EN
Bryant logo
Official user manual

Bryant 575A

16 pages·604 KB·Heat Pump·PDF·ENDEFRITNLJA
Bryant 575A
Table of Contents 65 sections CONTENTS · WARNING: · UNIT W/ ALUMINUM-FIN · UNIT W/ COPPER-FIN · … ShowHide
CONTENTSp.1WARNING:p.1UNIT W/ ALUMINUM-FINp.2UNIT W/ COPPER-FINp.2WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL)p.2UNIT 575Ap.2COILp.2ELECTRICAL CONNECTIONSp.2SERVICE VALVE CONNECTIONSp.2MAX WEIGHTp.3UNITp.3II. RIG AND MOUNT THE UNITp.3CAUTION:p.3LIQUID LINEp.4(F) 75 65 7 2p.4IV. MAKE ELECTRICAL CONNECTIONSp.6VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECTp.7UNIT 575A NOMINAL VOLTAGEp.7HEATERp.7AMPS MCA* MOCP*p.7HEATER RATINGp.7VOLTAGEp.7CORNER POSTp.8RACEWAY THERMOSTAT FIELD CONNECTIONp.8POWER WIRING CONNECTIONSp.8START-UPp.8I. PRELIMINARY CHECKSp.8LENGTH INSULATIONp.8RATING (C)p.8II. EVACUATE AND DEHYDRATEp.8III. REFRIGERANT AND OIL CHARGEp.8LEGENDp.8IV. REFRIGERANT SERVICE PORTSp.9V. SEQUENCE OF OPERATIONp.9VI. CHECKING COOLING AND HEATING CONTROL OPERATIONp.10SERVICEp.11I. CLEANINGp.11II. LUBRICATIONp.12TROUBLESHOOTING CHART, HEATING CYCLEp.13TROUBLESHOOTING CHART, COOLING CYCLEp.14START-UP CHECKLISTp.15I. PRELIMINARY INFORMATIONp.15ADDITIONAL ACCESSORIESp.15OUTDOOR UNITp.15IS THERE ANY SHIPPING DAMAGE? (Y/N)p.15IF SO, WHERE:p.15WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)p.15HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)p.15(Y/N)p.15CONTROLSp.15ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRINGp.15CONNECTIONS MADE AND CHECKED? (Y/N)p.15INDOOR UNITp.15ARE PROPER AIR FILTERS IN PLACE? (Y/N)p.15DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)p.15HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)p.15PIPINGp.15CHECK VOLTAGE IMBALANCEp.15LINE-TO-LINE VOLTS: AB V AC V BC Vp.15MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = Vp.15C. Start-Upp.16COOLING HEATINGp.16COMPRESSOR AMPS (L1/L2/L3) / /p.16NOTES:p.16CUT ALONG DOTTED LINEp.16
Page 1 of the Bryant 575A user manual — Table of Contents
Page 1 · Contents
Contents

Contents

CONTENTSp.1WARNING:p.1UNIT W/ ALUMINUM-FINp.2UNIT W/ COPPER-FINp.2WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL)p.2UNIT 575Ap.2COILp.2ELECTRICAL CONNECTIONSp.2SERVICE VALVE CONNECTIONSp.2MAX WEIGHTp.3UNITp.3II. RIG AND MOUNT THE UNITp.3CAUTION:p.3LIQUID LINEp.4(F) 75 65 7 2p.4IV. MAKE ELECTRICAL CONNECTIONSp.6VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECTp.7UNIT 575A NOMINAL VOLTAGEp.7HEATERp.7AMPS MCA* MOCP*p.7HEATER RATINGp.7VOLTAGEp.7CORNER POSTp.8RACEWAY THERMOSTAT FIELD CONNECTIONp.8POWER WIRING CONNECTIONSp.8START-UPp.8I. PRELIMINARY CHECKSp.8LENGTH INSULATIONp.8RATING (C)p.8II. EVACUATE AND DEHYDRATEp.8III. REFRIGERANT AND OIL CHARGEp.8LEGENDp.8IV. REFRIGERANT SERVICE PORTSp.9V. SEQUENCE OF OPERATIONp.9VI. CHECKING COOLING AND HEATING CONTROL OPERATIONp.10SERVICEp.11I. CLEANINGp.11II. LUBRICATIONp.12TROUBLESHOOTING CHART, HEATING CYCLEp.13TROUBLESHOOTING CHART, COOLING CYCLEp.14START-UP CHECKLISTp.15I. PRELIMINARY INFORMATIONp.15ADDITIONAL ACCESSORIESp.15OUTDOOR UNITp.15IS THERE ANY SHIPPING DAMAGE? (Y/N)p.15IF SO, WHERE:p.15WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)p.15HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)p.15(Y/N)p.15CONTROLSp.15ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRINGp.15CONNECTIONS MADE AND CHECKED? (Y/N)p.15INDOOR UNITp.15ARE PROPER AIR FILTERS IN PLACE? (Y/N)p.15DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)p.15HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)p.15PIPINGp.15CHECK VOLTAGE IMBALANCEp.15LINE-TO-LINE VOLTS: AB V AC V BC Vp.15MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = Vp.15C. Start-Upp.16COOLING HEATINGp.16COMPRESSOR AMPS (L1/L2/L3) / /p.16NOTES:p.16CUT ALONG DOTTED LINEp.16
Page 2 of the Bryant 575A user manual — SERVICE VALVE CONNECTIONS
Page 2 · click to enlarge
Page 2
Bryant 575A — UNIT W/ ALUMINUM-FIN diagram (page 2)
Fig. 1

UNIT W/ ALUMINUM-FIN

UNIT W/ COPPER-FIN

WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL)

UNIT 575A

Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z

COIL

COIL

Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg

090 18-89 [508.0]

18-59 [431.8]

18-91⁄29 [546.0]

18-43⁄49 [425] 540 245 132 60 100 45 133 60 175 80 608 276 160 73 117 53 142 64 189 86

ELECTRICAL CONNECTIONS

2. Center of Gravity. See chart for dimensions.

CONNECTION SIZES AA 13⁄89 Dia. [35] Field Power Supply Hole BB 29 Dia. [51] Power Supply Knockout CC 21⁄29 Dia. [64] Power Supply Knockout DD 7⁄89 Dia. [22] Field Control Wiring Hole

3. Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces, 0 in. (0 mm) b. Outdoor coil, for proper airflow, 36 in. (914 mm) one side, 12 in.

(305 mm) the other. The side getting the greater clearance is optional. c. Overhead, 60 in. (1524 mm) to assure proper outdoor-fan operation. d. Between units, control box side, 42 in. (1067 mm) per National

Electrical Code (NEC). e. Between unit and ungrounded surfaces, control box side, 36 in.

SERVICE VALVE CONNECTIONS

UNIT SUCTION LIQUID 575A090 11⁄89 [28.6] 1⁄29 [12.7]

(914 mm) per NEC. f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. (1067 mm) per NEC. 5. With the exception of the clearance for the outdoor coil as stated in note 4b, a removable fence or barricade requires no clearance. 6. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material. 7. Vertical center of gravity is approximately 40% of total unit height.

Fig. 2 — Dimensions

Page 3 of the Bryant 575A user manual — CAUTION:
Page 3 · click to enlarge
Page 3

Table 1 — Physical Data

B. Mounting The unit must be elevated to ensure drainage from basepan during sub-freezing conditions and to prevent or limit block- age of outdoor coil during snowfall. Consideration should be given to specific geographical areas when determining height of unit elevation. C. Compressor Mounting As shipped, compressors are held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pressure. See Fig. 4.

UNIT 575A 090 OPERATING WEIGHT (lb)

Aluminum Coils (Standard) 540 Copper Coils (Optional) 608 RIGGING WEIGHT (lb)

Aluminum Coils (Standard) 590 Copper Coils (Optional) 658 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity...Type 1...06DA818 Quantity Cylinders 4 Speed (rpm) 1750 Oil Charge (oz) (ea) 88 OUTDOOR FAN Propeller; Direct Drive Quantity...rpm 1...1100 Diameter (in.) 26 Motor Hp (NEMA) 3⁄4 Nominal Airflow (cfm) 6500 OUTDOOR COIL Enhanced Copper Tubes,

Bryant 575A — MAX WEIGHT diagram (page 3)
Fig. 2

Aluminum Lanced Fins Face Area (sq ft) 18.0 Storage Capacity (lb)† 16.56 Fins/in. 17.0 Rows (No.) 2 CONNECTIONS (Sweat)

Suction (in.) 11⁄8 Liquid (in.) 1⁄2 CONTROLS

High Cutout 426 6 7 Cut-in 320 6 20 Low Cutout 7 6 3 Cut-in 22 6 5 Defrost Thermostat

Initiate Defrost (F) 28 Terminates Defrost (F) 65

LEGEND NEMA — National Electrical Manufacturing Association

MAX WEIGHT

A B C w/Al

Coil Lb Kg Lb Kg in. mm in. mm in. mm 575A090 590 268 658 298 45.0 1143 38.5 989 43.5 1105

UNIT

*Unit is factory supplied with holding charge only. †Storage capacity of coil with coil 80% full of liquid R-22 at 120 F.

Al — Aluminum-Fin Cu — Copper-Fin

II. RIG AND MOUNT THE UNIT

Fig. 3 — Rigging Label

Be sure unit panels are securely in place prior to rigging.

CAUTION:

A. Rigging

Bryant 575A — CAUTION: diagram (page 3)
Fig. 3

The unit is designed for overhead rigging. Refer to rigging label for preferred rigging method. Spreader bars are not re- quired if top crating is left on unit. All panels must be in place when rigging. (See Fig. 3.) As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal plane is not less than 45 degrees. Raise and set unit down carefully. If it is necessary to roll unit into position, mount unit on rails, using a minimum of 3 rollers. Apply force to rails, not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to unit.

Raise from above to lift unit from rails or pad when unit is in final position. After unit is in position, remove all shipping wrapping and top crating.

Fig. 4 — Compressor Mounting

Pressurestat Settings (psig) · w/Cu · Coil

Page 4 of the Bryant 575A user manual — (F) 75 65 7 2
Page 4 · click to enlarge
Page 4

III. COMPLETE REFRIGERANT PIPING CONNECTIONS Suction connection is sweat with plastic cap; liquid connec- tion is sweat with plastic cap. Refer to Table 2 for the proper line sizes. Follow standard piping practices.

NOTE: Unit is shipped with R-22 holding charge. System pres- sure must be relieved before removing caps. Recover refrig- erant prior to brazing. Pass nitrogen or other inert gas through piping while braz- ing to prevent formation of copper oxide. C. Liquid Line Solenoid Valve A field-supplied liquid line solenoid valve (LLSV) is recom- mended when piping system length exceeds 75 feet. The LLSV must be of the biflow type, suited for use in heat pump systems. NOTE: Part number EF23JS214 (Sporlan model CB14S2, 5⁄8-in. ODF/7⁄8-in. ODM) is recommended and is available from the Replacement Components Division. This solenoid re- quires field-supplied Sporlan MKC-2 coils. Wire the solenoid in parallel with the compressor contactor coil. Install the LLSV near the outdoor unit. The flow arrow must be pointed toward the outdoor unit. D. Safety Relief A fusible plug is located on top of the accumulator. See Fig. 6. Note that all safety relief components are factory installed. Do not cap fusible plug. If local code requires additional safety device(s), install as directed.

Table 2 — Refrigerant Piping Sizes

LINEAR LENGTH OF PIPING — ft

0-25 25-50 50-75 75-100 Line Size (in. OD) L S L S L S L S 090 1⁄2 11⁄8 5⁄8 11⁄8 5⁄8 13⁄8 3⁄4 13⁄8

UNIT 575A

LEGEND L — Liquid Line OD — Outside Diameter S — Suction Line NOTES: 1. Pipe sizes are based on a 2° F loss for liquid and suction lines. 2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings. 3. Charge units with R-22 in accordance with unit installation instructions. A. Size Refrigerant Lines Consider length of piping required between 575A unit and 524A-H unit, amount of liquid lift, and compressor oil re- turn. See Table 3. Refer to 524A installation instructions for additional information.

E. Suction Piping at Indoor Coil and TXV Sensing Bulb Location

Table 3 — Liquid Line Data

UNIT 575A MAX ALLOWABLE LIQUID LIFT (ft)

Suction piping must be designed so that refrigerant is thor- oughly mixed after it leaves the indoor coil suction header. The thermostatic expansion valve (TXV) sensing bulb must also be correctly located. This ensures that the TXV sensing bulb receives reliable readings. Install the suction piping as follows:

LIQUID LINE

Max Allowable Pressure Drop

(F) 75 65 7 2

1. Install a minimum of two 90-degree elbows upstream of the TXV bulb location.

LEGEND db — Dry Bulb wb — Wet Bulb NOTES: 1. The liquid lift in cooling mode is based on 80/67 F (db/wb ) entering indoor-air temperature and a 95 F outdoor-air temperature, with R-22 refrigerant, at an indoor airflow of 3000 cfm. 2. The liquid lift in heating mode is based on 70/60 F (db/wb) entering indoor-air temperature and a 47/43 F (db/wb) outdoor-air tempera- ture, with R-22 refrigerant, at an indoor airflow of 3000 cfm. B. Filter Drier and Moisture Indicator

2. Locate the TXV bulb on a vertical riser where possible. If a horizontal location is necessary, secure the bulb at approximately the 4 o’clock position or the 8 o’clock position. See Fig. 7.
3. Make sure that the piping system has no inherent oil traps, and that the piping layout does not allow oil to migrate into an idle indoor coil.
4. Complete refrigerant piping from indoor coil to outdoor coil before opening liquid and suction lines at the 575A unit. See Tables 1 and 2 for piping selection data.

See Fig. 5. The filter drier is factory supplied and field- installed in the liquid line. Moisture indicator is field- supplied and should be installed just after liquid line shutoff valve. Do not use a receiver; there is none provided with unit and one should not be used.

Show 4 more labels / short text on this page
Max Allowable · 090 Heating Cooling · Temp Loss · (psi)
Page 5 of the Bryant 575A user manual — LIQUID LINE
Page 5 · click to enlarge
Page 5
Bryant 575A — LIQUID LINE diagram (page 5)
Fig. 4

LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion Valve

NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a spe- cific installation. 4. Liquid line solenoid valve (solenoid drop control) is recom- mended to prevent refrigerant migration to the compressor. A bi- flow type solenoid valve is required. 5. Filter drier must be of the biflow type, suitable for heat pump duty. 6. Internal factory-supplied TXV and bypass check valve not shown.

*Accessory item. †Field supplied.

Fig. 5 — Typical Piping Diagram, 575A/524A-H

Page 6 of the Bryant 575A user manual — WARNING:
Page 6 · click to enlarge
Page 6
Bryant 575A — IV. MAKE ELECTRICAL CONNECTIONS diagram (page 6)
Fig. 5

A. Field Power Supply All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v orange wire on the transformer and connecting it to the 208-v red wire from the transformer. The end of the orange wire must then be insulated. Refer to unit label diagram for additional information. Short wire leads (pigtails) are provided for field wire connections. Use factory-supplied splices or UL approved copper/aluminum connector. When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local requirements. Install field wiring as follows:

1. Install conduit through side panel openings. 2. Install power lines to connections as shown in Fig. 8. Wrap connections with electrical tape. Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 4). Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 4, Note 2, to determine the percentage of voltage im- balance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to elec- trical components. Such operation invalidates any applicable unit warranty.

Fig. 6 — Fusible Plug Locations

Bryant 575A — IV. MAKE ELECTRICAL CONNECTIONS diagram (page 6)
Fig. 6

B. Accessory Electric Heat

If the system is to be equipped with an accessory electric heater, refer to the 524A-H090 installation instructions and Table 5.

Bryant 575A — IV. MAKE ELECTRICAL CONNECTIONS diagram (page 6)
Fig. 7

LEGEND TXV — Thermostatic Expansion Valve NOTE: The 8 o’clock position is shown above.

Fig. 7 — TXV Sensing Bulb Location

IV. MAKE ELECTRICAL CONNECTIONS

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit ap- proved for electrical ground when installed in accor- dance with National Electrical Code (NEC) ANSI (American National Standards Institute)/NFPA 70 (National Fire Protection Association) and local electri- cal codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

WARNING:

LEGEND C — Contactor NEC — National Electrical Code

Splice Connection (Factory Supplied)

Fig. 8 — 575A090 Power Wiring Connections

Field Wiring · Factory Wiring

Page 7 of the Bryant 575A user manual — VOLTAGE
Page 7 · click to enlarge
Page 7

Table 4 — Electrical Data

VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECT

UNIT 575A NOMINAL VOLTAGE

Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA

090 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.7 80 1.4 21.0 25 25 89

LEGEND FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455 Average Voltage = 3

= 457 (AB) 457 2 452 = 5 v (BC) 464 2 457 = 7 v (AC) 457 2 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance

NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

7 % Voltage Imbalance = 100 457 = 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

max voltage deviation from average voltage = 100 x

Table 5 — Accessory Electric Heater Data

UNIT 524A-H NOMINAL kW V-PH-HZ HEATER PART NO.

HEATER

AMPS MCA* MOCP*

5 240-3-60 CAELHEAT001A00 12.0 25.6 30 480-3-60 CAELHEAT002A00 6.0 12.3 15

10 240-3-60 CAELHEAT004A00 24.1 40.7 50 480-3-60 CAELHEAT005A00 12.0 19.8 25

15 240-3-60 CAELHEAT007A00 36.0 55.7 80 480-3-60 CAELHEAT008A00 18.0 27.4 40

25 240-3-60 CAELHEAT010A00 60.1 85.8 125 480-3-60 CAELHEAT011A00 30.1 42.4 60

35 240-3-60 CAELHEAT013A00 84.0 115.8 175 480-3-60 CAELHEAT014A00 42.1 57.4 80

LEGEND MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps) *Sizes shown are for single-point connection of electric heat accessory and air handler.

HEATER RATING

ACTUAL SITE VOLTAGE 200 208 230 240 400 440 460 480 240.694 .751 .918 1 — 480 — .694 .840 .918 1

VOLTAGE

(V-Ph-Hz) · 1371 = 3 · average voltage

Page 8 of the Bryant 575A user manual — LEGEND
Page 8 · click to enlarge
Page 8

C. Field Control Wiring Install an approved accessory thermostat assembly accord- ing to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the condi- tioned space to sense average temperature in accordance with thermostat installation instructions. Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 9) as described in following Steps 1 through 3:

CORNER POST

RACEWAY THERMOSTAT FIELD CONNECTION

POWER WIRING CONNECTIONS

Bryant 575A — CORNER POST diagram (page 8)
Fig. 8

Fig. 10 — Field Control Wiring Raceway

1. Pass the control wires through the hole provided in the corner post. (See Fig. 10.) 2. Feed wire through the raceway built into the corner post to the 24-v barriers located on the left side of the con- trol box. The raceway provides the required clearance between the high- and low-voltage wiring. 3. Connect thermostat wires to screw terminals of low- voltage connection board. NOTE: 39 VA is available for field-installed accessories. Con- trol power requirement for heat pump outdoor unit is 36 VA (sealed). The factory-supplied control transformer is rated at 75 VA.

START-UP

I. PRELIMINARY CHECKS

1. Check that all internal wiring connections are tight and that all barriers, covers, and panels are in place. 2. Field electrical power source must agree with unit nameplate rating. 3. Ensure all service valves are open. Ensure all compressor service valves are backseated. 4. Verify that compressor holddown bolts have been loosened and that flat/snubber washers can be rotated by finger pressure (snug, but not tight).
5. Verify compressor crankcase heater is securely in place. Crankcase heater must operate for at least 24 hours before start-up.

SIZE Ft M AWG sq mm 0-50 0-15.2 35 18 0.82 50-75 15.2-22.9 35 16 1.30 Over 75 Over 22.9 35 14 2.08

LENGTH INSULATION

RATING (C)

6. Note that compressor oil level is visible in the sight glass.
7. Check for leaks in refrigerant system by using soap bubbles and/or electronic leak detector.

LEGEND AWG — American Wire Gage

8. Check voltage imbalance as shown in Table 4, Note 2.
9. Check that both outdoor and indoor units are properly mounted in accordance with installation instructions and applicable codes.

All wire larger than no. 18 AWG (American Wire Gage) can- not be directly connected to the thermostat and will require a junction box and splice at the thermostat.

II. EVACUATE AND DEHYDRATE

Bryant 575A — II. EVACUATE AND DEHYDRATE diagram (page 8)
Fig. 9

Evacuate and dehydrate entire refrigerant system using meth- ods described in GTAC II, Module 4, System Dehydration.

III. REFRIGERANT AND OIL CHARGE

Refer to GTAC II, Module 5, Charging Recovery, Recycling, and Reclamation.

Unit panels must be in place when unit is operating during charging procedure.

Unit is shipped with holding charge only. Weigh in 15 lb of R-22 to start unit. A. Refrigerant Charging Use Cooling Charging Chart (see Fig. 11). Vary refrigerant until the conditions of the chart are met. Note that charging chart is different from the type normally used. Chart is based on charging the units to the correct subcooling for the vari- ous operating conditions. Accurate pressure gage and tem- perature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line, close to the liquid line service valve, and insulate it so that outdoor am- bient temperature does not affect the reading. Indoor airflow must be within the normal operating range of the unit. Operate unit a minimum of 15 minutes. Ensure pressure and temperature readings have stabilized. Plot liquid pressure and temperature on chart and add or reduce charge to meet curve. Adjust charge to conform with charging chart, using liquid pressure and temperature to read chart.

LEGEND

C — Cooling H — Heating HR — Heater Relay IFC — Indoor Fan Contactor

LLSV — Liquid Line Solenoid

Valve SUPL — Supplemental TB — Terminal Block

Fig. 9 — Control Wiring Connections

Page 9 of the Bryant 575A user manual — V. SEQUENCE OF OPERATION
Page 9 · click to enlarge
Page 9
Bryant 575A — IV. REFRIGERANT SERVICE PORTS diagram (page 9)
Fig. 10

When the thermostat is satisfied, contacts open, deenergiz- ing C. The COMP, IFM, and OFM stop. As shown in Fig. 12, cooling mode refrigerant flow is as follows:

1. Hot refrigerant gas from compressor flows through the reversing valve and is directed to the outdoor coil vapor header. 2. Once at the outdoor coil vapor header, hot refrigerant gas flows up to check valve ‘‘A,’’ which is closed. All re- frigerant is then directed to complete a path through the lower 6 coil circuits (6 passes in each circuit). 3. Refrigerant flows through from the liquid header side outlets into the transfer header, where it flows upward. 4. Refrigerant leaves the transfer header through side con- nections in 4 locations and enters the middle coil cir- cuits (4 coil circuits above check valve ‘‘A’’). 5. Refrigerant leaves the 4 middle coil circuits and enters the top portion of vapor header. The refrigerant moves up to the top 2 remaining coil circuits, where it enters the subcooler section. 6. Subcooled refrigerant leaves the coil circuits through the side outlets. It passes through check valve ‘‘B’’ into the system liquid line and then into the indoor coil.

Fig. 11 — Cooling Charging Chart — 575A090

7. Liquid refrigerant is expanded and evaporated to a lowpressure vapor in the indoor coil. Refrigerant vapor then returns to the outdoor unit through the system vapor line, where it is drawn through the reversing valve and accumulator and back to the compressor suction connection.

B. Oil Charging

Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if necessary to bring oil into view in sight glass. See Table 1 for oil charge. Use only ap- proved compressor oil as follows:

Suniso 3GS and WF32-150

B. Heating

Do not reuse drained oil or use any oil that has been exposed to atmosphere. Procedures for adding or removing oil are given in Refrigerant Service Techniques manual.

On a call for heat, thermostat makes circuits R-Y and R-G. When compressor time delay (5 ± 2 minutes) is completed, a circuit is made to C, starting COMP and OFM. Circuit R-G also energizes IFC and starts IFM after a 1-second delay.

If oil is added, run unit for additional 10 minutes. Stop unit and check oil level. If level is still low, add oil only after de- termining that piping system is designed for proper oil re- turn and that system is not leaking oil.

If room temperature continues to fall, circuit R-W is made through second-stage thermostat bulb. If optional electric heat package is used, a relay is energized, bringing on supplemen- tal electric heat. When thermostat is satisfied, contacts open, deenergizing contactor and relay; motors and heaters deenergize.

IV. REFRIGERANT SERVICE PORTS

Each unit system has 3 service ports; one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure caps on the ports are tight.

As shown in Fig. 13, heating mode refrigerant flow is as follows:

V. SEQUENCE OF OPERATION

1. Hot gas from compressor flows through the reversing valve and is directed to the system vapor line and indoor coil vapor header (not shown). Refrigerant is condensed and subcooled in the indoor coil and returns to the outdoor unit through the system liquid line.

When power is supplied to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.

A. Cooling With the thermostat in the cooling position, and when the space temperature comes within 2° F of the cooling set point, the thermostat makes circuit R-O. This energizes the revers- ing valve solenoid (RVS) and places the unit in standby con- dition for cooling.

2. Check valve ‘‘B’’ is closed and all liquid refrigerant enters the liquid header.
3. Refrigerant leaves the liquid header through 12 locations. It is then expanded in fixed orifice metering devices contained within the outlet tubes.

As the space temperature continues to rise, the second stage of the thermostat makes, closing circuit R-Y. When compres- sor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C ), starting the compressor (COMP) and outdoor- fan motor (OFM). Circuit R-G is made at the same time, en- ergizing the indoor-fan contactor (IFC) and starting the indoor- fan motor (IFM) after one-second delay.

4. Refrigerant evaporates to low pressure vapor as it completes its passage through the 12 parallel coil circuits (6 passes each).
5. Refrigerant moves from the coil circuits into the vapor header, where it is drawn through the reversing valve and accumulator and back to compressor suction connection.
Page 10 of the Bryant 575A user manual — VI. CHECKING COOLING AND HEATING CONTROL OPERATION
Page 10 · click to enlarge
Page 10
Bryant 575A — VI. CHECKING COOLING AND HEATING CONTROL OPERATION diagram (page 10)
Fig. 11

Fig. 12 — Cooling Mode Operation

C. Defrost

Observe that heating cycle shuts down when control set- ting is satisfied.

Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost thermo- stat (DFT) is closed (below 28 F).

4. When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to call for cooling (below room temperature), and unit operates in Heating mode when temperature control is set to call for heating (above room temperature).

Defrost mode is identical to Cooling mode, except outdoor- fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F.

VII. MALFUNCTION The high-pressure switch, loss-of-charge switch, and compres- sor overtemperature safety are located in a Cycle-LOC™cir- cuit that prevents heat pump operation if these safety devices are activated. The lockout system can be reset by adjusting the thermostat to open the contacts (down for heating mode, up for cooling mode) deenergizing the Cycle-LOC circuitry. Compressor over- current protection is achieved with overload breakers which are temperature-sensitive and will automatically reset.

VI. CHECKING COOLING AND HEATING CONTROL OPERATION

Start and check the unit for proper control operation as follows:

1. Place room thermostat SYSTEM switch in an OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set control below room temperature. Observe that compressor, outdoor fan, and indoor fan motors start. Observe that cooling cycle shuts down when control setting is satisfied. 3. Place system switch in HEAT position. Set control above room temperature. Observe that compressor, outdoor fan, indoor-fan motor, and electric heaters (if equipped) start.

Unit is equipped with a no-dump reversing valve circuit. When unit is in cooling mode, reversing valve remains in cooling position until a call for heating is requested by thermostat. When unit is in heating mode, reversing valve remains in heat- ing position until there is a call for cooling.

Page 11 of the Bryant 575A user manual — I. CLEANING
Page 11 · click to enlarge
Page 11
Bryant 575A — SERVICE diagram (page 11)
Fig. 12

Fig. 13 — Heating Mode Operation

SERVICE

Bryant 575A — SERVICE diagram (page 11)
Fig. 13

CAUTION:

When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.

I. CLEANING

Inspect unit interior at the beginning of each cooling season and as operating conditions require.

A. Outdoor Coil

Inspect coil monthly. Clean outdoor coil annually and as re- quired by location or outdoor-air conditions. Clean coil as follows:

1. Turn off unit power. 2. Remove and save top panel screws on outdoor unit.
3. Remove outdoor coil corner post. See Fig. 14. To hold top panel open, place coil corner post between top panel and side panel. See Fig. 15.

Fig. 14 — Cleaning Outdoor Coil

Bryant 575A — I. CLEANING diagram (page 11)
Fig. 14
4. Remove bracket holding coil sections together at return end of outdoor coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 16.
5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 6. Reposition the outer coil section and secure the sections together. Remove the coil corner post from between the top panel and side panel. Install the coil corner post and replace all screws removed in Step 2.

Fig. 15 — Propping Up Top Panel —11—

Page 12 of the Bryant 575A user manual — II. LUBRICATION
Page 12 · click to enlarge
Page 12
Bryant 575A — II. LUBRICATION diagram (page 12)
Fig. 15

IV. COMPRESSOR REMOVAL See Table 1 for compressor information. Follow safety codes and wear safety glasses and work gloves.

1. Shut off power to unit. Remove unit access panel (front of unit). 2. Remove refrigerant from system using refrigerant removal methods described in Refrigerant Service Techniques manual. 3. Disconnect compressor wiring at compressor terminal box. Disconnect high-pressure switch. 4. Remove bolts from discharge service valve and suction flange.

Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to service.

CAUTION:

5. Remove crankcase heater from compressor base. 6. Remove compressor holddown bolts and lift compressor off basepan. 7. Remove compressor from unit. 8. Clean system. Add new liquid line filter drier (biflow type). 9. Install new compressor and position in unit. Connect suction and discharge lines to compressor. Connect highpressure switch. Ensure that compressor holddown bolts are in place. Connect wiring. Install crankcase heater. 10. Evacuate and recharge unit. 11. Restore unit power.

Fig. 16 — Separating Coil Sections

II. LUBRICATION

A. Compressors

Compressor has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Start-Up, Oil Charging section.

B. Fan Motor Bearings

Fan motor bearings are permanently lubricated. No further lubrication is required.

Bryant 575A — II. LUBRICATION diagram (page 12)
Fig. 16

III. OUTDOOR FAN ADJUSTMENT (Fig. 17)

1. Shut off unit power supply.
2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 17.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.

Fig. 17 — Outdoor-Fan Adjustment

Page 13 of the Bryant 575A user manual — LEGEND
Page 13 · click to enlarge
Page 13
Bryant 575A — TROUBLESHOOTING CHART, HEATING CYCLE diagram (page 13)
Fig. 17

N.C. — Normally Closed

LEGEND

TROUBLESHOOTING CHART, HEATING CYCLE

Page 14 of the Bryant 575A user manual — LEGEND
Page 14 · click to enlarge
Page 14
Bryant 575A — TROUBLESHOOTING CHART, COOLING CYCLE diagram (page 14)
Fig. 18

TXV — Thermostatic Expansion Valve

LEGEND

TROUBLESHOOTING CHART, COOLING CYCLE

Copyright 1995 Carrier Corporation CATALOG NO. BDP-3357-502

Page 15 of the Bryant 575A user manual — MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V
Page 15 · click to enlarge
Page 15

START-UP CHECKLIST

I. PRELIMINARY INFORMATION

OUTDOOR: MODEL NO.

SERIAL NO.

INDOOR: MODEL NO.

SERIAL NO.

ADDITIONAL ACCESSORIES

B. Pre-Start-Up

OUTDOOR UNIT

IS THERE ANY SHIPPING DAMAGE? (Y/N)

IF SO, WHERE:

WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)

HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)

HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?

(Y/N)

CONTROLS

ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING

CONNECTIONS MADE AND CHECKED? (Y/N)

ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)

HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)

INDOOR UNIT

HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)

ARE PROPER AIR FILTERS IN PLACE? (Y/N)

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)

DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)

HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)

PIPING

IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED? (Y/N)

HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR COIL, INDOOR COIL, TXV

(Thermostatic Expansion Valve), SOLENOID VALVES, FILTER DRIER, REVERSING VALVE, CHECK VALVE, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)

LOCATE, REPAIR, AND REPORT ANY LEAKS.

HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)

HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? (Y/N)

IS THE OIL LEVEL IN COMPRESSOR CRANKCASE INTO VIEW IN THE COMPRESSOR SIGHT GLASS?

(Y/N)

CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS: AB V AC V BC V

(AB + AC + BC)/3 = AVERAGE VOLTAGE = V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = %

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

Page 16 of the Bryant 575A user manual — COMPRESSOR AMPS (L1/L2/L3) / /
Page 16 · click to enlarge
Page 16

-

C. Start-Up

CHECK INDOOR-FAN SPEED AND RECORD.

CHECK OUTDOOR-FAN SPEED AND RECORD.

AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COOLING HEATING

OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR-AIR TEMP LEAVING OUTDOOR-AIR TEMP INDOOR ENTERING-AIR DB (dry bulb) TEMP INDOOR ENTERING-AIR WB (wet bulb) TEMP INDOOR LEAVING-AIR DB TEMP INDOOR LEAVING-AIR WB TEMP

COMPRESSOR AMPS (L1/L2/L3) / /

NOTES:

CUT ALONG DOTTED LINE

Copyright 1995 Carrier Corporation CATALOG NO. BDP-3357-502 CL-2

Ask about the Bryant 575A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 575A

Be the first to ask — other owners or our team will answer.

Original document

Bryant 575A manual PDF

16 pages·604 KB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…