Instruction/ maintenance manual of the product 598B Bryant
Go to page of 40
Form No. PDS 598B.24.4 TWO-SPEED PURON® PLUS™ ELECTRIC AIR CONDITIONER 598B (60 HZ) Sizes 024, 036, 048, and 060 • T W O - S P E E D • ™ Model 598B Air Conditioners incor porate innov ativ e 2-speed compressor technology with Puron ® , the refrigerant of the future, to pro vide quiet, ef fi cient cooling performance.
— 2 — DIMENSIONS A01062 DIMENSIONS (IN.) SOUND PO WER (dBA) *Sound lev els at high and low speeds are equivalent. UNIT SIZE SERIES A B C D E F G H K L M N MINIMUM MOUNTING P AD DIMENSIONS 024 A 33.
— 3 — RECOMMENDED TUBE DIAMETERS NO TE: Maximum long-line tube length of 50 ft liquid and v apor line sets indicated abov e must be f ollowed on all applications . Over 50 ft, refer to Application Guide- line and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant.
— 4 — SPECIFICA TIONS * P er missible limits of the voltage r ange at which the unit will operate satisf actor ily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 5 — COMBINA TION RA TINGS UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 024-A FV4ANF003* 735 440 24,000 12,000 15 11.7 CC5A/CD5AA024 885 475 23,600 11,400 12.25 10.05 CC5A/CD5AA030 900 520 24,000 11,400 12.
— 6 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 024-A COILS + 333(B,J)A V036060 V ARIABLE SPEED FURNA CE CC5A/CD5AA024 735 500 23,200 11,600 14 10.95 CC5A/CD5AA030 735 500 23,600 11,800 14.45 11.15 CC5A/CD5AA036 735 500 24,000 12,000 15 11.
— 7 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 036-A CK5P A036 1,300 720 34,800 17,600 13.5 10.5 CK5P A042 1,300 720 34,800 17,600 13.5 10.5 CK5P A048 1,300 720 35,000 17,600 13.5 10.6 CK5PE042 1,300 720 35,000 17,600 13.
— 8 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 036-A CC5A/CD5A C048 1,050 700 33,800 17,800 15.5 11.4 CC5A/CD5A W036 1,050 700 34,000 17,800 15.5 11.45 CC5A/CD5A W042 1,050 700 34,200 17,800 15.5 11.6 CC5A/CD5A W048 1,050 700 34,200 17,800 16 11.
— 9 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 036-A CK5PT036 1,100 680 34,400 17,800 15.5 11.25 CK5PT042 1,100 680 34,400 17,800 15.5 11.35 CK5PT048 1,100 680 34,800 18,000 15.5 11.5 CK5PW036 1,100 680 34,400 17,800 15.
— 10 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 036-A CC5A/CD5A W036 1,200 800 34,600 18,000 15 10.9 CD5AA048 1,200 800 34,800 18,000 15 11.05 CE3AA036 1,200 800 34,000 17,800 14.5 10.7 CE3AA042 1,200 800 34,800 18,000 15 10.
— 11 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 048-A FV4ANB006* 1,470 880 47,500 26,000 15 11.55 CC5A/CD5AA060 1,700 985 45,500 26,000 13 10.3 CC5A/CD5AA060 1,700 985 45,500 26,000 13 10.3 CC5A/CD5A C048 1,665 985 44,500 25,800 12.
— 12 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 048-A CE3AA060 1,400 875 46,000 26,000 15 11.35 CK3BA048 1,400 875 45,000 26,000 15 11.1 CK3BA060 1,400 875 46,000 26,000 15 11.35 CK5A/CK5BA048 1,400 875 45,000 26,000 15 11.
— 13 — UNIT SIZE INDOOR SECTION INDOOR AIR CFM T O T . CAP . BTUH SEER EER High Low High Low 048-A CE3AA060 1,600 1000 46,000 26,000 14 10.2 CK3BA048 1,600 1000 44,500 26,000 13.5 9.85 CK3BA060 1,600 1000 46,000 26,000 14 10.25 CK5A/CK5BA048 1,600 1000 44,500 26,000 13.
— 14 — * T ested combination. EER — Energy Ef fi ciency Ratio SEER — Seasonal Energy Ef fi ciency Ratio NO TES: 1. Ratings are net values re fl ecting the eff ects of circulating fan motor heat. Supplemental electr ic heat is not included. 2.
— 15 — DET AILED COOLING CAP A CITIES* EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal Syste.
— 16 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 17 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 18 — DET AILED COOLING CAP A CITIES* See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity .
— 19 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 20 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 24 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 25 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 26 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 27 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 28 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 29 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 30 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 31 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 32 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 33 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 34 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 35 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 36 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 37 — DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 38 — DET AILED COOLING CAP A CITIES* continued * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
— 39 — System Design 1. Intended for outdoor installation with free-air inlet and outlet. Outdoor f an external static pressure a vailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature is 55 ° F (12.8 ° C). 3. Lo w-ambient operation accessory is not av ailable.
— 40 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 598B.24.3 © 2002 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No.
An important point after buying a device Bryant 598B (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant 598B yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant 598B - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant 598B you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant 598B will certainly help you make a decision on the purchase.
If you already are a holder of Bryant 598B, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant 598B.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant 598B. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant 598B along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center