

FD, FF, FH

HEAT PUMP

OTHER HP THERMOSTAT

FD, FF, FH

HEAT PUMP

FAN COIL

FAN COIL

Bryant 661C — FA, FB, FC, diagram (page 6)
Fig. 10
Bryant 661C — FA, FB, FC, diagram (page 6)
Fig. 11

when installing outdoor thermostat.

energized when requesting supplemental heat.

FA, FB, FC,

TWO OUTDOOR THERMOSTATS

OTHER HP THERMOSTAT

FD, FF, FH

HEAT PUMP

FAN COIL

OTHER HP THERMOSTAT

FK4C FAN COIL

HEAT PUMP

Bryant 661C — FA, FB, FC, diagram (page 6)
Fig. 12
Bryant 661C — FA, FB, FC, diagram (page 6)
Fig. 13
24 VAC HOT R 24 VAC COM C HEAT STAGE 2 W2 COOL/HEAT Y STAGE 1 INDOOR FAN G RVS COOLING O EMERGENCY E HEATDH R CJ1JUMPER R C W2 JUMPER Y W1 W2 Y/Y2J2 G O Y1

IF AVAILABLE *

when installing outdoor thermostats.

energized when requesting supplemental heat.

Fig. 9—Typical 24v Circuit Connections using Other HP Thermostats with Fan Coils and No Outdoor T

Page 7 of the Bryant 661C user manual — COOLING
Page 7 · click to enlarge
Page 7

are equipped with a phase monitor to detect if the incoming power is correctly phased for compressor operation. (See Fig. 10 and Table 3.) If the phasing is correct, circuit R-Y energizes contactor, starting outdoor fan motor and compressor circuit. R-G energizes indoor unit blower relay, starting indoor blower motor on high speed. NOTE: If the phasing is incorrect, the contactor will not be energized. To correct the phasing, interchange any two of the three power connections on the field side. When thermostat is satisfied, its contacts open, de-energizing the contactor and blower relay. Compressor and motors should stop. NOTE: If indoor unit is equipped with a time-delay relay circuit, the blower runs an additional 90 sec to increase system efficiency.

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

ODT

OUTDOOR THERMOSTAT

EHR

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY SHR

HEATING On a call for heating, thermostat makes circuits R-Y and R-G. If phasing is correct, circuit R-Y energizes contactor, starting out- door fan motor and compressor. Circuit R-G energizes indoor blower relay, starting blower motor on high speed. Should temperature continue to fall, R-W2 is made through second-stage room thermostat bulb. Circuit R-W2 energizes a sequencer, bringing on first bank of supplemental electric heat and providing electrical potential to second heater sequencer (if used). If outdoor temperature falls below setting of outdoor thermostat (field-installed option), contacts close to complete circuit and bring on second bank of supplemental electric heat. When thermostat is satisfied, its contacts open, de-energizing contactor and sequencer. All heaters and motors should stop.

  • CAUTION: To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
  • Back-seating service valves are not equipped with Schrader valves. Fully back seat (counterclockwise) valve stem before removing gage-port cap.
  • Front-seating service valves are equipped with Schrader valves.
1. Fully back seat (open) liquidand vapor-tube service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger-tight and tighten with wrench an additional 1/12 turn.
3. Close electrical disconnects to energize system.
4. Set room thermostat to desired temperature. Be sure set point is below indoor-ambient temperature.
5. Set room thermostat to HEAT or COOL and fan control to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system-refrigerant charge.

Fig. 10—Phase Monitor Control

  • CAUTION:
  • 3-phase scroll compressors are rotation sensitive.
  • A flashing LED on phase monitor indicates reverse rotation. (See Fig. 10 and Table 3.)
  • This will not allow contactor to be energized.
  • Disconnect power to unit and interchange 2 field wiring leads on unit contactor.

DEFROST The defrost control is a time/temperature control which includes a field-selectable (quick-connects located at board edge) time period between defrost cycles (30, 50, or 90 minutes), factory set at 90 minutes. The electronic timer and defrost cycle start only when contactor energized and defrost thermostat is closed. Defrost mode is identical to cooling mode except that outdoor fan motor stops and second-stage heat is turned on to continue warming conditioned space. To initiate defrost, the defrost thermostat must be closed. This can be accomplished as follows:

A. Sequence of Operation l .

With power supplied to indoor and outdoor units, transformer is energized.

COOLING

1. Turn off power to outdoor unit.

On a call for cooling, thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes reversing valve, switching it to cooling position. On three phase models with scroll compressors, the units

2. Disconnect outdoor fan motor lead from OF2 on control board. (See Fig. 11.) Tape lead to prevent grounding.
Page 8 of the Bryant 661C user manual — CES0130024
Page 8 · click to enlarge
Page 8

3. Restart unit in heating mode, allowing frost to accumulate on outdoor coil. 4. After a few minutes in heating mode, liquid line tempera- ture should drop below closing point of defrost thermostat (approximately 30°F). 5. Short between speed-up terminals with a flat-bladed screw- driver. (See Fig. 11.) This reduces the timing sequence to 1/256th of original time. (See Table 2.) 6. When you hear reversing valve change position, remove screwdriver immediately; otherwise, control will terminate normal 10-minute defrost cycle in approximately 2 sec. NOTE: Length of defrost cycle is dependent on the length of time it takes to remove screwdriver from test pins after reversing valve has shifted.

TABLE 2—DEFROST CONTROL SPEED-UP

TIMING SEQUENCE

SPEED-UP (NOMINAL) 30-minute cycle 27 33 7 sec 50-minute cycle 45 55 12 sec 90-minute cycle 81 99 21 sec 10-minute cycle 9 11 2 sec 5 minutes 4.5 5.5 1 sec

PARAMETER MINIMUM (MINUTES)

MAXIMUM (MINUTES)

7. Unit will remain in defrost for remainder of defrost cycle time or until defrost thermostat reopens at approximately 80°F coil temperature of liquid line. 8. Turn off power to outdoor unit and reconnect fan motor lead to OF2 on control board. (See Fig. 11.)

A. Heating Check Chart Procedure To check system operation during heating cycle, refer to the Heating Check Chart on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.

OF2

OF1

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft - 15 ft = 10 ft X 0.6 oz/ft =6 oz of additional charge

XV. FINAL CHECKS

O R T2 Y TI DFT C TEST 30 50 90

1. Securely fasten all panels and covers.

W1

2. Tighten service valve stem caps to 1/12-turn past finger tight.

O

R

3. Leave User’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.

W2

Y

CES0110063,

4. Fill out Dealer Installation Checklist and place in customer file.

CES0130024

CARE AND MAINTENANCE

Fig. 11—Defrost Control

XIV. CHECK CHARGE Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure on unit wiring and charging label. To check charge in heating mode, refer to Heating Check Chart Procedure.

For continuing high performance and to minimize possible equip- ment failure, periodic maintenance must be performed on this equipment.

Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.

© 2002 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —8— Printed in U.S.A. 661c187 Catalog No. 5366-119

Ask about the Bryant 661C

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 661C

Be the first to ask — other owners or our team will answer.

Original document

Bryant 661C manual PDF

8 pages·107 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…