


UNIT W/ COPPER-FIN
WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL)
UNIT 575A
Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z
COIL
Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
090 18-89 [508.0]
18-59 [431.8]
18-91⁄29 [546.0]
18-43⁄49 [425] 540 245 132 60 100 45 133 60 175 80 608 276 160 73 117 53 142 64 189 86
CONNECTION SIZES AA 13⁄89 Dia. [35] Field Power Supply Hole BB 29 Dia. [51] Power Supply Knockout CC 21⁄29 Dia. [64] Power Supply Knockout DD 7⁄89 Dia. [22] Field Control Wiring Hole
(305 mm) the other. The side getting the greater clearance is optional. c. Overhead, 60 in. (1524 mm) to assure proper outdoor-fan operation. d. Between units, control box side, 42 in. (1067 mm) per National
Electrical Code (NEC). e. Between unit and ungrounded surfaces, control box side, 36 in.
UNIT SUCTION LIQUID 575A090 11⁄89 [28.6] 1⁄29 [12.7]
(914 mm) per NEC. f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. (1067 mm) per NEC. 5. With the exception of the clearance for the outdoor coil as stated in note 4b, a removable fence or barricade requires no clearance. 6. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material. 7. Vertical center of gravity is approximately 40% of total unit height.
Fig. 2 — Dimensions

Table 1 — Physical Data
B. Mounting The unit must be elevated to ensure drainage from basepan during sub-freezing conditions and to prevent or limit block- age of outdoor coil during snowfall. Consideration should be given to specific geographical areas when determining height of unit elevation. C. Compressor Mounting As shipped, compressors are held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pressure. See Fig. 4.
UNIT 575A 090 OPERATING WEIGHT (lb)
Aluminum Coils (Standard) 540 Copper Coils (Optional) 608 RIGGING WEIGHT (lb)
Aluminum Coils (Standard) 590 Copper Coils (Optional) 658 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity...Type 1...06DA818 Quantity Cylinders 4 Speed (rpm) 1750 Oil Charge (oz) (ea) 88 OUTDOOR FAN Propeller; Direct Drive Quantity...rpm 1...1100 Diameter (in.) 26 Motor Hp (NEMA) 3⁄4 Nominal Airflow (cfm) 6500 OUTDOOR COIL Enhanced Copper Tubes,

Aluminum Lanced Fins Face Area (sq ft) 18.0 Storage Capacity (lb)† 16.56 Fins/in. 17.0 Rows (No.) 2 CONNECTIONS (Sweat)
Suction (in.) 11⁄8 Liquid (in.) 1⁄2 CONTROLS
High Cutout 426 6 7 Cut-in 320 6 20 Low Cutout 7 6 3 Cut-in 22 6 5 Defrost Thermostat
Initiate Defrost (F) 28 Terminates Defrost (F) 65
LEGEND NEMA — National Electrical Manufacturing Association
A B C w/Al
Coil Lb Kg Lb Kg in. mm in. mm in. mm 575A090 590 268 658 298 45.0 1143 38.5 989 43.5 1105
*Unit is factory supplied with holding charge only. †Storage capacity of coil with coil 80% full of liquid R-22 at 120 F.
Al — Aluminum-Fin Cu — Copper-Fin
Fig. 3 — Rigging Label
Be sure unit panels are securely in place prior to rigging.
A. Rigging

The unit is designed for overhead rigging. Refer to rigging label for preferred rigging method. Spreader bars are not re- quired if top crating is left on unit. All panels must be in place when rigging. (See Fig. 3.) As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal plane is not less than 45 degrees. Raise and set unit down carefully. If it is necessary to roll unit into position, mount unit on rails, using a minimum of 3 rollers. Apply force to rails, not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to unit.
Raise from above to lift unit from rails or pad when unit is in final position. After unit is in position, remove all shipping wrapping and top crating.
Fig. 4 — Compressor Mounting
Pressurestat Settings (psig) · w/Cu · Coil

III. COMPLETE REFRIGERANT PIPING CONNECTIONS Suction connection is sweat with plastic cap; liquid connec- tion is sweat with plastic cap. Refer to Table 2 for the proper line sizes. Follow standard piping practices.
NOTE: Unit is shipped with R-22 holding charge. System pres- sure must be relieved before removing caps. Recover refrig- erant prior to brazing. Pass nitrogen or other inert gas through piping while braz- ing to prevent formation of copper oxide. C. Liquid Line Solenoid Valve A field-supplied liquid line solenoid valve (LLSV) is recom- mended when piping system length exceeds 75 feet. The LLSV must be of the biflow type, suited for use in heat pump systems. NOTE: Part number EF23JS214 (Sporlan model CB14S2, 5⁄8-in. ODF/7⁄8-in. ODM) is recommended and is available from the Replacement Components Division. This solenoid re- quires field-supplied Sporlan MKC-2 coils. Wire the solenoid in parallel with the compressor contactor coil. Install the LLSV near the outdoor unit. The flow arrow must be pointed toward the outdoor unit. D. Safety Relief A fusible plug is located on top of the accumulator. See Fig. 6. Note that all safety relief components are factory installed. Do not cap fusible plug. If local code requires additional safety device(s), install as directed.
Table 2 — Refrigerant Piping Sizes
LINEAR LENGTH OF PIPING — ft
0-25 25-50 50-75 75-100 Line Size (in. OD) L S L S L S L S 090 1⁄2 11⁄8 5⁄8 11⁄8 5⁄8 13⁄8 3⁄4 13⁄8
LEGEND L — Liquid Line OD — Outside Diameter S — Suction Line NOTES: 1. Pipe sizes are based on a 2° F loss for liquid and suction lines. 2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings. 3. Charge units with R-22 in accordance with unit installation instructions. A. Size Refrigerant Lines Consider length of piping required between 575A unit and 524A-H unit, amount of liquid lift, and compressor oil re- turn. See Table 3. Refer to 524A installation instructions for additional information.
E. Suction Piping at Indoor Coil and TXV Sensing Bulb Location
Table 3 — Liquid Line Data
UNIT 575A MAX ALLOWABLE LIQUID LIFT (ft)
Suction piping must be designed so that refrigerant is thor- oughly mixed after it leaves the indoor coil suction header. The thermostatic expansion valve (TXV) sensing bulb must also be correctly located. This ensures that the TXV sensing bulb receives reliable readings. Install the suction piping as follows:
Max Allowable Pressure Drop
LEGEND db — Dry Bulb wb — Wet Bulb NOTES: 1. The liquid lift in cooling mode is based on 80/67 F (db/wb ) entering indoor-air temperature and a 95 F outdoor-air temperature, with R-22 refrigerant, at an indoor airflow of 3000 cfm. 2. The liquid lift in heating mode is based on 70/60 F (db/wb) entering indoor-air temperature and a 47/43 F (db/wb) outdoor-air tempera- ture, with R-22 refrigerant, at an indoor airflow of 3000 cfm. B. Filter Drier and Moisture Indicator
See Fig. 5. The filter drier is factory supplied and field- installed in the liquid line. Moisture indicator is field- supplied and should be installed just after liquid line shutoff valve. Do not use a receiver; there is none provided with unit and one should not be used.


LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion Valve
NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a spe- cific installation. 4. Liquid line solenoid valve (solenoid drop control) is recom- mended to prevent refrigerant migration to the compressor. A bi- flow type solenoid valve is required. 5. Filter drier must be of the biflow type, suitable for heat pump duty. 6. Internal factory-supplied TXV and bypass check valve not shown.
*Accessory item. †Field supplied.
Fig. 5 — Typical Piping Diagram, 575A/524A-H


A. Field Power Supply All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v orange wire on the transformer and connecting it to the 208-v red wire from the transformer. The end of the orange wire must then be insulated. Refer to unit label diagram for additional information. Short wire leads (pigtails) are provided for field wire connections. Use factory-supplied splices or UL approved copper/aluminum connector. When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local requirements. Install field wiring as follows:
1. Install conduit through side panel openings. 2. Install power lines to connections as shown in Fig. 8. Wrap connections with electrical tape. Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 4). Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 4, Note 2, to determine the percentage of voltage im- balance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to elec- trical components. Such operation invalidates any applicable unit warranty.
Fig. 6 — Fusible Plug Locations

B. Accessory Electric Heat
If the system is to be equipped with an accessory electric heater, refer to the 524A-H090 installation instructions and Table 5.

LEGEND TXV — Thermostatic Expansion Valve NOTE: The 8 o’clock position is shown above.
Fig. 7 — TXV Sensing Bulb Location
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit ap- proved for electrical ground when installed in accor- dance with National Electrical Code (NEC) ANSI (American National Standards Institute)/NFPA 70 (National Fire Protection Association) and local electri- cal codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
LEGEND C — Contactor NEC — National Electrical Code
Splice Connection (Factory Supplied)
Fig. 8 — 575A090 Power Wiring Connections
Field Wiring · Factory Wiring

Table 4 — Electrical Data
UNIT 575A NOMINAL VOLTAGE
Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA
090 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.7 80 1.4 21.0 25 25 89
LEGEND FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
452 + 464 + 455 Average Voltage = 3
= 457 (AB) 457 2 452 = 5 v (BC) 464 2 457 = 7 v (AC) 457 2 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance
NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.
7 % Voltage Imbalance = 100 457 = 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
max voltage deviation from average voltage = 100 x
Table 5 — Accessory Electric Heater Data
UNIT 524A-H NOMINAL kW V-PH-HZ HEATER PART NO.
AMPS MCA* MOCP*
5 240-3-60 CAELHEAT001A00 12.0 25.6 30 480-3-60 CAELHEAT002A00 6.0 12.3 15
10 240-3-60 CAELHEAT004A00 24.1 40.7 50 480-3-60 CAELHEAT005A00 12.0 19.8 25
15 240-3-60 CAELHEAT007A00 36.0 55.7 80 480-3-60 CAELHEAT008A00 18.0 27.4 40
25 240-3-60 CAELHEAT010A00 60.1 85.8 125 480-3-60 CAELHEAT011A00 30.1 42.4 60
35 240-3-60 CAELHEAT013A00 84.0 115.8 175 480-3-60 CAELHEAT014A00 42.1 57.4 80
LEGEND MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps) *Sizes shown are for single-point connection of electric heat accessory and air handler.
ACTUAL SITE VOLTAGE 200 208 230 240 400 440 460 480 240.694 .751 .918 1 — 480 — .694 .840 .918 1
(V-Ph-Hz) · 1371 = 3 · average voltage

C. Field Control Wiring Install an approved accessory thermostat assembly accord- ing to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the condi- tioned space to sense average temperature in accordance with thermostat installation instructions. Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 9) as described in following Steps 1 through 3:
RACEWAY THERMOSTAT FIELD CONNECTION
POWER WIRING CONNECTIONS

Fig. 10 — Field Control Wiring Raceway
1. Pass the control wires through the hole provided in the corner post. (See Fig. 10.) 2. Feed wire through the raceway built into the corner post to the 24-v barriers located on the left side of the con- trol box. The raceway provides the required clearance between the high- and low-voltage wiring. 3. Connect thermostat wires to screw terminals of low- voltage connection board. NOTE: 39 VA is available for field-installed accessories. Con- trol power requirement for heat pump outdoor unit is 36 VA (sealed). The factory-supplied control transformer is rated at 75 VA.
I. PRELIMINARY CHECKS
SIZE Ft M AWG sq mm 0-50 0-15.2 35 18 0.82 50-75 15.2-22.9 35 16 1.30 Over 75 Over 22.9 35 14 2.08
RATING (C)
LEGEND AWG — American Wire Gage
All wire larger than no. 18 AWG (American Wire Gage) can- not be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Evacuate and dehydrate entire refrigerant system using meth- ods described in GTAC II, Module 4, System Dehydration.
Refer to GTAC II, Module 5, Charging Recovery, Recycling, and Reclamation.
Unit panels must be in place when unit is operating during charging procedure.
Unit is shipped with holding charge only. Weigh in 15 lb of R-22 to start unit. A. Refrigerant Charging Use Cooling Charging Chart (see Fig. 11). Vary refrigerant until the conditions of the chart are met. Note that charging chart is different from the type normally used. Chart is based on charging the units to the correct subcooling for the vari- ous operating conditions. Accurate pressure gage and tem- perature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line, close to the liquid line service valve, and insulate it so that outdoor am- bient temperature does not affect the reading. Indoor airflow must be within the normal operating range of the unit. Operate unit a minimum of 15 minutes. Ensure pressure and temperature readings have stabilized. Plot liquid pressure and temperature on chart and add or reduce charge to meet curve. Adjust charge to conform with charging chart, using liquid pressure and temperature to read chart.
C — Cooling H — Heating HR — Heater Relay IFC — Indoor Fan Contactor
LLSV — Liquid Line Solenoid
Valve SUPL — Supplemental TB — Terminal Block
Fig. 9 — Control Wiring Connections


When the thermostat is satisfied, contacts open, deenergiz- ing C. The COMP, IFM, and OFM stop. As shown in Fig. 12, cooling mode refrigerant flow is as follows:
1. Hot refrigerant gas from compressor flows through the reversing valve and is directed to the outdoor coil vapor header. 2. Once at the outdoor coil vapor header, hot refrigerant gas flows up to check valve ‘‘A,’’ which is closed. All re- frigerant is then directed to complete a path through the lower 6 coil circuits (6 passes in each circuit). 3. Refrigerant flows through from the liquid header side outlets into the transfer header, where it flows upward. 4. Refrigerant leaves the transfer header through side con- nections in 4 locations and enters the middle coil cir- cuits (4 coil circuits above check valve ‘‘A’’). 5. Refrigerant leaves the 4 middle coil circuits and enters the top portion of vapor header. The refrigerant moves up to the top 2 remaining coil circuits, where it enters the subcooler section. 6. Subcooled refrigerant leaves the coil circuits through the side outlets. It passes through check valve ‘‘B’’ into the system liquid line and then into the indoor coil.
Fig. 11 — Cooling Charging Chart — 575A090
B. Oil Charging
Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if necessary to bring oil into view in sight glass. See Table 1 for oil charge. Use only ap- proved compressor oil as follows:
Suniso 3GS and WF32-150
B. Heating
Do not reuse drained oil or use any oil that has been exposed to atmosphere. Procedures for adding or removing oil are given in Refrigerant Service Techniques manual.
On a call for heat, thermostat makes circuits R-Y and R-G. When compressor time delay (5 ± 2 minutes) is completed, a circuit is made to C, starting COMP and OFM. Circuit R-G also energizes IFC and starts IFM after a 1-second delay.
If oil is added, run unit for additional 10 minutes. Stop unit and check oil level. If level is still low, add oil only after de- termining that piping system is designed for proper oil re- turn and that system is not leaking oil.
If room temperature continues to fall, circuit R-W is made through second-stage thermostat bulb. If optional electric heat package is used, a relay is energized, bringing on supplemen- tal electric heat. When thermostat is satisfied, contacts open, deenergizing contactor and relay; motors and heaters deenergize.
Each unit system has 3 service ports; one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure caps on the ports are tight.
As shown in Fig. 13, heating mode refrigerant flow is as follows:
When power is supplied to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.
A. Cooling With the thermostat in the cooling position, and when the space temperature comes within 2° F of the cooling set point, the thermostat makes circuit R-O. This energizes the revers- ing valve solenoid (RVS) and places the unit in standby con- dition for cooling.
As the space temperature continues to rise, the second stage of the thermostat makes, closing circuit R-Y. When compres- sor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C ), starting the compressor (COMP) and outdoor- fan motor (OFM). Circuit R-G is made at the same time, en- ergizing the indoor-fan contactor (IFC) and starting the indoor- fan motor (IFM) after one-second delay.


Fig. 12 — Cooling Mode Operation
C. Defrost
Observe that heating cycle shuts down when control set- ting is satisfied.
Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost thermo- stat (DFT) is closed (below 28 F).
Defrost mode is identical to Cooling mode, except outdoor- fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F.
VII. MALFUNCTION The high-pressure switch, loss-of-charge switch, and compres- sor overtemperature safety are located in a Cycle-LOC™cir- cuit that prevents heat pump operation if these safety devices are activated. The lockout system can be reset by adjusting the thermostat to open the contacts (down for heating mode, up for cooling mode) deenergizing the Cycle-LOC circuitry. Compressor over- current protection is achieved with overload breakers which are temperature-sensitive and will automatically reset.
Start and check the unit for proper control operation as follows:
Unit is equipped with a no-dump reversing valve circuit. When unit is in cooling mode, reversing valve remains in cooling position until a call for heating is requested by thermostat. When unit is in heating mode, reversing valve remains in heat- ing position until there is a call for cooling.


Fig. 13 — Heating Mode Operation

When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.
Inspect unit interior at the beginning of each cooling season and as operating conditions require.
A. Outdoor Coil
Inspect coil monthly. Clean outdoor coil annually and as re- quired by location or outdoor-air conditions. Clean coil as follows:
Fig. 14 — Cleaning Outdoor Coil

Fig. 15 — Propping Up Top Panel —11—


IV. COMPRESSOR REMOVAL See Table 1 for compressor information. Follow safety codes and wear safety glasses and work gloves.
Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to service.
Fig. 16 — Separating Coil Sections
A. Compressors
Compressor has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Start-Up, Oil Charging section.
B. Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further lubrication is required.

III. OUTDOOR FAN ADJUSTMENT (Fig. 17)
Fig. 17 — Outdoor-Fan Adjustment


N.C. — Normally Closed
TROUBLESHOOTING CHART, HEATING CYCLE


TXV — Thermostatic Expansion Valve
TROUBLESHOOTING CHART, COOLING CYCLE
Copyright 1995 Carrier Corporation CATALOG NO. BDP-3357-502

I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO.
SERIAL NO.
INDOOR: MODEL NO.
SERIAL NO.
B. Pre-Start-Up
IS THERE ANY SHIPPING DAMAGE? (Y/N)
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
CONTROLS
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)
PIPING
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR COIL, INDOOR COIL, TXV
(Thermostatic Expansion Valve), SOLENOID VALVES, FILTER DRIER, REVERSING VALVE, CHECK VALVE, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? (Y/N)
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE INTO VIEW IN THE COMPRESSOR SIGHT GLASS?
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.

-
CHECK INDOOR-FAN SPEED AND RECORD.
CHECK OUTDOOR-FAN SPEED AND RECORD.
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR-AIR TEMP LEAVING OUTDOOR-AIR TEMP INDOOR ENTERING-AIR DB (dry bulb) TEMP INDOOR ENTERING-AIR WB (wet bulb) TEMP INDOOR LEAVING-AIR DB TEMP INDOOR LEAVING-AIR WB TEMP
NOTES:
CUT ALONG DOTTED LINE
Copyright 1995 Carrier Corporation CATALOG NO. BDP-3357-502 CL-2
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.