

! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
CAUTION !
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. Puronr (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing equipment.




Vertical Connections / Economizer

C10057 Fig. 1 - Unit Dimensional Drawing




C10058 Fig. 1 - Unit Dimensional Drawing (cont.)

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Complete the following checks before installation.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 9 — Install External Condensate Trap and Line – for required trap dimensions.
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Select a location for the unit and its support system (curb or other) that provides for minimum clearances required for safety (including clearance to combustible surfaces), unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2.
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

Install curb Install field-fabricated ductwork inside curb Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details) Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details) Rig and place unit Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Required bottom condensate drain connection. Otherwise, 36” (914mm) for condensate connection.
C07459 Fig. 2 - Service Clearance Dimensional Drawing
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Table 1 – Operating Weights

Roof mount — · Curb-mounted installation —

Prepare pad and unit supports Check and tighten the bottom condensate drain connection plug Rig and place unit Convert unit to side duct connection arrangement Install field-fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 3. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb.
Frame-mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.
Pad-mounted installation — · Frame-mounted installation —
![Page 7 of the Bryant Legacy Line Air Conditioner (551J) user manual — CRRFCURB002A01 2’-0” [610]](/cdn/reader/b8/b8d750d245fb069815ba4dc61a53e2d977ac1fdb35a1e115eb22e87ec3495d2d/images/page-7.webp?w=400)

CRRFCURB001A01 1’-2” [356]
13/4” [44.5] 1’-4” [406] CRBTMPWR004A01
![Bryant Legacy Line Air Conditioner (551J) — CRRFCURB002A01 2’-0” [610] diagram (page 7)](/cdn/reader/b8/b8d750d245fb069815ba4dc61a53e2d977ac1fdb35a1e115eb22e87ec3495d2d/images/fig-7-2.webp)
C10059 Fig. 3 - Roof Curb Details


For units with accessory electric heaters: Horizontal applications require a minimum clearance to combustible surfaces of 1-in (25 mm) from duct for first 12-in (305 mm) away from unit. Vertical applications do not require a minimum clearance around ductwork.
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.
DIFFERENCE IN. (MM)
C06110 Fig. 4 - Unit Leveling Tolerances
Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.
Before setting the unit onto the curb, recheck gasketing on curb.
Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure on vertical ducted units. Do not connect ductwork to unit.
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed for handling by fork truck. If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

Fig. 5 - Rigging Details

Positioning on Curb —
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
Position unit on roof curb so that the following clearances are maintained: 1/4 in. (6.4 mm) clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Fig. 3, section C-C.
The outdoor hood components are shipped in a box located in the unit return air compartment behind the outdoor-ar opening access panel (or economizer). Access is through the filter access panel. See Fig. 7.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed for handling by fork truck.
C06023 Fig. 7 - Typical Access Panel Locations
After unit is in position, remove rigging skids and shipping materials.
Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 6.


C06024 Fig. 8 - Hood Box Removal
Motorized 2-Position Damper Hood —
C06108 Fig. 6 - Horizontal Conversion Panels
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.


SCREEN RETAINER
HOOD TOP
HOOD SIDE
SEAL STRIP
SEAL STRIP
SCREEN TRACKS
HOOD SIDE
OUTDOOR AIR INLET SCREEN
OUTDOOR-AIR HOOD – UNASSEMBLED
HOOD TOP
HOOD SIDE
TRACKS FOR AIR INLET SCREEN
C06025 Fig. 10 - Indoor Coil Access Panel Relocation

C07504 Fig. 9 - Outdoor-Air Hood Details
1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bot- tom of the indoor coil access panel. See Fig. 10. 2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 11. 3. Remove the shipping tape holding the economizer ba- rometric relief damper in place. 4. Insert the hood divider between the hood sides. See Fig. 11 and 12. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter. 5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 12. 6. Caulk the ends of the joint between the unit top panel and the hood top. 7. Replace the filter access panel.
C06026 Fig. 11 - Economizer Hood Construction

FILTER CLIP
C06027 Fig. 12 - Economizer Filter Installation
Economizer Hood —

Step 10 — Make Electrical Connections
and Line
! WARNING
The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 13. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

ALTERNATE BOTTOM DRAIN
DRAIN (FACTORY-INSTALLED)
PLUG
C08021 Fig. 13 - Condensate Drain Pan (Side View)
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan plug can be tightened with a 1/2-in. square socket drive extension.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a 1/2-in. square socket drive extension) and install it in the side drain connection.
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 14.

MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE BASE RAIL
Refer to Fig. 19 for power transformer connections and the discussion on connecting the convenience outlet on page 12.
Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size is #2 AWG (copper only). (See Fig. 15.)
C08022 Fig. 14 - Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).

Units Without Disconnect Option
Units Without Factory-Installed Disconnect —
1-ph Belt Drive IFM
When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
C IFC Direct Drive IFM
All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 15 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2 ga AWG per pole.
Units With Disconnect Option
Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.
All field wiring must comply with the NEC and local requirements.
Disconnect factory test leads; discard.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 200-v 1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect.
C10056 Fig. 15 - Power Wiring Connections
Units with Factory-Installed Disconnect —
The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel. Discard the factory test leads (see Fig. 15).
FIRE HAZARD Failure to follow this warning could result in intermittent operation or performance satisfaction. Do not connect aluminum wire between disconnect switch and 551J unit. Use only copper wire. (See Fig. 16.)
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary.
SWITCH
COPPER
WIRE ONLY
ALUMINUM
Two types of convenience outlets are offered on 551J models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 17.
A93033 Fig. 16 - Disconnect Switch and Unit

Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.

Unit-powered type: A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 17.
C08128 Fig. 17 - Convenience Outlet Location
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non-fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 19.
Installing Weatherproof Cover –
A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 18. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.


Fig. 19 - Powered Convenience Outlet Wiring
Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.
C09022 Fig. 18 - Weatherproof Cover Installation
Pwd-CO Transformer · Convenience

hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.
Units without Thru-Base Connections —
A9225 Fig. 20 - Convenience Outlet Utilization Notice Label
Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 4. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 5, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
Convenience outlet usage rating:
up to 2 hours maximum
Field Control Wiring —
Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
The 551J unit requires an external temperature control device. This device can be a thermostat emulation device provided as part of a third-party Building Management System.
Factory-Option Thru-Base Connections —
This service connection kit consists of a 1/2-in electrical bulkhead connector and a 3/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. The 3/4-in bulkhead connector enables the low-voltage control wires to pass through the basepan. The 1/2-in electrical bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 21.
Install a Bryant-approved accessory thermostat according to installation instructions included with the accessory. For complete economizer function, select a two-stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
HIGH VOLTAGE CONDUIT CONNECTOR
Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
C08637 Fig. 21 - Thru-Base Connection Fittings
Check tightness of connector lock nuts before connecting electrical conduits.
For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35_C (95_F) minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35_C (95_F) minimum]. For over 75 ft. (23 m), use no. 14 AWG insulated wire [35_C (95_F) minimum]. All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Field-supplied and field-installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A
Convenience Outlet Utilization · Thermostat —


Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available.
T H E R M O S T A T (Note 1) (Note 2)
551J units may be equipped with field-installed accessory electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators, line-break limit switches and a control contactor. One or two heater modules may be used in a unit. Heater modules are installed in the compartment below the indoor (supply) fan outlet. Access is through the indoor access panel. Heater modules slide into the compartment on tracks along the bottom of the heater opening. See Fig. 24, Fig. 25 and Fig. 26.
C08069 Fig. 22 - Low-Voltage Connections

Unit without thru-base connection kit —
Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Controls Connection Board. See Fig. 23.

UNIT BLOCK-OFF PANEL
OUTDOOR ACCESS PANEL
C08133 Fig. 24 - Typical Access Panel Location (3-6 Ton)
Not all available heater modules may be used in every unit. Use only those heater modules that are UL listed for use in a specific size unit. Refer to the label on the unit cabinet for the list of approved heaters. Unit heaters are marked with Heater Model Numbers. But heaters are ordered as and shipped in cartons marked with a corresponding heater Sales Package part number. See Table 2 for correlation between heater Model Number and Sales Package part number. NOTE: The value in position 9 of the part number differs between the sales package part number (value is 1) and a bare heater model number (value is 0).
C08027 Fig. 23 - Field Control Wiring Raceway
Table 2 – Heater Model Number

Bare Heater Model Number C R H E A T E R 0 0 1 A 0 0
C R H E A T E R 1 0 1 A 0 0
Field Wiring

EMT OR RIGID CONDUIT (FIELD-SUPPLIED)
SINGLE POINT BOX
CENTER POST
MANUAL RESET LIMIT SWITCH


BUSHING
SINGLE POINT BOX MOUNTING SCREWS
DRIP BOOT BRACKET MOUNTING SCREWS
POWER WIRES
HEATER MOUNTING BRACKET
FOAM BUSHING
3 1 23 ISTED AIR NDITIONING UIP ACCESS 346N.
CONTROL WIRE TERMINAL BLOCK
C08134 Fig. 25 - Typical Component Location
C08136 Fig. 27 - Typical Single Point Installation

Low-Voltage Control Connections — Pull the low-voltage control leads from the heater module(s) - VIO and BRN (two of each if two modules are installed; identify for Module #1) - to the 4-pole terminal board TB4 located on the heater bulkhead to the left of Heater #1. Connect the VIO lead from Heater #1 to terminal TB4-1. For 2 stage heating, connect the VIO lead from Heater #2 to terminal TB4-2. For 1 stage heating with 2 heater modules connect the VIO lead from both Heater #1 and #2 to terminal TB4-1. Connect both BRN leads to terminal TB4-3. See Fig. 28.
FLANGE
CTB
C08135 Fig. 26 - Typical Module Installation

Single Point Boxes and Supplementary Fuses — When the unit MOCP device value exceeds 60-A, unit-mounted supplementary fuses are required for each heater circuit. These fuses are included in accessory Single Point Boxes, with power distribution and fuse blocks. The single point box will be installed directly under the unit control box, just to the left of the partition separating the indoor section (with electric heaters) from the outdoor section. The Single Point Box has a hinged access cover. See Fig. 27. The Single Point Box also includes a set of power taps and pigtails to complete the wiring between the Single Point Box and the unit’s main control box terminals. Refer to the accessory heater and Single Point Box installation instructions for details on tap connections. All fuses on 551J units are 60-A. (Note that all heaters are qualified for use with a 60-A fuse, regardless of actual heater ampacity, so only 60-A fuses are necessary.) Single Point Boxes without Fuses — Unit heater applications not requiring supplemental fuses require a special Single Point Box without any fuses. The accessory Single Point Boxes contain a set of power taps and pigtails to complete the wiring between the Single Point Box and the unit’s main control box terminals. Refer to accessory heater and Single Point Box installation instructions for details on tap connections.
HR1: On Heater 1 in Position #1 HR2: On Heater 2 in Position #2 (if installed)
C08331 Fig. 28 - Accessory Electric Heater Control
Connections

Smoke detectors are available as factory-installed options on 551J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.

Units equipped with factory-optional Return Air smoke detectors require a relocation of the sensor module at unit installation. See “Completing Installation of Return Air Smoke Sensor:” on page 19 for details.
Conduit couplings (supplied by installer)
The smoke detector system consists of a four-wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device.
C08208 Fig. 29 - Controller Assembly
The controller (see Fig. 29) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face).

The sensor (see Fig. 30) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left-side of the housing).
Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc.
C08209 Fig. 30 - Smoke Detector Sensor

The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not.
Return Air Detector module (shipping position shown)*

For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition.
Supply Air — The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 31. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-off filter panel.
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307 Fig. 32 - Typical Return Air Detector Location
Return Air with Economizer — The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 33. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See the following installation procedure.)


C08245 Fig. 31 - Typical Supply Air Smoke Detector Sensor
Return Air without Economizer — The sampling tube is located across the return air opening on the unit basepan. See Fig. 32. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See “Completing Installation of Return Air Smoke Sensor:” for details.)
Return Air Sampling Tube
C08129 Fig. 33 - Return Air Sampling Tube Location
Controller module · Location


1. Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 34. Save the screws. 2. Remove the Return Air Sensor and its detector plate. 3. Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 35. 4. Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 35. 5. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
C08127 Fig. 35 - Return Air Sensor Operating Position
Additional Application Data — Refer to Catalog No. HKRNKA-1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.

C08126 Fig. 34 - Return Air Detector Shipping Position
Screws · Flexible Exhaust Tubes · Sample Tube

RTU-MP control system —
The RTU-MP control is factory-mounted in the 551J unit’s main control box, to the left of the CTB. See Fig. 37. Factory wiring is completed through harnesses connected to the CTB. Field connections for RTU-MP sensors will be made at the Phoenix connectors on the RTU-MP board. The factory-installed RTU-MP control includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package.
The RTU-MP controller, see Fig. 36, provides expanded stand-alone operation of the HVAC system plus connection and control through communication with several Building Automation Systems (BAS) through popular third-party network systems. The available network systems are BACnet MP/TP, Modbus and Johnson J2. Communication with LonWorks is also possible by adding an accessory interface card to the RTU-MP. Selection of the communication protocol and baud rate are made at on-board DIP switches.
Refer to Table 2, RTU-MP Controller Inputs and Outputs for locations of all connections to the RTU-MP board.

C07129 Fig. 36 - RTU-MP Multi-Protocol Control Board

C10049 Fig. 37 - 551J Control Box Component Locations


C10044 Fig. 38 - RTU-MP System Control Wiring Diagram

Table 3 – RTU-MP Controller Inputs and Outputs

Space Temperature Sensor sptsens AI (10K Thermistor) J20---1, 2
Supply Air Temperature sat AI (10K Thermistor) J2---1, 2
Local Outside Air Temperature Sensor oatsens AI (10K Thermistor) J2---3, 4
Space Temperature Offset Pot sptopot AI (100K Potentiometer) J20---3
Indoor Air Quality iaq AI (4---20 ma) J4---2, 3
Outdoor Air Quality oaq AI (4---20 ma) J4---5, 6
Humidistat Input Status humstat DI (24 VAC) J5---7, 8
J4---2,3 or J4---5,6 Outside Air Relative Humidity oarh AI (4---20 ma)
J5 5,6 or J5---7,8 Filter Status filtstat DI (24 VAC)
Supply Fan Relay State sf DO Relay (24VAC , 1A) J1---4
Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J1---8
Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J1---7
Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J1---6
Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J1---5
Power Exhaust Relay State aux_2 DO Relay (24VAC , 1A) J11---3
Dehumidification Relay State humizer DO Relay (24VAC, 1A) J11---7, 8
LEGEND AI --- Analog Input AO --- Analog Output DI --- Discrete Input DO --- Discrete Output * These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.
The RTU-MP controller requires the use of a Byrant space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor - On FIOP-equipped 551J unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.
The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 39.
SUPPLY AIR TEMPERATURE SENSOR
C08200 Fig. 39 - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units

Outdoor Air Temperature (OAT) Sensor - The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

EconoMi$er2 - The RTU-MP control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU-MP control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field-installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors) Space CO2 sensor Outdoor air CO2 sensor
Field Connections - Field connections for accessory sensors and input devices are made the RTU-MP, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU-MP must be routed through the raceway built into the corner post as shown in Fig. 23. The raceway provides the UL required clearance between high- and low-voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU-MP. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.
C08201 Fig. 40 - T-55 Space Temperature Sensor Wiring
SEN
C08460 Fig. 41 - RTU-MP T-55 Sensor Connections
Connect T-56 - See Fig. 42 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to RTU-MP J20-1, J20-2 and J20-3 per Fig. 43.
A field-supplied Byrant space temperature sensor is required with the RTU-MP to monitor space temperature. There are 3 sensors available for this application:
S 33ZCT55SPT, space temperature sensor with override

S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used.
Connect T-55 - See Fig. 40 for typical T-55 internal connections. Connect the T-55 SEN terminals to RTU-MP J20-1 and J20-2. See Fig. 41.
C08202 Fig. 42 - T-56 Internal Connections
button

Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 45. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).
J20-2 SEN
SET
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
C08461 Fig. 43 - RTU-MP T-56 Sensor Connections
Differential Enthalpy Control — Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.
Connect T-59 - The T-59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 44 for internal connections at the T-59. Connect the SEN terminal (BLU) to RTU-MP J20-1. Connect the COM terminal (BRN) to J20-2. Connect the SET terminal (STO or BLK) to J20-3.
Return Air Enthalpy Sensor — Mount the return-air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy controller (33CSENTHSW). See Fig. 46.
BLK (STO)
SENSOR
RED ECONO MOTOR – 4-20 Main
BLU (SPT)
GND
BLK
ESL LOW
GRA
OR SET SEN
OPB COMPWR+
+ 24-36 VDC In
24 VAC
– 4-20 Main Out
C09027 Fig. 46 - Outside and Return Air Enthalpy Sensor
C07132 Fig. 44 - Space Temperature Sensor Typical Wiring
To wire the return air enthalpy sensor, perform the following:
Outdoor Air Enthalpy Control (PNO 33CSENTHSW) -
The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 45.)
Indoor Air Quality (CO2 sensor) — The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.
ECONO MOTOR
GND
BLK
CTB ECON LOW
GRA
7 ESL
The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical
C09026 Fig. 45 - Enthalpy Switch (33CSENTHSW) Connections

requirements and terminal locations. See Fig. 47 for typical CO2 sensor wiring schematic.

24 VAC
C08462 Fig. 48 - RTU-MP / Indoor CO2 Sensor
0-10VDC SIG COM 4-20mA
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 49. The outdoor air CO2 sensor must be located in the economizer outside air hood.
8 7 6 5 4 3 2 1 2 1

C08635 Fig. 47 - Indoor/Outdoor Air Quality (CO2) Sensor
(33ZCSENCO2) - Typical Wiring Diagram
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
C07135 Fig. 49 - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO2 Sensor — A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 47. Connect the 4 to 20 mA terminal to RTU-MP J4-5. Connect the SIG COM terminal to RTU-MP J4-6. See Fig. 50.
To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 47. Connect the 4-20 mA terminal to RTU-MP J4-2 and connect the SIG COM terminal to RTU-MP J4-3. See Fig. 48.
COM
24 VAC
C08463 Fig. 50 - RTU-MP / Outdoor CO2 Sensor

On 551J units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU-MP controller communicates the smoke detector’s tripped status to the BAS building control. See Fig. 38, the RTU-MP System Control wiring schematic.
Also set MENU→Schedules→occupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 36 and Table 3 for wire terminations at J5.
Connect the accessory Power Exhaust contactor coil(s) per Fig. 51.
The Fire Shutdown Switch configuration, MENU→Config→Inputs→input 5, identifies the normally open status of this input when there is no fire alarm.
TAN
Connecting Discrete Inputs
CTB THERMOSTAT
Filter Status
GRA
C08464 Fig. 51 - RTU-MP Power Exhaust Connections
The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 36 and Fig. 38 for wire terminations at J5.
General
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.
The fan status accessory is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 36 and Fig. 38 for wire terminations at J5.
The RTU-MP can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig. 52 for the switch setting per protocol. The 3rd party connection to the RTU-MP is through plug J19.
The remote occupancy accessory is a field-installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting MENU→Config→Inputs→input 3, 5, 8, or 9 to Remote Occupancy and normally open (N/O) or normally closed (N/C).
Refer to the RTU-MP 3rd Party Integration Guide for more detailed information on protocols, 3rd party wiring, and networking.
Power Exhaust


PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP (Master) Unused OFF OFF OFF ON OFF Select Baud Select Baud
Modbus (Slave) Unused OFF OFF ON ON OFF Select Baud Select Baud
N2 (Slave) Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF


Fig. 52 - RTU-MP SW3 Dip Switch Settings
Virtual BACview is a freeware computer program that functions as the BACview6 Handheld. The USB Link interface (USB-L) is required to connect a computer to the RTU-MP board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld.
The BACview6 is a keypad/display interface used to connect to the RTU-MP to access the control information, read sensor values, and test the RTU, see Fig. 53. This is an accessory interface that does not come with the MP controller and can only be used at the unit. Connect the BACview6 to the RTU-MP’s J12 local access port. There are 2 password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is idle. Contact your Bryant applications engineer for details on navigation and screen content.
Communication LEDs
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear.

C07170 Fig. 53 - BACview6 Handheld Connections

Table 4 – LEDs The LEDs on the RTU-MP show the status of certain functions
If this LED is on... Status is...
Power The RTU MP has power
Rx The RTU MP is receiving data from the network segment
Tx The RTU MP is transmitting data over the network segment
DO# The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows... And Error LED shows... Status is...
2 flashes per second Off Normal
2 flashes per second 2 flashes, alternating with Run LED Five minute auto---restart delay after system error
2 flashes per second 3 flashes, then off Control module has just been formatted
2 flashes per second 4 flashes, then pause
Two or more devices on this network have the same ARC156 network address
2 flashes per second On Exec halted after frequent system errors or control programs halted
5 flashes per second On Exec start---up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second 7 flashes per second, alternating with Run LED Ten second recovery period after brownout
14 flashes per second 14 flashes per second, alternating with Run LED Brownout
Failure. Try the following solutions: S Turn the RTU---MP off, then on. S Format the RTU---MP. S Download memory to the RTU---MP. S Replace the RTU---MP.
On On

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data
NO M. V---Ph---HZ
ELEC. HTR P.E. NO C.O. or UNPWR C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
29.2 45 29 88 31.1 45 31 90 101A00 3.3/4.4 15.9/18.3 29.2/32.1 45/45 29/30 88/88 31.5/34.5 45/45 31/32 90/90 102A00 4.9/6.5 23.5/27.1 38.6/43.1 45/45 36/40 88/88 41.0/45.5 45/45 38/42 90/90 103B00 6.5/8.7 31.4/36.3 48.5/54.6 50/60 45/50 88/88 50.9/57.0 60/60 47/52 90/90 104B00 7.9/10.5 37.9/43.8 56.6/64.0 60/70 52/59 88/88 59.0/66.4 60/70 54/61 90/90 102A00,102A00 9.8/13.0 46.9/54.2 67.9/77.0 70/80 62/71 88/88 70.3/79.4 80/80 65/73 90/90
DD---STD
21.4 30 22 82 23.2 30 24 84 101A00 3.3/4.4 9.2/10.6 21.4/22.5 30/30 22/22 82/82 23.3/24.9 30/30 24/24 84/84 102A00 4.9/6.5 13.6/15.6 26.3/28.8 30/30 24/26 82/82 28.6/31.1 30/35 26/29 84/84 103B00 6.5/8.7 18.1/20.9 31.9/35.4 35/40 29/33 82/82 34.3/37.8 35/40 32/35 84/84 104B00 7.9/10.5 21.9/25.3 36.6/40.9 40/45 34/38 82/82 39.0/43.3 40/45 36/40 84/84 105A00 12.0/16.0 33.4/38.5 51.0/57.4 60/60 47/53 82/82 53.4/59.8 60/60 49/55 84/84
DD---STD
18.9 25 19 87 20.8 30 21 89 101A00 3.3/4.4 9.2/10.6 18.9/19.4 25/25 19/19 87/87 20.8/21.8 30/30 21/21 89/89 102A00 4.9/6.5 13.6/15.6 23.1/25.6 25/30 21/24 87/87 25.5/28.0 30/30 23/26 89/89 103B00 6.5/8.7 18.1/20.9 28.8/32.3 30/35 26/30 87/87 31.1/34.6 35/35 29/32 89/89 104B00 7.9/10.5 21.9/25.3 33.5/37.8 35/40 31/35 87/87 35.9/40.1 40/45 33/37 89/89 105A00 12.0/16.0 33.4/38.5 47.9/54.3 50/60 44/50 87/87 50.3/56.6 60/60 46/52 89/89
MED
19.2 25 19 105 21.1 30 21 107 101A00 3.3/4.4 9.2/10.6 19.2/19.8 25/25 19/19 105/105 21.1/22.1 30/30 21/21 107/107 102A00 4.9/6.5 13.6/15.6 23.5/26.0 25/30 22/24 105/105 25.9/28.4 30/30 24/26 107/107 103B00 6.5/8.7 18.1/20.9 29.1/32.6 30/35 27/30 105/105 31.5/35.0 35/40 29/32 107/107 104B00 7.9/10.5 21.9/25.3 33.9/38.1 35/40 31/35 105/105 36.3/40.5 40/45 33/37 107/107 105A00 12.0/16.0 33.4/38.5 48.3/54.6 50/60 44/50 105/105 50.6/57.0 60/60 47/52 107/107
HIGH
11.8 15 12 43 12.8 15 13 44 106A00 6.0 7.2 14.0 15 13 43 15.3 20 14 44 107A00 8.8 10.6 18.3 20 17 43 19.5 20 18 44 108A00 11.5 13.8 22.3 25 20 43 23.5 25 22 44 109A00 14.0 16.8 26.0 30 24 43 27.3 30 25 44
DD---STD
9.9 15 10 45 10.9 15 11 46 106A00 6.0 7.2 11.6 15 11 45 12.9 15 12 46 107A00 8.8 10.6 15.9 20 15 45 17.1 20 16 46 108A00 11.5 13.8 19.9 20 18 45 21.1 25 19 46 109A00 14.0 16.8 23.6 25 22 45 24.9 25 23 46
MED
10.4 15 10 54 11.4 15 11 55 106A00 6.0 7.2 12.3 15 11 54 13.5 15 12 55 107A00 8.8 10.6 16.5 20 15 54 17.8 20 16 55 108A00 11.5 13.8 20.5 25 19 54 21.8 25 20 55 109A00 14.0 16.8 24.3 25 22 54 25.5 30 23 55
HIGH
DD---STD
NONE --- --- 1.9 9.3 15 10 42 11.2 15 12 44
NONE --- --- 1.9 7.2 15 7 43 9.1 15 9 45
NONE --- --- 1.9 7.3 15 7 49 9.2 15 9 51
See “Legend and Notes for Table 5” on page 35.

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
NO M. V---Ph---HZ
ELEC. HTR P.E. w/ PWRD C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
34.0 50 34 93 35.9 50 36 95 101A00 3.3/4.4 15.9/18.3 35.1/38.1 50/50 34/35 93/93 37.5/40.5 50/50 36/37 95/95 102A00 4.9/6.5 23.5/27.1 44.6/49.1 50/50 41/45 93/93 47.0/51.5 50/60 43/47 95/95 103B00 6.5/8.7 31.4/36.3 54.5/60.6 60/70 50/56 93/93 56.9/63.0 60/70 52/58 95/95 104B00 7.9/10.5 37.9/43.8 62.6/70.0 70/80 58/64 93/93 65.0/72.4 70/80 60/67 95/95 102A00,102A00 9.8/13.0 46.9/54.2 73.9/83.0 80/90 68/76 93/93 76.3/85.4 80/90 70/79 95/95
DD---STD
26.2 30 27 87 28.1 35 29 89 101A00 3.3/4.4 9.2/10.6 26.8/28.5 30/30 27/27 87/87 29.1/30.9 35/35 29/29 89/89 102A00 4.9/6.5 13.6/15.6 32.3/34.8 35/35 30/32 87/87 34.6/37.1 35/40 32/34 89/89 103B00 6.5/8.7 18.1/20.9 37.9/41.4 40/45 35/38 87/87 40.3/43.8 45/45 37/40 89/89 104B00 7.9/10.5 21.9/25.3 42.6/46.9 45/50 39/43 87/87 45.0/49.3 50/50 41/45 89/89 105A00 12.0/16.0 33.4/38.5 57.0/63.4 60/70 52/58 87/87 59.4/65.8 60/70 50/60 89/89
DD---STD
23.7 30 24 92 25.6 30 26 94 101A00 3.3/4.4 9.2/10.6 23.7/25.4 30/30 24/24 92/92 26.0/27.8 30/30 26/26 94/94 102A00 4.9/6.5 13.6/15.6 29.1/31.6 30/35 27/29 92/92 31.5/34.0 35/35 29/31 94/94 103B00 6.5/8.7 18.1/20.9 34.8/38.3 35/40 32/35 92/92 37.1/40.6 40/45 34/37 94/94 104B00 7.9/10.5 21.9/25.3 39.5/43.8 40/45 36/40 92/92 41.9/46.1 45/50 39/42 94/94 105A00 12.0/16.0 33.4/38.5 53.9/60.3 60/70 50/55 92/92 56.3/62.6 60/70 52/58 94/94
MED
24.0 30 25 110 25.9 30 27 112 101A00 3.3/4.4 9.2/10.6 24.0/25.8 30/30 25/25 110/110 26.4/28.1 30/30 27/27 112/112 102A00 4.9/6.5 13.6/15.6 29.5/32.0 30/35 27/29 110/110 31.9/34.4 35/35 29/32 112/112 103B00 6.5/8.7 18.1/20.9 35.1/38.6 40/40 32/36 110/110 37.5/41.0 40/45 35/38 112/112 104B00 7.9/10.5 21.9/25.3 39.9/44.1 40/45 37/41 110/110 42.3/46.5 45/50 39/43 112/112 105A00 12.0/16.0 33.4/38.5 54.3/60.6 60/70 50/56 110/110 56.6/63.0 60/70 52/58 112/112
HIGH
14.0 20 14 45 15.0 20 16 46 106A00 6.0 7.2 16.8 20 15 45 18.0 20 17 46 107A00 8.8 10.6 21.0 25 19 45 22.3 25 20 46 108A00 11.5 13.8 25.0 25 23 45 26.3 30 24 46 109A00 14.0 16.8 28.8 30 26 45 30.0 30 28 46
DD---STD
12.1 15 12 47 13.1 15 13 48 106A00 6.0 7.2 14.4 15 13 47 15.6 20 14 48 107A00 8.8 10.6 18.6 20 17 47 19.9 20 18 48 108A00 11.5 13.8 22.6 25 21 47 23.9 25 22 48 109A00 14.0 16.8 26.4 30 24 47 27.6 30 25 48
MED
12.6 15 13 56 13.6 20 14 57 106A00 6.0 7.2 15.0 15 14 56 16.3 20 15 57 107A00 8.8 10.6 19.3 20 18 56 20.5 25 19 57 108A00 11.5 13.8 23.3 25 21 56 24.5 25 23 57 109A00 14.0 16.8 27.0 30 25 56 28.3 30 26 57
HIGH
DD---STD
NONE --- --- 1.9 11.0 15 12 44 12.9 15 14 46
NONE --- --- 1.9 8.9 15 9 45 10.8 15 11 47
NONE --- --- 1.9 9.0 15 9 51 10.9 15 11 53
See “Legend and Notes for Table 5” on page 35.

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
NO M. V---Ph---HZ
ELEC. HTR P.E. NO C.O. or UNPWR C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
36.1 50 35 127 38.0 50 37 129 101A00 3.3/4.4 15.9/18.3 36.1/36.1 50/50 35/35 127/127 38.0/38.0 50/50 37/37 129/129 103B00 6.5/8.7 31.4/36.3 48.5/54.6 50/60 45/50 127/127 50.9/57.0 60/60 47/52 129/129 102A00,102A00 9.8/13.0 46.9/54.2 67.9/77.0 70/80 62/71 127/127 70.3/79.4 80/80 65/73 129/129 103B00,103B00 13.1/17.4 62.8/72.5 87.8/99.9 90/100 81/92 127/127 90.1/102.3 100/110 83/94 129/129 104B00,104B00 15.8/21.0 75.8/87.5 104.0/118.6 110/125 96/109 127/127 106.4/121.0 110/125 98/111 129/129
DD---STD
25.9 30 26 93 27.8 40 28 95 102A00 4.9/6.5 13.6/15.6 26.3/28.8 30/30 26/26 93/93 28.6/31.1 40/40 28/29 95/95 103B00 6.5/8.7 18.1/20.9 31.9/35.4 35/40 29/33 93/93 34.3/37.8 40/40 32/35 95/95 105A00 12.0/16.0 33.4/38.5 51.0/57.4 60/60 47/53 93/93 53.4/59.8 60/60 49/55 95/95 104B00,104B00 15.8/21.0 43.8/50.5 64.0/72.4 70/80 59/67 93/93 66.4/74.8 70/80 61/69 95/95
DD---STD
23.4 30 23 98 25.3 30 25 100 102A00 4.9/6.5 13.6/15.6 23.4/25.6 30/30 23/24 98/98 25.5/28.0 30/30 25/26 100/100 103B00 6.5/8.7 18.1/20.9 28.8/32.3 30/35 26/30 98/98 31.1/34.6 35/35 29/32 100/100 105A00 12.0/16.0 33.4/38.5 47.9/54.3 50/60 44/50 98/98 50.3/56.6 60/60 46/52 100/100 104B00,104B00 15.8/21.0 43.8/50.5 60.9/69.3 70/70 56/64 98/98 63.3/71.6 70/80 58/66 100/100
MED
23.7 30 23 116 25.6 30 26 118 102A00 4.9/6.5 13.6/15.6 23.7/26.0 30/30 23/24 116/116 25.9/28.4 30/30 26/26 118/118 103B00 6.5/8.7 18.1/20.9 29.1/32.6 30/35 27/30 116/116 31.5/35.0 35/40 29/32 118/118 105A00 12.0/16.0 33.4/38.5 48.3/54.6 50/60 44/50 1116/16 50.6/57.0 60/60 47/52 118/118 104B00,104B00 15.8/21.0 43.8/50.5 61.3/69.6 70/70 56/64 116/116 63.6/72.0 70/80 59/66 118/118
HIGH
12.7 15 13 47 13.7 20 14 48 106A00 6.0 7.2 14.0 15 13 47 15.3 20 14 48 108A00 11.5 13.8 22.3 25 20 47 23.5 25 22 48 109A00 14.0 16.8 26.0 30 24 47 27.3 30 25 48 108A00,108A00 23.0 27.7 39.6 40 36 47 40.9 45 38 48
DD---STD
10.8 15 11 49 11.8 15 12 50 106A00 6.0 7.2 11.6 15 11 49 12.9 15 12 50 108A00 11.5 13.8 19.9 20 18 49 21.1 25 19 50 109A00 14.0 16.8 23.6 25 22 49 24.9 25 23 50 108A00,108A00 23.0 27.7 37.3 40 34 49 38.5 40 35 50
MED
11.3 15 11 58 12.3 15 12 59 016A00 6.0 7.2 12.3 15 11 58 13.5 15 12 59 108A00 11.5 13.8 20.5 25 19 58 21.8 25 20 59 109A00 14.0 16.8 24.3 25 22 58 25.5 30 23 59 108A00,108A00 23.0 27.7 37.9 40 35 58 39.1 40 36 59
HIGH
DD---STD
NONE --- --- 1.9 10.9 15 11 43 12.8 15 13 45
NONE --- --- 1.9 8.8 15 9 44 10.7 15 11 46
NONE --- --- 1.9 8.9 15 9 50 10.8 15 11 52
See “Legend and Notes for Table 5” on page 35.

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
NO M. V---Ph---HZ
ELEC. HTR P.E. w/PWRD C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
40.9 60 41 132 42.8 60 43 134 101A00 3.3/4.4 15.9/18.3 40.9/40.9 60/60 41/41 132/132 42.8/42.8 60/60 43/43 134/134 103B00 6.5/8.7 31.4/36.3 54.5/60.6 60/70 50/56 132/132 56.9/63.0 60/70 52/58 134/134 102A00,102A00 9.8/13.0 46.9/54.2 73.9/83.0 80/90 68/76 132/132 76.3/85.4 80/90 70/79 134/134 103B00,103B00 13.1/17.4 62.8/72.5 93.8/105.9 100/110 86/97 132/132 96.1/108.3 100/110 88/100 134/134 104B00,104B00 15.8/21.0 75.8/87.5 110.0/124.6 125/125 101/115 132/132 112.4/127.0 125/150 103/117 134/134
DD---STD
30.7 40 31 98 32.6 45 34 100 102A00 4.9/6.5 13.6/15.6 32.3/34.8 40/40 31/32 98/98 34.6/37.1 45/45 34/34 100/100 103B00 6.5/8.7 18.1/20.9 37.9/41.4 40/45 35/38 98/98 40.3/43.8 45/45 37/40 100/100 105A00 12.0/16.0 33.4/38.5 57.0/63.4 60/70 52/58 98/98 59.4/65.8 60/70 55/60 100/100 104B00,104B00 15.8/21.0 43.8/50.5 70.0/78.4 80/80 64/72 98/98 72.4/80.8 80/90 67/74 100/100
DD---STD
28.2 40 29 103 30.1 40 31 105 102A00 4.9/6.5 13.6/15.6 29.1/31.6 40/40 29/29 103/103 31.5/34.0 40/40 31/31 105/105 103B00 6.5/8.7 18.1/20.9 34.8/38.3 40/40 32/35 103/103 37.1/40.6 40/45 34/37 105/105 105A00 12.0/16.0 33.4/38.5 53.9/60.3 60/70 50/55 103/103 56.3/62.6 60/70 52/58 105/105 104B00,104B00 15.8/21.0 43.8/50.5 66.9/75.3 70/80 62/69 103/103 69.3/77.6 70/80 64/71 105/105
MED
28.5 40 29 121 30.4 40 31 123 102A00 4.9/6.5 13.6/15.6 29.5/32.0 40/40 29/29 121/121 31.9/34.4 40/40 31/32 123/123 103B00 6.5/8.7 18.1/20.9 35.1/38.6 40/40 32/36 121/121 37.5/41.0 40/45 35/38 123/123 105A00 12.0/16.0 33.4/38.5 54.3/60.6 60/70 50/56 121/121 56.6/63.0 60/70 52/58 123/123 104B00,104B00 15.8/21.0 43.8/50.5 67.3/75.6 70/80 62/70 121/121 69.6/78.0 70/80 64/72 123/123
HIGH
14.9 20 15 49 15.9 20 16 50 106A00 6.0 7.2 16.8 20 15 49 18.0 20 17 50 108A00 11.5 13.8 25.0 25 23 49 26.3 30 24 50 109A00 14.0 16.8 28.8 30 26 49 30.0 30 28 50 108A00,108A00 23.0 27.7 42.4 45 39 49 43.6 45 40 50
DD---STD
13.0 15 13 51 14.0 20 14 52 106A00 6.0 7.2 14.4 15 13 51 15.6 20 14 52 108A00 11.5 13.8 22.6 25 21 51 23.9 25 22 52 109A00 14.0 16.8 26.4 30 24 51 27.6 30 25 52 108A00,108A00 23.0 27.7 40.0 45 37 51 41.3 45 38 52
MED
13.5 20 14 60 14.5 20 15 61 016A00 6.0 7.2 15.0 20 14 60 16.3 20 15 61 108A00 11.5 13.8 23.3 25 21 60 24.5 25 23 61 109A00 14.0 16.8 27.0 30 25 60 28.3 30 26 61 108A00,108A00 23.0 27.7 40.6 45 37 60 41.9 45 39 61
HIGH
DD---STD
NONE --- --- 1.9 12.6 15 13 45 14.5 20 15 47
NONE --- --- 1.9 10.5 15 11 46 12.4 15 13 48
NONE --- --- 1.9 10.6 15 11 52 12.5 15 13 54
See “Legend and Notes for Table 5” on page 35.

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
NO M. V---Ph---HZ
ELEC. HTR P.E. NO C.O. or UNPWR C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
40.1 60 39 144 42.0 60 41 146 102A00 4.9/6.5 23.5/27.1 40.1/43.1 60/60 39/40 144/144 42.0/45.5 60/60 41/42 146/146 103B00 6.5/8.7 31.4/36.3 48.5/54.6 60/60 45/50 144/144 50.9/57.0 60/60 47/52 146/146 102A00,102A00 9.8/13.0 46.9/54.2 67.9/77.0 70/80 62/71 144/144 70.3/79.4 80/80 65/73 146/146 103B00,103B00 13.1/17.4 62.8/72.5 87.8/99.9 90/100 81/92 144/144 90.1/102.3 100/110 83/94 146/146 104B00,104B00 15.8/21.0 75.8/87.5 104.0/118.6 110/125 96/109 144/144 106.4/121.0 110/125 98/111 146/146
DD---STD
28.7 40 28 120 30.6 45 31 122 102A00 4.9/6.5 13.6/15.6 28.7/28.8 40/40 28/28 120/120 30.6/31.1 45/45 31/31 122/122 104B00 7.9/10.5 21.9/25.3 36.6/40.9 40/45 34/38 120/120 39.0/43.3 45/45 36/40 1/22122 105A00 12.0/16.0 33.4/38.5 51.0/57.4 60/60 47/53 120/120 53.4/59.8 60/60 49/55 122/122 104B00,104B00 15.8/21.0 43.8/50.5 64.0/72.4 70/80 59/67 120/120 66.4/74.8 70/80 61/69 122/122 104B00,105A00 19.9/26.5 55.2/63.8 78.3/89.0 80/90 72/82 120/120 80.6/91.4 90/100 74/84 122/122
DD---STD
26.5 40 26 143 28.4 40 28 145 102A00 4.9/6.5 13.6/15.6 26.5/26.5 40/40 26/26 143/143 28.4/28.4 40/40 28/28 145/145 104B00 7.9/10.5 21.9/25.3 33.9/38.1 40/40 31/35 143/143 36.3/40.5 40/45 33/37 145/145 105A00 12.0/16.0 33.4/38.5 48.3/54.6 50/60 44/50 143/143 50.6/57.0 60/60 47/52 145/145 104B00,104B00 15.8/21.0 43.8/50.5 61.3/69.6 70/70 56/64 143/143 63.6/72.0 70/80 59/66 145/145 104B00,105A00 19.9/26.5 55.2/63.8 75.5/86.3 80/90 69/79 143/143 77.9/88.6 80/90 72/82 145/145
MED
28.8 40 29 169 30.7 45 31 171 102A00 4.9/6.5 13.6/15.6 28.8/28.9 40/40 29/29 169/169 30.7/31.3 45/45 31/31 171/171 104B00 7.9/10.5 21.9/25.3 36.8/41.0 40/45 34/38 169/169 39.1/43.4 45/45 36/40 171/171 105A00 12.0/16.0 33.4/38.5 51.1/57.5 60/60 47/53 169/169 53.5/59.9 60/60 49/55 171/171 104B00,104B00 15.8/21.0 43.8/50.5 64.1/72.5 70/80 59/67 169/169 66.5/74.9 70/80 61/69 171/171 104B00,104A00 19.9/26.5 55.2/63.8 78.4/89.1 80/90 72/82 169/169 80.8/91.5 90/100 74/84 171/171
HIGH
13.7 20 14 58 14.7 20 15 59 106A00 6.0 7.2 14.0 20 14 58 15.3 20 15 59 108A00 11.5 13.8 22.3 25 20 58 23.5 25 22 59 109A00 14.0 16.8 26.0 30 24 58 27.3 30 25 59 108A00,108A00 23.0 27.7 39.6 40 36 58 40.9 45 38 59 108A00,109A00 25.5 30.7 43.4 45 40 58 44.6 45 41 59
DD---STD
12.3 15 12 69 13.3 20 13 70 106A00 6.0 7.2 12.3 15 12 69 13.5 20 13 70 108A00 11.5 13.8 20.5 25 19 69 21.8 25 20 70 109A00 14.0 16.8 24.3 25 22 69 25.5 30 23 70 108A00,108A00 23.0 27.7 37.9 40 35 69 39.1 40 36 70 108A00,109A00 25.5 30.7 41.6 45 38 69 42.9 45 39 70
MED
13.1 20 13 82 14.1 20 14 83 016A00 6.0 7.2 13.3 20 13 82 14.5 20 14 83 108A00 11.5 13.8 21.5 25 20 82 22.8 25 21 83 109A00 14.0 16.8 25.3 30 23 82 26.5 30 24 83 108A00,108A00 23.0 27.7 38.9 40 36 82 40.1 45 37 83 108A00,109A00 25.5 30.7 42.6 45 39 82 43.9 45 40 83
HIGH
DD---STD
NONE --- --- 1.9 11.3 15 12 46 13.2 15 14 48
NONE --- --- 1.9 9.3 15 9 53 11.2 15 11 55
NONE --- --- 1.9 10.1 15 10 64 12.0 15 12 66
See “Legend and Notes for Table 5” on page 35.

Table 5 Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
NO M. V---Ph---HZ
ELEC. HTR P.E. w/ PWRD C.O.
NO P.E. w/P.E. (pwrd fr/unit)
CRHEATER*** NOM (KW) FLA FLA
FUSE
FUSE
DISC. SIZE
DISC. SIZE
MCA
MCA
FLA LRA FLA LRA
44.9 60 44 149 46.8 60 47 151 102A00 4.9/6.5 23.5/27.1 44.9/49.1 60/60 44/45 149/149 47.0/51.5 60/60 47/47 151/151 103B00 6.5/8.7 31.4/36.3 54.5/60.6 60/70 50/56 149/149 56.9/63.0 60/70 52/58 151/151 102A00,102A00 9.8/13.0 46.9/54.2 73.9/83.0 80/90 68/76 149/149 76.3/85.4 80/90 70/79 151/151 103B00,103B00 13.1/17.4 62.8/72.5 93.8/105.9 100/110 86/97 149/149 96.1/108.3 100/110 88/100 151/151 104B00,104B00 15.8/21.0 75.8/87.5 110.0/124.6 125/125 101/115 149/149 112.4/127.0 125/150 103/117 151/151
DD---STD
33.5 45 34 125 35.4 50 36 127 102A00 4.9/6.5 13.6/15.6 33.5/34.8 45/45 34/34 125/125 35.4/37.1 50/50 36/36 127/127 104B00 7.9/10.5 21.9/25.3 42.6/46.9 45/50 39/43 125/125 45.0/49.3 50/50 41/45 127/127 105A00 12.0/16.0 33.4/38.5 57.0/63.4 60/70 52/58 125/125 59.4/65.8 60/70 55/60 127/127 104B00,104B00 15.8/21.0 43.8/50.5 70.0/78.4 80/80 64/72 125/125 72.4/80.8 80/90 67/74 127/127 104B00,105A00 19.9/26.5 55.2/63.8 84.3/95.0 90/100 78/87 125/125 86.6/97.4 90/100 80/90 127/127
DD---STD
31.3 45 31 148 33.2 45 34 150 102A00 4.9/6.5 13.6/15.6 31.3/32.0 45/45 31/31 148/148 33.2/34.4 45/45 34/34 150/150 104B00 7.9/10.5 21.9/25.3 39.9/44.1 45/45 37/41 148/148 42.3/46.5 45/50 39/43 150/150 105A00 12.0/16.0 33.4/38.5 54.3/60.6 60/70 50/56 148/148 56.6/63.0 60/70 52/58 150/150 104B00,104B00 15.8/21.0 43.8/50.5 67.3/75.6 70/80 62/70 148/148 69.6/78.0 70/80 64/72 150/150 104B00,105A00 19.9/26.5 55.2/63.8 81.5/92.3 90/100 75/85 148/148 83.9/94.6 90/100 77/87 150/150
MED
33.6 45 34 174 35.5 50 36 176 102A00 4.9/6.5 13.6/15.6 33.6/34.9 45/45 34/34 174/174 35.5/37.3 50/50 36/36 176/176 104B00 7.9/10.5 21.9/25.3 42.8/47.0 45/50 39/43 174/174 45.1/49.4 50/50 42/45 176/176 105A00 12.0/16.0 33.4/38.5 57.1/63.5 60/70 53/58 174/174 59.5/65.9 60/70 55/61 176/176 104B00,104B00 15.8/21.0 43.8/50.5 70.1/78.5 80/80 65/72 174/174 72.5/80.9 80/90 67/74 176/176 104B00,104A00 19.9/26.5 55.2/63.8 84.4/95.1 90/100 78/88 174/174 86.8/97.5 90/100 80/90 176/176
HIGH
15.9 20 16 60 16.9 20 17 61 106A00 6.0 7.2 16.8 20 16 60 18.0 20 17 61 108A00 11.5 13.8 25.0 25 23 60 26.3 30 24 61 109A00 14.0 16.8 28.8 30 26 60 30.0 30 28 61 108A00,108A00 23.0 27.7 42.4 45 39 60 43.6 45 40 61 108A00,109A00 25.5 30.7 46.1 50 42 60 47.4 50 44 61
DD---STD
14.5 20 15 71 15.5 20 16 72 106A00 6.0 7.2 15.0 20 15 71 16.3 20 16 72 108A00 11.5 13.8 23.3 25 21 71 24.5 25 23 72 109A00 14.0 16.8 27.0 30 25 71 28.3 30 26 72 108A00,108A00 23.0 27.7 40.6 45 37 71 41.9 45 39 72 108A00,109A00 25.5 30.7 44.4 45 41 71 45.6 50 42 72
MED
15.3 20 16 84 16.3 20 17 85 016A00 6.0 7.2 16.0 20 16 84 17.3 20 17 85 108A00 11.5 13.8 24.3 25 22 84 25.5 30 23 85 109A00 14.0 16.8 28.0 30 26 84 29.3 30 27 85 108A00,108A00 23.0 27.7 41.6 45 38 84 42.9 45 39 85 108A00,109A00 25.5 30.7 45.4 50 42 84 46.6 50 43 85
HIGH
DD---STD
NONE --- --- 1.9 13.0 15 13 48 14.9 20 16 50
NONE --- --- 1.9 11.0 15 11 55 12.9 15 13 57
NONE --- --- 1.9 11.8 15 12 66 13.7 15 14 68
See “Legend and Notes for Table 5” on page 35.

Legend and Notes for Table 5
LEGEND: BRKR --- Circuit breaker CO --- Convenient outlet DD --- Direct drive indoor fan motor DISC --- Disconnect FLA --- Full load amps IFM --- Indoor fan motor LRA --- Locked rotor amps MCA --- Minimum circuit amps PE --- Power exhaust PWRD CO --- Powered convenient outlet UNPWR CO --- Unpowered convenient outlet NOTES:
AB = 224 v BC = 231 v AC = 226 v
(224 + 231 + 226)
Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v Maximum deviation is 4 v (BC) 231 – 227 = 4 v Determine percent of voltage imbalance
% Voltage Imbalance = 100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x

C09302 Fig. 54 - EconoMi$er IV Wiring
EconoMi$er IV Occupancy Switch —
Refer to Fig. 56 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Controls Connections Board.
Smoke detector(s) will be connected at the Controls Connections Board, at terminals marked “Smoke Shutdown”. Cut jumper JMP 3 when ready to energize unit.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY. Cut jumper JMP 2 to complete the installation.

Available accessories include:
Curb Thru-base connection kit (must be installed before unit is set on curb) Electric heaters and single-poing connection kits Manual outside air damper Two-Position motorized outside air damper EconoMi$er IV (with control) EconoMi$er2 (without control/for external signal) Power Exhaust Differential dry-bulb sensor (EconoMi$er IV) Outdoor enthalpy sensor Differential enthalpy sensor CO2 sensor Smoke detector (Return Air and/or Supply Air) Louvered hail guard Hood-type hail guard Phase monitor control
Refer to separate installation instructions for information on installing these accessories.
This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed Pre-Start and Start-Up instructions.
Copyright 2010 Bryant Heating & Cooling Sysemts D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.