C. Easy Select™—583B
POWER SUPPLY
INTRODUCTION
FIELD-SUPPLIED FUSED DISCONNECT
GND CONTROL BOX
DHUM
YEL(Y)
Y
THERMOSTAT (TYPICAL)
GRN(G)
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
G
These instructions cover the installation of a Bryant Small Pack- aged Product with ICM motor-factory installed option (FIOP). This option can be selected as a FIOP on gas heating/electric cooling (583B), dual fuel–electric heat pump with gas heat back-up (683B), electric cooling (702B) or electric heat pump (602B) units with Puron®.
R
BRN(C)
W1 WHI(W1)
SPLICE BOX
RECEIVING AND INSTALLATION
LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring
Refer to unit Installation Instructions.
Fig. 2—583B High- and Control-Voltage
I. ELECTRICAL CONNECTIONS
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
A. Control Voltage Connections
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35 C minimum) wires.
GND CONTROL BOX
DHUM BLK (DH)
W/W1 WHT(W1)
YEL(Y)
THERMOSTAT (THERMIDISTAT ™ )
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
Y/Y2
GRN(G)
B. Standard Connection
RED(R)
R
Remove knockout hole located in the heat section panel adjacent to the service access panel (See unit installation package). Remove the rubber grommet from the installer’s packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel. Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box. Locate 18-gage wires leaving control box. These low-voltage connection leads can be identified by colors (See Fig. 2, 3, 4 or 5). Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Route leads through hole in bottom of control box and make low-voltage connections (See Fig. 2, 3, 4 or 5). Secure all cut wires, so that they do not interfere with operation of unit.
ORN(O)
O/W2
SPLICE BOX
FIELD CONTROL - VOLTAGE WIRING FIELD HIGH - VOLTAGE WIRING
Fig. 3—683B High- and Control-Voltage
EASY SELECT™CONFIGURATION TAPS FOR 583B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a
Connections · Connections

Factory selected gas heat size should correspond to unit label. b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED
Factory selected air conditioner size should correspond to capacity of unit installed. Installer should verify air conditioner size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes. c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED
FIELD-SUPPLIED FUSED DISCONNECT
Factory selected on 583B for AC-Air conditioner. For Gas Heat/Electric Cool Unit–AC must be selected. d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR
BLK(DH)
DHUM
HIGH AIRFLOW
YEL(Y)
Y
The AC/HP CFM Adjust select is factory set to the High-HI (NOM for 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 8, D as indicated). e. ON/OFF DELAY—SELECT DESIRED
THERMOSTAT (TYPICAL)
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
G
RED(R)
R
BRN(C)
W1 WHI(W1)
GRA(W2)
W2
SPLICE BOX
LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring
Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 8, E as indicated). Selection options are: (1.) The standard 90 sec off delay (Factory Setting) at 100
Fig. 4—702B High- and Control-Voltage
percent airflow in cooling mode. In heating mode, IGC will control 45 sec on delay with no airflow and 45 sec off delay.
(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at
100 percent airflow profile is used when it is desirable to allow system coils time to cool-down in conjunction with the airflow in heating mode.
(3.) A no delay option used for servicing unit or when a
thermostat is utilized to perform delay functions in cooling mode. In heating mode IGC will control 45 sec on delay with no airflow and 45 sec off delay.
GND CONTROL BOX
BLK(DH)
(4.) Not recommended for 583B
YEL(Y)
Y
f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED
WHEN THERMOSTAT IS SET ON CONTINUOUS FAN
GRN(G)
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
G
RED(R)
(1.) LO speed—Factory setting, 50 percent cooling mode
BRN(C)
airflow.
(2.) MED speed—Move connector to MED, 65 percent cooling
mode airflow.
W2 ORN(0)
(3.) HI speed—Move connector to HI, 100 percent cooling
mode airflow (See Fig. 8, F as indicated).
g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE
The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol. h. BASIC UNIT CONFIGURATION
LEGEND Field Control-Voltage Wiring Field High-Voltage Wiring
Fig. 5—602B High- and Control-Voltage
The following basic configuration of the indoor motor will provide ARI rated performance of the 583B. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required, or if system enhancements such as super dehumidify are not needed. (1.) HEAT-Factory selected to match heat input size.
pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8). a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE
(2.) AC/HP Size-Factory selected to match system size, please
verify.
Connections · Connections

(3.) SYSTEM TYPE-Factory selected on 583B system AC-
KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating. c. HUMIDIFIER/HUMIDISTAT CONNECTIONS
AIR CONDITIONER.
(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM
for 036 & 060, and LO for 024 & 030..
Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat (See Fig. 6). These terminals are energized with 24-v. when G thermostat signal is present (See Fig. 6 & 7). Alternately, the 24-v. signal may be sourced from the W and C on the 9 pin connector. When using a Thermidis- tat™Control, Zone Perfect Plus or Comfort Zone II, the 24-v. signal may be sourced directly from the Thermidistat™HUM terminal (See Fig. 6, 7 & 8).
(5.) ON/OFF DELAY-Factory selected 0/90 profile.
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
mostat is set to continuous fan. i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick
The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super- Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort. This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published ARI SEER efficiency. During cool-to-dehumidify call, it provides maximum dehumidification by reducing airflow to a minimum. The actual super dehumidify command from Thermidistat™control to the indoor unit is a “Y” signal without a “G” signal in addition to dehumidify signal. The indoor unit responds to this combination by reducing the airflow to a minimum. All other characteristics of cool to dehumidify are the same. The following system configuration is recommended for maxi- mum cooling/dehumidifying comfort (See Fig. 8).
HUM 1
24-VAC
TO HUMIDIFIER
HUM 2
(G)
HUMIDIFIER WIRING
A95317
Fig. 6—Humidifier Wiring-583B
BLOCK
D H J1
(1.) HEAT-Factory selected to match gas heat size of unit
installed.
R
(2.) AC/HP Size-Factory selected to match system size, please
verify.
(3.) SYSTEM TYPE-Factory selected on 583B system AC-
AIR CONDITIONER.
Fig. 7—Humidistat Wiring for
(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).
(5.) ON/OFF DELAY-Select ENH profile.
d. DEHUMIDIFY CAPABILITY WITH STANDARD
HUMIDISTAT CONNECTION Latent capacities for this unit are better than average systems. If increased latent capacity is an application requirement, the ICM board provides connection terminals for use of a standard humidistat. The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode, remove jumper J1 and wire in a standard humidistat (See Fig. 7).
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
mostat is set to continuous fan.
(7.) DEHUMIDIFY MODE-Remove J1 jumper to activate.
(8.) LOW VOLTAGE CONNECTIONS-Make connections as
shown in ELECTRICAL CONNECTIONS section.
(9.) CONFIGURE THERMIDISTAT™-Follow Thermidis- tat™(or capable zoning system) installation instructions for Super Dehumidify operation. ACCESSORY INSTALLATION
e. DEHUMIDIFY AND SUPER DEHUMIDIFY
a. AUXILIARY TERMINALS
CAPABILITIES This model unit is capable of responding to a signal from indoor system control (Thermidistat™or capable zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.
The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 6). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of this operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.
D. 583B Sequence of Operation
b. ELECTRONIC AIR CLEANER CONNECTIONS
a. CONTINUOUS FAN
The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N.
(1.) Thermostat closes circuit R to G—The Blower runs at
continuous fan airflow b. COOLING MODE
Reference Guide) · De-Humidify Mode-583B

(1.) If indoor temperature is above temperature set point and
humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers single speed cooling airflow. c. COOLING MODE-DEHUMIDIFICATION

(1.) If indoor temperature is above temperature set point and
humidity is above humidity set point, thermostat or Ther- midistat™closes circuits R to G, R to Y/Y2, R to O and humidistat or Thermidistat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system. d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (SEE QUICK REFERENCE GUIDE)
B
DH R W1 W2 Y1 Y/Y2 G O C
E
F
(1.) If the indoor temperature is below the temperature set
point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and closes circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0–v.) for Super Dehu- midify mode, the motor delivers reduced airflow to maxi- mize the humidity removal of the system while minimizing over cooling.
Fig. 8—Detail of SPP Printed-Circuit Board
moval 2. HP-EFF (factory selected) Provides equal airflow for heating and cooling modes to increase overall heat pump efficiency. Provides approximately 400 CFM/ton.
e. GAS HEATING MODE
(1.) Thermostat closes circuit R to W/W1—The unit delivers
the selected gas heat airflow. The IGC will control a 45 sec. blower “On” delay and a 45 sec. “Off” delay.
d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR
E. Easy Select™—683B
The AC/HP CFM Adjust select is factory set to the High-HI (NOM for 036, 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 8, D as indicated).
EASY SELECT™CONFIGURATION TAPS FOR 683B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8).
e. ON/OFF DELAY—SELECT DESIRED
Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 8, E as indicated). Selection options are:
a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE
Factory selected gas heat size should correspond to unit label.
(1.) The standard 90 sec off delay (Factory Setting) at 100
percent airflow in cooling or heat pump heating mode. In gas heating mode, IGC will control a 45 sec “On” delay and a 45 sec “Off” delay.
b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED
Factory selected air conditioner size should correspond to capacity of unit installed. Installer should verify air conditioner size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes.
(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at
100 percent airflow profile is used when it is desirable to allow system coils time to cool-down/heat-up in conjunc- tion with the airflow in cooling or heat pump heating mode.
c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED
Factory selected on 683B for HP-EFF. SELECT OPTIONS 1. HP-COMFORT provides approximately 315 CFM/ton for higher normal heating air temperature and provides approxi- mately 350 CFM/ton cooling airflow for good humidity re-
(3.) A no delay option used for servicing unit or when a
thermostat is utilized to perform delay functions. In gas heating mode IGC will control 45 sec on delay with no airflow and 45 sec off delay.

(4.) ENH (enhanced) selection provides a 30 sec. cooling &
(8.) CONFIGURE THERMIDISTAT™-Follow Thermidis- tat™installation instructions for Super Dehumidify opera- tion. ACCESSORY INSTALLATION a. AUXILIARY TERMINALS
heat pump on delay with no airflow, plus 150 seconds at 70 percent airflow and no off delay for added comfort. This will minimize cold blow in heat pump operation and could enhance system efficiency. f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED
The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 9). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of this operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.
(1.) LO speed—Factory setting, 50 percent cooling mode
airflow.
(2.) MED speed—Move connector to MED, 65 percent cooling
mode airflow.
(3.) HI speed—Move connector to HI, 100 percent cooling
mode airflow (See Fig. 8, F as indicated). g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE
b. ELECTRONIC AIR CLEANER CONNECTIONS
The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N. KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating.
The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol. h. BASIC UNIT CONFIGURATION
c. HUMIDIFIER / THERMIDISTAT™CONNECTIONS
Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard Thermidistat™(See Fig. 9). These terminals are energized with 24-v. when G thermostat signal is present (See Fig. 10). Alternately, the 24-v. signal may be sourced from the W and C on the 9 pin connector. When using a Thermidis- tat™Control the 24-v. signal may be sourced directly from the Thermidistat™HUM terminal (See Fig. 8, 9 & 10).
The following basic configuration of the indoor motor will provide ARI rated performance of the 683B. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required. (1.) HEAT-Factory selected to match heat input size.
(2.) AC/HP Size-Factory selected to match system size, please
verify.
(3.) SYSTEM TYPE-Factory selected on 683B system for
HP-EFF.
(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM
for 036 & 060, and LO for 024 & 030.
24-VAC
TO HUMIDIFIER
(5.) ON/OFF DELAY-Factory selected 0/90 profile.
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
mostat is set to continuous fan.
i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick
Fig. 9—Humidifier Wiring-683B
The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super- Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort. This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published ARI SEER efficiency. The following system configuration is recommended for maxi- mum cooling/dehumidifying comfort (See Fig. 8). (1.) HEAT-Factory selected to match gas heat size of unit
BLOCK
D H J1
THERMIDISTAT
JUMPER
R
installed.
(2.) AC/HP Size-Factory selected to match system size, please
Fig. 10—Thermidistat™Wiring for
verify.
(3.) SYSTEM TYPE-Factory selected on 683B system for
d. DEHUMIDIFY CAPABILITY WITH STANDARD
HP-EFF.
(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).
Latent capacities for this unit are better than average systems. If increased latent capacity is an application requirement, the ICM board provides connection terminals for use of a Thermidis- tat™. The unit will detect the Thermidistat™contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls
(5.) ON/OFF DELAY-Select ENH profile.
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
mostat is set to continuous fan.
(7.) LOW VOLTAGE CONNECTIONS-Make connections as
shown in ELECTRICAL CONNECTIONS section.
Reference Guide) · De-Humidify Mode-683B

to a level which causes the Thermidistat™to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode wire in Thermidistat™see jumper in Fig. 10.
NOTE: The Thermidistat™is capable of providing Super Com- fort Heat operation mode and must be configured as outlined in its installation instructions. The system must be installed with appro- priate outdoor temperature sensor. Consult Thermidistat™litera- ture for configuration instructions. Consult sensor instructions for sensor installation details. If the outdoor temperature is in the range of 12° to 40° F, the Thermidistat™closes circuit R to Y/Y2 and opens circuit R to G. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full heating requested value. If circuit R to G is open (0-v.) for maximum heating comfort, the motor delivers reduced airflow to maximize the temperature and minimize the draft effect of the heated air leaving the unit.
e. DEHUMIDIFY AND SUPER DEHUMIDIFY
This model unit is capable of responding to a signal from Thermidistat™to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with Thermidistat™to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.
G. Easy Select™—702B & 602B
F. 683B Sequence of Operation

a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G—The Blower runs at
continuous fan airflow b. COOLING MODE
(1.) If indoor temperature is above temperature set point and
humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers single speed cooling airflow.
c. COOLING MODE-DEHUMIDIFICATION
DH R W1 W2 Y1 Y/Y2 G O C
(1.) If indoor temperature is above temperature set point and
humidity is above humidity set point, Thermidistat™ closes circuits R to G, R to Y/Y2, R to O and Thermidis- tat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system.
E
d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (SEE QUICK REFERENCE GUIDE)
(1.) If the indoor temperature is below the temperature set
point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and closes circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling.
Fig. 11—Detail of SPP Printed-Circuit Board
EASY SELECT™CONFIGURATION TAPS FOR 702B & 602B Easy Select™taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used. a. AUX HEAT kW/CFM—SELECT HEATER RANGE FOR
e. GAS HEATING MODE
(Occurs if outdoor temperature is below outdoor temperature change over setpoint.)
(1.) Thermostat closes circuit R to W/W1—The unit delivers
the selected gas heat airflow. The IGC will control 45 sec. on delay with no airflow and 45 sec. off delay. f. HEAT PUMP HEATING MODE
Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked with a range of heaters for which airflow (also marked), is approved. For increased comfort, select the narrowest kW range matching the heater size, for example, 0–10 for 10–kW heater. This airflow must be greater than the minimum for CFM for electric heater application with the size system installed for safe and continuous operation. (See Tables 16, 17 & 18 for airflow delivery and minimum CFM.) Note that airflow marked is the
(Occurs if outdoor temperature is above outdoor temperature change over setpoint.)
(1.) Thermidistat™closes circuit R to G and R to Y/Y2–The
unit delivers selected heat pump heating airflow. g. HEATING MODE—SUPER COMFORT HEAT OPERA-

airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ICM will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved (See Fig. 11, A as indicated).
(2.) MED speed—Move connector to MED, 65 percent cooling
mode airflow.
(3.) HI speed—Move connector to HI, 100 percent cooling
mode airflow (See Fig. 11, F as indicated). g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE
The low-voltage circuit is fused by a board-mounted 5–amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol.
b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED
The factory setting for air conditioner or heat pump size is the size which matches the model of packaged unit installed. Installer should verify air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes (See Fig. 11, B as indicated).
h. BASIC UNIT CONFIGURATION
The following basic configuration of the indoor motor will provide ARI rated performance of the System. This BASIC CONFIGURATION should be used when the rated ARI perfor- mance is required, or if system enhancements such as super dehumidify are not needed.
c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED
The type of system will be factory selected (see below for details):
(1.) AUX HEAT kW/CFM-Select the heater range for the size
of electric heater installed (skip this step if no heater is installed).
(1.) AC-Air conditioner (Factory Selected for 702B)
(2.) HP-COMFORT—Heat Pump Comfort provides approxi-
mately 315 CFM per ton for higher normal heating air delivery temperature and provides approximately 350 CFM per ton cooling airflow for good humidity removal.
(2.) AC/HP SIZE-Factory selected to match system size in-
stalled, please verify.
(3.) SYSTEM TYPE-Factory selected AC (702B) or HP-EFF
(602B).
(3.) HP-EFF (Factory Selected for 602B)— Heat Pump Effi-
ciency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton.
(4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM
for 036 & 060, and LO for 024 & 030.
(5.) ON/OFF DELAY-Select 0/90 profile.
d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
mostat is set to continuous fan.
The AC/HP CFM Adjust select is factory set to the High-Hi (NOM for 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. CFM Adjust selection options are provided to adjust airflow supplied to meet indi- vidual installation needs for such things as noise, comfort, and humidity removal (See Fig. 11, D as indicated).
i. COMFORT OPTIONS—SUPER DEHUMIDIFY (See Quick
The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat™control (Super Dehumidify does not require an outdoor temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort: This configuration will im- prove the comfort provided by the air conditioning system if more humidity removal is desired. While providing this im- proved comfort, the system will operate efficiently, but not at the published HSPF or ARI SEER efficiency. The following system configuration is recommended for maxi- mum heating and cooling/dehumidifying comfort (See Fig. 11).
e. ON/OFF DELAY—SELECT DESIRED
Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 11, E as indicated). Selection options are:
(1.) The standard 90 sec off delay (Factory Setting) at 100
(1.) AUX HEAT kW/CFM-Select the narrowest heater range to
match size of electric heater installed (skip this step if no heater is installed).
percent airflow in cooling or heat pump heating mode.
(2.) A 30 sec cooling delay with no airflow/90 sec off delay at
(2.) AC/HP Size-Factory selected to match system size in-
100 percent airflow profile is used when it is desirable to allow system coils time to heat-up/cool-down in conjunc- tion with the airflow in cooling or heat pump heating mode.
stalled, please verify.
(3.) SYSTEM TYPE-Select system type HP-COMFORT (for
heat pump system) or AC (for air conditioner system).
(3.) A no delay option used for servicing unit or when a
(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).
thermostat is utilized to perform delay functions.
(5.) ON/OFF DELAY-Select ENH profile.
(4.) ENH, enhanced selection, provides a 30 sec cooling on
(6.) CONTINUOUS FAN-Select desired fan speed when ther-
delay with no airflow/ plus 150 sec at 70 percent airflow/ no off delay for added comfort. This will minimize cold blow in heat pump operation (602B only) and could enhance system efficiency.
mostat is set to continuous fan.
(7.) DEHUMIDIFY MODE-Remove J1 jumper to activate.
(8.) LOW VOLTAGE CONNECTIONS-Make connections as
f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED
shown in ELECTRICAL CONNECTIONS section.
(9.) CONFIGURE THERMIDISTAT™(or capable zoning
(1.) LO speed—Factory setting, 50 percent cooling mode
system)-Following its installation instructions for Super Dehumidify and Super Comfort Heat operation.
airflow.
Reference Guide)

This configuration provides the following comfort enhance- ments:
BLOCK
(a.) A 30 sec blower on delay with 150 sec at 70 percent
airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100 percent airflow reducing the cold blow sensation at start up in heating and allowing the indoor coil to more quickly reach wet coil operating conditions in cooling.
HUMIDISTAT
REMOVE
R
(b.) A no blower off delay eliminates cold blow which may
be associated with running the blower after shut down of the compressor and avoids re-evaporation of con- densed moisture after cooling/dehumidifying opera- tion.
Fig. 13—Humidistat Wiring for De-Humidify Mode-for
(c.) Lower airflow while the compressor is running to
reduce draft effects and increase heating air tempera- ture and improved humidity control during cooling operation.
standard humidistat. The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode, remove jumper J1 and wire in a standard humidistat ( See Fig. 13).
ACCESSORY INSTALLATION a. ACCESSORY ELECTRIC HEATERS
Electric heaters may be installed with the 702B & 602B units per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits.
b. AUXILIARY TERMINALS
f. DEHUMIDIFY AND SUPER DEHUMIDIFY CAPABILITIES
The AUX and HUM terminals on the Easy Select™Board are tied directly to the G terminal, and provide a 24-v. signal whenever the G terminal is energized (See Fig. 12). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of the operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.
these models are capable of responding to a signal from indoor system control (thermostat, Thermidistat™, zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of unit is required.
H. 702B & 602B Sequence Of Operation
c. ELECTRONIC AIR CLEANER CONNECTIONS
a. CONTINUOUS FAN
The AUX1 and AUX2 terminals are not always energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow Sensor P/N KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the blower is operating.
(1.) Thermostat closes circuit R to G—The Blower runs at
continuous fan airflow.
b. COOLING MODE-LOW HUMIDITY
(1.) If indoor temperature is above temperature set point and
d. HUMIDIFIER/HUMIDISTAT CONNECTIONS
humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers cooling airflow.
Easy Select™Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat (See Fig. 12). These terminals are energized with 24-v. when G thermostat signal is present. (See Fig. 11, 12 & 13). Alternately, the 24-v. signal may be sourced from the W and C circuit board connections. When using a Thermidistat™Control, Zone Perfect Plus or Comfort Zone II, the 24-v. signal may be sourced directly from the Thermidis- tat™HUM terminal.
c. COOLING MODE-DEHUMIDIFICATION
(1.) If indoor temperature is above temperature set point and
humidity is above humidity set point, thermostat or Ther- midistat™closes circuits R to G, R to O, and R to Y/Y2 and humidistat or Thermidistat™opens R to DH—The unit delivers airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent capacity of the system. d. COOLING MODE-SUPER DEHUMIDIFY OPERATION (see
HUM 1
24-VAC
TO HUMIDIFIER
(G)
HUMIDIFIER WIRING
A95317
Fig. 12—Humidifier Wiring for 702B & 602B
(1.) If the indoor temperature is below the temperature set
e. DEHUMIDIFY CAPABILITY WITH STANDARD
point and the humidity is above the humidity set point, the Thermidistat™closes circuit R to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested
Latent capacities for these units are better than average systems. If increased latent capacity is an application requirement, the circuit board provides connection terminals for use of a
quick reference guide)

value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling. e. ELECTRIC HEATING MODE
I. 583B START-UP (ICM FIOP) CHECKING COOLING CONTROL OPERATION-Start and check the unit for proper cooling control operation as follows:
(1.) Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position. Note fan delay time setting selected on the Easy Select™board. (See Easy Select Section.)
(1.) Thermostat closes circuit R to W/W1, or W2—The unit
delivers the selected electric heat airflow. There are no on or off delays. f. HEAT PUMP HEATING MODE (602B only)
(2.) Place SYSTEM switch in COOL position and FAN switch
(1.) Thermostat closes circuits R to G and R to Y/Y2—The unit
in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the time setting selected on Easy Select™board. (See Easy Select Section.)
delivers selected heat pump heating airflow. g. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT (602B only)
(1.) Thermostat closes circuits R to G, R to Y/Y2 and R to
W/W1 or W2 (and R to O in the case of defrost). In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.
(3.) When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO position. Observe that unit operates in heating mode when tempera- ture control is set to “call for heating” (above room temperature) and operates in cooling mode when tempera- ture control is set to “call for cooling” (below room temperature).
AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges. The heating operation airflow must produce a temperature rise that falls with in the approved range. Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required. CHECK HEATING CONTROL-Start and check the unit for proper heating control operation as follows. (see furnace lighting instructions located inside burner or blower access panel.):
h. HEATING MODE—SUPER COMFORT HEAT OPERA-
NOTE: The indoor control used, such as a Thermidistat™, must be capable of providing Super Comfort Heat operation mode and control must be configured as outlined in its installation instruc- tions. The system must be installed with appropriate outdoor temperature sensor. Consult indoor control literature to determine if control is capable and for configuration instructions. Consult indoor control instructions and sensor instructions for sensor installation details.
If the outdoor temperature is in the range of 12° to 40° F, the Thermidistat™closes circuit R to Y/Y2 and opens circuit R to G. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full heating requested value. If circuit R to G is open (0-v.) for maximum heating comfort, the motor delivers reduced airflow to maximize the temperature and minimize the draft effect of the heated air leaving the unit.
(1.) Place room thermostat SYSTEM switch in the HEAT
position and the FAN switch in the AUTO position.
(2.) Set the heating temperature control of the thermostat above
room temperature.
(3.) The induced-draft motor will start.
ICM FIOP START-UP ICM General Start Up CHECKING AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with Puron® (R-410A) refrigerant, and is tested and factory sealed. NOTE: Adjustment of the refrigerant charge is not required UNLESS the unit is suspected of not having the proper R-410A charge. The charging label and the tables shown refer to system tempera- tures and pressures. The temperatures and pressures are calculated at rated airflow. When charging unit, set to rated airflow. A refrigerant charging chart label is attached to the outside of the compressor access door. The chart includes the required suction line temperature at given suction line pressures and outdoor ambients. An accurate superheat, thermocouple- or thermistor-type thermometer, and gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement IMPORTANT: When evaluating the refrigerant charge, an indi- cated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insuf- ficient airflow across either one or both coils.
(4.) After a call for heating, the main burner should light with
in 5 sec. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the lockout control, break the 24-v. power to W.
(5.) The indoor fan will turn on 45 sec after the flame has been
established. The indoor fan will turn off according to time delay selected on the Easy Select™board (See Easy Select Section) after the thermostat has been satisfied.
II. 683B START-UP (ICM FIOP) Also refer to the Thermidistat™instructions for start up and check out of the system.
The fan button on Thermidistat™switches fan icon between AUTO and ON. While ON is displayed, output will be on, turning fan on. Allow up to 10 sec. after button is pressed for fan to turn on and off. the fan will continue to run for the time setting selected on the Easy Select™ board after AUTO icon is displayed.
Press MODE button on the Thermidistat™until COOL icon is displayed. Cooling begins within 10 sec. and

remains on for 4 minutes. Observe that compressor, outdoor fan and indoor blower motors start after the call for Cooling. At the end of 4 minutes, the cooling cycle stops and the MODE reverts back to OFF. The Indoor Blower continues to run for the time selected on the Easy Select™board after OFF icon is displayed.
(3.) When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in heating mode when tempera- ture control is set to ‘‘call for heating’’ (above room temperature) and operates in cooling mode when tempera- ture control is set to ‘‘call for cooling’’ (below room temperature). NOTE: Once the compressor has started and then has stopped, it will not start again until 5 minutes have elapsed. (The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit between ther- mostat terminal R to terminals Y and G.) These open circuits de-energize contactor coil C and ICM board. The condenser and compressor motors stop. After the time delay setting selected on the Easy Select™board (See Easy Select Section) , the blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat.
Press MODE button on the Thermidistat™until HEAT icon is displayed. Heat pump heating begins within 10 sec. and remains on for 4 minutes. Observe that the compres- sor, outdoor fan and indoor blower come on. At the end of the 4 minutes, heating cycle stops and the MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™Board after the OFF icon is displayed. Heating maybe turned off anytime during the 4 minute cycle by pressing MODE button until OFF is displayed.
IV. 602B: START-UP (ICM FIOP) CHECKING COOLING AND HEATING CONTROL OPERA- TION– Start and check the unit for proper control operation as follows:
Press MODE button until E-HEAT(Emergency Heat or Back-Up Heat) icon is displayed. Gas heating begins within 10 sec. and remains on for 4 minutes. The induced draft motor should start immediately. The burners should light within 5 sec. of E-HEAT call. The indoor blower will turn on 45 sec. after the flame has been established. Gas heating stops at the end of 4 minutes and MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™Board after the OFF icon is displayed.
(1.) Place room thermostat SYSTEM switch or MODE control
in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down according to time delay selected on the Easy Select™ board (See Easy Select Section) when FAN MODE switch is placed in AUTO position.
(2.) Thermostat:
When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (through unit wire G) across the 24-v. secondary of transformer (TRAN). Thermidistat™or Thermostat and Humidistat: When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O, DH, and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (though unit wire G) across the 24-v. secondary of transformer (TRANS).
To test AUTO CHANGE-OVER function between COOL and HEAT: Enable the AUTO CHANGE-OVER mode during Thermi- distat™set-up. Refer to the Thermidistat™literature for details. Observe that the unit operates in cooling when in COOL MODE (when setting is below room temperature) and HEAT MODE (when setting is above room tempera- ture).
AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges. The heating operation airflow must produce a temperature rise that falls with in the approved range. Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required.
(3.) Place system switch or MODE control in HEAT position.
Set control above room temperature. Observe that com- pressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down according to time delay selected on the Easy Select™board (See Easy Select Section) when control setting is satisfied.
(4.) When using an automatic changeover room thermostat,
place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to “call for Cooling” (below room temperature), and unit operates in Heating mode when temperature control is set to “call for Heating” (above room temperature). NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit between thermostat terminal R to terminals Y and G. These open circuits de-energize contactor coil C and ICM board. The con- denser and compressor motors stop. After the time delay setting selected on the Easy Select™board (See Easy Select Section) , the
CHECKING COOLING CONTROL OPERATION–Start and check the unit for proper cooling control operation as follows:
(1.) Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
(2.) Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the selected off delay.

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 583B 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 290 290 313 313 321 321 382 382 COMPRESSORS
Quantity (lb.) 5.0 5.0 5.5 5.5 6.9 6.9 9.0 9.0
Orifice ID (in.) Check-Flo-Rater™Piston
.057 .065 .065 .070 .070
Rows...Fins/in. Face Area (sq ft)
1...17 10.9 1...17 10.9 1...17 12.7 1...17 12.7 2...17 9.1 2...17 9.1 2...17 12.3 2...17 12.3
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
Nominal Cfm Diameter (in.) Motor HP (Rpm)
Rows...Fins/in. Face Area (sq ft)
3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 3.7 3...15 4.7 3...15 4.7
800 10 X 10 1/2
800 10 X 10 1/2
1000 10 X 10 1/2
1000 10 X 10 1/2
1200 11 X 10 3/4
1200 11 X 10 3/4
1400 11 X 10 3/4
1400 11 X 10 3/4
Size (in.) Motor (HP)
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
2...44 2...50 2...38 2...46 2...44 2...50 2...38 2...46 2...38 2...46 3...38 3...46 2...38 2...46 3...38 3...46
Natural Gas Burner Orifice No. (Qty...Drill Size)
610 ± 15 420 ± 25
PRESSURE SWITCH
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1
* Based on altitude of 0 to 2000 ft.
blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat. The 5 minute compressor delay also applies to heat pump heating mode.
I. PHYSICAL DATA & ELECTRICAL SCHEMATICS Use the Physical Data and Electrical Tables on the following pages for information that applies to Bryant Puron® units with the ICM indoor motor FIOP.
To clean the blower motor and wheel:
a. Remove unit access panel.
II. TABLES FOR SYSTEM SET-UP Use the Airflow and Temperature Rise Tables on the following pages for information that applies to Bryant Puron® units with the ICM indoor motor FIOP.
b. Carefully pivot blower access panel outward towards the
electrical box. Route wiring above blower access panel.
c. Disconnect the 5 and 16 pin plugs at the blower motor.
d. On all units, remove blower assembly from unit. Re-
move screws securing blower to vertical partition and slide assembly out. Be careful not to tear insulation in blower compartment.
Indoor Blower and Motor NOTE: All motors are pre-lubricated. Do not attempt to lubricate these motors. For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
e. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 583B 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 4 4 4 5 5 5 OPERATING WEIGHT (lb.) 421 421 421 468 468 468 COMPRESSORS
Quantity (lb.) 9.5 9.5 9.5 10.0 10.0 10.0
Orifice ID (in.) Check-Flo-Rater™Piston
.073 .073 .073 .086 .086 .086
Rows...Fins/in. Face Area (sq ft)
2...17 12.3 2...17 12.3 2...17 12.3 2...17 16.4 2...17 16.4 2...17 16.4
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
Rows...Fins/in. Face Area (sq ft)
4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7
1600 11 X 10 3/4
1600 11 X 10 3/4
1600 11 X 10 3/4
2000 11 X 10 1.0
2000 11 X 10 1.0
2000 11 X 10 1.0
Size (in.) Motor (HP)
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
3...38 3...46 3...33 3...42 3...31 3...41 3...38 3...46 3...33 3...42 3...31 3...41
Natural Gas Burner Orifice No. (Qty...Drill Size)
610 ± 15 420 ± 25
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1
* Based on altitude of 0 to 2000 ft.
VOLTAGE
RANGE COMPRESSOR OUTDOOR FAN
INDOOR FAN
MOTOR POWER SUPPLY
UNIT SIZE 583B V-PH-HZ
MOTOR
MIN MAX RLA LRA FLA FLA MCA MAX FUSE OR CKT. BKR. 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 22.1 30 030 208/230–1–60 187 253 14.7 73.0 0.9 4.3 23.6 30 036 208/230–1–60 187 253 15.4 83.0 0.9 6.8 27.0 35 042 208/230–1–60 187 253 18.6 105.0 0.9 6.8 31.0 40 048 208/230–1–60 187 253 20.5 109.0 1.6 6.8 34.0 40 060 208/230–1–60 187 253 27.6 158.0 1.6 9.2 45.2 60
f. Loosen set-screw that secures wheel to motor shaft,
d. Reassemble wheel into housing.
remove screws that secure motor mount brackets to blower housing, and slide motor and motor mount out of blower housing.
e. Reassemble motor into housing. Be sure set-screw(s) are
tightened on motor shaft flats and not on round part of shaft.
f. Pivot blower access panel back into place. Adjust wire
assemblies so that wiring follows proper pathways.
g. Reinstall unit access panel.
b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
START-UP CHECKLIST


Fig. 14—ICM FIOP Electric Schematic—Unit 583B

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 024040 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 310 324 324 321 321 380 380 COMPRESSORS
Quantity (lb.) 7.0 8.9 8.9 9.3 9.3 9.5 9.5
Orifice Indoor (in.) Check-Flo-Rater™Piston
0.061 0.061 0.061 0.067 0.067 0.073 0.073
Orifice Outdoor (in.) Check-Flo-Rater™Piston
0.032 (2) 0.040 (2) 0.040 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.038 (2)
2...17 8.5 2...17 10.3 2...17 10.3 2...17 10.3 2...17 10.3 2...17 13.5 2...17 13.5
Rows...Fins/in. Face Area (sq ft)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2500 22 1/4 (1100)
2500 22 1/4 (1100)
2350 22 1/8 (825)
2350 22 1/8 (825)
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
INDOOR COIL Rows...Fins/in. Face Area (sq ft)
3...15 3.7 3...15 3.7 3...15 3.7 4...15 3.7 4...15 3.7 3...15 4.7 3...15 4.7
INDOOR BLOWER Nominal Airflow (Cfm)
1000 10 X 10 1/2
1000 10 X 10 1/2
1200 11 X 10 3/4
1200 11 X 10 3/4
1400 11 X 10 3/4
1400 11 X 10 3/4
Size (in.) Motor (HP)
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
2...44 2...50 2...44 2...50 2...38 2...46 2...38 2...46 3...38 3...46 2...38 2...46 3...38 3...46
Natural Gas Burner Orifice No. (Qty...Drill Size)
610 ± 15 420 ± 25
PRESSURE SWITCH
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1
* Based on altitude of 0 to 2000 ft.

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 4 4 4 5 5 5 OPERATING WEIGHT (lb.) 409 409 409 504 504 504 COMPRESSORS
Quantity (lb.) 10.6 10.6 10.6 12.4 12.4 12.4
Orifice Indoor (in.) Check-Flo-Rater™Piston
.076 .076 .076 .088 .088 .088
Orifice Outdoor (in.) Check-Flo-Rater™Piston
0.046 (2) 0.046 (2) 0.046 (2) 0.052 (2) 0.052 (2) 0.052 (2)
2...17 13.5 2...17 13.5 2...17 13.5 2...17 15.4 2...17 15.4 2...17 15.4
Rows...Fins/in. Face Area (sq ft)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
INDOOR COIL Rows...Fins/in. Face Area (sq ft)
4...15 4.7 4...15 4.7 4...15 4.7 4...15 5.7 4...15 5.7 4...15 5.7
INDOOR BLOWER Nominal Airflow (Cfm)
1600 11 X 10 3/4
1600 11 X 10 3/4
1750 11 X 10 1.0
1750 11 X 10 1.0
1750 11 X 10 1.0
Size (in.) Motor (HP)
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
3...38 3...46 3...33 3...42 3...31 3...41 3...38 3...46 3...33 3...42 3...31 3...41
Natural Gas Burner Orifice No. (Qty...Drill Size)
610 ± 15 420 ± 25
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1
* Based on altitude of 0 to 2000 ft.
VOLTAGE
RANGE COMPRESSOR OUTDOOR FAN
INDOOR FAN
MOTOR POWER SUPPLY
UNIT SIZE 683B V-PH-HZ
MOTOR
MIN MAX RLA LRA FLA FLA MCA MAX FUSE OR CKT. BKR. 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 22.1 30 030 208/230–1–60 187 253 15.9 73.0 0.9 4.3 25.1 35 036 208/230–1–60 187 253 16.9 83.0 1.6 6.8 29.5 40 042 208/230–1–60 187 253 22.4 105.0 0.9 6.8 35.7 50 048 208/230–1–60 187 253 21.3 109.0 1.6 6.8 35.0 50 060 208/230–1–60 187 253 27.6 158.0 1.6 9.2 45.3 60


Fig. 15—ICM FIOP Electric Schematic—Unit 683B

THIS DATA APPLIES TO 702B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb) 270 291 299 321 326 399 COMPRESSOR Scroll REFRIGERANT (R-410A)
Quantity (lb) 5.0 5.5 6.9 9.0 9.5 10.0
Check-Flo-Rater™Piston .057 .057 .065 .070 .073 .086 CONDENSER COIL
Orifice ID (in.)
1...17 10.9 1...17 12.7 2...17 9.1 2...17 12.3 2...17 12.3 2...17 16.4
Rows...Fins/in. Face Area (sq. ft.)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
2350 22 1/8 (825)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
Nominal Cfm Diameter (in.) Motor Hp (Rpm)
3...15 3.7 3...15 3.7 3...15 3.7 3...15 4.7 4...15 4.7 4...15 4.7
Rows...Fins/in. Face Area (sq. ft.)
Size (in.) Motor (HP)
610 ± 15 420 ± 25
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

VOLTAGE
OUTDOOR
INDOOR
ELECTRIC
SINGLE POINT POWER SUPPLY
RANGE COMPRESSOR
FAN MOTOR
FAN MOTOR
UNIT SIZE 702B V-PH-HZ
HEAT
MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP
-/- 3.8/5.0 5.4/7.2 7.5/10.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7
22.1/22.1 27.9/31.4 37.8/42.9 50.5/57.5
30/30 30/35 40/50 60/60
–
024 208/230–1–60 187 253 13.5 61.0 0.9 4.3
-/- 3.8/5.0 5.4/7.2 7.5/10.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7
23.5/23.5 27.9/31.4 37.8/42.9 50.5/57.5
30/30 30/35 40/50 60/60
–
030 208/230–1–60 187 253 14.7 73.0 0.9 4.3
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5
27.0/27.0 31.1/34.5 40.9/46.0 53.6/60.6 76.2/86.6
35/35 35/40 50/50 60/– –
–/70 80/90
036 208/230–1–60 187 253 15.4 83.0 0.9 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
31.0/31.0 31.1/34.5 40.9/46.0 53.6/60.6 76.2/86.6 98.8/112.7
40/10 40/40 50/50 60/– – –
–/70 90/90 100/125
042 208/230–1–60 187 253 18.6 105.0 0.9 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
34.0/34.0 34.0/34.5 40.9/46.0 53.6/60.6 76.2/86.6 98.8/112.7
40/40 40/40 50/50 60/- – –
–/70 90/90 100/125
048 208/230–1–60 187 253 20.5 109.0 1.6 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
45.2/45.2 45.2/45.2 43.8/48.9 56.5/63.5 79.1/89.5 101.6/115.5
60/60 60/60 50/50 60/- – –
–/70 90/90 110/125
060 208/230–1–60 187 253 27.6 158.0 1.6 9.1
* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer to Multiplication FactorsTable 23.


Fig. 16—ICM FIOP Electrical Schematic—702B

THIS DATA APPLIES TO 602B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 602B024 602B030 602B036 602B042 602B048 602B060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 299 320 328 350 355 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REFRIGERANT R-410A REFRIGERANT METERING DEVICE Check-Flo-Rater™ Refrigerant (R-410A) Quantity (lb.) 7.0 8.9 9.3 9.5 10.6 12.4 ORIFICE ID (in.) 0.061 0.061 0.067 0.073 0.076 0.088 ORIFICE OD (in.) 0.032 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.046 (2) 0.052 (2) OUTDOOR COIL
2...17 8.5 2...17 10.3 2...17 10.3 2...17 13.5 2...17 13.5 2...17 15.4
Rows... Fins/in. face area (sq. ft.)
OUTDOOR FAN Nominal Airflow (CFM)
2350 22 1/8 (825)
2350 22 1/8 (825)
2800 22 1/4 (1100)
2500 22 1/8 (825)
3300 22 1/4 (1100)
3300 22 1/4 (1100)
Diameter Motor HP (RPM)
INDOOR COIL Rows... Fins/in. face area (sq. ft.)
3...15 3.7 3...15 3.7 4...15 3.7 3...15 4.7 4...15 4.7 4...15 5.7
INDOOR BLOWER Nominal Airflow (CFM)
1000 10 X 10 1/2
1200 10 X 10 3/4
1400 11 X 10 3/4
1600 11 X 10 3/4
2000 11 X 10 1
Size (in.) Motor (HP)
610 ± 15 420 ± 25
20 ± 5 45 ± 10
RETURN-AIR FILTERS (in.)
throwaway 20 X 20 X 1 20 X 20 X 1 20 X 24 X 1 24 X 30 X 1 24 X 30 X 1 24 X 30 X 1

VOLTAGE
OUTDOOR
INDOOR
ELECTRIC
SINGLE POINT POWER SUPPLY
RANGE COMPRESSOR
FAN MOTOR
FAN MOTOR
UNIT SIZE 602B V-PH-HZ
HEAT
MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP
-/- 3.8/5.0 5.4/7.2 7.5/10.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7
22.1/22.1 44.6/48.1 54.5/59.6 67.2/74.2
30/30 50/50 60/– –
– – –/70 70/80
024 208/230–1–60 187 253 13.5 61.0 0.9 4.3
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5
25.1/25.1 47.6/51.1 57.4/62.6 70.2/77.2 92.8/103.2
30/30 60/60 – – –
– – 70/70 80/80 100/110
030 208/230–1–60 187 253 15.9 73.0 0.9 4.3
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5
29.5/29.5 52.1/55.6 61.9/67.0 74.7/81.6 97.2/107.7
40/40 60/60 – – –
– – 70/80 80/90 100/110
036 208/230–1–60 187 253 16.9 83.0 1.6 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
35.7/35.7 58.3/61.7 68.1/73.2 80.8/87.8 103.4/113.0 126.0/139.9
50/50 –
– 70/70 80/80 90/90 110/125 150/150
042 208/230–1–60 187 253 22.4 105.0 0.9 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
35.0/35.0 57.6/61.1 67.4/72.5 80.2/87.1 102.7/113.2 125.3/139.2
50/50 –
– 70/70 80/80 90/90 110/125 150/150
048 208/230–1–60 187 253 21.3 109.0 1.6 6.8
-/- 3.8/5.0 5.4/7.2 7.5/10.0 11.3/15.0 15.0/20.0
-/- 18.1/20.8 25.9/30.0 36.1/41.7 54.2/62.5 72.2/83.3
45.1/45.1 67.7/71.1 77.7/82.8 90.2/97.2 112.8/123.2 135.4/149.3
60/60 –
– 80/80 90/90 100/110 125/125 150/150
060 208/230–1–60 187 253 27.6 158.0 1.6 9.2
* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer to Multiplication FactorsTable 23.


Fig. 17—ICM FIOP Electrical Schematic—602B

TABLE 11–583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY)
SMALL CABINET
CFM ADJUST
PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0
COOLING † 745 675 – 835 750 690 940 880 815 COOLING DEHUMIDIFY 675 625 – 675 650 600 755 730 705
HEAT PUMP COMFORT (683B Only) 670 605 – 740 690 635 845 795 735
COOLING † 940 860 785 1020 965 895 1185 1100 1010 COOLING DEHUMIDIFY 820 785 735 820 800 770 955 920 880
HEAT PUMP COMFORT (683B Only) 850 780 745 935 905 845 1055 1040 955
COOLING † 1025 935 – 1145 1085 1005 1320 1260 1180 COOLING DEHUMIDIFY 925 885 – 925 900 870 1060 1040 1010
HEAT PUMP COMFORT (683B Only) 955 880 – 1075 990 920 1220 1180 1125
† On 683B Only Heat Pump Efficiency and Cooling pin selections deliver equal airflow
TABLE 12—583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY)
LARGE CABINET
CFM ADJUST
PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0
COOLING † 1100 1225 1410 COOLING DEHUMIDIFY 980 980 1125
HEAT PUMP COMFORT (683B Only) 990 1100 1265
COOLING † 1260 1400 1610 COOLING DEHUMIDIFY 1120 1120 1290
HEAT PUMP COMFORT (683B Only) 1135 1260 1450
COOLING † 1575 1750 2010 COOLING DEHUMIDIFY 1400 1400 1610
HEAT PUMP COMFORT (683B Only) 1415 1575 1810
† On 683B Only Heat Pump Efficiency and Cooling pin selections deliver equal airflow
SMALL CABINET
EASY SELECT™ BOARD SETTING (CFM) 700 800 1100 1250
Static Pressure 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0
024 040 – – – 855 770 710 – 060 – 1020 890 835 – – –
030 040 – – – 880 840 805 – 060 – 1030 970 910 – – –
036 060 – 1035 995 955 – – – 090 – 1170 1110 1025
External · Unit Size · Gas Heat Size

LARGE CABINET
EASY SELECT™ BOARD SETTING (CFM) 1000 1250 1600 1750 1800
Static Pressure 0.0–1.0
042 060 1000 – 090 – 1250 – – –
048 090 – 1250 – – – 115 – – 1600 – – 130 – – – 1750 –
060 090 – 1250 – – – 115 – – 1600 – – 130 – 1800
TABLE 15—583B & 683B ICM AIR FLOW VS. TEMPERATURE RISE CHART
AIRFLOW SETTING
CALCULATED TEMPERATURE
MIN. TEMP
MAX TEMP
MAX DISCH.
SIZE
EASY SELECT™
(X 1000)
(SCFM)
RISE
RISE
RISE
TEMP
024 40 800 36.5 20 50 175 60 (583B Only) 1100 40 35 65 165
030 40 800 36.5 20 50 175 60 1100 40 35 65 165
036 60 1100 40 25 55 165 90 1200 54 45 75 175
042 60 1000 44 20 50 165 90 1250 53 35 65 170
048 90 1250 53 25 55 165 115 1600 53 35 65 170 130 1750 54 40 70 175
060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175
TABLE 16—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW
CFM ADJUST
PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0
COOLING † 800 725 – 885 805 730 990 930 855 COOLING DEHUMIDIFY 715 670 – 715 695 645 795 775 745
HEAT PUMP COMFORT (602B Only) 720 660 – 790 745 685 890 850 785
COOLING † 1010 920 825 1105 1030 930 1255 1160 1050 COOLING DEHUMIDIFY 890 845 795 890 865 825 1010 980 925
HEAT PUMP COMFORT (602B Only) 945 850 765 1020 965 895 1140 1105 995
COOLING † 1110 1025 970 1235 1175 1115 1400 1355 1280 COOLING DEHUMIDIFY 990 960 910 990 975 940 1125 1110 1085
HEAT PUMP COMFORT (602B Only) 1035 975 910 1160 1080 1020 1305 1275 1220
† Heat Pump Efficiency and Cooling pin selections deliver equal airflow
External · Unit Size · Gas Heat Size

TABLE 17—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW
CFM ADJUST
PIN SELECT LO PIN NOM PIN HI PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0
COOLING † 1100 1225 1410 COOLING DEHUMIDIFY 980 980 1125
HEAT PUMP COMFORT (602B Only) 990 1100 1265
COOLING † 1260 1400 1610 COOLING DEHUMIDIFY 1120 1120 1290
HEAT PUMP COMFORT (602B Only) 1135 1260 1450
COOLING † 1575 1750 2010 COOLING DEHUMIDIFY 1400 1400 1610
HEAT PUMP COMFORT (602B Only) 1415 1575 1810
† Heat Pump Efficiency and Cooling pin selections deliver equal airflow
TABLE 18—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)
602B 750 1025 1250 1285 1710 1800 702B 750 750 1250 1205 1500 1800
SMALL CABINET
STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0.00 0.02 0.04 0.06 0.07 7.5 kW 0.00 0.02 0.03 0.05 0.07 0.08 0.09 10 kW 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.11 15 kW 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 20 kW 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19
TABLE 20— ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)
STATIC CFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 5 kW 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 7.5 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 10 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 15 kW 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 20 kW 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16

TABLE 21—ICM FIOP WET COIL PRESSURE DROP (IN. WG)
STANDARD CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 024 0.005 0.007 0.010 0.012 0.015 – 030 – 0.007 0.010 0.012 0.015 0.018 0.021 0.024 – 036 – – – 0.019 0.023 0.027 0.032 0.037 0.042 0.047 – 042 – 0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043 – – – 048 – 0.027 0.032 0.036 0.041 0.046 0.052 0.057 0.063 0.068 – 060 – 0.029 0.032 0.036 0.040 0.045 0.049 0.053
FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — 20 X 24 X 1 — 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — 24 X 30 X 1 — 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
HEATER KW
VOLTAGE DISTRIBUTION
MULTIPLICATION
RATING
FACTOR
200 .69 208 .75 230 .92 240 1.00
Example: 15.0 kW (at 240-v.) heater on 208-v. = 15.0 (.75 mult. factor) = 11.25 capacity at 208-v.

AND SUPER HUMIDITY CONTROL IN COOLING
A. AUX HEAT - Set for heater size (Ex: 0-10 for 10 kw) B. AC/HP SIZE - Set for size of outdoor unit C. SYSTEM TYPE - Select "HP COMFORT" D. AC/HP CFM ADJUST - Select "LO" E. ON/OFF DELAY - Select "ENH" F. CONTINUOUS FAN - Select desired speed 2. Remove Jumper J1 to activate all dehumidify modes. 3. Complete wiring and install outdoor temperature sensor according to Installation Instructions.
J1
EASY SELECT
TM
AUX HEAT KW/CFM 0-30 1075
0-20 875 0-10 725
VIO
AC/HP SIZE
036 030 024 018
BLU
SYSTEM TYPE
DH R W1 W2 Y1 Y/Y2 G O C
THERMIDISTAT™ CONTROL SETTINGS
ORN
AC/HP CFM ADJUST
D
NOM HI
LO
ON/OFF DELAY
0 90 30 90 0 0
E
ENH
WHT
AUX1 HUM1
F
MED HI YEL LO
HUM2 YEL
AUX2
24VAC
HEATER/MOTOR
GRY
ICM QUICK REFERENCE GUIDE
TABLE 24—TROUBLESHOOTING CHART

Blower wheel not secured to shaft Inspect and properly tighten blower wheel to shaft Insufficient voltage at motor Determine cause and correct Power connectors not properly seated Connectors should snap easily; do not force
0-5 625

START-UP CHECKLIST (Remove and Store in Job File) I. Preliminary Information MODEL NO.: SERIAL NO.: DATE: TECHNICIAN:
II. PRE-START-UP (Insert checkmark in box as each item is completed) ( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE) ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS ( ) MAKE SURE THAT - ON 060 SIZE PURON HEATPUMP, ONLY-THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED.
III. START-UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR (EVAPORATOR) FAN AMPS TEMPERATURES OUTDOOR (CONDENSER) AIR TEMPERATURE DB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB HEAT PUMP SUPPLY AIR GAS HEAT SUPPLY AIR ELECTRIC HEAT SUPPLY AIR PRESSURES GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE IN. WG REFRIGERANT SUCTION PSIG SUCTION LINE TEMP* REFRIGERANT DISCHARGE PSIG DISCHARGE TEMP† ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TEMPERATURE RISE TEMPERATURE RISE (LITERATURE) RANGE MEASURED TEMPERATURE RISE *Measured at suction inlet to compressor †Measured at liquid line leaving condenser.
Heat Settings
IV. EASY SELECT SETTINGS FULL UNIT MODEL NUMBER: ENTER AVAILABLE HEATSETTINGS ENTER AVAILABLE AIRFLOW HEAT AIR PIN CONNECTION SETTING ENTER AVAILABLE SIZES SIZE PIN CONNECTION SETTING TYPE PIN CONNECTION SETTING ADJUST PIN CONNECTION SETTING DELAY PIN CONNECTION SETTING (0/0 or 0/90 for gas/electric models) CONTINOUS FAN PIN CONNECTION SETTING
System Type AC HP-Comfort HP.Eff AC/HP CFM Adjust Norm Lo Hi On/Off Delay
0⁄90 30⁄90 0⁄0 ENH Continous Fan Lo Med Hi

© 2001 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —30— Printed in U.S.A. ii583b243 Catalog No. 5358-308