Bryant 650A

20 pages·174 KB·Heat Pump·PDF·ENDEFRITNLJA
Bryant 650A
Table of Contents 80 sections QUANTUM PLUS 13 SEER HEAT PUMP WITH PURON™ REFRIGERANT · 650A (60 Hz) · Sizes 024 thru 060 · Energy-Efficient Fan and Fan Motor · … ShowHide
QUANTUM PLUS 13 SEER HEAT PUMP WITH PURON™ REFRIGERANTp.1650A (60 Hz)p.1Sizes 024 thru 060p.1Energy-Efficient Fan and Fan Motorp.1Sound Hoodp.1Discharge Mufflerp.1WEATHER-PROTECTIVE CABINETp.1COIL PROTECTIONp.1EASY SERVICEABILITYp.1WIDE RANGE OF SIZESp.1LIMITED WARRANTYp.1TOTALLY ENCLOSED FAN MOTORp.1SMp.1FEATURESp.1REFRIGERANTp.1DEFROST CONTROL BOARDp.1APPLICATION VERSATILITYp.1RELIABLE BUILT-IN COMPONENTSp.1EXTERNAL SERVICE VALVESp.1COMPRESSOR PROTECTIONp.1THERMOSTATIC EXPANSION VALVE (TXV)p.1UNIT DESIGNp.1AeroQuiet System (AQS)p.1ELECTRICAL RANGEp.1Aerocoustic Designp.1Form No. PDS 650A.24.2p.1DIMENSIONSp.2A94148p.2DIMENSIONS (IN.)p.2RECOMMENDED TUBE DIAMETERSp.3NOTES:p.3METERING DEVICEp.3SOUND RATING (dBA)p.3CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEMp.3REGISTERED QUALITY SYSTEMp.3SPECIFICATIONSp.4SPECIFICATIONS Continuedp.5NOTE:p.5THERMOSTATS AND ACCESSORIESp.6ACCESSORY USAGE GUIDELINEp.6ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)p.7COMBINATION RATINGS*p.8COMBINATION RATINGS Continuedp.9COPp.9EERp.9HSPFp.9SEERp.9TCp.9TDRp.9TXVp.9BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HRp.10A99002p.10DETAILED COOLING CAPACITIES*p.11DETAILED COOLING CAPACITIES* Continuedp.12EVAPp.13CFM EWBp.13650AN042-A,C Outdoor Section With FV4ANF003 Indoor Sectionp.13FV4ANF 003 1.00 1.00 CE3AA 048 1.00 1.08p.13F(A,B)4AN(F,B,C) 048 0.99 1.07 CJ5A/CK5A/CK5BA 048 0.99 1.08p.13FC4BN(F,B) 048 1.00 1.09 CJ5A/CK5A/CK5BN 048 0.99 1.08p.13FK4CNF 003 1.00 1.00 CJ5A/CK5A/CK5BW 048 0.99 1.08p.13005 1.01 0.98 CK3BA 048 0.99 1.08p.13FV4ANF 005 1.01 0.98 — — —p.13FX4ANF 042 1.00 1.09p.13650AN048-A,C Outdoor Section With FV4ANF005 Indoor Sectionp.13FV4ANF 005 1.00 1.00 FX4ANF 048 0.99 1.06p.13F(A,B)4AN(F,B,C) 060 0.98 1.10 FX4ANB 060 1.00 1.06p.13FB4ANB 070 1.01 1.06 CE3AA 060 1.00 1.06p.13FC4BN(F,B) 060 0.98 1.10 CJ5A/CK5A/CK5BA 060 0.99 1.06p.13FC4BNB 070 1.01 1.06 CJ5A/CK5A/CK5BN 060 1.00 1.06p.13FK4CNB 006 1.02 0.98 CJ5A/CK5A/CK5BX 060 1.00 1.06p.13FK4CNF 005 1.00 1.00 CK3BA 060 0.99 1.06p.13FV4ANB 006 1.02 0.98 — — —p.13650AN060-B,C Outdoor Section With FV4ANB006 Indoor Sectionp.14FV4ANB 006 1.00 1.00 FX4ANB 060 0.98 1.04p.14FB4ANB 070 0.98 1.04 CC5A/CD5AW 060 0.97 0.99p.14FC4BNB 070 0.98 1.04 CJ5A/CK5A/CK5BX 060 0.97 1.00p.14FK4CNB 006 1.00 1.00 — — —p.14HEAT PUMP HEATING PERFORMANCEp.15INDOORp.15
Page 1 of the Bryant 650A user manual — Form No. PDS 650A.24.2
Page 1 · click to enlarge
Page 1

QUANTUM PLUS 13 SEER HEAT PUMP WITH PURON™ REFRIGERANT

650A (60 Hz)

Sizes 024 thru 060

wire dome top results in quieter and more efficient operation.

Energy-Efficient Fan and Fan Motor

provide a slower fan operation, thus reducing noise and improving efficiency.

Sound Hood

muffles noise from operation.

Discharge Muffler

minimizes low frequency sound and pressure pulsation generated by compressor discharge gas.

WEATHER-PROTECTIVE CABINET

—Steel is galvanized and coated with a layer of zinc phosphate. A layer of modified polyester powder is then applied and baked on, providing each unit with a durable finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting, rust-resistant, quality appearance.

COIL PROTECTION

—The DuraGuard coil protector, made of a 12 gage coated steel wire grid with vertical 3/8-in. spacing, is designed to help protect the coil from inclement weather, van- dalism, and incidental damage. It provides protection while not restricting airflow and maintaining ease of coil inspection and cleaning.

EASY SERVICEABILITY

—One access panel provides access to electrical controls and compressor. Removal of wire dome gives access to fan motor and removal of the top gives access to the coil.

The Quantum Plus line of split-system outdoor units has been expanded to include the Model 650A 13 SEER heat pump (with efficiencies up to 14.5 SEER). Homeowners will appreci- ate the Quantum Plus with Puron Refrigerant because of its efficiency, environmental soundness and its availability for years to come. Another benefit of the Quantum Plus is the durability of the scroll compressor. Model 650A has received certifications from UL, c-UL, ARI, CEC, and CSA-EEV. The 650A is also approved by Energy Star

WIDE RANGE OF SIZES

—Available in 6 nominal sizes from 024 through 060 to meet the needs of residential and light commercial applications.

LIMITED WARRANTY

—Standard 1-year limited warranty on parts, with an additional 9-year limited warranty on compressor.

TOTALLY ENCLOSED FAN MOTOR

—Means greater reli- ability under adverse weather conditions and dependable performance for many years. Permanent split-capacitor-type motors provide more economical operation.

for energy efficiency and by Green Seal for efficiency and environmental soundness.

SM

FEATURES

REFRIGERANT

—The environmentally sound refrigerant used in the 650A is Puron. This advanced refrigerant con- tains no chlorine which can contribute to ozone depletion in the atmosphere, so it’s a smart choice for homeowners who are concerned with protecting our environment, now and for future generations. And it’s a smart choice for anyone inter- ested in high-efficiency cooling.

DEFROST CONTROL BOARD

—Incorporates a built-in 5-minute compressor time-delay relay, defrost relay, defrost timer, and low-voltage terminal board. The defrost control is a time/temperature initiation/termination control, which includes 3 field-selectable time periods of 30, 50, and 90 minutes.

APPLICATION VERSATILITY

—Due to PressureGuard™ the 650A can be combined with a wide variety of evaporator coils and blower packages to provide quiet, dependable comfort. The 650A can be installed on a roof or at ground level on a slab.

RELIABLE BUILT-IN COMPONENTS

—All units include a suction line accumulator that minimizes the amount of liquid refrigerant that reaches the compressor; a high-pressure switch for high-pressure protection; a low-pressure switch for loss of charge protection; and a liquid-line filter drier to remove any moisture or foreign matter from the system. A crankcase heater is standard on the 048 and 060 sizes.

EXTERNAL SERVICE VALVES

—Both service valves are brass, back seating type with sweat connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures.

COMPRESSOR PROTECTION

—Each scroll compressor motor is protected with internal temperature and current- sensitive overloads. For improved serviceability each com- pressor is equipped with a compressor terminal plug.

THERMOSTATIC EXPANSION VALVE (TXV)

—This unit must be installed with a Puron™ approved TXV on the indoor coil. The FX4 and FV4 fan coils come factory equipped with Puron TXVs. When installed with these fan coils, no further change is required. For any other coil combination, the approved field accessory Puron TXV must be installed. For applications with fan coils such as the FC4 and FK4 which have R-22 TXVs, the R-22 TXV must be replaced with the approved field accessory Puron TXV.

UNIT DESIGN

—Copper tube, enhanced aluminum fin coil is designed for strong heat transfer. Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. Heat pump style base pan is popular for its easy removal of water, dirt, and leaves. The

consists of 4 design features to achieve ultra-low sound ratings.

AeroQuiet System (AQS)

ELECTRICAL RANGE

—All units are offered in 208/230v single phase only.

Aerocoustic Design

featuring the Aeromax opening and

Form No. PDS 650A.24.2

Page 2 of the Bryant 650A user manual — DIMENSIONS (IN.)
Page 2 · click to enlarge
Page 2

DIMENSIONS

MINIMUM MOUNTING PAD DIMENSIONSSnow Stand31 x 3531 x 3531 x 3531 x 3531 x 3531 x 35 Support Feet26 x 3226 x 3226 x 3226 x 3226 x 3226 x 32 UNIT DIMENSIONSN2-15/162-15/162-15/162-15/162-15/162-15/16 M14-1/413-3/413-1/413-1/814-1/214 L14-3/813-1/814-1/81414-1/413-3/4 K15-7/81416-1/816-1/416-1/416 H5/83/43/47/87/87/8 G34-3/828-3/822-3/822-3/834-3/834-3/8 F27-15/1621-15/1615-15/1615-15/1627-15/1627-15/16 E9-11/169-11/169-11/169-11/169-11/169-11/16 D5-1/165-1/165-1/165-1/165-1/165-1/16 C333333333333 B303030303030 A39-13/1633-13/1627-13/1627-13/1639-13/1639-13/16 SERIESA,CA,CA,CA,CA,CB,C UNIT SIZE024030036042048060
Bryant 650A — DIMENSIONS diagram (page 2)
Fig. 1

A94148

FIELD POWER SUPPLY CONN 7/8 IN. DIA (22.22)

HOLE WITH 1 1/8 IN. DIA (34.92) KNOCKOUT

Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F. 2. Maximum outdoor operating ambient in heating mode is 66°F. 3. Series designation is the 14th position of the unit model number. 4. Center of gravity . 5.

1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow.

DIMENSIONS (IN.)

3/8 IN. DIA (9.5) TIEDOWN KNOCKOUTS (2) PLACES IN BASEPAN

Page 3 of the Bryant 650A user manual — R
Page 3 · click to enlarge
Page 3

RECOMMENDED TUBE DIAMETERS

Bryant 650A — RECOMMENDED TUBE DIAMETERS diagram (page 3)
Fig. 2
UNIT SIZELIQUID TUBE DIAMETER (IN.)VAPOR TUBE DIAMETER (IN.) 0 to 50 Ft Tube LengthAlternate0 to 50 Ft Tube LengthAlternateRST* (Not Permitted) 0243/83/85/83/4 ACR3/4 0303/83/83/47/81-1/8 0363/83/83/47/81-1/8 042, 0483/83/87/87/83/4 and 1-1/8 0603/83/81-1/87/83/4

* RST—Refrigeration Service Tubing, standard refrigerant grade tubing.

NOTES:

1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual for Residential SplitSystem Air Conditioners and Heat Pumps using Puron Refrigerant. 2. Refrigerant tubes and indoor coils must be evacuated to 500 microns to minimize contamination and moisture in the system.

METERING DEVICE

Bryant 650A — METERING DEVICE diagram (page 3)
Fig. 3
UNIT SIZESERIESOUTDOOR PISTONREQU INDOOR TXV*IRED SUBCOOLING (°F) 024A,C46KSATX0201HSZ11 030A,C52KSATX0201HSZ9 036A,C57KSATX0301HSZ9 042A,C59KSATX0301HSZ11 048A,C61KSATX0401HSZ10 060B,C73KSATX0501HSZ12

* TXV must be installed when indoor coil is not equipped with a Puron approved TXV. TXV listed is for any approved coil combination. All TXVs are Puron spe- cific bi-flow hard shutoff.

SOUND RATING (dBA)

Bryant 650A — SOUND RATING (dBA) diagram (page 3)
Fig. 4 · SOUND RATING (dBA)

024-A,C 72 030-A,C 74 036-A,C 76 042-A,C 76 048-A,C 78 060-B,C 78

As an ENERGY STAR

partner, Bryant Heating & Cooling Systems has determined that this prod- uct meets the ENERGY STAR guidelines for energy efficiency.

SM

Meets GREEN SEAL Environmental Criteria for high energy efficiency, low noise, and recycled packaging. Does not use an ozone depleting substance during manufacturing, or as a refrigerant.

E

D

T

O

E

R

T

F

A

R

A

S

Bryant 650A — E diagram (page 3)
Fig. 5

R

E

R

A

R

O

M

T

U

T

A

R

Y

O

N

D

P

Y

F

A

U

N

T

O

N

N

G

A

N

U

N

G

W

M

H

T

A

E

Q

U

P

M

E

N

T

R

S

T

A

A

R

D

N

D

CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM

REGISTERED QUALITY SYSTEM

IS LISTED WITH ARI.

Page 4 of the Bryant 650A user manual — SPECIFICATIONS
Page 4 · click to enlarge
Page 4

SPECIFICATIONS

UNIT SIZE-SERIES024-A,C030-A,C036-A,C Operating Weight (Lb)214205217 ELECTRICAL Unit Volts—Hertz—Phase208/230—60—1 Operating Voltage Range*187—253 Compressor Rated Load Amps15.114.715.4 Compressor Locked Rotor Amps61.072.583.0 Condenser Fan Motor—Full Load Amps0.81.11.1 Minimum Unit Ampacity for Wire Sizing19.719.520.4 Minimum Wire Size (60°C Copper) (AWG)†141412 Minimum Wire Size (75°C Copper) (AWG)†141412 Maximum Wire Length (60°C) (Ft)‡393960 Maximum Wire Length (75°C) (Ft)‡373757 Maximum Branch Circuit Fuse Size**303030 COMPRESSOR & REFRIGERANT Compressor ManufacturerCopeland Compressor TypeScroll Refrigerant TypePuron Refrigerant Amount (Lb)††7.186.638.87 OUTDOOR COIL & FAN Coil Face Area (Sq Ft)18.1815.1512.12 Fins per In.—Rows—Circuits25—1—225—1—320—2—3 Fan Motor—HP & RPM1/8 and 8251/5 and 8251/5 and 825 Rated Airflow (CFM)240028002800 OPTIONAL EQUIPMENT Support Feet—4 In. (4)KSASF0101AAA Snow Stand—18 In.KHASS0206MPK Time Delay RelayKAATD0101TDR Interface Control (Energy Minder)‡‡KHAIC0101AAA Service Alarm***KHASA0101AAA Outdoor ThermostatKHAOT0301FST Secondary Outdoor ThermostatKHAOT0201SEC Crankcase HeaterKAACH1201AAA Start Assist—Capacitor/Relay TypeKSAHS1501AAA Start Assist—PTC TypeStandard Bi-Flow TXV (Hard Shutoff)KSATX0201HSZKSATX0301HSZ Filter Drier (Suction Line)KH45LG140 (RCD) Evaporator Freeze Thermostat†††KAAFT0101AAA Isolation Relay†††KHAIR0101AAA Liquid-Line Solenoid Valve (LSV)KHALS0401LLS Low-Ambient Pressure SwitchKSALA0301410
Page 5 of the Bryant 650A user manual — NOTE:
Page 5 · click to enlarge
Page 5

SPECIFICATIONS Continued

UNIT SIZE-SERIES042-A.C048-A,C060-B,C Operating Weight (Lb)218266295 ELECTRICAL Unit Volts—Hertz—Phase208/230—60—1 Operating Voltage Range*187—253 Compressor Rated Load Amps21.120.527.6 Compressor Locked Rotor Amps104.0109.0158.0 Condenser Fan Motor—Full Load Amps1.11.41.4 Minimum Unit Ampacity for Wire Sizing27.527.035.9 Minimum Wire Size (60°C Copper) (AWG)†10108 Minimum Wire Size (75°C Copper) (AWG)†10108 Maximum Wire Length (60°C) (Ft)‡717486 Maximum Wire Length (75°C) (Ft)‡687082 Maximum Branch Circuit Fuse Size**404060 COMPRESSOR & REFRIGERANT Compressor ManufacturerCopeland Compressor TypeScroll Refrigerant TypePuron Refrigerant Amount (Lb)††8.6313.2513.25 OUTDOOR COIL & FAN Coil Face Area (Sq Ft)12.1218.1818.18 Fins per In.—Rows—Circuits20—2—320—2—420—2—5 Fan Motor—HP & RPM1/5 and 8251/4 and 11001/4 and 1100 Rated Airflow (CFM)280033003300 OPTIONAL EQUIPMENT Support Feet—4 In. (4)KSASF0101AAA Snow Stand—18 In.KHASS0206MPK Time Delay RelayKAATD0101TDR Interface Control (Energy Minder)‡‡KHAIC0101AAA Service Alarm***KHASA0101AAA Outdoor ThermostatKHAOT0301FST Secondary Outdoor ThermostatKHAOT0201SEC Crankcase HeaterKAACH1201AAAStandard Start Assist—Capacitor/Relay TypeKSAHS1501AAAKSAHS1601AAA Start Assist—PTC TypeStandardKAACS0201PTC Bi-Flow TXV (Hard Shutoff)KSATX0301HSZKSATX0401HSZKSATX0501HSZ Filter Drier (Suction Line)KH45LG141 (RCD) Evaporator Freeze Thermostat†††KAAFT0101AAA Isolation Relay†††KHAIR0101AAA Liquid-Line Solenoid Valve (LSV)KHALS0401LLS Low-Ambient Pressure SwitchKSALA0301410

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure. † If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than

10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70). If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. ‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for a voltage drop not to exceed 2 percent. ** Time-delay fuse or circuit breaker. †† The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, refer to the Residential Split-Systems Long-Line

Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron (R-410A). ‡‡ Outdoor thermostat required. *** For indicator function, thermostat specified must be used and wired according to service alarm Installation Instructions. ††† Use with low-ambient pressure switch.

NOTE:

Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Page 6 of the Bryant 650A user manual — ACCESSORY USAGE GUIDELINE
Page 6 · click to enlarge
Page 6

THERMOSTATS AND ACCESSORIES

Thermostat—Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage CoolTSTATBBNHP01-B Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat, 1-Stage CoolTSTATBBPHP01-B Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, Dual Fuel, Includes Outdoor Sensor (TSTATXXSEN01)TSTATBBPDF01-B* Thermidistat™ Control—Non-Programmable/Programmable Thermostat with Humidity Control (For use in Dual Fuel, AC, HP, and 2S applications. Includes Outdoor Air Temperature Sensor.)TSTATBBPRH01-B* Builder’s Thermostat—Manual Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool, Heat PumpTSTATBBBHP01* Outdoor Air Temperature SensorTSTATXXSEN01 Backplate for Non-Programmable ThermostatTSTATXXNBP01† Backplate for Programmable Thermostat and Thermidistat™ ControlTSTATXXPBP01† Backplate for Builder’s ThermostatTSTATXXBBP01† Thermostat Conversion Kit (4 to 5 Wire)—10 PackTSTATXXCNV10‡

* Do not use in zoning heat pump applications. † This plate is designed to cover surrounding wall area located behind thermostat. ‡ Thermostat conversion kit is a 24-vac accessory that can turn a 4-wire thermostat application into a 5-wire application. This kit can also be used

to replace a broken thermostat wire, or add an extra wire when needed. ** Outdoor air temperature sensor is an accessory for all Bryant electronic thermostats, except the non-programmable air conditioner version and builder’s thermostats. It allows the temperature at a remote location (outdoors) to be displayed on the thermostat. The outdoor air temperature sensor

used with the dual fuel thermostat. The outdoor air temperature sensor is included with the Thermidistat Control and dual fuel thermostat.

ACCESSORY USAGE GUIDELINE

ACCESSORYREQUIRED FOR LOW-AMBIENT APPLICATIONS (Below 55°F)REQUIRED FOR LONG-LINE APPLICATIONS* (Over 50 Ft) Crankcase HeaterYesYes Evaporator Freeze ThermostatYesNo Compressor Start Assist—Capacitor and RelayYesYes Puron Low-Ambient Pressure SwitchYesNo Wind BaffleSee Low-Ambient Pressure Switch InstructionsNo Support FeetRecommendedNo Puron Hard Shutoff TXVYes†Yes† Puron Liquid-Line Solenoid Valve for HeatingNoSee Long-Line Application Guideline

* For tubing line sets between 50 and 175 ft and/or 20 ft elevation difference between indoor and outdoor units, refer to the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron Refrigerant. † Required for all applications.

must be

Page 7 of the Bryant 650A user manual — ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
Page 7 · click to enlarge
Page 7

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

Compressor Start Assist—Capacitor and Relay

Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C). Units installed with Low Ambient Pressure Switch. Units installed with Liquid-Line Solenoid Valve. 2.

Compressor Start Assist—PTC Type

Solid-state electrical device which gives a “soft” boost to the compressor at each start-up. SUGGESTED USE: Installations with marginal power supply.

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Pressure Switch.) All commercial installations. 4.

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE: All units to which Low-Ambient Pressure Switch has been added.

A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps. SUGGESTED USE: Split-system heat pumps.

Interface Control (Energy Minder)

An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat (Item 11) to be adjusted for economic balance point temperature. SUGGESTED USE: For heat pump and gas- or oil-fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat™ Control is used.

An SPDT relay which switches the Low-Ambient Controller out of the outdoor fan motor circuit when the heat pump switches to heating mode. SUGGESTED USE: All heat pumps where Low-Ambient Pressure Switch has been added.

Liquid-Line Solenoid Valve (LSV)

An electrically operated shutoff valve to be installed at the outdoor unit which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. SUGGESTED USE: In long-line applications. (Refer to the Residential Split-System Long-Line Application Guideline and Service Manual.)

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed. SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C). 10.

Outdoor Air Temperature Sensor

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat. SUGGESTED USE: All Bryant programmable thermostats. 11.

An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point. SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters. 12.

An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point. SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired. 13.

A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper room thermostat, a thermostat signal is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental heaters only. SUGGESTED USE: As a feature to notify owner immediately when the system is not operating most efficiently. 14.

Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base. SUGGESTED USE: Heat pump installations in heavy snowfall areas.

Heat pump installations in snowdrift locations. Heat pump installations in areas of prolonged subfreezing temperatures. All commercial installations. 15.

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes corrosion. SUGGESTED USE: Coastal installations.

Windy areas or where debris is normally circulating. Rooftop installations. 16.

Thermostatic Expansion Valve (TXV)—Bi-Flow

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. SUGGESTED USE: Required for all installations. 17.

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)

Required for use on all zoning systems.

Show 11 more labels / short text on this page
Crankcase Heater · Evaporator Freeze Thermostat · Filter Drier—Suction Line · Isolation Relay · Low-Ambient Pressure Switch · Outdoor Thermostat · Secondary Outdoor Thermostat · Service Alarm · Snow Stand · Support Feet · Time-Delay Relay
Page 8 of the Bryant 650A user manual — COMBINATION RATINGS*
Page 8 · click to enlarge
Page 8

COMBINATION RATINGS*

UNIT SIZESERIESINDOOR UNITCFM††ARI STANDARD RATINGS* CoolingHeating TCSeasonal Efficiency SEEREERHigh-TempLow-TempHSPF FactorySupplied EnhancementStandard RatingField-Supplied Accessory‡ Puron TXVPuron TXV & TDR**TCCOPTCCOP 024-A,CFX4ANF030† F(A,B)4AN(F,C)030 FC4BNF030 FK4CNF001 FK4CNF002 FK4CNF003 FV4ANF002 FV4ANF003 CC5A/CD5AA036 CD5AW036 CE3AA036 CJ5A/CK5A/CK5BA036 CJ5A/CK5A/CK5BW036 CJ5A/CK5A/CK5BN036 CK3BA036800 800 800 700 900 900 80025,000 23,600 24,000 24,400 25,200 24,000 24,000 23,800 24,200TDR&TXV TDR&TXV TDR&TXV NONE13.00 — 14.20 14.50 —— 12.50 12.50 13.80 14.00 14.20 —— 13.00 13.00 12.60 13.0011.10 10.95 10.95 12.00 12.35 12.60 12.05 12.35 11.10 11.10 11.05 11.2025,000 24,400 24,400 23,800 25,000 25,200 25,200 25,000 24,800 24,800 24,600 24,8003.30 3.18 3.18 3.30 3.58 3.54 3.44 3.44 3.28 3.28 3.20 3.3416,600 16,500 16,500 16,000 16,100 16,000 16,100 15,900 16,6002.38 2.32 2.32 2.42 2.54 2.54 2.48 2.48 2.36 2.36 2.34 2.388.00 7.50 7.50 7.75 8.00 7.50 7.50 7.40 7.50 030-A,CFX4ANF030† F(A,B)4AN(F,C)036 FC4BNF036 FK4CNF001 FK4CNF002 FK4CNF003 FV4ANF002 FV4ANF003 FX4ANF036 CC5A/CD5AA036 CD5AW036 CE3AA036 CJ5A/CK5A/CK5BN036 CJ5A/CK5A/CK5BW036 CK3BA0361050 1050 1050 875 1050 1080 1080 1050 1000 1050 105029,000 28,400 28,400 28,600 28,800 29,000 29,200 29,400 29,000 28,800 28,800 28,600 28,800 28,800 28,800TDR&TXV TDR&TXV TDR&TXV TDR&TXV NONE13.00 — 14.00 14.50 12.30 —— 12.20 12.20 13.70 13.70 14.20 —— 13.00 13.00 12.70 12.70 13.00 13.0011.15 10.75 10.75 12.10 12.15 12.55 12.15 12.55 10.85 11.25 11.25 11.15 11.25 11.30 11.3030,000 29,800 29,800 28,600 29,000 28,600 29,000 28,600 30,000 29,400 29,400 29,200 29,400 29,400 29,4003.56 3.42 3.42 3.54 3.68 3.68 3.68 3.70 3.52 3.52 3.52 3.44 3.54 3.56 3.5618,500 18,700 18,700 17,800 17,900 17,700 17,900 17,700 18,800 18,5002.38 2.32 2.32 2.44 2.48 2.50 2.48 2.52 2.36 2.38 2.38 2.36 2.38 2.40 2.408.00 7.40 7.40 7.80 8.00 8.00 8.10 8.10 8.00 7.65 7.65 7.45 7.65 7.70 7.70 036-A,CFX4ANF042† F(A,B)4AN(F,B,C)042 FC4BN(F,B)042 FK4CNF003 FK4CNF005 FV4ANF003 FV4ANF005 CC5A/CD5AA042 CC5A/CD5AW042 CC5A/CD5AC048 CC5A/CD5AW048 CD5AA048 CE3AA042 CE3AA048 CJ5A/CK5A/CK5BA042 CJ5A/CK5A/CK5BN042 CJ5A/CK5A/CK5BA048 CJ5A/CK5A/CK5BN048 CJ5A/CK5A/CK5BW048 CK3BA042 CK3BA0481125 1125 1125 1050 1125 1260 1260 1275 1275 112535,000 33,600 33,600 34,000 35,400 34,400 35,600 34,000 33,600 33,600 34,000 34,000 34,000 34,200 33,800 33,800 34,200 34,200 34,200 33,800 34,200TDR&TXV TDR&TXV TDR&TXV NONE13.00 — 13.70 14.00 —— 12.30 12.30 13.70 14.00 —— 12.50 12.20 12.20 12.5010.80 10.65 10.65 11.80 12.30 11.80 12.30 10.65 10.50 10.50 10.60 10.65 10.65 10.70 10.60 10.60 10.70 10.70 10.70 10.60 10.7035,000 34,200 34,200 33,600 33,800 33,600 34,000 34,000 34,000 33,600 34,200 34,400 34,400 34,400 34,200 34,4003.40 3.26 3.26 3.40 3.70 3.44 3.70 3.20 3.16 3.10 3.24 3.26 3.26 3.30 3.26 3.26 3.32 3.32 3.32 3.26 3.3221,600 21,400 21,400 20,600 20,800 20,600 20,800 21,400 21,6002.34 2.28 2.28 2.40 2.52 2.40 2.52 2.26 2.24 2.22 2.28 2.28 2.28 2.30 2.28 2.28 2.30 2.30 2.30 2.28 2.307.70 7.40 7.40 7.70 8.00 7.80 8.10 7.30 7.40 7.45 7.40 7.40 7.50 7.50 7.50 7.40 7.50 042-A,CFV4ANF003† F(A,B)4AN(F,B,C)048 FC4BN(F,B)048 FK4CNF003 FK4CNF005 FV4ANF005 FX4ANF042 CE3AA048 CJ5A/CK5A/CK5BA048 CJ5A/CK5A/CK5BN048 CJ5A/CK5A/CK5BW048 CK3BA0481225 1400 1400 1225 1225 1225 140040,500 40,000 40,500 40,500 41,000 41,000 40,500 40,500 40,000 40,000 40,000 4,0000TDR&TXV TDR&TXV TDR&TXV NONE13.00 — 14.00 12.00 —— 12.00 12.00 13.00 13.50 —— 12.0011.00 10.25 10.25 11.10 11.55 11.55 10.25 10.35 10.3040,500 41,500 41,500 40,000 40,000 40,000 41,5003.36 3.34 3.38 3.32 3.56 3.56 3.40 3.32 3.3425,400 26,600 26,600 25,400 25,200 25,200 26,600 26,4002.46 2.42 2.42 2.44 2.56 2.56 2.42 2.407.70 7.50 7.55 7.40 8.00 8.10 7.55 7.40 7.50 048-A,CFV4ANF005† F(A,B)4AN(F,B,C)060 FB4ANB070 FC4BN(F,B)060 FC4BNB070 FK4CNF005 FK4CNB006 FV4ANB006 FX4ANF048 FX4ANB060 CE3AA060140045,500 44,500 46,000 44,500 46,000 45,500 46,500 46,500 45,000 45,500 45,500TDR&TXV TDR&TXV TDR&TXV TDR&TXV NONE13.50 — 14.10 12.50 12.60 —— 11.70 12.50 11.70 12.50 13.20 14.00 —— 12.5011.60 10.20 10.90 10.20 10.90 11.60 12.05 12.05 10.75 10.90 10.8047,500 48,500 48,0003.58 3.32 3.54 3.32 3.54 3.58 3.76 3.76 3.42 3.54 3.4027,600 29,000 28,600 29,000 28,600 27,800 27,600 27,600 28,400 28,600 28,4002.46 2.26 2.38 2.26 2.38 2.46 2.54 2.54 2.34 2.38 2.348.50 7.80 8.00 7.70 8.00 8.20 8.50 8.60 8.00 8.10 8.00
Page 9 of the Bryant 650A user manual — TDR
Page 9 · click to enlarge
Page 9

COMBINATION RATINGS Continued

UNIT SIZESERIESINDOOR UNITCFM††ARI STANDARD RATINGS* CoolingHeating TCSeasonal Efficiency SEEREERHigh-TempLow-TempHSPF FactorySupplied EnhancementStandard RatingField-Supplied Accessory‡ Puron TXVPuron TXV & TDR**TCCOPTCCOP 048-A,CCJ5A/CK5A/CK5BA060 CJ5A/CK5A/CK5BN060 CJ5A/CK5A/CK5BX060 CK3BA060140045,000 45,500 45,500 45,000NONE——12.50 13.00 13.00 12.5010.75 10.90 10.90 10.7548,000 48,500 48,500 48,0003.50 3.52 3.52 3.5028,6002.388.20 8.25 8.25 8.20 060-B,CFV4ANB006† FB4ANB070 FC4BNB070 FK4CNB006 FX4ANB060 CC5A/CD5AW060 CJ5A/CK5A/CK5BX060175058,000 57,000 57,000 58,000 57,000 56,000 56,500TDR&TXV TDR&TXV NONE NONE13.00 — — — 12.00 — —— 12.00 12.00 12.80 — — —— 12.50 12.5010.75 10.20 10.20 10.75 10.20 10.45 10.5560,000 60,000 60,000 59,500 60,000 58,500 59,0003.56 3.44 3.44 3.56 3.44 3.26 3.4437,000 37,800 37,800 37,000 37,800 36,800 37,0002.54 2.46 2.46 2.54 2.46 2.42 2.508.00 7.80 7.80 8.00 7.80 7.50 7.70

* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:

Cooling Standard:

80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.

High-Temp Heating Standard:

70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.

70°F (21°C) db indoor entering air temperature and 17°F (–9°C) db 15°F (–10°C) wb air entering outdoor unit. † Outdoor section/indoor section combination tested in accordance with DOE test procedure for heat pumps. ‡ Based on computer simulation. TXV must be Puron compatible and hard shutoff type. ** In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR except for the 394HAD. †† Indoor Airflow

Low-Temp Heating Standard:

COP

— Coefficient of Performance

EER

— Energy Efficiency Ratio

HSPF

— Heating Seasonal Performance Factor

SEER

— Seasonal Energy Efficiency Ratio

TC

— Total Capacity (Btuh)

TDR

TXV

— Thermostatic Expansion Valve

— Time-Delay Relay

Page 10 of the Bryant 650A user manual — A99002
Page 10 · click to enlarge
Page 10
Bryant 650A — BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR diagram (page 10)
Fig. 6

BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR

80 70 60 50 40 30 20 10 0 -10

BASED ON INDOOR ENT. AIR AT 70˚F AND AT RATED CFM

A99002

Page 11 of the Bryant 650A user manual — DETAILED COOLING CAPACITIES*
Page 11 · click to enlarge
Page 11

DETAILED COOLING CAPACITIES*

EVAP AIRCONDENSER ENTERING AIR TEMPERATURES °F 758595105115125 CFMEWBCapacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw** TotalSens‡TotalSens‡TotalSens‡TotalSens‡TotalSens‡TotalSens‡ 650AN024-A,C, Outdoor Section With FX4ANF030 Indoor Section 70072 67 63†† 62 5729.7 27.2 25.3 24.8 23.714.5 18.2 17.7 21.7 23.71.85 1.85 1.85 1.84 1.8428.4 25.9 24.1 23.7 22.814.0 17.6 17.2 21.2 22.82.07 2.0626.9 24.6 22.9 22.5 21.913.5 17.1 16.6 20.6 21.92.31 2.30 2.29 2.29 2.2925.4 23.2 21.6 21.3 20.912.9 16.5 16.1 20.0 20.92.57 2.55 2.54 2.54 2.5423.8 21.7 20.2 20.0 19.812.3 15.9 15.5 19.4 19.82.85 2.83 2.82 2.81 2.8122.0 20.1 18.7 18.6 18.611.7 15.3 14.8 18.5 18.63.14 3.12 3.11 3.11 3.11 80072 67 63†† 62 5730.3 27.7 25.8 25.4 24.715.2 19.3 18.8 23.3 24.71.8828.9 26.4 24.6 24.2 23.714.6 18.7 18.2 22.7 23.72.11 2.1027.3 25.0 23.3 23.0 22.714.1 18.2 17.7 22.1 22.72.35 2.34 2.33 2.33 2.3325.8 23.6 21.9 21.8 21.613.6 17.6 17.1 21.4 21.62.61 2.59 2.58 2.58 2.5824.1 22.0 20.5 20.5 20.513.0 17.0 16.5 20.5 20.52.88 2.87 2.85 2.85 2.8522.2 20.4 19.0 19.2 19.212.3 16.4 15.8 19.2 19.23.18 3.16 3.15 3.15 3.15 90072 67 63†† 62 5730.8 28.2 26.2 25.9 25.515.8 20.4 19.8 24.7 25.51.92 1.9129.3 26.8 24.9 24.7 24.515.3 19.8 19.2 24.1 24.52.14 2.14 2.13 2.13 2.1327.7 25.3 23.6 23.5 23.414.7 19.3 18.6 23.3 23.42.38 2.3726.1 23.9 22.2 22.3 22.314.2 18.7 18.1 22.3 22.32.64 2.63 2.62 2.62 2.6224.3 22.3 20.8 21.1 21.113.6 18.1 17.4 21.1 21.12.92 2.90 2.89 2.89 2.8922.4 20.5 19.1 19.7 19.712.9 17.4 16.7 19.7 19.73.22 3.20 3.19 3.19 3.19 Multipliers for Determining the Performance With Other Indoor Sections Indoor SectionSizeCoolingIndoor SectionSizeCooling CapacityPowerCapacityPower FX4ANF0301.001.00CE3AA0300.941.00 F(A,B)4AN(F,C)0300.941.000360.951.00 FC4BNF0300.961.00CJ5A/CK5A/CK5BA0300.941.00 FK4CNF0010.980.930360.971.00 0021.010.93CJ5A/CK5A/CK5BN0360.971.00 0031.010.91CJ5A/CK5A/CK5BW0300.941.00 FV4ANF0021.010.930360.971.00 0031.010.91CK3BA0300.941.00 ———0360.971.00
Page 12 of the Bryant 650A user manual — DETAILED COOLING CAPACITIES* Continued
Page 12 · click to enlarge
Page 12

DETAILED COOLING CAPACITIES* Continued

EVAP AIRCONDENSER ENTERING AIR TEMPERATURES °F 758595105115125 CFMEWBCapacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw**Capacity MBtuh†Total Sys Kw** TotalSens‡TotalSens‡TotalSens‡TotalSens‡TotalSens‡TotalSens‡ 650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section 182572 67 63†† 62 5734.3 31.4 29.2 28.8 27.817.2 21.7 21.1 26.2 27.82.07 2.06 2.04 2.04 2.0432.6 29.9 27.8 27.4 26.716.6 21.1 20.5 25.5 26.72.31 2.29 2.28 2.28 2.2730.9 28.3 26.4 26.0 25.615.9 20.5 19.9 24.8 25.62.58 2.56 2.55 2.55 2.5429.0 26.6 24.8 24.5 24.315.3 19.8 19.2 24.0 24.32.87 2.86 2.84 2.84 2.8427.0 24.8 23.1 23.0 23.014.6 19.1 18.5 23.0 23.03.20 3.18 3.17 3.17 3.1724.8 22.7 21.2 21.4 21.413.8 18.3 17.7 21.4 21.43.56 3.54 3.53 3.53 3.53 105072 67 63†† 62 5735.2 32.4 30.2 29.9 29.818.7 24.3 23.6 29.4 29.82.14 2.13 2.11 2.11 2.1133.5 30.7 28.6 28.6 28.518.1 23.7 22.9 28.5 28.52.38 2.36 2.35 2.35 2.3531.6 29.0 27.0 27.2 27.217.4 23.0 22.3 27.2 27.22.65 2.63 2.62 2.62 2.6229.7 27.2 25.4 25.8 25.816.8 22.3 21.5 25.8 25.82.94 2.93 2.91 2.91 2.9127.6 25.3 23.6 24.3 24.316.1 21.6 20.8 24.3 24.33.27 3.25 3.24 3.24 3.2425.2 23.2 21.6 22.5 22.615.3 20.7 19.9 22.5 22.63.62 3.61 3.59 3.60 3.60 125072 67 63†† 62 5735.8 32.9 30.7 31.0 31.020.0 26.5 25.6 31.0 31.02.20 2.19 2.17 2.17 2.1734.0 31.2 29.1 29.7 29.719.4 25.8 24.9 29.7 29.72.44 2.42 2.41 2.41 2.4132.1 29.4 27.5 28.3 28.318.7 25.1 24.2 28.3 28.32.71 2.69 2.67 2.68 2.6830.0 27.6 25.7 26.8 26.818.1 24.4 23.4 26.8 26.83.00 2.98 2.97 2.98 2.9827.8 25.6 23.9 25.1 25.117.3 23.6 22.6 25.1 25.13.33 3.31 3.30 3.31 3.3125.4 23.4 21.9 23.2 23.216.5 22.6 21.5 23.2 23.23.68 3.67 3.65 3.67 3.67 Multipliers for Determining the Performance With Other Indoor Sections Indoor SectionSizeCoolingIndoor SectionSizeCooling CapacityPowerCapacityPower FX4ANF0301.001.00FV4ANF0021.010.93 F(A,B)4AN(F,C)0300.971.000031.010.90 0360.981.03FX4ANF0361.001.03 FC4BNF0300.971.00CE3AA0360.991.00 0360.981.03CJ5A/CK5A/CK5BN0360.991.00 FK4CNF0010.990.92CJ5A/CK5A/CK5BW0360.991.00 0020.990.93CK3BA0360.991.00 0031.000.90——— 650AN036-A,C Outdoor Section With FX4ANF042 Indoor Section 112572 67 63†† 62 5742.3 38.7 36.1 35.5 34.721.3 27.3 26.5 33.0 34.72.64 2.6340.3 36.9 34.4 33.9 33.320.6 26.5 25.7 32.2 33.32.93 2.93 2.92 2.92 2.9238.3 35.0 32.6 32.2 31.919.8 25.8 25.0 31.4 31.93.26 3.25 3.24 3.24 3.2436.0 33.0 30.6 30.4 30.419.1 25.0 24.1 30.3 30.43.61 3.60 3.59 3.59 3.5933.7 30.8 28.6 28.7 28.718.3 24.1 23.3 28.7 28.74.00 3.98 3.96 3.96 3.9631.0 28.3 26.3 26.8 26.817.4 23.2 22.3 26.8 26.84.40 4.38 4.36 4.37 4.37 125072 67 63†† 62 5742.7 39.2 36.6 36.1 35.722.1 28.6 27.8 34.8 35.72.69 2.6840.7 37.3 34.8 34.5 34.321.4 27.9 27.0 33.9 34.32.98 2.98 2.97 2.97 2.9738.6 35.4 32.9 32.8 32.820.6 27.1 26.2 32.8 32.83.31 3.30 3.29 3.29 3.2936.3 33.2 31.0 31.2 31.219.9 26.3 25.4 31.2 31.23.66 3.65 3.64 3.64 3.6433.9 31.0 28.8 29.4 29.419.0 25.4 24.5 29.4 29.44.05 4.03 4.01 4.02 4.0231.2 28.5 26.5 27.4 27.418.1 24.5 23.5 27.4 27.44.46 4.43 4.41 4.42 4.42 137572 67 63†† 62 5743.1 39.6 36.9 36.7 36.622.8 30.0 29.0 36.4 36.62.74 2.7341.1 37.7 35.1 35.1 35.122.1 29.2 28.2 35.1 35.13.03 3.03 3.02 3.02 3.0238.9 35.6 33.2 33.5 33.521.4 28.4 27.4 33.5 33.53.36 3.35 3.34 3.34 3.3436.6 33.5 31.2 31.8 31.820.6 27.6 26.6 31.8 31.83.71 3.70 3.69 3.69 3.6934.1 31.3 29.0 30.0 30.019.8 26.7 25.7 30.0 30.04.10 4.08 4.06 4.07 4.0731.3 28.7 26.7 28.0 27.918.9 25.7 24.6 28.0 27.94.51 4.48 4.46 4.48 4.48 Multipliers for Determining the Performance With Other Indoor Sections Indoor SectionSizeCoolingIndoor SectionSizeCooling CapacityPowerCapacityPower FX4ANF0421.001.00CE3AA0420.971.00 F(A,B)4AN(F,B,C)0420.961.000480.981.00 FC4BN(F,B)0420.961.00CJ5A/CK5A/CK5BA0420.971.00 FK4CNF0030.970.910480.981.00 0051.010.91CJ5A/CK5A/CK5BN0420.971.00 FV4ANF0030.980.910480.981.00 0051.020.91CJ5A/CK5A/CK5BW0480.981.00 CC5A/CD5AA0420.991.00CK3BA0420.971.00 ———0480.981.00
Page 13 of the Bryant 650A user manual — FV4ANF 005 1.00 1.00 FX4ANF 048 0.99 1.06
Page 13 · click to enlarge
Page 13

DETAILED COOLING CAPACITIES* Continued

EVAP

CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125

Sys Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

CFM EWB

650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section

72 48.5 24.4 2.95 46.4 23.6 3.32 44.1 22.8 3.72 41.7 21.9 4.17 39.0 21.0 4.65 36.1 20.0 5.17 67 44.6 30.9 2.91 42.6 30.1 3.28 40.5 29.2 3.68 38.3 28.3 4.12 35.8 27.4 4.61 33.2 26.3 5.12 63†† 41.7 30.1 2.89 39.8 29.3 3.25 37.8 28.4 3.65 35.7 27.5 4.09 33.4 26.5 4.57 31.0 25.5 5.09 62 41.0 37.2 2.88 39.2 36.3 3.24 37.3 35.3 3.65 35.3 34.3 4.09 33.2 33.0 4.57 31.1 31.1 5.09 57 39.7 39.7 2.87 38.2 38.2 3.24 36.7 36.7 3.64 35.0 35.0 4.08 33.1 33.1 4.57 31.1 31.1 5.09

72 49.4 25.6 2.99 47.1 24.8 3.36 44.8 23.9 3.77 42.2 23.1 4.22 39.5 22.1 4.70 36.5 21.1 5.22 67 45.4 32.9 2.96 43.3 32.0 3.32 41.2 31.2 3.73 38.8 30.2 4.17 36.3 29.3 4.65 33.6 28.2 5.17 63†† 42.5 32.0 2.93 40.5 31.1 3.30 38.4 30.2 3.70 36.2 29.3 4.14 33.9 28.3 4.62 31.3 27.2 5.14 62 41.9 39.7 2.93 40.0 38.7 3.29 38.2 37.6 3.70 36.2 36.2 4.14 34.2 34.2 4.62 32.0 32.0 5.15 57 41.2 41.2 2.92 39.6 39.6 3.29 37.9 37.9 3.69 36.1 36.1 4.14 34.2 34.2 4.62 32.0 32.0 5.15

Cooling Capacity Power Capacity Power

FV4ANF 003 1.00 1.00 CE3AA 048 1.00 1.08

F(A,B)4AN(F,B,C) 048 0.99 1.07 CJ5A/CK5A/CK5BA 048 0.99 1.08

FC4BN(F,B) 048 1.00 1.09 CJ5A/CK5A/CK5BN 048 0.99 1.08

FK4CNF 003 1.00 1.00 CJ5A/CK5A/CK5BW 048 0.99 1.08

005 1.01 0.98 CK3BA 048 0.99 1.08

FV4ANF 005 1.01 0.98 — — —

FX4ANF 042 1.00 1.09

650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section

72 54.7 27.7 3.20 52.2 26.8 3.56 49.6 25.9 3.96 46.9 24.9 4.41 43.9 23.9 4.90 40.7 22.8 5.43 67 50.2 35.2 3.16 47.9 34.3 3.52 45.5 33.3 3.92 43.0 32.3 4.36 40.3 31.3 4.85 37.4 30.1 5.39 63†† 46.8 34.3 3.13 44.7 33.3 3.49 42.4 32.4 3.89 40.1 31.3 4.33 37.6 30.3 4.82 34.9 29.1 5.36 62 46.1 42.5 3.12 44.0 41.5 3.48 42.0 40.5 3.88 39.7 39.3 4.33 37.5 37.5 4.82 35.2 35.2 5.37 57 44.9 44.9 3.11 43.2 43.2 3.47 41.4 41.4 3.88 39.6 39.6 4.33 37.5 37.5 4.82 35.2 35.2 5.37

72 55.6 29.1 3.26 53.0 28.1 3.62 50.3 27.2 4.02 47.4 26.2 4.47 44.4 25.2 4.96 41.1 24.1 5.49 67 51.1 37.5 3.22 48.7 36.6 3.58 46.2 35.6 3.98 43.6 34.6 4.42 40.8 33.5 4.91 37.8 32.3 5.45 63†† 47.7 36.5 3.19 45.4 35.5 3.55 43.1 34.5 3.95 40.7 33.5 4.39 38.1 32.4 4.88 35.3 31.2 5.42 62 47.1 45.5 3.18 45.1 44.4 3.54 42.9 42.9 3.95 41.0 41.0 4.39 38.8 38.8 4.89 36.3 36.3 5.43 57 46.7 46.7 3.18 44.8 44.8 3.54 42.9 42.9 3.94 40.9 40.9 4.39 38.8 38.8 4.89 36.4 36.4 5.43

Cooling Capacity Power Capacity Power

FV4ANF 005 1.00 1.00 FX4ANF 048 0.99 1.06

F(A,B)4AN(F,B,C) 060 0.98 1.10 FX4ANB 060 1.00 1.06

FB4ANB 070 1.01 1.06 CE3AA 060 1.00 1.06

FC4BN(F,B) 060 0.98 1.10 CJ5A/CK5A/CK5BA 060 0.99 1.06

FC4BNB 070 1.01 1.06 CJ5A/CK5A/CK5BN 060 1.00 1.06

FK4CNB 006 1.02 0.98 CJ5A/CK5A/CK5BX 060 1.00 1.06

FK4CNF 005 1.00 1.00 CK3BA 060 0.99 1.06

FV4ANB 006 1.02 0.98 — — —

Show 11 more labels / short text on this page
MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · Sys Kw** · Sys Kw** · Sys Kw** · Sys Kw** · Sys Kw**
Page 14 of the Bryant 650A user manual — FV4ANB 006 1.00 1.00 FX4ANB 060 0.98 1.04
Page 14 · click to enlarge
Page 14

DETAILED COOLING CAPACITIES* Continued

EVAP

CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125

Sys Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

CFM EWB

650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section

72 70.1 35.6 4.43 66.6 34.4 4.92 63.1 33.1 5.47 59.2 31.7 6.07 55.0 30.3 6.73 50.2 28.7 7.42 67 64.4 45.5 4.35 61.3 44.2 4.85 58.0 42.9 5.40 54.5 41.5 6.00 50.6 40.0 6.65 46.4 38.4 7.35 63†† 60.2 44.3 4.30 57.2 43.0 4.79 54.2 41.7 5.34 50.9 40.3 5.94 47.3 38.8 6.60 43.4 37.1 7.30 62 59.2 55.1 4.29 56.4 53.7 4.78 53.5 52.3 5.33 50.5 50.4 5.93 47.5 47.5 6.60 44.2 44.2 7.32 57 57.8 57.8 4.27 55.6 55.6 4.77 53.1 53.1 5.32 50.5 50.5 5.93 47.5 47.5 6.60 44.2 44.2 7.32

72 71.1 37.4 4.52 67.6 36.1 5.02 63.9 34.8 5.57 59.8 33.4 6.16 55.5 32.0 6.81 50.6 30.4 7.51 67 65.5 48.5 4.44 62.2 47.2 4.94 58.8 45.9 5.49 55.1 44.4 6.09 51.1 42.9 6.74 46.8 41.2 7.44 63†† 61.2 47.1 4.39 58.1 45.8 4.88 54.9 44.4 5.43 51.6 43.0 6.03 47.9 41.5 6.68 43.8 39.7 7.39 62 60.5 59.0 4.38 57.7 57.4 4.88 54.9 54.9 5.43 52.1 52.1 6.04 48.9 48.9 6.70 45.3 45.3 7.42 57 60.1 60.1 4.38 57.6 57.6 4.88 54.9 54.9 5.43 52.1 52.1 6.04 49.0 49.0 6.70 45.4 45.4 7.42

Cooling Capacity Power Capacity Power

FV4ANB 006 1.00 1.00 FX4ANB 060 0.98 1.04

FB4ANB 070 0.98 1.04 CC5A/CD5AW 060 0.97 0.99

FC4BNB 070 0.98 1.04 CJ5A/CK5A/CK5BX 060 0.97 1.00

FK4CNB 006 1.00 1.00 — — —

* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower motor heat has been subtracted. ‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh

(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C). ** System kw is total of indoor and outdoor unit kilowatts. †† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb. EWB—Entering Wet Bulb

Show 11 more labels / short text on this page
MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · MBtuh† Total · Sys Kw** · Sys Kw** · Sys Kw** · Sys Kw** · Sys Kw**
Page 15 of the Bryant 650A user manual — FX4ANF 030 1.00 1.00 FV4ANF 002 0.97 0.94
Page 15 · click to enlarge
Page 15

HEAT PUMP HEATING PERFORMANCE

INDOOR

OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67

Pwr Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

EDB CFM

650AN024-A,C Outdoor Section With FX4ANF030 Indoor Section

65 700 12.0 11.1 1.79 14.3 13.1 1.87 16.6 15.1 1.95 19.0 16.9 2.04 21.9 19.9 2.16 25.0 25.0 2.30 28.5 28.5 2.48 32.6 32.6 2.74 800 12.2 11.2 1.80 14.5 13.3 1.87 16.8 15.3 1.95 19.2 17.1 2.03 22.1 20.1 2.13 25.4 25.4 2.27 28.9 28.9 2.44 33.1 33.1 2.69 900 12.4 11.4 1.82 14.6 13.4 1.88 17.0 15.5 1.95 19.4 17.3 2.03 22.4 20.4 2.13 25.6 25.6 2.25 29.3 29.3 2.43 33.4 33.4 2.67

70 700 11.8 10.8 1.87 14.1 13.0 1.96 16.4 15.0 2.05 18.8 16.7 2.14 21.6 19.6 2.26 24.7 24.7 2.41 28.1 28.1 2.60 32.0 32.0 2.87 800 12.0 11.0 1.88 14.3 13.1 1.96 16.6 15.1 2.04 19.0 16.9 2.13 21.8 19.9 2.24 25.0 25.0 2.38 28.5 28.5 2.56 32.5 32.5 2.81 900 12.1 11.2 1.90 14.4 13.3 1.97 16.8 15.3 2.05 19.2 17.0 2.13 22.1 20.1 2.23 25.3 25.3 2.36 28.8 28.8 2.54 32.9 32.9 2.79

Cooling Capacity Power Capacity Power

FX4ANF 030 1.00 1.00 CE3AA 030 0.98 1.01

F(A,B)4AN(F,C) 030 0.98 1.01 036 0.98 1.01

FC4BNF 030 0.98 1.01 CJ5A/CK5A/CK5BA 030 0.98 1.01

FK4CNF 001 0.95 0.95 036 0.99 0.98

002 1.00 0.92 CJ5A/CK5A/CK5BN 036 0.99 0.98

003 1.01 0.94 CJ5A/CK5A/CK5BW 030 0.98 1.01

FV4ANF 002 1.01 0.97 036 0.99 0.98

003 1.00 0.96 CK3BA 030 0.98 1.01

— — — 036 0.99 0.98

650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section

65 825 12.6 11.6 2.07 15.4 14.1 2.12 18.3 16.7 2.16 21.6 19.2 2.22 25.4 23.1 2.29 29.7 29.7 2.39 34.6 34.6 2.69 32.7 32.7 2.55 1050 12.9 11.9 2.11 15.7 14.4 2.14 18.7 17.0 2.17 22.0 19.6 2.21 25.9 23.6 2.27 30.4 30.4 2.35 35.4 35.4 2.63 33.5 33.5 2.49 1250 13.2 12.2 2.15 16.0 14.7 2.17 19.0 17.3 2.19 22.4 19.9 2.23 26.3 23.9 2.28 30.8 30.8 2.36 36.0 36.0 2.64 33.9 33.9 2.49

70 825 12.3 11.3 2.18 15.2 14.0 2.23 18.1 16.5 2.28 21.4 19.0 2.33 25.1 22.8 2.41 29.4 29.4 2.52 34.1 34.1 2.82 32.2 32.2 2.67 1050 12.7 11.7 2.21 15.6 14.3 2.25 18.5 16.9 2.28 21.8 19.4 2.32 25.6 23.3 2.38 30.0 30.0 2.47 34.9 34.9 2.76 33.0 33.0 2.60 1250 13.0 11.9 2.25 15.8 14.5 2.28 18.8 17.1 2.30 22.1 19.6 2.34 26.0 23.6 2.39 30.4 30.4 2.47 35.4 35.4 2.76 33.4 33.4 2.60

Cooling Capacity Power Capacity Power

FX4ANF 030 1.00 1.00 FV4ANF 002 0.97 0.94

F(A,B)4AN(F,C) 030 0.98 1.02 003 0.95 0.92

036 0.99 1.03 FX4ANF 036 1.00 1.01

FC4BNF 030 0.98 1.02 CE3AA 036 0.97 1.01

036 0.99 1.03 CJ5A/CK5A/CK5BN 036 0.98 0.99

FK4CNF 001 0.95 0.96 CJ5A/CK5A/CK5BW 036 0.98 0.98

002 0.97 0.94 CK3BA 036 0.98 0.98

003 0.95 0.92 — — —

Show 23 more labels / short text on this page
Total · Total · Total · Total · Total · Total · Total · Total · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh†
Page 16 of the Bryant 650A user manual — F(A,B)4AN(F,B,C) 048 1.02 1.03 CE3AA 048 1.02 1.04
Page 16 · click to enlarge
Page 16

HEAT PUMP HEATING PERFORMANCE Continued

INDOOR

OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67

Pwr Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

EDB CFM

650AN036-A,C Outdoor Section With FX4ANF042 Indoor Section

65 1125 14.7 13.5 2.42 18.3 16.8 2.51 21.9 20.0 2.59 25.8 22.9 2.66 30.4 27.6 2.76 35.6 35.6 2.88 41.7 41.7 3.04 48.8 48.8 3.27 1250 14.9 13.7 2.45 18.5 17.0 2.53 22.9 20.9 2.61 26.1 23.2 2.67 30.7 27.9 2.76 35.9 35.9 2.87 42.1 42.1 3.03 49.3 49.3 3.25 1375 15.1 13.9 2.49 18.7 17.2 2.56 22.4 20.4 2.62 26.3 23.4 2.68 31.0 28.2 2.76 36.3 36.3 2.87 42.5 42.5 3.03 49.7 49.7 3.25

70 1125 14.1 13.0 2.51 17.9 16.4 2.61 21.6 19.7 2.70 25.4 22.6 2.79 29.9 27.2 2.89 35.0 35.0 3.02 41.5 41.5 3.19 48.0 48.0 3.42 1250 14.4 13.2 2.54 18.1 16.7 2.63 21.9 19.9 2.72 25.7 22.8 2.79 30.2 27.5 2.89 35.4 35.4 3.00 41.5 41.5 3.17 48.5 48.5 3.40 1375 14.6 13.4 2.58 18.4 16.9 2.66 22.1 20.1 2.74 26.0 23.1 2.81 30.5 27.8 2.89 35.7 35.7 3.00 41.8 41.8 3.16 48.9 48.9 3.39

Cooling Capacity Power Capacity Power FX4ANF 042 1.00 1.00 CJ5A/CK5A/CK5BA 042 0.98 1.02

F(A,B)4AN(F,B,C) 042 0.98 1.02 048 0.98 1.01

FC4BN(F,B) 042 0.98 1.02 CJ5A/CK5A/CK5BN 042 0.98 1.02

FK4CNF 003 0.96 0.96 048 0.98 1.01

005 0.97 0.89 CJ5A/CK5A/CK5BW 048 0.98 1.01

FV4ANF 003 0.96 0.95 CK3BA 042 0.98 1.02

005 0.97 0.89 048 0.98 1.01

CE3AA 042 0.98 1.02 — — —

048 0.98 1.01 650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section

65 1225 17.3 15.9 2.61 21.5 19.8 2.74 25.7 23.4 2.86 30.0 26.6 2.99 35.1 32.0 3.14 41.1 41.1 3.34 40.4 40.4 3.30 39.5 39.5 3.21 1400 17.6 16.2 2.61 22.5 20.7 2.74 25.9 23.6 2.84 30.2 26.9 2.95 35.5 32.3 3.09 41.5 41.5 3.28 40.8 40.8 3.22 40.0 40.0 3.14 1575 17.8 16.4 2.62 21.9 20.2 2.73 26.1 23.8 2.83 30.5 27.1 2.93 35.8 32.6 3.06 41.9 41.9 3.24 41.2 41.2 3.18 40.4 40.4 3.09

70 1225 16.8 15.5 2.74 21.1 19.4 2.88 25.4 23.2 3.03 29.6 26.3 3.16 34.7 31.6 3.32 40.5 40.5 3.53 39.8 39.8 3.48 38.9 38.9 3.38 1400 17.1 15.7 2.75 21.4 19.6 2.87 25.6 23.4 3.00 29.9 26.6 3.12 35.0 31.9 3.27 41.0 41.0 3.46 40.2 40.2 3.40 39.4 39.4 3.30 1575 17.3 15.9 2.76 21.6 19.8 2.87 25.8 23.6 2.99 30.1 26.8 3.10 35.3 32.2 3.24 41.3 41.3 3.42 40.6 40.6 3.35 39.8 39.8 3.25

Cooling Capacity Power Capacity Power FV4ANF 003 1.00 1.00 FX4ANF 042 1.02 1.01

F(A,B)4AN(F,B,C) 048 1.02 1.03 CE3AA 048 1.02 1.04

FC4BN(F,B) 048 1.02 1.02 CJ5A/CK5A/CK5BA 048 1.02 1.03

FK4CNF 003 0.99 1.00 CJ5A/CK5A/CK5BN 048 1.02 1.03

005 0.99 0.93 CJ5A/CK5A/CK5BW 048 1.02 1.03

FV4ANF 005 0.99 0.93 CK3BA 048 1.02 1.03

Show 23 more labels / short text on this page
Total · Total · Total · Total · Total · Total · Total · Total · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh†
Page 17 of the Bryant 650A user manual — FB4ANB 070 1.00 1.03 CC5A/CD5AW 060 0.98 1.06
Page 17 · click to enlarge
Page 17

HEAT PUMP HEATING PERFORMANCE Continued

INDOOR

OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67

Pwr Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†

EDB CFM

650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section

65 1400 18.5 17.0 2.86 22.9 21.1 2.99 27.9 25.4 3.11 33.5 29.8 3.26 40.2 36.6 3.45 48.2 48.2 3.69 53.8 53.8 4.34 53.1 53.1 4.20 1600 18.7 17.2 2.87 23.2 21.3 2.98 28.1 25.6 3.10 33.8 30.1 3.23 40.7 37.0 3.41 48.7 48.7 3.64 54.4 54.4 4.28 53.7 53.7 4.14 1800 18.9 17.4 2.89 23.4 21.5 2.99 28.4 25.9 3.10 34.1 30.3 3.23 41.0 37.3 3.40 49.1 49.1 3.63 54.9 54.9 4.26 54.1 54.1 4.12

70 1400 18.1 16.7 3.03 22.7 20.9 3.16 27.6 25.2 3.29 33.2 29.4 3.44 39.8 36.2 3.64 47.5 47.5 3.89 54.3 54.3 4.57 52.3 52.3 4.40 1600 18.4 16.9 3.03 23.0 21.1 3.15 27.8 25.4 3.27 33.5 29.7 3.41 40.2 36.5 3.60 48.0 48.0 3.83 53.6 53.6 4.50 52.9 52.9 4.33 1800 18.6 17.1 3.05 23.2 21.3 3.16 28.1 25.6 3.27 33.8 30.0 3.41 40.5 36.9 3.58 48.4 48.4 3.81 54.1 54.1 4.47 53.3 53.3 4.31

Cooling Capacity Power Capacity Power FV4ANF 005 1.00 1.00 FX4ANB 060 1.01 1.02

F(A,B)4AN(F,B,C) 060 1.02 1.10 FX4ANF 048 1.01 1.06

FB4ANB 070 1.01 1.02 CE3AA 060 1.01 1.06

FC4BN(F,B) 060 1.01 1.09 CJ5A/CK5A/CK5BA 060 1.01 1.03

FC4BNB 070 1.01 1.02 CJ5A/CK5A/CK5BN 060 1.02 1.04

FK4CNB 006 1.01 0.96 CJ5A/CK5A/CK5BX 060 1.02 1.04

FK4CNF 005 1.01 1.01 CK3BA 060 1.01 1.03

FV4ANB 006 1.01 0.96 — — — 650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section

65 1750 24.4 22.4 3.73 30.9 28.4 3.88 37.9 34.6 4.05 45.0 40.0 4.24 52.6 47.9 4.45 60.8 60.8 4.68 58.2 58.2 4.52 56.3 56.3 4.47 2000 24.9 22.9 3.76 31.5 28.9 3.90 38.5 35.1 4.05 45.7 40.6 4.22 53.2 48.4 4.41 61.6 61.6 4.61 59.0 59.0 4.44 57.1 57.1 4.37 2250 25.3 23.3 3.80 31.9 29.3 3.93 39.0 35.5 4.06 46.2 41.0 4.23 53.7 48.9 4.39 62.2 62.2 4.58 59.6 59.6 4.39 57.8 57.8 4.31

70 1750 23.4 21.5 3.92 30.0 27.6 4.09 37.0 33.7 4.27 44.2 39.2 4.46 52.0 47.3 4.70 60.0 60.0 4.94 57.4 57.4 4.76 55.4 55.4 4.71 2000 23.8 21.9 3.95 30.5 28.0 4.10 37.6 34.3 4.26 44.8 39.8 4.44 52.5 47.8 4.65 60.7 60.7 4.87 58.1 58.1 4.67 56.2 56.2 4.60 2250 24.3 22.3 4.00 31.0 28.5 4.13 38.1 34.7 4.28 45.4 40.3 4.45 53.1 48.3 4.63 61.4 61.4 4.83 58.8 58.8 4.62 56.9 56.9 4.53

Cooling Capacity Power Capacity Power FV4ANB 006 1.00 1.00 FX4ANB 060 1.00 1.03

FB4ANB 070 1.00 1.03 CC5A/CD5AW 060 0.98 1.06

FC4BNB 070 1.00 1.03 CJ5A/CK5A/CK5BX 060 0.98 1.02

FK4CNB 006 0.99 0.99 — – —

* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity. † The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to

obtain total system kilowatts. EDB—Entering Dry Bulb

Show 23 more labels / short text on this page
Total · Total · Total · Total · Total · Total · Total · Total · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh† · Pwr · MBtuh†
Page 18 of the Bryant 650A user manual — System Design
Page 18 · click to enlarge
Page 18

System Design

1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C). 4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C). 5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C). 6. For reliable operation, unit should be level in all horizontal planes. 7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and 9 following). 8. For interconnecting refrigerant tube lengths greater than 50 ft and/or elevation differences between indoor and outdoor units greater than 20 ft, con- sult Residential Split-System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron Refrigerant. 9. If ANY refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36-in. may be buried without further considerations. Buried refrigerant tubing lengths greater than 36 in. are not recommended. 10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. 11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity (unless so specified) may result in inadequate indoor comfort. 12. Do not apply capillary tube indoor coils to these units. 13. Factory-supplied filter drier must be installed.

Bryant 650A — System Design diagram (page 18)
Fig. 7 · System Design
Page 19 of the Bryant 650A user manual — HEAT PUMP HEATING PERFORMANCE
Page 19 · click to enlarge
Page 19
Page 19 of the Bryant 650A user manual — HEAT PUMP HEATING PERFORMANCE
Page 20 of the Bryant 650A user manual — A94328
Page 20 · click to enlarge
Page 20

SERVICE TRAINING

  • Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
  • Unit Familiarization
  • Maintenance
  • Installation Overview
  • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-962-9212

[ ] Packaged Service Training [ ] Classroom Service Training

A94328

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

CancelsPDS 650A.24.1

© 1998 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231 —20— PRINTED IN U.S.A. Catalog No. 5265-002 1-99

Ask about the Bryant 650A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 650A

Be the first to ask — other owners or our team will answer.

Original document

Bryant 650A manual PDF

20 pages·174 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…