! WARNING
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. Puronr (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
It is important to recognize safety information. This is the safety-alert symbol
. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
CAUTION !
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.


C11110 Fig. 1 - Unit Dimensional Drawing — Sizes 07-09



C11111 Fig. 1 - Unit Dimensional Drawing — Sizes 07-09 (cont.)


Vertical Connections / Economizer

C11112 Fig. 2 - Unit Dimensional Drawing — Size 12


C11113 Fig. 2 - Unit Dimensional Drawing — Size 12 (cont.)

Be sure that the unit is installed such that snow will not block the combustion intake or flute outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Complete the following checks before installation.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA- -54- -84- -1. In Canada, installation must be in accordance with the CAN1- -B149 installation codes for gas burning appliances.
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.

Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
Required bottom condensate drain connection. Otherwise, 36” (914mm) for condensate connection.
C10145 Fig. 3 - Service Clearance Dimensional Drawing
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Table 1 – Operating Weights

Roof Mount —

Step 4 — Provide Unit Support
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 4 and Fig. 5. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
Install curb Install field-fabricated ductwork inside curb Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details) Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 11 for details) Rig and place unit Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 6. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired, use factory-supplied pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.
Prepare pad and unit supports Check and tighten the bottom condensate drain connection plug Rig and place unit Convert unit to side duct connection arrangement Install field-fabricated ductwork at unit duct openings Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.
Frame-mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Curb-Mounted Installation — · Pad-Mounted Installation — · Frame-Mounted Installation —



C11081 Fig. 4 - Roof Curb Details — Sizes 07-09


C11082 Fig. 5 - Roof Curb Details — Size 12


A minimum clearance is not required around ductwork.

PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roofing materials. Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
DIFFERENCE IN. (MM)
C06110 Fig. 6 - Unit Leveling Tolerances
Step 6 — Rig and Place Unit
Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 7 for additional information.

For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Lifting holes are provided in base rails as shown in Fig. 7. Refer to rigging instructions on unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed for handling by fork truck.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
Before setting the unit onto the curb, recheck gasketing on curb.

Fig. 7 - Rigging Details

Positioning on Curb —
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
Position unit on roof curb so that the following clearances are maintained: 1/4 in. (6.4 mm) clearance between the roof curb and the base rail inside the front and back, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Fig. 4 and Fig. 5, section C-C.
Economizer and Two Position Damper Hood Package Removal and Setup - Factory Option
1. The hood is shipped in knock-down form and must be field assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are packaged together, attached to a metal support tray us- ing plastic stretch wrap, and shipped in the return air compartment behind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie- wraps. 2. To gain access to the hood, remove the filter access panel. (See Fig. 9.)
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48 in. (1220 mm) from an adjacent building or combustible material.

After unit is in position, remove rigging skids and shipping materials.
Step 7 — Convert to Horizontal and Connect Ductwork (when required) Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 8.
C10146 Fig. 9 - Typical Access Panel Locations


Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
C06108 Fig. 8 - Horizontal Conversion Panels
C08639 Fig. 10 - Economizer and Two-Position Damper
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Hood Parts Location

each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter. 5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 13. 6. Caulk the ends of the joint between the unit top panel and the hood top. 7. Replace the filter access panel.
Economizer Hood and Two-Position Hood —


FILTER CLIP
INDOOR COIL ACCESS PANEL
C08634 Fig. 13 - Economizer Filter Installation
C06025 Fig. 11 - Indoor Coil Access Panel Relocation
Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 14.


C07081 Fig. 14 - Flue Hood Details
Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
C06026 Fig. 12 - Economizer Hood Construction

This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.

NOTE: Furance gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.
1/2 3/4 or 1 11/4 or larger
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to the 1/2-in. or 3/4-in. FPT gas inlet port on the unit gas valve.
C11091 Fig. 15 - Gas Piping Guide (with Accessory Thru-the-Curb Service Connections)
Factory-Option Thru-Base Connections (Gas Connections) —
Table 2 – Natural Gas Supply Line Pressure Ranges
This service connection kit consists of a NPT gas adapter fitting, an electrical bulkhead connector and a 3/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section.

581J 07, 08, 09, 12 4.0 in. wg (996 Pa)

EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to equipment. When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe smaller than the size specified. Size the gas supply line to allow for a maximum pressure drop of 0.5-in wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.
C008621 Fig. 16 - Thru-Base Connection Fittings
The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru-curb/under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 15.
Check tightness of connector lock nuts before connecting gas piping.
Gas Line: Install a 1/2-in (08 & 09 size Low Gas units only) or 3/4-in (for all other units) NPT street elbow on the thru-base gas fitting. Attach an appropriate size pipe nipple with minimum length of 16-in (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 17.



C08579 Fig. 17 - Gas Line Piping
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6-ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9-in (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4-ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 18 and Fig. 19 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 20 for typical piping arrangement when thru-base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
C07469 Fig. 18 - Gas Piping with Thru-Curb Accessory

When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4-in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter. 2. Protect all segments of piping system against physical and thermal damage. Support all piping with appro- priate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than 1/2-in., follow recommendations of national codes. 3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connec- tions. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s in- structions. 4. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connect- ing piping to unit.
C07470 Fig. 19 - Gas Piping with Thru-Curb Accessory

C08018 Fig. 20 - Gas Piping with Thru-Base Accessory
Unit Base Rail · (alternate layout)

NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 22. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a 1/2-in. square socket drive extension.
Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations).
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a 1/2-in. square socket drive extension) and install it in the side drain connection.

FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. S Connect gas pipe to unit using a backup wrench to

avoid damaging gas controls. S Never purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections. S Use proper length of pipe to avoid stress on gas
ALTERNATE BOTTOM DRAIN
DRAIN (FACTORY-INSTALLED)
PLUG
C08021 Fig. 22 - Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 23.


MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE BASE RAIL
C08022 Fig. 23 - Condensate Drain Piping Details
A93059 Fig. 21 - Orifice Hole
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).

Field power wires will be connected line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect.
Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size is #4 AWG (copper only).
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
FIRE HAZARD Failure to follow this warning could result in intermittent operation or performance satisfaction. Do not connect aluminum wire between disconnect switchand581J unit. Use onlycopper wire. (See Fig. 25.)
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads (see Fig. 24).
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
Units Without Disconnect Option
A93033 Fig. 25 - Disconnect Switch and Unit
Units with Factory-Installed Disconnect —
The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel.
Units Without Factory-Installed Disconnect —
When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
Units With Disconnect Option
All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 24 for power wiring connections to the unit power terminal block and equipment ground. Maximum wire size is #4 ga AWG per pole.
Disconnect factory test leads and discard.
C11109 Fig. 24 - Power Wiring Connections

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.
circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 26.
Installing Weatherproof Cover: A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 208-v 1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information.
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 5. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 5, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL POWER.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 27. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.

ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock-out and tag-out this switch, if necessary.
RECEPTACLE NOT INCLUDED


C09022 Fig. 27 - Weatherproof Cover Installation
Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.
C08128 Fig. 26 - Convenience Outlet Location
Unit-powered type: A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the
Two types of convenience outlets are offered on 581J models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault
Convenience Outlets — · Pwd-CO Transformer · Convenience

convenience outlet; access is through the unit’s control box access panel. See Fig. 26.
Using unit- mounted convenience outlets: Units with unit- mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non-fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 28.
Factory-Option Thru-Base Connections (Electrical Connections) —
This service connection kit consists of a 1/2-in electrical bulkhead connector and a 11/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. The 1/2-in bulkhead connector enables the low-voltage control wires to pass through the basepan. The 11/4-in electrical bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 16.

Check tightness of connector lock nuts before connecting electrical conduits.
Field-supplied and field-installed liquidtight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.
Units without Thru-Base Connections —
Fig. 28 - Powered Convenience Outlet Wiring
Field Control Wiring —
The 581J unit requires an external temperature control device. This device can be a thermostat emulation device provided as part of a third-party Building Management System.
Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps (i.e., limit loads exceeding 8-amps to 30 minutes of operation every hour).
Install a Bryant-approved accessory 2-stage thermostat according to installation instructions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.
Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.
Thermostat —

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire (35_C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Unit without Thru-Base Connection Kit —
Pass the thermostat control wires through the hole provided in the end panel (see item “D” in the view labeled “LEFT” in Fig. 1 or Fig. 2); then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Central Terminal Board (CTB). See Fig. 30.


C08027 Fig. 30 - Field Control Wiring Raceway
C09350 Fig. 29 - Typical Low-Voltage Control Connections
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available.

Perfect Humidityt Control Connections
Perfect Humidity - Space RH Controller —
The Perfect Humidity dehumidification system requires a field-supplied and -installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination thermostat-humidistat control device such as Bryant’s EDGER Pro Thermidistat with isolated contact set for dehumidification control. The humidistat is normally used in applications where a temperature control is already provided (such as a third-party Building Management System).
To connect a field-supplied humidistat:
1. Route the humidistat 2-conductor cable (field-sup- plied) through the hole provided in the unit corner post. 2. Feed wires through the raceway built into the corner post (see Fig. 30) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring. 3. Use wire nuts to connect humidistat cable to two PINK leads in the low–voltage wiring as shown in Fig. 32. Refer to the instructions for the field-sup- plied humidistat for more information.
C09502 Fig. 31 - Edge Programmable Thermostat
To connect the Edge Programmable Thermidistat (T6-PRH01-A):
1. Route the Edge Programmable Thermostat multi- conductor cable (field-supplied) through the hole provided in the unit corner post. 2. Feed wires through the raceway build into the corner post (see Fig. 30) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring. 3. The Edge Programmable Thermostat has dry contacts at terminals D1 and D2 for dehumidification operation (see Fig. 33). The dry contacts must be wired between CTB terminal R and the PINK lead to the LTLO switch with field-supplied wire nuts. Refer to the installation instructions included with the Bryant Edge Programmable Thermidistat device for more information.


C11071 Fig. 32 - Typical Perfect Humidityt Dehumidification System Humidistat Wiring

C09501 Fig. 33 - Typical Rooftop Unit with Perfect Humidity Dehumidification System with Edge Programmable Thermostat

The RTU Open controller is an integrated component of the Bryant rooftop unit. Its internal application programming provides optimum performance and energy efficiency. RTU Open enables the unit to run in 100% stand-alone control mode, Bryant’s I-Vu Open network, or a Third Party Building Automation System (BAS). On-board DIP switches allow you to select your protocol (and baud rate) of choice among the four most popular protocols in use today: BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 34.)
The RTU Open control is factory-mounted in the 48DC*D unit’s main control box, to the left of the CTB. See Fig. 35. Factory wiring is completed through harnesses connected to the CTB. Field connections for RTU Open sensors will be made at the Phoenix connectors on the RTU Open board. The factory-installed RTU Open control includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package.
Refer to Table 3, RTU Open Controller Inputs and Outputs for locations of all connections to the RTU Open board.

C10811 Fig. 34 - RTU Open Multi-Protocol Control Board


C11069 Fig. 35 - RTU Open System Control Wiring Diagram


C11070 Fig. 36 - RTU Open System Control Wiring Diagram with Perfect Humidityt

Table 3 – RTU Open Controller Inputs and Outputs
POINT NAME BACnet OBJECT
NUMBER(S)
DEDICATED INPUTS Space Temp / Zone Temp zone_temp AI (10K Thermistor) J20---1, 2 Supply Air Temperature sa_temp AI (10K Thermistor) J2---1, 2 Outdoor Air Temperature oa_temp AI (10K Thermistor) J2---3, 4 Space Temperature Offset Pot stpt_adj_offset AI (100K Potentiometer) J20---3 Safety Chain Feedback safety_status DI (24 VAC) J1---9 Compressor Safety Status comp_status DI (24 VAC) J1---2 Fire Shutdown Status firedown_status DI (24 VAC) J1---10 Enthalpy Status enthalpy_status DI (24 VAC) J2---6 Humidistat Input Status humstat_status DI (24 VAC) J5---7
CONFIGURABLE INPUTS Indoor Air CO2 iaq AI (4---20 ma)
J4---2 or J4---5 Outdoor Air CO2 oaq AI (4---20 ma) Space Relative Humidity space_rh AI (4---20 ma) Supply Fan Status* sfan_status DI (24 VAC)
J5 5 or J5---7 Filter Status* filter_status DI (24 VAC) Door Contact Input* door_contact_status DI (24 VAC) Occupancy Contact* occ_contact_status DI (24 VAC)
J5---1 or J5---3 or
OUTPUTS Economizer Output econ_output AO (4---20ma) J2---5 Supply Fan Relay State sfan DO Relay (24VAC , 1A) J1---4 Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J1---8 Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J1---7 Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J1---6 Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J1---5 Power Exhaust Relay State pexh DO Relay (24VAC , 1A) J11---3 Dehumidification Relay State dehum DO Relay (24VAC, 1A) J11---7, 8
LEGEND AI --- Analog Input AO --- Analog Output DI --- Discrete Input DO --- Discrete Output * These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.
The RTU Open controller requires the use of a Bryant space sensor. A standard thermostat cannot be used with the RTU Open system.

Supply Air Temperature (SAT) Sensor —
On FIOP-equipped 581J unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.
The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 37.
ROOF CURB
C08200 Fig. 37 - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.


The RTU Open control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU Open control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field-installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO2 sensor Outdoor air CO2 sensor
Field connections for accessory sensors and input devices are made the RTU Open, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post as shown in Fig. 30. The raceway provides the UL required clearance between high- and low-voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU Open. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.
C08201 Fig. 38 - T-55 Space Temperature Sensor Wiring
SEN
C08460 Fig. 39 - RTU Open T-55 Sensor Connections
Connect T-56: See Fig. 40 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to RTU Open J20-1, J20-2 and J20-3 per Fig. 41.
There are 2 types of SPT sensors available from Bryant, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone operation for back-up. Refer to the configuration section for details on controller configurations associated with space sensors.

S 33ZCT55SPT, space temperature sensor with override
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment (T-56)
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and setpoint adjustment (T-59)
C08202 Fig. 40 - T-56 Internal Connections
Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used.
J20-2 SEN
Connect T-55: See Fig. 38 for typical T-55 internal connections. Connect the T-55 SEN terminals to RTU Open J20-1 and J20-2. See Fig. 39.
J20-3 SET
C08461 Fig. 41 - RTU Open T-56 Sensor Connections
EconoMi$er2 — · button (T-55) · Jumper

Connect T-59: The T-59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 42 for internal connections at the T-59. Connect the SEN terminal (BLU) to RTU Open J20-1. Connect the COM terminal (BRN) to J20-2. Connect the SET terminal (STO or BLK) to J20-3.


0-10VDC SIG COM 4-20mA
8 7 6 5 4 3 2 1 2 1
C08635 Fig. 43 - Indoor/Outdoor Air Quality (CO2) Sensor
(33ZCSENCO2) - Typical Wiring Diagram
Wiring the Indoor Air Quality Sensor: For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
C10291 Fig. 42 - Space Temperature Sensor Typical Wiring
Indoor Air Quality (CO2) Sensor —
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 43. Connect the 4-20 mA terminal to RTU Open J4-2 and connect the SIG COM terminal to RTU Open J4-3. See Fig. 44.
The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.
The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 43 for typical CO2 sensor wiring schematic.
24 VAC
C08462 Fig. 44 - RTU Open / Indoor CO2 Sensor
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) —
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 45. The outdoor air CO2 sensor must be located in the economizer outside air hood.
IAQ Sensor · (33ZCSENCO2) Connections


Space Humidity Sensor or Humidistat —
Perfect Humidityt Control Wiring: In units equipped with the Perfect Humidity option there are two pink (PNK) wires loose in the control box used to control the dehumidification function of the unit. These pink wires are meant to be tied to a space humidistat or thermidistat on an electromechanical unit. On RTU Open equipped units these pink wires must be connected to J11-7 & 8 to allow the Open board to operate the dehumidification function for the unit. Disconnect the J11 Phoenix style connector from the board and use the plug screws to secure the pink wires in pins 7 and 8, reconnect the plug to the board at J11. Relative Humidity Sensors (Space or Duct Mounted): The accessory space humidity sensor (33ZCSENSRH-01) or duct humidity sensor (33ZCSENDRH-01) is used to measure the relative humidity of air within the space or return air duct. The RH reading is used to control the Perfect Humidityt option of the rooftop unit. For wiring distances up to 500 ft (152 m), use a 3-conductor, 18 or 20 AWG shielded cable. The shield must be removed from the sensor end of the cable and grounded at the unit end. The current loop power for sensor is provided by the RTU Open controller as 24vdc. Refer to the instructions supplied with the RH sensor for the electrical requirements and terminal locations. RTU Open configurations must be changed after adding an RH sensor. See Fig. 47 and 48 for typical RH sensor wiring.
C07135 Fig. 45 - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO2 Sensor: A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 43. Connect the 4 to 20 mA terminal to RTU Open J4-5. Connect the SIG COM terminal to RTU Open J4-6. See Fig. 46.
S J4-1 or J4-4 = 24vdc loop power
S J4-2 or J4-5 = 4-20mA signal input

MOUNTING HOLES
24 VAC
WIRING OPENING
C08463 Fig. 46 - RTU Open / Outdoor CO2 Sensor
Smoke Detector/Fire Shutdown (FSD) —
On 581J units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open controller communicates the smoke detector’s tripped status to the BAS building control. See Figs. 35 and 36, the RTU Open System Control wiring schematics.
The Fire Shutdown Switch configuration, MENU→Config→Inputs→input 5, identifies the normally open status of this input when there is no fire alarm.
Vin - J4-1 or J4-4 24Vdc Io - J4-2 or J4-5 -20mA output
C11087 Fig. 47 - Space Relative Humidity Sensor Typical Wiring
OAQ Sensor/RH Sensor · (33ZCSENCO2) Connections

J4-1 or J4-4 + 24 VDC Supply Voltage

J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
Relative Humidity Sensor (Polarized Male Connector)
4-20 VAC GND 0-5V mA or or VDC 0-10V
C10839 Fig. 48 - Duct Relative Humidity Sensor Typical Wiring
Humidistat: Use of a field-supplied humidistat provides the RTU Open insight to the relative humidity in the space. The humidistat reads the RH level in the space and compares it to its setpoint to operate a dry contact. The humidistat is a dedicated input on the configurable input 9 and tells the RTU Open when the RH level is HIGH or LOW. The normal condition for humidity is LOW. A normally open humidistat is the factory default control for the Perfect Humidityt option.
Remote Occupancy: The remote occupancy accessory is a field-installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Remote Occupancy and normally open (N/O) or normally closed (N/C).
Also set MENU→Schedules→occupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 34 and Table 3 for wire terminations at J5.
S J5-7 = Signal input
Power Exhaust (output): The relay used by the RTU Open board to control power exhaust is a dry contact which means it does not have 24vac. This 24vac must be connected to the relay to allow it to operate the power exhaust relay in the PE accessory. A 24vac source must be provided to J11-2 on the RTU Open control board. This can be provided by the unit’s transformer from various sources. The “R” terminal on the unit’s low voltage terminal board (LVTB) is a logical source. Refer to Fig. 34 and Figs. 35 or 36 for wire terminations at J11.
Connecting Discrete Inputs —
Filter Status: The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 34 and Figs. 35 or 36 for wire terminations at J5.
Fan Status: The fan status accessory is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 34 and Figs. 35 or 36 for wire terminations at J5.
to RTU-OPEN

The RTU Open can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig. 49 and 50 for protocol switch settings and address switches. The 3rd party connection to the RTU Open is through plug J19. See Fig. 51 for wiring. NOTE: Power must be cycled after changing the SW1-3 switch settings. Contact your Bryant applications engineer for more detailed information on protocols, 3rd party wiring, and networking.
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.

PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP (Master) Unused OFF OFF OFF ON OFF Select Baud Select Baud
Modbus (Slave) Unused OFF OFF ON ON OFF Select Baud Select Baud
N2 (Slave) Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF


Fig. 49 - RTU Open SW3 Dip Switch Settings


C10815 Fig. 50 - RTU Open Address Switches
C10816 Fig. 51 - Network Wiring
General — · Baud Rate Selections

Virtual BACview: Virtual BACview is a freeware computer program that functions as the BACview6 Handheld. The USB Link interface (USB-L) is required to connect a computer to the RTU Open board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld.
BACview6 Handheld: The BACview6 is a keypad/display interface used to connect to the RTU Open to access the control information, read sensor values, and test the RTU, see Fig. 52. This is an accessory interface that does not come with the RTU Open controller and can only be used at the unit. Connect the BACview6 to the RTU Open J12 local access port. There are 2 password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is idle. Contact your Bryant applications engineer for details on navigation and screen content.
RTU Open Troubleshooting —
Communication LEDs The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear. See Table 4.

P5 P5
BACview6 Local Access Cable
C10812 Fig. 52 - BACview6 Handheld Connections

Table 4 – LEDs The LEDs on the RTU Open show the status of certain functions

Rx RTU Open is receiving data from the network segment
Tx RTU Open is transmitting data over the network segment
The Run and Error LEDs indicate control module and network status
If Run LED shows... And Error LED shows... Status is...
2 flashes per second Off Normal
2 flashes per second 2 flashes, alternating with Run LED Five minute auto---restart delay after system error
2 flashes per second 3 flashes, then off Control module has just been formatted
2 flashes per second 4 flashes, then pause
Two or more devices on this network have the same ARC156 network address
2 flashes per second On Exec halted after frequent system errors or control programs halted
5 flashes per second On Exec start---up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second 7 flashes per second, alternating with Run LED Ten second recovery period after brownout
14 flashes per second 14 flashes per second, alternating with Run LED Brownout
Failure. Try the following solutions: S Turn RTU Open off, then on. S Format RTU Open. S Download memory to RTU Open. S Replace RTU Open.
PL6-1 (24-V)
GND
BLK
PL6-4 (COM)
Outdoor Air Enthalpy Control (PNO 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 53.)
C11169 Fig. 53 - Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 53. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.
On On · Enthalpy Switch · Factory Wiring Harness

Return Air Enthalpy Sensor —
Mount the return-air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy controller (33CSENTHSW). See Fig. 54.
The controller (see Fig. 55) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face).

BLK
PL6-4 (COM)
GRA
Return Air Enthalpy Sensor

C11170 Fig. 54 - Outside and Return Air Enthalpy Sensor
To wire the return air enthalpy sensor, perform the following:
Conduit couplings (supplied by installer)
C08208 Fig. 55 - Controller Assembly
Smoke detectors are available as factory-installed options on 581J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.
The sensor module (see Fig. 56) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left-side of the housing).
Units equipped with factory-optional Return Air smoke detectors require a relocation of the sensor module at unit installation. See “Completing Installation of Return Air Smoke Sensor:” on page 36 for details.
Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically
The smoke detector system consists of a four-wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device.

takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc.

The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not.
For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition.
C08245 Fig. 57 - Typical Supply Air Smoke Detector Sensor
Return Air without Economizer —
The sampling tube is located across the return air opening on the unit basepan. See Fig. 58. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See “Completing Installation of Return Air Smoke Sensor:” on page 36 for details.)

Return Air Detector module (shipping position shown)*

C08209 Fig. 56 - Smoke Detector Sensor
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307 Fig. 58 - Typical Return Air Detector Location
Return Air with Economizer —
The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 59. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See the following installation procedure.)
The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 57. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-off filter panel.



Return Air Sampling Tube
C08126 Fig. 60 - Return Air Detector Shipping Position

C08129 Fig. 59 - Return Air Sampling Tube Location
1. Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 60. Save the screws. 2. Remove the Return Air Sensor and its detector plate. 3. Rotate the detector plate so the sensor is facing out- wards and the sampling tube connection is on the bot- tom. See Fig. 61. 4. Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the ex- haust tube is on the top. See Fig. 61. 5. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
C08127 Fig. 61 - Return Air Sensor Operating Position
Additional Application Data —
Refer to Catalog No. HKRNKA-1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.
Screws · Flexible Exhaust Tubes · Sample Tube

Table 5 – Unit Wire/Fuse or HACR Breaker Sizing Data

MED 34.3 50 34 185 38.1 50 38 189
HIGH 41.8 60 43 211 45.6 60 47 215
MED 17.1 25 17 94 18.9 25 19 96
HIGH 21.1 30 22 107 22.9 30 24 109
MED 13.3 20 13 76 17.1 20 17 80
HIGH 16.1 20 16 90 19.9 25 21 94
MED 38.8 50 41 202 42.6 50 45 206
HIGH 43.6 50 46 245 47.4 60 51 249
MED 17.9 20 19 101 19.7 25 21 103
HIGH 19.7 25 21 123 21.5 25 23 125
MED 12.7 15 13 81 16.5 20 18 85
HIGH 13.5 15 14 92 17.3 20 19 96
MED 39.0 50 41 202 42.8 50 45 206
HIGH 43.8 50 46 245 47.6 60 51 249
MED 18.2 20 19 101 20.0 25 21 103
HIGH 20.0 25 21 123 21.8 25 23 125
MED 14.0 20 15 81 17.8 20 19 85
HIGH 14.8 20 16 92 18.6 20 20 96
MED 52.0 60 55 325 55.8 60 60 329
HIGH 57.0 70 61 334 60.8 70 65 338
MED 24.8 30 26 157 26.6 30 28 159
HIGH 27.8 30 30 161 29.6 35 32 163
MED 18.1 20 19 116 21.9 25 24 120
HIGH 20.9 25 22 130 24.7 30 27 134
See: “Legend and Notes for Table 5” on page 39.

Table 5 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)

MED 39.1 50 39 190 42.9 60 44 194
HIGH 46.6 60 48 216 50.4 60 52 220
MED 19.3 25 19 96 21.1 30 22 98
HIGH 23.3 30 24 109 25.1 30 26 111
MED 15.0 20 15 78 18.8 25 19 82
HIGH 17.8 25 18 92 21.6 25 23 96
MED 43.6 50 46 207 47.4 60 51 211
HIGH 48.4 60 52 250 52.2 60 56 254
MED 20.1 25 21 103 21.9 25 23 105
HIGH 21.9 25 23 125 23.7 30 26 127
MED 14.4 20 15 83 18.2 20 20 87
HIGH 15.2 20 16 94 19.0 25 21 98
MED 43.8 50 46 207 47.6 60 51 211
HIGH 48.6 60 52 250 52.4 60 56 254
MED 20.4 25 22 103 22.2 25 24 105
HIGH 22.2 25 24 125 24.0 30 26 127
MED 15.7 20 17 83 19.5 25 21 87
HIGH 16.5 20 18 94 20.3 25 22 98
MED 56.8 70 61 330 60.6 70 65 334
HIGH 61.8 70 66 339 65.6 80 71 343
MED 27.0 30 29 159 28.8 35 31 161
HIGH 30.0 35 32 163 31.8 35 34 165
MED 19.8 25 21 118 23.6 30 26 122
HIGH 22.6 25 24 132 26.4 30 29 136
See: “Legend and Notes for Table 5” on page 39.

LEGEND: BRKR --- Circuit breaker CO --- Convenient outlet DISC --- Disconnect FLA --- Full load amps LRA --- Locked rotor amps MCA --- Minimum circuit amps PE --- Power exhaust PWRD CO --- Powered convenient outlet UNPWR CO --- Unpowered convenient outlet NOTES:
AB = 224 v BC = 231 v AC = 226 v
(224 + 231 + 226)
Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
= 1.76%
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.


Economizer 2 Position Damper Unit Without Economizer or 2 Position Damper
C10150 Fig. 62 - EconoMi$ert IV Wiring
High Altitude Gas kits Flue Discharge Deflector Flue Exhaust Heat Shield Low Ambient Controls Thermostat / Sensors Two-Position motorized outside air damper EconoMi$er2 (without control/for external signal and integrated barometric relief) EconoMi$er2 (without control/for external signal) Power Exhaust Differential dry-bulb sensor (EconoMi$er IV) Outdoor enthalpy sensor Differential enthalpy sensor CO2 sensor Louvered hail guard Phase monitor control Winter Start kit
Smoke detector(s) will be connected at the Controls Connections Board, at terminals marked “Smoke Shutdown”. Remove jumper JMP 3 when ready to energize unit.
EconoMi$er IV Occupancy Switch —
Refer to Fig. 62 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Central Terminal Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY on CTB. Remove or cut jumper JMP 2 to complete the installation.
Available accessories include:
Refer to separate installation instructions for information on installing these accessories.
Roof Curb Thru-base connection kit (must be installed before unit is set on curb) LP conversion kit Manual outside air damper
This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed Pre-Start and Start-up instructions.
Copyright 2011 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/11