B. Alternate Unit Support When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit with a minimum of three 4-in. x 4-in. pads, two at the corners and one at the unit’s center of gravity. If more than 3 pads are used, equally space them along the side.
comfort may be compromised when these lower air tempera- tures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN- SATE DRAIN The unit’s 3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications. When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
C. Slab Mount (Horizontal Units Only) Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a 6-in. gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 5A. The piping for the condensate drain and external trap can be completed after the unit is in place. All units must have an external trap for condensate drain- age. Install a trap a minimum of 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.). See Fig. 5B. The center drain plug looks like a star connection, however it can be removed with a 1/2 in. socket drive extension.
II. STEP 2 — FIELD FABRICATE DUCTWORK Secure all ducts to roof curb and building structure on verti- cal units. Do not connect ductwork to unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external duct- work, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli- cable fire codes.
IV. STEP 4 — RIG AND PLACE UNIT Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 6 for additional information. Operating weight is shown in Table 1 and Fig. 6.
A minimum clearance is not required around ductwork. Cab- inet return-air static shall not exceed –.30 in. wg with EconoMi$er+ or .45 in. wg without economizer. These units are designed for a minimum heating operation continuous return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat. To operate at lower return air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor
Lifting holes are provided in base rails as shown in Fig. 1 and 6. Refer to rigging instructions on unit.



CRRFCURB003A01 1′-2″ [356] 580F 090-151 CRRFCURB004A01 2′-0″ [610]
3/4″ [19] NPT 11/4″ [31.7]


Maintain clearance around and above unit to provide mini- mum distance from combustible materials, proper airflow, and service access. See Fig. 1A and 1B Notes. Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami- nated air.
Be sure that unit is installed so that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Position unit on roof curb so that the following clearances are maintained: 1/4-in. clearance between roof curb and base rails on each side and duct end of unit; 35/16-in. clearance between roof curb and condenser section end. (See Fig. 3, section C-C.) Locate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade. Flue vent discharge must have a minimum horizontal clear- ance of 48 in. from electric and gas meters, gas regulators, and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit so that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation com- plies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-latest year and addendum Z223.1A-latest year. In Canada, installation must be in accordance with the CAN1. B149.1 and CAN1.B149.2 installation codes for gas burning appliances.



†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 and 151 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.

†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 and 151 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.

Table 1B — Physical Data (580F091, 103, 121, 151 [ASHRAE 90.1-1999 Compliant Units])
†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 and 151 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.

Table 1B — Physical Data (580F091, 103, 121, 151 [ASHRAE 90.1-1999 Compliant Units]) (cont)
†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat. NOTE: High-static motor not available on size 150 and 151 units.
Al — Aluminum Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre- sentative for details about coated fins.

V. STEP 5 — INSTALL FLUE HOOD Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood and screen in location shown in Fig. 7.

Unit is equipped for use with type of gas shown on name- plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-latest year and addendum Z223.1A- latest year entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appli- ances when installing gas piping. For natural gas applications, gas pressure at unit gas con- nection must not be less than 4.0 in. wg (5.0 in. wg in high heat units) or greater than 13.0 in. wg while unit is operat- ing. For liquid propane applications, the pressure must not be less than 5.0 in. wg or greater than 13.0 in. wg at the unit connection. Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Support gas piping as shown in the table in Fig. 8. For exam- ple, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft.
See Fig. 8 for typical pipe guide and locations of external manual gas shutoff valve.
NFGC — National Fuel
*Field supplied. NOTE: Follow all local codes.
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
Thru-the-Curb Service Connections)
WARNING: Unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Associa- tion), latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.
Install conduit through side panel openings indicated in Fig. 1A and 1B. Route power lines through connector to ter- minal connections as shown in Fig. 9.
On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A and 2B, Note 2 to determine the percent- age of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty. NOTE: If field-installed thru-the-bottom connections are used, refer to the accessory installation instructions for power wiring and gas connections. Refer to Fig. 1A and 1B for drilling holes in basepan.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v 1/4-in. male spade terminal on the transformer and connecting it to the 208-v 1/4-in. male spade terminal from the transformer.
B. Field Control Wiring Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor- dance with thermostat installation instructions.
Refer to unit label diagram for additional information. Pig- tails are provided for field service.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
When installing units, provide a disconnect per NEC. Use copper conductors only when splice connectors are used.
All field wiring must comply with NEC and local require- ments. In Canada, electrical connections must be in accor- dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Gas Code

Route thermostat cable or equivalent single leads of colored wire from thermostat subbase terminals to low-voltage con- nections on unit (shown in Fig. 10) as described in Steps 1-4 below.
See Fig. 11. The raceway provides the UL-required (Under- writers’ Laboratories) clearance between high- and low- voltage wiring. Connect thermostat wires to screw terminals on low-voltage connection board.
If unit is mounted on roof curb and accessory thru-the-curb service plate connection is used, route wire through connec- tion plate. Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 1A and 1 B). Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box.
Set heat anticipator settings at .14 amp for the first stage and .20 amp for second-stage heating.
VOLTAGE
COMPR
OFM
POWER SUPPLY* DISCONNECT
UNIT 580F NOMINAL VOLTAGE
IFM TYPE
SIZE† Min Max Qty RLA LRA Qty Hp FLA FLA MCA MOCP** FLA LRA
FAN MOTOR
FLA
40.1/40.1 45/45 42/42 229/229 Alt 5.8 40.1/40.1 45/45 42/42 229/229 High 10.6 44.9/44.9 50/50 48/48 273/273
187 254 2 14.0 91.0 2 1/4 1.4 5.8 .6
18.4 20 19 108 Alt 2.6 18.4 20 19 108 High 4.8 20.6 25 22 130
414 508 2 6.4 42.0 2 1/4 0.7 2.6 .3
090 (71/2 Tons)
14.9 20 16 97 Alt 2.6 14.9 20 16 97 High 4.8 16.7 20 18 114
518 632 2 5.2 39.0 2 1/4 0.7 2.6 .3
40.1/40.1 45/45 42/42 229/229 Alt 5.8 40.1/40.1 45/45 42/42 229/229 High 10.6 44.9/44.9 50/50 48/48 273/273
187 254 2 14.0 91.0 2 1/4 1.4 5.8 .6
18.4 20 19 108 Alt 2.6 18.4 20 19 108 High 4.8 20.6 25 22 130
414 508 2 6.4 42.0 2 1/4 0.7 2.6 .3
091 (71/2 Tons)
14.9 20 16 97 Alt 2.6 14.9 20 16 97 High 4.8 16.7 20 18 114
518 632 2 5.2 39.0 2 1/4 0.7 2.6 .3
208/230-3-60 Std 187 254 2 16.0 137.0 2 1/4 1.4 5.8 .6 44.6/44.6 50/50 47/47 321/321 High 10.6 49.4/49.4 60/60 52/52 365/365
102 (81/2 Tons)
460-3-60 Std 414 508 2 8.3 69.0 2 1/4 0.7 2.6 .3 22.7 25 24 162 High 4.8 24.9 30 26 184
575-3-60 Std 518 632 2 6.4 58.0 2 1/4 0.7 2.6 .3 17.6 20 18 135 High 4.8 19.4 25 20 152
208/230-3-60 Std 187 254 2 17.3*** 120.0*** 2 1/4 1.4 5.8 .6 44.3/44.3 50/50 46/46 272/272 High 10.6 49.1/49.1 60/60 52/52 316/316
103 (81/2 Tons)
460-3-60 Std 414 508 2 7.9*** 70.0*** 2 1/4 0.7 2.6 .3 21.0 25 22 149 High 4.8 23.2 30 24 171
575-3-60 Std 518 632 2 5.5*** 50.0*** 2 1/4 0.7 2.6 .3 16.7 20 17 109 High 4.8 18.5 25 19 126
44.2/44.2 50/50 46/46 307/307 Alt 7.5 45.9/45.9 50/50 48/48 326/326 High 15.0 53.4/53.4 60/60 57/57 374/374
187 254 2 15.8 130.0 2 1/4 1.4 5.8 .6
21.8 25 23 152 Alt 3.4 22.6 25 24 191 High 7.4 26.6 30 28 185
414 508 2 7.9 64.0 2 1/4 0.7 2.6 .3
18.1 25 19 123 Alt 3.4 18.7 25 20 155 High 7.4 21.9 30 23 150
518 632 2 6.6 52.0 2 1/4 0.7 2.6 .3
44.6/44.6 50/50 47/47 297/297 Alt 7.5 46.3/46.3 60/60 49/49 316/316 High 15.0 53.4/53.4 60/60 57/57 374/374
187 254 2 16.0 125.0 2 1/4 1.4 5.8 .6
22.0 25 24 188 Alt 3.4 22.8 25 24 191 High 7.4 26.8 30 29 182
414 508 2 8.0 62.5 2 1/4 0.7 2.6 .3
17.4 20 18 119 Alt 3.4 18.0 20 19 151 High 7.4 21.2 25 23 146
518 632 2 6.3 50.0 2 1/4 0.7 2.6 .3
208/230-3-60 Std 187 254 2 23.0 146.0 2 1/4 1.4 10.6 .6 65.2/65.2 80/80†† 68/68 383/383 Alt 15.0 69.6/69.6 80/80†† 73/73 406/406
150 (121/2 Tons)
460-3-60 Std 414 508 2 10.4 73.0 2 1/4 0.7 4.8 .3 29.6 40 31 192 Alt 7.4 32.2 45 34 203
575-3-60 Std 518 632 2 8.3 58.4 2 1/4 0.7 4.8 .3 23.6 30 25 154 Alt 7.4 25.7 30 27 162
208/230-3-60 Std 187 254 2 19.0 156.0 2 1/4 1.4 10.6 .6 56.2/56.2 70/70†† 59/59 359/359 Alt 15.0 60.6/60.6 70/70†† 64/64 378/378
151 (121/2 Tons)
460-3-60 Std 414 508 2 9.0 75.0 2 1/4 0.7 4.8 .3 26.5 30 28 174 Alt 7.4 29.1 35 31 213
575-3-60 Std 518 632 2 7.4 54.0 2 1/4 0.7 4.8 .3 21.6 25 23 127 Alt 7.4 23.7 30 25 159

NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the overcur- rent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP— Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
= 100 x max voltage deviation from average voltage
*The values listed in this table do not include power exhaust. See table below for power exhaust requirements. †Used to determine minimum disconnect per NEC. **Fuse or HACR circuit breaker. ††Fuse only. ***Compressor no. 1 data indicated in table. 208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is 105 amps. 460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps. 575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage = 452 + 464 + 455
MOCP (for separate power source) CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH024A00 1.6 N/A 0.64 15 CRPWREXH025A00 N/A 0.9 N/A 15 CRPWREXH026A00 3.3 N/A 1.32 15 CRPWREXH027A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15 CRPWREXH030A00 1.6 N/A 0.64 15
PART NO.
= 457 Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Must be in accordance with NEC or local codes. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the fol- lowing formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580FPV090 unit with MCA = 40.1 and MOCP = 45, with CRPWREXH030A00 power exhaust. MCA New = 40.1 amps + 1.6 amps = 41.7 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 45 amps and the MCA New is below 45; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

VOLTAGE
COMPR
OFM
POWER SUPPLY* DISCONNECT
UNIT 580F NOMINAL VOLTAGE
IFM TYPE
RANGE
N FAN MOTOR
SIZE†
Min Max Qty RLA LRA Qty Hp FLA FLA MCA MOCP** FLA LRA
46.1/46.1 50/50 48/48 233/233 Alt 5.8 46.1/46.1 50/50 48/48 233/233 High 10.6 50.9/50.9 60/60 53/53 273/273
187 254 2 14.0 91.0 2 1/4 1.4 5.8 .6
24.1 25 22 110 Alt 2.6 24.1 25 22 110 High 4.8 23.3 30 24 132
414 508 2 6.4 42.0 2 1/4 0.7 2.6 .3
090 (71/2 Tons)
20.9 25 18 99 Alt 2.6 20.9 25 18 99 High 4.8 19.4 25 20 117
518 632 2 5.2 39.0 2 1/4 0.7 2.6 .3
44.9/44.9 50/50 48/48 234/234 Alt 5.8 44.9/44.9 50/50 48/48 234/234 High 10.6 49.7/49.7 60/60 53/53 277/277
187 254 2 14.0 91.0 2 1/4 1.4 5.8 .6
20.6 25 22 110 Alt 2.6 20.6 25 22 110 High 4.8 22.8 30 24 132
414 508 2 6.4 42.0 2 1/4 0.7 2.6 .3
091 (71/2 Tons)
16.6 20 18 99 Alt 2.6 16.6 20 18 99 High 4.8 18.4 20 20 116
518 632 2 5.2 39.0 2 1/4 0.7 2.6 .3
208/230-3-60 Std 187 254 2 16.0 137.0 2 1/4 1.4 5.8 .6 50.6/50.6 60/60 52/52 325/325 High 10.6 55.4/55.4 60/60 58/58 369/369
102 (81/2 Tons)
460-3-60 Std 414 508 2 8.3 69.0 2 1/4 0.7 2.6 .3 25.4 30 26 164 High 4.8 27.6 35 29 138
575-3-60 Std 518 632 2 6.4 58.0 2 1/4 0.7 2.6 .3 20.3 25 20 137 High 4.8 22.1 30 22 155
208/230-3-60 Std 187 254 2 17.3*** 120.0*** 2 1/4 1.4 5.8 .6 49.1/49.1 60/60 52/52 277/277 High 10.6 53.9/53.9 60/60 57/57 320/320
103 (81/2 Tons)
460-3-60 Std 414 508 2 7.9*** 70.0*** 2 1/4 0.7 2.6 .3 23.2 30 24 151 High 4.8 25.4 30 27 173
575-3-60 Std 518 632 2 5.5*** 50.0*** 2 1/4 0.7 2.6 .3 18.4 25 19 111 High 4.8 20.2 25 21 128
50.2/50.2 60/60 52/52 311/311 Alt 7.5 51.9/51.9 60/60 54/54 330/330 High 15.0 59.4/59.4 70/70†† 62/62 378/378
187 254 2 15.8 130.0 2 1/4 1.4 5.8 .6
27.8 30 25 154 Alt 3.4 25.3 30 26 193 High 7.4 29.3 35 31 187
414 508 2 7.9 64.0 2 1/4 0.7 2.6 .3
24.1 25 21 109 Alt 3.4 24.7 25 22 141 High 7.4 24.6 30 25 136
518 632 2 6.6 52.0 2 1/4 0.7 2.6 .3
49.4/49.4 60/60 52/52 302/302 Alt 7.5 51.9/51.9 60/60 54/54 321/321 High 15.0 58.6/58.6 70/70†† 63/63 369/369
187 254 2 16.0 125.0 2 1/4 1.4 5.8 .6
24.2 30 26 151 Alt 3.4 25.0 30 26 190 High 7.4 29.0 35 31 184
414 508 2 8.0 62.5 2 1/4 0.7 2.6 .3
19.1 25 20 121 Alt 3.4 19.7 25 21 152 High 7.4 22.9 25 25 148
518 632 2 6.3 50.0 2 1/4 0.7 2.6 .3
208/230-3-60 Std 187 254 2 23.0 146.0 2 1/4 1.4 10.6 .6 71.2/71.2 80/80†† 74/74 387/387 Alt 15.0 75.6/75.6 80/80†† 79/79 410/410
150 (121/2 Tons)
460-3-60 Std 414 508 2 10.4 73.0 2 1/4 0.7 4.8 .3 35.6 40 34 194 Alt 7.4 34.9 40 37 205
575-3-60 Std 518 632 2 8.3 58.4 2 1/4 0.7 4.8 .3 29.6 35 27 156 Alt 7.4 31.7 35 29 165
208/230-3-60 Std 187 254 2 19.0 156.0 2 1/4 1.4 10.6 .6 61.0/61.0 70/70†† 65/65 364/364 Alt 15.0 65.4/65.4 80/80†† 70/70 383/383
151 (121/2 Tons)
460-3-60 Std 414 508 2 9.0 75.0 2 1/4 0.7 4.8 .3 28.7 35 30 176 Alt 7.4 31.3 35 33 215
575-3-60 Std 518 632 2 8.3 58.4 2 1/4 0.7 4.8 .3 23.3 30 25 129 Alt 7.4 25.4 30 27 160
See Legend and Notes on page 14.


LEGEND C — Contactor COMPS — Compressors IFC — Indoor (Evaporator) Fan Contactor NEC — National Electrical Code TB — Terminal Block Terminal Block Connection Splice Connection (Factory Supplied) Field Wiring Factory Wiring


The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6. 8. Adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws. 9. Remove and save screws currently on sides of hood. Insert screens. Secure screens to hood using the screws. See Fig. 14.


B. Optional EconoMi$er+ See Fig. 16 for EconoMi$er+ component locations.
Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.

6. Insert the hood divider between the hood sides. See Fig. 20. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter. 7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 21.



ECON — Economizer OAT — Outdoor-Air Temperature IAQ — Indoor-Air Quality (4 to 20 mA) ORH — Outdoor-Air Relative Humidity (Sensor) IARH — Indoor-Air Relative Humidity (Signal) POT — Potentiometer IRH — Indoor-Air Relative Humidity (Sensor) RAT — Return-Air Temperature OARH — Outdoor-Air Relative Humidity (Signal) SAT — Supply-Air Temperature

Differential Dry Bulb Changeover The control supports differential dry bulb changeover con- trol. This requires an accessory return air temperature sensor CRTEMPSN001A00 installed in the return air- stream. Refer to the Start-up section for details on how to configure and enable the control mode. The user can check the operation of the sensor using the Read function. Outdoor Air Enthalpy Changeover
FLOW IN CUBIC FEET PER MINUTE (cfm)
7 1/2 - 12 1/2 Ton
0.05 0.15 0.25
The control supports outdoor air enthalpy changeover control. This mode requires a factory-supplied outdoor air temperature sensor (OAT) and an accessory outdoor air humidity sensor (ORH) (part no. CRHUMDSN001B00). Refer to the Start-Up section for details on how to configure and enable the control mode. The user can check the operation of the sensors using the Read function. Differential Enthalpy Changeover
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
The control supports differential enthalpy changeover con- trol. This requires the factory-supplied outdoor air tempera- ture sensor, an accessory outdoor air humidity sensor, an accessory return air temperature sensor, and an accessory indoor air humidity sensor. Refer to the Start-Up section for details on how to configure and enable the control mode. The user can check the operation of the sensors using the Read function.
7 1/2-12 1/2 Ton
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
D. Damper Movement When the EconoMi$er+ board receives initial power, it will take the damper up to 21/2 minutes before it begins to posi- tion itself. After the initial positioning, subsequent changes to damper position will take up to 30 seconds to initiate. Damper movement from full open to full closed (or vice versa) takes 21/2 minutes. If the damper is in the process of changing positions (for example it is trying to open to 100%) and the fan signal is turned off, the damper will continue to its 100% open posi- tion before closing. NOTE: Occupied minimum position can not be set lower than +1% higher than the value of IAQ minimum economizer posi- tion. Refer to the setup examples on page 56.
FLOW IN CUBIC FEET PER MINUTE (cfm)
7 1/2-12 1/2 Ton
0.05 0.10 0.15 0.20 0.25 0.30 0.35
STATIC PRESSURE (in. wg)
C. EconoMi$er+ Control Mode Determine the EconoMi$er+ control mode before installing sensors and accessories. Different sensors are required for different control modes, and a number of accessories are available. Refer to Tables 3 and 4. Outdoor Dry Bulb Changeover
The EconoMi$er+ is supplied from the factory with a supply air temperature sensor and an outside air temperature sensor. This allows for operation of the EconoMi$er+ with outdoor air dry bulb changeover control. Additional accesso- ries can be added to allow for different types of change over control and operation of the EconoMi$er+ and unit.
The standard control mode for the EconoMi$er+ is Outdoor Dry Bulb Changeover. The outdoor air and supply air tem- perature sensors are also included as standard. EconoMi$er+ control is based on the outdoor temperature relative to a set point in the software. If the outdoor-air tem- perature is above the set point then the EconoMi$er should be in minimum position. If the outdoor-air temperature is below the set point, the position should be controlled to maintain the leaving air temperature set point. The set point range is 45 to 70 F.
F. Thermostats The EconoMi$er+ control works with conventional thermo- stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er+ control does not support sensor thermostats like the T56 and T57. Connections are made at the thermostat terminal con- nection board located in the main control box.

ACCESSORY OUTDOOR AIR HUMIDITY SENSOR
ACCESSORY INDOOR
APPLICATION STANDARD OUTDOOR AIR
RETURN AIR HUMIDITY SENSOR Standard Unit Included — HH79NZ039 — — — Differential
TEMPERATURE SENSOR
TEMPERATURE SENSOR
Dry Bulb Included — HH79NZ039 Required — CRTEMPSN001A00 — —
Enthalpy Included — HH79NZ039 — Required — CRHUMDSN001B00 —
Differential Enthalpy Included — HH79NZ039 Required — CRTEMPSN001A00
1. CO2 Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.). 33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO2 room sensor. 33ZCT55CO2 — Space temperature and CO2 room sensor with override. 33ZCT56CO2 — Space temperature and CO2 room sensor with override and set point. CRCBDIOX002A00 — Return air CO2 sensor. 2. All units include the following Standard Sensors: Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F. Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F. All temperature adjustments are made at the EconoMi$er+ controller.
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
DESCRIPTION PART NUMBER 71/2-121/2 Ton Power Exhaust 208-230 v 1 Ph CRPWREXH022A00
Any indoor air quality or CO2 sensor that provides a 4 to 20 mA output can be used as the IAQ sensor. The controller will modulate the outdoor-air damper to provide ventilation based on the sensor output and the IAQ setting of the control- ler. The CO2 sensor will modulate the outdoor-air damper from the minimum position (IAQ minimum damper position set point) to the maximum position (occupied minimum damper position). When there is no CO2 call, the damper will go to the unoccupied minimum position. When there is a CO2 call, the damper will be between the IAQ minimum economizer set point position and the occupied minimum damper position. Mount the sensor according to manufacturer specifications. In order to wire this sensor, an accessory 5-pin plug (part number CRE+PLUG001A00) is required. See Fig. 22.
71/2-121/2 Ton Power Exhaust 460 v 3 Ph CRPWREXH023A00
Return Air Temperature Sensor with Harness CRTEMPSN001A00
Outdoor Air Humidity Sensor with Harness CRHUMDSN001B00
Indoor Air Humidity Sensor w/Harness CRHUMDSN001B00 Return Air CO2 Sensor CRCBDIOX002A00* CO2 Room Sensor 33ZCSENCO2* Aspirator Box for Duct Mount CO2 Sensor 33ZCASPCO2
Space Temperature and CO2 Room Sensor with Override 33ZCT55CO2*
Space Temperature and CO2 Room Sensor with Override and Set Point
The IAQ sensor is wired to the ground and IAQ wires in the harness. The accessory 5-pin wiring plug is connected to pins 13-17 of J3 on the EconoMi$er+ controller. Push the plug down onto the pins of the EconoMi$er+ controller to install. Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are used for the field-installed remote potentiometer. Connect the IAQ sensor to the BRN and WHT wires of the accessory 5-pin plug.
5-Pin Sensor Wiring Plug CRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is required to install IAQ sensor.
The outdoor air temperature sensor is a 10K thermistor used to measure the outdoor-air temperature. The sensor controls EconoMi$er+ changeover and compressor lockout. The sensor is factory-installed on the EconoMi$er+ in the outdoor air- stream. The operating range of temperature measurement is 0° to158 F. See Tables 5 and 6 for thermistor resistance and resolution values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Sensor wiring should be extended with wire and wire nuts and routed to the IAQ sensor location. Adjust the IAQ set- ting at the controller to correspond to the IAQ voltage output of the sensor at the user-determined set point. See Fig. 26. Power the sensor with a field-supplied transformer.
The user can read the value of the sensor using the Read mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The EconoMi$er+ controller will accept input from the acces- sory 10K return air temperature sensor (CRTEMPSN001A00) in addition to the outdoor air temperature sensor shipped with the EconoMi$er+. By using both sensors, the outdoor air and the return air temperatures are compared (differential dry bulb) for optimal energy savings. See Tables 5 and 6 for thermistor resistance and resolution values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The supply air temperature sensor is a 10K thermistor located at the inlet to the indoor fan. This sensor must be field installed. The operating range of temperature measure- ment is 0° to158 F. See Tables 5 and 6 for thermistor resis- tance and resolution values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air · Required — CRHUMDSN001B00 · Required — CRHUMDSN001B00

The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
The controller selects the lower enthalpy air (return or out- door) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er+ control- ler opens the damper to bring in outdoor air for free cooling.
Mount the return air temperature sensor on the EconoMi$er+, through pre-punched holes. See Fig. 27.
Mount the return-air humidity sensor in the return-air duct. See Fig. 31.
The return air temperature (RAT) sensor is provided with a 2-wire, 42-in. long wiring harness with a 2-pin connector. The plug is installed on pins 5 and 6 on J3 of the EconoMi$er+ controller. The pins are labeled with a ground symbol and RAT on the EconoMi$er+ controller. See Fig. 22. The red wire of the harness is connected to pin 5 (ground). The black wire of the harness is connected to pin 6 (RAT). The wiring harness should be routed from the EconoMi$er+ controller to the sensor. The controller compares the temper- atures of the two airstreams, chooses the best one, and mod- ulates the EconoMi$er+ actuator accordingly. This 10K thermistor is used to measure the return air temperature vs. resistance curve, per Table 5. The range of temperature measurement is between 0° and 158 F. See Table 6 for resolution.
The outdoor enthalpy changeover curve is set with at the EconoMi$er+ controller. The selectable curves are A, B, C, and D. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
800 ppm 900 ppm 1000 ppm 1100 ppm
The EconoMi$er+ controller accepts input from the accessory outdoor air humidity sensor in addition to the outdoor air tem- perature sensor shipped with the EconoMi$er+. By using both sensors, the total enthalpy of the outside air is calculated.
Mount the outdoor-air humidity sensor in to the EconoMi$er+, through the pre-punched holes. See Fig. 28. The outdoor-air humidity sensor is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 11 and 12 on J3 of the EconoMi$er+ con- troller. The pins are labeled ORH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 11 (ORH). The blue wire of the harness is connected to pin 12 (VREF). The wiring harness should be routed from the EconoMi$er+ controller to the sen- sor location. The outdoor enthalpy changeover curve is set at the EconoMi$er+ controller. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
2 3 4 5 6 7 8
Fig. 26 — Indoor Air Quality Voltage Setting
ECONOMI$ER+ CONTROLLER
HOOD
ACTUATOR
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ control- ler uses the standard outdoor air temperature sensor, the outdoor air humidity sensor, and the optional indoor air humidity sensor, an optional return air temperature sensor (RAT). The indoor-air humidity sensor is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 8 and 9 on J3 of the EconoMi$er+ controller. The pins are labeled IRH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 8 (IRH). The blue wire of the har- ness is connected to pin 9 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the sensor location. The EconoMi$er+ controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er+ use.
(HIDDEN)
GROMMET
CURB
INDOOR AIR HUMIDITY SENSOR
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
Fig. 27 — Return Air Temperature Sensor
RANGE CONFIGURATION (ppm)

(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE C F ohms C F ohms C F ohms 120 248.0 390.0 66 150.8 2,011.0 12 53.6 18,090.0 119 246.2 401.2 65 149.0 2,083.0 11 51.8 18,972.0 118 244.4 412.8 64 147.2 2,157.0 10 50.0 19,903.0 117 242.6 424.8 63 145.4 2,235.0 9 48.2 20,883.0 116 240.8 437.2 62 143.6 2,315.0 8 46.4 21,918.0 115 239.0 450.0 61 141.8 2,400.0 7 44.6 23,013.0 114 237.2 462.5 60 140.0 2,488.0 6 42.8 24,117.0 113 235.4 475.5 59 138.2 2,579.0 5 41.0 25,396.0 112 233.6 488.9 58 136.4 2,675.0 4 39.2 26,686.0 111 231.8 502.7 57 134.6 2,774.0 3 37.4 28,052.0 110 230.0 517.0 56 132.8 2,878.0 2 35.6 29,498.0 109 228.2 531.0 55 131.0 2,986.0 1 33.8 31,030.0 108 226.4 545.6 54 129.2 3,099.0 0 32.0 32,654.0 107 224.6 560.5 53 127.4 3,217.0 –1 30.2 34,367.0 106 222.8 576.0 52 125.6 3,340.0 –2 28.4 36,182.0 105 221.0 592.0 51 123.8 3,469.0 –3 26.6 38,109.0 104 219.2 608.5 50 122.0 3,603.0 –4 24.8 40,153.0 103 217.4 625.5 49 120.2 3,743.0 –5 23.0 42,324.0 102 215.6 643.0 48 118.4 3,889.0 –6 21.2 44,617.0 101 213.8 661.2 47 116.6 4,042.0 –7 19.4 47,052.0 100 212.0 680.0 46 114.8 4,203.0 –8 17.6 49,640.0 99 210.2 700.0 45 113.0 4,370.0 –9 15.8 52,392.0 98 208.4 720.6 44 111.2 4,544.0 –10 14.0 55,319.0 97 206.6 742.0 43 109.4 4,727.0 –11 12.2 58,415.0 96 204.8 764.1 42 107.6 4,918.0 –12 10.4 61,711.0 95 203.0 787.0 41 105.8 5,117.0 –13 8.6 65,219.0 94 201.2 810.8 40 104.0 5,327.0 –14 6.8 68,957.0 93 199.4 835.5 39 102.2 5,546.0 –15 5.0 72,940.0 92 197.6 861.0 38 100.4 5,774.0 –16 3.2 77,162.0 91 195.8 888.5 37 98.6 6,014.0 –17 1.4 81,662.0 90 194.0 915.0 36 96.8 6,266.0 –18 –0.4 86,463.0 89 192.2 944.0 35 95.0 6,530.0 –19 –2.2 91,588.0 88 190.4 974.0 34 93.2 6,806.0 –20 –4.0 97,060.0 87 188.6 1005.0 33 91.4 7,096.0 –21 –5.8 102,868.0 86 186.8 1037.0 32 89.6 7,401.0 –22 –7.6 109,075.0 85 185.0 1070.0 31 87.8 7,720.0 –23 –9.4 115,710.0 84 183.2 1104.0 30 86.0 8,056.0 –24 –11.2 122,807.0 83 181.4 1140.0 29 84.2 8,407.0 –25 –13.0 130,402.0 82 179.6 1177.0 28 82.4 8,776.0 –26 –14.8 138,482.0 81 177.8 1215.0 27 80.6 9,164.0 –27 –16.6 147,134.0 80 176.0 1255.0 26 78.8 9,571.0 –28 –18.4 156,404.0 79 174.2 1297.0 25 77.0 10,000.0 –29 –20.2 166,342.0 78 172.4 1340.0 24 75.2 10,449.0 –30 –22.0 177,000.0 77 170.6 1385.0 23 73.4 10,921.0 –31 –23.8 188,340.0 76 168.8 1431.0 22 71.6 11,418.0 –32 –25.6 200,510.0 75 167.0 1480.0 21 69.8 11,942.0 –33 –27.4 213,570.0 74 165.2 1530.0 20 68.0 12,493.0 –34 –29.2 227,610.0 73 163.4 1582.0 19 66.2 13,071.0 –35 –31.0 242,700.0 72 161.6 1637.0 18 64.4 13,681.0 –36 –32.8 258,730.0 71 159.8 1693.0 17 62.6 14,323.0 –37 –34.6 275,970.0 70 158.0 1752.0 16 60.8 15,000.0 –38 –36.4 294,520.0 69 156.2 1813.0 15 59.0 15,714.0 –39 –38.2 314,490.0 68 154.4 1876.0 14 57.2 16,464.0 –40 –40.0 336,000.0 67 152.6 1943.0 13 55.4 17,255.0

Table 6 — Outdoor Air, Return Air, and Supply Air Temperature Sensors (CRTEMPSN001A00 or HH79NZ039)
— Thermistor Resolution
CONTROLLER ECONOMI$ER+
RANGE RESOLUTION Low High F F F –41 –18 4.0 –17 14 2.0 15 28 1.0 29 47 0.8 48 86 0.7 87 108 0.8 109 126 1.0 127 171 2.0 127 195 4.0
OUTDOOR AIR HUMIDITY SENSOR
RELIEF BLADE
OUTDOOR AIR TEMPERATURE SENSOR
Fig. 28 — Outdoor-Air Humidity Sensor



10 20 30 40 50 60 70 80 90
5.6 7.2 8.8 10.4 12.0 13.6 15.2 16.8 18.4
0 10 20 30 40 50 60 70 80 90 100

An occupied/unoccupied switch can be field-installed in place of the jumper to allow the user to force the control into occu- pied or unoccupied mode of operation for EconoMi$er+ damper position. The occupied/unoccupied switch is required if the user wants to use unoccupied free cooling or different EconoMi$er+ damper vent positions in the unoccupied mode.
N. Power Exhaust Refer to the Accessory Power Exhaust installation instructions for information on installing the power exhaust accessory.
O. Remote EconoMi$er+ Enable Control When the control is used with energy management systems that enable and disable the EconoMi$er+, the user can install a field- supplied enable/disable switch. The switch must be wired in series with a 3K ohm, 1 watt or greater resistor. The switch is wired to terminals ORH (pin 11) and VREF (pin 12) on J3. Refer to the Start-Up section for details on how to configure the control.
The occupied minimum position set point remote potentiom- eter (field-supplied) is used when requiring additional tem- porary ventilation. The remote potentiometer (10K ohm - closed damper, 100K ohm - open damper) will only control the occupied minimum position. The accessory 5-in wiring plug, CRE+PLUG001A00 is required to connect the potentiometer. The plug is installed on pins 15, 16 and 17 on J3 of the EconoMi$er+ controller. The pins are labeled with the ground symbol, MIN and VREF on the EconoMi$er+ controller. See Fig. 22. The pink wire from the harness is connected to pin 15 (ground symbol). The gray wire from the harness is con- nected to pin 16 (MIN). The yellow wire from the harness is connected to pin 16 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the remote potentiometer location.
M. Occupied/Unoccupied Switch The EconoMi$er+ supports the use of a field-supplied occupied/ unoccupied switch. When the switch is closed it provides a 24-vac signal to the unit for occupied mode and when open, there is no signal to indicate unoccupied mode. The control can be configured to allow different minimum economizer damper positions and to control how mechanical cooling will and will not be used in the occupied mode.

The unoccupied minimum position can only be set at the con- troller. The occupied minimum position set point configured at the EconoMi$er+ controller should be set to 0 when using a remote potentiometer. The occupied minimum position will also be used as part of the IAQ routing; it will be the maximum position the damper moves to when there is an IAQ call. If the remote potentiometer (occupied) position is greater than the EconoMi$er+ controller unoccupied minimum posi- tion, then the remote potentiometer setting will be used. The remote potentiometer is field supplied and must be a 3-wire, linear potentiometer with a resistance between 10K ohm and 100K ohm (such as the Honeywell S963B1128).
The following equation is used to determine EconoMi$er+ damper position (ECONOMIN_POS):
IAQMIN_SP + = (ECONOMIN_SP – IAQMIN_SP) * (IAQ – OAQ – DAQLO)
R. CO2 Sensor Configuration The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 7.
Demand ventilation control uses an IAQ sensor (CRE+PLUG001A00 required) to control the amount of out- side air admitted into the system. Normally, the minimum position of the EconoMi$er+ damper is established based on the demand occupancy of the space. The IAQ sensor will be used to modulate the EconoMi$er+ minimum damper posi- tion below the normal minimum position based on full occu- pancy. The lower limit is called the base ventilation rate. See Fig. 32. If there is no IAQ signal the damper will be in the unoccu- pied minimum position (configuration item number 3). If there is an IAQ signal the damper will be in the occupied minimum position (configuration item number 15), unless the remote potentiometer is used to override it.
Press Mode to exit and resume normal operation. The cus- tom settings of the CO2 sensor can be changed any time after the sensor is energized. Follow the steps below to change the non-standard settings:
For the demand ventilation control logic, the user configures the lower and upper actuator position to establish the base ventilation rate (IAQMIN_SP) and the design ventilation rate (ECONOMIN_SP) for full occupancy. When the EconoMi$er+ damper is being modulated for demand ventilation control, the damper position will be between IAQMIN_SP and ECONOMIN_SP. The upper IAQ differential set point is DAQHI. The lower IAQ differential set point is DAQLO.
S. Dehumidification of Fresh Air with Demand Control Ventilation (DCV) Information from ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) indicates that the largest humidity load on any zone is the fresh air intro- duced. For some applications, a device such as a energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling pro- cesses are more than adequate to remove the humidity loads for most commercial applications.
The differential set points represent the differential CO2 level (in ppm) above the outdoor reference IAQ levels. Nor- mally, the outdoor reference IAQ levels are around 400 ppm, but the value should be configured based on the reference levels taken at the job site.
This makes the control of the dehumidification device simple when using the enthalpy or differential enthalpy sensor. The enthalpy sensor or differential enthalpy sensor is installed on the equipment to determine economizer operation. The high enthalpy signal from the temperature and humidity sensors or differential temperature and humidity sensors can be used to turn on the outdoor air moisture removal device any time fresh air is required for the space.
ECONOMIZER MINIMUM OCCUPIED DAMPER POSITION (ECONOMIN_SP)
VENTILATION FOR PEOPLE
IAQ MINIMUM ECONOMIZER POSITION SET POINT (IAQMIN_SP)
The energy recovery device should be sized for maximum latent and sensible conditioning at maximum ventilation on a design day. A calculation for leaving-air temperature on a low ambient, low ventilation day should also be done to determine the supply-air temperature of the return and pre-conditioned outside air. The design should produce air temperature somewhat near room conditions to prevent reheat of the air mixture. The energy recovery device should be interlocked with the heat to turn off the device when in the heat mode.
CO LEVEL 2
OUTDOOR REFERENCE LEVEL (OAQ)= 400
100 500 700 1100 INSIDE/OUTSIDE CO2 DIFFERENTIAL INSIDE CO2 CONCENTRATION
AQ DIFFERENTIAL HIGH (DAQHI)
Fig. 32 — Demand Ventilation Control

VENTILATION
OPTIONAL RELAY SETPOINT
RELAY HYSTERESIS
SETTING EQUIPMENT OUTPUT
ANALOG
CO 2 CONTROL
OUTPUT
(ppm) 1 Interface with Standard Building Control System
Proportional Any 4-20 mA 0-2000 1000 50 2 Proportional Any 7-20 mA 0-2000 1000 50 3 Exponential Any 4-20 mA 0-2000 1100 50 4
Proportional 15 4-20 mA 0-1100 1100 50 5 Proportional 20 4-20 mA 0- 900 900 50 6 Exponential 15 4-20 mA 0-1100 1100 50 7 Exponential 20 4-20 mA 0- 900 900 50 8 Health & Safety Proportional — 4-20 mA 0-9999 5000 500 9 Parking/Air Intakes/ Loading Docks Proportional — 4-20 mA 0-2000 700 50
ppm — Parts Per Million
*Available sensor part numbers are listed in Table 4.
deflection with 5 to 10 lb of force) and tighten mount- ing nuts (see Fig. 33). Units 120-151 — Slide motor mounting plate down- ward to tighten belt tension. (1/2-in. deflection with 5 to 10 lb of force.) Secure motor mounting plate nuts. See Fig. 34.
Adjust evaporator-fan speed to meet jobsite requirement. Table 8 shows fan rpm at motor pulley settings and Table 9 shows motor efficiencies. Table 10 shows motor performance. Refer to Fan Performance Tables 11-30 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Tables 1A and 1B.
To change fan speed:
Realign fan and motor pulleys:
1. Shut off unit power supply and install lockout tag. 2. Loosen belt by loosening fan motor mounting plate nuts (see Fig. 33 and 34). 3. Loosen movable pulley flange setscrew (see Fig. 35). 4. Screw movable flange toward fixed flange to increase fan speed and away from fixed flange to decrease fan speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Tables 1A and 1B. 5. Set movable flange at nearest flat of pulley hub and tighten setscrew (see Tables 1A and 1B for speed change for each full turn of pulley flange). To align fan and motor pulleys:
To adjust belt tension (see Fig. 33 and 34):
for Sizes 090-103


UNIT 580F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 090,091† 840 815 790 765 740 715 690 665 635 615 590 — — 090,091** 935 910 885 860 835 810 785 760 735 710 685 — — 090,091†† 1080 1025 1007 988 970 952 933 915 897 878 860 — — 102,103† 935 910 885 860 835 810 785 760 735 710 685 — — 102,103†† 1080 1025 1007 988 970 952 933 915 897 878 860 — — 120,121† 935 910 885 860 835 810 785 760 735 710 685 — — 120,121** 1085 1060 1035 1010 985 960 935 910 885 860 835 — — 120,121†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830 150,151† 1080 1060 1035 1015 990 970 950 925 905 880 860 — — 150,151** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
*Approximate fan rpm shown. †Indicates standard motor and drive package.
**Indicates alternate motor and drive package. ††Indicates high-static motor and drive package.
UNIT 580F MOTOR EFFICIENCY
(%) 090-121 80 150,151 87

UNIT 580F EVAPORATOR-FAN
UNIT VOLTAGE
MAXIMUM ACCEPTABLE
MAXIMUM ACCEPTABLE
MAXIMUM AMP DRAW
MOTOR
CONTINUOUS BHP*
OPERATING WATTS
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 2.40 2120 6.7 460 3.0 575 3.0
208/230 2.90 2615 8.6 460 3.9 575 3.9
208/230 5.25 4400 17.3 460 8.5 575 8.5
208/230 3.70 3313 12.2 460 5.5 575 5.5
208/230 5.25 4400 17.3 460 8.5 575 8.5
LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected.
be affected. See Evaporator-Fan Motor Performance data in Tables 10 for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate.

Table 11 — Fan Performance 580F090,091 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 — 2300 844 1.90 1773 893 2.22 2073 — 2400 854 1.99 1855 903 2.32 2159 — 2500 865 2.08 1940 — 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 12 — Fan Performance 580F090,091 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 — 2300 844 1.90 1773 893 2.22 2073 — 2400 854 1.99 1855 903 2.32 2159 — 2500 865 2.08 1940 — 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 13 — Fan Performance 580F090,091 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 2400 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 2500 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 839 1.86 1735 889 2.18 2032 935 2.52 2345 980 2.87 2673 1022 3.23 3015 2300 844 1.90 1773 893 2.22 2073 940 2.56 2389 984 2.91 2718 1027 3.28 3062 2400 854 1.99 1855 903 2.32 2159 950 2.66 2478 993 3.02 2812 1035 3.39 3159 2500 865 2.08 1940 913 2.41 2249 959 2.76 2573 1003 3.12 2911 1044 3.50 3261 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 — — — 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 — — — 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 — — — 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 — 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 — 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 — 3300 955 3.01 2810 1000 3.39 3159 — 3400 967 3.16 2945 1012 3.54 3299 — 3500 980 3.31 3084 1024 3.69 3445 — 3600 992 3.46 3230 — 3700 1005 3.63 3383 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 14 — Fan Performance 580F102,103 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 — — — 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 — — — 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 3700 744 1.84 1716 804 2.17 2023 — 3750 752 1.91 1778 812 2.24 2089 — 3800 761 1.98 1842 820 2.31 2156 — 3900 777 2.12 1974 — 4000 794 2.27 2113 — 4100 — 4200 — 4250 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 870 2.13 1985 — 2600 875 2.18 2031 — 2700 886 2.28 2126 — 2800 897 2.39 2227 — 2900 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 15 — Fan Performance 580F102,103 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100 3800 761 1.98 1842 820 2.31 2156 874 2.66 2484 925 3.03 2824 973 3.41 3177 3900 777 2.12 1974 835 2.46 2296 889 2.82 2630 939 3.19 2977 986 3.58 3336 4000 794 2.27 2113 851 2.62 2442 904 2.99 2784 953 3.36 3137 — — — 4100 811 2.42 2259 867 2.78 2595 919 3.16 2944 968 3.54 3304 — — — 4200 828 2.59 2412 883 2.95 2755 934 3.34 3110 — 4250 837 2.67 2490 891 3.04 2838 942 3.43 3197 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 — — — 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 — — — 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 — — — 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 — 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 — 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 — 3300 955 3.01 2810 1000 3.39 3159 — 3400 967 3.16 2945 1012 3.54 3299 — 3500 980 3.31 3084 1024 3.69 3445 — 3600 992 3.46 3230 — 3700 1005 3.63 3383 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 16 — Fan Performance 580F120,121 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 — — — 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 — — — 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 — 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 — 4300 989 1.93 1694 1039 2.19 1920 — 4400 1009 2.06 1804 1058 2.32 2034 — 4500 1030 2.19 1919 — 4600 1051 2.32 2039 — 4700 — 4800 — 4900 — 5000 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 — 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 — 3200 1041 1.97 1732 1088 2.22 1947 — 3300 1056 2.07 1817 1102 2.32 2036 — 3400 1071 2.17 1905 — 3500 1087 2.28 1998 — 3600 1102 2.39 2094 — 3700 — 3800 — 3900 — 4000 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 17 — Fan Performance 580120,121 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 — — — 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 — — — 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 — 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 — 4700 1071 2.47 2165 1118 2.75 2409 — 4800 1092 2.62 2295 1138 2.90 2545 — 4900 1113 2.77 2431 — 5000 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 — — — 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 — — — 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 — 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 — 3600 1102 2.39 2094 1146 2.65 2326 — 3700 1118 2.50 2195 1162 2.77 2430 — 3800 1134 2.62 2300 1177 2.89 2539 — 3900 1150 2.75 2410 — 4000 1167 2.88 2524 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 18 — Fan Performance 580F120,121 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 1175 3.01 2640 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 1192 3.15 2768 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 1168 3.01 2646 1210 3.31 2901 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 1186 3.17 2780 1228 3.46 3040 4700 1071 2.47 2165 1118 2.75 2409 1162 3.03 2661 1205 3.33 2919 1245 3.63 3184 4800 1092 2.62 2295 1138 2.90 2545 1181 3.19 2801 1223 3.49 3064 1264 3.80 3333 4900 1113 2.77 2431 1158 3.06 2685 1201 3.36 2947 1242 3.66 3214 1282 3.97 3487 5000 1134 2.93 2572 1178 3.23 2832 1220 3.53 3097 1261 3.84 3369 1300 4.16 3647
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 1215 3.00 2636 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 1228 3.12 2735 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 1201 2.96 2595 1241 3.23 2839 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 1215 3.08 2699 1255 3.36 2946 3600 1102 2.39 2094 1146 2.65 2326 1188 2.92 2563 1229 3.20 2808 1268 3.48 3058 3700 1118 2.50 2195 1162 2.77 2430 1203 3.04 2672 1243 3.33 2920 1282 3.62 3174 3800 1134 2.62 2300 1177 2.89 2539 1218 3.17 2785 1258 3.46 3036 1296 3.75 3295 3900 1150 2.75 2410 1193 3.02 2653 1233 3.31 2902 1273 3.60 3158 1311 3.90 3420 4000 1167 2.88 2524 1208 3.16 2770 1249 3.45 3024 1287 3.74 3284 1325 4.04 3549 4100 1183 3.01 2642 1224 3.30 2893 1264 3.59 3151 1302 3.89 3414 1340 4.20 3683 4200 1200 3.15 2765 1240 3.44 3020 1280 3.74 3282 1318 4.04 3549 1355 4.36 3823 4300 1216 3.30 2893 1257 3.59 3152 1295 3.89 3418 1333 4.20 3690 1370 4.52 3967 4400 1233 3.45 3025 1273 3.75 3289 1311 4.05 3559 1349 4.37 3834 1385 4.69 4116 4500 1250 3.60 3163 1290 3.91 3431 1328 4.22 3705 1364 4.54 3985 — — — 4600 1268 3.77 3306 1306 4.08 3578 1344 4.39 3856 1380 4.72 4140 — — — 4700 1285 3.94 3454 1323 4.25 3730 1360 4.57 4013 1396 4.90 4300 — — — 4800 1303 4.11 3608 1340 4.43 3888 1377 4.76 4175 — 4900 1320 4.29 3766 1357 4.62 4051 1394 4.95 4342 — 5000 1338 4.48 3930 1375 4.81 4219 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 19 — Fan Performance 580F150,151 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 — — — 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 — — — 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 — 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 — 5100 961 3.29 3068 1007 3.59 3345 — 5200 978 3.48 3241 — 5300 995 3.67 3420 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 — — — 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 — — — 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 — 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 — 4200 1066 3.22 3004 1112 3.50 3264 — 4300 1078 3.38 3148 1123 3.66 3413 — 4400 1090 3.54 3297 — 4500 1103 3.70 3451 — 4600 — 4700 — 4800 — 4900 — 5000 — 5100 — 5200 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 20 — Fan Performance 580F150,151 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 1084 3.75 3500 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 1098 3.93 3668 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 1067 3.82 3558 1111 4.12 3841 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 1082 4.00 3733 1125 4.31 4021 5100 961 3.29 3068 1007 3.59 3345 1053 3.89 3627 1096 4.20 3915 1139 4.51 4208 5200 978 3.48 3241 1024 3.78 3523 1068 4.09 3811 1111 4.40 4103 1153 4.72 4400 5300 995 3.67 3420 1040 3.98 3707 1084 4.29 4000 1126 4.61 4298 1168 4.93 4600 5400 1012 3.87 3606 1056 4.18 3899 1099 4.50 4196 1141 4.82 4499 1182 5.15 4806 5500 1029 4.07 3799 1073 4.39 4097 1115 4.72 4400 1156 5.05 4707 — — — 5600 1046 4.29 3999 1089 4.61 4302 1131 4.94 4610 — 5700 1063 4.51 4207 1105 4.84 4515 1146 5.18 4827 — 5800 1080 4.74 4420 1122 5.08 4734 — 5900 1098 4.98 4642 — 6000 1115 5.22 4872 — 6100 — 6200 — 6300 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 1243 4.37 4077 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 1210 4.24 3958 1252 4.54 4238 4400 1090 3.54 3297 1135 3.82 3566 1179 4.12 3841 1221 4.42 4121 1262 4.72 4405 4500 1103 3.70 3451 1147 4.00 3726 1190 4.29 4005 1232 4.60 4289 1273 4.91 4578 4600 1115 3.87 3612 1159 4.17 3891 1201 4.48 4175 1243 4.79 4464 1283 5.10 4757 4700 1128 4.05 3778 1171 4.36 4062 1213 4.67 4350 1254 4.98 4644 — — — 4800 1141 4.24 3951 1183 4.55 4239 1225 4.86 4532 1265 5.18 4830 — — — 4900 1154 4.43 4130 1196 4.74 4422 1237 5.06 4720 — 5000 1167 4.63 4314 1209 4.95 4611 — 5100 1181 4.83 4505 1221 5.16 4808 — 5200 1194 5.04 4703 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 21 — Fan Performance 580F090,091 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 — 2300 842 1.84 1719 895 2.17 2019 — 2400 851 1.92 1793 903 2.25 2097 — 2500 860 2.01 1873 911 2.34 2180 — 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 22 — Fan Performance 580F090,091 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 — 2300 842 1.84 1719 895 2.17 2019 — 2400 851 1.92 1793 903 2.25 2097 — 2500 860 2.01 1873 911 2.34 2180 — 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 23 — Fan Performance 580F090,091 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 2400 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 2500 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 838 1.81 1683 891 2.12 1981 941 2.46 2297 988 2.82 2629 1033 3.19 2976 2300 842 1.84 1719 895 2.17 2019 944 2.51 2336 992 2.86 2669 1037 3.24 3018 2400 851 1.92 1793 903 2.25 2097 952 2.59 2416 999 2.95 2752 1043 3.33 3104 2500 860 2.01 1873 911 2.34 2180 960 2.68 2502 1006 3.05 2842 1051 3.43 3196 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 — — — 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 — — — 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 — — — 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 — 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 — 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 — 3400 954 3.02 2816 1000 3.39 3159 — 3500 966 3.16 2950 1011 3.54 3297 — 3600 978 3.31 3088 1022 3.69 3442 — 3700 990 3.47 3233 — 3750 996 3.55 3308 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 24 — Fan Performance 580F102,103 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — — — 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 — — — 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — — — 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 3700 736 1.78 1660 793 2.09 1944 — 3750 745 1.85 1721 801 2.15 2008 — 3800 753 1.91 1783 808 2.22 2074 — 3900 770 2.05 1912 824 2.37 2209 — 4000 787 2.20 2047 — 4100 804 2.35 2189 — 4200 — 4250 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 865 2.05 1914 916 2.38 2223 — 2600 869 2.10 1957 — 2700 879 2.19 2046 — 2800 889 2.29 2140 — 2900 899 2.40 2239 — 3000 — 3100 — 3200 — 3300 — 3400 — 3500 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 25 — Fan Performance 580F102,103 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962 3800 753 1.91 1783 808 2.22 2074 861 2.55 2380 910 2.90 2701 957 3.26 3036 3900 770 2.05 1912 824 2.37 2209 875 2.70 2522 924 3.05 2848 970 3.42 3189 4000 787 2.20 2047 840 2.52 2351 890 2.86 2669 938 3.22 3002 984 3.59 3348 4100 804 2.35 2189 856 2.68 2499 905 3.03 2824 952 3.39 3162 — — — 4200 821 2.51 2338 872 2.85 2655 920 3.20 2986 967 3.57 3331 — — — 4250 829 2.59 2415 880 2.93 2735 928 3.29 3069 974 3.66 3417 — — —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 — — — 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 — — — 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 — — — 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 — 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 — 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 — 3400 954 3.02 2816 1000 3.39 3159 — 3500 966 3.16 2950 1011 3.54 3297 — 3600 978 3.31 3088 1022 3.69 3442 — 3700 990 3.47 3233 — 3750 996 3.55 3308 — 3800 1002 3.63 3385 — 3900 — 4000 — 4100 — 4200 — 4250 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 26 — Fan Performance 580F120,121 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 — — — 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 — 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 — 4400 750 2.01 1764 806 2.23 1958 — 4500 764 2.14 1879 819 2.37 2077 — 4600 779 2.28 1998 — 4700 — 4800 — 4900 — 5000 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 — — — 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 — — — 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 — — — 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 — 3500 911 2.01 1760 959 2.21 1937 — 3600 920 2.11 1854 967 2.32 2033 — 3700 929 2.22 1951 — 3800 939 2.34 2053 — 3900 — 4000 — 4100 — 4200 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 27 — Fan Performance 580F120,121 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 — — — 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 — — — 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 — 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 — 4800 808 2.56 2251 860 2.81 2462 — 4900 822 2.72 2385 — 5000 837 2.88 2525 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 — — — 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 — — — 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 — 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 — 4000 959 2.59 2269 1004 2.81 2462 — 4100 969 2.72 2384 — 4200 979 2.85 2504 — 4300 — 4400 — 4500 — 4600 — 4700 — 4800 — 4900 — 5000 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 835 to 1085 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 28 — Fan Performance 580F120,121 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 955 2.91 2553 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 966 3.06 2684 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 932 2.97 2611 978 3.21 2820 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 944 3.13 2747 989 3.37 2960 4800 808 2.56 2251 860 2.81 2462 909 3.05 2674 956 3.29 2889 1001 3.54 3106 4900 822 2.72 2385 873 2.96 2601 922 3.21 2818 968 3.46 3037 1013 3.71 3258 5000 837 2.88 2525 887 3.13 2745 935 3.38 2966 981 3.63 3189 1024 3.89 3414
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 1098 2.96 2600 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 1106 3.09 2710 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 1073 2.99 2625 1114 3.22 2824 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 1081 3.12 2741 1122 3.35 2943 4000 959 2.59 2269 1004 2.81 2462 1048 3.03 2660 1090 3.26 2861 1130 3.49 3067 4100 969 2.72 2384 1014 2.94 2581 1057 3.17 2782 1098 3.40 2987 1139 3.64 3195 4200 979 2.85 2504 1024 3.08 2705 1066 3.31 2909 1107 3.55 3117 1147 3.79 3329 4300 990 3.00 2629 1034 3.23 2833 1076 3.46 3040 1117 3.71 3252 1156 3.95 3467 4400 1000 3.14 2758 1044 3.38 2966 1085 3.62 3177 1126 3.87 3392 1165 4.11 3611 4500 1011 3.30 2892 1054 3.54 3104 1095 3.78 3319 1135 4.03 3537 1174 4.28 3759 4600 1022 3.45 3032 1064 3.70 3247 1105 3.95 3466 1145 4.20 3688 1183 4.46 3913 4700 1033 3.62 3176 1075 3.87 3395 1115 4.12 3618 1155 4.38 3843 1193 4.64 4072 4800 1044 3.79 3326 1085 4.04 3549 1126 4.30 3775 1164 4.56 4004 1202 4.83 4237 4900 1055 3.97 3482 1096 4.22 3708 1136 4.49 3938 1174 4.75 4171 1212 5.02 4406 5000 1066 4.15 3642 1107 4.41 3873 1146 4.68 4106 1184 4.95 4342 1221 5.22 4582
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 29 — Fan Performance 580F150,151 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 — — — 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 — — — 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 — 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 — 5300 912 3.13 2917 966 3.47 3233 — 5400 927 3.30 3073 980 3.64 3395 — 5500 943 3.47 3234 — 5600 958 3.65 3402 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 — — — 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 — 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 — 4300 1042 3.16 2951 1089 3.45 3218 — 4400 1053 3.31 3085 1100 3.60 3357 — 4500 1064 3.46 3224 — 4600 1075 3.61 3367 — 4700 — 4800 — 4900 — 5000 — 5100 — 5200 — 5300 — 5400 — 5500 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

Table 30 — Fan Performance 580F150,151 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 1062 3.78 3528 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 1074 3.95 3685 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 1039 3.80 3540 1086 4.13 3849 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 1052 3.97 3702 1099 4.31 4017 5300 912 3.13 2917 966 3.47 3233 1016 3.81 3551 1065 4.15 3870 1111 4.49 4191 5400 927 3.30 3073 980 3.64 3395 1030 3.99 3719 1078 4.34 4044 1123 4.69 4370 5500 943 3.47 3234 994 3.82 3563 1044 4.17 3892 1091 4.53 4223 1136 4.88 4555 5600 958 3.65 3402 1009 4.01 3736 1057 4.37 4071 1104 4.73 4408 1149 5.09 4746 5700 973 3.83 3575 1023 4.20 3915 1071 4.56 4256 1117 4.93 4599 — — — 5800 988 4.03 3754 1038 4.40 4100 1085 4.77 4447 1130 5.14 4796 — — — 5900 1004 4.22 3939 1052 4.60 4292 1099 4.98 4645 — 6000 1019 4.43 4131 1067 4.81 4489 1113 5.20 4848 — 6100 1034 4.64 4329 1082 5.03 4693 — 6200 1050 4.86 4533 — 6300 1065 5.09 4744 —
EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 1221 4.32 4031 4400 1053 3.31 3085 1100 3.60 3357 1145 3.90 3632 1188 4.19 3909 1230 4.49 4187 4500 1064 3.46 3224 1110 3.76 3502 1155 4.06 3782 1198 4.36 4064 1239 4.66 4348 4600 1075 3.61 3367 1121 3.91 3650 1165 4.22 3937 1208 4.53 4224 1249 4.84 4514 4700 1086 3.77 3515 1131 4.08 3805 1175 4.39 4096 1217 4.71 4389 1258 5.02 4684 4800 1097 3.93 3668 1142 4.25 3963 1186 4.57 4260 1228 4.89 4559 1268 5.21 4860 4900 1109 4.10 3826 1153 4.43 4128 1196 4.75 4430 1238 5.08 4734 — — — 5000 1120 4.28 3990 1164 4.61 4296 1207 4.94 4604 — 5100 1132 4.46 4159 1175 4.79 4471 1218 5.13 4784 — 5200 1144 4.65 4333 1187 4.99 4651 — 5300 1155 4.84 4512 1198 5.19 4836 — 5400 1167 5.04 4697 — 5500 1179 5.24 4889 — 5600 — 5700 — 5800 — 5900 — 6000 — 6100 — 6200 — 6300 —
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field- supplied drive.
(Cfm) · (Cfm)

START-UP
I. UNIT PREPARATION Make sure that unit has been installed in accordance with these installation instructions and applicable codes. Make sure that Start-Up Checklist, located on back page of this booklet, has been completed and filled out.
Make sure correct filters are installed in filter tracks (see Tables 1A and 1B). Do not operate unit without return-air filters.
III. OUTDOOR-AIR INLET SCREENS Outdoor-air inlet screens must be in place before operating unit.
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts. On 580F150 and 151 units, remove the tiedown bands that hold the compressors together.
V. INTERNAL WIRING Check all electrical connections in unit control boxes. Tighten as required. Ensure wiring does not come into direct contact with refrigerant tubing.
a. Shut off electrical power and then gas to unit. b. Reclaim refrigerant to relieve all pressure from system using both high- and low-pres- sure ports. c. Cut component connection tubing with tub- ing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.
VI. GAS PIPING Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres- sures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is sub- jected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field- supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by man- ually closing the gas valve.
Proceed as follows to inspect and prepare the unit for initial start-up:
2. Read and follow instructions on all WARNING, CAU- TION, and INFORMATION labels attached to, or shipped with, unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires, etc. b. Inspect for oil at all refrigerant tubing connec- tions and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrig- erant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. c. Inspect all field-wiring and factory-wiring con- nections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges. d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 4. Verify the following conditions: a. Make sure that condenser-fan blade are correctly positioned in fan orifice. See Condenser-Fan Adjustment section on page 62 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed.
To service refrigerant service ports, remove compressor access panel. Each unit system has 3 Schrader-type service gage ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure that caps on the ports are tight. The Schrader-type valve on the discharge line is located under the low-pressure switch. Another valve is located on the discharge line underneath the high- pressure switch. It is screwed on a Schrader fitting but there is no Schrader core.
Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
IX. COMPRESSOR ROTATION On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:

If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels:
Observe manifold pressure in high fire (W1 and W2 ener- gized) and proceed as follows to adjust gas input:
X. COOLING To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor, indoor and outdoor fans start on closure of contactors.
Check unit charge. Refer to Checking and Adjusting Refrigerant Charge section, page 62. Unit must operate a minimum of 10 minutes before adjusting charge. Reset thermostat at a position above room temperature. Compressor and outdoor fans will shut off. Evaporator fan will shut off after 30-second delay.
250,000 BTUH NOMINAL INPUT
ELEVATION
Size† 0-2,000 31 41 30 38 2,000 32 42 30 39 3,000 32 42 31 40 4,000 32 42 32 41 5,000 33 43 33 42 6,000 34 43 34 43 7,000 35 44 35 43 8,000 36 44 36 44 9,000 37 45 37 44 10,000 38 46 38 45 11,000 39 47 39 45 12,000 40 47 40 46 13,000 41 48 41 47 14,000 42 48 42 47
A. To Shut Off Unit Set system selector switch at OFF position. Resetting ther- mostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move thermostat set point above room temperature and ver- ify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off (fan will turn off only if fan selector switch is in the AUTO. posi- tion). Refer to Table 31 for the correct orifice to use at high altitudes. NOTE: Upon a call for heat, the main burners will remain on for a minimum of 60 seconds.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifice available through your local distributor.
1. Purge gas supply line of air by opening union ahead of gas valve. When gas odor is detected, tighten union and wait 5 minutes before proceeding. 2. Turn on electrical supply and open manual gas valve. 3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper- ature lever above room temperature. 4. The induced-draft motor will start, purging heat exchangers. 5. After a call for heating, the main burners should light within 5 seconds. If the burners do not light, then there is a 22-second delay before another 5-second ignition try. If the burners still do not light, the time delay is repeated. If the burners do not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1. 6. The evaporator-fan motor will turn on 45 seconds after the burners are ignited. 7. The evaporator-fan motor will turn off 45 seconds after the thermostat temperature is satisfied. 8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate and in Tables 1A and 1B.
A. Adjust Gas Input The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Manifold pressure should be 3.5 in. wg. in high-fire operation. NOTE: Unit uses a 2-stage gas valve. There is no need to adjust the “Low Fire” manifold pressure. Measure Gas Flow (Natural Gas Units)
Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be 3.5 in. wg. Normal manifold pressure is 3.5 in. wg in high fire (W1 and W2 inputs to gas valve).
Proceed as follows:

XIII. INTEGRATED GAS CONTROLLER (IGC) OPERATION NOTE: The default value for the evaporator-fan motor ON and OFF delay is 45 seconds. The Integrated Gas Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended to 180 seconds. When one flash of the LED (light-emitting diode) is observed, the evaporator-fan ON/OFF delay has been modi- fied. If the limit switch trips at the start of the heating cycle during the evaporator ON delay, the time period of the ON delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 min- utes has elapsed since the last call for heating. The evaporator-fan OFF delay can also be modified. Once the call for heating has ended, there is a 10-minute period dur- ing which the modification can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds on the next cycle. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds. To restore the original default value, reset the power to the unit.
The EconoMi$er+ microprocessor based control system pro- vides the following control functions:
External devices are not required to operate and configure the control.
Set system selector switch at OFF position. Resetting heat- ing selector lever below room temperature will shut unit off temporarily until space temperature falls below thermostat setting.
During the first 3 seconds after power is applied to the con- trol, the four LEDs flash as shown in Table 33, indicating that the control is being initialized. The buttons are not operational during Startup mode.
XIV. SAFETY RELIEF A soft-solder joint at the suction line Schrader port provides pressure relief under abnormal temperature and pressure conditions.
C. Run Mode Run mode indicates status of controller and unit. The mode can be changed to the Read, Setup, or Manual modes by pushing various buttons.
XV. VENTILATION (Continuous Fan) Set fan and system selector switches at ON and OFF posi- tions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.
While the control is in Run mode, the DS1 heartbeat indica- tor LED (red) will flash to indicate the controller is operating properly. The DS2 Econo indicator LED (yellow) will flash whenever economizer is being used for free cooling. The DS3 first stage cooling indicator LED (green) will be on steady indicate demand for stage 1 cooling. The DS4 second stage cooling indicator LED (green) will be on steady to indicate demand for stage 2 cooling.
XVI. ECONOMI$ER+ CONTROLLER The EconoMi$er+ controller is mounted to the top of the EconoMi$er+ damper and is accessible by removing the filter access door of the unit.
If the controller is in a different mode, the controller will return to Run mode after 10 minutes of user inactivity or if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) but- tons are held for at least 3 seconds until all LEDs flash.
The EconoMi$er+ controller is protected by a sheet metal enclosure mounted over the controller. Remove the single screw on the front of the enclosure and lift off the top for access to the controller. The primary purpose of the control- ler is to provide control of the EconoMi$er+ dampers and the cooling compression stages. The status of the indoor fan is monitored through the G input but is not directly controlled by the controller. The heating function is completely inde- pendent of the controller. IMPORTANT: The controller can only be used with conven- tional thermostats with Y1, Y2 and G input to the controller; it can NOT be used with electronic thermostats with a pro- portional room temperature input, or with Variable Air Vol- ume systems.
Read mode is used to check set points (Table 34) and I/O channel status (Table 35). Enter the Read mode by pushing and releasing the READ/ADJUST (#1) button. A user can only enter Read mode from the Run mode (to get to Run mode, press both the #1 and #2 buttons for at least 3 seconds until all LEDs flash). In Read mode, LEDs are not lit until the READ/ADJUST button (#1) is pushed. NOTE: If the user pushes and holds the READ/ADJUST but- ton (#1) for more than 3 seconds, then the control will go into the Setup mode, indicated by the yellow LED (on steady).
There are 4 LEDs on the controller, which are used to read val- ues and display status and configuration information. There are 2 buttons (READ/ADJUST and ADVANCE/MANUAL), which change modes and configure the controller. See Fig. 36.
While in Read mode, push button #1 then the DS1 LED (Red) flashes to indicate setup point number as defined in the setup table. The two green LEDs will then show the value of the display item. The DS3 LED will first display the

tens digit and the DS4 LED will then display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at 1-second intervals to complete the display of the number 54. NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were displayed. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54. To read the display again, push the READ/ADJUST (#1) but- ton and the sequence will repeat as many times as needed. To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycle through all the setup channels (Table 34) and then the I/O channels (Table 35) and then back to the first setup channel.
NOTE: The user can only advance forward, not reset to #1 or go backwards. Cycling the EconoMi$er+ power will reset the item number (but not the item value) to item #1. In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash. Steady-on indicators are reserved for the configuration modes. No data is modified in the Read mode. The controller will always remain at the last read number even if reset back to normal operation.
If no button is pushed in 10 minutes, Read mode will auto- matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While in the Read mode, the controller will continue to operate with normal unit control.

Relays rated at 24 VAC 3A and traces for 8A. NOTE: For 1 and 2 stage cooling, 2 stages of power exhaust will be used. For 3 cooling stages, only 1 stage of power exhaust will be used, and for 4 stages no power exhaust will be controlled directly by the control.
Occupied/unoccupied I/O support dry circuit contact (min 24 mA I)
4-20 mA external powered between signal and ground 4-20 mA loop powered between 24 VDC and signal

INPUT NAME TYPE USE INPUT/OUTPUT
CONVERSION
CONVERSION
RESOLUTION CONNECTION PIN NO.
RANGE
THERMOSTAT INPUTS Y1 (Cool/Low Cool) Y1 Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 1 Y2 (Cool 2/High Cool) Y2 Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 2 G (fan) G Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 3 Occupied/Unoccupied OCC Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 4,5 POWER Power 24V Input Standard 18-30 VAC 50/60 Hz NA NA J2 1,2 ECONOMIZER MOTOR Control CNT 2-10 vdc Standard 2-10 vdc 0-100% 1% J2 3,4,5 ANALOG INPUTS Supply Air Temperature SAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 1,2 Outside Air Temperature OAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 3,4 Return Air Temperature RAT 10 K Thermistor Option 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 5,6
Indoor Humidity IRH 4-20 mA, Loop Powered Option 4-20 mA, 24 vdc 0-100% .08 mA J3 7,8,9
Outdoor Humidity ORH 4-20 mA, Loop Powered Option 4-20 mA, 24 vdc 0-100% .08 mA J3 10,11,12
Indoor CO2 IAQ 4-20 mA, Ext Sourced Option 4-20 mA, 24 vdc 0-200 PPM/10 10 PPM J3 13,14
Remote Minimum Position Pot MIN 10K Option 10K to 100K Ohms 0 to 100% 1% J3 15,16,17
RELAY OUTPUTS Cooling Stage 1 CP1 Relay Standard 24 vac, 2.5 Amps at 24 vac NA On/Off J4 1,3,4 Cooling Stage 2 CP2 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 2,3,4 Power Exhaust 2/ Cooling Stage 3*
EX2 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,6
Power Exhaust 1/ Cooling Stage 4†
EX1 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,7
DISPLAY Setpoint Switch 1 SP1 Digital Standard Open/Closed Logic Open/Closed On Board NA Setpoint Switch 2 SP2 Digital Standard Open/Closed Logic Open/Closed On Board NA LED 1 DS1 LED Output Standard Red Logic On/Off On Board NA LED 2 DS2 LED Output Standard Yellow Logic On/Off On Board NA LED 3 DS3 LED Output Standard Green Logic On/Off On Board NA LED 4 DS4 LED Output Standard Green Logic On/Off On Board NA
*If there are 3 stages then there can only be 1 stage of power exhaust. †If there are 4 stages then there will not be power exhaust stages that will be directly controlled.
TIME LED 1/DS1 (RED) LED 2/DS2 (YELLOW) LED 3/DS3 (GREEN) LED 4/DS4 (GREEN) 0-1.0 SEC OFF 1-1.5 SEC FLASH ½ SEC OFF OFF OFF 1.5-2.0 SEC OFF FLASH ½ SEC OFF OFF 2.0-2.5 SEC OFF OFF FLASH ½ SEC OFF 2.5-3.0 SEC OFF OFF OFF FLASH ½ SEC
LED — Light-Emitting Diode

NO. SETUP POINTS (viewable and adjustable) UNITS MINIMUM
FACTORY
SETTING INC COMMENTS
VALUE
VALUE
1 Supply Air Temperature Setpoint F 40 F 65 F 55 F 1 F Leaving Air Temperature Control Point
2 Occupied Minimum Economizer Position % Item 15 +1% 100% 15% 1% Min Econo Position (occupied mode)
3 Unoccupied Minimum Economizer Position % 1% 100% 5% 1% Min Econo Position (unoccupied mode)
4 Economizer Maximum Position % 1% 100% 100% 1% Maximum Econo Position
5 Economizer Type — 1 3 2 1 1 = Vent Only, 2 = Proportional, 3 = 3 Position 6 Economizer Changeover Type — 1 5 2 1 1 = Switch, 2 = Outdoor Dry Bulb, 3 = Diff Dry Bulb, 4 = Outdoor Enthalpy, 5 = Diff Enthalpy
7 Economizer Changeover Setpoint (mode 2) F 45 F 70 F 65 F 1 F For Outdoor Changeover
8 Economizer Changeover Setpoint (mode 3)
— 1 4 1 1 Outdoor Enthalpy Changeover Setpoint 1 = A, 2 = B, 3 = C, 4 = D 9 No. of compressors — 1 4 2 1 1, 2, 3, or 4
10 Compressor Sequencing — 1 4 1 1 1 = DC-Sensible, 2 = DC-Latent, 3 = LAT-Sensible, 4 = LAT-Latent 11 Power Exhaust Stage 1 Activation % 1% Item 12 -5% 25% 1% Economizer Position 12 Power Exhaust Stage 2 Activation % Item 11 +1% 100% 50% 1% Economizer Position (> stage 1) 13 Unoccupied Configuration — 1 3 3 1 1 = No Unoccupied Cooling, 2 = Unoccupied Free Cooling, 3 = Unoccupied Free & Mech Cooling 14 Compressor Lockout Temperature — 1 F 65 F 45 F 1 F Compressor Operation
15 IAQ Min Economizer Position Setpoint % 1% Item 2 +1% 5% 1% Min IAQ Position for VOC Emissions
16 IAQ Enable — 1 2 1 1 1 = Disabled, 2 = Enabled 17 Outdoor IAQ Reference PPM/10 1 PPM/10 100 PPM/10 40 PPM/10 1 PPM/10 Outdoor Reference IAQ Level
18 IAQ Lower Limit Control Point Differential PPM/10 1 PPM/10 Item 19 -1
PPM/10 60 PPM/10 1 PPM/10 Differential Lower Limit Indoor IAQ Level
19 IAQ Upper Limit Control Point Differential PPM/10 Item 18 +1
PPM/10 200 PPM/10 140 PPM/10 1 PPM/10 Differential Upper Limit Indoor IAQ Level 20 1st Most Recent Error/Reset — 1 8 — — Used in Setup Mode to Reset Alarms 21 2nd Most Recent Error (read only) — 1 8 — — Not Displayed in Setup Mode 22 3rd Most Recent Error (read only) — 1 8 — — Not Displayed in Setup Mode 23 4th Most Recent Error (read only) — 1 8 — — Not Displayed in Setup Mode 24 5th Most Recent Error (read only) — 1 8 — — Not Displayed in Setup Mode
LEGEND NOTE: The accessibility of these channels will be as follows: READ MODE — All channels will be accessible. SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to reset alarms.
DC — Direct Control IAQ — Indoor Air Quality LAT — Leaving Air Temperature Compensated Control VOC — Volatile Organic Compounds
NO. I/O POINTS UNITS MINIMUM VALUE MAXIMUM VALUE INC COMMENTS 1 C1 Output — Off On — Compressor 1 2 C2 Output — Off On — Compressor 2 3 C3 Output — Off On — Compressor 3/Power Exhaust 2 4 C4 Output — Off On — Compressor 4/Power Exhaust 1 5 Economizer Damper Output % 1 F 100 F 1% Damper Commanded Position 6 Supply Air Temperature F 1 F 150 F 1 F Supply Air Temperature 7 Outdoor Air Temperature F 1 F 150 F 1 F Outdoor Air Temperature 8 Return Air Temperature F 1 F 150 F 1 F Return Air Temperature 9 Indoor Relative Humidity % 1% 100% 1% Return Air Relative Humidity 10 Outdoor Relative Humidity % 1% 100% 1% Outdoor Air Relative Humidity 11 Indoor Air Quality PPM 1 PPM/10 200 PPM/10 10 PPM Indoor Air Quality (/10) 12 Remote Minimum Position % 1% 100% 1% Remote Minimum Pot Position 13 Y1 Status — Open Close — Thermostat Y1 Status 14 Y2 Status — Open Close — Thermostat Y2 Status 15 G Status — Open Close — Indoor Fan Status 16 Occ Status — Open Close — Remote Occupied Status
ADJUST MODE — Only channels 1-5 will be accessible. MANUAL MODE — Only channels 1-5 will be accessible.

After advancing through all the configuration variables in the Read mode, the controller will then advance through the status of the I/O channels. As in the Read mode, there will be no LEDs on. Push the READ/ADJUST (#1) button and the yellow LED will flash the “I/O Point” number and the green LEDs will flash the “I/O Values” in the same manner described in the Read mode section. See Table 35. At the first I/O point (Compressor 1 Output), the DS2 LED (Yellow) will flash with the number of the I/O channel and the DS1 LED (red) will stop flashing. This will be followed by the I/O chan- nel status. To read the value again, push the READ/ADJUST (#1) button.
Verify what Setup Point is being read by pushing the READ/ ADJUST button (#1). First the Red LED will flash the set point number, then the Green LEDs will flash the value. Then, the green DS3 and DS4 LEDs will each come on steady for about 2 seconds. While DS3 is on steady, its new value can be entered by pushing READ/ADJUST (#1), and entering the value for the ten’s digit. When the DS4 comes on steady, enter the value for the one's digit. After the green LEDs are off, push the READ/ADJUST button (#1) again to verify that the correct value has been entered. If the configu- ration is a discrete On/off setting, push the READ/ADJUST button (#1) to toggle LED 3 or 4 on or off.
To advance to the next channel, push the ADVANCE/ MANUAL (#2) button. If the number of the channel or the status value is greater than 4 the controller will count out the increments of 5 at a high flash rate followed by the remaining digits. The channel number will be counted out through the DS2 LED (yellow). The status value will be counted out through the DS3 and DS4 LEDs (green). If the status value is an analog value then the numeric value will be displayed by using the DS3 Green LED to display the tens digit and the DS4 will be used to display the ones digit.
Setup Example 1: Change “Occupied Minimum Position” (configuration item 2) to 53%.
If the channel is a digital output (relay), the DS3 LED (flash- ing green) will indicate ON status and the DS4 LED (flash- ing green) will indicate OFF status. If the output is the economizer control signal then the DS3 LED will be used to indicate the motor is being driven open, and the DS4 LED will be used to indicate it is being closed. If the motor is not being commanded in either direction then both the DS3 and DS4 LEDs will be on. The controller will first go through the output relays, then the economizer motor, and will then fol- low with the values currently being read for the analog input channels as defined in the configuration table. All values are maintained in memory even during a power loss. To exit Setup mode, push and hold the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons for more than 3 seconds. Setup mode will automatically be exited after 10 minutes of no activity.
E. Setup Mode The Setup mode is used to change set points and configura- tion values. Enter the Setup mode by pushing and holding the READ/ ADJUST (#1) button 1 for at least 3 seconds until all LEDs flash once. Then, the yellow LED will come on steady. A user can only enter the Setup mode from the Run mode (to get to Run mode, press buttons both buttons #1 and #2 for at least 3 seconds). In Setup mode, all configurations can be modified even while the unit is running, but the user will not be able to adjust the I/O channels. Only channels 1 through 20 on Table 34 will be accessible in the Setup mode. Channel 20 will be used to reset any alarms that may have occurred. As an option, alarms can also be reset by cycling power to the controller. NOTE: During the Setup mode, all routines including safety routines will continue to run and control the unit. While in this mode, the DS1 LED (red) will flash to indicate the number of the configuration item. The DS2 LED (yellow) will be on continuously to indicate that the unit is in configu- ration mode. Use the ADVANCE/MANUAL button to sequence through the setup channels. If the value of the channel is less than 5 it will count out the value of the chan- nel on the DS1 LED at 1-second intervals. If the channel value is 5 or greater, the DS1 LED will first count out the groups of 5 and then following with the remaining digit.

F. Manual Mode Manual mode is used to control the status of I/O channels for use in troubleshooting. See Table 35. Enter the Manual mode by holding down the ADVANCE/ MANUAL (#2) button for at least 3 seconds until all LEDs flash and then the red LED comes on steady.
NOTE: A user can only enter the Manual mode from the Run mode, which is entered by pushing buttons #1 and #2 for at least 3 seconds. All EconoMi$er+ control outputs are turned off. “I/O Inputs” 1-5 can be adjusted even if the unit is in operation. In manual mode, the yellow DS2 LED flashes once to indicate the I/O channel. See Table 35. If the value is less than 5, the yellow DS2 LED will count out the value using 1-second flashes. If the value is greater than 4, the yellow DS2 LED will count out groups of 5 at a high flash rate and then follow with the additional value at a flash rate of once per second. For example a flash of 1 indicates Compressor Relay Output 1.
Push READ/ADJUST button (#1) to read the value. The yel- low LED will flash the I/O Channel number being viewed.
Once the channel number is displayed it will then turn on the appropriate green LED (DS3 or DS4) to indicate the sta- tus of the output. For relay outputs if the DS3 LED is on, then the output is on. If DS4 is on, then the output is off. The green DS3 and DS4 LEDs will remain on for about 2 seconds and if during this time the READ/ADJUST (#1) button is pushed, then the output will toggle to the alternate state. To change again, push the READ/ADJUST button and repeat the test or change the status of the output. As an example, for channel 5 (EconoMi$er+ control damper motor) use the READ/ADJUST button to toggle the motor from open to close in %.
At any time, the ADVANCE/MANUAL (#2) button can be used to advance to the next SET I/O. To exit the mode, push and hold the READ/ADJUST and ADVANCE/MANUAL but- tons (#1 and #2) for more than 3 seconds. NOTE: After exiting the Manual mode, the controller will re- initialize and start with all outputs off.
G. Error Mode The error mode is used to indicate that an error has occurred The error is indicated by LED #1 red and #2 yellow are on steady.
Enter the RUN mode by pushing the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for at least 3 sec- onds until all LEDs flash. Next, push and release button #1 to enter the Read mode. Then push button #2 to advance to item 20 (“first most recent error”). Determine the error by reading the value in items 20 to 24 and referring to the Trou- bleshooting section. Once the error has been fixed, press buttons #1 and 2 for at least 3 seconds to exit Read mode. All LEDs will flash. Enter Setup mode by pressing the READ/ADJUST button (#1) for at least 3 seconds. All LEDs will flash. Push the ADVANCE/MANUAL button (#2) to advance to item 20. Push READ/ADJUST to read item 20. To reset the error code while the green DS4 LED is on, press the READ/ADJUST button (#1) once. In addition to resetting the error mode, this will erase all error codes. Cycling the power will also erase the error code.
16. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink twice. NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in Table 34) are dependent upon other items. Before attempting to change one of these items, be sure to check the value of the item it depends upon (as described in Example 2 above). IMPORTANT: During SETUP MODE, changes are allowed when the DS3 LED and DS4 LED are lit for 2 seconds (as described in Example 1 and 2 above). During this time, if button #1 is pushed to change one position and not the other, the value for that one position will change and the other will default to zero (unless a dependency prevents the zero). How- ever, if button #1 is not pushed at all during the 2 seconds that the green LEDs are lit, the configuration item will not change.

XVII. ECONOMI$ER+ CONFIGURATION For most applications, the factory setting will be used to con- trol the EconoMi$er+. However, there are 19 different vari- ables that can be used to configure the control for wide range of applications. The factory settings and variables are shown in Table 34.
logic includes time guards on the compressors to provide a minimum of 3 minutes on and 3 minutes off time. The con- trol will also prevent two compressors from starting at the same time. The logic uses the EconoMi$er+ to prevent rapid cycling of the compressors and low air temperatures.
IMPORTANT: There is no way to reset/restore the factory default configurations; use caution when making changes to any set point or operational variable. The EconoMi$er+ control accepts an occupied/unoccupied switch input. This input is used to control the occupied and unoccupied minimum ventilation damper position as shown in Table 34 items 2 (ECONOMIN_SP) and 3 (U_ECONOMIN_SP). These values represent the minimum damper position. In addi- tion, the controls allows for different modes of compressor opera- tion in the unoccupied mode. Using item 13 in Table 34 (OCC_MODE), the user can select one of the following unoccu- pied modes:
In order for the EconoMi$er+ to control ventilation air and free cooling, several items must be configured.
EconoMi$er+ Type First, select the EconoMi$er+ control type that will be used. This is the EconoMi$er+ Type function (ECONO_TYPE) defined by item 5 in Table 34. The choices are:
2. Proportional — In this configuration, full propor- tional EconoMi$er+ control will be used. When EconoMi$er+ free cooling cannot be used, the damp- ers will be set to the appropriate occupied and unoc- cupied minimum positions. 3. Three-Position — This mode of EconoMi$er+ is used to provide a minimum ventilation EconoMi$er+ posi- tion and a fixed free cooling or high ventilation posi- tion. The high ventilation position is controlled by the optional Remote EconoMi$er+ Enable Switch Input connected to terminals 11 and 12 on T3. Supply Air Temperature Set Point
Once the type of EconoMi$er+ control has been selected, the user will need to set the Supply Air Temperature set point (SAT_SP). The SAT_SP has a range of 40 to 65 F. NOTE: This will be the set point when both Y1 and Y2 are closed. When just Y1 is closed, the set point will be ° F higher. Minimum Damper Position Set the occupied minimum damper position (ECONOMIN_SP) and unoccupied minimum position (U_ECONOMIN_SP). These should be set to provide the ventilation requirements at full occupancy as defined by the building specifications. When demand ventilation is used, the control will close the dampers below this position based on measured CO2 levels in the space to provide additional operation savings.
A. Compressor Configuration And Control The EconoMi$er+ control can support from 1 to 4 compres- sor stages. For the 3 to 121/2 ton units, there will only be 1 or 2 stages of compressor cooling, so the control is factory configured for 2 stages. There is no difference between 1 and 2 stages. The control also provides the option to configure for high sensible or high latent loads, but for units with only two compressors this option does not apply.
The control will also allow for the use of a remote minimum position potentiometer. This will only adjust the Occupied Minimum position. If used, the software set point ECONOMIN_SP should be set to 0 as the control will use the largest set point. The damper position is not linear with the amount of outside air, so the user will need to set the position of the EconoMi$er+ accordingly. It is best to use the following equa- tion and measured data to set the position:
Compressors are configured using item 10 (STAGE_TYPE) in Table 34. The control also has the capability of controlling directly to Y1 and Y2 inputs. The control can be configured to control to the leaving-air temperature using Y1 and Y2 as a low cool and high cool demand based on the supply air set point and the rate of change of supply-air temperature. For low cool the leaving air temperature set point will be SAT_SP +2° F. For high cool the leaving air temperature set point will be the supply-air temperature set point (SAT_SP). To use this option, configure the compressor sequencing vari- able (STAGE_TYPE) to a value of 3. Configure the supply air temperature set point (SAT_SP) to the desired leaving air temperature. NOTE: The supply air temperature set point is also the tem- perature used for EconoMi$er+ control. The logic will control the operation of the compressors depending on the configuration selected. If free cooling can be used, then the compressors will be integrated with the EconoMi$er+ to provide the lowest cost cooling control. The
OA = SAT – RAT *100 OAT – RAT
OA = % outdoor air
SAT = supply air temperature RAT = return air temperature
OAT = outdoor air temperature The SAT and OAT values can be read from the control and, if the unit is equipped with an RAT sensor, then all three values can be read. For the calculation to work properly, there should be at least a 10° F difference between the OAT and RAT temperatures.

Maximum Damper Position Set the maximum EconoMi$er+ position. Normally this is set at 100%. If using 3-position control or there is a reason not to use 100% outside air, this can be set using the EconoMi$er+ Maximum Position (MAX_POS_SP). Compressor Lockout Temperature
The higher position is referred to as the Occupied EconoMi$er+ Minimum Position (ECONOMIN_SP). The IAQMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO2 generated by sources other than people. The ECONOMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO2 generated by all sources including peo- ple at the design value for maximum occupancy.
Set the Compressor Lockout Temperature. The Compressor Lockout Temperature (CMP_LOCK) is used to prevent com- pressor from running at low ambient conditions when an EconoMi$er+ can easily satisfy the load.
A reference differential CO2 level above the outside CO2 level is used as the starting point for IAQ control and another reference differential level for maximum ventilation at design occupancy is used for the end of IAQ control. Between these points the control will modulate the dampers open from the IAQMIN_SP and the ECONOMIN_SP set- points. The damper position will never go above ECONOMIN_SP or below IAQMIN_SP.
EconoMi$er+ Changeover Control Determine the type of EconoMi$er+ changeover control which will be used to enable and disable free cooling. This is done using the EconoMi$er+ Changeover Type.
The control does not measure the outdoor IAQ reference level as these levels are relatively constant. The installer should take a measurement at start-up of the unit and enter this value into the control using the Outdoor Air IAQ refer- ence level configuration. The control is configured for air quality sensors which pro- vide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has a different range, these bounds must be reconfigured.
2. Outdoor Dry Bulb — For this changeover setting, the EconoMi$er+ will be enabled based on the outdoor-air temperature. The EconoMi$er+ is shipped with an outdoor air temperature sensor. The outdoor air tem- perature set point can be configured by the user. The EconoMi$er+ will be disabled when the outdoor-air temperature rises above the set point. The configura- tion variable is the EconoMi$er+ Changeover set point (OAT_SP). 3. Differential Dry Bulb — For this changeover setting, the EconoMi$er+ will be enabled whenever the out- side-air temperature is lower than the return-air temperature. No configuration of set points is required other than to select the differential dry bulb function.
To configure the control for an IAQ sensor perform the fol- lowing steps:
5. Differential Enthalpy — For this changeover setting, the EconoMi$er+ will be enabled based on the com- parison of the enthalpy of the return air and outside air. If the outside air enthalpy is lower than the return air, then the EconoMi$er+ will be enabled. To use this option, an accessory outside air humidity sensor, a return air dry bulb sensor and a return air humidity sensor must be ordered and installed. No configuration of set points is required other than to select the function.
D. Power Exhaust Configuration The EconoMi$er+ can control up to 2 stages of power exhaust. Power exhaust activation is done through config- urable damper position set points. The first stage of power is controlled by relay C4 on the EconoMi$er+ board. The acti- vation point for the first stage is set using the Power Exhaust Stage 1 Activation set point (PE_SP1). The second stage of power exhaust must be set at a value greater than the first stage. It is configured using the Power Exhaust Stage 2 Activation set point (PE_SP2).
The EconoMi$er+ control has demand ventilation control capability when using an IAQ sensor. The indoor air quality (IAQ) is measured using a CO2 sensor. The IAQ sensor can be field-installed in the return duct or the occupied space.
The EconoMi$er+ control algorithm modulates the position of the EconoMi$er+ damper between two user configurations depending upon the relationship between the IAQ and the Outdoor Air Quality (OAQ). The lower of these two positions is referred to as the Minimum IAQ Minimum EconoMi$er+ Position (IAQMIN_SP).

Compressor stages will be used to cool the air. If the control is configured for direct control by Y1 and Y2, then the stages will sequence based on the demand of Y1 and Y2. If the control is configured for leaving air temperature control, then Y1 will maintain the leaving air temperature at the supply air set point plus 2° F. If Y1 and Y2 are closed, then the leaving air will be controlled to the supply air set point. If Y2 is closed and Y1 is open, then control will shut down and indicate an error due to a thermostat failure or improper wiring of the thermostat.
When thermostat calls for cooling, terminals G and Y1 and the compressor contactor (C) are energized. The indoor (evap- orator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. When the thermostat is satisfied, C is deen- ergized and the compressor and OFM shut off. After a 30-second delay, the (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously.
If the unit is in the unoccupied mode, then the control of the temperature will depend on the unoccupied free cooling con- figuration: no unoccupied cooling, unoccupied free cooling with any mechanical cooling, or unoccupied free and mechanical cooling. If free cooling is enabled, then the con- trol will check if free cooling can be used. The EconoMi$er+ will then control to the leaving air temperature set point plus 2° F for a Y1 command, or the leaving air temperature set point for a Y1 and Y2 command. If mechanical cooling is allowed to be used, then the control will then bring on addi- tional stages of mechanical cooling if free cooling cannot sat- isfy the load.
B. Heating, Units Without EconoMi$er+ When the thermostat calls for heating, terminal W1 is ener- gized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. When additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay.
C. Cooling, Units With EconoMi$er+ For EconoMi$er+ operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position.
When the EconoMi$er+ control is the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er+ damper to the minimum position. On the initial power to the EconoMi$er+ board, it will take the damper up to 21/2 minutes before it begins to position itself. With subsequent fan signal (G) to the board, the change in damper position will take up to 30 seconds to ini- tiate. Damper movement from full closed to full open (or vice versa) will take 21/2 minutes.
then the EconoMi$er+ damper position will be set to the IAQMIN_SP set point. If the CO2 level rises above the DAQLO limit, then the dampers will modulate open in a lin- ear relationship until the return air or space CO2 levels are at or above the DAQHI limit. The damper position will be at the ECONOMIN_SP set point.
When the EconoMi$er+ is being used for free cooling and the position exceeds the power exhaust set point, then the con- trol will turn on the appropriate power exhaust fans. Refer to Fig. 23 for barometric relief capacity, Fig. 24 for outdoor air leakage, and Fig. 25 for pressure drop.
If the damper is in the process of a change (for example going to 100% open) and the signal (G) is turned off, the damper will continue to open to 100% before it closes (due to no fan signal [G]).
Unoccupied and Occupied Minimum Position Control There is an unoccupied minimum damper position and an occupied minimum damper position on the EconoMi$er+ controller. When the HVAC fan is off the outdoor air damper will always be closed. When the fan is on and in the unoccu- pied mode, the outdoor air damper will be at the unoccupied minimum position. When the fan is on (G call) and in the occupied mode, the outdoor air damper will be at the occu- pied minimum position. A jumper wire is factory-installed to force the unit into occu- pied configuration whenever G or Y1 are closed. Without the jumper wire, the unit will always be in unoccupied mode.
If free cooling can be used as determined from the appropri- ate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), then the con- trol will modulate the dampers open to main the supply air temperature set point plus 2° F. If there is a further demand for cooling (cooling second stage — Y2 is energized), then the control set point for the leaving air will be set at the supply air set point to increase the cool- ing capacity. If this cannot satisfy the load then the control will bring on compressor stages as needed to maintain the supply air temperature set point. The EconoMi$er+ damper will be locked open at 100% or the maximum damper posi- tion set point. To ensure that there is oil return, the compressors will oper- ate for at least 3 minutes. If, during this period, the leaving temperature drops below the set point by 5° F, then the EconoMi$er+ dampers will be closed to 60% until the com- pressor is turned off to avoid cold leaving air temperatures.
The 2 minimum position settings are also used in the IAQ sequence of operation. See Indoor Air Quality Sensor on page 21. NOTE: The minimum position signal takes priority over the maximum position signal. If the maximum damper position is set below the minimum damper position, the EconoMi$er+ controller will maintain the actuator at minimum position.
If the conditions are not suitable for free cooling then the EconoMi$er+ dampers will be closed to the minimum venti- lation position.

Adjust the unoccupied minimum position to allow the mini- mum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F (6 C) temperature difference between the outdoor and return air temperatures. To determine the unoccupied minimum position setting, per- form the following procedure: Calculate the appropriate supply-air temperature using the following formula: (TO x OA) + (TR x RA) = TM
as to not overflow the evaporator drain condensate pan.
B. Condenser Coil Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor-air conditions. One-Row Coils
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air TR = Return-Air Temperature
Wash coil with commercial cleaner. Clean outer surfaces with a stiff brush in the normal manner. It is not necessary to remove top panel. 2-Row Coils
RA = Percent of Return Air TM = Supply-Air Temperature
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F:
Clean coil as follows:
(60 x 0.10) + (75 x 0.90) = 73.5 F
Carefully adjust the unoccupied minimum position until the measured supply-air temperature matches the calculated value. Then, carefully adjust the occupied minimum position set point on the controller until the desired position is reached.
4. Remove screws securing coil to center post. 5. Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 39. 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 7. Secure inner and outer coil rows together with a field- supplied fastener. 8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post.
When the thermostat calls for heating, terminal W1 is ener- gized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. When additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. The economizer damper moves to the minimum position. When the thermo- stat is satisfied, the damper moves to the fully closed position.
C. Condensate Drain Check and clean each year at start of cooling season. In win- ter, keep drain dry or protect against freeze-up.
I. CLEANING
Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
Inspect unit interior at the beginning of each heating and cooling season or more frequently as operating conditions require.
A. Evaporator Coil Clean coil as required. Inspect coil at beginning of heating and cooling seasons.



Each compressor is charged with the correct amount of oil at the factory.
Fan-motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser-fan or evaporator-fan motors is required.

IV. BLOWER BELT ADJUSTMENT Inspect blower belt for wear, proper belt tension, and pulley alignment as conditions require or at the beginning of each heating and air conditioning season. Refer to Step 9 — Adjust Evaporator Fan Speed on page 27 for adjustment and alignment procedures.
V. MANUAL OUTDOOR-AIR DAMPER If outdoor-air damper blade is required, see Manual Outdoor-Air Damper section on page 17.
Refer to Optional EconoMi$er+ section on page 18.
Condenser coil grille is shipped factory-installed. No adjust- ments are required.
VIII. HIGH-PRESSURE SWITCH Located on the compressor’s hot gas line is a high-pressure switch. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Tables 1A and 1B.

IX. LOSS-OF-CHARGE SWITCH Located on the condenser’s liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch contains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary. Refer to Tables 1A and 1B.
580F UNIT VOLTAGE FAN HEIGHT “A” (in.) 208/230 V 2.75 460 V and 575 V 3.50
X. FREEZESTAT Located on the “hair pin” end of the evaporator coil is a bimetal temperature sensing switch. This switch protects the evaporator coil from freeze-up due to lack of airflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Tables 1A and 1B.
line temperature at given suction line pressures and outdoor ambient temperatures.
An accurate superheat, thermocouple-type or thermistor- type thermometer, and a gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.
XI. CHECKING AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with R-22 refriger- ant, tested, and factory-sealed. Unit must operate in Cooling mode a minimum of 10 minutes before checking charge.

Proceed as follows:

b. Evaporator inlet-air temperature (F wb). c. Suction-tube temperature (F) at low-side service
fitting. d. Suction (low-side) pressure (psig).
A. To Use Cooling Charging Chart
some of the charge. Recheck the suction pressure as charge is adjusted. Example (Fig. 44, Circuit 2):
This method is to be used in Cooling mode only. Take the out- door ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover
Outdoor Temperature 85 F Suction Pressure 74 psig Suction Temperature should be 56 F (Suction temperature may vary ± 3 F.)
Fig. 42 — Cooling Charging Chart; 580F102

Fig. 43 — Cooling Charging Chart; 580F120






XII. FLUE GAS PASSAGEWAYS To inspect the flue collector box and upper areas of the heat exchanger:
be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. For additional information, refer to the Start-Up, Heating section on page 51. The LED error code can be observed through the viewport. See Fig. 11. During servicing refer to the label on the control box cover or Table 36 for an explanation of LED error code descriptions. If lockout occurs, unit may be adjusted by interrupting power supply to unit for at least 5 seconds.
XIII. COMBUSTION-AIR BLOWER Clean seasonally to assure proper airflow and heating effi- ciency. Inspect blower wheel every fall and periodically dur- ing heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
At the beginning of each heating season, inspect for deterio- ration, blockage due to corrosion or other causes. Observe the main burner flames and replace burners if necessary.
To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:

LED INDICATION ERROR CODE DESCRIPTION ON Normal Operation OFF Hardware Failure 1 Flash† Evaporator Fan On/Off Delay Modified 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced-Draft Motor Fault 7 Flashes Rollout Switch Fault 8 Flashes Internal Control Fault 9 Flashes Software Lockout
Remove blower access panel (Fig. 1A and 1B). Limit switch is located on the fan deck. Verify operation of limit by tempo- rarily blocking return air until limit trips.
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 11). Module contains a self-diagnostic LED. A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is interrupted. When a break in power occurs, the module will
LEGEND LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence. †Indicates a code that is not an error. The unit will continue to operate

when this code is displayed.


A complete list of replacement parts may be obtained from any Bryant distributor upon request.

580F090,091,102,103,120,121 180,000 BTUH INPUT
580F090,091,102,103,120,121,150,151 220,000 BTUH INPUT AND 580F120,121,150,151 250,000 BTUH INPUT

C. Error Code 3 — OAT Sensor Failure Error Criteria
I. ECONOMI$ER+ TROUBLESHOOTING The EconoMi$er+ control has built-in diagnostics. The con- trol can detect and display 10 different diagnostic codes as shown in Table 37. The user can also use the integrated dis- play to check the status of all the inputs and outputs and run the manual control mode to check the operation of the EconoMi$er+ and compressors.
An OAT Sensor Failure error occurs if the sensor is shorted or faulty, then the measured temperature will be below –40 F or above 250 F. Required Action
— If this error occurs disable the economizer and set the economizer to the minimum economizer position.
Reset Method This error should automatically reset after the value has returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
NO. DESCRIPTION CRITERIA 1 SAT Sensor Failure Temperature
Error Criteria If the unit is configured for economizer changeover type 3 or 4, and the input signal is less than 2 mA or greater than 22 mA, then the sensor is faulty and an error will occur.
Required Action If this error occurs, switch the EconoMi$er+ to dry bulb changeover control. Reset Method
IAQ — Indoor Air Quality IRH — Indoor Relative Humidity OAT — Outdoor Air Temperature ORH — Outdoor Relative Humidity RAT — Return Air Temperature SAT — Supply Air Temperature
This error should automatically reset after the value has returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash. †If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.
E. Error Code 5 — IRH (Indoor Relative Humidity) Sensor Failure Error Criteria
Error Criteria An SAT Sensor Failure error will occur if the sensor is shorted or faulty. If the measured temperature reads below –40 F or above 250 F an error will occur.
This error occurs if the unit is configured for EconoMi$er+ changeover type 5 and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Required Action If an error occurs, then the control will default to Mode 2 compressor stage control where Y1 and Y2 have direct con- trol of the compressors. Use of free cooling is disabled and the EconoMi$er+ will be set to the minimum damper posi- tion for either the occupied or unoccupied mode of operation. Replace sensor if faulty. Reset Method
Required Action If this error occurs, switch the EconoMi$er+ to differential dry bulb changeover control. Reset Method
This error should automatically reset after the value has returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
The error will automatically reset after the value has returned to a normal level. The alarm has to be cleared from the display in the Setup mode or a power reset.
Error Criteria This error occurs if the unit is configured for IAQ demand ventilation control and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Error Criteria The RAT Sensor failure error is only applicable the unit has been configured for EconoMi$er+ changeover methods 3 (dif- ferential dry bulb) or 5 (differential humidity). For other modes it should be ignored. If the sensor is shorted or faulty, then the measured temperature will be below –40 F or above 250 F and the error will occur. Required Action
Required Action If this error occurs, disable the IAQ control routine and default to the standard EconoMi$er+ minimum position. Reset Method
This error should automatically reset after the value has returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
If this error occurs, then change the default EconoMi$er+ changeover control to method 2 (dry bulb changeover con- trol) or replace sensor. Reset Method
Error Criteria This error occurs if Y2 is turned on and Y1 is off. This indi- cates that there is a wiring error at the thermostat connec- tions. This alarm should be ignored for the first 20 seconds of operation so that it does not conflict with the special produc- tion test mode.
This error will automatically reset after the value has returned to a normal level. The alarm will have to be cleared from the display in the Setup mode.

Required Action Shut the unit off and check wiring.
Reset Method This error must be manually reset and requires a power reset.
J. RAM Test Failure Error Criteria
H. Error Code 8 — E2 Test Failure Error Criteria
If internal hardware detects a RAM failure, this alarm will be displayed by alternately flashing DS1+DS3 and DS2+DS4.
Required Action Shut the unit off.
This error occurs if internal hardware detects an E2 failure. Required Action
Reset Method This error must be manually reset and requires a power reset.
Shut the unit off. Reset Method
This error must be manually reset and requires a power reset.
I. Error Mode
Error Criteria If internal hardware detects a ROM failure, the alarm is dis- played by alternately flashing DS1+DS2 and DS3+DS4. Required Action
When an error occurs, the red and yellow LEDs both come on steady. To determine the error, follow these steps:
Shut the unit off. Reset Method
This error must be manually reset and requires a power reset.
L. Unit Always In Unoccupied Mode A jumper wire is factory-installed to force the unit into occu- pied configuration whenever G or Y1 are closed. Without the jumper wire, the unit will always be in unoccupied mode. Check the wire. An occupied/unoccupied switch may be installed in place of the jumper. Check the wiring and setting of the switch.
Refer to Tables 38-40 and Fig. 52.
SYMPTOM CAUSE REMEDY Hardware Failure. (LED OFF)
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. Fan ON/OFF Delay Modified (LED/FLASH)
High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower-off delay timing in Heating mode.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Limit Switch Fault. (LED 2 flashes)
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate. Flame Sense Fault. (LED 3 flashes)
The IGC sensed flame that should not be present.
Reset unit. If problem persists, replace control board.
4 Consecutive Limit Switch Faults. (LED 4 flashes)
Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information. Ignition Lockout. (LED 5 flashes)
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas. Induced-Draft Motor Fault. (LED 6 flashes)
Unit unsuccessfully attempted ignition for 15 minutes.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black. Rollout Switch Fault. (LED 7 flashes)
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to lock out unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect. Internal Control Fault. (LED 8 flashes)
Microprocessor has sensed an error in the software or hardware.
If error code is not cleared by resetting unit power, replace the IGC.
Temporary Software Lockout (LED 9 flashes)
Electrical interference is impeding the IGC software
Reset 24-v to control board or turn the thermostat off and on. Fault will automatically reset itself in one hour.
IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshoot- ing analysis.

PROBLEM CAUSE REMEDY Compressor and Condenser Fan Will Not Start.
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control relay.
Replace component.
Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Compressor Will Not Start But Condenser Fan Runs.
Faulty wiring or loose connections in com- pressor circuit.
Check wiring and repair or replace.
Compressor motor burned out, seized, or internal overload open.
Determine cause. Replace compressor.
Defective run/start capacitor, overload, or start relay.
Determine cause and replace.
One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Compressor cCycles (Other than Normally Satisfying Thermostat).
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge to nameplate. Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start relay.
Determine cause and replace.
Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Compressor Makes Excessive Noise (580F103,121,150, and 151 Scroll Only).
Compressor rotating in wrong direction. Reverse the 3-phase power leads as described on page 50.
Compressor Operates Continuously. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction. Excessive Head Pressure. Dirty air filter. Replace filter. Dirty condenser coil. Clean coil. Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling. Determine cause and correct. Head Pressure Too Low. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction. Excessive Suction Pressure. High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Suction Pressure Too Low. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if nec- essary. Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace. Compressor No. 2 Will Not Run. Unit in economizer mode. Proper operation; no remedy necessary.

PROBLEM CAUSE REMEDY Burners Will Not Ignite.
Misaligned spark electrodes. Check flame ignition and sensor electrode positioning. Adjust as needed. No gas at main burners. Check gas line for air purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 min- utes before attempting to relight unit. Check gas valve. Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection require a cool down period before resetting. Miswired or loose connections. Check all wiring and wirenut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary. Inadequate Heating. Dirty air filter. Clean or replace filter as necessary. Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too low, increase manifold pressure, or replace with correct orifices. Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units. Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. Too much outdoor air. Adjust minimum position. Check economizer operation. Poor Flame Characteristics.
Incomplete combustion (lack of Check all screws around flue outlets and burner combustion air) results in: compartment. Tighten as necessary. Aldehyde odors, CO, sooting flame, or floating flame.
Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Burners Will Not Unit is locked into Heating mode for a Wait until mandatory one minute time period has Turn Off. one minute minimum. elapsed or power to unit.

RS — Rollout Switch SAT — Supply Air Temperature Sensor SEN — Sensor TRAN — Transformer
C — Contactor, Compressor CB — Circuit Breaker COMP — Compressor Motor EQUIP — Equipment FPT — Freeze Up Protection Thermostat GND — Ground HPS — High-Pressure Switch HS — Hall-Effect Sensor I — Ignitor IDM — Induced-Draft Motor IFC — Indoor Fan Contactor
IFM — Indoor Fan Motor IFMOVL — Indoor Fan Motor Overload Switch IGC — Integrated Gas Unit Controller LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve OFC — Outdoor Fan Contactor OFM — Outdoor Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal
Accessory or Optional Wiring To indicate common potential only; not to represent wiring.

OR ON ONES OR
Actions Hold/Push Push flash, no steady flash no flash no
Each time the ADV button is pushed, the SET NO flashes the point number and then displays
Actions Push Hold/Push steady flash no flash no flash no
OFF
DS4
on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)
Names ADJUST ADV SET NO SETUP TEN'S
Names ADJUST MAN MAN I/O NO TEN'S
Each time the MAN button is pushed, the I/O NO flashes the I/O point number.
Wait for indicator to turn off and then push read/adjust to check the setting
Then wait for the ONES indicator to turn on and enter the ONES setting
2 RAT Sensor Invalid (only with changeover type 3&5)
4 ORH Sensor invalid (only with changeover type 3&4)
5 IRH Sensor invalid (only with changeover type 5)
and off or open and closed
6 IAQ Sensor Invalid (only if IAQ=1)
3 OAT Sensor Invalid
8 Micro Fails E2 test
NO DESCRIPTION
MANUAL
ALARM CODES
7 Y2 on Y1 off
To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes)
Action flash
Actions flash flash steady steady
Actions Push Push flash, no flash no flash no flash no
Each time the ADV button is pushed, the SET NO flashes the point number until the desired
button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5)
Names HB ECONO Y1 Y2
Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no
NO I/O Points UNITS
1 C1 Output -
2 C2 Output -
3 C3 Output -
4 C4 Output -
5 Economizer Damper Output %
6 Supply Air temperature F
7 Outside Air temperature F
8 Return Air Temperature F
9 Indoor Relative Humidity %
10 Outdoor Relative Humidity %
11 Indoor Air Quality PPM
12 Remote Minimum Position %
13 Y1 Status (next version) -
14 Y2 Status (next version) -
15 G Status (next version) -
16 Occ Status (next version) -
and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)
Names READ ADV SET NO I/O NO TEN'S
I/O point is reached and then the I/O NO flashes the I/O point no.
or a steady TEN's indicator for an on and a steady ONE's for off.
to indicate the setup point is selected for viewing
STARTUP MODE
READ MODE
RUN MODE



Enter the job specific settings in the “Job Setting” column below.


Access panels 18 Altitude compensation 51 Barometric flow capacity 20 Burner ignition 67 Burner rack 67 Burner section 67 Burner spark gap 68 Charging chart, refrigerant 63-66 Clearance 2, 3, 6 CO2 sensor
Manual outdoor air damper 17, 62 Mounting
Compressor 50 Unit 6 Natural gas 9, 11 Operating limits 4 Operating sequence 60, 61 Cooling 60 EconoMi$er+ 60, 61 Heating 60 Outdoor air hood 17, 19 Outdoor air humidity sensor 22, 24 Outdoor air inlet screens
Configuration 26 Settings 27 Combustion blower wheel 67 Compressor
Dimensions 9, 11 Outdoor air temperature sensor 21 Physical data 8-11 Power supply
Lubrication 62 Mounting 50 Rotation 50 Condensate drain
Wiring 12, 16 Pressure switches
Cleaning 61 Location 4, 6 Condenser coil 8, 10 Cleaning 61 Condenser fan 8, 10 Adjustment 62 Control circuit
High pressure 9, 11, 62 Low pressure 9, 11, 62 Pre-Start-Up 50 Refrigerant
Charge 8, 10, 62-66 Type 8, 10 Refrigerant service ports 50 Replacement parts 68 Return air filter 9, 11, 50 Return air temperature sensor 21, 22 Rigging unit 4, 7 Roof curb
Wiring 12 Wiring raceway 16 Demand control ventilation 26 Dimensions 2, 3, 5 Ductwork 4 EconoMi$er+ 18-26, 52-61 Adjustment 62 Components 18 Configuration 58, 59 Controller wiring 20 Damper movement 20 Inputs and outputs 54 Wiring 19 Electrical connections 12 Electrical data 13-15 Enthalpy changeover set points 24 Evaporator coil 8, 10 Cleaning 61 Evaporator fan motor 8, 10 Lubrication 62 Motor data 29 Performance 30-49 Pulley adjustment 27, 28 Pulley setting 8, 10, 28 Speed 28 Factory-installed options
Assembly 1 Dimensions 5 Connector package 5 Leveling tolerances 6 Weight 8, 10 Safety considerations 1 Safety relief 52 Service 61-68 Service ports 50 Slab mount 4 Start-up 50-61 Start-up checklist CL-1 Thermostat 12, 16 Troubleshooting 69-73 Ventilation 52 Weight
Corner 2, 3 EconoMi$er+ 2, 3, 8, 10 Unit 2, 3, 7, 8, 10 Wiring
EconoMi$er+ 18-26 Manual outdoor air damper 17 Filter
EconoMi$er+ 19 Power connections 16 Thermostat 16 Unit 73
Cleaning 61 Installation 19 Size 9, 11 Flue gas passageways 67 Flue hood 12 Freeze protection thermostat 9, 11, 62 Gas connection 9, 11 Gas input 9, 11 Gas piping 12, 50 Gas pressure 1, 9, 11, 50 Heat anticipator settings 9, 11, 13 Heat exchanger 9, 11 High flow valves 50 High pressure switch 9, 11, 62 Horizontal units 1, 4 Indoor air humidity sensor 22 Indoor air quality sensor 21 Integrated gas controller 52, 67 Error codes 67, 70 Leak test 50 Limit switch 67 Liquid propane 9, 11 Low pressure switch 9, 11, 62 Main burners 51, 67

Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
CALL FOR FREE CATALOG 1-800-644-5544 [ ] Packaged Service Training [ ] Classroom Service Training
Copyright 2004 Bryant Heating & Cooling Systems CATALOG NO. 5358-024



I. PRELIMINARY INFORMATION
MODEL NO. _______________________________________
SERIAL NO. ___________________________________________
DATE: _____________________________________________
TECHNICIAN: _________________________________________
UNIT NO.: _________________________________________
JOB LOCTION:_________________________________________
JOB NAME:____________________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE SHIPPING TIE DOWN BANDS ON COMPRESSOR (SIZE 150 AND 151 ONLY) PER
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK THAT RETURN-AIR FILTERS ARE CLEAN AND IN PLACE
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
ENSURE BELT TENSION IS CORRECT AND BLOWER PULLEYS ARE PROPERLY ALIGNED.
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1
COMPRESSOR AMPS L1 L2 L3
COMPRESSOR AMPS L1 L2 L3
INDOOR-FAN AMPS L1 L2 L3
TEMPERATURES AND PRESSURES
OUTDOOR-AIR TEMPERATURE DB
RETURN-AIR TEMPERATURE DB WB
COOLING SUPPLY AIR DB WB
GAS HEAT SUPPLY AIR DB
GAS INLET PRESSURE IN. WG
GAS MANIFOLD PRESSURE IN. WG (HI FIRE) IN. WG (LO FIRE)
REFRIGERANT SUCTION PRESSURE PSIG — CIRCUIT NO. 1 PSIG — CIRCUIT NO. 2
REFRIGERANT TEMP. (SUCTION) PRESSURE CIRCUIT NO. 1 CIRCUIT NO. 2
REFRIGERANT DISCHARGE PSIG — CIRCUIT NO. 1 PSIG — CIRCUIT NO. 2
DISCHARGE TEMPERATURE °F/C — CIRCUIT NO. 1 °F/C — CIRCUIT NO. 2
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION
Copyright 2004 Bryant Heating & Cooling Systems CL-1 CATALOG NO. 5358-024
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Hardware Failure. (LED OFF) | Loss of power to control module (IGC). | Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. | p.70 |
| Fan ON/OFF Delay Modified (LED/FLASH) | High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower-off delay timing in Heating mode. | Ensure unit is fired on rate and temperature rise is correct. Ensure unit’s external static pressure is within application guidelines. | p.70 |
| Limit Switch Fault. (LED 2 flashes) | High temperature limit switch is open. | Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate. | p.70 |
| Flame Sense Fault. (LED 3 flashes) | The IGC sensed flame that should not be present. | Reset unit. If problem persists, replace control board. | p.70 |
| 4 Consecutive Limit Switch Faults. (LED 4 flashes) | Inadequate airflow to unit. | Check operation of indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information. | p.70 |
| Ignition Lockout. (LED 5 flashes) | Unit unsuccessfully attempted ignition for 15 minutes. | Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas. | p.70 |
| Induced-Draft Motor Fault. (LED 6 flashes) | IGC does not sense that induced-draft motor is operating. | Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black. | p.70 |
| Rollout Switch Fault. (LED 7 flashes) | Rollout switch has opened. | Rollout switch will automatically reset, but IGC will continue to lock out unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect. | p.70 |
| Internal Control Fault. (LED 8 flashes) | Microprocessor has sensed an error in the software or hardware. | If error code is not cleared by resetting unit power, replace the IGC. | p.70 |
| Temporary Software Lockout (LED 9 flashes) | Electrical interference is impeding the IGC software | Reset 24-v to control board or turn the thermostat off and on. Fault will automatically reset itself in one hour. | p.70 |
| Compressor and Condenser Fan Will Not Start. | Power failure. | Call power company. | p.71 |
| Compressor and Condenser Fan Will Not Start. | Fuse blown or circuit breaker tripped. | Replace fuse or reset circuit breaker. | p.71 |
| Compressor and Condenser Fan Will Not Start. | Defective thermostat, contactor, transformer, or control relay. | Replace component. | p.71 |
| Compressor and Condenser Fan Will Not Start. | Insufficient line voltage. | Determine cause and correct. | p.71 |
| Compressor and Condenser Fan Will Not Start. | Incorrect or faulty wiring. | Check wiring diagram and rewire correctly. | p.71 |
| Compressor and Condenser Fan Will Not Start. | Thermostat setting too high. | Lower thermostat setting below room temperature. | p.71 |
| Compressor Will Not Start But Condenser Fan Runs. | Faulty wiring or loose connections in com- pressor circuit. | Check wiring and repair or replace. | p.71 |
| Compressor Will Not Start But Condenser Fan Runs. | Compressor motor burned out, seized, or internal overload open. | Determine cause. Replace compressor. | p.71 |
| Compressor Will Not Start But Condenser Fan Runs. | Defective run/start capacitor, overload, or start relay. | Determine cause and replace. | p.71 |
| Compressor Will Not Start But Condenser Fan Runs. | One leg of 3-phase power dead. | Replace fuse or reset circuit breaker. Determine cause. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Refrigerant overcharge or undercharge. | Recover refrigerant, evacuate system, and recharge to nameplate. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Defective compressor. | Replace and determine cause. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Insufficient line voltage. | Determine cause and correct. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Blocked condenser. | Determine cause and correct. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Defective run/start capacitor, overload, or start relay. | Determine cause and replace. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Defective thermostat. | Replace thermostat. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Faulty condenser-fan motor or capacitor. | Replace. | p.71 |
| Compressor cCycles (Other than Normally Satisfying Thermostat). | Restriction in refrigerant system. | Locate restriction and remove. | p.71 |
| Compressor Makes Excessive Noise (580F103,121,150, and 151 Scroll Only). | Compressor rotating in wrong direction. | Reverse the 3-phase power leads as described on page 50. | p.71 |
| Compressor Operates Continuously. | Dirty air filter. | Replace filter. | p.71 |
| Compressor Operates Continuously. | Unit undersized for load. | Decrease load or increase unit size. | p.71 |
| Compressor Operates Continuously. | Thermostat set too low. | Reset thermostat. | p.71 |
| Compressor Operates Continuously. | Low refrigerant charge. | Locate leak, repair, and recharge. | p.71 |
| Compressor Operates Continuously. | Leaking valves in compressor. | Replace compressor. | p.71 |
| Compressor Operates Continuously. | Air in system. | Recover refrigerant, evacuate system, and recharge. | p.71 |
| Compressor Operates Continuously. | Condenser coil dirty or restricted. | Clean coil or remove restriction. | p.71 |
| Excessive Head Pressure. | Dirty air filter. | Replace filter. | p.71 |
| Excessive Head Pressure. | Dirty condenser coil. | Clean coil. | p.71 |
| Excessive Head Pressure. | Refrigerant overcharged. | Remove excess refrigerant. | p.71 |
| Excessive Head Pressure. | Air in system. | Recover refrigerant, evacuate system, and recharge. | p.71 |
| Excessive Head Pressure. | Condenser air restricted or air short-cycling. | Determine cause and correct. | p.71 |
| Head Pressure Too Low. | Low refrigerant charge. | Check for leaks, repair, and recharge. | p.71 |
| Head Pressure Too Low. | Compressor valves leaking. | Replace compressor. | p.71 |
| Head Pressure Too Low. | Restriction in liquid tube. | Remove restriction. | p.71 |
| Excessive Suction Pressure. | High heat load. | Check for source and eliminate. | p.71 |
| Excessive Suction Pressure. | Compressor valves leaking. | Replace compressor. | p.71 |
| Excessive Suction Pressure. | Refrigerant overcharged. | Recover excess refrigerant. | p.71 |
| Suction Pressure Too Low. | Dirty air filter. | Replace filter. | p.71 |
| Suction Pressure Too Low. | Low refrigerant charge. | Check for leaks, repair, and recharge. | p.71 |
| Suction Pressure Too Low. | Metering device or low side restricted. | Remove source of restriction. | p.71 |
| Suction Pressure Too Low. | Insufficient evaporator airflow. | Increase air quantity. Check filter and replace if nec- essary. | p.71 |
| Suction Pressure Too Low. | Temperature too low in conditioned area. | Reset thermostat. | p.71 |
| Suction Pressure Too Low. | Field-installed filter drier restricted. | Replace. | p.71 |
| Compressor No. 2 Will Not Run. | Unit in economizer mode. | Proper operation; no remedy necessary. | p.71 |
| Burners Will Not Ignite. | Misaligned spark electrodes. | Check flame ignition and sensor electrode positioning. Adjust as needed. | p.72 |
| Burners Will Not Ignite. | No gas at main burners. | Check gas line for air purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 min- utes before attempting to relight unit. | p.72 |
| Burners Will Not Ignite. | Check gas valve. | p.72 | |
| Burners Will Not Ignite. | Water in gas line. | Drain water and install drip leg to trap water. | p.72 |
| Burners Will Not Ignite. | No power to furnace. | Check power supply, fuses, wiring, and circuit breaker. | p.72 |
| Burners Will Not Ignite. | No 24 v power supply to control circuit. | Check transformer. Transformers with internal overcurrent protection require a cool down period before resetting. | p.72 |
| Burners Will Not Ignite. | Miswired or loose connections. | Check all wiring and wirenut connections. | p.72 |
| Burners Will Not Ignite. | Burned-out heat anticipator in thermostat. | Replace thermostat. | p.72 |
| Burners Will Not Ignite. | Broken thermostat wires. | Run continuity check. Replace wires, if necessary. | p.72 |
| Inadequate Heating. | Dirty air filter. | Clean or replace filter as necessary. | p.72 |
| Inadequate Heating. | Gas input to unit too low. | Check gas pressure at manifold. Clock gas meter for input. If too low, increase manifold pressure, or replace with correct orifices. | p.72 |
| Inadequate Heating. | Unit undersized for application. | Replace with proper unit or add additional unit. | p.72 |
| Inadequate Heating. | Restricted airflow. | Clean filter, replace filter, or remove any restrictions. | p.72 |
| Inadequate Heating. | Blower speed too low. | Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units. | p.72 |
| Inadequate Heating. | Limit switch cycles main burners. | Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. | p.72 |
| Inadequate Heating. | Too much outdoor air. | Adjust minimum position. | p.72 |
| Inadequate Heating. | Check economizer operation. | p.72 | |
| Poor Flame Characteristics. | Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO, sooting flame, or floating flame. | Check all screws around flue outlets and burner compartment. Tighten as necessary. | p.72 |
| Poor Flame Characteristics. | Cracked heat exchanger. | p.72 | |
| Poor Flame Characteristics. | Overfired unit — reduce input, change orifices, or adjust gas line or manifold pressure. | p.72 | |
| Poor Flame Characteristics. | Check vent for restriction. Clean as necessary. | p.72 | |
| Poor Flame Characteristics. | Check orifice to burner alignment. | p.72 | |
| Burners Will Not Turn Off. | Unit is locked into Heating mode for a one minute minimum. | Wait until mandatory one minute time period has elapsed or power to unit. | p.72 |