Table of Contents 80 sections Models 542J, 548F, 549B · COMMERCIAL SINGLE PACKAGE ROOFTOP STANDARD AND HIGH EFFICIENCY HEAT PUMP UNITS · Sizes 036-180 Dura Pac and Dura Pac Plus · 3 to 15 Tons · … ShowHide
Models 542J, 548F, 549Bp.1COMMERCIAL SINGLE PACKAGE ROOFTOP STANDARD AND HIGH EFFICIENCY HEAT PUMP UNITSp.1Sizes 036-180 Dura Pac and Dura Pac Plusp.13 to 15 Tonsp.1548F036-072 549B036-072 548F090-120 549B090-120p.1542J150,180p.1FEATURES/BENEFITSp.1Form No. PDS 548F.36.4p.1TABLE OF CONTENTSp.2OPTIONS AND ACCESSORIESp.4OPTIONS AND ACCESSORIES (cont)p.5MOTORMASTER IV CONTROLp.5(OUTDOOR FAN CYCLINGp.5MOTORMASTER I, III CONTROL (OUTDOOR FAN SPEED MODULATOR)p.5MOTORMASTER II CONTROL (OUTDOOR FAN CYCLING)p.5EMERGENCY HEAT CONTROL PACKAGEp.5BAROMETRIC RELIEF/POWER EXHAUSTp.5(150,180 shown)p.5OUTDOOR COIL PROTECTION APPLICATIONSp.6ELECTRIC HEATERSp.6ECONOMI$ER (036-120 shown)p.6ECONOMI$ER PLUGp.6CONTROLLERp.6GEAR-DRIVEN DAMPERp.6ACTUATORp.6OUTDOOR AIR TEMPERATURE SENSORp.6BAROMETRIC RELIEF DAMPERSp.6ECONOMI$ER MICROPROCESSOR CONTROLLERp.6ECONOMI$ER STEPPER MOTORp.64-20 mA ECONOMI$ER ACTUATOR (use for EMS Interface)p.6AD-DME1711-1p.6OFF 500 1000p.60 A Bp.6CONFIGp.6C Dp.65P CO SPp.6(FFM)p.62 MIN POS (%) MECH C Op.6LOCKOUTp.6L STATUSp.6ECONp.6UNIT-MOUNTED DISCONNECT (sizes 036-120) UNIT-MOUNTED DISCONNECT (sizes 150,180)p.7CONVENIENCE OUTLETp.7GLYCOL COIL (150,180 only)p.7FILTER HINGED PANEL OPTION (549B036-120) INDOOR-FAN HINGED PANEL OPTION (549B036-120)p.9CONTROLSp.10CONTROLS (cont)p.11Typical Smoke Control/Fire Shutdown Wiring — 542J150,180p.13APPLICATION DATAp.14REQUIREDp.14UNIT 549B UNIT VOLTAGEp.14HEATERp.14UNIT CONFIGURATIONp.14MINIMUMp.14CFMp.14UNIT 548F UNIT VOLTAGEp.14APPLICATION DATA (cont)p.15BAFFLEp.15NOTE:p.15Concentric Duct Distribution —p.15Concentric Duct Details —p.15TYPICAL PIPING AND WIRINGp.16TYPICAL PIPING AND WIRING (cont)p.17MODEL NUMBER NOMENCLATURE — 548F UNITSp.18(ODS Model Number)p.18548F E X 090 000 AAp.18ARI* CAPACITY RATINGSp.18548F036-060p.18UNIT 548F NOMINALp.18TONSp.18548F072-120p.18COOLING HEATINGp.18HEATINGp.18PHYSICAL DATAp.19548F036-072p.19FREEZE-PROTECTION THERMOSTAT (F)p.19PHYSICAL DATA (cont)p.20548F090-120p.20ACCESSORY DIMENSIONSp.23CONNECTORp.23
Page 1 of the Bryant 549B user manual — Form No. PDS 548F.36.4
Page 1 · click to enlarge
Page 1

Models 542J, 548F, 549B

COMMERCIAL SINGLE PACKAGE ROOFTOP STANDARD AND HIGH EFFICIENCY HEAT PUMP UNITS

Sizes 036-180 Dura Pac and Dura Pac Plus

3 to 15 Tons

548F036-072 549B036-072 548F090-120 549B090-120

542J150,180

  • Standard-efficiency (548F), and high-efficiency (542J and 549B) heat pump units with:
  • Pre-painted galvanized steel cabinet for long life and quality appearance
  • Commercial strength base rails with built-in rigging capability
  • Convertible design for vertical or horizontal supply/return
  • Non-corrosive, sloped condensate drain pan, meets ASHRAE 62 (IAQ)
  • Two-inch return-air filters
  • A wide assortment of factory-installed options available, including high static drives that provide additional performance range
  • Optional gear driven EconoMi$er with CO 2 ventilation control (2 to 10 vac actuator)
  • Optional gear-driven EconoMi$er with 4 to 20 mA actuator for EMS controls
  • State-of-the-art defrost system
  • Dependable 4-way valve operation Heat Options
  • Field-installed electric heat available
  • Glycol hydronic coils

FEATURES/BENEFITS

Every compact one-piece unit arrives fully assembled, charged, tested, and ready to run. QUIET, EFFICIENT OPERATION AND DEPENDABLE PER- FORMANCE — Compressors have vibration isolators for quiet operation. Efficient fan and motor design permits operation at low sound levels. Unit sizes 090-180 offer lower utility costs through part-load operation using 2 stages of cooling. Quiet and efficient operation is provided by belt-driven indoor fans (standard on all units over 5 tons). The belt-driven indoor fan is equipped with variable-pitch pulleys which allow adjust- ment within the rpm ranges of the factory-supplied pulleys. Increased operating efficiency is achieved through computer- designed coils featuring staggered internally enhanced copper tubes. Fins are ripple-edged for strength, lanced, and double waved for higher heat transfer.

Form No. PDS 548F.36.4

Page 2 of the Bryant 549B user manual — Table of Contents
Page 2 · Contents
Contents

Contents

Models 542J, 548F, 549Bp.1COMMERCIAL SINGLE PACKAGE ROOFTOP STANDARD AND HIGH EFFICIENCY HEAT PUMP UNITSp.1Sizes 036-180 Dura Pac and Dura Pac Plusp.13 to 15 Tonsp.1548F036-072 549B036-072 548F090-120 549B090-120p.1542J150,180p.1FEATURES/BENEFITSp.1Form No. PDS 548F.36.4p.1TABLE OF CONTENTSp.2OPTIONS AND ACCESSORIESp.4OPTIONS AND ACCESSORIES (cont)p.5MOTORMASTER IV CONTROLp.5(OUTDOOR FAN CYCLINGp.5MOTORMASTER I, III CONTROL (OUTDOOR FAN SPEED MODULATOR)p.5MOTORMASTER II CONTROL (OUTDOOR FAN CYCLING)p.5EMERGENCY HEAT CONTROL PACKAGEp.5BAROMETRIC RELIEF/POWER EXHAUSTp.5(150,180 shown)p.5OUTDOOR COIL PROTECTION APPLICATIONSp.6ELECTRIC HEATERSp.6ECONOMI$ER (036-120 shown)p.6ECONOMI$ER PLUGp.6CONTROLLERp.6GEAR-DRIVEN DAMPERp.6ACTUATORp.6OUTDOOR AIR TEMPERATURE SENSORp.6BAROMETRIC RELIEF DAMPERSp.6ECONOMI$ER MICROPROCESSOR CONTROLLERp.6ECONOMI$ER STEPPER MOTORp.64-20 mA ECONOMI$ER ACTUATOR (use for EMS Interface)p.6AD-DME1711-1p.6OFF 500 1000p.60 A Bp.6CONFIGp.6C Dp.65P CO SPp.6(FFM)p.62 MIN POS (%) MECH C Op.6LOCKOUTp.6L STATUSp.6ECONp.6UNIT-MOUNTED DISCONNECT (sizes 036-120) UNIT-MOUNTED DISCONNECT (sizes 150,180)p.7CONVENIENCE OUTLETp.7GLYCOL COIL (150,180 only)p.7FILTER HINGED PANEL OPTION (549B036-120) INDOOR-FAN HINGED PANEL OPTION (549B036-120)p.9CONTROLSp.10CONTROLS (cont)p.11Typical Smoke Control/Fire Shutdown Wiring — 542J150,180p.13APPLICATION DATAp.14REQUIREDp.14UNIT 549B UNIT VOLTAGEp.14HEATERp.14UNIT CONFIGURATIONp.14MINIMUMp.14CFMp.14UNIT 548F UNIT VOLTAGEp.14APPLICATION DATA (cont)p.15BAFFLEp.15NOTE:p.15Concentric Duct Distribution —p.15Concentric Duct Details —p.15TYPICAL PIPING AND WIRINGp.16TYPICAL PIPING AND WIRING (cont)p.17MODEL NUMBER NOMENCLATURE — 548F UNITSp.18(ODS Model Number)p.18548F E X 090 000 AAp.18ARI* CAPACITY RATINGSp.18548F036-060p.18UNIT 548F NOMINALp.18TONSp.18548F072-120p.18COOLING HEATINGp.18HEATINGp.18PHYSICAL DATAp.19548F036-072p.19FREEZE-PROTECTION THERMOSTAT (F)p.19PHYSICAL DATA (cont)p.20548F090-120p.20ACCESSORY DIMENSIONSp.23CONNECTORp.23
Page 4 of the Bryant 549B user manual — OPTIONS AND ACCESSORIES
Page 4 · click to enlarge
Page 4

OPTIONS AND ACCESSORIES

ITEMOPTION*ACCESSORY† 100% Open Two-Position Damper (036-120)X 25% Open Two-Position DamperX Alternate Motors and Drives (548F036-120)X Barometric Relief Damper (150 and 180 only, not for use with horizontal roof curb)X Convenience Outlet 115VX Copper fins indoor and outdoor coilX Copper fins outdoor coilX Double Wall in unit airstream (150,180)X** E-Coat outdoor coil (Aluminum Fin)X E-Coat outdoor coil (Copper Fin)X EconoMi$erXX EconoMi$er with Power ExhaustX Electric HeatX Electronic Programmable ThermostatX Emergency Heat PackageX Enthalpy or differential enthalpy sensorX Fan/Filter StatusX High-Static Motor and Drive (548F036-120)X Hinged Access Panels (549B036-120 and 542J150,180)X Horizontal Adapter Curb (150,180)X Hot Gas Bypass (150,180)X** Hydronic Glycol Coil (150,180)X Johnson METASYS ControlX** Manual Outdoor-Air Damper (25% Open) (036-120)X Manual Outdoor-Air Damper (50% Open) (036-120)X Motormaster® Head Pressure Control (Cycle Control or Fan Speed Modulation)X Novar ControlX** Outdoor Air Enthalpy Sensor (EconoMi$er Only)X Outdoor Coil Grille (036-120)X Outdoor Coil Hail Guard AssemblyX Power Exhaust (no barometric relief on sizes 150,180)X Power Exhaust Transformer for 460 or 575 v (036-120)X Power Exhaust with Barometric Relief (036-120)X Precoat Al. Fins on outdoor coilX Return Air Enthalpy Sensor (EconoMi$er Only)X Return Air Temperature Sensor (EconoMi$er Only)X Roof Curbs (Vertical and Horizontal Discharge)X Smoke DetectorsX** Stainless Steel Condensate Pan (150,180)X** Thermostats and SubbasesX Thru-the-Bottom Utility ConnectionsX Time Guard® II Control CircuitX Unit-Mounted Non-Fused DisconnectX UVC LampsX**X Winter Start Time Delay (150,180)X

*Factory-installed. †Field-installed. **Special order/DEC only. NOTES:

1. Refer to unit price pages or contact your local representative for accessory/and option package information. 2. Some options may increase product lead times.
Page 5 of the Bryant 549B user manual — MOTORMASTER IV CONTROL
Page 5 · click to enlarge
Page 5

OPTIONS AND ACCESSORIES (cont)

LOW AMBIENT CONTROLS Standard units are designed to operate in cooling at outdoor temperatures down to 25 F (for size 036-120 units) and 40 F (for size 150,180 units). With accessory Motormaster control (outdoor-fan cycling) units can operate at outdoor temperatures down to –20 F. The head pressure controls, which mount in the outdoor section, control the outdoor-fan motor to maintain correct condensing temperature.

MOTORMASTER IV CONTROL

(OUTDOOR FAN CYCLING

MOTORMASTER I, III CONTROL (OUTDOOR FAN SPEED MODULATOR)

MOTORMASTER II CONTROL (OUTDOOR FAN CYCLING)

EMERGENCY HEAT CONTROL PACKAGE

BAROMETRIC RELIEF/POWER EXHAUST

(150,180 shown)

When used with accessory/optional economizer, the barometric relief or power exhaust accessory helps to relieve building overpressurization. NOTE: This is not available with horizontal supply adapter curb.

Emergency heat control package allows emergency operation of electric heat and fans by bypassing compressor circuits and out- door thermostats.

Page 6 of the Bryant 549B user manual — C D
Page 6 · click to enlarge
Page 6

OPTIONS AND ACCESSORIES (cont)

DURA-SHIELD OUTDOOR COIL OPTIONS Outdoor coil options are available to match coil construction to site conditions for the best corrosion durability. Pre-coated coils provide protections in mild coastal environments. All copper coils are best suited for moderate coastal applications, while E-coated coils provide superior protection in severe coastal and industrial applications.

OUTDOOR COIL PROTECTION APPLICATIONS

DESCRIPTION ura-Shield Option)ENVIRONMENT Standard, Mild Moderate Severe Combined Coastal Industrial Non-Corrosive Coastal Coastal Coastal and Industrial Mild CoastalModerate CoastalSevere CoastalC Industrialombined Coastal and Industrial Standard, Al/CuX Pre-Coated Al/CuX Cu/CuX E-Coated Al/CuX E-Coated Cu/CuXX

Al/Cu — Aluminum Fin with Copper Tube Coil Cu/Cu — Copper Fin with Copper Tube Coil Dura-Shield — Family of Coil Protection Options E-Coated — Extremely flexible and durable epoxy coating uniformly applied to the coil surfaces. Pre-Coated — Epoxy Coating Applied to Fin Stock Material

ELECTRIC HEATERS

ECONOMI$ER (036-120 shown)

ECONOMI$ER PLUG

CONTROLLER

GEAR-DRIVEN DAMPER

ACTUATOR

OUTDOOR AIR TEMPERATURE SENSOR

BAROMETRIC RELIEF DAMPERS

Electric heaters (and single point kits) are avail- able in a wide range of capacities for factory or field installation. Factory-installed EconoMi$er utilizes a microprocessor-based con- trol, gear drive damper system, low pressure drop characteristics, built-in spring return (for close upon power loss), and an integral barometric damper.

ECONOMI$ER MICROPROCESSOR CONTROLLER

ECONOMI$ER STEPPER MOTOR

4-20 mA ECONOMI$ER ACTUATOR (use for EMS Interface)

AD-DME1711-1

OFF 500 1000

10° 20°

0 A B

CONFIG

50° 60° 40°

C D

5P CO SP

(FFM)

2 MIN POS (%) MECH C O

LOCKOUT

L STATUS

ECON

Inputs for Dry Bulb, Enthalpy, Differential Tem- perature or Enthalpy, or Potentiometer

30° · 1400 1200 · 60 80 100

Page 7 of the Bryant 549B user manual — GLYCOL COIL (150,180 only)
Page 7 · click to enlarge
Page 7

OPTIONS AND ACCESSORIES (cont)

UNIT-MOUNTED DISCONNECT (sizes 036-120) UNIT-MOUNTED DISCONNECT (sizes 150,180)

Factory-installed, internally mounted, NEC (National Electrical Code) and UL (Underwriters’ Laboratories) approved non-fused switch provides unit power shutoff with disconnect lockout protec- tion capability. The switch is accessible from outside the unit.

CONVENIENCE OUTLET

Bryant 549B — CONVENIENCE OUTLET diagram (page 7)
Fig. 1

Factory-installed, internally mounted and externally accessible 115-v female receptacle. Includes 15-amp GFI (Ground Fault Interrupter) receptacle with independent fuse protection. Voltage required to operate convenience outlet is provided by a field- installed transformer (150,180 units).

GLYCOL COIL (150,180 only)

Factory-installed, internally-mounted, NEC (National Elec- trical Code) and UL (Underwriters’ Laboratories) approved non-fused switch provides unit power shutoff with discon- nect lockout protection capability. The control box access door is interlocked with the non-fused disconnect. The non- fused disconnect must be in the OFF position to open this door. The switch is accessible from outside the unit.

Glycol coil is intended for add-on type applications or new work where a boiler system is available. Glycol coil and electric heat can- not be installed together.

Page 8 of the Bryant 549B user manual — OPTIONS AND ACCESSORIES (cont)
Page 8 · click to enlarge
Page 8

OPTIONS AND ACCESSORIES (cont)

Bryant 549B — OPTIONS AND ACCESSORIES (cont) diagram (page 8)
Fig. 2 · OPTIONS AND ACCESSORIES (cont)

Outdoor coil hail guard accessory (field installed) protects coils against damage from hail and other flying debris.

Coil guard grille protects coils against large objects and vandalism.

Designed specifically for use with Bryant commercial systems, this Bryant programmable thermostat features LED occupied/unoccupied displays and setback mode which can override continuous fan operation.

Page 9 of the Bryant 549B user manual — FILTER HINGED PANEL OPTION (549B036-120) INDOOR-FAN HINGED PANEL OPTION (549B036-120)
Page 9 · click to enlarge
Page 9

OPTIONS AND ACCESSORIES (cont)

Bryant 549B — OPTIONS AND ACCESSORIES (cont) diagram (page 9)
Fig. 3 · OPTIONS AND ACCESSORIES (cont)

FILTER HINGED PANEL OPTION (549B036-120) INDOOR-FAN HINGED PANEL OPTION (549B036-120)

This is included as a factory-installed option. It per- mits quick and simple indoor-fan access.

This is included as a factory-installed option. It permits tool-less filter access.

Page 10 of the Bryant 549B user manual — CONTROLS
Page 10 · click to enlarge
Page 10

CONTROLS

OPERATING SEQUENCE — 548F036-120 AND 549B036-120 Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS1) and compres- sor contactor no. 1 (C1) are energized and indoor-fan motor, compressor no. 1, and outdoor fans start. The outdoor-fan motor(s) run continuously while unit is cooling. On 548F090- 120 units, if the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) and revers- ing valve solenoid (RVS2) are energized and compressor no. 2 starts. Heating, Units Without Economizer (548F036-072 and 549B036-072) — Set system switch at AUTO. or HEAT position. Set thermostat at desired temperature.

with mechanical cooling. This is accomplished by the strategies below. NOTE: Compressor has a 2-minute Minimum On, Minimum Off, and Interstage delay timer.

1. If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), the compressor and OFM are ener- gized. The EconoMi$er damper is maintained at its current position. 2. If Y1 is energized for more than 20 minutes, and Y2 is not energized (whether or not a 2-stage thermostat is used), the compressor and OFM are energized. The EconoMi$er damper is maintained at its current position. 3. If Y1 is energized, and the compressor is already energized (see Step 2) and the room thermostat calls for Y2, the com- pressor continues to operate. 4. If compressor is energized and the thermostat is satisfied, the compressor, the OFM, and IFM are deenergized and the EconoMi$er modulates closed. When the OAT is below the MECH CLG LOCKOUT set point, the compressors remain off. Cooling, Units With EconoMi$er (548F090-120 and 549B090,120) — When the outdoor-air temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan motor (IFM) is energized and the EconoMi$er damper modulates to mini- mum position. The compressor contactor is energized to start the compressor and outdoor-fan motor (OFM) and RVS1 (reversing valve solenoid). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized.

When the thermostat calls for heat, the IFC, outdoor-fan con- tactor (OFC), and compressor contactor are energized. The RVS is deenergized and switches position, and the indoor fan, outdoor fan, and compressor are energized.

If the thermostat calls for a second stage of heat, the heater contactor (HC) is energized and starts the electric heaters.

When the space temperature approaches the heating tem- perature set point, heating stages cycle off. The reversing valve solenoid is reenergized. Heating, Units Without Economizer (548F090-120 and 549B090,120) — Upon a request for heating from the space thermostat, terminal W1 will be energized with 24 v. The IFC, outdoor-fan contactor (OFC), C1, and C2 will be energized. The reversing valves switch position and the indoor fan, outdoor fan, compressor no. 1, and compressor no. 2 are energized.

If the space temperature continues to fall while W1 is ener- gized, W2 will be energized with 24 v, and the heater contac- tor(s) (HC) will be energized, which will energize the electric heater(s).

When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor-air dampers to maintain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position. If outdoor-air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below. NOTE: Compressors have a 2-minute Minimum On, Minimum Off, and Interstage delay timer.

When the space thermostat is satisfied, W2 will be deen- ergized first, and the electric heater(s) will be deenergized.

Upon a further rise in space temperature, W1 will be deener- gized, and the reversing valve solenoids (RVS1 and RVS2) will be energized. Cooling, Units With EconoMi$er (548F036-072 and 549B036- 072) — When the outdoor-air temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan motor (IFM) is energized and the EconoMi$er damper modulates to minimum position. The compressor contactor is energized to start the compressor and outdoor-fan motor (OFM) and RVS1 (reversing valve sole- noid). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized.

When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor-air dampers to maintain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position. If outdoor-air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling

1. If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), compressor no. 1 and OFM are ener- gized. The EconoMi$er damper is maintained at its current position. 2. If Y1 is energized for more than 20 minutes, and Y2 is not energized (whether or not a 2-stage thermostat is used), compressor no. 1 and OFM are energized. The EconoMi$er damper is maintained at its current position. 3. If Y1 is energized, and compressor no. 1 is already ener- gized (see Step 2) and the room thermostat calls for Y2, compressor no. 1 continues to operate. If Y2 remains energized for more than 20 minutes, compressor no. 2 is energized.

Page 11 of the Bryant 549B user manual — CONTROLS (cont)
Page 11 · click to enlarge
Page 11

CONTROLS (cont)

During the Defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between Heating and Cooling modes until the Defrost mode is complete.

4. If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressor no. 1 and 2 are deener- gized. Reasserting Y2 will start compressor no. 1 and (after a 20-minute interstage delay) compressor 2. 5. If compressor no. 1 is energized and the thermostat is satis- fied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed. Heating, Units With Economizer — Upon a call for heat through W1, the IFC energizes to start the evaporator fan and the economizer damper blade opens to the minimum position. If the accessory two-position damper is used, the outdoor-air damper opens to the minimum position whenever the evapora- tor fan runs. If unit is equipped with 2 stages of heat, when addi- tional heat is needed a call is made through W2.

At the end of the defrost cycle, the electric heaters (if installed) will be deenergized; the reversing valves switch and the outdoor-fan motor will be energized. The unit will now oper- ate in the Heating mode.

If the space thermostat is satisfied during a defrost cycle, the unit will continue in the Defrost mode until the time or tempera- ture constraints are satisfied. SEQUENCE OF OPERATION — 542J150,180 Cooling, Units Without Economizer — With unit main power on, set thermostat to COOL position and desired room temper- ature. Set fan switch at AUTO. (on demand) or ON (continuous) position.

On a rise in room temperature, cooling contactor no. 1 in the thermostat closes. The indoor and outdoor fan motors start. If the 5-minute compressor time-delay (CTD) on the defrost board (DB) is satisfied, then compressor no. 1 (542J180) or unloaded compressor (542J150) contactor is energized and compressor will start. Compressor cycles on demand of the thermostat to satisfy room conditions. Each time the cooling contactor no. 1 opens, the CTD starts the 5-minute delay.

As space temperature approaches the heating temperature set point, heating stages cycle off. Economizer or two-position damper returns to fully closed position. Defrost (548F036-072 and 549B036-072) — As frost builds up on the outdoor coil, the coil temperature drops below 28 F. When this outdoor-coil temperature drop is sensed by the defrost thermostat (DFT) and the defrost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), the unit oper- ates in a defrost cycle controlled by the defrost timer and ther- mostat. During this cycle, the reversing valve solenoid (RVS) is energized and the outdoor fan shuts off. The electric heaters (if installed) will be energized.

On 542J180 units, with an additional rise in room tempera- ture, cooling contactor no. 2 in the thermostat closes, energiz- ing compressor contactor no. 2. Compressor no. 2 starts and cycles on demand of the thermostat to satisfy the occupied space demands.

The unit continues to defrost until the coil temperature as measured by DFT reaches 65 F, or the duration of defrost cycle completes a 10-minute period.

On 542J150 units, compressor runs fully loaded on a call for second-stage cooling. Cooling, Units With EconoMi$er — Upon a call for cooling, when outdoor ambient temperature is above the temperature control setting, the indoor and outdoor fans and compressor(s) energize. The economizer damper moves to vent position.

At the end of the defrost cycle, the electric heaters (if installed) and the reversing valve will be deenergized, and the outdoor-fan motor will be energized. The unit will now operate in the Heating mode.

Upon a first-stage call for cooling, when outdoor ambient tem- perature is below the temperature control setting, the indoor fan starts and economizer damper modulates to maintain mixed-air temperature. The compressor(s) remains off.

If the thermostat is satisfied during a defrost cycle, the unit will continue in the Defrost mode until the time or temperature constraints are satisfied. Defrost (548F090-120 and 549B090,120) — When the tem- perature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fan. The electric heaters (if installed) will be energized.

Upon a second-stage call for cooling, compressor no. 1 (542J180) or loaded compressor (542J150) is energized and mechanical cooling is integrated with economizer cooling. Com- pressor no. 2 (542J180) is locked out. If the air temperature is below 50 F, a cooling lockout switch prevents the compressor(s) from running.

When supply-air temperature drops below a fixed set point, the economizer damper modulates to maintain the temperature at the fixed set point.

The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F, or the duration of defrost cycle completes a 10-minute period.

A freeze protection thermostat (FPT) is located on the indoor coil. It detects frost build-up and turns off the compressor(s), allowing the coil to clear. Once frost has melted, the compres- sor can be reenergized.

Page 12 of the Bryant 549B user manual — CONTROLS (cont)
Page 12 · click to enlarge
Page 12

CONTROLS (cont)

Heating, Units Without Economizer — With unit main power on, set thermostat at HEAT position and desired room tempera- ture. Set fan switch at AUTO. (on demand) or ON (continuous) position.

During the defrost mode, when a circuit defrosts, RVS will oscil- late between heating and cooling modes until defrost mode is complete. This will prevent the head pressure from getting too high. At the end of the defrost cycle, the electric heaters (if applica- ble) will be deenergized, the reversing valve solenoids will be energized, and the outdoor fans will start. Automatic Changeover — When the system selection switch is set at AUTO. position, unit automatically changes from heat- ing operation to cooling operation when the temperature of the conditioned space rises to the cooling level setting. When the temperature of the conditioned space falls to the heating level setting, unit automatically changes from cooling to heating operation (with a 3 F deadband in between). Continuous Air Circulation — Turn unit power on. Set system control at OFF position. Set fan switch at ON position. The indoor-fan contactor is energized through the thermostat switch and the indoor fan runs continuously. Cycle-LOC™ Protection — If unit operation is interrupted by an open high-pressure switch, low-pressure switch, indoor coil freezestat, or by compressor internal line-break device (over- current or overtemperature), and compressor is calling for either cooling or heating, Cycle-LOC protection device simultaneously locks out unit and lights a warning light on the thermostat. Restart the unit by manually turning thermostat to OFF and then to ON position. If any of the protective devices opens again, the unit continues to lock out until corrective action is taken. NOTE: If the unit fails to operate due to compressor over- current condition, restart by manually resetting circuit breakers at the unit. Restart cannot be accomplished at the room thermostat. Emergency Heat — If compressor is inoperative due to a tripped safety device (high or low pressure, indoor coil freez- estat, overcurrent, or overtemperature), the Cycle-LOC device locks out the compressor and lights a warning light on the room thermostat. When the switch is on (thermostat is set to the EM HT position), compressor circuit and outdoor thermostats are bypassed, and the second stage of thermostat energizes the indoor blower and the electric resistance heaters.

On a drop in room temperature, heating contactor no. 1 in the thermostat closes, energizing heat relay (HR), reversing valve relay (RVR), reversing valve solenoids (RVS1 and RVS2) and compressor no. 2 contactor. Compressor (542J150) or com- pressor no. 2 (542J180) and indoor and outdoor fan motors start. If the 5-minute CTD on the DB is satisfied, then compres- sor no. 1 contactor is energized and compressor no. 1 will start.

On units equipped with electric heat, when additional heat is needed, heating contactor no. 2 in the thermostat closes, ener- gizing W2. Heating, Units With EconoMi$er — With unit main power on, set thermostat at HEAT position and desired room temperature. Set fan switch at AUTO. (on demand) or ON (continuous) position.

On a drop in room temperature, heating contactor no. 1 in the thermostat closes, energizing heat relay (HR), reversing valve relay (RVR), reversing valve solenoids (RVS1 and RVS2) and compressor no. 2 contactor. Compressor no. 2 (542J180) and indoor and outdoor fan motors start. If the 5-minute CTD on the DB is satisfied, then compressor (542J150) or compressor no. 1 (542J180) contactor is energized and compressor (542J150) or compressor no. 1 (542J180) will start. The outdoor-air damper stays at vent position while the indoor fan is operating.

On units equipped with electric heat, when additional heat is needed, heating contactor no. 2 in the thermostat closes, ener- gizing W2. Defrost Cycle — When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT1 or DFT2), the defrost timer starts. At the end of a timed period (field set at 30, 50, or 90 minutes), the defrost cycle will begin. The defrost board energizes terminals O and W2, energizes the defrost relay (DR), deenergizes the reversing valve solenoids (RVS1 and RVS2), and energizes the electric heat. The outdoor- fan motor will stop. The unit continues to defrost either until the coil temperature as measured by DFT1 or DFT2 reaches 65 F, or until unit com- pletes a 10-minute defrost cycle.

Page 13 of the Bryant 549B user manual — Typical Smoke Control/Fire Shutdown Wiring — 542J150,180
Page 13 · click to enlarge
Page 13

CONTROLS (cont)

Bryant 549B — CONTROLS (cont) diagram (page 13)
Fig. 4 · CONTROLS (cont)

See Legend on page 14. *Included in power exhaust accessory.

OPERATING MODES BP — Building Pressurization: Indoor fan on, economizer energized to fully open position, power exhaust disabled. E — Evacuation: Indoor fan off, economizer energized to fully open position, power exhaust on (open). SD — Complete Unit Shutdown: Breaks 24-v power to the thermostat. SP — Smoke Purge: Indoor fan on, economizer energized to fully open position, power exhaust on.

Typical Smoke Control/Fire Shutdown Wiring — 542J150,180

Field Wiring · Field-Supplied Switch

Page 14 of the Bryant 549B user manual — UNIT 548F UNIT VOLTAGE
Page 14 · click to enlarge
Page 14

CONTROLS (cont)

AHA — Adjustable Heat Anticipator CB — Circuit Breaker CC — Cooling Compensator CLO — Compressor Lockout DAT — Discharge Air Thermistor DM — Damper Motor EAS — Economizer Actuator Auxiliary Switch EMC — Economizer Motor Contactor FU — Fuse IFC — Indoor-Fan Contactor

IFR — Indoor-Fan Relay L — Light LLS — Liquid Line Solenoid OAT — Outdoor-Air Thermostat PL — Plug Assembly SR — Solenoid Relay TB — Terminal Block TC — Thermostat Cooling TH — Thermostat Heating TRAN — Transformer UR — Unloader Relay

Splice Factory Wiring Field Wiring Option/Accessory Wiring To Indicate Common Potential Only, Not To Represent Wiring

APPLICATION DATA

1. OUTDOOR INSTALLATION — Units approved for outdoor installation only. 2. DUCTWORK — Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, either attach ductwork to unit, or use field-supplied flanges attached to the horizontal discharge openings and attach all ductwork to flanges. 3. HORIZONTAL ECONOMI$ER — A field-installed acces- sory for horizontal discharge applications. Field-installed power exhaust accessory also available for vertical or hori- zontal EconoMi$er applications (036-120). 4. THRU-THE-BOTTOM POWER CONNECTIONS — For applications requiring thru-the-bottom connections, Bryant accessory thru-the-bottom package must be purchased to ensure proper connections (036-120). 5. THERMOSTAT — Use of 2-stage heating and cooling ther- mostat is recommended for all units. A 2-stage cooling ther- mostat is required on units with accessory economizer to provide integrated cooling. A two-stage thermostat is required for all 548F/549B090,120 and 542J150,180 units. 6. HEATING-TO-COOLING — All units are automatic changeover from heating to cooling when automatic changeover thermostat and subbase are used. 7. AIRFLOW — Units are draw-thru on cooling and blow-thru on heating. 8. MAXIMUM AIRFLOW — To minimize the possibility of con- densate blow-off from indoor coil, airflow through units should not exceed 500 cfm/ton. 9. MINIMUM AIRFLOW — For cooling, minimum airflow is 300 cfm/ton. For 548F units with electric heating, the required minimum cfm is 900 for 548F036; 1200 for 548F048; 1500 for 548F060; 1800 for 548F072; 2250 for 548F090; 2500 for 548F102; and 3000 for 548F120, with the following exceptions:

For 549B and 542J units with electric heating, the required minimum cfm is 900 for 549B036; 1200 for 549B048; 1500 for 549B060; 1700 for 549B072; 2250 for 549B090; 3000 for 549B120; 3900 for 542J150; and 4500 for 542J180, with the fol- lowing exceptions:

REQUIRED

UNIT 549B UNIT VOLTAGE

HEATER

UNIT CONFIGURATION

MINIMUM

CFM

208/230 50.0 Horizontal

460 50.0 Horizontal

10. MINIMUM AMBIENT COOLING OPERATING TEMPERA- TURE — The minimum temperature for standard units is 25 F (036-120) and 40 F (542J150,180). With accessory Motormaster® control, units can operate at outdoor temper- atures down to –20 F. 11. INTERNAL UNIT DESIGN — Due to Bryant’s internal unit design (draw-thru over the motor), air path, and specially designed motors, the full horsepower (maximum continuous bhp) listed in the Physical Data table and the notes following each Fan Performance table can be utilized with confidence. Using Bryant motors with the values listed in the Physical and Fan Performance Data tables will not result in nuisance tripping or premature motor failure. The unit warranty will not be affected.

UNIT 548F UNIT VOLTAGE

HEATER

UNIT CONFIGURATION

REQUIRED

MINIMUM

CFM

208/230 42.4 Horizontal 3200 208/230 50.0 Horizontal 3200

460 50.0 Horizontal

090-120 575 17.0 Horizontal

34.0 2350

Show 9 more labels / short text on this page
Terminal (Marked) · Terminal (Unmarked) · Terminal Block · kW · or Vertical · or Vertical · kW · or Vertical · or Vertical
Page 15 of the Bryant 549B user manual — Concentric Duct Distribution —
Page 15 · click to enlarge
Page 15

APPLICATION DATA (cont)

Bryant 549B — APPLICATION DATA (cont) diagram (page 15)
Fig. 5 · APPLICATION DATA (cont)

1'-10 11/16'' MAX.

6'-2 3/8'' MAX. 5'-9 3/16'' MAX.

4'-6 13/16''1'-0 3/16''

B

B 24'' MIN.

A

A

BAFFLE

NOTE:

Shaded area indicates block-off panels.

1. Do not drill in this area, damage to basepan may result in water leak. 2. A 90-degree elbow must be provided in the supply ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.

Concentric Duct Distribution —

542J150,180

Concentric Duct Details —

542J150,180

5 3/16'' · 1'-7 15/16'' · 1'-0 3/16''

Page 16 of the Bryant 549B user manual — TYPICAL PIPING AND WIRING
Page 16 · click to enlarge
Page 16

TYPICAL PIPING AND WIRING

Bryant 549B — TYPICAL PIPING AND WIRING diagram (page 16)
Fig. 6
Page 17 of the Bryant 549B user manual — 542J150,180
Page 17 · click to enlarge
Page 17

TYPICAL PIPING AND WIRING (cont)

Bryant 549B — TYPICAL PIPING AND WIRING (cont) diagram (page 17)
Fig. 7 · TYPICAL PIPING AND WIRING (cont)

NEC — National Electrical Code

1. Illustration shown is a general guide only and is not intended for or to include all details for any specific installation. 2. Installation must comply with all applicable codes. 3. A 90-degree elbow must be provided in the supply ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.

542J150,180

Page 18 of the Bryant 549B user manual — COOLING HEATING
Page 18 · click to enlarge
Page 18

MODEL NUMBER NOMENCLATURE — 548F UNITS

(ODS Model Number)

548F E X 090 000 AA

548F – Single-Package Heat Pump Unit

Voltage Designation E – 460-3-60 J – 208/230-1-60† P – 208/230-3-60 T – 575-3-60

X – No Heat Installed.

(Field-installed electric heaters available.)

Nominal Tons 036 – 3 090 – 7-1/2 048 – 4 102 – 8-1/2 060 – 5 120 – 10 072 – 6 Electric Heaters 000 – No factory-installed electric heaters

Bryant 549B — MODEL NUMBER NOMENCLATURE — 548F UNITS diagram (page 18)
Fig. 8

ODS — Order Distribution System

*Refer to Trade Price Sheets or contact your local representative for specific information regarding which options are available on which units. †Single-phase is only available on 036-060 size units. NOTE: The example model number 548FEX090000AA designates a 71/2 ton 460-3-60 volt electric heat pump unit with factory-installed economizer.

ARI* CAPACITY RATINGS

548F036-060

COOLING HEATING (High Temp) SOUND RATING (decibels) Capacity

UNIT 548F NOMINAL

TONS

(Btuh) HSPF Belt Drive

Drive 036 3 35,600 10.20 10.00 34,400 6.7 84 048 4 46,500 10.00 9.70 46,500 7.0 80 060 5 57,000 10.00 9.90 57,000 7.5 82

548F072-120

SOUND RATING (decibels) Capacity

COOLING HEATING

HEATING

UNIT 548F NOMINAL

TONS

072†† 6 70,000 9.05 72,400 3.20 42,000 2.14 — 82 090†† 71/2 86,000 9.00 78,000 3.00 39,000 1.80 9.3 86 102†† 81/2 96,000 8.90 96,000 3.00 55,000 2.00 8.85 86 120†† 10 112,000 9.00 105,000 3.10 59,000 2.00 9.0 84

3. Ratings are based on:

COP — Coefficient of Performance db — dry bulb EER — Energy Efficiency Ratio HSPF — Heating Seasonal Performance Factor IPLV — Integrated Part-Load Values SEER — Seasonal Energy Efficiency Ratio wb — wet bulb

*Air Conditioning and Refrigeration Institute. †Applies only to units with capacity of 60,000 Btuh or less. **The IPLV applies only to 2-stage heat pump units. ††Not ASHRAE 90.1-99 compliant.

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db out- door entering-air temperature. High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F db, 43 F wb outdoor entering-air temperature. Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F db, 15 F wb outdoor entering-air temperature.

Show 9 more labels / short text on this page
Factory-Installed Options* · SEER† Capacity · Direct · (Btuh) · (High) · (Low) IPLV** · (Btuh) EER Capacity · (Btuh) COP Capacity · (Btuh) COP
Page 19 of the Bryant 549B user manual — FREEZE-PROTECTION THERMOSTAT (F)
Page 19 · click to enlarge
Page 19

PHYSICAL DATA

548F036-072

UNIT SIZE 548F 036 048 060 072 NOMINAL CAPACITY (tons) 3 4 5 6

Unit 500 520 550 590 Economizer

Durablade 34 EconoMi$er 47 Roof Curb* 115

COMPRESSOR Hermetic Quantity 1 Oil (oz) 45 54 50 54

REFRIGERANT TYPE R-22 Operating Charge (lb-oz)

Circuit 1 5-1 6-0 8-0 11-2 Circuit 2 —

OUTDOOR COIL Enhanced Copper Tubes, Aluminum Lanced Fins, Fixed Orifice Metering Device Rows...Fins/in. 1...17 1...17 2...17 2...17 Total Face Area (sq ft) 10.31 14.58 12.25 16.53

OUTDOOR FAN Propeller Type Nominal Cfm 4000 Quantity...Diameter (in.) 1...22.0 Motor Hp...Rpm 1/4...1100 Watts Input (Total) 325 INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Fixed Orifice Metering Device Rows...Fins/in. 2...15 2...15 3...15 3...15 Total Face Area (sq ft) 4.2 4.2 5.5 5.5

INDOOR FAN Centrifugal Type Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 Alt 1...10 x 10 1...10 x 10 1...10 x 10 — High-Static 1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 Type Drive Std Direct Direct Direct Belt Alt Belt Belt Belt — High-Static Belt Nominal Cfm 1200 1600 2000 2400 Maximum Continuous Bhp Std.34 .75 1.20 2.40 Alt 1.00 1.00 1.30/2.40† — High-Static 2.40 2.40 2.90 2.90 Motor Frame Size Std 48 48 48 56 Alt 48 48 56 — High-Static 56 Nominal Rpm High/Low Std 860/800 1075/970 1075/970 — Alt 1620 1620 1725 — High-Static 1725 Fan Rpm Range Std — — — 1070-1460 Alt 760-1000 835-1185 900-1300 — High-Static 1075-1455 1075-1455 1300-1685 1300-1685 Motor Bearing Type Ball Maximum Allowable Rpm 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std — — — 2.8/3.8 Alt 1.9/2.9 1.9/2.9 2.4/3.4 — High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4 Nominal Motor Shaft Diameter (in.) Std 1/2 1/2 1/2 5/8 Alt 1/2 1/2 5/8 — High-Static 5/8 Fan Pulley Pitch Diameter (in.) Std — — — 4.5 Alt 4.5 4.0 4.5 — High-Static 4.5 Belt, Quantity...Type...Length (in.) Std — — — 1...A...40 Alt 1...A...34 1...A...34 1...A...39 — High-Static 1...A...39 1...A...39 1...A...40 1...A...40 Pulley Center Line Distance (in.) Std — — — 14.7-15.5 Alt 10.0-12.4 10.0-12.4 14.7-15.5 — High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 Speed Change per Full Turn of

Movable Pulley Flange (rpm) Std — — — 80

Alt 48 70 80 — High-Static 65 65 60 60 Movable Pulley Maximum Full Turns

From Closed Position Std — — — 5

Alt 5 5 5 — High-Static 6 6 5 5 Factory Setting Std — — — 3 Alt 3 3 3 — High-Static 31/2 Factory Speed Setting (rpm) Std — — — 1225 Alt 856 975 1060 — High-Static 1233 1233 1396 1396 Fan Shaft Diameter at Pulley (in.) 5/8

Standard Compressor Internal Relief (Differential) 450 ± 50 Cutout 428 Reset (Auto.) 320

Cutout 7 ± 3 Reset (Auto.) 22 ± 7

FREEZE-PROTECTION THERMOSTAT (F)

Opens 30 ± 5 Closes 45 ± 5

OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 1...20 x 24 x 1

RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 2...16 x 25 x 2

Bhp — Brake Horsepower

*Weight of 14-in. roof curb. †Single phase/three phase.

OPERATING WEIGHT (lb) · HIGH-PRESSURE SWITCH (psig) · LOSS-OF-CHARGE SWITCH (psig)

Page 20 of the Bryant 549B user manual — FREEZE-PROTECTION THERMOSTAT (F)
Page 20 · click to enlarge
Page 20

PHYSICAL DATA (cont)

548F090-120

UNIT SIZE 548F 090 102 120 NOMINAL CAPACITY (tons) 71/2 81/2 10

Unit 940 965 1015 Economizer Durablade 44 44 44 EconoMi$er 62 62 62 Roof Curb* 143 143 143

COMPRESSOR Hermetic Quantity 2 2 2 Oil (oz) 45 ea 54 ea 54 ea

REFRIGERANT TYPE R-22 Operating Charge (lb-oz)

Circuit 1 5-14 8- 6 7-14 Circuit 2 5-13 8-13 8- 3

OUTDOOR COIL Enhanced Copper Tubes, Aluminum Lanced Fins Fixed Orifice Metering Device Rows...Fins/in. 1...17 2...17 2...17 Total Face Area (sq ft) 20.50 18.00 18.30 OUTDOOR FAN Propeller Type Nominal Cfm 6500 6500 6500 Quantity...Diameter (in.) 2...22 2...22 2...22 Motor Hp...Rpm 1/4...1100 1/4...1100 1/4...1100 Watts Input (Total) 500 500 500

INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Fixed Orifice Metering Device Rows...Fins/in. 3...15 3...15 3...15 Total Face Area (sq ft) 8.0 8.0 11.1

INDOOR FAN Centrifugal Type Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15 Alt 1...15 x 15 — 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15 Type Drive Std Belt Belt Belt Alt Belt — Belt High-Static Belt Belt Belt Nominal Cfm 3000 3600 4000 Maximum Continuous Bhp Std 2.40 2.40 2.40 Alt 2.40 — 2.90 High-Static 3.70 3.70 5.25 Motor Frame Size Std 56 56 56 Alt 56 — 56 High-Static 56 56 56 Nominal Rpm High/Low Std — — — Alt — — — High-Static 1725 1725 1725 Fan Rpm Range Std 590- 840 685- 935 685- 935 Alt 685- 935 — 835-1085 High-Static 860-1080 860-1080 830-1130 Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8 Alt 2.8/3.8 — 3.4/4.4 High-Static 4.0/5.0 4.0/5.0 2.8/3.8 Nominal Motor Shaft Diameter (in.) Std 5/8 5/8 5/8 Alt 5/8 — 7/8 High-Static 7/8 7/8 7/8 Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0 Alt 7.0 — 7.0 High-Static 8.0 8.0 5.8 Belt, Quantity...Type...Length (in.) Std 1...A...49 1...A...49 1...A...49 Alt 1...A...49 — 1...A...49 High-Static 1...A...55 1...A...55 1...BX...46 Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50 Alt 15.75-19.25 — 15.85-17.50 High-Static 15.75-19.25 16.75-19.25 15.85-17.50 Speed Change per Full Turn of

Movable Pulley Flange (rpm) Std 50 50 50 Alt 50 — 50 High-Static 60 60 60 Movable Pulley Maximum Full Turns

From Closed Position Std 5 5 5 Alt 5 — 5 High-Static 5 5 6 Factory Setting Std 5 5 5 Alt 5 — 5 High-Static 5 5 5 Factory Speed Setting (rpm) Std 590 685 685 Alt 685 — 835 High-Static 860 860 887 Fan Shaft Diameter at Pulley (in.) 1 1 1

Standard Compressor Internal Relief (Differential) 450 ± 50 Cutout 428 Reset (Auto.) 320

Cutout 7 ± 3 Reset (Auto.) 22 ± 5

FREEZE-PROTECTION THERMOSTAT (F)

Opens 30 ± 5 Closes 45 ± 5 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 1...20 x 25 x 1 1...16 x 25 x 1

RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2

Bhp — Brake Horsepower

*Weight of 14-in. roof curb.

OPERATING WEIGHT (lb) · HIGH-PRESSURE SWITCH (psig) · LOSS-OF-CHARGE SWITCH (psig)

Page 21 of the Bryant 549B user manual — PHYSICAL DATA (cont)
Page 21 · click to enlarge
Page 21
Bryant 549B — PHYSICAL DATA (cont) diagram (page 21)
Fig. 9 · PHYSICAL DATA (cont)
Page 22 of the Bryant 549B user manual — PHYSICAL DATA (cont)
Page 22 · click to enlarge
Page 22
Bryant 549B — PHYSICAL DATA (cont) diagram (page 22)
Fig. 10 · PHYSICAL DATA (cont)
Page 23 of the Bryant 549B user manual — 548F036-072
Page 23 · click to enlarge
Page 23

ACCESSORY DIMENSIONS

CONNECTOR

PKG. ACCY. B C D ALT DRAIN HOLE GAS POWER CONTROL

ROOF CURB ACCESSORY A UNIT SIZE

CRBTMPWR001A00

3/4″ [19] NPT 1/2″ [12.7] CRBTMPWR002A00 11/4″ [31.7]

3 / 4 ″ [19] NPT

CRRFCURB001A00 1′-2″ [356] 548F036-072 CRRFCURB002A00 2′-0″ [610]

1′-911/16″ [551]

1′-4″ [406]

13/4″ [44.5]

CRBTMPWR003A00

3/4″ [19] NPT 1/2″ [12.7] CRBTMPWR004A00

1 / 2 ″ [12.7] NPT

3/4″ [19] NPT 11/4″ [31.7]

7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 002A00 are for thru-the-curb type gas. Packages CRBTMPWR003A00 and 004A00 are for thru-thebottom type gas connections.

TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE

TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE

548F036-072

Page 24 of the Bryant 549B user manual — 548F090-120
Page 24 · click to enlarge
Page 24

ACCESSORY DIMENSIONS (cont)

CONNECTOR

D ALT DRAIN

ROOF CURB ACCESSORY “A” UNIT SIZE

PKG. ACCY. B C

GAS POWER CONTROL

HOLE

CRRFCURB003A00 1′-2″ [356] 548F090-120 CRRFCURB004A00 2′-0″ [610]

CRBTMPWR001A00

3/4″ [19] NPT 1/2″ [12.7] NPT CRBTMPWR002A00 11/4″ [31.7]

3 / 4 ″ [19] NPT

2′-87/16″ [827]

1′-1015/16″ [583]

13/4″ [44.5]

CRBTMPWR003A00

3/4″ [19] NPT 1/2″ [12.7] NPT CRBTMPWR004A00

1 / 2 ″ [12.7] NPT

3/4″ [19] NPT 11/4″ [31.7]

1. Roof curb accessory is shipped disassembled. 2. Insulated panels: 1-in. thick polyurethane foam, 1 3 / 4 lb density. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: 16-gage steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thruthe-bottom type gas connections.

TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.

TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.

548F090-120

Page 25 of the Bryant 549B user manual — SELECTION PROCEDURE (WITH 548F048 EXAMPLE)
Page 25 · click to enlarge
Page 25

SELECTION PROCEDURE (WITH 548F048 EXAMPLE)

I DETERMINE COOLING AND HEATING LOADS AT

Enter the Electric Heating Capacities table (page 54) for 548F048 at 208/230, 3 phase. The 6.5-kW heater at 240 v most closely satisfies the heating required. To calcu- late kW at 230 v, use the Multiplication Factors table.

DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) 38,000 Btuh Sensible Heat Capacity (SHC) 24,000 Btuh Required Heating Capacity 35,000 Btuh Outdoor Entering-Air Temperature db 95 F Outdoor-Air Winter Design Temperature 0° F Indoor-Air Winter Design Temperature 70 F Indoor-Air

6.5 kW x .92 = 5.98 kW 6.5 kW x .92 x 3413 = 20,410 Btuh Total unit heating capacity is 38,410 Btuh (18,000 + 20,410). IV DETERMINE FAN SPEED AND POWER REQUIRE-

MENTS AT DESIGN CONDITIONS. Before entering Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Pressure Drop tables, find:

Temperature 80 F edb (entering air, dry bulb) 67 F ewb (entering air, wet bulb) Indoor-Air Quantity 1600 cfm External Static Pressure 0.45 in. wg Electrical Characteristics (V-Ph-Hz) 230-3-60 II SELECT UNIT BASED ON REQUIRED COOLING

External static pressure .45 in. wg Durablade economizer .05 in. wg Electric heat .09 in. wg Total static pressure .59 in. wg

CAPACITY. Enter Cooling Capacities table at outdoor entering temper- ature of 95 F, indoor air entering at 1600 cfm and 67 F ewb. The 548F048 unit will provide a total cooling capacity of 49,900 Btuh and a sensible heat capacity of 33,900 Btuh. For indoor-air temperature other than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in Note 3 following the cooling capacities tables. NOTE: Unit ratings are gross capacities and do not include the effect of indoor-fan motor heat. To calculate net capacities, see Step V. III SELECT ELECTRIC HEAT.

Enter the Fan Performance table for 548F048 vertical dis- charge. At 1600 cfm and 230-v high speed, the standard motor will deliver 0.76 in. wg static pressure, 723 watts, and 0.64 brake horsepower (bhp). This will adequately handle job requirements. V DETERMINE NET CAPACITIES.

Capacities are gross and do not include the effect of indoor-fan motor (IFM) heat. Determine net cooling capacity as follows: Net capacity = Total capacity – IFM heat

= 49,900 Btuh – (723 Watts x 3.413

Enter the Instantaneous and Integrated Heating Ratings table at 1600 cfm. At 70 F return indoor air and 0° F air entering outdoor coil, the integrated heating capacity is 18,000 Btuh. (Select integrated heating capacity value since deductions for outdoor-coil frost and defrosting have already been made. No correction is required.) The required heating capacity is 35,000 Btuh. Therefore, 17,000 Btuh (35,000 – 18,000) additional electric heat is required. Determine additional electric heat capacity in kW.

Btuh/Watts) = 49,900 Btuh – 2468 Btuh = 47,432 Net sensible capacity = 33,900 Btuh – 2468 Btuh = 31,432 Btuh Integrated heating capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it. Therefore, net capacity is equal to 38,410 Btuh, the total heating capacity determined in Step III. 17,000 Btuh = 5.0 kW of heat required. 3413 Btuh/kW

Page 26 of the Bryant 549B user manual — 548F060 (5 TONS)
Page 26 · click to enlarge
Page 26

PERFORMANCE DATA

COOLING CAPACITIES

548F036 (3 TONS)

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry-Bulb Lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity

Indoor Entering Air — Cfm/BF 900/0.10 1200/0.15 1500/0.21 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 42.4 39.9 36.5 43.0 41.2 38.7 45.1 42.8 40.3 SHC 16.7 22.0 26.8 17.5 24.2 30.9 19.3 26.9 34.1 kW 2.77 2.71 2.62 2.78 2.74 2.68 2.85 2.79 2.73

(1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

85 TC 41.5 38.4 34.8 43.3 40.4 37.0 44.0 41.7 38.7 SHC 16.6 21.6 26.2 18.2 24.6 30.3 19.3 27.2 33.7 kW 3.01 2.92 2.80 3.07 2.98 2.88 3.09 3.03 2.94

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

95 TC 40.0 36.3 33.0 42.3 38.5 35.2 43.4 40.0 36.7 SHC 16.2 20.9 25.7 18.2 24.2 29.8 19.7 27.2 32.7 kW 3.24 3.10 2.99 3.32 3.19 3.07 3.36 3.24 3.13

tldb = tedb – sensible capacity (Btuh)

105 TC 38.4 34.7 31.0 40.0 36.7 33.1 41.2 37.7 35.2 SHC 15.7 20.5 24.8 17.5 23.9 28.8 19.3 26.6 31.7 kW 3.47 3.32 3.16 3.53 3.41 3.26 3.58 3.44 3.35

1.10 x cfm

tlwb = Wet-bulb temperature corresponding

to enthalpy of air leaving indoor coil (hlwb)

115 TC 36.1 32.5 28.9 38.1 34.3 31.1 39.3 35.5 33.2 SHC 15.1 19.8 23.9 17.2 23.2 27.8 19.1 26.2 30.2 kW 3.66 3.50 3.32 3.76 3.59 3.44 3.81 3.65 3.54

hlwb = hewb – total capacity (Btuh)

125 TC 34.2 30.5 26.8 35.9 32.0 29.3 36.8 33.0 31.3 SHC 14.6 19.2 22.9 16.7 22.6 26.3 18.5 25.5 28.4 kW 3.88 3.68 3.49 3.97 3.77 3.62 4.02 3.83 3.74

4.5 x cfm

Where: hewb = Enthalpy of air entering evap- orator coil 3. The SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

548F048 (4 TONS)

Indoor Entering Air — Cfm/BF 1200/0.11 1600/0.15 2000/0.22 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 55.5 51.9 47.4 56.9 54.6 50.3 59.3 56.5 52.1 SHC 24.5 31.2 37.4 26.0 35.2 43.4 28.4 39.0 47.6 kW 3.80 3.70 3.55 3.84 3.79 3.66 3.93 3.86 3.71

ENTERING AIR DRY-BULB TEMP (F)

BYPASS FACTOR

79 78 77 76 75 under

85 TC 53.4 49.7 45.3 56.3 52.6 47.8 57.5 54.1 49.8 SHC 23.8 30.4 36.7 26.3 34.9 42.6 28.3 38.6 46.9 kW 4.10 3.99 3.84 4.23 4.11 3.94 4.27 4.16 4.01

(BF)

81 82 83 84 85 over

85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula

95 TC 52.0 47.4 43.0 53.7 49.9 45.5 54.5 51.6 47.4 SHC 23.4 29.6 35.8 25.5 33.9 41.6 27.3 38.2 45.2 kW 4.47 4.28 4.11 4.53 4.39 4.23 4.56 4.48 4.29

.10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

105 TC 49.3 45.0 40.6 51.8 47.2 43.0 52.6 48.7 45.4 SHC 22.5 28.8 34.7 25.3 33.0 40.3 27.1 37.1 43.3 kW 4.77 4.59 4.39 4.90 4.68 4.52 4.92 4.76 4.63

shown below.

115 TC 46.6 42.4 38.0 48.8 44.6 40.6 50.2 45.8 43.2 SHC 21.7 27.9 33.6 24.3 32.4 38.7 26.8 36.1 41.2 kW 5.08 4.90 4.66 5.21 5.01 4.81 5.29 5.06 4.96

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

125 TC 44.0 39.6 35.4 45.6 41.6 38.3 47.0 42.9 40.9 SHC 20.9 26.9 32.4 23.3 31.6 36.5 25.9 35.6 39.0 kW 5.45 5.21 4.96 5.51 5.34 5.14 5.60 5.41 5.30

548F060 (5 TONS)

Indoor Entering Air — Cfm/BF 1500/0.05 2000/0.08 2500/0.14 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 69.3 64.5 59.3 70.8 67.9 62.8 72.9 69.3 65.4 SHC 30.9 39.2 47.4 33.1 44.9 55.4 35.8 49.4 61.4 kW 4.28 4.15 4.03 4.32 4.25 4.12 4.38 4.29 4.19

85 TC 67.7 62.4 56.8 69.1 65.7 60.2 71.1 67.7 63.2 SHC 30.4 38.6 46.5 32.8 44.6 54.4 35.8 50.0 59.8 kW 4.76 4.61 4.49 4.79 4.72 4.56 4.86 4.78 4.65

95 TC 65.2 59.8 54.4 67.7 62.9 57.6 69.1 64.8 60.7 SHC 29.6 37.6 45.5 32.8 43.6 53.2 35.6 49.3 57.7 kW 5.27 5.10 4.97 5.35 5.20 5.07 5.39 5.27 5.14

105 TC 62.3 57.2 51.8 65.1 59.6 54.9 66.8 61.7 58.3 SHC 28.6 33.8 44.4 32.1 42.6 51.6 35.4 48.2 55.5 kW 5.79 5.66 5.50 5.90 5.73 5.61 5.97 5.79 5.68

115 TC 59.7 54.2 49.0 61.7 57.0 52.5 63.2 58.4 55.8 SHC 27.6 35.8 43.2 31.1 41.9 49.6 34.3 47.0 53.2 kW 6.37 6.24 6.06 6.47 6.34 6.20 6.53 6.36 6.31

125 TC 56.5 51.0 46.0 58.2 53.5 49.8 59.4 55.1 53.0 SHC 26.8 34.7 41.9 30.0 40.8 47.3 33.0 46.5 50.5 kW 7.03 6.87 6.65 7.07 6.96 6.82 7.13 7.03 6.96

Show 9 more labels / short text on this page
Temp (F) · Outdoor Entering Air · (Edb) · Temp (F) · Outdoor Entering Air · (Edb) · Temp (F) · Outdoor Entering Air · (Edb)
Page 27 of the Bryant 549B user manual — 548F102 (8 1 / 2 TONS)
Page 27 · click to enlarge
Page 27

COOLING CAPACITIES (cont)

548F072 (6 TONS)

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry-Bulb Lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity

Indoor Entering Air — Cfm/BF 1800/0.10 2400/0.13 3000/0.19 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 81.1 77.6 72.1 84.0 80.3 75.2 84.2 81.1 77.8 SHC 36.2 46.9 57.0 39.1 52.4 65.4 40.8 56.2 72.2 kW 5.16 5.11 5.01 5.23 5.16 5.06 5.23 5.17 5.11

(1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

85 TC 80.7 75.8 70.0 83.9 79.3 73.4 84.1 80.8 76.2 SHC 36.1 46.5 56.4 39.7 52.9 65.2 41.6 58.3 71.9 kW 5.83 5.74 5.65 5.90 5.81 5.69 5.90 5.84 5.76

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

95 TC 79.3 73.0 67.3 82.0 76.7 70.8 83.0 79.1 73.5 SHC 35.8 45.4 55.3 39.3 52.3 64.3 42.2 58.9 69.7 kW 6.54 6.37 6.28 6.60 6.47 6.37 6.62 6.55 6.40

tldb = tedb – sensible capacity (Btuh)

105 TC 76.0 70.6 64.3 79.6 73.4 67.9 80.7 75.5 71.3 SHC 34.6 44.8 54.1 38.8 51.2 62.9 42.0 57.6 67.8 kW 7.21 7.12 6.94 7.34 7.15 7.06 7.36 7.22 7.14

1.10 x cfm

tlwb = Wet-bulb temperature corresponding

to enthalpy of air leaving indoor coil (hlwb)

115 TC 72.7 67.5 61.1 75.8 70.6 64.7 77.9 71.8 68.5 SHC 33.6 43.7 52.7 37.6 50.7 60.9 41.5 56.4 65.2 kW 7.95 7.86 7.63 8.06 7.95 7.77 8.14 7.94 7.90

hlwb = hewb – total capacity (Btuh)

125 TC 70.1 63.9 57.6 71.8 66.9 61.6 73.5 68.6 65.4 SHC 32.9 42.4 51.2 36.4 49.5 58.4 40.2 56.1 62.3 kW 8.82 8.62 8.37 8.83 8.73 8.54 8.89 8.79 8.69

4.5 x cfm

Where: hewb = Enthalpy of air entering evap- orator coil 3. The SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

548F090 (7 1 / 2 TONS)

Indoor Entering Air — Cfm/BF 2250/0.04 3000/0.06 3200/0.08 3750/0.11 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62

75 TC 109.8 101.4 92.2 116.2 107.0 98.0 117.6 108.8 100.2 118.8 110.4 102.4 SHC 44.2 57.4 69.4 49.6 66.0 82.0 51.8 69.8 87.0 54.0 74.0 92.0 kW 6.66 6.44 6.18 6.86 6.60 6.36 6.92 6.66 6.42 6.94 6.70 6.48

ENTERING AIR DRY-BULB TEMP (F)

BYPASS FACTOR

79 78 77 76 75 under

85 TC 105.2 96.4 87.0 111.4 102.2 92.6 113.0 104.0 95.0 114.6 105.8 97.6 SHC 42.8 55.6 67.6 48.4 65.0 80.0 50.8 69.0 84.4 53.4 73.8 88.8 kW 7.20 6.94 6.64 7.42 7.14 6.82 7.48 7.20 6.90 7.54 7.28 7.00

(BF)

81 82 83 84 85 over

85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula

95 TC 100.6 91.0 82.0 105.6 96.2 87.4 107.2 98.0 89.8 108.6 99.6 92.8 SHC 41.6 54.0 65.8 47.0 63.2 77.8 49.4 67.4 81.4 52.0 72.2 84.6 kW 7.78 7.42 7.08 7.96 7.62 7.30 8.00 7.70 7.40 8.06 7.76 7.50

.10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

105 TC 94.8 85.4 76.8 99.8 90.2 82.2 101.4 91.6 85.0 103.2 93.2 88.0 SHC 40.0 52.2 63.8 45.6 61.6 74.6 48.2 65.8 77.6 51.2 70.4 80.4 kW 8.26 7.88 7.50 8.48 8.10 7.76 8.56 8.18 7.88 8.64 8.24 8.02

shown below.

115 TC 88.8 79.9 71.4 93.4 84.0 77.6 94.8 85.4 80.0 96.0 86.6 83.0 SHC 38.4 50.4 61.6 44.2 59.8 70.6 46.6 64.0 73.2 49.4 68.6 75.8 kW 8.76 8.32 7.90 8.98 8.54 8.22 9.04 8.62 8.36 9.10 8.70 8.50

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

125 TC 82.6 73.8 65.8 86.6 77.4 74.4 88.0 78.8 75.0 89.2 80.0 77.6 SHC 36.8 48.6 59.2 42.2 57.8 66.2 45.2 62.0 68.6 48.2 66.6 71.0 kW 9.20 8.74 8.30 9.44 8.96 8.68 9.52 9.02 8.82 9.60 9.12 8.98

548F102 (8 1 / 2 TONS)

Indoor Entering Air — Cfm/BF 2400/0.06 3200/0.09 3600/0.11 4000/0.14 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62

75 TC 111.4 102.3 91.0 115.7 108.2 97.6 117.0 110.1 100.4 118.1 111.6 102.5 SHC 51.8 64.3 75.3 54.9 71.9 87.6 55.8 74.9 92.5 56.7 77.1 96.4 kW 8.64 8.48 8.23 9.32 9.18 8.95 9.73 9.61 9.30 10.19 10.12 9.72

85 TC 108.8 97.4 86.1 113.7 104.2 92.9 115.2 106.6 94.8 116.6 108.3 98.0 SHC 50.9 62.3 73.2 54.7 70.9 85.1 55.7 74.3 89.3 56.7 77.2 92.2 kW 9.27 9.09 8.76 9.98 9.79 9.40 10.40 10.24 9.83 10.88 10.74 10.20

95 TC 104.5 92.7 81.2 110.4 98.8 87.7 112.0 101.3 90.8 113.2 103.1 93.8 SHC 49.3 60.2 70.9 53.7 68.7 82.4 55.1 72.6 86.3 56.2 75.7 88.2 kW 9.90 9.56 9.22 10.64 10.39 9.88 11.07 10.86 10.25 11.55 11.36 10.67

105 TC 98.8 87.8 75.9 105.5 93.4 83.0 107.4 95.4 86.5 108.9 97.1 89.5 SHC 47.1 58.3 68.1 52.2 66.5 79.0 53.7 69.9 82.2 55.1 72.9 83.9 kW 10.37 10.08 9.70 11.26 10.90 10.33 11.71 11.34 10.73 12.20 11.82 11.24

115 TC 93.8 82.4 71.1 98.7 87.9 78.6 100.8 89.8 82.1 102.9 91.3 85.3 SHC 45.3 56.0 65.9 49.5 64.5 75.5 51.3 68.0 77.9 53.0 71.0 79.6 kW 10.99 10.56 10.13 11.72 11.39 10.79 12.16 11.86 11.24 12.76 12.38 11.76

125 TC 88.4 77.2 66.7 93.1 82.2 74.5 94.9 83.9 77.9 96.2 85.3 80.8 SHC 43.4 54.1 63.1 47.7 62.3 71.4 49.2 65.8 73.7 50.4 68.8 75.2 kW 11.52 11.03 10.56 12.33 11.87 11.30 12.78 12.33 11.75 13.29 12.81 12.27

Show 9 more labels / short text on this page
Temp (F) · Outdoor Entering Air · (Edb) · Temp (F) · Outdoor Entering Air · (Edb) · Temp (F) · Outdoor Entering Air · (Edb)
Page 28 of the Bryant 549B user manual — LEGEND NOTES:
Page 28 · click to enlarge
Page 28

COOLING CAPACITIES (cont)

548F120 (10 TONS)

Indoor Entering Air — Cfm/BF 2800/0.11 3750/0.16 4100/0.18 4700/0.21 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62

75 TC 127.4 120.4 110.6 134.2 126.2 116.2 135.6 127.4 117.8 137.0 129.0 120.6 SHC 60.0 76.4 91.0 66.2 86.0 104.4 67.8 89.0 108.8 70.2 93.4 115.6 kW 8.30 8.18 7.88 8.54 8.34 8.04 8.60 8.36 8.10 8.64 8.38 8.20

85 TC 124.6 116.2 106.4 131.0 122.0 112.4 132.4 123.6 114.0 133.8 126.0 116.4 SHC 59.2 74.6 89.4 65.4 84.8 103.6 67.4 88.4 107.4 70.0 94.2 112.8 kW 9.24 9.04 8.74 9.50 9.24 8.98 9.54 9.28 9.02 9.60 9.36 9.08

95 TC 121.8 112.0 102.2 126.2 117.4 107.4 127.8 119.0 109.4 130.0 121.2 112.6 SHC 58.4 73.2 87.4 63.8 83.4 101.0 66.0 87.2 104.8 69.6 93.4 110.2 kW 10.34 10.04 9.66 10.46 10.18 9.90 10.52 10.26 9.96 10.62 10.36 10.08

105 TC 116.9 107.2 97.6 122.4 112.4 102.8 123.6 113.8 105.0 124.6 115.6 108.4 SHC 56.6 71.4 85.4 63.0 82.0 98.4 65.0 85.8 101.8 67.8 91.4 106.2 kW 11.38 11.08 10.66 11.64 11.28 10.90 11.68 11.32 11.00 11.68 11.38 11.16

115 TC 112.0 102.0 92.8 116.6 107.0 98.0 118.0 108.2 100.2 120.0 110.0 103.8 SHC 55.0 69.6 83.2 61.2 80.2 95.2 63.6 84.2 98.0 67.4 90.2 101.8 kW 12.58 12.18 11.74 12.78 11.42 12.00 12.84 12.48 12.12 12.96 12.56 12.30

125 TC 106.4 96.8 87.8 110.4 101.2 93.6 111.6 102.2 95.8 113.6 103.8 99.0 SHC 53.2 67.4 80.8 59.2 78.4 91.4 61.4 82.2 94.0 65.4 88.0 97.2 kW 13.84 13.36 12.90 13.96 13.62 13.22 14.02 13.68 13.34 14.14 13.76 13.54

Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC..

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry-Bulb Lwb — Leaving Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

Bryant 549B — COOLING CAPACITIES (cont) diagram (page 28)
Fig. 11 · COOLING CAPACITIES (cont)

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

tldb = tedb – sensible capacity (Btuh)

1.10 x cfm

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving

indoor coil (hlwb)

hlwb = hewb – total capacity (Btuh)

4.5 x cfm

INSTANTANEOUS AND INTEGRATED HEATING RATINGS

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

900 Cap. 15.4 13.1 19.2 17.6 21.7 19.8 27.4 24.0 31.9 31.9 35.3 35.3 36.9 36.9 41.4 41.4 kW 2.25 2.44 2.57 2.86 3.10 3.29 3.38 3.64

1200 Cap. 15.9 13.5 19.4 17.8 22.5 20.5 28.3 24.8 32.9 32.9 35.8 35.8 37.0 37.0 40.1 40.1 kW 2.24 2.40 2.54 2.80 3.02 3.15 3.21 3.35

1500 Cap. 16.2 13.8 19.8 18.2 22.9 20.9 28.8 25.2 33.1 33.1 35.3 35.3 36.5 36.5 38.6 38.6 kW 2.23 2.38 2.52 2.76 2.94 3.03 3.08 3.17

900 Cap. 13.2 11.2 17.1 15.7 20.0 18.2 25.4 22.2 29.8 29.8 33.2 33.2 34.7 34.7 40.1 40.1 kW 2.29 2.50 2.67 2.98 3.24 3.45 3.55 3.91

1200 Cap. 13.7 11.6 17.7 16.3 20.3 18.5 26.3 23.1 30.8 30.8 34.4 34.4 36.0 36.0 40.9 40.9 kW 2.28 2.49 2.62 2.93 3.17 3.36 3.45 3.72

1500 Cap. 14.0 11.9 18.1 16.6 20.7 18.9 26.9 23.6 31.6 31.6 35.1 35.1 36.9 36.9 40.2 40.2 kW 2.27 2.47 2.60 2.89 3.12 3.30 3.38 3.54

900 Cap. 11.5 9.8 15.5 14.2 18.4 16.8 23.7 20.8 28.1 28.1 31.7 31.7 33.2 33.2 38.5 38.5 kW 2.30 2.54 2.71 3.04 3.32 3.55 3.65 4.03

1200 Cap. 12.0 10.2 16.2 14.8 19.2 17.5 24.7 21.6 29.3 29.3 33.0 33.0 34.5 34.5 40.2 40.2 kW 2.30 2.52 2.69 2.99 3.26 3.47 3.56 3.91

1500 Cap. 12.3 10.5 16.6 15.2 19.7 18.0 25.4 22.3 30.1 30.1 33.7 33.7 35.3 35.3 39.2 39.2 kW 2.29 2.51 2.68 2.97 3.22 3.41 3.50 3.70

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) db — dry bulb kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input)

Show 7 more labels / short text on this page
Temp (F) · Outdoor Entering Air · (Edb) · 548F036 Return · Cfm (Standard · Air (F db) · Air)
Page 29 of the Bryant 549B user manual — LEGEND NOTES:
Page 29 · click to enlarge
Page 29

INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

1200 Cap. 22.7 19.3 26.6 24.4 30.2 27.6 37.4 32.7 43.1 43.1 47.6 47.6 49.8 49.8 57.2 57.2 kW 2.91 3.14 3.35 3.77 4.12 4.40 4.54 5.04

1600 Cap. 23.1 19.7 27.2 25.0 30.8 28.1 38.2 33.5 44.1 44.1 48.9 48.9 51.1 51.1 59.0 59.0 kW 2.87 3.09 3.28 3.66 3.97 4.23 4.34 4.80

2000 Cap. 23.4 19.9 27.4 25.2 31.2 28.4 38.7 33.9 44.8 44.8 49.7 49.7 52.0 52.0 60.2 60.2 kW 2.85 3.05 3.23 3.59 3.88 4.11 4.23 4.65

1200 Cap. 20.6 17.5 25.5 23.4 28.4 25.9 35.6 31.2 41.0 41.0 45.5 45.5 47.5 47.5 54.9 54.9 kW 3.00 3.33 3.52 4.01 4.39 4.71 4.85 5.40

1600 Cap. 21.2 18.0 25.6 23.5 29.1 26.6 36.3 31.8 42.1 42.1 46.8 46.8 48.9 48.9 56.5 56.5 kW 2.99 3.25 3.47 3.90 4.25 4.54 4.67 5.15

2000 Cap. 21.6 18.3 25.9 23.8 29.5 26.9 36.9 32.3 42.8 42.8 47.5 47.5 49.7 49.7 57.6 57.6 kW 2.97 3.22 3.43 3.84 4.16 4.42 4.55 5.00

1200 Cap. 18.6 15.8 23.9 21.9 27.1 24.7 34.2 29.9 39.7 39.7 44.1 44.1 46.1 46.1 53.2 53.2 kW 3.01 3.40 3.62 4.15 4.56 4.90 5.06 5.63

1600 Cap. 19.4 16.4 24.7 22.6 27.8 25.4 35.1 30.8 40.7 40.7 45.3 45.3 47.3 47.3 54.9 54.9 kW 3.01 3.37 3.58 4.06 4.43 4.74 4.88 5.39

2000 Cap. 19.8 16.8 25.1 23.1 28.2 25.7 35.7 31.3 41.5 41.5 46.0 46.0 48.2 48.2 55.8 55.8 kW 3.01 3.35 3.54 4.00 4.35 4.63 4.76 5.24

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

1500 Cap. 29.7 25.2 34.5 31.7 38.4 35.0 46.0 40.3 52.4 52.4 57.2 57.2 59.6 59.6 67.9 67.9 kW 3.96 4.14 4.30 4.62 4.90 5.14 5.25 5.67

2000 Cap. 29.8 25.4 34.7 31.8 38.6 35.2 46.3 40.6 52.9 52.9 57.7 57.7 60.1 60.1 68.7 68.7 kW 3.83 3.98 4.12 4.38 4.63 4.82 4.91 5.25

2500 Cap. 29.8 25.4 34.8 31.9 38.7 35.3 46.6 40.8 53.1 53.1 58.0 58.0 60.4 60.4 68.4 68.4 kW 3.76 3.89 4.01 4.26 4.47 4.63 4.72 4.99

1500 Cap. 28.7 24.4 33.8 31.0 37.8 34.4 45.4 39.8 51.5 51.5 56.2 56.2 58.4 58.4 66.5 66.5 kW 4.43 4.66 4.84 5.21 5.53 5.79 5.91 6.39

2000 Cap. 29.0 24.7 34.0 31.2 38.0 34.7 45.7 40.1 51.9 51.9 56.7 56.7 59.0 59.0 67.4 67.4 kW 4.30 4.48 4.63 4.94 5.20 5.41 5.52 5.91

2500 Cap. 29.2 24.8 34.2 31.4 38.2 34.8 45.8 40.2 52.2 52.2 57.1 57.1 59.4 59.4 67.9 67.9 kW 4.22 4.38 4.51 4.78 5.01 5.21 5.30 5.63

1500 Cap. 28.1 23.8 33.1 30.4 37.2 33.9 44.9 39.3 51.0 51.0 55.6 55.6 57.8 57.8 65.7 65.7 kW 4.77 5.03 5.23 5.64 5.99 6.27 6.41 6.92

2000 Cap. 28.4 24.2 33.5 30.7 37.6 34.2 45.3 39.7 51.4 51.4 56.1 56.1 58.3 58.3 66.5 66.5 kW 4.63 4.84 5.01 5.34 5.63 5.86 5.97 6.39

2500 Cap. 28.6 24.3 33.7 30.9 37.7 34.4 45.5 39.8 51.6 51.6 56.4 56.4 58.7 58.7 67.0 67.0 kW 4.55 4.73 4.88 5.17 5.42 5.62 5.72 6.09

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) db — dry bulb kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input)

Show 8 more labels / short text on this page
548F048 Return · Cfm (Standard · Air (F db) · Air) · 548F060 Return · Cfm (Standard · Air (F db) · Air)
Page 30 of the Bryant 549B user manual — LEGEND NOTES:
Page 30 · click to enlarge
Page 30

INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

1800 Cap. 37.8 32.2 43.9 40.3 48.3 44.1 58.0 50.8 66.2 66.2 72.3 72.3 75.2 75.2 86.0 86.0 kW 4.72 4.97 5.16 5.58 5.96 6.25 6.40 6.95

2400 Cap. 37.9 32.2 44.0 40.4 48.5 44.2 58.4 51.2 66.6 66.6 72.8 72.8 75.9 75.9 87.0 87.0 kW 4.55 4.76 4.92 5.28 5.57 5.81 5.93 6.38

3000 Cap. 38.0 32.3 44.0 40.4 48.5 44.3 58.5 51.3 66.9 66.9 73.1 73.1 76.2 76.2 87.5 87.5 kW 4.46 4.64 4.78 5.09 5.35 5.56 5.67 6.07

1800 Cap. 37.3 31.7 43.6 40.0 48.1 43.9 57.5 50.4 65.2 65.2 71.1 71.1 74.0 74.0 84.6 84.6 kW 5.32 5.61 5.84 6.33 6.75 7.10 7.27 7.91

2400 Cap. 37.5 31.9 43.8 40.2 48.2 43.9 57.7 50.5 65.6 65.6 71.8 71.8 74.7 74.7 85.4 85.4 kW 5.13 5.38 5.57 5.97 6.32 6.61 6.74 7.25

3000 Cap. 37.6 32.0 43.9 40.3 48.3 44.0 57.8 50.7 66.0 66.0 72.1 72.1 75.0 75.0 86.0 86.0 kW 5.03 5.25 5.41 5.76 6.08 6.32 6.44 6.89

1800 Cap. 36.8 31.3 43.1 39.6 47.9 43.7 57.1 50.1 64.8 64.8 70.5 70.5 73.4 73.4 83.6 83.6 kW 5.75 6.09 6.34 6.88 7.35 7.72 7.90 8.58

2400 Cap. 37.0 31.4 43.4 39.8 48.0 43.8 57.4 50.3 65.1 65.1 71.1 71.1 73.9 73.9 84.5 84.5 kW 5.55 5.83 6.04 6.49 6.87 7.18 7.33 7.89

3000 Cap. 37.1 31.5 43.5 39.9 48.1 43.9 57.5 50.4 65.3 65.3 71.5 71.5 74.4 74.4 85.0 85.0 kW 5.44 5.68 5.87 6.26 6.60 6.88 7.01 7.49

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

2000 Cap. 36.6 31.2 44.0 40.4 49.8 45.4 61.4 53.8 70.4 70.4 77.4 77.4 80.6 80.6 91.8 91.8 kW 5.24 5.64 5.94 6.58 7.08 7.50 7.68 8.32

2600 Cap. 37.6 32.0 45.2 41.4 51.2 46.6 63.0 55.2 72.4 72.4 79.6 79.6 83.0 83.0 92.4 92.4 kW 5.18 5.56 5.82 6.40 6.84 7.20 7.36 7.78

3200 Cap. 38.2 32.4 45.8 42.0 51.8 47.2 63.8 55.8 73.6 73.6 81.0 81.0 83.8 83.8 91.2 91.2 kW 5.16 5.50 5.74 6.28 6.70 7.02 7.12 7.40

2000 Cap. 32.4 27.6 40.4 37.2 46.0 41.8 57.8 50.6 66.8 66.8 73.6 73.6 76.6 76.6 87.8 87.8 kW 5.42 5.90 6.22 6.92 7.48 7.94 8.16 8.90

2600 Cap. 33.4 28.4 41.8 38.2 47.4 43.2 59.6 52.2 68.8 68.8 75.8 75.8 79.0 79.0 90.4 90.4 kW 5.38 5.82 6.12 6.76 7.28 7.68 7.86 8.48

3200 Cap. 34.2 29.0 42.2 38.6 48.4 44.0 60.6 53.0 70.0 70.0 77.2 77.2 80.6 80.6 91.0 91.0 kW 5.36 5.76 6.06 6.66 7.14 7.50 7.68 8.16

2000 Cap. 29.2 24.8 37.4 34.4 43.4 39.6 54.8 48.0 64.0 64.0 70.8 70.8 73.8 73.8 84.8 84.8 kW 5.52 6.02 6.40 7.12 7.72 8.22 8.44 9.24

2600 Cap. 30.2 25.8 38.8 35.6 44.6 40.6 56.8 49.8 66.2 66.2 73.2 73.2 76.4 76.4 87.8 87.8 kW 5.48 5.96 6.30 6.98 7.54 7.98 8.18 8.88

3200 Cap. 31.0 26.4 39.6 36.4 45.4 41.4 58.0 50.8 67.4 67.4 74.6 74.6 78.0 78.0 89.0 89.0 kW 5.46 5.92 6.24 6.90 7.42 7.82 8.00 8.58

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) db — dry bulb kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input)

Show 8 more labels / short text on this page
548F072 Return · Cfm (Standard · Air (F db) · Air) · 548F090 Return · Cfm (Standard · Air (F db) · Air)
Page 31 of the Bryant 549B user manual — LEGEND NOTES:
Page 31 · click to enlarge
Page 31

INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

2400 Cap. 37.0 34.1 47.1 43.3 54.8 50.0 70.3 61.6 83.2 83.2 92.0 92.0 95.5 95.5 107.9 107.9 kW 5.30 5.81 6.18 6.92 7.56 8.11 8.27 8.92

3200 Cap. 40.7 37.4 51.31 47.1 59.28 54.0 75.51 66.2 88.59 88.6 96.82 96.8 100.58 100.6 112.54 112.5 kW 5.88 6.36 6.69 7.35 7.96 8.30 8.44 8.93

3600 Cap. 42.6 39.2 53.4 49.1 61.5 56.1 78.1 68.4 90.9 90.9 98.9 98.9 102.6 102.6 114.5 114.5 kW 6.29 6.75 7.07 7.70 8.29 8.56 8.70 9.14

4000 Cap. 44.8 41.2 55.7 51.1 63.9 58.2 80.7 70.7 93.1 93.1 98.8 98.8 104.6 104.6 116.5 116.5 kW 6.78 7.23 7.53 8.15 8.70 8.88 9.05 9.46

2400 Cap. 30.0 27.6 39.8 36.5 47.4 43.2 62.8 55.0 75.4 75.4 85.0 85.0 89.0 89.0 101.6 101.6 kW 5.38 5.97 6.41 7.25 7.95 8.55 8.85 9.61

3200 Cap. 33.3 30.6 43.8 40.2 51.8 47.2 68.0 59.6 81.5 81.5 91.0 91.0 94.6 94.6 107.5 107.5 kW 5.96 6.53 6.93 7.70 8.34 8.91 9.08 9.68

3600 Cap. 35.1 32.3 45.8 42.1 53.9 49.2 70.4 61.7 84.1 84.1 92.4 92.4 97.1 97.1 109.8 109.8 kW 6.37 6.92 7.31 8.06 8.68 9.21 9.35 9.90

4000 Cap. 37.1 34.2 48.0 44.1 56.2 51.3 72.9 63.9 86.7 86.7 95.8 95.8 99.5 99.5 112.0 112.0 kW 6.85 7.39 7.77 8.50 9.10 9.57 9.71 10.21

2400 Cap. 25.7 23.7 35.0 32.1 42.4 38.6 57.6 50.5 70.1 70.1 79.7 79.7 83.9 83.9 96.8 96.8 kW 5.52 6.07 6.52 7.45 8.21 8.82 9.12 10.05

3200 Cap. 28.6 26.3 38.5 35.3 46.5 42.4 62.6 54.9 75.9 75.9 86.0 86.0 90.2 90.2 103.2 103.2 kW 6.05 6.62 7.06 7.91 8.59 9.18 9.48 10.14

3600 Cap. 30.2 27.8 40.5 37.1 48.6 44.3 65.0 57.0 78.6 78.6 88.7 88.7 92.8 92.8 105.8 105.8 kW 6.43 7.00 7.44 8.27 8.92 9.50 9.78 10.37

4000 Cap. 32.2 29.6 42.6 39.1 50.9 46.4 67.5 59.2 81.2 81.2 91.3 91.3 95.2 95.2 108.3 108.3 kW 6.90 7.47 7.90 8.71 9.34 9.91 10.13 10.70

Air Temperature Entering Outdoor Coil (F)

0 10 17 30 40 47 50 60

2650 Cap. 52.2 44.4 62.2 57.0 69.6 63.4 84.2 73.8 96.0 96.0 104.6 104.6 108.8 108.8 123.6 123.6 kW 7.20 7.58 7.86 8.46 9.00 9.42 9.62 10.38

3500 Cap. 52.7 44.8 62.8 57.6 70.2 64.0 85.0 74.4 96.8 96.8 105.8 105.8 109.8 109.8 125.4 125.4 kW 6.98 7.30 7.52 8.02 8.46 8.80 8.96 9.62

4100 Cap. 53.2 45.2 63.0 58.0 70.4 64.2 85.2 74.8 97.2 97.2 105.8 105.8 110.2 110.2 126.0 126.0 kW 6.88 7.16 7.38 7.82 8.22 8.54 8.68 9.28

4400 Cap. 53.2 45.2 63.2 58.0 70.6 64.4 85.4 74.8 97.4 97.4 106.0 106.0 110.4 110.4 126.4 126.4 kW 6.84 7.12 7.32 7.74 8.14 8.44 8.58 9.14

2650 Cap. 49.8 42.2 59.2 54.4 67.0 61.2 82.0 72.0 94.0 94.0 102.6 102.6 106.8 106.8 121.2 121.2 kW 8.08 8.50 8.86 9.56 10.14 10.62 10.86 11.72

3500 Cap. 50.6 43.0 60.2 55.2 63.2 62.2 83.2 72.8 95.2 95.2 103.8 103.8 108.0 108.0 122.8 122.8 kW 7.86 8.20 8.50 9.04 9.52 9.92 10.10 10.80

4100 Cap. 51.0 43.2 60.6 55.6 68.6 62.6 83.6 73.2 95.6 95.6 104.2 104.2 108.4 108.4 123.4 123.4 kW 7.74 8.06 8.32 8.82 9.26 9.62 9.78 10.40

4400 Cap. 51.0 43.4 60.8 55.8 68.8 62.6 83.8 73.4 95.8 95.8 104.4 104.4 108.6 108.6 123.8 123.8 kW 7.70 8.02 8.26 8.74 9.16 9.50 9.66 10.26

2650 Cap. 47.6 40.6 57.6 52.8 64.6 58.8 80.2 70.4 92.0 92.0 101.0 101.0 105.2 105.2 119.8 119.8 kW 8.72 9.20 9.56 10.36 11.00 11.52 11.76 12.70

3500 Cap. 48.6 41.4 58.6 53.8 66.0 60.2 81.6 71.4 93.6 93.6 102.4 102.4 106.6 106.6 121.2 121.2 kW 8.48 8.88 9.18 9.82 10.34 10.74 10.96 11.70

4100 Cap. 49.0 41.8 58.6 53.8 66.6 60.8 82.0 71.8 94.2 94.2 103.0 103.0 107.2 107.2 121.8 121.8 kW 8.36 8.72 9.02 9.58 10.04 10.42 10.60 11.28

4400 Cap. 49.2 41.8 58.8 54.0 66.8 61.0 82.2 72.2 94.4 94.4 103.2 103.2 107.4 107.4 122.2 122.2 kW 8.32 8.66 8.94 9.48 9.92 10.28 10.46 11.10

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) db — dry bulb kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input)

Show 8 more labels / short text on this page
548F102 Return · Cfm (Standard · Air (F db) · Air) · 548F120 Return · Cfm (Standard · Air (F db) · Air)
Page 32 of the Bryant 549B user manual — 548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Page 32 · click to enlarge
Page 32
Bryant 549B — ACCESSORY DIMENSIONS diagram (page 32)
Fig. 12

Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 900 0.67 0.21 253 0.68 0.23 277 0.69 0.26 307 0.69 0.31 363 1000 0.60 0.23 270 0.61 0.25 292 0.61 0.27 321 0.63 0.32 374 1100 0.55 0.24 287 0.56 0.26 307 0.57 0.28 335 0.58 0.33 385 1200 0.51 0.26 304 0.51 0.27 323 0.52 0.29 349 0.53 0.34 397 1300 0.45 0.27 321 0.46 0.29 338 0.46 0.31 364 0.47 0.34 408 1400 0.38 0.29 338 0.41 0.30 354 0.43 0.32 378 — — — 1500 0.34 0.30 355 0.36 0.31 369 0.38 0.33 392 — — —

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 581 0.12 119 673 0.18 179 736 0.22 219 805 0.25 249 865 0.29 288 911 0.34 338 1000 644 0.19 189 709 0.22 219 782 0.28 279 835 0.30 298 900 0.35 348 937 0.38 378 1100 687 0.22 219 746 0.26 259 806 0.30 298 867 0.35 348 929 0.40 398 964 0.40 398 1200 733 0.26 259 785 0.32 318 843 0.35 348 903 0.41 408 960 0.47 467 994 0.50 497 1300 754 0.29 288 826 0.38 378 891 0.43 428 942 0.48 477 991 0.53 527 1047 0.60 597 1400 810 0.35 348 868 0.45 448 937 0.51 507 984 0.57 567 1032 0.62 617 1067 0.67 666 1500 841 0.42 418 911 0.53 527 985 0.61 607 1029 0.66 656 1073 0.72 716 1109 0.77 766

548F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 0.7 0.8 0.9 1.0 1.1 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 957 0.39 388 988 0.43 428 1039 0.45 448 1061 0.47 487 1083 0.53 527 1105 0.57 567 1000 992 0.44 438 1039 0.49 487 1061 0.51 507 1086 0.55 547 1111 0.59 587 1136 0.63 627 1100 1013 0.49 487 1068 0.55 547 1090 0.58 577 1109 0.61 607 1127 0.64 637 1145 0.67 666 1200 1045 0.56 557 1090 0.64 637 1109 0.64 647 1156 0.68 676 1203 0.71 706 1250 0.74 736 1300 1075 0.64 637 1122 0.70 696 1152 0.72 716 1190 0.76 756 1228 0.80 796 1266 0.84 836 1400 1110 0.73 726 1160 0.84 766 1181 0.81 806 1237 0.85 845 1293 0.89 885 1349 0.93 925 1500 1150 0.82 816 1190 1.00 855 1225 0.90 895 1271 0.95 945 1317 1.00 995 1363 1.05 1044

Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 1000 and maximum continuous bhp is 1.00.

*Motor drive range: 760 to 1000 rpm. All other rpms require field-supplied drive.

548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 673 0.18 179 805 0.25 249 911 0.34 338 988 0.43 428 1061 0.47 487 1000 709 0.22 219 835 0.30 298 937 0.38 378 1039 0.49 487 1086 0.55 547 1100 746 0.26 259 867 0.35 348 964 0.40 398 1068 0.55 547 1109 0.61 607 1200 785 0.32 318 903 0.41 408 994 0.50 497 1090 0.64 637 1156 0.68 676 1300 826 0.38 378 942 0.48 477 1047 0.60 597 1122 0.70 696 1190 0.76 756 1400 868 0.45 448 984 0.57 567 1067 0.67 666 1160 0.84 766 1237 0.85 845 1500 911 0.53 527 1029 0.66 656 1109 0.77 766 1190 1.00 855 1271 0.95 945

548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1105 0.57 567 1140 0.63 622 1170 0.68 674 1198 0.73 723 1224 0.77 771 1000 1136 0.63 627 1172 0.69 688 1203 0.75 745 1232 0.80 799 1258 0.86 852 1100 1145 0.67 666 1181 0.73 731 1213 0.80 792 1242 0.85 850 1268 0.91 906 1200 1210 0.74 736 1248 0.81 808 1282 0.88 875 1312 0.94 939 1340 1.01 1000 1300 1266 0.84 836 1306 0.92 917 1341 1.00 993 1373 1.07 1066 1402 1.14 1136 1400 1349 0.93 925 1391 1.02 1015 1429 1.11 1100 1463 1.19 1180 1494 1.26 1257 1500 1383 1.05 1044 1426 1.15 1146 1465 1.25 1242 1500 1.34 1332 1532 1.43 1419

Refer to page 51 for general Fan Performance notes. NOTES:

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.4, and the maximum continuous watts are 2120.

*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.

Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 33 of the Bryant 549B user manual — 548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Page 33 · click to enlarge
Page 33

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1200 0.93 0.41 458 0.94 0.45 506 0.94 0.51 572 0.99 0.56 632 1300 0.86 0.42 471 0.87 0.46 521 0.87 0.52 589 0.92 0.58 651 1400 0.78 0.45 503 0.79 0.49 556 0.79 0.54 616 0.87 0.60 681 1500 0.70 0.47 536 0.73 0.52 593 0.73 0.56 631 0.80 0.62 698 1600 0.61 0.49 557 0.64 0.54 616 0.66 0.58 654 0.76 0.64 723 1700 0.51 0.52 584 0.54 0.57 646 0.58 0.60 678 0.68 0.66 750 1800 0.40 0.54 610 0.44 0.60 674 0.51 0.62 698 0.63 0.68 772 1900 0.29 0.56 629 0.37 0.62 696 0.46 0.64 720 0.56 0.70 796 2000 0.25 0.58 651 0.30 0.64 720 0.39 0.66 744 0.50 0.73 823

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.6 0.7 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 542 0.16 168 616 0.21 221 678 0.27 278 739 0.32 336 842 0.44 462 886 0.50 525 929 0.56 588 1300 576 0.20 210 644 0.25 263 704 0.31 326 764 0.37 389 867 0.50 525 910 0.56 588 952 0.62 651 1400 610 0.24 252 673 0.30 315 732 0.36 378 791 0.42 441 889 0.55 578 933 0.62 651 976 0.69 725 1500 646 0.28 294 704 0.35 368 761 0.42 436 818 0.48 504 912 0.61 641 957 0.69 720 1001 0.76 777 1600 681 0.33 347 735 0.40 420 790 0.47 494 845 0.54 567 920 0.68 695 931 0.76 772 1023 0.83 848 1700 718 0.39 410 768 0.46 483 836 0.54 562 873 0.61 641 965 0.76 777 1005 0.84 853 1045 0.91 930 1800 754 0.45 473 801 0.53 557 851 0.61 641 900 0.69 725 992 0.84 858 1032 0.92 940 1071 1.00 1022 1900 791 0.52 546 836 0.60 630 832 0.69 720 828 0.77 809 1019 0.93 950 1058 1.02 1037 1097 1.10 1124 2000 828 0.60 630 870 0.68 714 864 0.77 809 858 0.86 904 1046 1.03 1053 1085 1.12 1139 1124 1.21 1237

548F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.0 1.1 1.2 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1008 0.67 704 1052 0.73 762 1096 0.78 820 1134 0.89 835 1203 1.00 885 — — — 1300 1029 0.75 788 1065 0.81 846 1101 0.86 904 1174 1.01 1040 1229 1.15 1100 1277 1.27 1029 1400 1052 0.83 826 1087 0.90 890 1121 0.96 918 1183 1.09 1042 1255 1.22 1167 1305 1.38 1190 1500 1076 0.91 905 1111 0.99 980 1145 1.06 1014 1208 1.20 1138 1274 1.33 1272 1337 1.47 1350 1600 1100 1.00 995 1134 1.08 1069 1168 1.15 1100 1232 1.31 1253 1291 1.46 1396 1350 1.60 1558 1700 1124 1.09 1084 1158 1.17 1164 1192 1.25 1196 1255 1.42 1358 1314 1.58 1511 1370 1.77 1738 1800 1147 1.18 1174 1182 1.27 1263 1217 1.36 1301 1279 1.54 1473 1381 1.71 1635 1393 1.89 1907 1900 1169 1.27 1263 1205 1.37 1363 1240 1.47 1406 1303 1.66 1588 1408 1.85 1769 1417 2.03 2068 2000 1194 1.38 1373 1228 1.48 1472 1262 1.58 1511 1327 1.78 1702 1436 1.98 1894 1440 2.18 2229

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied motor drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 1000 and maximum continuous bhp is 1.00.

*Motor drive range: 835 to 1185 rpm. All other rpms require field-supplied drive.

Refer to page 51 for general Fan Performance notes.

548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 665 0.25 263 779 0.36 378 872 0.48 504 957 0.60 630 1028 0.69 725 1300 699 0.30 315 809 0.42 441 902 0.55 578 984 0.67 704 1058 0.80 841 1400 735 0.36 378 840 0.48 504 933 0.62 651 1011 0.75 788 1086 0.89 885 1500 770 0.42 441 873 0.55 578 963 0.69 725 1041 0.84 858 1113 0.99 985 1600 835 0.49 515 907 0.63 662 993 0.77 787 1072 0.93 950 1141 1.09 1084 1700 873 0.57 599 941 0.72 757 1024 0.87 889 1103 1.04 1063 1171 1.20 1194 1800 881 0.66 693 976 0.81 851 1057 0.97 991 1132 1.14 1165 1202 1.32 1313 1900 919 0.75 788 1011 0.92 967 1091 1.08 1104 1162 1.25 1277 1232 1.45 1442 2000 958 0.86 904 1046 1.03 1082 1125 1.21 1237 1195 1.38 1410 1262 1.58 1572

548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1083 0.74 778 1134 0.80 935 1185 0.88 965 1331 0.99 1000 1374 1.09 1083 1300 1121 0.89 935 1171 0.94 988 1219 1.00 999 1268 1.10 1029 1309 1.21 1203 1400 1153 1.00 976 1210 1.12 1071 1257 1.17 1105 1307 1.25 1190 1349 1.37 1367 1500 1180 1.13 1081 1241 1.27 1215 1295 1.37 1294 1339 1.43 1350 1382 1.57 1564 1600 1207 1.25 1196 1269 1.40 1339 1326 1.54 1454 1376 1.65 1558 1420 1.81 1805 1700 1235 1.37 1310 1296 1.53 1463 1354 1.70 1605 1407 1.84 1738 1452 2.02 2013 1800 1263 1.49 1425 1323 1.57 1597 1381 1.85 1757 1436 2.02 1907 1482 2.22 2210 1900 1294 1.63 1559 1351 1.81 1731 1408 2.00 1889 1463 2.19 2068 — — — 2000 1325 1.78 1702 1362 1.97 1884 1436 2.16 2040 1489 2.36 2229 — — —

Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.4 and the maximum continuous watts are 2120.

*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.

Show 10 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 34 of the Bryant 549B user manual — 548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Page 34 · click to enlarge
Page 34

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1500 0.88 0.67 750 1.20 0.71 791 1.19 0.70 782 1.36 0.76 845 1.38 0.79 875 1.44 0.85 949 1600 0.68 0.70 780 1.04 0.74 824 1.04 0.74 821 1.22 0.79 883 1.25 0.82 913 1.33 0.89 988 1700 0.51 0.73 810 0.89 0.77 857 0.89 0.77 861 1.09 0.83 921 1.13 0.85 950 1.22 0.92 1027 1800 0.35 0.75 839 0.73 0.80 891 0.74 0.81 900 0.96 0.86 959 1.00 0.89 988 1.11 0.96 1066 1900 0.26 0.78 873 0.58 0.83 924 0.59 0.84 940 0.86 0.90 997 0.88 0.92 1025 1.00 0.99 1105 2000 0.18 0.81 905 0.42 0.86 957 0.44 0.88 979 0.73 0.93 1035 0.78 0.95 1063 0.92 1.03 1144 2100 0.08 0.84 940 0.27 0.89 990 0.29 0.91 1018 0.59 0.96 1073 0.63 0.99 1101 0.81 1.06 1183 2200 — — — 0.19 0.92 1023 0.19 0.93 1035 0.46 1.00 1111 0.49 1.02 1138 0.69 1.10 1222 2300 — — — 0.11 0.95 1056 0.11 0.97 1076 0.34 1.03 1149 0.41 1.06 1176 0.59 1.13 1261 2400 — — — 0.03 0.98 1096 0.04 1.00 1113 0.19 1.07 1187 0.22 1.09 1213 0.43 1.17 1300 2500 — 0.09 1.10 1225 0.12 1.12 1251 0.34 1.20 1340

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 730 0.34 347 789 0.40 409 896 0.53 542 990 0.67 685 1072 0.83 848 1600 770 0.40 409 826 0.46 470 931 0.61 623 1020 0.75 766 1101 0.91 930 1700 811 0.47 480 865 0.54 552 966 0.69 705 1051 0.84 858 1133 1.01 1032 1800 852 0.55 562 905 0.62 634 1002 0.78 797 1084 0.93 950 1163 1.10 1124 1900 894 0.54 552 945 0.72 736 1037 0.88 899 1119 1.04 1063 1194 1.21 1237 2000 936 0.74 756 984 0.82 838 1072 0.98 1001 1154 1.16 1185 1226 1.33 1359 2100 978 0.85 869 1024 0.93 950 1108 1.10 1124 1192 1.29 1318 1259 1.47 1502 2200 1021 0.97 991 1064 1.05 1073 1145 1.22 1247 1225 1.43 1461 1294 1.62 1656 2300 1064 1.10 1124 1104 1.18 1206 1183 1.36 1390 1260 1.57 1604 1330 1.78 1819 2400 1107 1.24 1267 1145 1.32 1349 1222 1.45 1482 1296 1.73 1768 1365 1.94 1983 2500 1150 1.39 1420 1186 1.48 1512 1262 1.68 1717 1331 1.80 1921 1400 2.12 2166

548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1153 1.00 1022 1221 1.17 1196 1256 1.30 1328 1280 1.32 1349 1320 1.22 1400 1600 1178 1.09 1114 1252 1.27 1298 1311 1.45 1482 1340 1.58 1615 1380 1.61 1645 1700 1205 1.18 1206 1278 1.37 1400 1345 1.57 1604 1397 1.76 1799 1424 1.89 1931 1800 1235 1.29 1318 1303 1.48 1512 1371 1.69 1727 1433 1.90 1942 1480 2.09 2136 1900 1266 1.40 1431 1330 1.59 1625 1396 1.80 1850 1460 2.03 2074 1517 2.25 2299 2000 1297 1.53 1564 1362 1.73 1768 1422 1.94 1983 1485 2.16 2207 1544 2.40 2453 2100 1327 1.66 1696 1393 1.80 1911 1452 2.08 2126 1510 2.31 2361 1569 2.55 2606 2200 1359 1.80 1850 1423 2.02 2064 1483 2.24 2289 1538 2.46 2514 1595 2.71 2769 2300 1392 1.97 2013 1454 2.18 2228 1515 2.41 2463 1569 2.64 2698 1622 2.88 2943 2400 1426 2.15 2197 1485 2.36 2412 1544 2.59 2647 1601 2.84 2902 1652 3.07 3137 2500 1461 2.34 2391 1518 2.55 2606 1575 2.78 2841 1631 3.03 3096 1684 3.28 3352

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 1.30 for single-phase units and 2.40 for 3-phase units.

*Motor drive range: 900 to 1300 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 6 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 35 of the Bryant 549B user manual — 548F072 (6 TONS)* — STANDARD MOTOR (BELT DRIVE)
Page 35 · click to enlarge
Page 35

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 808 0.42 429 914 0.56 572 1001 0.69 705 1084 0.85 869 1168 1.01 1032 1600 846 0.49 501 950 0.64 645 1034 0.78 797 1111 0.94 961 1194 1.11 1134 1700 884 0.57 582 983 0.72 736 1068 0.88 899 1145 1.03 1053 1218 1.21 1237 1800 924 0.66 674 1018 0.82 838 1105 0.98 1001 1179 1.13 1155 1246 1.32 1349 1900 965 0.76 777 1057 0.92 940 1143 1.10 1124 1212 1.26 1288 1280 1.43 1461 2000 1008 0.87 889 1096 1.04 1063 1177 1.22 1247 1247 1.40 1431 1300 1.57 1604 2100 1051 0.99 1012 1136 1.17 1196 1210 1.35 1380 1284 1.54 1574 1347 1.72 1758 2200 1095 1.12 1145 1173 1.30 1328 1245 1.49 1523 1322 1.70 1737 1380 1.89 1931 2300 1140 1.26 1288 1210 1.47 1502 1284 1.65 1686 1356 1.80 1901 1418 2.07 2115 2400 1185 1.41 1441 1249 1.61 1645 1323 1.80 1860 1389 2.03 2074 1456 2.26 2310 2500 1231 1.57 1604 1289 1.78 1819 1363 2.00 2044 1424 2.22 2269 1500 2.45 2504

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1199 1.19 1216 1126 1.46 1492 1250 1.69 1757 1301 1.91 1944 1349 2.12 2164 1600 1263 1.28 1308 1275 1.49 1523 1299 1.78 1800 1352 2.01 2047 1401 2.23 2280 1700 1295 1.39 1420 1351 1.58 1615 1352 1.80 1850 1407 2.03 2070 1459 2.26 2305 1800 1319 1.52 1553 1389 1.71 1747 1435 1.91 1952 1494 2.15 2197 1548 2.40 2446 1900 1343 1.64 1676 1415 1.80 1891 1478 2.05 2095 1538 2.31 2358 1594 2.57 2625 2000 1374 1.77 1809 1438 1.99 2034 1505 2.21 2258 1566 2.49 2542 1624 2.77 2830 2100 1409 1.91 1952 1465 2.14 2167 1533 2.45 2501 1596 2.77 2821 1654 3.08 3141 2200 1442 2.08 2126 1498 2.30 2350 1568 2.64 2688 1632 2.97 3031 1691 3.31 3375 2300 1475 2.26 2310 1554 2.64 2698 1627 3.03 3091 1693 3.42 3486 1755 3.81 3881 2400 1565 2.47 2524 1649 2.89 2948 1726 3.31 3379 — 2500 1596 2.95 3010 1682 3.45 3522 1760 3.96 4036 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.9 and the maximum continuous watts are 2562.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.

Refer to page 51 for general Fan Performance notes.

548F072 (6 TONS)* — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 852 0.55 562 905 0.62 615 1002 0.78 739 1084 0.93 859 1163 1.10 998 1900 894 0.64 630 945 0.72 692 1037 0.88 818 1119 1.04 948 1194 1.21 1089 2000 936 0.74 708 984 0.82 771 1072 0.98 899 1154 1.16 1047 1226 1.33 1190 2100 978 0.85 795 1024 0.93 859 1108 1.10 998 1190 1.29 1156 1259 1.47 1310 2200 1021 0.97 891 1064 1.05 956 1145 1.22 1097 1225 1.43 1275 1294 1.62 1439 2300 1064 1.10 998 1104 1.18 1064 1183 1.36 1216 1260 1.57 1396 1330 1.78 1578 2400 1107 1.24 1114 1145 1.32 1182 1222 1.52 1353 1296 1.73 1534 1365 1.94 1718 2500 1150 1.39 1241 1186 1.48 1318 1262 1.68 1491 1331 1.89 1674 1400 2.12 1875 2600 1193 1.56 1387 1228 1.65 1465 1301 1.86 1648 1367 2.07 1831 1435 2.31 2041 2700 1237 1.74 1543 1269 1.83 1621 1341 2.05 1814 1404 2.26 1997 1471 2.51 2214 2800 1280 1.94 1718 1311 2.03 1796 1381 2.25 1989 1442 2.47 2180 1506 2.72 2394 2900 1324 2.15 1901 1354 2.24 1980 1420 2.47 2180 1481 2.69 2369 1542 2.94 2579 3000 1368 2.37 2093 1396 2.46 2171 1460 2.69 2369 1521 2.93 2571 — — —

548F072 (6 TONS)* — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1235 1.29 1156 1303 1.48 1318 1371 1.69 1499 1433 1.90 1638 1900 1266 1.40 1250 1330 1.59 1413 1396 1.81 1604 1460 2.03 1796 2000 1297 1.53 1361 1362 1.73 1534 1422 1.94 1718 1485 2.16 1910 2100 1327 1.66 1473 1393 1.87 1656 1452 2.08 1840 1510 2.31 2041 2200 1359 1.81 1604 1423 2.02 1779 1483 2.24 1980 1538 2.46 2171 2300 1392 1.97 1744 1454 2.18 1927 1515 2.41 2128 1569 2.64 2326 2400 1426 2.15 1901 1485 2.36 2084 1544 2.59 2283 1601 2.84 2459 2500 1461 2.34 2067 1518 2.55 2249 1575 2.78 2445 — — — 2600 1497 2.54 2240 1552 2.76 2428 — 2700 1532 2.75 2420 — 2800 — 2900 — 3000 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 1070 to 1460 rpm. All other rpms require field-supplied drive.

Refer to page 51 for general Fan Performance notes.

Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 36 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 36 · click to enlarge
Page 36

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 978 0.66 700 1063 0.82 771 1147 0.97 891 1248 1.20 1081 1322 1.33 1190 1900 1023 0.78 779 1097 0.91 843 1175 1.11 1006 1266 1.29 1158 1356 1.47 1310 2000 1068 0.90 867 1132 1.01 924 1218 1.23 1106 1303 1.41 1258 1397 1.52 1353 2100 1115 1.00 998 1180 1.17 1056 1261 1.35 1207 1340 1.53 1361 1428 1.66 1473 2200 1159 1.15 1081 1214 1.28 1148 1310 1.52 1353 1375 1.63 1447 1459 1.80 1595 2300 1202 1.29 1140 1248 1.38 1233 1358 1.69 1499 1410 1.72 1526 1488 1.93 1709 2400 1237 1.41 1224 1292 1.55 1378 1392 1.81 1604 1460 1.90 1683 1532 2.14 1892 2500 1272 1.53 1335 1335 1.71 1517 1427 1.94 1718 1518 2.16 1910 1575 2.35 2076 2600 1320 1.68 1482 1368 1.81 1604 1458 2.06 1823 1562 2.42 2136 1620 2.59 2283 2700 1361 1.82 1595 1400 1.91 1691 1490 2.19 1936 1602 2.64 2326 1666 2.85 2504 2800 1402 1.95 1639 1439 2.08 1840 1543 2.43 2145 1642 2.86 2512 1775 3.62 3290 2900 1446 2.16 1814 1477 2.16 1989 1585 2.65 2335 1753 3.58 3262 — — — 3000 1489 2.36 2032 1529 2.52 2223 1598 2.73 2444 1767 3.69 3360 — — —

548F072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1395 1.46 1301 1475 1.56 1387 1542 1.71 1517 1607 1.94 1761 1667 2.16 1967 1900 1430 1.58 1404 1504 1.69 1499 1556 1.82 1613 1621 2.06 1874 1682 2.30 2093 2000 1459 1.67 1482 1532 1.82 1613 1588 1.97 1744 1655 2.23 2029 1717 2.49 2266 2100 1489 1.80 1595 1567 1.99 1761 1626 2.16 1910 1694 2.44 2224 1758 2.73 2485 2200 1528 1.95 1726 1603 2.17 1919 1666 2.37 2093 1736 2.68 2441 — — — 2300 1561 2.13 1884 1637 2.35 2076 1710 2.54 2272 1782 2.87 2616 — — — 2400 1584 2.28 2015 1671 2.55 2249 1756 2.70 2467 — 2500 1633 2.53 2232 1698 2.72 2405 1779 3.13 2848 — 2600 1675 2.77 2436 1768 3.26 2964 — 2700 1775 3.45 3141 — 2800 — 2900 — 3000 —

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.9 and the maximum continuous watts are 2562.

*Motor drive range: 1300 to 1685 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 37 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 37 · click to enlarge
Page 37

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F090 (71/2 TONS)* — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 511 0.52 539 592 0.74 708 659 0.95 875 722 1.19 1072 778 1.43 1275 829 1.68 1491 2300 518 0.55 562 599 0.77 731 665 0.98 899 727 1.22 1097 783 1.47 1310 834 1.72 1526 2400 534 0.61 607 613 0.84 787 677 1.06 965 738 1.30 1165 794 1.55 1378 844 1.81 1604 2500 549 0.67 653 627 0.90 835 690 1.14 1031 750 1.38 1233 805 1.64 1456 855 1.91 1691 2550 557 0.71 684 633 0.94 867 697 1.18 1064 756 1.42 1267 811 1.69 1499 861 1.96 1735 2600 565 0.74 708 639 0.97 891 703 1.22 1097 761 1.46 1301 816 1.74 1543 866 2.01 1779 2700 581 0.81 763 652 1.04 948 717 1.31 1173 773 1.55 1378 827 1.83 1621 878 2.12 1875 2800 597 0.89 827 665 1.12 1014 733 1.40 1250 786 1.66 1473 839 1.93 1709 889 2.23 1971 2900 613 0.97 891 679 1.20 1081 745 1.50 1335 799 1.76 1560 850 2.04 1805 900 2.34 2067 3000 629 1.06 965 694 1.29 1156 759 1.59 1413 812 1.88 1665 862 2.15 1901 911 2.46 2171 3100 646 1.15 1039 709 1.39 1241 772 1.70 1508 825 1.99 1761 875 2.28 2015 923 2.58 2275 3200 662 1.25 1123 724 1.50 1335 785 1.80 1595 840 2.11 1866 887 2.41 2128 934 2.71 2386 3300 679 1.35 1207 740 1.61 1430 798 1.91 1691 854 2.24 1980 900 2.54 2240 946 2.85 2504 3400 696 1.46 1301 756 1.73 1534 811 2.02 1788 868 2.37 2093 914 2.69 2369 959 3.00 2629 3500 712 1.57 1396 771 1.85 1639 824 2.14 1892 881 2.50 2206 928 2.84 2495 971 3.16 2759 3600 729 1.69 1499 787 1.98 1753 839 2.21 2006 894 2.64 2326 942 2.99 2620 984 3.22 2886 3700 746 1.85 1613 803 2.12 1875 854 2.42 2136 907 2.78 2445 956 3.15 2751 997 3.49 3017 3750 755 1.89 1674 811 2.20 1945 862 2.49 2197 914 2.85 2504 963 3.23 2815 — — —

548F090 (71/2 TONS)* — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 884 1.97 1744 937 2.33 2058 947 2.66 2343 1022 3.10 2710 2300 885 2.00 1770 939 2.36 2084 979 2.69 2369 1025 3.12 2727 2400 892 2.08 1840 944 2.40 2119 987 2.76 2428 1039 3.20 2791 2500 902 2.18 1927 949 2.48 2188 1002 2.84 2495 1041 3.25 2831 2550 908 2.24 1980 953 2.53 2232 1003 2.87 2521 1045 3.28 2854 2600 913 2.29 2023 957 2.58 2275 1004 2.91 2554 1050 3.31 2878 2700 924 2.40 2120 967 2.70 2377 1010 3.01 2637 1056 3.37 2925 2800 935 2.52 2223 978 2.62 2479 1019 3.13 2735 1061 3.47 3002 2900 946 2.65 2335 989 2.96 2595 1030 3.27 2847 — — — 3000 957 2.78 2445 1000 3.09 2702 1040 3.41 2956 — — — 3100 968 2.91 2554 1011 3.24 2832 — 3200 980 3.04 2661 1022 3.38 2933 — 3300 991 3.18 2775 — 3400 1003 3.32 2886 — 3500 1014 3.48 3009 — 3600 — 3700 — 3750 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Standard motor drive range: 590 to 840 rpm. Alternate motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 38 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 38 · click to enlarge
Page 38

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 514 0.55 562 593 0.76 723 662 0.99 907 724 1.22 1097 781 1.48 1318 2300 521 0.57 577 600 0.79 747 668 1.02 932 730 1.26 1131 786 1.50 1335 2400 536 0.63 623 613 0.85 795 680 1.09 989 741 1.34 1199 796 1.59 1413 2500 551 0.69 669 626 0.93 859 693 1.17 1056 753 1.43 1275 808 1.69 1499 2550 559 0.72 692 634 0.97 891 700 1.21 1089 759 1.48 1318 814 1.74 1543 2600 567 0.75 716 641 1.00 916 706 1.25 1123 764 1.52 1353 819 1.79 1587 2700 582 0.83 779 655 1.08 981 719 1.34 1199 776 1.61 1430 831 1.89 1674 2800 598 0.90 835 670 1.17 1056 732 1.43 1275 789 1.71 1617 842 2.00 1770 2900 614 0.98 899 684 1.25 1123 745 1.53 1361 802 1.81 1604 854 2.11 1866 3000 630 1.07 973 699 1.35 1207 759 1.63 1147 815 1.92 1700 866 2.23 1971 3100 646 1.16 1047 714 1.45 1292 773 1.74 1543 828 2.04 1805 878 2.35 2076 3200 662 1.28 1131 729 1.55 1378 787 1.86 1648 841 2.16 1910 891 2.48 2188 3300 679 1.36 1216 744 1.66 1473 801 1.98 1753 854 2.29 2023 904 2.61 2300 3400 695 1.47 1310 759 1.78 1578 816 2.10 1868 867 2.42 2136 917 2.75 2420 3500 712 1.59 1413 774 1.90 1683 830 2.23 1971 881 2.56 2257 930 2.90 2546 3600 729 1.71 1617 790 2.03 1796 845 2.37 2093 895 2.71 2386 943 3.05 2670 3700 745 1.84 1630 805 2.17 1919 860 2.52 2223 909 2.87 2521 956 3.22 2807 3750 754 1.91 1691 813 2.24 1980 868 2.59 2283 917 2.95 2587 963 3.30 2870

548F090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 841 1.81 1604 902 2.25 1989 939 2.60 2292 979 2.94 2589 1015 3.29 2892 2300 843 1.83 1621 905 2.28 2015 943 2.52 2309 983 2.96 2609 1020 3.31 2914 2400 848 1.88 1665 910 2.31 2041 952 2.74 2411 992 3.10 2729 1029 3.46 3048 2500 859 1.96 1735 912 2.31 2050 963 2.81 2470 1004 3.18 2798 1041 3.55 3126 2550 864 2.01 1779 915 2.34 2067 968 2.81 2479 1009 3.18 2798 1047 3.55 3126 2600 869 2.06 1823 918 2.37 2093 973 2.81 2487 1014 3.18 2798 1052 3.55 3126 2700 880 2.17 1919 927 2.47 2180 976 2.84 2495 1017 3.21 2828 1055 3.59 3159 2800 892 2.29 2023 938 2.58 2275 983 2.92 2562 1024 3.30 2908 1063 3.69 3248 2900 903 2.42 2136 949 2.71 2386 993 3.03 2653 1035 3.43 3017 1074 3.83 3370 3000 915 2.54 2240 961 2.85 2504 1003 3.17 2767 1045 3.59 3157 1084 4.01 3526 3100 926 2.67 2352 972 3.00 2629 1015 3.32 2886 1058 3.76 3306 1097 4.20 3693 3200 938 2.81 2470 983 3.14 2743 1026 3.47 3002 1069 3.93 3456 — — — 3300 950 2.95 2587 995 3.30 2870 1043 3.80 3341 — 3400 963 3.10 2710 1007 3.45 2987 1055 3.97 3493 — 3500 976 3.25 2831 1030 3.82 3362 — 3600 988 3.41 2956 1043 4.01 3528 — 3700 1019 3.90 3431 — 3750 1026 4.00 3517 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 3.7 and the maximum continuous watts are 3313.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 39 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 39 · click to enlarge
Page 39

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F102 (8 TONS)* — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 557 0.71 684 633 0.94 867 697 1.18 1064 756 1.42 1267 811 1.69 1499 861 1.96 1735 2600 565 0.74 708 639 0.97 891 703 1.22 1097 761 1.46 1301 816 1.74 1543 866 2.01 1779 2700 581 0.81 763 652 1.04 948 717 1.31 1173 773 1.55 1378 827 1.83 1621 878 2.12 1875 2800 597 0.89 827 665 1.12 1014 733 1.40 1250 786 1.66 1473 839 1.93 1709 889 2.23 1971 2900 613 0.97 891 679 1.20 1081 745 1.50 1335 799 1.76 1560 850 2.04 1805 900 2.34 2067 3000 629 1.06 965 694 1.29 1156 759 1.59 1413 812 1.88 1665 862 2.15 1901 911 2.46 2171 3100 646 1.15 1039 709 1.39 1241 772 1.70 1508 825 1.99 1761 875 2.28 2015 923 2.58 2275 3200 662 1.25 1123 724 1.50 1335 785 1.80 1595 840 2.11 1866 887 2.41 2128 934 2.71 2386 3300 679 1.35 1207 740 1.61 1430 798 1.91 1691 854 2.24 1980 900 2.54 2240 946 2.85 2504 3400 696 1.46 1301 756 1.73 1534 811 2.02 1788 868 2.37 2093 914 2.69 2369 959 3.00 2629 3500 712 1.57 1396 771 1.85 1639 824 2.14 1892 881 2.50 2206 928 2.84 2495 971 3.16 2759 3600 729 1.69 1499 787 1.98 1753 839 2.27 2006 894 2.64 2326 942 2.99 2620 984 3.32 2886 3700 746 1.82 1613 803 2.12 1875 854 2.42 2136 907 2.78 2445 956 3.15 2751 997 3.49 3017 3750 755 1.89 1674 811 2.20 1945 862 2.49 2197 914 2.85 2504 963 3.23 2815 — — — 3800 763 1.95 1726 819 2.27 2006 869 2.56 2257 920 2.92 2562 970 3.31 2878 — — — 3900 780 2.09 1849 835 2.42 2136 884 2.72 2394 933 3.07 2686 983 3.48 3009 — — — 4000 796 2.23 1971 851 2.56 2257 900 2.89 2537 946 3.23 2815 — 4100 813 2.39 2110 867 2.74 2411 915 3.06 2678 960 3.40 2948 — 4200 830 2.55 2249 883 2.91 2554 931 3.24 2823 — 4250 839 2.63 2317 892 3.00 2629 939 3.34 2902 —

548F102 (8 TONS)* — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 908 2.24 1980 953 2.53 2232 1003 2.87 2521 1045 3.28 2854 2600 913 2.29 2023 957 2.58 2275 1004 2.91 2554 1050 3.31 2878 2700 924 2.40 2120 967 2.70 2377 1010 3.01 2637 1056 3.37 2925 2800 935 2.52 2223 978 2.62 2479 1019 3.13 2735 1061 3.41 3002 2900 946 2.65 2335 989 2.96 2595 1030 3.27 2847 — — — 3000 957 2.78 2445 1000 3.09 2702 1040 3.41 2956 — — — 3100 968 2.91 2554 1011 3.24 2832 — 3200 980 3.04 2661 1022 3.38 2933 — 3300 991 3.18 2775 — 3400 1003 3.52 2886 — 3500 1014 3.48 3009 — 3600 — 3700 — 3750 — 3800 — 3900 — 4000 — 4100 — 4200 — 4250 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 40 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 40 · click to enlarge
Page 40

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 559 0.72 692 634 0.97 891 700 1.21 1089 759 1.48 1318 814 1.74 1543 2600 567 0.76 716 641 1.00 916 706 1.25 1123 764 1.52 1353 819 1.79 1587 2700 582 0.83 779 655 1.08 981 719 1.34 1199 776 1.61 1430 831 1.89 1674 2800 598 0.90 835 670 1.17 1056 732 1.43 1275 789 1.71 1517 842 2.00 1770 2900 614 0.98 899 684 1.25 1123 745 1.53 1361 802 1.81 1604 854 2.11 1866 3000 630 1.07 973 690 1.35 1207 759 1.63 1147 816 1.92 1700 866 2.23 1971 3100 646 1.16 1047 714 1.45 1292 773 1.74 1543 828 2.04 1805 878 2.35 2076 3200 662 1.26 1131 729 1.55 1378 787 1.86 1648 841 2.16 1910 891 2.48 2188 3300 679 1.36 1216 744 1.66 1473 801 1.98 1753 854 2.29 2023 904 2.61 2300 3400 695 1.47 1310 759 1.78 1578 816 2.10 1958 867 2.42 2136 917 2.75 2420 3500 712 1.59 1413 774 1.90 1683 830 2.23 1971 881 2.56 2257 930 2.90 2546 3600 729 1.71 1517 790 2.03 1796 845 2.37 2093 895 2.71 2386 943 3.05 2670 3700 745 1.84 1630 805 2.17 1919 860 2.52 2223 909 2.87 2521 956 3.22 2807 3750 754 1.91 1691 813 2.24 1980 868 2.59 2283 917 2.95 2587 963 3.30 2870 3800 762 1.98 1753 821 2.31 2041 875 2.66 2343 924 3.03 2653 970 3.38 2933 3900 779 2.12 1875 836 2.46 2171 890 2.82 2479 938 3.19 2783 981 3.65 3209 4000 796 2.27 2006 852 2.61 2300 905 2.98 2612 953 3.37 2925 996 3.85 3390 4100 813 2.42 2136 868 2.78 2445 920 3.15 2751 974 3.74 3294 — — — 4200 830 2.59 2283 884 2.95 2587 935 3.33 2894 990 3.96 3482 — — — 4250 839 2.68 2360 890 3.04 2661 965 3.88 3412 —

548F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 864 2.01 1779 915 2.34 2067 968 2.81 2479 991 3.02 2654 1012 3.21 2827 2600 869 2.06 1823 918 2.37 2093 973 2.81 2487 996 3.02 2654 1017 3.21 2827 2700 880 2.17 1919 927 2.47 2180 976 2.84 2495 999 3.05 2682 1021 3.25 2857 2800 892 2.29 2023 938 2.58 2275 983 2.92 2562 1006 3.13 2758 1028 3.34 2938 2900 903 2.42 2136 949 2.71 2386 993 3.03 2653 1017 3.25 2862 1038 3.46 3048 3000 915 2.54 2240 961 2.85 2504 1003 3.17 2767 1027 3.40 2994 1049 3.62 3189 3100 926 2.67 2352 972 3.00 2629 1016 3.32 2886 1040 3.56 3136 1062 3.80 3340 3200 938 2.81 2470 983 3.14 2743 1026 3.47 3002 1050 3.72 3277 1073 3.97 3491 3300 950 2.95 2587 995 3.30 2870 1022 3.58 3146 1046 3.84 3377 1069 4.09 3597 3400 963 3.10 2710 1007 3.45 2987 1034 3.74 3289 1059 4.01 3530 — — — 3500 976 3.25 2831 1007 3.56 3137 1034 3.85 3399 1058 4.15 3648 — — — 3600 988 3.41 2956 1019 3.74 3292 1047 4.05 3566 — 3700 992 3.59 3161 1023 3.94 3467 — 3750 999 3.68 3240 1030 4.04 3554 — 3800 1006 3.77 3318 1038 4.14 3640 — 3900 1017 4.07 3580 — 4000 — 4100 — 4200 — 4250 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 3.7 and the maximum continuous watts are 3313.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 41 of the Bryant 549B user manual — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
Page 41 · click to enlarge
Page 41

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

548F120 (10 TONS)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 532 0.64 630 605 0.81 763 670 0.97 891 725 1.12 1014 778 1.28 1148 825 1.43 1275 3100 544 0.70 677 616 0.86 803 680 1.03 940 735 1.20 1081 787 1.36 1216 835 1.52 1353 3200 557 0.75 716 628 0.93 859 690 1.10 998 746 1.28 1148 796 1.44 1284 844 1.61 1430 3300 570 0.81 763 639 0.99 907 700 1.18 1064 757 1.36 1216 805 1.52 1353 854 1.70 1508 3400 583 0.88 818 651 1.06 965 711 1.25 1123 767 1.44 1284 815 1.61 1430 863 1.79 1587 3500 596 0.94 867 663 1.14 1031 721 1.33 1190 777 1.52 1353 826 1.71 1517 871 1.88 1665 3600 609 1.01 924 674 1.22 1097 732 1.42 1267 787 1.61 1430 836 1.80 1595 880 1.98 1753 3700 622 1.09 989 686 1.30 1165 744 1.50 1335 797 1.70 1508 847 1.91 1691 890 2.09 1849 3800 635 1.16 1047 698 1.39 1241 755 1.59 1413 808 1.80 1595 857 2.01 1779 901 2.20 1945 3900 649 1.25 1123 713 1.48 1318 767 1.68 1491 818 1.90 1683 867 2.11 1866 912 2.32 2050 4000 662 1.33 1190 722 1.57 1396 778 1.78 1578 829 2.01 1779 878 2.22 1962 922 2.44 2203 4100 675 1.42 1267 734 1.67 1482 790 1.89 1674 839 2.12 1875 888 2.33 2058 933 2.56 2309 4200 689 1.52 1353 746 1.77 1569 801 1.99 1761 851 2.23 1971 898 2.45 2212 943 2.69 2424 4300 702 1.61 1430 759 1.88 1665 813 2.11 1866 862 2.34 2067 908 2.58 2326 953 2.81 2533 4400 715 1.72 1526 772 1.99 1761 825 2.22 1962 873 2.46 2221 919 2.71 2442 963 2.94 2651 4500 729 1.83 1621 785 2.10 1858 837 2.35 2076 885 2.59 2335 929 2.85 2569 973 3.08 2782 4600 742 1.94 1718 797 2.22 1962 848 2.48 2238 896 2.72 2451 940 2.98 2688 984 3.22 2914 4700 756 2.06 1823 810 2.34 2067 860 2.61 2353 908 2.86 2578 951 3.12 2727 994 3.38 3068 4800 770 2.18 1927 823 2.46 2221 872 2.75 2505 919 3.00 2707 963 3.27 2847 1003 3.43 3202 4900 783 2.31 2041 836 2.60 2344 884 2.89 2605 931 3.14 2838 974 3.41 2956 1013 3.59 3349 5000 797 2.44 2203 849 2.73 2460 897 3.04 2661 943 3.30 2870 984 3.44 3211 1023 3.75 3501

548F120 (10 TONS)* (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 874 1.60 1422 926 1.82 1613 974 2.11 1920 1012 2.41 2134 3100 880 1.68 1491 933 1.87 1656 983 2.16 1963 1017 2.44 2177 3200 888 1.77 1569 934 1.94 1718 988 2.18 1980 1025 2.47 2230 3300 897 1.86 1648 940 2.03 1853 989 2.24 2031 1032 2.53 2282 3400 907 1.97 1744 947 2.14 1946 991 2.32 2099 1038 2.57 2318 3500 916 2.07 1831 956 2.25 2039 997 2.43 2195 1043 2.64 2380 3600 926 2.18 1927 966 2.41 2134 1004 2.54 2291 1045 2.74 2478 3700 934 2.28 2015 976 2.48 2238 1013 2.66 2397 1051 2.85 2569 3800 943 2.41 2160 985 2.60 2334 1023 2.79 2514 1059 2.98 2688 3900 952 2.51 2265 994 2.72 2451 1032 2.92 2633 1068 3.12 2819 4000 962 2.63 2371 1003 2.84 2560 1042 3.06 2763 1078 3.26 2952 4100 973 2.77 2496 1011 2.97 2679 1051 3.20 2895 1087 3.41 3097 4200 983 2.91 2624 1021 3.11 2810 1060 3.34 3029 1090 3.51 3276 4300 994 3.05 2754 1031 3.25 2943 1068 3.48 3166 1097 3.70 3453 4400 1004 3.19 2885 1042 3.41 3097 1080 3.63 3388 1105 3.91 3642 4500 1015 3.33 2020 1051 3.45 3218 1090 3.75 3493 1112 4.12 3843 4600 1025 3.48 3166 1060 3.61 3369 1100 3.92 3655 1119 4.35 4057 4700 1037 3.58 3335 1070 3.84 3325 1111 4.10 3822 1126 4.59 4284 4800 1048 3.75 3494 1080 3.95 3686 1121 4.28 3995 1133 4.85 4523 4900 1060 3.92 3659 1089 4.13 3854 1132 4.48 4174 1140 5.12 4775 5000 1072 4.11 3830 1099 4.32 4027 1144 4.67 4359 — — —

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates high-static motor and drive are required. 2. Maximum usable watts input is 2120 with standard motor, 2615 with alternate motor, and 4400 for the high-static motor. Maximum continuous bhp is 2.40 with standard motor, 2.90 with alternate motor, and 5.25 for the high-static motor.

*Standard motor drive range: 685 to 935 rpm. Alternate motor drive range: 835 to 1085 rpm. High-static motor drive range is 830 to 1130 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm · Airflow · (Cfm)
Page 42 of the Bryant 549B user manual — 548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Page 42 · click to enlarge
Page 42
Bryant 549B — ACCESSORY DIMENSIONS diagram (page 42)
Fig. 13

Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 900 0.72 0.21 253 0.75 0.23 277 0.73 0.26 307 0.76 0.31 363 1000 0.67 0.23 270 0.69 0.25 292 0.70 0.27 321 0.71 0.32 374 1100 0.61 0.24 287 0.63 0.26 307 0.64 0.28 335 0.65 0.33 385 1200 0.57 0.26 304 0.58 0.27 323 0.56 0.29 349 0.59 0.34 397 1300 0.51 0.27 321 0.53 0.29 338 0.53 0.31 364 0.54 0.34 408 1400 0.44 0.29 338 0.46 0.30 354 0.47 0.32 378 — — — 1500 0.39 0.30 355 0.41 0.31 369 0.43 0.33 392 — — —

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 526 0.06 70 584 0.08 99 656 0.12 139 734 0.22 219 818 0.25 269 875 0.27 289 1000 570 0.09 109 627 0.13 149 738 0.19 189 800 0.26 259 848 0.29 288 895 0.31 308 1100 614 0.13 149 670 0.16 189 758 0.23 229 812 0.29 288 863 0.32 308 914 0.35 348 1200 658 0.16 189 710 0.23 229 780 0.28 279 840 0.32 318 889 0.36 358 938 0.40 398 1300 703 0.20 239 752 0.27 269 808 0.32 318 868 0.37 368 916 0.41 408 963 0.45 448 1400 725 0.29 288 776 0.31 308 845 0.38 378 891 0.42 418 937 0.47 467 983 0.51 507 1500 755 0.33 328 816 0.38 378 870 0.43 428 924 0.48 477 969 0.53 527 1014 0.58 577

548F036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 0.7 0.8 0.9 1.0 1.1 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 924 0.32 308 953 0.35 348 989 0.38 388 1028 0.42 438 1074 0.49 487 1120 0.54 537 1000 936 0.35 348 977 0.39 388 1020 0.44 438 1064 0.48 477 1124 0.54 537 1185 0.60 597 1100 960 0.39 388 1005 0.43 428 1052 0.49 487 1100 0.52 527 1163 0.59 587 1225 0.65 647 1200 960 0.45 388 1038 0.50 497 1076 0.53 527 1136 0.59 577 1201 0.65 647 1266 0.72 716 1300 1012 0.51 507 1061 0.56 557 1090 0.61 607 1172 0.65 647 1239 0.72 716 1306 0.79 786 1400 1027 0.56 557 1071 0.60 597 1108 0.67 666 1208 0.70 706 1278 0.79 786 1347 0.87 865 1500 1056 0.63 627 1097 0.68 676 1117 0.70 696 1245 0.74 776 1315 0.87 865 1385 0.96 955

Refer to page 51 for general Fan Performance notes. NOTES:

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. Maximum usable watts input is 1000 and maximum continuous bhp is 1.00.

*Motor drive range: 760 to 1000 rpm. All other rpms require field-supplied drive.

548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 584 0.08 99 734 0.22 219 875 0.27 269 953 0.35 348 1028 0.42 438 1000 627 0.13 149 800 0.26 259 895 0.31 308 977 0.39 388 1064 0.48 477 1100 670 0.16 189 812 0.29 288 914 0.35 348 1005 0.43 428 1100 0.52 527 1200 710 0.23 229 840 0.32 318 938 0.40 398 1038 0.50 497 1136 0.59 577 1300 752 0.27 269 868 0.37 368 963 0.45 448 1061 0.56 557 1172 0.65 647 1400 776 0.31 308 891 0.42 418 983 0.51 507 1071 0.60 597 1208 0.70 706 1500 816 0.38 378 924 0.48 477 1014 0.58 577 1097 0.68 676 1245 0.74 776

548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1120 0.54 537 1155 0.59 589 1186 0.64 639 1215 0.69 685 1240 0.73 730 1000 1185 0.60 597 1222 0.66 655 1255 0.71 709 1285 0.77 761 1312 0.82 811 1100 1225 0.65 647 1263 0.71 709 1298 0.77 769 1328 0.83 825 1357 0.88 879 1200 1266 0.72 716 1306 0.79 786 1341 0.86 851 1373 0.92 914 1402 0.98 973 1300 1306 0.79 786 1347 0.87 862 1383 0.94 934 1416 1.01 1003 1446 1.07 1068 1400 1347 0.87 865 1389 0.95 950 1427 1.03 1029 1461 1.11 1104 1492 1.18 1176 1500 1385 0.96 955 1428 1.05 1048 1467 1.14 1135 1502 1.22 1218 1534 1.30 1298

1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.4 and the maximum continuous watts are 2120.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 43 of the Bryant 549B user manual — 548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Page 43 · click to enlarge
Page 43

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1200 0.93 0.41 458 0.97 0.45 506 1.04 0.51 572 1.09 0.56 632 1300 0.86 0.42 471 0.90 0.46 521 0.96 0.52 589 1.02 0.58 651 1400 0.78 0.45 503 0.84 0.49 556 0.90 0.54 616 0.96 0.60 681 1500 0.73 0.47 536 0.76 0.52 593 0.83 0.56 631 0.89 0.62 698 1600 0.67 0.49 557 0.70 0.54 616 0.75 0.58 654 0.82 0.64 723 1700 0.60 0.52 584 0.63 0.57 646 0.67 0.60 678 0.74 0.66 750 1800 0.51 0.54 610 0.54 0.60 674 0.62 0.62 698 0.69 0.68 772 1900 0.40 0.56 629 0.45 0.62 696 0.54 0.64 720 0.62 0.70 796 2000 0.32 0.58 661 0.33 0.65 731 0.47 0.66 744 0.54 0.73 823

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.6 0.7 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 514 0.15 158 590 0.20 210 657 0.25 263 723 0.30 315 828 0.42 441 876 0.49 510 924 0.55 578 1300 545 0.18 189 615 0.23 242 680 0.29 305 744 0.35 368 849 0.47 494 895 0.54 562 940 0.60 630 1400 577 0.21 221 642 0.27 284 704 0.33 347 766 0.39 410 870 0.52 546 915 0.59 620 959 0.66 693 1500 609 0.26 273 670 0.31 326 729 0.38 394 788 0.44 462 892 0.58 609 936 0.65 683 980 0.72 757 1600 642 0.30 315 699 0.36 378 755 0.43 447 811 0.49 515 913 0.64 672 957 0.72 751 1001 0.79 830 1700 675 0.36 378 728 0.42 441 782 0.49 510 836 0.55 578 935 0.71 746 979 0.79 825 1023 0.86 904 1800 709 0.41 431 759 0.48 504 810 0.55 578 860 0.62 651 957 0.78 820 1001 0.86 904 1044 0.94 988 1900 743 0.48 504 790 0.55 578 838 0.62 651 886 0.69 725 980 0.86 904 1023 0.95 993 1066 1.03 1082 2000 778 0.55 578 836 0.62 651 875 0.70 730 913 0.77 809 1004 0.94 988 1046 1.03 1082 1088 1.12 1177

548F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.0 1.1 1.2 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 999 0.66 674 1018 0.67 685 1036 0.68 695 1073 0.71 756 1109 0.75 794 1138 0.79 851 1300 1025 0.74 756 1058 0.79 807 1090 0.84 858 1121 0.87 832 1159 0.90 918 1193 0.95 976 1400 1042 0.81 828 1080 0.88 899 1118 0.95 971 1175 1.06 1014 1206 1.09 1042 1244 1.12 1138 1500 1060 0.88 899 1098 0.96 981 1136 1.04 1063 1205 1.19 1138 1258 1.30 1243 1289 1.34 1282 1600 1080 0.95 971 1117 1.04 1058 1153 1.12 1140 1224 1.29 1234 1287 1.45 1387 1337 1.56 1492 1700 1101 1.03 1053 1137 1.12 1139 1172 1.20 1226 1241 1.38 1320 1307 1.56 1492 1366 1.73 1655 1800 1122 1.11 1134 1157 1.20 1226 1192 1.29 1318 1258 1.48 1415 1323 1.67 1597 1385 1.86 1779 1900 1143 1.21 1237 1179 1.30 1328 1214 1.39 1420 1279 1.58 1511 1341 1.78 1702 1402 1.98 1894 2000 1165 1.31 1339 1200 1.40 1431 1235 1.49 1523 1300 1.69 1616 1361 1.90 1817 1419 2.10 2008

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 1000 and maximum continuous bhp is 1.00.

*Motor drive range: 835 to 1185 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 641 0.23 242 761 0.34 357 859 0.46 483 943 0.58 609 1030 0.70 695 1300 673 0.28 294 788 0.39 410 887 0.52 546 968 0.65 683 1044 0.77 736 1400 705 0.33 347 817 0.45 473 914 0.59 620 996 0.72 757 1069 0.86 838 1500 738 0.38 399 847 0.51 536 940 0.65 683 1024 0.81 851 1095 0.95 930 1600 772 0.44 462 877 0.58 609 967 0.73 767 1051 0.89 935 1123 1.05 1073 1700 806 0.51 536 908 0.66 693 997 0.81 851 1077 1.01 1030 1151 1.15 1185 1800 841 0.59 620 939 0.75 788 1026 0.91 956 1104 1.07 1124 1178 1.26 1318 1900 876 0.68 714 971 0.84 883 1056 1.01 1061 1132 1.18 1240 1204 1.37 1502 2000 912 0.77 809 1004 0.94 988 1087 1.12 1177 1162 1.30 1366 1231 1.48 1604

548F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1106 0.87 889 1134 0.98 998 1189 1.12 1138 1245 1.21 1358 1292 1.35 1345 1300 1128 0.91 930 1183 1.10 1052 1226 1.23 1215 1297 1.35 1406 1346 1.51 1500 1400 1139 1.01 1012 1218 1.14 1090 1286 1.34 1282 1320 1.48 1463 1370 1.65 1645 1500 1162 1.09 1114 1228 1.24 1186 1303 1.40 1339 1343 1.60 1530 1393 1.79 1778 1600 1185 1.20 1226 1250 1.35 1291 1319 1.51 1444 1382 1.68 1607 1434 1.88 1867 1700 1215 1.31 1339 1276 1.48 1415 1334 1.64 1569 1398 1.80 1722 1451 2.01 2001 1800 1243 1.43 1461 1303 1.61 1540 1359 1.78 1702 1418 1.95 1865 1471 2.18 2167 1900 1271 1.56 1594 1330 1.74 1664 1386 1.93 1846 1439 2.11 2018 1493 2.36 2345 2000 1298 1.69 1727 1358 1.89 1808 1413 2.08 1989 1466 2.27 2171 — — —

Refer to page 51 for general Fan Performance notes. NOTES:

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.4 and the maximum continuous watts are 2120.

*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.

Show 10 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 44 of the Bryant 549B user manual — 548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Page 44 · click to enlarge
Page 44

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 1500 1.01 0.67 750 1.25 0.71 791 1.26 0.70 782 1.46 0.76 845 1.46 0.79 875 1.52 0.85 949 1600 0.82 0.70 780 1.09 0.74 824 1.11 0.74 821 1.32 0.79 883 1.33 0.82 913 1.41 0.89 988 1700 0.64 0.73 810 0.97 0.77 857 0.99 0.77 861 1.22 0.83 921 1.24 0.85 950 1.33 0.92 1027 1800 0.44 0.75 839 0.81 0.80 891 0.84 0.80 900 1.09 0.86 959 1.11 0.89 988 1.22 0.96 1066 1900 0.32 0.78 869 0.66 0.83 924 0.69 0.83 940 0.96 0.90 997 0.99 0.92 1025 1.11 0.99 1105 2000 0.21 0.81 899 0.47 0.86 957 0.51 0.86 979 0.80 0.93 1035 0.83 0.95 1063 0.97 1.03 1144 2100 0.13 0.83 929 0.32 0.89 990 0.36 0.89 1018 0.64 0.96 1073 0.71 0.99 1101 0.86 1.06 1183 2200 0.05 0.86 959 0.19 0.92 1023 0.21 0.92 1058 0.50 1.00 1111 0.58 1.02 1138 0.75 1.10 1222 2300 — — — 0.08 0.95 1057 0.08 0.95 1097 0.34 1.03 1149 0.39 1.06 1176 0.57 1.13 1261 2400 — 0.24 1.07 1187 0.29 1.09 1213 0.49 1.17 1300 2500 — 0.15 1.10 1225 0.15 1.12 1251 0.34 1.20 1340

LEGEND Refer to page 51 for general Fan Performance notes.

Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg) Watts — Input Watts to Motor

548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 658 0.27 276 722 0.33 337 840 0.46 470 937 0.59 603 1027 0.74 756 1600 693 0.32 327 754 0.38 388 867 0.52 531 963 0.65 664 1052 0.81 828 1700 729 0.38 388 787 0.44 450 895 0.58 593 991 0.73 746 1075 0.88 899 1800 765 0.45 460 821 0.51 521 923 0.65 664 1019 0.81 828 1099 0.96 981 1900 802 0.52 531 854 0.58 593 953 0.73 746 1046 0.90 920 1126 1.06 1083 2000 840 0.60 613 900 0.66 674 984 0.82 838 1073 0.99 1012 1154 1.16 1185 2100 878 0.69 705 923 0.75 766 1015 0.91 930 1101 1.08 1104 1182 1.27 1298 2200 916 0.78 797 958 0.85 869 1046 1.01 1032 1129 1.19 1216 1209 1.39 1420 2300 954 0.89 910 993 0.96 981 1079 1.13 1155 1160 1.31 1339 1237 1.51 1543 2400 993 1.00 1022 1029 1.07 1093 1112 1.25 1277 1190 1.43 1461 1264 1.63 1666 2500 1031 1.13 1155 1066 1.20 1226 1145 1.39 1420 1220 1.57 1604 1292 1.77 1809

548F060 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1108 0.90 920 1186 1.08 1104 1263 1.30 1328 1343 1.58 1615 1431 1.79 1829 1600 1130 0.97 991 1205 1.15 1175 1278 1.35 1380 1350 1.61 1645 1424 1.80 1921 1700 1154 1.06 1083 1226 1.23 1257 1296 1.42 1451 1364 1.64 1676 1432 1.89 1931 1800 1178 1.14 1165 1249 1.32 1349 1316 1.52 1553 1382 1.72 1758 1447 1.95 1993 1900 1201 1.23 1257 1274 1.43 1461 1338 1.62 1656 1402 1.80 1870 1464 2.05 2095 2000 1226 1.33 1359 1297 1.53 1564 1363 1.73 1768 1424 1.94 1983 1484 2.16 2207 2100 1252 1.45 1482 1320 1.64 1676 1388 1.80 1891 1448 2.07 2115 1505 2.29 2340 2200 1280 1.58 1615 1345 1.77 1809 1410 1.97 2013 1473 2.20 2248 1529 2.43 2483 2300 1309 1.71 1747 1372 1.91 1952 1434 2.11 2156 1496 2.34 2391 1554 2.58 2637 2400 1336 1.80 1891 1400 2.06 2105 1459 2.26 2310 1519 2.48 2534 1578 2.76 2820 2500 1363 2.00 2044 1428 2.22 2269 1486 2.43 2483 1543 2.65 2708 1600 2.89 2953

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 1.30 for single-phase units and 2.40 for 3-phase units.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 900 to 1300 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 6 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 45 of the Bryant 549B user manual — 548F072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)*
Page 45 · click to enlarge
Page 45

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 789 0.40 420 896 0.53 557 990 0.67 704 1072 0.83 872 1153 1.00 1051 1600 826 0.46 483 931 0.61 641 1020 0.75 788 1101 0.91 956 1178 1.09 1145 1700 865 0.54 567 966 0.69 725 1051 0.84 883 1133 1.01 1061 1205 1.18 1240 1800 905 0.62 661 1002 0.78 820 1084 0.93 977 1163 1.10 1156 1235 1.29 1355 1900 945 0.72 757 1037 0.88 925 1119 1.04 1093 1194 1.21 1271 1266 1.40 1471 2000 984 0.82 862 1072 0.98 1030 1154 1.16 1219 1226 1.33 1397 1297 1.53 1608 2100 1024 0.93 977 1108 1.10 1156 1192 1.29 1355 1259 1.47 1545 1327 1.66 1744 2200 1064 1.05 1103 1145 1.22 1282 1225 1.43 1503 1294 1.62 1702 1359 1.80 1902 2300 1104 1.18 1240 1183 1.36 1429 1260 1.57 1650 1330 1.78 1870 1392 1.97 2070 2400 1145 1.32 1387 1222 1.45 1524 1296 1.73 1818 1365 1.94 2038 1426 2.15 2259 2500 1186 1.48 1555 1262 1.68 1765 1331 1.89 1986 1400 2.12 2227 1461 2.34 2459

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1221 1.17 1229 1256 1.30 1366 1283 1.32 1387 1303 1.22 1282 1345 1.34 1390 1600 1252 1.27 1334 1311 1.45 1524 1340 1.58 1660 1330 1.61 1692 1373 1.77 1834 1700 1278 1.37 1439 1345 1.57 1650 1397 1.76 1849 1424 1.89 1986 1470 2.08 2153 1800 1303 1.48 1555 1371 1.69 1776 1433 1.90 1996 1480 2.09 2196 1528 2.30 2381 1900 1330 1.59 1671 1396 1.80 1902 1460 2.03 2133 1517 2.25 2364 1566 2.47 2563 2000 1362 1.73 1818 1422 1.94 2038 1485 2.16 2270 1544 2.40 2522 1594 2.64 2734 2100 1393 1.87 1965 1452 2.08 2185 1510 2.31 2427 1570 2.55 2674 1620 2.80 2905 2200 1423 2.02 2122 1483 2.24 2354 1538 2.46 2585 1594 2.71 2821 1645 2.98 3087 2300 1454 2.18 2291 1515 2.41 2532 1571 2.64 2758 1623 2.88 2976 1675 3.17 3280 2400 1485 2.36 2480 1544 2.59 2721 1604 2.84 2947 1657 3.07 3152 1710 3.38 3497 2500 1518 2.55 2679 1574 2.78 2905 1633 3.03 3134 1692 3.28 3345 1746 3.61 3736

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.9 and the maximum continuous watts are 2562.

*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

548F072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 765 0.45 487 821 0.51 532 923 0.65 638 1019 0.81 843 1099 0.96 883 1900 802 0.45 539 854 0.58 585 953 0.73 700 1046 0.90 835 1126 1.06 965 2000 840 0.60 600 888 0.66 646 984 0.82 771 1073 0.99 907 1154 1.16 1047 2100 878 0.69 669 923 0.75 716 1015 0.91 843 1101 1.08 981 1182 1.27 1140 2200 916 0.78 739 958 0.85 795 1046 1.01 924 1129 1.19 1072 1209 1.39 1241 2300 954 0.89 827 993 0.96 883 1079 1.13 1022 1160 1.31 1173 1237 1.51 1344 2400 993 1.00 916 1029 1.07 973 1112 1.25 1123 1190 1.43 1275 1264 1.63 1447 2500 1031 1.13 1022 1066 1.20 1081 1145 1.39 1241 1220 1.57 1396 1292 1.77 1569 2600 1070 1.26 1131 1103 1.34 1199 1179 1.52 1353 1251 1.71 1517 1322 1.92 1700 2700 1109 1.41 1258 1140 1.48 1318 1212 1.67 1482 1283 1.87 1656 1352 2.09 1849 2800 1148 1.57 1396 1177 1.64 1456 1246 1.83 1621 1316 2.04 1805 1383 2.26 1997 2900 1188 1.74 1543 1215 1.81 1604 1281 2.00 1770 1349 2.22 1962 1413 2.44 2154 3000 1227 1.92 1700 1253 2.00 1770 1316 2.19 1936 1382 2.42 2136 1444 2.63 2317

548F072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1178 1.14 1031 1249 1.32 1182 1316 1.52 1353 1382 1.72 1526 1900 1201 1.23 1106 1274 1.43 1275 1338 1.62 1439 1402 1.83 1621 2000 1226 1.33 1990 1297 1.53 1361 1363 1.73 1534 1424 1.94 1718 2100 1252 1.45 1292 1320 1.64 1456 1388 1.85 1639 1448 2.07 1831 2200 1280 1.58 1404 1345 1.77 1569 1410 1.97 1744 1473 2.20 1945 2300 1309 1.71 1517 1372 1.91 1691 1434 2.11 1866 1496 2.34 2067 2400 1336 1.85 1639 1400 2.06 1823 1459 2.26 1997 1519 2.48 2188 2500 1363 2.00 1770 1428 2.22 1962 1486 2.43 2145 1543 2.65 2335 2600 1390 2.15 1901 1456 2.38 2102 1514 2.61 2300 1569 2.83 2487 2700 1418 2.31 2041 1483 2.56 2257 1543 2.80 2462 — — — 2800 1446 2.48 2188 1510 2.73 2403 — 2900 1476 2.67 2352 1537 2.92 2562 — 3000 1506 2.88 2529 —

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

*Motor drive range: 1070 to 1460 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 46 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 46 · click to enlarge
Page 46

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 942 0.73 700 1047 0.90 835 1139 1.05 956 1193 1.14 1031 1276 1.30 1165 1900 982 0.83 779 1084 1.02 932 1160 1.11 1006 1223 1.24 1114 1301 1.38 1233 2000 1022 0.94 867 1121 1.12 1014 1188 1.22 1097 1254 1.36 1216 1329 1.44 1284 2100 1063 1.10 998 1140 1.18 1064 1196 1.27 1140 1272 1.45 1292 1354 1.58 1404 2200 1104 1.20 1081 1159 1.23 1106 1229 1.41 1258 1306 1.53 1361 1363 1.70 1508 2300 1130 1.27 1140 1196 1.37 1224 1264 1.56 1387 1340 1.66 1473 1397 1.86 1648 2400 1174 1.37 1224 1245 1.57 1396 1305 1.63 1447 1373 1.84 1630 1440 1.95 1726 2500 1201 1.50 1335 1284 1.65 1465 1338 1.75 1552 1402 1.99 1761 1469 2.04 1805 2600 1246 1.67 1482 1312 1.76 1560 1366 1.96 1735 1435 2.10 1858 1494 2.19 1936 2700 1285 1.80 1595 1354 1.95 1726 1403 2.14 1892 1474 2.21 1954 1536 2.46 2171 2800 1304 1.85 1639 1374 2.12 1875 1459 2.25 1989 1514 2.42 2136 1570 2.66 2343 2900 1345 2.05 1814 1412 2.32 2050 1496 2.54 2240 1529 2.61 2300 1603 2.87 2521 3000 1378 2.30 2032 1451 2.40 2119 1534 2.66 2343 1560 2.81 2470 1611 3.01 2648

548F072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1341 1.40 1250 1413 1.55 1378 1474 1.58 1404 1522 1.74 1564 1566 1.89 1704 1900 1374 1.53 1361 1437 1.62 1439 1490 1.67 1482 1538 1.84 1653 1583 2.00 1801 2000 1396 1.66 1473 1460 1.68 1491 1509 1.77 1569 1558 1.95 1752 1603 2.12 1909 2100 1413 1.75 1552 1475 1.73 1534 1529 1.92 1700 1578 2.11 1901 1624 2.30 2070 2200 1434 1.81 1604 1487 1.85 1639 1554 2.07 1831 1604 2.28 2049 1651 2.48 2232 2300 1459 1.88 1665 1520 2.07 1831 1576 2.24 1980 1627 2.46 2218 1674 2.68 2415 2400 1502 2.06 1823 1552 2.24 1980 1604 2.42 2136 1656 2.66 2396 1704 2.90 2609 2500 1524 2.24 1980 1585 2.42 2136 1638 2.60 2292 1691 2.86 2574 1740 3.12 2804 2600 1552 2.40 2119 1616 2.63 2317 1671 2.80 2462 1725 3.08 2772 1775 3.35 3019 2700 1584 2.61 2300 1646 2.83 2487 1706 2.97 2653 1761 3.27 2941 — — — 2800 1624 2.85 2504 1677 2.99 2661 1739 3.33 2998 1795 3.67 3299 — — — 2900 1671 3.03 2725 1742 3.43 3090 — 3000 1692 3.49 3140 1764 3.95 3558 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.9 and the maximum continuous watts are 2562.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 1300 to 1685 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 47 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 47 · click to enlarge
Page 47

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F090 (71/2 TONS) — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 465 0.43 473 554 0.64 630 630 0.86 803 695 1.09 989 757 1.34 1199 2300 471 0.45 487 559 0.66 646 635 0.89 827 699 1.12 1014 760 1.37 1224 2400 482 0.50 524 569 0.71 684 645 0.95 875 708 1.18 1064 768 1.44 1284 2500 494 0.54 554 581 0.76 723 654 1.01 924 717 1.25 1123 776 1.51 1344 2550 501 0.57 577 587 0.79 747 659 1.05 956 722 1.29 1156 780 1.55 1378 2660 507 0.59 592 592 0.82 771 663 1.08 981 727 1.32 1182 784 1.58 1404 2700 520 0.65 638 604 0.89 827 672 1.14 1031 737 1.40 1250 793 1.66 1473 2800 533 0.71 684 615 0.95 875 683 1.20 1081 747 1.49 1327 802 1.75 1552 2900 546 0.77 731 626 1.02 932 693 1.27 1140 756 1.57 1396 813 1.84 1630 3000 559 0.83 779 637 1.09 989 704 1.35 1207 765 1.66 1473 823 1.94 1718 3100 572 0.90 835 648 1.17 1056 715 1.43 1275 775 1.74 1543 832 2.05 1814 3200 585 0.96 883 660 1.24 1114 727 1.52 1353 785 1.83 1321 841 2.15 1901 3300 598 1.03 940 671 1.32 1182 739 1.62 1439 795 1.91 1691 851 2.26 1997 3400 610 1.10 998 682 1.41 1258 750 1.72 1526 806 2.01 1779 860 2.36 2084 3500 623 1.17 1056 694 1.50 1335 761 1.82 1613 817 2.11 1866 870 2.47 2180 3600 636 1.25 1123 707 1.60 1422 772 1.93 1709 828 2.23 1971 880 2.57 2266 3700 649 1.33 1190 720 1.71 1517 783 2.03 1796 840 2.35 2076 890 2.69 2369 3750 655 1.37 1224 727 1.77 1569 789 2.09 1849 846 2.42 2136 896 2.75 2420

548F090 (71/2 TONS) — STANDARD MOTOR AND DRIVE AND ALTERNATE DRIVE (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 810 1.62 1439 850 1.91 1691 873 2.20 1945 883 2.50 2206 895 2.78 2445 2300 816 1.65 1465 859 1.94 1718 888 2.24 1980 903 2.55 2249 911 2.85 2504 2400 824 1.72 1526 872 2.01 1779 909 2.32 2050 931 2.64 2326 935 2.96 2595 2500 832 1.79 1587 882 2.09 1849 925 2.40 2119 955 2.72 2394 972 3.06 2678 2550 836 1.83 1621 887 2.13 1884 931 2.45 2162 964 2.77 2436 986 3.11 2718 2660 839 1.87 1656 891 2.17 1919 936 2.49 2197 973 2.82 2479 999 3.16 2759 2700 846 1.95 1726 898 2.26 1997 946 2.58 2275 987 2.91 2554 1019 3.26 2839 2800 855 2.04 1805 906 2.35 2076 954 2.67 2352 997 3.01 2637 1034 3.36 2917 2900 863 2.13 1884 913 2.44 2154 961 2.77 2436 1006 3.12 2727 — — — 3000 872 2.22 1962 921 2.54 2240 969 2.88 2529 1014 3.22 2807 — — — 3100 882 2.33 2058 930 2.65 2335 976 2.99 2620 1021 3.34 2902 — — — 3200 892 2.45 2162 939 2.76 2428 984 3.10 2710 — 3300 902 2.57 2266 948 2.88 2529 993 3.21 2799 — 3400 912 2.69 2369 958 3.01 2637 1002 3.34 2902 — 3500 921 2.82 2479 968 3.15 2751 — 3600 930 2.95 2587 978 3.29 2862 — 3700 940 3.07 2686 — 3750 945 3.14 2743 —

1. Boldface indicates field-supplied drive is required. 2. indicates high-static motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 590 to 840 rpm. Alternate motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 48 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 48 · click to enlarge
Page 48

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 507 0.53 547 586 0.73 700 658 0.97 891 722 1.22 1097 783 1.46 1301 2300 513 0.55 562 592 0.76 723 663 1.00 916 727 1.26 1131 786 1.49 1327 2400 528 0.60 600 606 0.83 779 674 1.06 965 738 1.34 1199 795 1.58 1404 2500 542 0.68 648 619 0.90 835 686 1.13 1022 748 1.41 1258 806 1.68 1491 2550 550 0.69 669 627 0.94 867 692 1.17 1056 754 1.45 1292 812 1.74 1543 2660 557 0.72 692 634 0.97 891 698 1.21 1089 759 1.49 1327 816 1.79 1587 2700 573 0.79 747 648 1.05 956 711 1.29 1156 770 1.58 1404 827 1.88 1665 2800 588 0.86 803 662 1.13 1022 723 1.38 1233 782 1.66 1473 837 1.98 1763 2900 604 0.94 867 676 1.21 1089 737 1.48 1318 794 1.76 1560 849 2.08 1840 3000 620 1.02 932 690 1.30 1165 750 1.58 1404 806 1.86 1648 849 2.18 1927 3100 636 1.11 1006 704 1.39 1241 764 1.69 1499 818 1.97 1744 870 2.29 2023 3200 652 1.21 1089 718 1.49 1327 778 1.90 1595 831 2.09 1849 882 2.40 2119 3300 668 1.31 1173 732 1.59 1413 793 1.92 1700 844 2.21 1954 894 2.53 2232 3400 684 1.41 1258 747 1.70 1508 807 2.04 1805 857 2.35 2076 907 2.66 2343 3500 701 1.53 1361 762 1.82 1613 821 2.16 1010 871 2.48 2188 919 2.80 2462 3600 717 1.65 1465 777 1.94 1718 835 2.29 2023 885 2.63 2317 932 2.95 2587 3700 733 1.77 1569 792 2.07 1831 849 2.42 2136 899 2.78 2445 945 3.11 2718 3750 742 1.84 1630 800 2.14 1892 856 2.49 2197 907 2.86 2512 952 3.20 2719

548F090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 843 1.81 1604 908 2.25 1989 955 2.59 2283 991 2.89 2543 1023 3.19 2805 2300 846 1.84 1630 910 2.25 2015 959 2.61 2300 995 2.91 2563 1028 3.21 2827 2400 853 1.88 1665 912 2.31 2041 967 2.68 2360 1003 2.99 2631 1036 3.30 2902 2500 859 1.94 1718 919 2.37 2093 971 2.73 2403 1007 3.05 2681 1041 3.36 2956 2550 864 1.99 1761 920 2.39 2110 974 2.76 2428 1010 3.08 2710 1044 3.40 2989 2660 868 2.04 1805 921 2.41 2136 976 2.78 2445 1012 3.10 2730 1046 3.42 3011 2700 878 2.16 1910 928 2.45 2162 983 2.88 2529 1020 3.21 2828 1053 3.54 3119 2800 889 2.29 2023 937 2.57 2266 986 2.91 2554 1023 3.25 2857 1057 3.58 3181 2900 900 2.41 2128 947 2.70 2377 993 3.01 2637 1030 3.36 2955 1064 3.70 3260 3000 910 2.52 2223 958 2.85 2504 1002 3.15 2751 1039 3.51 3093 1074 3.88 3411 3100 920 2.64 2326 968 2.99 2620 1012 3.30 2870 1050 3.68 3240 1084 4.06 3574 3200 931 2.76 2428 979 3.13 2735 1023 3.47 3002 1061 3.87 3407 — — — 3300 942 2.89 2537 989 3.26 2839 1034 3.63 3121 1072 4.05 3564 — — — 3400 954 3.02 2645 1000 3.40 2948 1044 3.79 3237 — 3500 966 3.15 2751 1011 3.55 3062 1054 3.94 3340 — 3600 978 3.30 2870 1022 3.69 3165 1065 4.10 3445 — 3700 990 3.45 2987 1034 3.84 3272 — 3750 997 3.54 3055 1040 3.93 3333 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 3.7 and the maximum continuous watts are 3313.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 49 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 49 · click to enlarge
Page 49

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 501 0.57 577 587 0.79 747 659 1.05 956 722 1.29 1156 780 1.55 1378 2660 507 0.59 592 592 0.82 771 663 1.08 981 727 1.32 1182 784 1.58 1404 2700 520 0.65 638 604 0.89 827 672 1.14 1031 737 1.40 1250 793 1.66 1473 2800 533 0.71 684 615 0.95 875 683 1.20 1081 747 1.49 1327 802 1.75 1552 2900 546 0.77 731 626 1.02 932 693 1.27 1140 756 1.57 1396 813 1.84 1630 3000 559 0.83 779 637 1.09 989 704 1.35 1207 765 1.66 1473 823 1.94 1718 3100 572 0.90 835 648 1.17 1056 715 1.43 1275 775 1.74 1543 832 2.05 1814 3200 585 0.96 883 660 1.24 1114 727 1.52 1353 785 1.83 1321 841 2.15 1901 3300 598 1.03 940 671 1.32 1182 739 1.62 1439 795 1.91 1691 851 2.26 1997 3400 610 1.10 998 682 1.41 1258 750 1.72 1526 806 2.01 1779 860 2.36 2084 3500 623 1.17 1056 694 1.50 1335 761 1.82 1613 817 2.11 1866 870 2.47 2180 3600 636 1.25 1123 707 1.60 1422 772 1.93 1709 828 2.23 1971 880 2.57 2266 3700 649 1.33 1190 720 1.71 1517 783 2.03 1796 840 2.35 2076 890 2.69 2369 3750 655 1.37 1224 727 1.77 1569 789 2.09 1849 846 2.42 2136 896 2.75 2420 3800 661 1.41 1258 733 1.82 1613 795 2.15 1901 852 2.48 2188 901 2.80 2462 3900 674 1.49 1327 746 1.93 1709 806 2.26 1997 863 2.61 2300 912 2.93 2571 4000 687 1.57 1396 759 2.05 1814 817 2.38 2102 874 2.75 2420 923 3.08 2694 4100 699 1.60 1473 772 2.17 1919 828 2.50 2206 885 2.88 2529 935 3.23 2815 4200 712 1.75 1552 785 2.30 2032 840 2.64 2326 897 3.03 2653 947 3.39 2940 4250 719 1.80 1595 792 2.37 2093 846 2.71 2386 903 3.10 2710 — — —

548F102 (81/2 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 836 1.83 1621 887 2.13 1884 931 2.45 2162 964 2.77 2436 986 3.11 2718 2660 839 1.87 1656 891 2.17 1919 936 2.49 2197 973 2.82 2479 999 3.16 2759 2700 846 1.95 1726 898 2.26 1997 946 2.58 2275 987 2.91 2554 1019 3.26 2839 2800 855 2.04 1805 906 2.35 2076 954 2.67 2352 997 3.01 2637 1034 3.36 2917 2900 863 2.13 1884 913 2.44 2154 961 2.77 2436 1006 3.12 2727 — — — 3000 872 2.22 1962 921 2.54 2240 969 2.88 2529 1014 3.22 2807 — — — 3100 882 2.33 2058 930 2.65 2335 976 2.99 2620 1021 3.34 2902 — — — 3200 892 2.45 2162 939 2.76 2428 984 3.10 2710 — 3300 902 2.57 2266 948 2.88 2529 993 3.21 2799 — 3400 912 2.69 2369 958 3.01 2637 1002 3.34 2902 — 3500 921 2.82 2479 968 3.15 2751 — 3600 930 2.95 2587 978 3.29 2862 — 3700 940 3.07 2686 — 3750 945 3.14 2743 — 3800 949 3.20 2781 — 3900 959 3.33 2894 — 4000 — 4100 — 4200 — 4250 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum usable watts input is 2120 and maximum continuous bhp is 2.40.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 50 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 50 · click to enlarge
Page 50

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 550 0.69 669 627 0.94 867 692 1.17 1056 754 1.45 1292 812 1.74 1543 2660 557 0.72 692 634 0.97 891 698 1.21 1089 759 1.49 1327 816 1.79 1587 2700 573 0.79 747 648 1.05 956 711 1.29 1156 770 1.58 1404 827 1.88 1665 2800 588 0.86 803 662 1.13 1022 723 1.38 1233 782 1.66 1473 837 1.98 1753 2900 604 0.94 867 676 1.21 1089 737 1.48 1318 794 1.76 1560 848 2.08 1840 3000 620 1.02 932 690 1.30 1165 750 1.58 1404 806 1.86 1648 849 2.18 1927 3100 636 1.11 1006 704 1.39 1241 764 1.69 1499 818 1.97 1744 870 2.29 2023 3200 652 1.21 1089 718 1.49 1327 778 1.80 1595 831 2.09 1849 882 2.40 2119 3300 668 1.31 1173 732 1.59 1413 793 1.92 1700 844 2.21 1954 894 2.53 2232 3400 684 1.41 1258 747 1.70 1508 807 2.04 1805 857 2.35 2076 907 2.66 2343 3500 701 1.53 1361 762 1.82 1613 821 2.16 1910 871 2.48 2188 919 2.80 2462 3600 717 1.65 1465 777 1.94 1718 835 2.29 2023 885 2.63 2317 932 2.95 2587 3700 733 1.77 1569 792 2.07 1831 849 2.42 2136 899 2.78 2445 945 3.11 2718 3750 742 1.84 1630 800 2.14 1892 856 2.49 2197 907 2.86 2512 952 3.20 2719 3800 750 1.90 1683 807 2.21 1954 863 2.56 2257 914 2.93 2571 958 3.28 2854 3900 767 2.04 1805 822 2.35 2076 877 2.71 2386 928 3.09 2702 972 3.45 2987 4000 783 2.18 1927 838 2.50 2206 891 2.86 2512 942 3.26 2839 986 3.63 3121 4100 800 2.34 2067 854 2.66 2343 905 3.02 2645 956 3.43 2971 1000 3.81 3251 4200 817 2.49 2197 869 2.82 2479 920 3.19 2783 970 3.60 3099 1015 4.00 3380 4250 826 2.58 2275 877 2.91 2554 928 3.28 2854 977 3.69 3165 1022 4.10 3445

548F102 (81/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2550 864 1.99 1761 920 2.39 2110 974 2.76 2428 1005 3.04 2672 1034 3.31 2910 2660 868 2.04 1805 921 2.41 2136 976 2.78 2445 1008 3.06 2691 1037 3.33 2931 2700 878 2.16 1910 928 2.45 2162 983 2.88 2529 1015 3.17 2788 1044 3.45 3036 2800 889 2.29 2023 937 2.57 2266 986 2.91 2554 1018 3.20 2817 1047 3.49 3068 2900 900 2.41 2128 947 2.70 2377 993 3.01 2637 1025 3.31 2914 1055 3.61 3174 3000 910 2.52 2223 958 2.85 2504 1002 3.15 2751 1034 3.47 3049 1064 3.77 3321 3100 920 2.64 2326 968 2.99 2620 1012 3.30 2870 1045 3.63 3195 1075 3.95 3479 3200 931 2.76 2428 979 3.13 2735 1023 3.47 3002 1056 3.82 3359 1087 4.16 3659 3300 942 2.89 2537 989 3.26 2839 1034 3.63 3121 1067 3.99 3514 — — — 3400 954 3.02 2645 1000 3.40 2948 1044 3.79 3237 1078 4.17 3669 — — — 3500 966 3.15 2751 1011 3.55 3062 1054 3.94 3340 — 3600 978 3.30 2870 1022 3.69 3165 1065 4.10 3445 — 3700 990 3.45 2987 1034 3.84 3272 — 3750 997 3.54 3055 1040 3.93 3333 — 3800 1003 3.62 3114 1045 4.01 3387 — 3900 1015 3.80 3244 1057 4.18 3495 — 4000 1028 3.99 3373 — 4100 1042 4.18 3495 — 4200 — 4250 —

1. Boldface indicates field-supplied drive is required. 2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 3.7 and the maximum continuous watts are 3313.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive. Refer to page 51 for general Fan Performance notes.

Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 51 of the Bryant 549B user manual — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
Page 51 · click to enlarge
Page 51

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

548F120 (10 TONS)*

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 484 0.55 562 560 0.70 677 631 0.87 810 690 1.03 940 747 1.20 1081 3100 495 0.61 607 570 0.76 723 638 0.92 851 699 1.10 998 755 1.27 1140 3200 505 0.66 646 579 0.81 763 646 0.98 899 708 1.16 1047 761 1.34 1199 3300 516 0.72 692 589 0.87 810 655 1.05 956 717 1.23 1106 767 1.40 1250 3400 527 0.78 739 599 0.93 859 664 1.11 1006 724 1.30 1165 775 1.48 1318 3500 537 0.85 795 609 0.99 907 672 1.18 1064 731 1.36 1216 784 1.56 1387 3600 548 0.92 851 619 1.05 956 680 1.24 1114 738 1.43 1275 794 1.64 1456 3700 560 1.00 916 629 1.12 1014 688 1.31 1173 747 1.51 1344 802 1.73 1534 3800 571 1.08 981 639 1.19 1072 698 1.39 1241 756 1.60 1422 810 1.81 1604 3900 582 1.16 1047 649 1.27 1140 708 1.47 1310 764 1.69 1499 816 1.89 1674 4000 593 1.25 1123 659 1.35 1207 717 1.56 1387 773 1.78 1578 823 1.98 1753 4100 605 1.35 1207 670 1.44 1284 727 1.65 1465 781 1.86 1648 832 2.08 1840 4200 616 1.45 1292 680 1.53 1361 737 1.74 1543 789 1.95 1726 841 2.18 1927 4300 628 1.56 1387 690 1.63 1447 747 1.83 1621 798 2.05 1814 849 2.30 2032 4400 639 1.67 1482 701 1.73 1534 757 1.92 1700 807 2.16 1910 858 2.41 2177 4500 651 1.78 1578 712 1.84 1630 767 2.02 1788 817 2.27 2006 866 2.51 2265 4600 662 1.91 1691 722 1.95 1726 777 2.13 1884 827 2.38 2102 874 2.62 2362 4700 674 2.03 1796 733 2.07 1831 787 2.24 1980 836 2.50 2256 882 2.73 2460 4800 686 2.17 1919 744 2.20 1945 797 2.36 2084 846 2.62 2362 891 2.85 2569 4900 698 2.31 2041 755 2.33 2058 808 2.48 2238 856 2.73 2460 900 2.99 2698 5000 710 2.45 2212 766 2.47 2230 818 2.61 2353 866 2.86 2578 910 3.12 2819

548F120 (10 TONS)* (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 800 1.38 1233 850 1.52 1353 879 1.38 1233 925 1.81 1604 964 1.92 1761 3100 805 1.44 1284 857 1.63 1447 896 1.66 1473 935 1.93 1709 975 1.98 1811 3200 812 1.51 1344 862 1.71 1517 908 1.85 1639 944 2.01 1836 984 2.09 1903 3300 819 1.59 1413 867 1.78 1578 915 1.98 1753 952 2.11 1920 993 2.22 2014 3400 827 1.67 1482 873 1.85 1639 920 2.07 1831 963 2.21 2005 1001 2.31 2091 3500 833 1.75 1552 880 1.94 1718 926 2.15 1901 970 2.41 2134 1007 2.46 2221 3600 840 1.83 1621 888 2.04 1805 931 2.23 1971 976 2.47 2230 1017 2.62 2362 3700 847 1.92 1700 895 2.13 1884 938 2.33 2108 981 2.56 2309 1024 2.77 2496 3800 856 2.02 1788 901 2.23 1971 945 2.44 2203 986 2.65 2389 1029 2.89 2605 3900 865 2.12 1875 908 2.32 2050 953 2.55 2300 993 2.75 2478 1034 3.00 2707 4000 875 2.22 1962 915 2.42 2186 960 2.65 2389 1000 2.87 2587 1039 3.10 2800 4100 883 2.32 2050 924 2.54 2291 966 2.76 2487 1008 2.99 2698 1046 3.21 2904 4200 889 2.41 2177 934 2.65 2389 972 2.87 2587 1015 3.12 2819 1053 3.34 3029 4300 896 2.51 2265 943 2.77 2406 980 2.99 2698 1021 3.23 2923 1061 3.48 3166 4400 903 2.62 2362 951 2.89 2603 990 3.12 2819 1028 3.36 3049 1068 3.61 3241 4500 912 2.74 2469 958 3.00 2707 999 3.26 2982 1035 3.51 3161 1074 3.74 3346 4600 921 2.87 2587 965 3.11 2810 1008 3.39 3078 1041 3.68 3295 1081 3.90 3450 4700 930 3.00 2707 972 3.23 2923 1017 3.45 3224 1048 3.80 3436 1088 4.13 3552 4800 938 3.14 2838 980 3.37 3058 1025 3.55 3362 1055 3.85 3584 1095 4.30 3653 4900 946 3.27 2962 990 3.51 3149 1034 3.71 3505 1062 3.98 3741 1101 4.45 3753 5000 954 3.39 3078 998 3.62 3271 1042 3.85 3654 1068 4.08 3907 1108 4.59 3851

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Boldface indicates field-supplied drive is required. 2. indicates high-static motor and drive are required. 3. Maximum usable watts input is 2120 with standard motor, 2615 with alternate motor, and 4400 for the high-static motor. Maximum continuous bhp is 2.40 with standard motor, 2.90 with alternate motor and 5.25 with high-static motor.

*Standard motor drive range: 685 to 935 rpm. Alternate motor drive range: 835 to 1085 rpm. High static motor drive range: 830 to 1130 rpm. All other rpms require field-supplied drive. Refer to this page for general Fan Performance notes.

GENERAL NOTES FOR FAN PERFORMANCE TABLES 1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Indoor-Fan Motor Performance table on page 55.

2. Values include losses for filters, unit casing, and wet coils. See page 52 for accessory/FIOP (factory-installed option) static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate. (Belt drive units only.)
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 52 of the Bryant 549B user manual — FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120
Page 52 · click to enlarge
Page 52

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 548F036-072

COMPONENT CFM 900 1200 1400 1600 1800 2000 2200 2400 2600 3000 1 Heater Module 0.05 0.07 0.09 0.09 0.10 0.11 0.11 0.12 0.13 0.15 2 Heater Modules 0.15 0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18 0.19 Durablade Economizer Accessory 0.05

EconoMi$er 0.05 0.09 0.13 0.17 0.22 0.27 0.32 0.39 0.45 0.53

LEGEND FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 548F090-120

COMPONENT CFM 2250 2500 3000 3500 4000 4500 5000 5500 6000 6250 1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17 2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20 Durablade Economizer Accessory 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.09

EconoMi$er 0.07 0.09 0.13 0.18 0.23 0.30 0.36 — — —

LEGEND FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120

UNIT 548F MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 036† 1000 976 952 928 904 880 856 832 808 784 760 — — 036** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048† 1185 1150 1115 1080 1045 1010 975 940 905 870 835 — — 048** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060† 1300 1260 1220 1180 1140 1100 1060 1020 980 940 900 — — 060** 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — — 072†† 1460 1420 1380 1345 1305 1265 1225 1185 1150 1110 1070 — — 072** 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 — — 090†† 840 815 790 765 740 715 690 665 635 615 590 — — 090*** 935 910 885 860 835 810 785 760 735 710 685 — — 090** 1080 1025 1007 988 970 952 933 915 897 878 860 — — 102†† 935 910 885 860 835 810 785 760 735 710 685 — — 102** 1080 1025 1007 988 970 952 933 915 897 878 860 — — 120†† 935 910 885 860 835 810 785 760 735 710 685 — — 120† 1085 1060 1035 1010 985 960 935 910 885 860 835 — — 120** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830

*Approximate fan rpm shown. †Indicates alternate motor and drive package. **Indicates high-static motor and drive package. ††Indicates standard motor and drive package. ***Indicates alternate drive package only.

Page 53 of the Bryant 549B user manual — EconoMi$er Power Exhaust Performance
Page 53 · click to enlarge
Page 53

OPTIONAL POWER EXHAUST

POWER REQUIREMENTS

STATIC PRESSURE (in. wg)

MOCP 230 VAC 460 VAC 575 VAC 548F036-072 1.40 Amps @ 60 Hz 15.0 amps 15.0 amps 15.0 amps 548F090-120 3.04 Amps @ 60 Hz

UNIT SIZE

AMPS @ 230 V (2 Fans Running)

MOCP — Maximum Overcurrent Protection

0.00 0 500 1000 1500 2000

548F036-072 548F090-120

FLOW (CFM)

EconoMi$er Barometric Relief

Damper Characteristics

2 FANS OPERATING

2 FANS OPERATING

1 FAN OPERATING

1 FAN OPERATING

0 0 0.1 0.2 0.3 0.4 0.5

STATIC PRESSURE (in. wg)

0 0.1 0.2 0.3 0.4 0.5

STATIC PRESSURE (in. wg)

EconoMi$er Power Exhaust Performance

EconoMi$er Power Exhaust Performance

(548F036-072)

(548F090-120)

FLOW (cfm) · 4000 3000 · FLOW (cfm)

Page 54 of the Bryant 549B user manual — MULTIPLICATION FACTORS
Page 54 · click to enlarge
Page 54

ELECTRIC HEATING CAPACITIES

ACCESSORY

ACCESSORY

ACCESSORY

ACCESSORY

UNIT 548F VOLTAGE

ACCESSORY

HEATER PART NUMBER CRHEATER---A00

SINGLE POINT BOX

UNIT 548F VOLTAGE

ACCESSORY

HEATER PART NUMBER CRHEATER---A00

SINGLE POINT BOX

PART NO. CRSINGLE---A00

PART NO. CRSINGLE---A00

4.4 101 — 6.5 102 — 8.7 103 — 10.5 104 — 13.0* 102* 004

6.5 102 — 10.5 104 — 16.0 105 — 21.0* 104* 002 26.5* 105,104 002

4.4 101 — 6.5 102 — 8.7 103 — 10.5 104 — 16.0 105 —

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* — 25.5* 109,108 —

6.0 106 — 8.8 107 — 11.5 108 — 14.0 109 —

10.4 117 006 16.0 110 006 24.8 111 007 32.0 112 007 42.4* 112,117 009

4.4 101 — 8.7 103 — 13.0* 102* 004 17.4* 103* 004 21.0* 104* 004

13.9 116 006 16.5 113 006 27.8 114 006 33.0 115 006 41.7* 114,116 008

6.5 102 — 8.7 103 — 16.0 105 — 21.0* 104* 002

10.4 117 012 16.0 110 012 32.0 112 012 42.4* 112,117 015 50.0* 112,110 015

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* —

16.5 113 011 27.8 114 011 33.0 115 011† 41.7* 114,116 014 50.0* 115,113 014

6.5 102 — 8.7 103 — 13.0* 102* 004 17.4* 103* 004 21.0* 104* 004

*Two heater packages required to provide kW indicated. †On units with factory-installed outlet, use CRSINGLE014A00. NOTES: The kW ratings shown above are at 240 and 480 v. Use the Multiplication Factors table to determine heater capacity for your particular voltage.

6.5 102 — 10.5 104 — 16.0 105 — 21.0* 104* 002 26.5* 105,104 002

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* — 25.5* 109,108 —

MULTIPLICATION FACTORS

HEATER RATING

VOLTAGE DISTRIBUTION

MULTIPLICATION

VOLTAGE

FACTOR

240 200 0.69 208 0.75 230 0.92 240 1.00

480 440 0.84 460 0.92 480 1.00

575 545 0.90 575 1.00 600 1.09

EXAMPLE32.0 kW (at 240 v) heater on 208 v

= 32.0 (.75 mult factor) = 24.0 kW capacity at 208 v.

Show 20 more labels / short text on this page
(60 Hz) · kW · (60 Hz) · kW · 208/230 (single phase) · 208/230 (3 phase) · 208/230 (3 phase) · 460 (3 phase) · 460 (3 phase) · 208/230 (3 phase) · 090,102 · 208/230 (single phase) · 460 (3 phase) · 208/230 (3 phase) · 208/230 (3 phase) · 460 (3 phase) · 460 (3 phase) · 208/230 (single phase) · 208/230 (3 phase) · 460 (3 phase)
Page 55 of the Bryant 549B user manual — INDOOR-FAN MOTOR PERFORMANCE — 548F UNITS
Page 55 · click to enlarge
Page 55

INDOOR-FAN MOTOR PERFORMANCE — 548F UNITS

UNIT 548F INDOOR-FAN

UNIT VOLTAGE

MAXIMUM ACCEPTABLE

MAXIMUM ACCEPTABLE

MAXIMUM AMP DRAW

MOTOR EFFICIENCY (%)

MOTOR

CONTINUOUS BHP*

OPERATING WATTS

208/230 0.34 440 3.3

460 1.8 575 1.8

208/230 1.00 1000 5.1 460 2.2 575 2.2

208/230 2.40 2120 6.1 460 2.7 575 2.7

208/230 0.75 850 3.1

460 1.9 575 1.9

208/230 1.00 1000 5.1 460 2.2 575 2.2

208/230 2.40 2120 6.1 460 2.7 575 2.7

208/230 1.20 1340 6.2

460 3.4 575 3.4

208/230 1.30/2.40† 2120 9.2/6.1† 460 2.7 575 2.7

208/230 2.90 2562 6.1 460 2.7 575 2.7

208/230 2.40 2120 6.1

460 2.7 575 2.7

208/230 2.90 2562 7.9 460 3.6 575 3.6

208/230 2.40 2120 6.1

460 2.7 575 2.7

208/230 3.70 3313 11.1 460 5.0 575 5.0

208/230 2.40 2120 6.1

460 2.7 575 2.7

208/230 3.70 3313 11.1 460 5.0 575 5.0

208/230 2.40 2120 6.1

460 2.7 575 2.7

208/230 2.90 2615 7.9 460 3.6 575 3.6

208/230 5.25 4400 15.0 460 7.4 575 7.4

LEGEND BHP — Brake Horsepower

1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. 2. High-static motor not available on single-phase units.

*Extensive motor and electrical testing on these units ensures that the full horse- power range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance trip- ping or premature motor failure. Unit warranty will not be affected. †Single-phase/three-phase.

Show 19 more labels / short text on this page
Standard · Alternate · High Static · Standard · Alternate · High Static · Standard · Alternate · High Static · Standard · High Static · Standard, · Alternate · High Static · Standard · High Static · Standard · Alternate · High Static
Page 56 of the Bryant 549B user manual — HIGH-STATIC 187 254 16.8 91.0 1.5 5.8
Page 56 · click to enlarge
Page 56

ELECTRICAL DATA

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 25.5/ 25.5 30/ 30†† 25/ 25 107/107 3.3/ 4.4 15.9/18.3 45.4/ 48.4 50/ 50†† 43/ 46 123/125 4.9/ 6.5 23.6/27.1 55.0/ 59.4 60/ 60†† 52/ 56 131/184 6.5/ 8.7 31.3/36.3 64.6/ 70.9 70/ 80 61/ 66 138/143 7.9/10.5 38.0/43.8 73.0/ 80.3 80/ 90 68/ 75 145/151 9.8/13.0 47.1/54.2 84.4/ 93.3 90/100 79/ 87 154/161***

STD 187 254 16.4 96.0 1.5 3.1

— — 26.9/ 26.9 30/ 30†† 26/ 26 111/111 3.3/ 4.4 15.9/18.3 46.8/ 49.8 50/ 50†† 45/ 47 127/130 4.9/ 6.5 23.6/27.1 56.4/ 60.8 60/ 70 53/ 57 135/138 6.5/ 8.7 31.3/36.3 66.0/ 72.3 70/ 80 62/ 68 143/148 7.9/10.5 38.0/43.8 74.4/ 81.7 80/ 90 70/ 77 149/155 9.8/13.0 47.1/54.2 85.8/ 94.7 90/100 80/ 89 158/166***

ALT 187 254 16.4 96.0 1.5 4.9

— — 17.8/ 17.8 20/ 20†† 17/ 17 86/ 86 3.3/ 4.4 9.2/10.6 29.3/ 31.0 30/ 35†† 28/ 30 95/ 97 4.9/ 6.5 13.6/15.6 34.8/ 37.3 35/ 40†† 33/ 35 100/102 6.5/ 8.7 18.0/20.9 40.3/ 43.9 45/ 45†† 38/ 42 104/107 7.9/10.5 21.9/25.3 45.1/ 49.4 50/ 50†† 43/ 47 108/111 12.0/16.0 33.3/38.5 59.4/ 65.9 60/ 70 56/ 62 119/124

STD 187 254 10.2 75.0 1.5 3.1

— — 19.2/ 19.2 20/ 20†† 19/ 19 90/ 90 3.3/ 4.4 9.2/10.6 30.7/ 32.4 35/ 35†† 30/ 31 100/101 4.9/ 6.5 13.6/15.6 36.2/ 38.7 40/ 40†† 35/ 37 104/106 6.5/ 8.7 18.0/20.9 41.7/ 45.3 45/ 50†† 40/ 43 108/111 7.9/10.5 21.9/25.3 46.5/ 50.8 50/ 60†† 44/ 48 112/116 12.0/16.0 33.3/38.5 60.8/ 67.3 70/ 70 57/ 63 124/129

ALT 187 254 10.2 75.0 1.5 4.9

— — 20.1/ 20.1 25/ 25†† 20/ 20 120/120 3.3/ 4.4 9.2/10.6 31.6/ 33.3 35/ 35†† 31/ 32 129/130 4.9/ 6.5 13.6/15.6 37.1/ 39.6 40/ 40†† 36/ 38 133/135 6.5/ 8.7 18.0/20.9 42.6/ 46.2 45/ 50†† 41/ 44 138/141 7.9/10.5 21.9/25.3 47.4/ 51.7 50/ 60†† 45/ 49 142/145 12.0/16.0 33.3/38.5 61.7/ 68.2 70/ 70 58/ 64 153/158

HIGH-STATIC 187 254 10.2 75.0 1.5 5.8

— — 8.1 15†† 8 45 6.0 7.2 12.1 20†† 16 52 8.8 10.6 21.4 25†† 20 55 11.5 13.8 25.4 30†† 24 59 14.0 16.8 29.1 30†† 27 62

STD 414 508 4.8 40.0 0.8 1.7

— — 8.9 15†† 9 48 6.0 7.2 17.9 20†† 17 55 8.8 10.6 22.2 25†† 21 59 11.5 13.8 26.2 30†† 25 62 14.0 16.8 29.9 30†† 28 65

ALT 414 508 4.8 40.0 0.8 2.1

— — 9.4 15†† 9 62 6.0 7.2 18.4 20†† 18 70 8.8 10.6 22.7 25†† 22 73 11.5 13.8 26.7 30†† 25 76 14.0 16.8 30.4 35†† 29 79

HIGH-STATIC 414 508 4.8 40.0 0.8 2.6

575-3-60 STD 518 632 3.8 31.0 0.8 1.7 — — 6.4 15†† 6 35 ALT 518 632 3.8 31.0 0.8 2.1 — — 7.1 15†† 7 37 HIGH-STATIC 518 632 3.8 31.0 0.8 2.6 — — 7.5 15†† 7 49

— — 41.4/ 41.4 45/ 45†† 39/ 39 143/143 3.3/ 4.4 15.9/18.3 61.3/ 64.3 70/ 70 58/ 60 159/161 6.5/ 8.7 31.3/36.3 80.5/ 86.8 90/ 90 75/ 81 174/179 9.8/13.0 47.1/54.2 100.3/109.1 110/110 93/102 190/197 13.1/17.4 63.0/72.5 120.1/132.0 125/150 112/123 206/215 15.8/21.0 76.0/87.5 136.4/150.8 150/175 127/140 219/230

STD 187 254 29.1 132.0 1.5 3.5

— — 42.8/ 42.8 45/ 45†† 41/ 41 147/147 3.3/ 4.4 15.9/18.3 62.7/ 65.7 70/ 70 59/ 62 163/166 6.5/ 8.7 31.3/36.3 81.9/ 88.2 90/ 90 77/ 83 179/184 9.8/13.0 47.1/54.2 107.7/110.5 110/125 95/103 194/202 13.1/17.4 63.0/72.5 121.5/133.4 125/150 113/124 210/220 15.8/21.0 76.0/87.5 137.8/152.2 150/175 128/141 223/235

ALT 187 254 29.1 132.0 1.5 4.9

— — 26.0/ 26.0 30/ 30†† 25/ 25 102/102 4.9/ 6.5 13.6/15.6 43.0/ 45.5 45/ 50†† 41/ 43 115/117 6.5/ 8.7 18.0/20.9 48.5/ 52.1 50/ 60†† 46/ 49 120/123 12.0/16.0 33.3/38.5 67.6/ 74.1 70/ 80 63/ 69 135/140 15.8/21.0 43.9/50.5 80.9/ 89.1 90/ 90 76/ 83 146/152

STD 187 254 16.8 91.0 1.5 3.5

— — 27.4/ 27.4 30/ 30†† 27/ 27 106/106 4.9/ 6.5 13.6/15.6 44.4/ 46.9 45/ 50†† 42/ 45 120/122 6.5/ 8.7 18.0/20.9 49.9/ 53.5 50/ 60†† 47/ 45 124/127 12.0/16.0 33.3/38.5 69.0/ 75.5 70/ 80 65/ 71 140/145 15.8/21.0 43.9/50.5 82.3/ 90.5 90/100 77/ 85 150/157

ALT 187 254 16.8 91.0 1.5 4.9

— — 28.3/ 28.3 30/ 30†† 28/ 28 136/136 4.9/ 6.5 13.6/15.6 45.3/ 47.8 50/ 60†† 43/ 46 149/151 6.5/ 8.7 18.0/20.9 50.8/ 54.4 60/ 60†† 48/ 52 154/157 12.0/16.0 33.3/38.5 69.9/ 76.4 70/ 80 66/ 72 169/174 15.8/21.0 43.9/50.5 83.2/ 91.4 90/100 78/ 86 180/186***

HIGH-STATIC 187 254 16.8 91.0 1.5 5.8

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-1-60 · 208/230-3-60 · 036 (3 Tons) · 460-3-60 · 208/230-1-60 · 048 (4 Tons) · 208/230-3-60
Page 57 of the Bryant 549B user manual — HIGH-STATIC 414 508 7.7 59.6 0.8 3.4
Page 57 · click to enlarge
Page 57

ELECTRICAL DATA (cont)

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 13.1 15†† 13 56 6.0 7.2 22.1 25†† 21 63 11.5 13.8 30.4 35†† 29 70 14.0 16.8 34.1 35†† 32 73 23.0 27.7 47.7 50†† 45 84

STD 414 508 8.4 50.0 0.8 1.8

— — 13.4 15†† 13 58 6.0 7.2 22.4 25†† 21 65 11.5 13.8 30.7 35†† 29 72 14.0 16.8 34.4 35†† 32 75 23.0 27.7 48.0 50†† 45 86

ALT 414 508 8.4 50.0 0.8 2.1

— — 13.9 15†† 14 72 6.0 7.2 22.9 25†† 22 80 11.5 13.8 31.2 35†† 29 86 14.0 16.8 34.9 35†† 33 89 23.0 27.7 48.5 50†† 45 100

HIGH-STATIC 414 508 8.4 50.0 0.8 2.6

575-3-60 STD 518 632 6.7 37.0 0.8 1.8 — — 10.7 15†† 10 42 ALT 518 632 6.7 37.0 0.8 2.1 — — 10.7 15†† 10 43 HIGH-STATIC 518 632 6.7 37.0 0.8 2.6 — — 11.1 15†† 11 55

— — 40.8/ 40.8 45/ 45†† 39/ 39 184/184 4.9/ 6.5 23.6/27.0 70.3/ 74.7 80/ 80 66/ 70 208/211 6.5/ 8.7 31.3/36.3 79.9/ 86.2 80/ 90 75/ 81 215/220*** 9.8/13.0 47.1/54.2 99.7/108.5 100/110 93/102 231/238*** 13.1/17.4 63.0/72.5 119.5/131.4 125/150 112/123 247/257*** 15.8/21.0 76.0/87.5 135.8/150.2 150/175 127/140 260/272***

STD 187 254 26.7 170.0 1.5 5.9

— — 48.5/ 48.5 50/ 50†† 48/ 48 222/222 4.9/ 6.5 23.6/27.1 78.0/ 82.4 80/ 90 75/ 79 246/249 6.5/ 8.7 31.3/36.3 87.6/ 93.9 90/100 84/ 90 253/258*** 9.8/13.0 47.1/54.2 107.4/116.2 110/125 102/110 269/276*** 13.1/17.4 63.0/72.5 127.2/139.1 150/150 121/131 285/294*** 15.8/21.0 76.0/87.5 143.5/157.9 150/175 135/149 298/309***

ALT 187 254 26.7 170.0 1.5 8.8

— — 26.7/ 26.7 30/ 30†† 26/ 26 138/138 4.9/ 6.5 13.6/15.6 43.7/ 46.2 45/ 50†† 42/ 44 152/154 7.9/10.5 21.9/25.3 54.0/ 58.3 60/ 60†† 51/ 55 160/163 12.0/16.0 33.3/38.5 68.3/ 74.8 70/ 80 65/ 70 171/177 15.8/21.0 43.9/50.5 81.5/ 89.8 90/ 90 77/ 84 182/189*** 19.9/26.5 55.2/63.8 95.7/106.4 100/110 90/100 193/202***

STD 187 254 15.4 124.0 1.5 5.9

— — 26.6/ 26.6 30/ 30†† 26/ 26 169/169 4.9/ 6.5 13.6/15.6 43.6/ 46.1 45/ 50†† 42/ 44 182/184 7.9/10.5 21.9/25.3 53.9/ 58.2 60/ 60 51/ 55 191/194 12.0/16.0 33.3/38.5 68.2/ 74.7 70/ 80 64/ 70 202/207 15.8/21.0 43.9/50.5 81.4/ 89.7 90/ 90 77/ 84 213/219*** 19.9/26.5 55.2/63.8 95.6/106.3 100/110 90/ 99 224/233***

ALT 187 254 15.4 124.0 1.5 5.8

— — 28.3/ 28.3 30/ 30†† 28/ 28 188/188 4.9/ 6.5 13.6/15.6 45.3/ 47.8 50/ 50†† 44/ 46 201/203 7.9/10.5 21.9/25.3 55.6/ 59.9 60/ 60†† 53/ 57 210/213 12.0/16.0 33.3/38.5 69.9/ 76.4 70/ 80 66/ 72 221/226 15.8/21.0 43.9/50.5 83.1/ 91.4 90/100 79/ 86 232/238*** 19.9/26.5 55.2/63.8 97.3/108.0 100/110 92/101 243/252***

HIGH-STATIC 187 254 15.4 124.0 1.5 7.5

— — 13.6 15†† 13 67 6.0 7.2 22.6 25†† 22 75 11.5 13.8 30.9 35†† 29 81 14.0 16.8 34.6 35†† 33 84 23.0 27.7 48.3 50†† 45 95 25.5 30.7 52.0 60†† 49 98

STD 414 508 7.7 59.6 0.8 3.2

— — 13.0 15†† 13 82 6.0 7.2 22.0 25†† 21 89 11.5 13.8 30.3 35†† 29 96 14.0 16.8 34.0 35†† 32 99 23.0 27.7 47.7 50†† 45 110 25.5 30.7 51.4 60†† 48 113

ALT 414 508 7.7 59.6 0.8 2.6

— — 13.8 15†† 14 92 6.0 7.2 22.8 25†† 22 99 11.5 13.8 31.1 35†† 30 105 14.0 16.8 34.8 35†† 33 108 23.0 27.7 48.5 50†† 46 119 25.5 30.7 52.2 60†† 49 122

HIGH-STATIC 414 508 7.7 59.6 0.8 3.4

575-3-60 STD 518 632 6.2 49.4 0.8 3.2 — — 11.0 15†† 11 56 ALT 518 632 6.2 49.4 0.8 2.6 — — 10.5 15†† 10 67 HIGH-STATIC 518 632 6.2 49.4 0.8 3.4 — — 11.1 15†† 11 75

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 460-3-60 · 048 (4 Tons) · (cont) · 208/230-1-60 · 208/230-3-60 · 060 (5 Tons) · 460-3-60
Page 58 of the Bryant 549B user manual — STD
Page 58 · click to enlarge
Page 58

ELECTRICAL DATA (cont)

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

FLA

Min Max RLA LRA Nominal

kW** FLA MCA MOCP FLA LRA

— — 35.6/ 35.6 40/ 40†† 34/ 34 190/190 4.9/ 6.5 13.6/15.6 52.6/ 55.1 60/ 60†† 50/ 52 204/206 7.9/10.5 21.9/25.3 63.0/ 67.2 70/ 70 60/ 63 212/215 12.0/16.0 33.3/38.5 77.2/ 83.7 80/ 90 73/ 79 223/229 15.8/21.0 43.9/50.5 90.5/ 98.7 100/100 85/ 92 234/241*** 19.9/26.5 55.2/63.8 104.6/115.3 110/125 98/108 245/254***

STD 187 254 22.7 146.0 1.4 5.8

— — 37.3/ 37.3 40/ 40†† 36/ 36 209/209 4.9/ 6.5 13.6/15.6 54.3/ 56.8 60/ 60†† 52/ 54 223/225 7.9/10.5 21.9/25.3 64.7/ 68.9 70/ 70 62/ 65 231/234 12.0/16.0 33.3/38.5 78.9/ 85.4 80/ 90 75/ 81 242/248*** 15.8/21.0 43.9/50.5 92.2/100.4 100/110 87/ 94 253/260*** 19.9/26.5 55.2/63.8 106.3/117.0 110/125 100/110 264/273***

HIGH-STATIC 187 254 22.7 146.0 1.4 7.5

— — 17.6 20†† 17 95 6.0 7.2 26.6 30†† 25 102 11.5 13.8 34.8 35†† 33 109 14.0 16.8 38.6 40†† 36 112 23.0 27.7 52.2 60†† 49 123 25.5 30.7 55.9 60†† 52 126

STD 414 508 11.4 73.0 0.7 2.6

— — 18.4 20†† 18 105 6.0 7.2 27.4 30†† 26 112 11.5 13.8 35.6 40†† 34 118 14.0 16.8 39.4 40†† 37 121 23.0 27.7 53.0 60†† 50 132 25.5 30.7 56.7 60†† 53 135

HIGH-STATIC 414 508 11.4 73.0 0.7 3.4

575-3-60 STD 518 632 9.1 58.4 0.7 2.6 — — 14.0 15†† 14 76 HIGH-STATIC 518 632 9.1 58.4 0.7 3.4 — — 14.7 15†† 14 84

— — 38.8/ 38.8 40/ 40†† 41/ 41 229/229 7.8/10.5 21.7/ 25.0 65.9/ 70.0 70/ 80 66/ 69 251/254 12.0/16.0 33.3/ 38.5 80.4/ 86.9 90/ 90 79/ 85 262/268*** 18.6/24.8 51.6/ 59.7 103.3/113.4 110/125 100/109 281/289*** 24.0/32.0 66.6/ 77.0 122.0/135.0 125/150 117/129 296/306*** 31.8/42.4 88.3/102.0 149.1/166.3 150/175 142/158 317/331***

STD 187 254 13.4 91.0 1.4 5.8

— — 43.6/ 43.6 45/ 45†† 46/ 46 273/273 7.8/10.5 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 294/298 12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 306/311*** 18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 324/332*** 24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 339/350*** 31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 361/375***

HIGH-STATIC 187 254 13.4 91.0 1.4 10.6

— — 19.1 20†† 20 108 14.0 16.7 40.0 45†† 39 124 16.5 19.8 43.8 45†† 43 128 27.8 33.4 60.8 70 58 141 33.0 39.7 68.7 70 66 147 41.7 50.2 81.8 90 78 158

090 (71/2 Tons)

STD 414 508 6.7 42.0 0.7 2.6

— — 21.3 25†† 23 130 14.0 16.7 42.2 45†† 42 146 16.5 19.8 46.0 50†† 45 149 27.8 33.4 63.0 70 61 163 33.0 39.7 70.9 80 68 169 41.7 50.2 84.0 90 80 180***

HIGH-STATIC 414 508 6.7 42.0 0.7 4.8

2.6 — — 15.4 20†† 16 97 17.0 17.1 36.7 40†† 36 114 34.0 34.1 68.0 60†† 55 131

STD

518 632 5.4 39.0 0.7

HIGH-STATIC 4.8 — — 17.1 20†† 18 114 17.0 17.1 38.5 40†† 38 132 34.0 34.1 59.7 60†† 57 149

Show 8 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-3-60 · 072 (6 Tons) · 460-3-60 · 208/230-3-60 · 460-3-60 · 575-3-60
Page 59 of the Bryant 549B user manual — HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
Page 59 · click to enlarge
Page 59

ELECTRICAL DATA (cont)

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 44.6/ 44.6 45/ 45†† 47/ 47 321/321 7.8/10.5 21.7/ 25.0 71.7/ 75.9 80/ 80 72/ 75 343/346 12.0/16.0 33.3/ 38.5 86.2/ 92.7 90/100 85/ 91 354/360*** 18.6/24.8 51.6/ 59.7 109.1/119.2 110/125 106/115 373/381*** 24.0/32.0 66.6/ 77.0 127.9/140.9 150/150 123/135 388/398*** 31.8/42.4 88.3/102.0 155.0/172.1 175/175 148/164 409/428***

STD 187 254 16.0 137.0 1.4 5.8

— — 49.4/ 49.4 50/ 50†† 52/ 52 365/365 7.8/10.5 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 386/390*** 12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 398/403*** 18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 416/424*** 24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/141 431/442*** 31.8/42.4 88.3/102.0 159.8/176.9 175/200 154/170 453/467***

HIGH-STATIC 187 254 16.0 137.0 1.4 10.6

— — 22.7 25†† 24 162 14.0 16.7 43.6 45†† 43 178 16.5 19.8 47.4 50†† 46 182 27.8 33.4 64.4 70 62 195 33.0 39.7 72.3 80 69 201 41.7 50.2 85.4 90 81 212***

102 (81/2 Tons)

STD 414 508 8.3 69.0 0.7 2.6

— — 24.9 25†† 26 184 14.0 16.7 45.8 50†† 45 200 16.5 19.8 49.6 50†† 49 203 27.8 33.4 66.6 70 65 217 33.0 39.7 74.5 80 72 223 41.7 50.2 87.6 90 84 234***

HIGH-STATIC 414 508 8.3 69.0 0.7 4.8

2.6 — — 17.6 20†† 18 135 17.0 17.1 59.0 40†† 38 152 34.0 34.1 60.2 70†† 58 169

STD

HIGH-STATIC 4.8 — — 19.4 20†† 20 152 17.0 17.1 40.7 45†† 40 170 34.0 34.1 62.0 70 60 187

518 632 6.4 58.0 0.7

— — 47.3/ 47.3 50/ 50†† 49/ 49 295/295 7.8/10.4 21.7/ 25.0 74.4/ 78.6 80/ 80 74/ 78 317/320 12.0/16.0 33.3/ 38.5 88.9/ 95.4 90/100 88/ 94 328/334*** 24.0/32.0 66.6/ 77.0 130.6/143.6 150/150 126/138 362/372*** 31.8/42.4 88.3/102.0 157.7/174.8 175/175 151/167 383/397*** 37.6/50.0 104.4/120.3 177.8/167.6 200/175 170/188 399/415***

STD 187 254 17.2 124.0 1.4 5.8

— — 49.0/ 49.0 50/ 50†† 51/ 51 314/314 7.8/10.4 21.7/ 25.0 76.1/ 80.8 80/ 90 76/ 80 336/389*** 12.0/16.0 33.3/ 38.5 90.6/ 97.1 100/100 90/ 96 347/353*** 24.0/32.0 66.6/ 77.0 132.3/145.3 150/150 128/140 381/391*** 31.8/42.4 88.3/102.0 159.4/176.5 175/200 153/169 402/416*** 37.6/50.0 104.4/120.3 179.5/169.3 200/175 171/190 418/434***

ALT 187 254 17.2 124.0 1.4 7.5

— — 56.5/ 56.5 60/ 60†† 60/ 60 362/362 7.8/10.4 21.7/ 25.0 83.6/ 87.8 90/ 90 85/ 89 384/387*** 12.0/16.0 33.3/ 38.5 98.1/104.6 100/110 98/104 395/401*** 24.0/32.0 66.6/ 77.0 139.8/152.8 150/175 137/149 429/439*** 31.8/42.4 88.3/102.0 166.9/184.0 175/200 162/177 450/464*** 37.6/50.0 104.4/120.3 187.0/176.8 200/200 180/198 466/482***

HIGH-STATIC 187 254 17.2 124.0 1.4 15.0

— — 23.4 25†† 24 143 16.5 19.8 48.1 50†† 47 163 27.8 33.4 65.1 70 63 176 33.0 39.7 73.0 80 70 183 41.7 50.2 86.1 90 82 193*** 50.0 60.1 83.5 90 93 203***

STD 414 508 8.6 59.6 0.7 2.6

— — 24.2 25†† 25 182 16.5 19.8 48.9 50†† 48 202 27.8 33.4 65.9 70 64 216 33.0 39.7 73.8 80 71 222 41.7 50.2 86.9 90 83 233*** 50.0 60.1 84.3 90 94 243***

ALT 414 508 8.6 59.6 0.7 3.4

— — 28.2 30†† 30 176 16.5 19.8 52.9 60†† 53 196 27.8 33.4 69.9 70 68 210 33.0 39.7 77.8 80 76 216 41.7 50.2 90.9 100 88 227*** 50.0 60.1 88.3 100 99 237***

HIGH-STATIC 414 508 8.6 59.6 0.7 7.4

— — 18.7 20†† 20 118 17.0 17.1 40.1 50†† 39 135 34.0 34.1 61.4 70 59 152 51.0 51.2 69.9 70 78 169

STD 518 632 6.9 49.4 0.7 2.6

— — 19.4 20†† 20 149 17.0 17.1 40.7 50†† 40 166 34.0 34.1 62.0 70 60 183 51.0 51.2 70.6 80 79 201***

ALT 518 632 6.9 49.4 0.7 3.4

— — 22.6 25†† 24 145 17.0 17.1 43.9 45†† 44 162 34.0 34.1 65.2 70 63 179 51.0 51.2 73.8 80 83 196***

HIGH-STATIC 518 632 6.9 49.4 0.7 7.4

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-3-60 · 460-3-60 · 575-3-60 · 208/230-3-60 · 120 (10 Tons) · 460-3-60 · 575-3-60
Page 60 of the Bryant 549B user manual — HIGH-STATIC 187 254 16.8 91.0 1.5 5.8
Page 60 · click to enlarge
Page 60

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 30.3/ 30.3 35/ 35†† 30/ 30 112/112 3.3/ 4.4 15.9/18.3 50.2/ 53.2 60/ 60†† 48/ 51 128/130 4.9/ 6.5 23.6/27.1 59.8/ 64.2 70/ 70 57/ 61 135/139 6.5/ 8.7 31.3/36.3 69.4/ 75.7 70/ 80 66/ 72 143/148 7.9/10.5 38.0/43.6 77.8/ 85.1 80/ 90 74/ 81 150/156*** 9.8/13.0 47.1/54.2 89.2/ 98.1 90/100 84/ 72 159/166***

STD 187 254 16.4 96.0 1.5 3.1

— — 31.7/ 31.7 35/ 35†† 32/ 32 116/116 3.3/ 4.4 15.9/18.3 51.6/ 54.6 60/ 60†† 50/ 53 132/134 4.9/ 6.5 23.6/27.1 61.2/ 65.6 70/ 70 59/ 63 140/143 6.5/ 8.7 31.3/36.3 70.8/ 77.1 80/ 80 68/ 73 147/152 7.9/10.5 38.0/43.6 79.2/ 86.5 80/ 90 75/ 82 154/160*** 9.8/13.0 47.1/54.2 90.6/ 99.5 100/110 86/ 94 163/170***

ALT 187 254 16.4 96.0 1.5 4.9

— — 22.6/ 22.6 25/ 25†† 23/ 23 91/ 91 3.3/ 4.4 9.2/10.6 34.1/ 35.8 40/ 40†† 34/ 35 100/101 4.9/ 6.5 13.6/15.6 39.6/ 42.1 45/ 45†† 39/ 41 104/106 8.5/ 8.7 18.0/20.9 45.1/ 48.7 50/ 50†† 44/ 47 109/112 7.9/10.5 21.9/25.3 49.9/ 54.2 60/ 60†† 48/ 52 113/116 12.0/16.0 33.3/38.5 64.2/ 70.7 70/ 80†† 61/ 67 124/129

STD 187 254 10.2 75.0 1.5 3.1

— — 24.0/ 24.0 30/ 30†† 25/ 25 95/ 95 3.3/ 4.4 9.2/10.6 35.5/ 37.2 40/ 40†† 35/ 37 104/106 4.9/ 6.5 13.6/15.6 41.0/ 43.5 45/ 45†† 40/ 43 109/111 6.5/ 8.7 18.0/20.9 46.5/ 50.1 50/ 60†† 45/ 49 113/116 7.9/10.5 21.9/25.3 51.3/ 55.6 60/ 60†† 50/ 54 117/120 12.0/16.0 33.3/38.5 65.6/ 72.1 70/ 80 63/ 69 128/134

ALT 187 254 10.2 75.0 1.5 4.9

— — 24.9/ 24.9 25/ 25†† 26/ 26 125/125 3.3/ 4.4 9.2/10.6 36.4/ 38.1 40/ 40†† 36/ 38 134/135 4.9/ 6.5 13.6/15.6 41.9/ 44.4 45/ 45†† 41/ 44 138/140 6.5/ 8.7 18.0/20.9 47.4/ 51.0 50/ 50†† 46/ 50 143/145 7.9/10.5 21.9/25.3 52.2/ 56.5 60/ 60†† 51/ 55 146/150 12.0/16.0 33.3/38.5 66.5/ 73.0 70/ 80 64/ 70 158/163

HIGH-STATIC 187 254 10.2 75.0 1.5 5.8

— — 10.3 15†† 10 47 6.0 7.2 19.3 20†† 19 54 8.8 10.6 23.5 25†† 23 58 11.5 13.8 27.5 30†† 26 61 14.0 16.8 31.3 35†† 30 64

STD 414 508 4.8 40.0 0.8 1.7

— — 11.1 15†† 11 50 6.0 7.2 20.1 25†† 20 57 8.8 10.6 24.3 25†† 24 61 11.5 13.8 28.3 30†† 27 64 14.0 16.8 32.1 35†† 31 67

ALT 414 508 4.8 40.0 0.8 2.1

— — 11.6 15†† 12 65 6.0 7.2 20.6 25†† 20 72 8.8 10.6 24.8 25†† 24 75 11.5 13.8 28.8 30†† 28 78 14.0 16.8 32.6 35†† 31 81

HIGH-STATIC 414 508 4.8 40.0 0.8 2.6

575-3-60 STD 518 632 3.8 31.0 0.8 1.7 — — 8.2 15†† 8 37 ALT 518 632 3.8 31.0 0.8 2.1 — — 8.8 15†† 9 39 HIGH-STATIC 518 632 3.8 31.0 0.8 2.6 — — 9.2 15†† 9 51

— — 46.2/ 46.2 50/ 50†† 45/ 45 148/148 3.3/ 4.4 15.9/18.3 66.1/ 69.1 70/ 70 63/ 66 163/166 6.5/ 8.7 31.3/36.3 85.3/ 91.6 90/100 81/ 86 179/184 9.8/13.0 47.1/54.2 105.1/113.9 110/126 99/107 195/202 13.1/17.4 63.0/72.5 124.1/136.8 125/150 117/128 211/220 15.8/21.0 76.0/87.5 142.1/155.6 150/175 132/145 224/235

STD 187 254 29.1 132.0 1.5 3.5

— — 47.6/ 47.6 50/ 50†† 46/ 46 152/152 3.3/ 4.4 15.9/18.3 67.5/ 70.5 70/ 80 65/ 67 168/170 6.5/ 8.7 31.3/36.3 86.7/ 93.0 90/100 82/ 88 183/188 9.8/13.0 47.1/54.2 106.5/115.3 110/125 101/109 199/206 13.1/17.4 63.0/72.5 126.3/138.2 150/150 119/130 215/225 15.8/21.0 76.0/87.5 142.6/157.0 150/175 134/147 228/240

ALT 187 254 29.1 132.0 1.5 4.9

— — 30.8/ 30.8 35/ 35†† 31/ 31 107/107 4.9/ 6.5 13.6/15.6 47.8/ 50.3 50/ 60†† 46/ 49 120/107 6.5/ 8.7 18.0/20.9 53.3/ 56.9 60/ 60†† 51/ 55 125/127 12.0/16.0 33.3/38.5 72.4/ 78.9 80/ 80 69/ 75 140/145 15.8/21.0 43.9/50.5 85.7/ 93.9 90/100 81/ 89 150/157

STD 187 254 16.8 91.0 1.5 3.5

— — 32.2/ 32.2 35/ 35†† 32/ 32 111/111 4.9/ 6.5 13.6/15.6 49.2/ 51.7 50/ 60†† 48/ 50 125/127 6.5/ 8.7 18.0/20.9 54.7/ 58.3 60/ 60†† 53/ 56 129/132 12.0/16.0 33.3/38.5 73.8/ 80.3 80/ 90 71/ 76 144/150 15.8/21.0 43.9/50.5 87.1/ 95.3 90/100 83/ 90 155/162

ALT 187 254 16.8 91.0 1.5 4.9

— — 33.1/ 33.1 35/ 35†† 33/ 33 141/141 4.9/ 6.5 13.6/15.6 50.1/ 52.6 60/ 60†† 49/ 51 154/156 6.5/ 8.7 18.0/20.9 55.6/ 59.2 60/ 60†† 54/ 57 159/161 12.0/16.0 33.3/38.5 74.7/ 81.2 80/ 90 72/ 78 174/179 15.8/21.0 43.9/50.5 88.0/ 96.2 90/100 84/ 91 184/191***

HIGH-STATIC 187 254 16.8 91.0 1.5 5.8

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-1-60 · 208/230-3-60 · 036 (3 Tons) · 460-3-60 · 208/230-1-60 · 048 (4 Tons) · 208/230-3-60
Page 61 of the Bryant 549B user manual — HIGH-STATIC 414 508 7.7 59.6 0.8 3.4
Page 61 · click to enlarge
Page 61

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 15.3 20†† 15 58 6.0 7.2 24.3 25†† 23 66 11.5 13.8 32.5 35†† 31 72 14.0 16.8 36.3 40†† 34 75 23.0 27.7 49.9 50†† 47 86

STD 414 508 8.4 50.0 0.8 1.8

— — 15.6 20†† 15 60 6.0 7.2 24.6 25†† 24 67 11.5 13.8 32.8 35†† 31 74 14.0 16.8 36.6 40†† 35 77 23.0 27.7 50.2 60†† 47 88

ALT 414 508 8.4 50.0 0.8 2.1

— — 16.1 20†† 16 75 6.0 7.2 25.1 30†† 24 82 11.5 13.8 33.3 35†† 32 88 14.0 16.8 37.1 40†† 35 91 23.0 27.7 50.7 60†† 48 102

HIGH-STATIC 414 508 8.4 50.0 0.8 2.6

575-3-60 STD 518 632 6.7 37.0 0.8 1.8 — — 12.2 15†† 12 44 ALT 518 632 6.7 37.0 0.8 2.1 — — 12.4 15†† 12 45 HIGH-STATIC 518 632 6.7 37.0 0.8 2.6 — — 12.8 15†† 13 57

— — 45.6/ 45.6 50/ 50†† 45/ 45 189/189 4.9/ 6.5 23.6/27.1 75.1/ 79.5 80/ 80 72/ 76 213/216 6.5/ 8.7 31.3/36.3 84.7/ 91.0 90/100 81/ 86 220/225*** 9.8/13.0 47.1/54.2 104.3/113.3 110/125 99/107 236/243*** 13.1/17.4 63.0/72.5 124.3/136.2 150/150 117/128 252/261*** 15.8/21.0 76.0/87.5 140.6/155.0 150/175 132/145 265/276***

STD 187 254 26.7 170.0 1.5 5.9

— — 48.5/ 48.5 50/ 50†† 48/ 48 222/222 4.9/ 6.5 23.6/27.1 78.0/ 82.4 80/ 90 75/ 79 246/249 6.5/ 8.7 31.3/36.3 87.6/ 93.9 90/100 84/ 90 253/258*** 9.8/13.0 47.1/54.2 107.4/116.2 110/125 102/110 269/276*** 13.1/17.4 63.0/72.5 127.2/139.1 150/150 121/131 285/294*** 15.8/21.0 76.0/87.5 143.5/157.9 150/175 135/149 298/309***

ALT 187 254 26.7 170.0 1.5 8.8

— — 31.5/ 31.5 35/ 35†† 32/ 32 143/143 4.9/ 6.5 13.6/15.6 48.5/ 51.0 50/ 60†† 47/ 50 157/159 7.9/10.5 21.9/25.3 58.8/ 63.1 60/ 70 57/ 61 165/168 12.0/16.0 33.3/38.5 73.1/ 79.6 80/ 90 70/ 76 176/181 15.8/21.0 43.9/50.5 86.3/ 94.6 90/100 82/ 90 187/193*** 19.9/26.5 55.2/63.8 100.5/111.2 110/125 95/105 198/207***

STD 187 254 15.4 124.0 1.5 5.9

— — 31.4/ 31.4 35/ 35†† 32/ 32 174/174 4.9/ 6.5 13.6/15.6 48.4/ 50.9 50/ 60†† 47/ 50 187/189 7.9/10.5 21.9/25.3 58.7/ 63.0 60/ 70 57/ 61 195/199 12.0/16.0 33.3/38.5 73.0/ 79.5 80/ 90 70/ 76 207/212 15.8/21.0 43.9/50.5 86.2/ 94.5 90/100 82/ 90 217/224*** 19.9/26.5 55.2/63.8 100.4/111.1 110/125 95/105 229/237***

ALT 187 254 15.4 124.0 1.5 5.8

— — 33.1/ 33.1 35/ 35†† 34/ 34 193/193 4.9/ 6.5 13.6/15.6 50.1/ 52.6 60/ 60†† 49/ 52 206/208 7.9/10.5 21.9/25.3 60.4/ 64.7 70/ 70 59/ 63 214/218 12.0/16.0 33.3/38.5 74.7/ 81.2 80/ 90 72/ 78 226/231 15.8/21.0 43.9/50.5 87.9/ 96.2 90/100 84/ 92 236/243*** 19.9/26.5 55.2/63.8 102.1/112.8 110/125 97/107 248/256***

HIGH-STATIC 187 254 15.4 124.0 1.5 7.5

— — 15.8 20†† 16 70 6.0 7.2 24.8 30†† 24 77 11.5 13.8 33.1 35†† 32 83 14.0 16.8 36.8 40†† 35 86 23.0 27.7 50.4 60†† 48 97 25.5 30.7 54.2 60†† 51 100

STD 414 508 7.7 59.6 0.8 3.2

— — 15.2 20†† 15 84 6.0 7.2 24.2 30†† 24 91 11.5 13.8 32.5 35†† 31 98 14.0 16.8 36.2 40†† 35 101 23.0 27.7 49.8 60†† 47 112 25.5 30.7 53.6 60†† 51 115

ALT 414 508 7.7 59.6 0.8 2.6

— — 16.0 20†† 16 94 6.0 7.2 25.0 25†† 24 101 11.5 13.8 33.3 35†† 32 107 14.0 16.8 34.8 35†† 33 108 23.0 27.7 50.6 60†† 48 121 25.5 30.7 54.4 60†† 51 124

HIGH-STATIC 414 508 7.7 59.6 0.8 3.4

575-3-60 STD 518 632 6.2 49.4 0.8 3.2 — — 12.7 15†† 13 57 ALT 518 632 6.2 49.4 0.8 2.6 — — 12.2 15†† 12 69 HIGH-STATIC 518 632 6.2 49.4 0.8 3.4 — — 12.9 15†† 13 77

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 460-3-60 · 048 (4 Tons) · (cont) · 208/230-1-60 · 208/230-3-60 · 060 (5 Tons) · 460-3-60
Page 62 of the Bryant 549B user manual — HIGH-STATIC 414 508 6.7 42.0 0.7 4.8
Page 62 · click to enlarge
Page 62

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

FLA

Min Max RLA LRA Nominal

kW** FLA MCA MOCP FLA LRA

— — 40.4/ 40.4 45/ 45†† 40/ 40 195/195 4.9/ 6.5 13.6/15.6 57.4/ 59.9 60/ 60†† 56/ 58 208/211 7.9/10.5 21.9/25.3 67.8/ 72.0 70/ 80 65/ 69 217/220 12.0/16.0 33.3/38.5 82.0/ 88.5 90/ 90 78/ 84 228/233*** 15.8/21.0 43.9/50.5 95.3/103.5 100/110 90/ 98 239/245*** 19.9/26.5 55.2/63.8 109.4/120.1 110/125 103/113 250/259***

STD 187 254 22.7 146.0 1.4 5.8

— — 42.1/ 42.1 45/ 45†† 42/ 42 214/214 4.9/ 6.5 13.6/15.6 59.1/ 61.6 60/ 70 58/ 60 227/229 7.9/10.5 21.9/25.3 69.5/ 73.7 70/ 80 67/ 71 236/239 12.0/16.0 33.3/38.5 83.7/ 90.2 90/100 80/ 86 247/252*** 15.8/21.0 43.9/50.5 97.0/105.2 100/110 92/100 258/264*** 19.9/26.5 55.2/63.8 111.1/121.8 125/125 105/115 269/278***

HIGH-STATIC 187 254 22.7 146.0 1.4 7.5

— — 19.7 20†† 19 97 6.0 7.2 28.7 30†† 28 104 11.5 13.8 37.0 40†† 35 111 14.0 16.8 40.7 45†† 39 114 23.0 27.7 54.4 60†† 51 125 25.5 30.7 58.1 60†† 55 128

STD 414 508 11.4 73.0 0.7 2.6

— — 20.5 25†† 20 107 6.0 7.2 29.5 30†† 29 114 11.5 13.8 37.8 40†† 36 121 14.0 16.8 41.5 45†† 40 124 23.0 27.7 55.2 60†† 52 134 25.5 30.7 58.9 60†† 56 137

HIGH-STATIC 414 508 11.4 73.0 0.7 3.4

575-3-60 STD 518 632 9.1 58.4 0.7 2.6 — — 15.8 20†† 16 78 HIGH-STATIC 518 632 9.1 58.4 0.7 3.4 — — 16.4 20†† 16 85

— — 43.6/ 43.6 45/ 45†† 46/ 46 234/234 7.8/10.5 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 256/259 12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 267/272*** 18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 285/294*** 24.0/32.0 66.6/ 77.0 126.8/139.8 150/150 123/135 300/311*** 31.8/42.4 88.3/102.0 153.9/171.1 175/175 148/164 322/336***

STD 187 254 13.4 91.0 1.4 5.8

— — 48.4/ 48.4 50/ 50†† 52/ 52 277/277 7.8/10.5 21.7/ 25.0 75.5/ 79.6 80/ 80 77/ 81 299/302*** 12.0/16.0 33.3/ 38.5 90.0/ 96.5 90/100 90/ 96 311/316*** 18.6/24.8 51.6/ 59.7 112.9/123.0 125/125 111/120 329/337*** 24.0/32.0 66.6/ 77.0 131.6/144.6 150/150 128/140 344/354*** 31.8/42.4 88.3/102.0 158.7/175.9 175/200 153/169 366/379***

HIGH-STATIC 187 254 13.4 91.0 1.4 10.6

— — 21.3 25†† 23 110 14.0 16.7 42.1 45†† 42 127 16.5 19.8 46.0 50†† 45 130 27.8 33.4 63.0 70 61 143 33.0 39.7 70.9 80 68 150 41.7 50.2 84.0 90 80 160***

090 (71/2 Tons)

STD 414 508 6.7 42.0 0.7 2.6

— — 23.5 25†† 25 132 14.0 16.7 44.3 45†† 44 148 16.5 19.8 48.2 50†† 48 151 27.8 33.4 65.2 70 63 165 33.0 39.7 73.1 80 71 171 41.7 50.2 86.2 90 83 182***

HIGH-STATIC 414 508 6.7 42.0 0.7 4.8

STD 518 632 5.4 39.0 0.7 2.6 — — 17.1 20†† 18 99 17.0 17.1 38.5 40†† 38 116 34.0 34.1 59.7 60†† 57 133

HIGH-STATIC 518 632 5.4 39.0 0.7 4.8 — — 18.9 20†† 20 116 17.0 17.1 40.2 45†† 40 133 34.0 34.1 61.5 70 59 150

Show 8 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-3-60 · 072 (6 Tons) · 460-3-60 · 208/230-3-60 · 460-3-60 · 575-3-60
Page 63 of the Bryant 549B user manual — HIGH-STATIC 518 632 6.9 49.4 0.7 7.4
Page 63 · click to enlarge
Page 63

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

COMPRESSOR

ELECTRIC

HEAT* POWER SUPPLY DISCONNECT

UNIT 548F NOMINAL

IFM TYPE

RANGE

IFM FLA

SIZE†

Min Max RLA LRA Nominal

FLA

kW** FLA MCA MOCP FLA LRA

— — 44.6/ 49.9 50/ 50†† 52/ 52 326/326 7.8/10.5 21.7/ 25.0 76.5/ 80.7 80/ 90 77/ 81 348/351 12.0/16.0 33.3/ 38.5 91.0/ 97.5 100/100 91/ 96 359/364 18.6/24.8 51.6/ 59.7 113.9/124.0 125/125 112/121 377/386 24.0/32.0 66.6/ 77.0 132.7/145.7 150/150 129/144 392/403 31.8/42.4 88.3/102.0 154.8/176.9 175/200 154/170 414/428

STD 187 254 16.0 137.0 1.4 5.8

— — 49.2/ 54.2 60/ 60†† 58/ 58 369/369 7.8/10.5 21.7/ 25.0 81.3/ 85.5 90/ 90 83/ 86 391/394*** 12.0/16.0 33.3/ 38.5 95.8/102.3 100/110 96/102 403/408*** 18.6/24.8 51.6/ 59.7 118.7/128.8 125/150 117/126 421/429*** 24.0/32.0 66.6/ 77.0 137.5/150.5 150/175 134/146 436/446*** 31.8/42.4 88.3/102.0 164.6/181.7 175/200 159/175 458/471***

HIGH-STATIC 187 254 16.0 137.0 1.4 10.6

— — 24.9 25†† 26 164 14.0 16.7 45.7 50†† 45 181 16.5 19.8 49.6 50†† 49 184 27.8 33.4 66.6 70 65 197 33.0 39.7 74.5 80 72 204 41.7 50.2 87.6 90 84 214***

102 (81/2 Tons)

STD 414 508 8.3 69.0 0.7 2.6

— — 24.9 30†† 29 186 14.0 16.7 47.9 50†† 48 202 16.5 19.8 51.8 60†† 51 205 27.8 33.4 68.8 70 67 219 33.0 39.7 76.7 80 74 225 41.7 50.2 89.8 90 86 236***

HIGH-STATIC 414 508 8.3 69.0 0.7 4.8

STD 518 632 6.4 58.0 0.7 2.6 — — 18.4 20†† 20 137 17.0 17.1 40.7 45†† 40 154 34.0 34.1 62.0 70 60 171

HIGH-STATIC 518 632 6.4 58.0 0.7 4.8 — — 20.6 25†† 22 154 17.0 17.1 42.5 45†† 42 171 34.0 34.1 63.7 70 62 188

— — 52.1/ 52.1 60/ 60†† 55/ 55 300/300 7.8/10.4 21.7/ 25.0 79.2/ 83.4 80/ 90 80/ 84 322/325*** 12.0/16.0 33.3/ 38.5 93.7/100.2 100/110 93/ 99 333/338*** 24.0/32.0 66.6/ 77.0 135.4/148.4 150/150 132/144 366/377*** 31.8/42.4 88.3/102.0 162.5/179.6 175/200 157/172 388/402*** 37.6/50.0 104.4/120.3 182.6/172.4 200/200 175/193 404/420***

STD 187 254 17.2 124.0 1.4 5.8

— — 53.8/ 53.8 60/ 60†† 57/ 57 319/319 7.8/10.4 21.7/ 25.0 80.9/ 85.1 90/ 90 82/ 86 341/344*** 12.0/16.0 33.3/ 38.5 95.4/101.9 100/110 93/101 352/357*** 24.0/32.0 66.6/ 77.0 137.1/150.1 150/175 134/145 385/396*** 31.8/42.4 88.3/102.0 164.2/181.3 175/200 158/174 407/421*** 37.6/50.0 104.4/120.3 184.3/174.1 200/200 177/195 423/439***

ALT 187 254 17.2 124.0 1.4 7.5

— — 61.3/ 61.3 70/ 70 66/ 66 367/367 7.8/10.4 21.7/ 25.0 88.4/ 92.6 90/100 91/ 94 389/392*** 12.0/16.0 33.3/ 38.5 102.9/109.4 110/110 104/110 400/405*** 24.0/32.0 66.6/ 77.0 144.6/157.6 150/175 142/154 433/444*** 31.8/42.4 88.3/102.0 171.7/188.8 175/200 167/183 455/459*** 37.6/50.0 104.4/120.3 191.8/181.6 200/200 186/204 471/487***

HIGH-STATIC 187 254 17.2 124.0 1.4 15.0

— — 25.5 30†† 27 145 16.5 19.8 50.3 60†† 50 165 27.8 33.4 67.3 80 65 178 33.0 39.7 75.2 80 73 185 41.7 50.2 88.3 90 85 195*** 50.0 60.1 85.6 90 96 205***

STD 414 508 8.6 59.6 0.7 2.6

— — 26.3 30†† 28 185 16.5 19.8 51.1 60†† 51 204 27.8 33.4 68.1 70 66 218 33.0 39.7 76.0 80 73 224 41.7 50.2 89.1 90 85 235*** 50.0 60.1 86.4 90 97 245***

ALT 414 508 8.6 59.6 0.7 3.4

— — 30.3 35†† 32 179 16.5 19.8 55.1 60†† 55 198 27.8 33.4 72.1 80 71 212 33.0 39.7 80.0 80 78 218 41.7 50.2 93.1 100 90 229*** 50.0 60.1 90.4 100 102 239***

HIGH-STATIC 414 508 8.6 59.6 0.7 7.4

— — 20.5 25†† 22 120 17.0 17.1 41.8 45†† 41 137 34.0 34.1 63.1 70 61 154 51.0 51.2 71.7 80 80 171***

STD 518 632 6.9 49.4 0.7 2.6

— — 21.1 25†† 22 151 17.0 17.1 42.5 45†† 42 168 34.0 34.1 63.7 70 62 185 51.0 51.2 72.3 80 81 202***

ALT 518 632 6.9 49.4 0.7 3.4

— — 24.3 25†† 26 146 17.0 17.1 45.7 50†† 46 163 34.0 34.1 66.9 70 65 180 51.0 51.2 75.5 80 85 198***

HIGH-STATIC 518 632 6.9 49.4 0.7 7.4

Show 9 more labels / short text on this page
(each) OFM · V-PH-Hz · 208/230-3-60 · 460-3-60 · 575-3-60 · 208/230-3-60 · 120 (10 Tons) · 460-3-60 · 575-3-60
Page 64 of the Bryant 549B user manual — ELECTRICAL DATA (cont)
Page 64 · click to enlarge
Page 64

ELECTRICAL DATA (cont)

LEGEND AND NOTES FOR ELECTRICAL TABLES LEGEND

Example: Supply voltage is 460-3-60.

FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455

= 457 Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the overcur- rent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance

= 100 x max voltage deviation from average voltage

= 1371 · average voltage

Page 65 of the Bryant 549B user manual — MUST
Page 65 · click to enlarge
Page 65

TYPICAL WIRING SCHEMATIC

LEGEND AHA — Adjustable Heat Anticipator AWG — American Wire Gage C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Capacitor CH — Crankcase Heater COMP — Compressor Motor D — Diode DB — Defrost Board DFT — Defrost Thermostat EC — Enthalpy Control ECON — Economizer EPS — Emergency Power Supply

(Nine-Volt Battery) ER — Economizer Relay FSS — Filter Status Switch FPT — Freeze-Up Protection Thermostat FU — Fuse GND — Ground HC — Heater Contactor (Strip Heat) HPS — High-Pressure Switch HR — Heater Relay IFC — Indoor-Fan Contactor IFM — Indoor-Fan Motor LPS — Low-Pressure Switch LSM — Limit Switch (Manual Reset) MTR — Motor OAT — Outdoor-Air Thermostat OFM — Outdoor-Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal R — Relay RAT — Return-Air Thermostat RVS — Reversing Valve Solenoid SAT — Supply-Air

Thermostat ST — Start Thermistor SW1 — Switch Fully Open SW2 — Switch Fully Closed SW3 — Switch Min.

Vent Position SW4 — Switch Max.

Vent Position TB — Terminal Block TC — Thermostat-

Cooling TH — Thermostat-

Heating TRAN — Transformer

Bryant 549B — TYPICAL WIRING SCHEMATIC diagram (page 65)
Fig. 14
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent. 2. Thermostat: HH07AT170, 172, 174. Subbase: HH93AZ176. 3. Set heat anticipator at .8 amp for first stage and .3 amp for second stage. 4. Use copper conductors only. 5. Use copper, copper-clad aluminum or aluminum conductors.

Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only. Not to represent wiring.

VOLTAGE

CB

RATING

TRIP AMPS MFG. PT. NO.

MUST

24V POTTER & BRUMFIELD W28X-1024-3.2 3.2

548F036-072

Show 7 more labels / short text on this page
Field Splice · Marked Wire · Terminal (Marked) · Terminal (Unmarked) · Terminal Block · Splice · Splice (Marked)
Page 66 of the Bryant 549B user manual — WHT/YEL BLK/YEL
Page 66 · click to enlarge
Page 66

TYPICAL WIRING SCHEMATIC (cont)

7 1/2 AND 8 1/2 TON UNITS ONLY

AHA — Adjustable Heat Anticipator AWG — American Wire Gage C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Capacitor CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor D — Diode DB — Defrost Board DFT — Defrost Thermostat EC — Enthalpy Control ECON — Economizer EPS — Emergency Power Supply (Nine-Volt Battery) EQUIP — Equipment ER — Economizer Relay FPT — Freeze-Up Protection Thermostat FU — Fuse GND — Ground HC — Heater Contactor (Strip Heat) HPS — High-Pressure Switch HR — Heater Relay IFC — Indoor-Fan Contactor IFM — Indoor-Fan Motor IFMOVL — Indoor-Fan Motor Overload Switch LPS — Low-Pressure Switch LSM — Limit Switch (Manual Reset) MCA — Minimum Circuit Amps MTR — Motor OAT — Outdoor-Air Thermostat OFC — Outdoor-Fan Contactor OFM — Outdoor-Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal R — Relay RAT — Return-Air Thermostat RVS — Reversing Valve Solenoid SAT — Supply-Air Thermostat SW1 — Switch Fully Open SW2 — Switch Fully Closed SW3 — Switch Min. Vent Position SW4 — Switch Max. Vent Position TB — Terminal Block TC — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer

50DK508234

USED FORMOUTDOOR

CONFIG

STATUS

RED

24VAC

OAT

TAN

OAT

AIR ENTHALPY

50DK509044 ACTUATOR

BRN

24COM

COM

VIO

1 RED

GRN

GND

OAH

WHT

GRY

+15V

RED

BLU

ORN

RAT

TAN

VIO WHT RED

BLK

COM

VIO

BRN

STEPPER

50DK508232

MIN

POS (X)

RAM

WHT

GRY

DRIVE

+15V

RED

VIO

A B

C D

LOCKOUT ECON

CO2 +

RAT

SP

CO2 (COM)

PNK

B1

OFF 20º

30º

(PPM) MECH CLG

DAT

VIO

YEL

BLU

Y1

10º

50º 40º

COM

PNK

ORN

YEL

Y2

REM POT

BLK

G

CO SP

COM

AO

COM

LED

FIELD INSTALLED OPTION

COM

PL6

12-PIN FEMALE

Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only. Not to represent wiring.

WHT/YEL BLK/YEL

WHT/GRY

3-PIN MOLEX

BLK/GRY

3 BRN

NOT USED

MOLEX CONNECTOR

CONNECTOR CABLE

548F090-120

Show 11 more labels / short text on this page
AD-DME1711-1 EconoMi$er · 0 20 40 · Field Splice · Marked Wire · Terminal (Marked) · 800 1000 · 1200 1400 · Terminal (Unmarked) · Terminal Block · Splice · Splice (Marked)
Page 67 of the Bryant 549B user manual — TONS
Page 67 · click to enlarge
Page 67

MODEL NUMBER NOMENCLATURE

(ODS Model Number)

549B E X 090 000 AA

549B – Single-Packaged High-Efficiency Heat Pump Unit

Factory-Installed Options See 549B price pages for factory-installed option codes

Voltage Designation E – 460-3-60 J – 208/230-1-60 P – 208/230-3-60

X – No Heat Installed

(Field-installed electric heaters available)

Nominal Tons 036 – 3 048 – 4 060 – 5 072 – 6 090 – 7-1/2 120 – 10

Electric Heaters 000 – No factory-installed electric heaters

50TFQ004-012 549B036-120

LEGEND ODS — Order Distribution System

ARI* CAPACITY RATINGS

549B036-060

COOLING HEATING (High Temp) SOUND RATING (decibels) Cap. (Btuh) SEER† Cap. (Btuh) HSPF†

UNIT 549B NOMINAL

TONS

036 3 36,000 12.0 34,000 7.6 76 048 4 46,000 12.0 46,000 7.6 76 060 5 60,000 11.9 60,000 7.6 80

549B072-120

COOLING HEATING

HEATING

(Low) SOUND RATING (decibels)

UNIT 549B NOMINAL

IPLV Cap. (Btuh) EER Cap. (Btuh) COP Cap. (Btuh) COP

TONS

072 6 71,000 10.5 69,000 3.4 37,000 2.2 80 — 090 71/2 88,000 10.3 85,000 3.3 48,000 2.2 82 — 120 10 116,000 10.3 114,000 3.3 64,000 2.2 84 10.4

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature. High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F db, 43 F wb outdoor entering-air temperature. Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F db, 15 F wb outdoor entering-air temperature.

Cap. — Net Capacity (Btuh) COP — Coefficient of Performance EER — Energy Efficiency Ratio HSPF — Heating Seasonal Performance Factor IPLV — Integrated Part-Load Values SEER — Seasonal Energy Efficiency Ratio

*Air Conditioning and Refrigeration Institute. †Applies only to units with capacity of 60,000 Btuh or less. NOTE: Rated in accordance with ARI Standard 210/240-95 and 270-95. Rat- ings are net values, reflecting effects of circulating fan heat. Supple- mentary electric heat is not included. Ratings based on: Cooling Standard: 80 F db (dry bulb), 67 F wb (wet bulb) indoor entering-air temperature and 95 F db outdoor entering-air temperature.

(High)

Page 68 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 68 · click to enlarge
Page 68

PHYSICAL DATA

549B036-072

BASE UNIT 549B 036 048 060 072 NOMINAL CAPACITY (tons) 3 4 5 6 OPERATING WEIGHT (lb)

Unit 500 550 590 630 Durablade Economizer 34 EconoMi$er 47 Roof Curb 115 COMPRESSOR Scroll Quantity 1 Oil (oz) 42 53 50 60 REFRIGERANT TYPE R-22 Operating Charge (lb) 6.9 9.6 10.8 17.7 OUTDOOR FAN Propeller Quantity...Diameter (in.) 1...22 Nominal Cfm 3500 Motor Hp...Rpm 1/8...825 1/8...825 1/4...1100 1/4...1100 OUTDOOR COIL Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device Rows...Fins/in. 1...17 2...17 2...17 2...17 Total Face Area (sq ft) 14.58 16.53 16.53 16.53 INDOOR FAN Centrifugal Size (in.) 10 x 10 10 x 10 10 x 10 10 x 10 Type Drive Belt Nominal Cfm 1200 1600 2000 2400 Maximum Continuous Bhp 1.20 1.20 1.80 2.40 Motor Frame 48 48 48 56 Fan Rpm 760-1090 840-1185 1020-1460 1120-1585 Motor Bearing Type Ball Maximum Fan Rpm 1725 Motor Pulley Pitch Diameter A/B (in.) 1.9/2.9 1.9/2.9 2.4/3.4 2.4/3.4 Fan Pulley Pitch Diameter (in.) 4.5 4.0 4.0 3.7 Belt — Type...Length (in.) A...33 A...33 A...38 A...38 Pulley Center Line Distance (in.) 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 Speed Change per Full Turn of

50TFQ004-012 549B036-120

Movable Pulley Flange (rpm) 65 70 93 93 Movable Pulley Maximum Full Turns

From Closed Position 5 5 6 5 Factory Setting Full Turns Open 3 Factory Speed Setting (rpm) 890 980 1240 1305 Fan Shaft Diameter at Pulley (in.) 5/8 INDOOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins, Fixed Orifice Metering Device Rows...Fins/in. 2...15 2...15 4...15 4...15 Total Face Area (sq ft) 5.5 HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief 625 Cutout 428 Reset (Auto.) 320 LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

Cutout 7 ± 3 Reset (Auto.) 22 ± 5 FREEZE PROTECTION THERMOSTAT

Opens (F) 30 Closes (F) 45 OUTDOOR-AIR INLET SCREENS Cleanable Quantity...Size (in.) 1...20 x 24 x 1 RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 2...16 x 25 x 2

Bhp — Brake Horsepower

(Liquid Line) (psig)

Page 69 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 69 · click to enlarge
Page 69

PHYSICAL DATA (cont)

549B090,120

BASE UNIT 549B 090 120 NOMINAL CAPACITY (tons) 71/2 10 OPERATING WEIGHT (lb)

Unit 870 1000 Durablade Economizer 44 44 EconoMi$er 62 62 Roof Curb 223 223 COMPRESSOR Scroll Quantity 2 2 Oil (oz) (each compr) 57 57 REFRIGERANT TYPE R-22 Operating Charge (lb) Circuit 1 9.1 10.6 Circuit 2 9.6 9.9 OUTDOOR FAN Propeller Quantity...Diameter (in.) 2...22 2...22 Nominal Cfm 6500 6500 Motor Hp...Rpm 1/4...1100 1/4...1100 OUTDOOR COIL Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device Rows...Fins/in. 2...17 2...17 Total Face Area (sq ft) 20.5 25.1 INDOOR FAN Centrifugal Size (in.) 15 x 15 15 x 15 Type Drive Belt Belt Nominal Cfm 3000 4000 Maximum Continuous Bhp 2.90 4.20 Motor Frame 56 56 Fan Rpm Range 725-925 860-1080 Motor Bearing Type Ball Ball Maximum Fan Rpm 1725 2100 Motor Pulley Pitch Diameter

50TFQ004-012 549B036-120

A/B (in.) 3.4/4.4 4.0/5.0 Fan Pulley Pitch Diameter (in.) 8.0 8.0 Belt — Type...Length (in.) A...51 A...51 Pulley Center Line Distance (in.) 16.75-19.25 15.85-17.50 Fan Shaft Diameter at Pulley (in.) 1 1 Speed Change per Full Turn of

Movable Pulley Flange (rpm) 50 45 Movable Pulley Maximum Full

Turns from Closed Position 5 5 Factory Setting — Full Turns Open 5 5 Factory Speed Setting (rpm) 725 860 INDOOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins, Fixed Orifice Metering Device Rows...Fins/in. 3...15 4...15 Total Face Area (sq ft) 8.89 11.11 HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief 625 Cutout 428 Reset (Auto.) 320 LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig) Cutout 7 ± 3 Reset (Auto.) 22 ± 5 FREEZE PROTECTION THERMOSTAT

Opens (F) 30 Closes (F) 45 OUTDOOR-AIR INLET FILTER Cleanable

Quantity...Size (in.) 1...20 x 25 x 1 1...16 x 25 x 1 RETURN-AIR FILTERS Throwaway Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2

Bhp — Brake Horsepower

Page 70 of the Bryant 549B user manual — BASE UNIT DIMENSIONS
Page 70 · click to enlarge
Page 70

BASE UNIT DIMENSIONS

Bryant 549B — BASE UNIT DIMENSIONS diagram (page 70)
Fig. 15
Page 71 of the Bryant 549B user manual — BASE UNIT DIMENSIONS (cont)
Page 71 · click to enlarge
Page 71

BASE UNIT DIMENSIONS (cont)

Bryant 549B — BASE UNIT DIMENSIONS (cont) diagram (page 71)
Fig. 16 · BASE UNIT DIMENSIONS (cont)
Page 72 of the Bryant 549B user manual — 549B036-072
Page 72 · click to enlarge
Page 72

ACCESSORY DIMENSIONS

CONNECTOR

PKG. ACCY. B C D ALT DRAIN HOLE GAS POWER CONTROL

ROOF CURB ACCESSORY A UNIT SIZE

CRBTMPWR001A00

3/4″ [19] NPT 1/2″ [12.7] CRBTMPWR002A00 11/4″ [31.7]

3 / 4 ″ [19] NPT

CRRFCURB001A00 1′-2″ [356] 549B036-072 CRRFCURB002A00 2′-0″ [610]

1′-911/16″ [551]

1′-4″ [406]

13/4″ [44.5]

CRBTMPWR003A00

3/4″ [19] NPT 1/2″ [12.7] CRBTMPWR004A00

1 / 2 ″ [12.7] NPT

3/4″ [19] NPT 11/4″ [31.7]

7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 002A00 are for thru-the-curb type gas. Packages CRBTMPWR003A00 and 004A00 are for thru-thebottom type gas connections.

50TFQ004-012 549B036-120

TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE

TO ENSURE AIRTIGHT CONNECTION. PLACE UNIT AS CLOSE TO THIS END AS POSSIBLE

549B036-072

Page 73 of the Bryant 549B user manual — 549B090,120
Page 73 · click to enlarge
Page 73

ACCESSORY DIMENSIONS (cont)

D ALT DRAIN

ROOF CURB ACCESSORY “A” UNIT SIZE

CONNECTOR

PKG. ACCY. B C

GAS POWER CONTROL

HOLE

CRRFCURB003A00 1′-2″ [356] 549B090,120 CRRFCURB004A00 2′-0″ [610]

CRBTMPWR001A00

3/4″ [19] NPT 1/2″ [12.7] NPT CRBTMPWR002A00 11/4″ [31.7]

3 / 4 ″ [19] NPT

CRBTMPWR003A00

3/4″ [19] NPT 1/2″ [12.7] NPT CRBTMPWR004A00

2′-87/16″ [827]

1′-1015/16″ [583]

13/4″ [44.5]

1 / 2 ″ [12.7] NPT

1. Roof curb accessory is shipped disassembled. 2. Insulated panels: 1-in. thick polyurethane foam, 1 3 / 4 lb density. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: 16-gage steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance 4 ft on each side.

3/4″ [19] NPT 11/4″ [31.7]

7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thruthe-bottom type gas connections.

50TFQ004-012 549B036-120

TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.

TO ENSURE AN AIRTIGHT CONNECTION, PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE.

549B090,120

Page 74 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 74 · click to enlarge
Page 74

SELECTION PROCEDURE (WITH 549B048 EXAMPLE)

I DETERMINE COOLING AND HEATING REQUIRE-

IV DETERMINE FAN SPEED AND POWER REQUIRE-

MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) 38,000 Btuh Sensible Heat Capacity (SHC) 24,000 Btuh Required Heating Capacity 35,000 Btuh Outdoor Entering-Air Temperature 95 F Outdoor-Air Winter Design Temperature 0° F Indoor-Air Winter Design Temperature 70 F Indoor Entering-Air

MENTS AT DESIGN CONDITIONS. Before entering Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Pressure Drop tables, find:

External static pressure .45 in. wg Durablade economizer .05 in. wg Electric heat .09 in. wg Total static pressure .59 in. wg

Temperature 80 F edb (entering air, dry bulb),

Enter the Fan Performance table for 549B048 vertical dis- charge. At 1600 cfm and 230-v, the standard motor will deliver 1.2 in. wg static pressure and 1.15 brake horse- power (bhp). This will adequately handle job requirements. NOTE: Convert bhp to Watts using the formula below and the motor efficiency found in the Indoor-Fan Motor Data table. For this example:

67 F ewb (entering air, wet bulb) Indoor-Air Quantity 1600 cfm External Static Pressure 0.45 in. wg Electrical Characteristics (V-Ph-Hz) 230-3-60 II SELECT UNIT BASED ON REQUIRED COOLING

CAPACITY. Enter Cooling Capacities table at outdoor entering temper- ature of 95 F, indoor air entering at 1600 cfm and 67 F ewb. The 549B048 unit will provide a total cooling capacity of 47,400 Btuh and a sensible heat capacity of 32,800 Btuh. For indoor-air temperature other than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in Note 3 following the cooling capacities tables. NOTE: Unit ratings are gross capacities and do not include the effect of indoor-fan motor heat. To calculate net capac- ities, see Step V. III SELECT ELECTRIC HEAT.

50TFQ004-012 549B036-120

Watts = 746 x Bhp Motor Efficiency

Watts = 746 x 1.15

Watts = 1144 V DETERMINE NET CAPACITIES.

Capacities are gross and do not include the effect of indoor-fan motor (IFM) heat. Determine net cooling capacity as follows:

Net capacity = Total capacity – IFM heat = 47,400 Btuh – (1144 Watts x 3.413

Enter the Instantaneous and Integrated Heating Ratings table at 1600 cfm. At 70 F return indoor air and 0° F air entering outdoor coil, the integrated heating capacity is 20,400 Btuh. (Select integrated heating capacity value since deductions for outdoor-coil frost and defrosting have already been made. No correction is required.) The required heating capacity is 35,000 Btuh. Therefore, 14,600 Btuh (35,000 – 20,400) additional electric heat is required. Determine additional electric heat capacity in kW.

Btuh/Watts) = 47,400 Btuh – 3904 Btuh = 43,496

Net sensible capacity = 32,800 Btuh – 3904 Btuh

Integrated heating capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it. Therefore, net capacity is equal to 40,810 Btuh, the total heating capacity determined in Step III.

14,600 Btuh = 4.3 kW of heat required. 3413 Btuh/kW

Enter the Electric Heating Capacities table for 549B048 at 208/230, 3 phase. The 6.5-kW heater at 240 v most closely satisfies the heating required. To calculate kW at 230 v, use the Multiplication Factors table. 6.5 kW x .92 = 5.98 kW 6.5 kW x .92 x 3413 = 20,410 Btuh Total unit heating capacity is 40,810 Btuh (20,400 + 20,410).

= 28,896 Btuh

Page 75 of the Bryant 549B user manual — (BF)
Page 75 · click to enlarge
Page 75

PERFORMANCE DATA

COOLING CAPACITIES

Indoor Entering Air — Cfm/Bf 900/0.13 1200/0.17 1500/0.19 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

Bf — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

75 TC 41.7 38.4 34.1 43.2 40.3 37.3 44.4 41.4 36.8 SHC 20.3 25.0 29.0 21.9 28.0 33.7 23.2 30.6 36.8 kW 2.22 2.17 2.13 2.23 2.20 2.17 2.25 2.21 2.18

85 TC 40.5 37.2 32.4 42.1 39.0 36.0 43.1 40.2 37.2 SHC 19.9 24.6 28.1 21.6 27.8 33.2 23.1 30.5 36.3 kW 2.49 2.45 2.40 2.51 2.48 2.44 2.53 2.49 2.45

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

95 TC 39.1 35.9 30.6 40.8 37.6 33.9 42.0 38.7 35.8 SHC 19.4 24.1 27.2 21.2 27.4 32.2 23.0 30.2 35.8 kW 2.80 2.75 2.69 2.82 2.78 2.74 2.85 2.80 2.76

(Btuh) 1.10 x cfm

tldb = tedb –

105 TC 37.6 33.9 28.8 39.2 36.0 32.3 40.1 37.0 34.6 SHC 18.8 23.3 26.3 20.8 26.8 31.4 22.3 29.7 34.5 kW 3.13 3.08 3.01 3.16 3.11 3.06 3.18 3.13 3.09

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

115 TC 35.9 31.9 27.9 37.4 34.2 30.2 38.3 35.3 32.5 SHC 18.2 22.5 25.8 20.2 26.1 30.1 21.8 29.0 32.5 kW 3.49 3.43 3.36 3.52 3.47 3.40 3.54 3.50 3.45

hlwb = hewb –

(Btuh) 4.5 x cfm

50TFQ004-012 549B036-120

125 TC 34.2 30.5 26.3 35.5 32.1 28.6 36.3 33.2 31.0 SHC 17.6 21.9 25.0 19.5 25.3 28.6 21.4 28.2 31.0 kW 3.88 3.81 3.74 3.91 3.85 3.79 3.92 3.88 3.84

Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Indoor Entering Air — Cfm/Bf 1200/0.13 1600/0.16 2000/0.19 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

ENTERING AIR DRY-BULB TEMP (F)

75 TC 53.1 48.7 45.0 55.6 49.6 46.7 56.1 50.7 48.4 SHC 25.1 30.7 36.7 27.3 32.6 40.5 28.2 35.1 44.6 kW 2.92 2.86 2.82 2.96 2.87 2.84 2.96 2.88 2.87

BYPASS FACTOR

79 78 77 76 75 under

(BF)

81 82 83 84 85 over

85 TC 51.9 47.3 43.7 53.9 49.1 45.6 54.4 50.2 46.9 SHC 24.9 30.2 36.2 26.7 33.4 40.4 27.7 36.1 44.2 kW 3.29 3.22 3.19 3.32 3.25 3.21 3.32 3.27 3.23

85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula

95 TC 50.5 45.5 42.1 51.8 47.4 44.0 52.3 47.4 44.6 SHC 24.3 29.5 35.6 26.0 32.8 39.9 27.0 34.3 42.4 kW 3.70 3.62 3.58 3.71 3.65 3.61 3.72 3.64 3.61

.10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

shown below.

105 TC 48.2 43.7 40.5 50.0 45.3 42.2 50.8 46.3 43.2 SHC 23.6 28.9 35.1 25.7 32.0 39.5 27.2 34.8 42.4 kW 4.14 4.06 4.04 4.16 4.08 4.05 4.18 4.10 4.06

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

115 TC 45.1 42.1 38.2 46.4 43.5 39.9 46.0 44.4 41.3 SHC 22.1 28.7 34.0 23.6 31.9 38.6 23.8 34.4 41.3 kW 4.57 4.55 4.50 4.59 4.56 4.52 4.58 4.57 4.54

125 TC 43.2 39.5 36.1 43.9 41.2 37.7 44.9 41.8 39.6 SHC 21.7 27.7 33.0 23.0 31.3 37.6 24.5 33.9 39.6 kW 5.10 5.05 5.02 5.11 5.08 5.05 5.13 5.09 5.08

Indoor Entering Air — Cfm/Bf 1500/0.03 2000/0.05 2500/0.07 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 70.4 62.3 52.9 73.6 68.2 58.4 75.5 69.1 64.9 SHC 34.2 42.0 48.1 37.8 49.6 57.6 41.1 53.8 64.8 kW 3.75 3.73 3.58 3.80 3.80 3.69 3.83 3.74 3.75

85 TC 68.5 58.9 50.8 71.0 65.4 56.5 72.7 66.9 62.7 SHC 33.6 40.6 47.1 37.1 48.5 56.4 40.3 53.9 62.6 kW 4.20 4.16 4.03 4.24 4.23 4.12 4.27 4.20 4.17

95 TC 65.8 55.3 47.4 68.8 62.2 53.5 70.5 64.0 60.3 SHC 32.8 39.2 45.5 36.6 47.3 53.5 40.2 53.1 60.2 kW 4.69 4.63 4.49 4.75 4.70 4.60 4.78 4.68 4.67

105 TC 63.0 51.4 43.6 65.6 58.1 50.2 67.1 60.7 57.5 SHC 31.7 37.6 43.6 35.6 45.8 50.2 39.1 52.1 57.5 kW 5.22 5.13 5.00 5.27 5.21 5.12 5.30 5.22 5.20

115 TC 59.4 48.2 40.8 62.1 52.6 46.8 63.7 55.5 52.6 SHC 30.6 36.4 40.8 34.6 43.7 46.8 38.4 50.3 52.5 kW 5.83 5.70 5.59 5.87 5.77 5.70 5.89 5.81 5.77

125 TC 53.8 44.6 40.4 56.8 46.3 43.3 59.5 47.8 47.3 SHC 28.7 35.0 40.3 33.0 41.3 43.3 37.3 46.9 47.3 kW 6.44 6.30 6.21 6.50 6.36 6.32 6.54 6.40 6.39

Show 15 more labels / short text on this page
Standard Ratings · 549B036 (3 Tons) · Temp (F) · Outdoor Entering Air · (Edb) · sensible capacity · total capacity · 549B048 (4 Tons) · Temp (F) · Outdoor Entering Air · (Edb) · 549B060 (5 Tons) · Temp (F) · Outdoor Entering Air · (Edb)
Page 76 of the Bryant 549B user manual — (BF)
Page 76 · click to enlarge
Page 76

COOLING CAPACITIES (cont)

Indoor Entering Air — Cfm/Bf 1800/0.06 2100/0.066 2400/0.071 3000/0.088 Indoor Entering Air — Ewb (F) 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57

Bf — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

75 TC 83.2 77.6 71.6 67.9 84.7 79.8 73.6 71.5 85.9 81.0 75.0 74.3 88.4 82.9 78.4 78.3 SHC 39.7 50.4 60.6 66.6 41.6 54.3 65.9 70.1 43.4 57.6 70.6 72.8 47.2 63.9 76.9 76.8 kW 4.90 4.78 4.69 4.63 4.94 4.84 4.71 4.69 4.97 4.86 4.74 4.73 5.04 4.91 4.81 4.81

85 TC 81.5 75.5 69.0 64.8 83.2 77.3 71.1 69.4 84.5 78.5 72.7 72.2 86.2 80.8 76.5 76.5 SHC 39.2 49.8 59.6 63.6 41.4 53.5 65.0 68.0 43.3 56.9 69.7 70.8 47.1 64.1 75.0 75.0 kW 5.45 5.34 5.23 5.16 5.49 5.36 5.27 5.23 5.52 5.38 5.29 5.27 5.57 5.45 5.36 5.36

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

95 TC 78.8 72.5 64.1 61.8 80.9 74.5 67.0 66.1 82.0 76.0 69.9 69.9 83.7 78.1 74.2 74.1 SHC 38.4 48.6 57.4 60.6 40.8 52.6 63.2 64.8 42.8 56.4 68.3 68.5 46.8 63.7 72.7 72.7 kW 6.03 5.91 5.79 5.73 6.09 5.96 5.84 5.82 6.11 6.00 5.89 5.89 6.16 6.05 5.96 5.96

(Btuh) 1.10 x cfm

tldb = tedb –

105 TC 76.2 69.5 58.6 57.8 77.9 71.3 63.4 63.1 79.3 72.7 67.2 67.2 81.1 74.5 71.3 71.2 SHC 37.6 47.4 55.0 56.6 39.9 51.4 61.4 61.9 42.2 55.3 65.9 65.9 46.5 62.5 69.9 69.9 kW 6.69 6.56 6.40 6.38 6.73 6.61 6.45 6.44 6.77 6.64 6.51 6.51 6.82 6.67 6.57 6.57

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

115 TC 72.5 65.1 54.8 54.7 74.3 67.8 58.6 58.6 75.6 69.1 63.2 63.2 77.3 70.9 68.4 68.4 SHC 36.3 45.8 53.2 53.6 38.7 50.2 57.4 57.5 41.1 54.0 62.0 62.0 45.5 61.3 67.1 67.1 kW 7.37 7.24 7.08 7.07 7.43 7.30 7.16 7.16 7.48 7.34 7.21 7.21 7.52 7.38 7.32 7.32

hlwb = hewb –

(Btuh) 4.5 x cfm

50TFQ004-012 549B036-120

549B090 (71/2 Tons)

Where: hewb = Enthalpy of air entering evaporator coil 3. The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

Indoor Entering Air — Cfm/Bf 2250/0.12 3000/0.15 3750/0.18 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 97.6 92.5 84.3 100.8 95.6 89.9 101.6 97.8 91.7 SHC 47.7 61.0 72.7 51.5 67.3 83.8 55.0 74.4 89.7 kW 5.80 5.76 5.73 5.86 5.78 5.78 5.86 5.82 5.73

ENTERING AIR DRY-BULB TEMP (F)

85 TC 97.2 89.9 79.8 100.0 94.1 86.7 102.4 96.0 89.9 SHC 48.1 60.2 70.5 51.7 68.1 82.4 55.8 74.1 89.3 kW 6.61 6.50 6.43 6.65 6.56 6.62 6.69 6.58 6.50

BYPASS FACTOR

79 78 77 76 75 under

(BF)

81 82 83 84 85 over

95 TC 94.4 86.9 75.0 98.2 91.3 81.8 99.6 93.7 87.3 SHC 47.3 59.2 68.1 51.7 67.5 79.8 55.0 74.8 87.3 kW 7.43 7.37 7.19 7.50 7.41 7.30 7.50 7.43 7.35

85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18 Use formula

105 TC 91.7 82.2 70.7 94.8 87.3 76.6 97.0 90.1 83.4 SHC 46.3 57.4 65.9 50.9 66.3 76.4 54.8 74.1 83.4 kW 8.37 8.22 8.04 8.39 8.33 8.15 8.44 8.35 8.26

.10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

shown below.

115 TC 87.7 77.4 66.9 91.7 81.6 72.5 93.9 85.3 78.8 SHC 44.9 55.4 64.0 50.3 64.2 72.5 55.0 72.5 78.6 kW 9.33 9.16 8.98 9.44 9.27 9.11 9.48 9.33 9.22

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

125 TC 83.6 73.3 66.7 87.1 76.0 69.1 89.5 79.0 74.4 SHC 43.6 53.9 63.8 48.7 62.0 69.1 53.7 70.1 74.4 kW 10.38 10.16 9.94 10.49 10.27 10.14 10.53 10.36 10.25

Indoor Entering Air — Cfm/Bf 3000/0.03 4000/0.04 5000/0.06 Indoor Entering Air — Ewb (F) 72 67 62 72 67 62 72 67 62

75 TC 136.0 124.0 111.4 141.2 129.0 116.6 145.6 132.0 121.2 SHC 64.6 80.8 96.0 71.2 92.4 111.8 78.6 103.2 121.0 kW 7.51 7.35 7.20 7.61 7.45 7.29 7.72 7.53 7.39

85 TC 132.6 119.6 106.6 137.6 124.4 112.0 140.4 127.4 118.0 SHC 63.6 79.2 94.0 70.6 91.4 110.0 77.0 102.6 118.0 kW 8.40 8.23 8.09 8.50 8.33 8.17 8.58 8.40 8.27

95 TC 127.8 114.6 99.4 133.2 119.4 107.2 136.2 121.8 114.2 SHC 62.2 77.6 90.8 69.6 89.8 107.0 76.8 101.2 113.8 kW 9.36 9.18 9.01 9.48 9.30 9.15 9.56 9.36 9.24

105 TC 122.4 108.8 92.0 127.4 113.6 101.4 130.4 116.0 109.6 SHC 60.4 75.4 87.4 68.0 88.0 101.4 75.4 99.4 109.4 kW 10.41 10.26 10.02 10.53 10.35 10.22 10.63 10.43 10.35

115 TC 116.8 101.8 86.6 121.2 106.6 94.8 123.6 109.2 104.6 SHC 58.6 72.8 84.6 66.0 85.4 94.8 73.4 97.0 104.6 kW 11.58 11.37 11.15 11.68 11.51 11.35 11.76 11.60 11.51

125 TC 110.6 95.8 84.6 114.6 98.4 88.8 117.0 100.8 96.4 SHC 56.4 70.6 83.4 64.4 82.4 88.8 71.4 93.8 96.4 kW 12.87 12.62 12.36 12.97 12.73 12.60 13.03 12.83 12.77

Show 14 more labels / short text on this page
Standard Ratings · 549B072 (6 Tons) · Temp (F) · Outdoor Entering Air · (Edb) · sensible capacity · total capacity · Temp (F) · Outdoor Entering Air · (Edb) · 549B120 (10 Tons) · Temp (F) · Outdoor Entering Air · (Edb)
Page 77 of the Bryant 549B user manual — LEGEND NOTES:
Page 77 · click to enlarge
Page 77

INSTANTANEOUS AND INTEGRATED HEATING RATINGS

549B036 (3 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

900 Cap. 10.9 10.0 13.7 12.6 16.6 15.3 19.7 18.1 22.1 20.1 26.8 23.5 30.9 30.9 34.0 34.0 35.3 35.3 40.7 40.7 kW 1.97 2.06 2.14 2.22 2.30 2.42 2.54 2.64 2.69 2.87

1200 Cap. 11.4 10.4 14.2 13.0 17.1 15.7 20.1 18.4 22.5 20.5 27.3 24.0 31.5 31.5 34.7 34.7 36.1 36.1 41.7 41.7 kW 2.02 2.09 2.15 2.22 2.27 2.37 2.46 2.53 2.56 2.71

1500 Cap. 11.7 10.8 14.6 13.4 17.4 16.0 20.5 18.8 22.9 20.9 27.8 24.4 32.0 32.0 35.2 35.2 36.7 36.7 42.5 42.5 kW 2.08 2.14 2.19 2.26 2.29 2.37 2.44 2.50 2.53 2.66

900 Cap. 9.5 8.8 12.6 11.6 15.6 14.5 19.0 17.4 21.4 19.5 26.2 23.0 30.1 30.1 33.1 33.1 34.5 34.5 39.5 39.5 kW 2.18 2.31 2.42 2.54 2.63 2.80 2.95 3.06 3.11 3.33

1200 Cap. 10.0 9.2 13.1 12.1 16.2 14.9 19.5 17.9 21.9 20.0 26.7 23.4 30.7 30.7 33.8 33.8 35.1 35.1 40.5 40.5 kW 2.24 2.34 2.44 2.52 2.60 2.73 2.83 2.93 2.97 3.12

1500 Cap. 10.4 9.6 13.5 12.4 16.6 15.3 19.9 18.2 22.3 20.4 27.1 23.8 31.2 31.2 34.3 34.3 35.7 35.7 41.2 41.2 kW 2.30 2.39 2.47 2.55 2.61 2.72 2.80 2.87 2.91 3.05

50TFQ004-012 549B036-120

900 Cap. 8.4 7.7 11.6 10.7 14.9 13.7 18.3 16.8 20.8 18.9 25.7 22.6 29.6 29.6 32.5 32.5 33.8 33.8 38.7 38.7 kW 2.32 2.47 2.62 2.76 2.87 3.08 3.22 3.37 3.43 3.67

1200 Cap. 8.9 8.2 12.2 11.2 15.4 14.3 18.9 17.3 21.4 19.5 26.2 23.0 30.2 30.2 33.2 33.2 34.6 34.6 39.7 39.7 kW 2.38 2.50 2.63 2.75 2.83 2.99 3.12 3.21 3.25 3.44

1500 Cap. 9.3 8.5 12.6 11.6 15.9 14.7 19.3 17.7 21.8 19.9 26.7 23.4 30.6 30.6 33.7 33.7 35.0 35.0 40.4 40.4 kW 2.44 2.55 2.67 2.77 2.83 2.97 3.07 3.15 3.19 3.34

549B048 (4 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

1200 Cap. 14.9 13.8 18.7 17.2 22.8 20.9 27.0 24.8 30.3 27.6 36.8 32.3 42.2 42.2 46.3 46.3 48.3 48.3 55.5 55.5 kW 2.61 2.73 2.86 3.00 3.10 3.31 3.50 3.65 3.73 4.02

1600 Cap. 15.5 14.4 19.4 17.8 23.4 21.5 27.7 25.4 30.9 28.2 37.5 32.9 43.1 43.1 47.4 47.4 49.5 49.5 57.0 57.0 kW 2.67 2.77 2.87 2.98 3.05 3.21 3.35 3.46 3.52 3.75

2000 Cap. 16.1 14.9 19.9 18.3 23.9 22.0 28.2 25.8 31.5 28.7 38.1 33.5 43.8 43.8 48.2 48.2 50.3 50.3 58.0 58.0 kW 2.75 2.83 2.92 3.00 3.07 3.19 3.31 3.40 3.45 3.65

1200 Cap. 13.1 12.1 17.1 15.7 21.4 19.7 25.8 23.7 29.2 26.6 35.9 31.5 41.2 41.2 45.1 45.1 47.0 47.0 53.9 53.9 kW 2.92 3.10 3.28 3.46 3.60 3.88 4.10 4.28 4.37 4.71

1600 Cap. 13.8 12.7 17.9 16.4 22.2 20.4 26.6 24.5 30.0 27.3 36.6 32.2 42.0 42.0 46.1 46.1 48.1 48.1 55.2 55.2 kW 2.98 3.14 3.28 3.42 3.53 3.74 3.91 4.04 4.11 4.37

2000 Cap. 14.4 13.2 18.5 17.0 22.8 20.9 27.2 24.9 30.7 27.9 37.2 32.7 42.7 42.7 46.8 46.8 48.9 48.9 56.2 56.2 kW 3.06 3.20 3.32 3.44 3.54 3.70 3.84 3.95 4.01 4.22

1200 Cap. 11.5 10.6 15.8 14.6 20.3 18.6 24.8 22.9 28.3 25.8 35.1 30.8 40.4 40.4 44.5 44.5 46.2 46.2 52.9 52.9 kW 3.13 3.35 3.56 3.78 3.94 4.28 4.55 4.75 4.85 5.22

1600 Cap. 12.3 11.3 16.5 15.2 21.1 19.4 25.6 23.6 29.1 26.5 36.0 31.6 41.3 41.3 45.4 45.4 47.2 47.2 54.2 54.2 kW 3.19 3.39 3.57 3.74 3.87 4.13 4.33 4.48 4.56 4.84

2000 Cap. 12.8 11.8 17.2 15.8 21.7 19.9 26.3 24.2 29.8 27.1 36.6 32.1 42.0 42.0 46.0 46.0 48.0 48.0 55.1 55.1 kW 3.28 3.45 3.61 3.76 3.87 4.08 4.24 4.37 4.43 4.66

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input) rh — Relative Humidity

Show 6 more labels / short text on this page
Cfm (Standard · Air (F db) · Air) · Cfm (Standard · Air (F db) · Air)
Page 78 of the Bryant 549B user manual — LEGEND NOTES:
Page 78 · click to enlarge
Page 78

INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)

549B060 (5 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

1500 Cap. 19.4 17.8 24.8 22.8 29.7 27.3 34.7 31.8 38.5 35.1 46.8 41.0 53.9 53.9 59.5 59.5 62.1 62.1 71.9 71.9 kW 3.28 3.53 3.67 3.77 3.85 4.04 4.21 4.36 4.43 4.73

2000 Cap. 20.7 19.0 25.9 23.8 30.6 28.1 35.6 32.6 39.5 36.0 48.0 42.1 55.4 55.4 61.1 61.1 63.8 63.8 73.3 73.3 kW 3.48 3.68 3.77 3.84 3.90 4.04 4.18 4.30 4.37 4.60

2500 Cap. 21.7 20.0 26.8 24.7 31.4 28.9 36.4 33.4 40.4 36.8 49.0 42.9 56.5 56.5 62.2 62.2 65.0 65.0 72.1 72.1 kW 3.69 3.85 3.92 3.98 4.03 4.15 4.28 4.40 4.46 4.61

1500 Cap. 14.5 13.3 21.8 20.0 28.2 26.0 34.0 31.2 37.8 34.5 45.7 40.1 52.4 52.4 57.7 57.7 60.2 60.2 69.5 69.5 kW 3.20 3.71 4.07 4.30 4.42 4.64 4.83 5.00 5.08 5.40

2000 Cap. 15.9 14.7 23.3 21.4 29.5 27.1 34.9 32.1 38.7 35.3 46.8 41.0 53.7 53.7 59.3 59.3 61.8 61.8 71.5 71.5 kW 3.44 3.91 4.20 4.36 4.43 4.59 4.74 4.87 4.94 5.21

2500 Cap. 17.2 15.8 24.5 22.5 30.5 28.1 35.8 32.9 39.6 36.1 47.8 41.9 54.8 54.8 60.4 60.4 63.1 63.1 72.4 72.4 kW 3.67 4.11 4.35 4.47 4.53 4.66 4.79 4.91 4.97 5.21

50TFQ004-012 549B036-120

1500 Cap. 9.9 9.1 18.3 16.8 25.9 23.8 32.8 30.1 37.0 33.8 45.1 39.5 51.6 51.6 56.7 56.7 59.1 59.1 68.1 68.1 kW 3.04 3.66 4.20 4.60 4.80 5.10 5.32 5.49 5.58 5.92

2000 Cap. 11.2 10.3 20.0 18.4 27.5 25.3 34.2 31.4 38.2 34.8 46.1 40.4 52.8 52.8 58.1 58.1 60.6 60.6 70.0 70.0 kW 3.27 3.89 4.38 4.69 4.83 5.02 5.18 5.32 5.38 5.66

2500 Cap. 12.4 11.4 21.3 19.6 28.8 26.5 35.1 32.3 39.1 35.6 47.1 41.2 53.9 53.9 59.3 59.3 61.8 61.8 71.4 71.4 kW 3.50 4.12 4.56 4.81 4.92 5.07 5.20 5.32 5.38 5.65

549B072 (6 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

1800 Cap. 16.5 15.2 20.8 19.1 26.4 22.4 33.6 30.8 41.0 37.6 51.3 44.9 61.9 61.9 69.5 69.5 78.0 78.0 77.9 77.9 kW 3.50 3.63 3.79 4.01 4.18 4.57 4.94 5.22 5.57 5.55

2100 Cap. 16.9 15.5 21.2 19.5 27.2 23.1 34.9 32.0 41.8 38.3 52.2 45.8 63.2 63.2 69.6 69.6 75.7 75.7 76.5 76.5 kW 3.56 3.68 3.84 4.04 4.18 4.54 4.86 5.07 5.30 5.32

2400 Cap. 17.2 15.9 21.8 20.0 28.0 23.8 35.6 32.6 43.1 39.5 53.8 47.2 64.1 64.1 69.0 69.0 74.8 74.8 74.3 74.3 kW 3.64 3.75 3.89 4.08 4.21 4.54 4.82 4.97 5.18 5.15

3000 Cap. 18 16.5 23.0 21.1 29.4 25.0 37.4 34.4 45.2 41.4 56.6 49.6 63.2 63.2 65.5 65.5 69.8 69.8 70.6 70.6 kW 3.79 3.90 4.03 4.19 4.32 4.61 4.77 4.84 4.98 4.99

1800 Cap. 15.2 14.0 18.2 16.7 24.1 20.5 31.1 28.5 38.0 34.8 47.7 41.8 58.4 58.4 67.1 67.1 78.0 78.0 77.9 77.9 kW 3.97 4.12 4.33 4.57 4.75 5.19 5.59 5.94 6.43 6.41

2100 Cap. 15.6 14.4 18.6 17.1 24.8 21.1 32.0 29.4 39.1 35.9 49.1 43.1 59.7 59.7 68.5 68.5 77.3 77.3 76.7 76.7 kW 4.04 4.18 4.37 4.59 4.76 5.15 5.51 5.81 6.17 6.13

2400 Cap. 16.1 14.8 19.0 17.5 25.9 22.0 32.7 30.0 39.9 36.6 51.1 44.7 61.3 61.3 69.0 69.0 75.6 75.6 76.3 76.3 kW 4.11 4.24 4.43 4.63 4.79 5.17 5.48 5.73 5.97 5.99

3000 Cap. 16.8 15.5 19.7 18.1 26.7 22.7 34.3 31.5 41.8 38.3 53.5 46.8 63.7 63.7 68.3 68.3 73.0 73.0 73.8 73.8 kW 4.28 4.39 4.56 4.75 4.89 5.22 5.49 5.63 5.80 5.82

1800 Cap. 13.6 12.5 17.1 15.7 21.7 18.4 29.2 26.8 36.5 33.4 45.6 40.0 55.3 55.3 64.2 64.2 77.2 77.2 76.9 76.9 kW 4.20 4.46 4.67 4.95 5.16 5.62 6.02 6.40 7.00 6.98

2100 Cap. 14.1 13.0 17.6 16.2 22.6 19.2 30.1 27.6 37.1 34.0 46.9 41.1 57.0 57.0 66.4 66.4 76.3 76.3 77.2 77.2 kW 4.28 4.52 4.72 4.98 5.16 5.58 5.95 6.30 6.71 6.74

2400 Cap. 14.5 13.4 18.0 16.6 23.1 19.6 31.2 28.7 37.9 32.7 48.5 42.5 58.7 58.7 67.7 67.7 76.3 76.3 75.9 75.9 kW 4.37 4.59 4.77 5.03 34.7 5.59 5.93 6.23 6.57 6.54

3000 Cap. 15.4 14.1 18.8 17.3 24.1 20.5 32.2 29.6 39.6 36.3 50.4 44.2 61.6 61.6 68.9 68.9 74.3 74.3 74.5 74.5 kW 4.54 4.74 4.91 5.14 5.29 5.64 5.95 6.17 6.37 6.36

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input) rh — Relative Humidity

Show 6 more labels / short text on this page
Cfm (Standard · Air (F db) · Air) · Cfm (Standard · Air (F db) · Air)
Page 79 of the Bryant 549B user manual — LEGEND NOTES:
Page 79 · click to enlarge
Page 79

INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)

549B090 (71/2 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

2250 Cap. 31.4 28.8 37.8 34.9 44.5 41.0 52.1 47.8 57.6 52.5 70.2 61.5 79.9 79.9 87.9 87.9 91.6 91.6 105.9 105.9 kW 5.32 5.47 5.61 5.74 5.84 6.09 6.72 6.92 7.02 7.48

3000 Cap. 33.3 30.6 39.6 36.5 46.3 42.5 53.9 49.4 59.6 54.3 72.1 63.1 81.9 81.9 90.0 90.0 93.9 93.9 105.1 105.1 kW 5.76 5.90 6.01 6.13 6.23 6.44 7.05 7.25 7.35 7.64

3750 Cap. 35.1 32.1 41.4 38.2 48.0 44.1 55.7 51.0 61.3 56.1 73.9 64.7 83.6 83.6 91.8 91.8 94.7 94.7 103.4 103.4 kW 6.23 6.34 6.44 6.56 6.63 6.85 7.48 7.68 7.75 7.93

2250 Cap. 28.8 26.5 35.9 32.9 43.1 39.8 50.8 46.6 56.4 51.4 68.4 60.0 77.8 77.8 85.6 85.6 89.2 89.2 103.2 103.2 kW 5.76 5.99 6.21 6.40 6.54 6.85 7.54 7.77 7.89 8.36

3000 Cap. 30.6 28.2 37.8 34.7 45.1 41.6 52.5 48.2 58.2 53.1 70.2 61.5 79.7 79.7 87.5 87.5 91.4 91.4 105.3 105.3 kW 6.19 6.40 6.60 6.77 6.89 7.14 7.83 8.03 8.16 8.61

3750 Cap. 32.3 29.8 39.4 36.3 46.8 43.8 54.3 49.8 60.0 54.7 72.1 63.3 81.7 81.7 89.6 89.6 93.3 93.3 105.5 105.5 kW 6.63 6.85 7.00 7.18 7.28 7.53 8.22 8.43 8.53 8.88

50TFQ004-012 549B036-120

2250 Cap. 26.3 24.1 33.9 31.2 41.7 38.4 49.6 45.7 55.5 50.6 67.2 58.8 76.4 76.4 84.0 84.0 87.7 87.7 101.1 101.1 kW 6.01 6.34 6.62 6.87 7.06 7.39 8.18 8.43 8.55 9.06

3000 Cap. 28.0 25.9 35.9 33.1 43.7 40.2 51.3 47.2 57.2 52.3 69.0 60.6 78.4 78.4 86.1 86.1 89.8 89.8 103.4 103.4 kW 6.44 6.75 7.00 7.22 7.37 7.68 8.43 8.65 8.78 9.25

3750 Cap. 29.8 27.4 37.8 34.7 45.5 41.9 53.3 48.8 59.0 53.9 71.0 62.1 80.1 80.1 88.1 88.1 91.8 91.8 105.3 105.3 kW 6.89 7.18 7.41 7.60 7.76 8.03 8.80 9.00 9.13 9.58

549B120 (10 Tons) Return

Temperature Air Entering Outdoor Coil (F db at 70% rh)

–20 –10 0 10 17 30 40 47 50 60

3000 Cap. 37.7 34.6 45.5 41.9 53.5 49.2 62.6 57.5 69.2 63.1 84.3 74.0 101.3 101.3 111.3 111.3 116.0 116.0 134.2 134.2 kW 6.87 7.07 7.25 7.43 7.55 7.88 8.26 8.52 8.64 9.20

4000 Cap. 40.0 36.7 47.6 43.8 55.6 51.1 64.8 59.4 71.6 65.2 86.7 75.8 103.7 103.7 114.0 114.0 118.9 118.9 133.2 133.2 kW 7.45 7.63 7.78 7.93 8.05 8.33 8.67 8.92 9.05 9.40

5000 Cap. 42.2 38.6 49.7 45.9 57.7 53.0 66.9 61.2 73.7 67.4 88.8 77.7 105.9 105.9 116.2 116.2 119.9 119.9 131.0 131.0 kW 8.05 8.20 8.33 8.48 8.58 8.86 9.20 9.45 9.53 9.76

3000 Cap. 34.6 31.8 43.1 39.6 51.8 47.8 61.0 56.1 67.8 61.7 82.2 72.1 98.5 98.5 108.4 108.4 113.0 113.0 130.7 130.7 kW 7.45 7.75 8.03 8.28 8.45 8.86 9.28 9.55 9.71 10.29

4000 Cap. 36.7 33.9 45.5 41.7 54.2 49.9 63.1 57.9 69.9 63.8 84.3 74.0 101.0 101.0 110.8 110.8 115.8 115.8 133.4 133.4 kW 8.00 8.28 8.53 8.76 8.91 9.23 9.63 9.88 10.04 10.59

5000 Cap. 38.9 35.8 47.3 43.6 56.3 51.8 65.2 59.8 72.1 65.7 86.7 76.1 103.5 103.5 113.5 113.5 118.2 118.2 133.7 133.7 kW 8.58 8.86 9.06 9.28 9.41 9.73 10.11 10.37 10.49 10.92

3000 Cap. 31.6 29.0 40.7 37.4 50.2 46.2 59.6 54.9 66.7 60.8 80.8 70.7 96.8 96.8 06.4 106.4 111.1 111.1 128.0 128.0 kW 7.78 8.20 8.56 8.88 9.13 9.56 10.06 10.37 10.52 11.15

4000 Cap. 33.7 31.1 43.1 39.8 52.5 48.3 61.9 56.8 68.8 62.9 82.9 72.8 99.3 99.3 109.1 109.1 113.8 113.8 131.0 131.0 kW 8.33 8.73 9.06 9.33 9.53 9.93 10.37 10.64 10.80 11.38

5000 Cap. 35.8 33.0 45.5 41.7 54.6 50.4 64.1 58.6 70.9 64.8 85.3 74.7 101.5 101.5 111.6 111.6 116.2 116.2 133.4 133.4 kW 8.91 9.28 9.58 9.83 10.04 10.39 10.82 11.08 11.23 11.78

LEGEND NOTES:

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat) kW — Total Power Input (includes compressor motor power input,

1. indicates integrated ratings. 2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

outdoor-fan motor input, and indoor-fan motor input) rh — Relative Humidity

Show 6 more labels / short text on this page
Cfm (Standard · Air (F db) · Air) · Cfm (Standard · Air (F db) · Air)
Page 80 of the Bryant 549B user manual — 549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)
Page 80 · click to enlarge
Page 80

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS

Bryant 549B — FAN PERFORMANCE — VERTICAL DISCHARGE UNITS diagram (page 80)
Fig. 17

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 581 0.12 673 0.18 736 0.22 805 0.25 865 0.29 911 0.34 1000 644 0.19 709 0.22 782 0.28 835 0.30 900 0.35 937 0.38 1100 687 0.22 746 0.26 806 0.30 867 0.35 929 0.40 964 0.40 1200 733 0.26 785 0.32 843 0.35 903 0.41 960 0.47 994 0.50 1300 754 0.29 826 0.38 891 0.43 942 0.48 991 0.53 1047 0.60 1400 810 0.35 868 0.45 937 0.51 984 0.57 1032 0.62 1067 0.67 1500 841 0.42 911 0.53 985 0.61 1029 0.66 1073 0.72 1109 0.77

549B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 0.7 0.8 0.9 1.0 1.1 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 957 0.39 988 0.43 1039 0.45 1061 0.47 1083 0.53 1105 0.57 1000 992 0.44 1039 0.49 1061 0.51 1086 0.55 1111 0.59 1136 0.63 1100 1013 0.49 1068 0.55 1090 0.58 1109 0.61 1127 0.64 1145 0.67 1200 1045 0.56 1090 0.64 1109 0.64 1156 0.68 1203 0.71 1250 0.74 1300 1075 0.64 1122 0.70 1152 0.72 1190 0.76 1228 0.80 1266 0.84 1400 1110 0.73 1160 0.84 1181 0.81 1237 0.85 1293 0.89 1349 0.93 1500 1150 0.82 1190 1.00 1225 0.90 1271 0.95 1317 1.00 1363 1.05

50TFQ004-012 549B036-120

2. Maximum continuous bhp is 1.20.

Bhp — Brake Horsepower Input to Fan

3. Motor drive range: 760 to 1090 rpm. All other rpms require fieldsupplied drive.

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 3.)

549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.6 0.7 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 542 0.16 616 0.21 678 0.27 739 0.32 842 0.44 886 0.50 929 0.56 1300 576 0.20 644 0.25 704 0.31 764 0.37 867 0.50 910 0.56 952 0.62 1400 610 0.24 673 0.30 732 0.36 791 0.42 889 0.55 933 0.62 976 0.69 1500 646 0.28 704 0.35 761 0.42 818 0.48 912 0.61 957 0.69 1001 0.76 1600 681 0.33 735 0.40 790 0.47 845 0.54 920 0.68 931 0.76 1023 0.83 1700 718 0.39 768 0.46 836 0.54 873 0.61 965 0.76 1005 0.84 1045 0.91 1800 754 0.45 801 0.53 851 0.61 900 0.69 992 0.84 1032 0.92 1071 1.00 1900 791 0.52 836 0.60 832 0.69 828 0.77 1019 0.93 1058 1.02 1097 1.10 2000 828 0.60 870 0.68 864 0.77 858 0.86 1046 1.03 1085 1.12 1124 1.21

549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.1 1.2 1.4 1.6 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 1008 0.67 1052 0.73 1096 0.78 1134 0.89 1203 1.00 — — 1300 1029 0.75 1065 0.81 1101 0.86 1174 1.01 1229 1.15 1277 1.27 1400 1052 0.83 1087 0.90 1121 0.96 1183 1.09 1255 1.22 1305 1.38 1500 1076 0.91 1111 0.99 1145 1.06 1208 1.20 1274 1.33 1337 1.47 1600 1100 1.00 1134 1.08 1168 1.15 1232 1.31 1291 1.46 1350 1.60 1700 1124 1.09 1158 1.17 1192 1.25 1255 1.42 1314 1.58 1370 1.77 1800 1147 1.18 1182 1.27 1217 1.36 1279 1.54 1381 1.71 1393 1.89 1900 1169 1.27 1205 1.37 1240 1.47 1303 1.66 1408 1.85 1417 2.03 2000 1194 1.38 1228 1.48 1262 1.58 1327 1.78 1436 1.98 1440 2.18

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 1.20.

Refer to page 87 for general Fan Performance notes. NOTES:

4. Motor drive range: 840 to 1185 rpm. All other rpms require fieldsupplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 6 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 81 of the Bryant 549B user manual — 549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)
Page 81 · click to enlarge
Page 81

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

549B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 711 0.33 769 0.39 878 0.51 971 0.64 1052 0.78 1600 751 0.39 806 0.45 906 0.53 1024 0.73 1087 0.88 1700 791 0.46 846 0.53 941 0.66 1030 0.80 1112 0.96 1800 852 0.55 905 0.62 1002 0.78 1084 0.93 1163 1.10 1900 894 0.64 945 0.72 1037 0.88 1119 1.04 1194 1.21 2000 936 0.74 984 0.82 1072 0.98 1154 1.16 1226 1.33 2100 978 0.85 1024 0.93 1108 1.10 1190 1.29 1259 1.47 2200 1021 0.97 1064 1.05 1145 1.22 1225 1.43 1294 1.62 2300 1064 1.10 1104 1.18 1183 1.36 1260 1.57 1330 1.78 2400 1107 1.24 1145 1.32 1222 1.52 1296 1.73 1365 1.94 2500 1150 1.39 1186 1.48 1262 1.68 1331 1.89 1400 2.12

549B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 1134 0.95 1213 1.11 1276 1.38 1331 1.49 1600 1159 1.02 1231 1.20 1311 1.39 1395 1.59 1700 1184 1.12 1258 1.30 1322 1.49 1403 1.69 1800 1235 1.29 1303 1.48 1371 1.69 1433 1.90 1900 1266 1.40 1330 1.59 1396 1.81 1460 2.03 2000 1297 1.53 1362 1.73 1422 1.94 1485 2.16 2100 1327 1.66 1393 1.87 1452 2.08 1510 2.31 2200 1359 1.81 1423 2.02 1483 2.24 1538 2.46 2300 1392 1.97 1454 2.18 1515 2.41 1569 2.64 2400 1426 2.15 1485 2.36 1544 2.59 1601 2.84 2500 1461 2.34 1518 2.55 1575 2.78 — —

50TFQ004-012 549B036-120

2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 1.80. 4. Standard motor drive range: 1020 to 1460 rpm. All other rpms require fieldsupplied drive.

Bhp — Brake Horsepower Input to Fan

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 4.)

549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1800 852 0.55 905 0.62 1002 0.78 1084 0.93 1163 1.10 1900 894 0.64 945 0.72 1037 0.88 1119 1.04 1194 1.21 2000 936 0.74 984 0.82 1072 0.98 1154 1.16 1226 1.33 2100 978 0.85 1024 0.93 1108 1.10 1190 1.29 1259 1.47 2200 1021 0.97 1064 1.05 1145 1.22 1225 1.43 1294 1.62 2300 1064 1.10 1104 1.18 1183 1.36 1260 1.57 1330 1.78 2400 1107 1.24 1145 1.32 1222 1.52 1296 1.73 1365 1.94 2500 1150 1.39 1186 1.48 1262 1.68 1331 1.89 1400 2.12 2600 1193 1.56 1228 1.65 1301 1.86 1367 2.07 1435 2.31 2700 1237 1.74 1269 1.83 1341 2.05 1404 2.26 1471 2.51 2800 1280 1.94 1311 2.03 1381 2.25 1442 2.47 1506 2.72 2900 1324 2.15 1354 2.24 1420 2.47 1481 2.69 1542 2.94 3000 1368 2.37 1396 2.46 1460 2.69 1521 2.93 — —

549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1800 1235 1.29 1303 1.48 1371 1.69 1433 1.90 1900 1266 1.40 1330 1.59 1396 1.81 1460 2.03 2000 1297 1.53 1362 1.73 1422 1.94 1485 2.16 2100 1327 1.66 1393 1.87 1452 2.08 1510 2.31 2200 1359 1.81 1423 2.02 1483 2.24 1538 2.46 2300 1392 1.97 1454 2.18 1515 2.41 1569 2.64 2400 1426 2.15 1485 2.36 1544 2.59 1601 2.84 2500 1461 2.34 1518 2.55 1575 2.78 — — 2600 1497 2.54 1552 2.76 — 2700 1532 2.75 — 2800 — 2900 — 3000 —

2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.40. 4. Standard motor drive range: 1120 to 1585 rpm. All other rpms require fieldsupplied drive.

Bhp — Brake Horsepower Input to Fan

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 82 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 82 · click to enlarge
Page 82

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 511 0.52 592 0.74 659 0.95 722 1.19 778 1.43 829 1.68 2300 518 0.55 599 0.77 665 0.98 727 1.22 783 1.47 834 1.72 2400 534 0.61 613 0.84 677 1.06 738 1.30 794 1.55 844 1.81 2500 549 0.67 627 0.90 690 1.14 750 1.38 805 1.64 855 1.91 2550 557 0.71 633 0.94 697 1.18 756 1.42 811 1.69 861 1.96 2600 565 0.74 639 0.97 703 1.22 761 1.46 816 1.74 866 2.01 2700 581 0.81 652 1.04 717 1.31 773 1.55 827 1.83 878 2.12 2800 597 0.89 665 1.12 733 1.40 786 1.66 839 1.93 889 2.23 2900 613 0.97 679 1.20 745 1.50 799 1.76 850 2.04 900 2.34 3000 629 1.06 694 1.29 759 1.59 812 1.88 862 2.15 911 2.46 3100 646 1.15 709 1.39 772 1.70 825 1.99 875 2.28 923 2.58 3200 662 1.25 724 1.50 785 1.80 840 2.11 887 2.41 934 2.71 3300 679 1.35 740 1.61 798 1.91 854 2.24 900 2.54 946 2.85 3400 696 1.46 756 1.73 811 2.02 868 2.37 914 2.69 959 3.00 3500 712 1.57 771 1.85 824 2.14 881 2.50 928 2.84 971 3.16 3600 729 1.69 787 1.98 839 2.21 894 2.64 942 2.99 984 3.22 3700 746 1.85 803 2.12 854 2.42 907 2.78 956 3.15 997 3.49 3750 755 1.89 811 2.20 862 2.49 914 2.85 963 3.23 — —

50TFQ004-012 549B036-120

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 884 1.97 937 2.33 947 2.66 1022 3.10 2300 885 2.00 939 2.36 979 2.69 1025 3.12 2400 892 2.08 944 2.40 987 2.76 1039 3.20 2500 902 2.18 949 2.48 1002 2.84 1041 3.25 2550 908 2.24 953 2.53 1003 2.87 1045 3.28 2600 913 2.29 957 2.58 1004 2.91 1050 3.31 2700 924 2.40 967 2.70 1010 3.01 1056 3.37 2800 935 2.52 978 2.62 1019 3.13 1061 3.47 2900 946 2.65 989 2.96 1030 3.27 — — 3000 957 2.78 1000 3.09 1040 3.41 — — 3100 968 2.91 1011 3.24 — 3200 980 3.04 1022 3.38 — 3300 991 3.18 — 3400 1003 3.32 — 3500 1014 3.48 — 3600 — 3700 — 3750 —

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 2.90.

Refer to page 87 for general Fan Performance notes. NOTES:

4. Standard motor drive range: 725 to 925 rpm. All other rpms require field-supplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 83 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 83 · click to enlarge
Page 83

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

549B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3000 459 0.46 625 0.85 691 1.01 734 1.10 787 1.30 829 1.50 3100 478 0.57 637 0.90 702 1.08 744 1.16 796 1.36 837 1.56 3200 500 0.62 647 0.97 712 1.16 753 1.23 805 1.43 845 1.63 3300 519 0.69 658 1.03 721 1.23 762 1.30 814 1.50 853 1.71 3400 537 0.77 669 1.10 731 1.30 773 1.38 823 1.57 862 1.78 3500 561 0.86 680 1.17 741 1.37 784 1.47 832 1.65 871 1.86 3600 592 0.98 692 1.24 751 1.45 796 1.57 841 1.72 880 1.95 3700 654 1.12 714 1.31 767 1.50 815 1.67 861 1.85 906 2.08 3800 668 1.20 727 1.40 780 1.60 827 1.77 873 1.95 916 2.18 3900 683 1.28 741 1.49 793 1.70 839 1.88 884 2.05 927 2.28 4000 697 1.37 754 1.59 806 1.80 851 1.99 895 2.16 938 2.38 4100 711 1.46 767 1.69 819 1.90 864 2.10 907 2.28 949 2.49 4200 726 1.56 780 1.80 832 2.01 877 2.22 919 2.41 960 2.60 4300 741 1.66 794 1.91 845 2.12 889 2.35 931 2.54 971 2.72 4400 755 1.77 808 2.03 858 2.24 902 2.48 943 2.68 983 2.86 4500 770 1.89 821 2.15 871 2.37 915 2.61 955 2.82 995 3.01 4600 784 2.00 835 2.27 884 2.49 928 2.75 968 2.96 1006 3.17 4700 799 2.13 849 2.40 897 2.63 941 2.88 981 3.11 1018 3.32 4800 814 2.25 863 2.53 910 2.77 954 3.02 993 3.27 1030 3.48 4900 829 2.39 877 2.67 923 2.92 967 3.17 1006 3.43 1043 3.65 5000 843 2.52 892 2.81 937 3.08 980 3.32 1019 3.60 1055 3.82

50TFQ004-012 549B036-120

549B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.4 1.6 1.8 2.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3000 886 1.73 943 1.88 988 1.91 995 1.95 3100 892 1.78 947 2.00 995 2.05 1008 2.07 3200 899 1.85 951 2.06 1000 2.17 1021 2.20 3300 907 1.93 959 2.10 1004 2.33 1036 2.36 3400 915 2.01 966 2.17 1009 2.46 1043 2.47 3500 924 2.09 974 2.24 1015 2.51 1054 2.59 3600 933 2.18 983 2.32 1023 2.58 1058 2.70 3700 950 2.27 991 2.47 1030 2.65 1064 2.82 3800 959 2.38 1001 2.58 1040 2.78 1075 2.96 3900 969 2.50 1010 2.70 1049 2.91 1085 3.11 4000 979 2.62 1020 2.83 1059 3.04 1095 3.25 4100 989 2.74 1029 2.96 1068 3.18 1105 3.39 4200 1000 2.86 1039 3.10 1077 3.31 1114 3.54 4300 1011 2.97 1049 3.23 1087 3.46 1124 3.69 4400 1022 3.10 1059 3.37 1097 3.61 1133 3.84 4500 1033 3.23 1070 3.51 1107 3.76 1143 4.00 4600 1044 3.37 1081 3.64 1117 3.92 1152 4.17 4700 1056 3.52 1092 3.78 1127 4.07 1162 4.33 4800 1057 3.69 1103 3.93 1138 4.23 1172 4.50 4900 1079 3.87 1114 4.09 1149 4.37 1182 4.68 5000 1091 4.05 1126 4.25 1160 4.53 1193 4.85

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 4.20 with standard motor.

Refer to page 87 for general Fan Performance notes. NOTES:

4. Standard motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 84 of the Bryant 549B user manual — 549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)
Page 84 · click to enlarge
Page 84

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS

Bryant 549B — FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS diagram (page 84)
Fig. 18

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 526 0.06 584 0.08 656 0.12 734 0.22 818 0.25 875 0.27 1000 570 0.09 627 0.13 738 0.19 800 0.26 848 0.29 895 0.31 1100 614 0.13 670 0.16 758 0.23 812 0.29 863 0.32 914 0.35 1200 658 0.16 710 0.23 780 0.28 840 0.32 889 0.36 938 0.40 1300 703 0.20 752 0.27 808 0.32 868 0.37 916 0.41 963 0.45 1400 725 0.29 776 0.31 845 0.38 891 0.42 937 0.47 983 0.51 1500 755 0.33 816 0.38 870 0.43 924 0.48 969 0.53 1014 0.58

549B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 0.7 0.8 0.9 1.0 1.1 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 924 0.32 953 0.35 989 0.38 1028 0.42 1074 0.49 1120 0.54 1000 936 0.35 977 0.39 1020 0.44 1064 0.48 1124 0.54 1185 0.60 1100 960 0.39 1005 0.43 1052 0.49 1100 0.52 1163 0.59 1225 0.65 1200 960 0.45 1038 0.50 1076 0.53 1136 0.59 1201 0.65 1266 0.72 1300 1012 0.51 1061 0.56 1090 0.61 1172 0.65 1239 0.72 1306 0.79 1400 1027 0.56 1071 0.60 1108 0.67 1208 0.70 1278 0.79 1347 0.87 1500 1056 0.63 1097 0.68 1117 0.70 1245 0.74 1315 0.87 1385 0.96

50TFQ004-012 549B036-120

2. Maximum continuous bhp is 1.20.

Bhp — Brake Horsepower Input to Fan

3. Motor drive range: 760 to 1090 rpm. All other rpms require fieldsupplied drive.

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 3.)

549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.6 0.7 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 514 0.15 590 0.20 657 0.25 723 0.30 828 0.42 876 0.49 924 0.55 1300 545 0.18 615 0.23 680 0.29 744 0.35 849 0.47 895 0.54 940 0.60 1400 577 0.21 642 0.27 704 0.33 766 0.39 870 0.52 915 0.59 959 0.66 1500 609 0.26 670 0.31 729 0.38 788 0.44 892 0.58 936 0.65 980 0.72 1600 642 0.30 699 0.36 755 0.43 811 0.49 913 0.64 957 0.72 1001 0.79 1700 675 0.36 728 0.42 782 0.49 836 0.55 935 0.71 979 0.79 1023 0.86 1800 709 0.41 759 0.48 810 0.55 860 0.62 957 0.78 1001 0.86 1044 0.94 1900 743 0.48 790 0.55 838 0.62 886 0.69 980 0.86 1023 0.95 1066 1.03 2000 778 0.55 836 0.62 875 0.70 913 0.77 1004 0.94 1046 1.03 1088 1.12

549B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.1 1.2 1.4 1.6 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 999 0.66 1018 0.67 1036 0.68 1073 0.71 1109 0.75 1138 0.79 1300 1025 0.74 1058 0.79 1090 0.84 1121 0.87 1159 0.90 1193 0.95 1400 1042 0.81 1080 0.88 1118 0.95 1175 1.06 1206 1.09 1244 1.12 1500 1060 0.88 1098 0.96 1136 1.04 1205 1.19 1258 1.30 1289 1.34 1600 1080 0.95 1117 1.04 1153 1.12 1224 1.29 1287 1.45 1337 1.56 1700 1101 1.03 1137 1.12 1172 1.20 1241 1.38 1307 1.56 1366 1.73 1800 1122 1.11 1157 1.20 1192 1.29 1258 1.48 1323 1.67 1385 1.86 1900 1143 1.21 1179 1.30 1214 1.39 1279 1.58 1341 1.78 1402 1.98 2000 1165 1.31 1200 1.40 1235 1.49 1300 1.69 1361 1.90 1419 2.10

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 1.20.

Refer to page 87 for general Fan Performance notes. NOTES:

4. Motor drive range: 840 to 1185 rpm. All other rpms require fieldsupplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 6 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 85 of the Bryant 549B user manual — 549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)
Page 85 · click to enlarge
Page 85

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

549B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 665 0.31 729 0.35 843 0.47 940 0.60 1026 0.74 1600 703 0.36 763 0.40 872 0.53 965 0.66 1049 0.81 1700 741 0.40 801 0.47 902 0.60 993 0.75 1077 0.89 1800 765 0.45 821 0.51 923 0.65 1019 0.81 1099 0.96 1900 802 0.45 854 0.58 953 0.73 1046 0.90 1126 1.06 2000 840 0.60 888 0.66 984 0.82 1073 0.99 1154 1.16 2100 878 0.69 923 0.75 1015 0.91 1101 1.08 1182 1.27 2200 916 0.78 958 0.85 1046 1.01 1129 1.19 1209 1.39 2300 954 0.89 993 0.96 1079 1.13 1160 1.31 1237 1.51 2400 993 1.00 1029 1.07 1112 1.25 1190 1.43 1264 1.63 2500 1031 1.13 1066 1.20 1145 1.39 1220 1.57 1292 1.77

549B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 1108 0.89 1187 1.06 1202 1.18 1079 1.10 1600 1130 0.97 1206 1.14 1275 1.32 1281 1.44 1700 1152 1.05 1226 1.23 1298 1.41 1359 1.60 1800 1178 1.14 1249 1.32 1316 1.52 1382 1.72 1900 1201 1.23 1274 1.43 1338 1.62 1402 1.83 2000 1226 1.33 1297 1.53 1363 1.73 1424 1.94 2100 1252 1.45 1320 1.64 1388 1.85 1448 2.07 2200 1280 1.58 1345 1.77 1410 1.97 1473 2.20 2300 1309 1.71 1372 1.91 1434 2.11 1496 2.34 2400 1336 1.85 1400 2.06 1459 2.26 1519 2.48 2500 1363 2.00 1428 2.22 1486 2.43 1543 2.65

50TFQ004-012 549B036-120

2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 1.80. 4. Standard motor drive range: 1020 to 1460 rpm. All other rpms require fieldsupplied drive.

Bhp — Brake Horsepower Input to Fan

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 4.)

549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1800 765 0.45 821 0.51 923 0.65 1019 0.81 1099 0.96 1900 802 0.45 854 0.58 953 0.73 1046 0.90 1126 1.06 2000 840 0.60 888 0.66 984 0.82 1073 0.99 1154 1.16 2100 878 0.69 923 0.75 1015 0.91 1101 1.08 1182 1.27 2200 916 0.78 958 0.85 1046 1.01 1129 1.19 1209 1.39 2300 954 0.89 993 0.96 1079 1.13 1160 1.31 1237 1.51 2400 993 1.00 1029 1.07 1112 1.25 1190 1.43 1264 1.63 2500 1031 1.13 1066 1.20 1145 1.39 1220 1.57 1292 1.77 2600 1070 1.26 1103 1.34 1179 1.52 1251 1.71 1322 1.92 2700 1109 1.41 1140 1.48 1212 1.67 1283 1.87 1352 2.09 2800 1148 1.57 1177 1.64 1246 1.83 1316 2.04 1383 2.26 2900 1188 1.74 1215 1.81 1281 2.00 1349 2.22 1413 2.44 3000 1227 1.92 1253 2.00 1316 2.19 1382 2.42 1444 2.63

549B072 (6 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1800 1178 1.14 1249 1.32 1316 1.52 1382 1.72 1900 1201 1.23 1274 1.43 1338 1.62 1402 1.83 2000 1226 1.33 1297 1.53 1363 1.73 1424 1.94 2100 1252 1.45 1320 1.64 1388 1.85 1448 2.07 2200 1280 1.58 1345 1.77 1410 1.97 1473 2.20 2300 1309 1.71 1372 1.91 1434 2.11 1496 2.34 2400 1336 1.85 1400 2.06 1459 2.26 1519 2.48 2500 1363 2.00 1428 2.22 1486 2.43 1543 2.65 2600 1390 2.15 1456 2.38 1514 2.61 1569 2.83 2700 1418 2.31 1483 2.56 1543 2.80 — — 2800 1446 2.48 1510 2.73 — 2900 1476 2.67 1537 2.92 — 3000 1506 2.88 —

2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.40. 4. Standard motor drive range: 1120 to 1585 rpm. All other rpms require fieldsupplied drive.

Bhp — Brake Horsepower Input to Fan

Refer to page 87 for general Fan Performance notes. NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 8 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm) · Airflow · (Cfm)
Page 86 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 86 · click to enlarge
Page 86

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 465 0.43 554 0.64 630 0.86 695 1.09 757 1.34 2300 471 0.45 559 0.66 635 0.89 699 1.12 760 1.37 2400 482 0.50 569 0.71 645 0.95 708 1.18 768 1.44 2500 494 0.54 581 0.76 654 1.01 717 1.25 776 1.51 2550 501 0.57 587 0.79 659 1.05 722 1.29 780 1.55 2600 507 0.59 592 0.82 663 1.08 727 1.32 784 1.58 2700 520 0.65 604 0.89 672 1.14 737 1.40 793 1.66 2800 533 0.71 615 0.95 683 1.20 747 1.49 802 1.75 2900 546 0.77 626 1.02 693 1.27 756 1.57 813 1.84 3000 559 0.83 637 1.09 704 1.35 765 1.66 823 1.94 3100 572 0.90 648 1.17 715 1.43 775 1.74 832 2.05 3200 585 0.96 660 1.24 727 1.52 785 1.83 841 2.15 3300 598 1.03 671 1.32 739 1.62 795 1.91 851 2.26 3400 610 1.10 682 1.41 750 1.72 806 2.01 860 2.36 3500 623 1.17 694 1.50 761 1.82 817 2.11 870 2.47 3600 636 1.25 707 1.60 772 1.93 828 2.23 880 2.57 3700 649 1.33 720 1.71 783 2.03 840 2.35 890 2.69 3750 655 1.37 727 1.77 789 2.09 846 2.42 896 2.75

50TFQ004-012 549B036-120

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 810 1.62 850 1.91 873 2.20 890 2.50 903 2.78 2300 816 1.65 859 1.94 888 2.24 897 2.55 922 2.85 2400 824 1.72 872 2.01 909 2.32 931 2.64 935 2.96 2500 832 1.79 882 2.09 925 2.40 955 2.72 972 3.06 2550 836 1.83 887 2.13 931 2.45 964 2.77 986 3.11 2600 839 1.87 891 2.17 936 2.49 973 2.82 999 3.16 2700 846 1.95 898 2.26 946 2.58 987 2.91 1019 3.26 2800 855 2.04 906 2.35 954 2.67 997 3.01 1034 3.36 2900 863 2.13 913 2.44 961 2.77 1006 3.12 — — 3000 872 2.22 921 2.54 969 2.88 1014 3.22 — — 3100 882 2.33 930 2.65 976 2.99 1021 3.34 — — 3200 892 2.45 939 2.76 984 3.10 — 3300 902 2.57 948 2.88 993 3.21 — 3400 912 2.69 958 3.01 1002 3.34 — 3500 921 2.82 968 3.15 — 3600 930 2.95 978 3.29 — 3700 940 3.07 — 3750 945 3.14 —

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 2.90.

Refer to page 87 for general Fan Performance notes. NOTES:

4. Standard motor drive range: 725 to 925 rpm. All other rpms require field-supplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 87 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 87 · click to enlarge
Page 87

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

549B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3000 459 0.35 595 0.74 657 0.88 716 1.05 770 1.24 3100 478 0.46 605 0.79 667 0.94 725 1.10 779 1.30 3200 500 0.57 615 0.85 679 1.01 734 1.16 787 1.36 3300 519 0.62 625 0.90 691 1.08 744 1.23 796 1.43 3400 537 0.69 637 0.97 702 1.16 753 1.30 805 1.50 3500 561 0.77 647 1.03 712 1.23 762 1.38 814 1.57 3600 592 0.86 658 1.10 721 1.30 773 1.47 823 1.65 3700 607 0.97 670 1.18 732 1.37 782 1.56 833 1.73 3800 621 1.05 681 1.25 742 1.45 795 1.66 842 1.82 3900 636 1.13 693 1.32 751 1.53 808 1.76 851 1.92 4000 650 1.21 705 1.40 761 1.61 819 1.86 861 2.02 4100 665 1.30 717 1.48 772 1.71 830 1.96 871 2.13 4200 680 1.39 728 1.57 783 1.81 839 2.05 883 2.25 4300 696 1.49 739 1.66 794 1.91 848 2.14 896 2.38 4400 711 1.60 750 1.75 805 2.02 857 2.24 908 2.51 4500 727 1.70 762 1.85 817 2.12 867 2.35 919 2.63 4600 742 1.82 774 1.96 828 2.23 877 2.46 929 2.75 4700 758 1.94 786 2.07 840 2.34 888 2.59 938 2.87 4800 773 2.06 799 2.18 852 2.46 899 2.72 947 2.98 4900 789 2.19 812 2.30 863 2.57 910 2.86 957 3.11 5000 805 2.32 826 2.43 875 2.70 921 2.99 966 3.24

50TFQ004-012 549B036-120

549B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3000 822 1.44 872 1.69 919 1.88 950 1.70 962 1.82 3100 829 1.50 882 1.73 932 2.00 965 1.80 971 1.95 3200 837 1.56 886 1.78 943 2.06 978 1.91 984 2.07 3300 845 1.63 892 1.85 947 2.10 988 2.05 995 2.20 3400 853 1.71 899 1.93 951 2.17 995 2.17 1008 2.32 3500 862 1.78 907 2.01 959 2.24 1000 2.33 1021 2.47 3600 871 1.86 915 2.09 965 2.32 1005 2.46 1036 2.59 3700 879 1.95 927 2.17 973 2.38 1013 2.57 1046 2.73 3800 889 2.03 934 2.26 980 2.48 1022 2.69 1058 2.87 3900 898 2.12 942 2.36 987 2.59 1030 2.81 1068 3.01 4000 908 2.21 950 2.46 994 2.70 1037 2.92 1077 3.14 4100 917 2.32 960 2.55 1001 2.81 1045 3.04 1085 3.21 4200 925 2.44 969 2.65 1009 2.92 1051 3.17 1092 3.40 4300 935 2.56 979 2.77 1018 3.03 1058 3.29 1100 3.53 4400 945 2.68 988 2.89 1028 3.14 1066 3.41 1106 3.67 4500 955 2.82 996 3.02 1037 3.25 1074 3.54 1113 3.81 4600 967 2.96 1005 3.16 1046 3.38 1084 3.66 1121 3.95 4700 980 3.11 1015 3.30 1056 3.52 1093 3.79 1129 4.09 4800 992 3.26 1025 3.45 1064 3.67 1103 3.92 1137 4.22 4900 1003 3.41 1036 3.61 1073 3.83 1112 4.07 1147 4.36 5000 1014 3.56 1049 3.79 1083 4.00 1121 4.23 1157 4.50

2. indicates field-supplied motor and drive are required.

Bhp — Brake Horsepower Input to Fan

3. Maximum continuous bhp is 4.20 with standard motor.

Refer to this page for general Fan Performance notes. NOTES:

4. Standard motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive.
1. Boldface indicates a field-supplied drive is required. (See Note 4.)

GENERAL NOTES FOR FAN PERFORMANCE TABLES 1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Indoor-Fan Motor Data table on page 89.

2. Values include losses for filters, unit casing, and wet coils. See page 88 for accessory/FIOP static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate.
Show 4 more labels / short text on this page
Airflow · (Cfm) · Airflow · (Cfm)
Page 88 of the Bryant 549B user manual — FAN RPM AT MOTOR PULLEY SETTINGS* — 549B036-120
Page 88 · click to enlarge
Page 88

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 549B036-072

COMPONENT CFM 900 1200 1400 1600 1800 2000 2200 2400 2600 3000 1 Heater Module 0.05 0.07 0.09 0.09 0.10 0.11 0.11 0.12 0.13 0.15 2 Heater Modules 0.15 0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18 0.19 Durablade Economizer Accessory 0.05

EconoMi$er 0.05 0.09 0.13 0.17 0.22 0.27 0.32 0.39 0.45 0.53

LEGEND FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 549B090,120

COMPONENT CFM 2250 2500 3000 3500 4000 4500 5000 5500 6000 6250 1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17 2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20 Durablade Economizer Accessory 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.09

50TFQ004-012 549B036-120

EconoMi$er 0.07 0.09 0.13 0.18 0.23 0.30 0.36 — — —

LEGEND FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* — 549B036-120

UNIT 549B MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 036 1090 1055 1025 990 960 925 890 860 825 795 760 — — 048 1185 1150 1115 1080 1045 1015 980 945 910 875 840 — — 060 1460 1425 1385 1350 1315 1275 1240 1205 1165 1130 1095 1055 1020 072 1585 1540 1490 1445 1400 1350 1305 1260 1210 1165 1120 — — 090 925 905 888 865 845 825 805 785 765 745 725 — — 120 1080 1060 1035 1015 990 970 950 925 905 880 860 — —

*Approximate fan rpm shown.

Page 89 of the Bryant 549B user manual — EconoMi$er Power Exhaust Performance
Page 89 · click to enlarge
Page 89

OPTIONAL POWER EXHAUST

POWER REQUIREMENTS

STATIC PRESSURE (in. wg)

MOCP 230 VAC 460 VAC 549B036-072 1.40 Amps @ 60 Hz 15.0 amps 15.0 amps 549B090,120 3.04 Amps @ 60 Hz

UNIT SIZE

AMPS @ 230 V (2 Fans Running)

MOCP — Maximum Overcurrent Protection

0.00 0 500 1000 1500 2000

549B036-072 549B090,120

FLOW (CFM)

EconoMi$er Barometric Relief

50TFQ004-012 549B036-120

Damper Characteristics

2 FANS OPERATING

2 FANS OPERATING

1 FAN OPERATING

1 FAN OPERATING

0 0 0.1 0.2 0.3 0.4 0.5

0 0.1 0.2 0.3 0.4 0.5

STATIC PRESSURE (in. wg)

STATIC PRESSURE (in. wg)

EconoMi$er Power Exhaust Performance

EconoMi$er Power Exhaust Performance

(549B036-072)

(549B090,120)

INDOOR-FAN MOTOR DATA — 549B036-120

UNIT 549B UNIT PHASE

MAXIMUM CONTINUOUS BHP*

MAXIMUM OPERATING WATTS* UNIT VOLTAGE MAXIMUM AMP DRAW

MOTOR EFFICIENCY (%)

036 Single 1.20 1000 208/230 5.1 75 Three 1.20 1000 208/230 5.1 460 2.3

048 Single 1.20 1000 208/230 5.1 75 Three 1.20 1000 208/230 5.1 460 2.3

060 Single 1.80 1921 208/230 9.2 74 Three 1.80 1921 208/230 6.1 460 2.7

072 Three 2.40 2120 208/230 6.1 84 460 2.7

090 Three 2.90 2615 208/230 7.9 80 460 3.6

120 Three 4.20 3775 208/230 11.1 85 460 5.0

Bhp — Brake Horsepower Input to Fan

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

FLOW (cfm) · FLOW (cfm) · 4000 3000

Page 90 of the Bryant 549B user manual — 549B ARI RATING
Page 90 · click to enlarge
Page 90

ELECTRIC HEATING CAPACITIES ELECTRIC HEATING CAPACITIES (cont)

ACCESSORY

ACCESSORY

ACCESSORY

ACCESSORY

UNIT 549B VOLTAGE

ACCESSORY

HEATER PART NUMBER CRHEATER---A00

SINGLE POINT BOX

UNIT 549B VOLTAGE

ACCESSORY

HEATER PART NUMBER CRHEATER---A00

SINGLE POINT BOX

PART NO. CRSINGLE---A00

PART NO. CRSINGLE---A00

4.4 101 — 6.5 102 — 8.7 103 — 10.5 104 — 13.0* 102* 004

10.4 117 006 16.0 110 006 24.8 111 007 32.0 112 007 42.4* 112,117 009

4.4 101 — 6.5 102 — 8.7 103 — 10.5 104 — 16.0 105 —

13.9 116 006 16.5 113 006 27.8 114 006 33.0 115 006 41.7* 114,116 008

6.0 106 — 8.8 107 — 11.5 108 — 14.0 109 —

10.4 117 012 16.0 110 012 32.0 112 012 42.4* 112,117 015 50.0* 112,110 015

4.4 101 — 8.7 103 — 13.0* 102* 004 17.4* 103* 004 21.0* 104* 004

16.5 113 011 27.8 114 011 33.0 115 011† 41.7* 114,116 014 50.0* 115,113 014

50TFQ004-012 549B036-120

6.5 102 — 8.7 103 — 16.0 105 — 21.0* 104* 002

*Two heater packages required to provide kW indicated. †On units with factory-installed outlet, use CRSINGLE014A00. NOTES: The kW ratings shown above are at 240 and 480 v. Use the Multiplication Factors table to determine heater capacity for your particular voltage.

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* —

6.5 102 — 8.7 103 — 13.0* 102* 004 17.4* 103* 004 21.0* 104* 004

MULTIPLICATION FACTORS

VOLTAGE DISTRIBUTION

MULTIPLICATION

RATING

FACTOR

V/3/60

6.5 102 — 10.5 104 — 16.0 105 — 21.0* 104* 002 26.5* 105,104 002

240 200 .69 208 .75 230 .92 240 1.00

480 440 .84 460 .92 480 1.00

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* — 25.5* 109,108 —

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v = 32.0 (.75 mult factor) = 24.0 kW capacity at 208 v.

6.5 102 — 10.5 104 — 16.0 105 — 21.0* 104* 002 26.5* 105,104 002

OUTDOOR SOUND POWER (TOTAL UNIT)

6.0 106 — 11.5 108 — 14.0 109 — 23.0* 108* — 25.5* 109,108 —

549B ARI RATING

OCTAVE BANDS; Lw (A)

63 125 250 500 1000 2000 4000 8000

036,048 76 50.8 63.4 62.2 65.9 69.2 65.9 63.0 56.5 060,072 80 57.6 70.2 66.9 71.7 74.7 72.2 67.8 62.4 090 82 62.3 69.3 71.5 74.7 76.2 72.9 68.7 61.5 120 84 64.6 71.1 73.3 76.9 77.6 73.7 70.6 63.7

ARI — Air Conditioning and Refrigeration Institute Lw (A) — Unit A — Weighted Sound Power Level

Show 21 more labels / short text on this page
(60 Hz) · kW · (60 Hz) · kW · 208/230 (single phase) · 208/230 (3 phase) · 208/230 (3 phase) · 460 (3 phase) · 460 (3 phase) · 208/230 (3 phase) · 208/230 (single phase) · 460 (3 phase) · 208/230 (3 phase) · 460 (3 phase) · 208/230 (single phase) · HEATER kW · 208/230 (3 phase) · 460 (3 phase) · 208/230 (3 phase) · 460 (3 phase) · (dB)
Page 91 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 91 · click to enlarge
Page 91

ELECTRICAL DATA

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET

VOLTAGE

RANGE COMPRESSOR OFM IFM ELECTRIC

POWER SUPPLY

MINIMUM UNIT

UNIT 549B

NOMINAL

DISCONNECT

SIZE Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA

HEAT*

—/— —/— 25.6/ 25.6 30/ 30** 25/ 25 101/101 3.3/ 4.4 15.9/18.3 45.5/ 48.5 50/ 50** 43/ 46 117/120 4.9/ 6.5 23.6/27.1 55.1/ 59.5 60/ 60** 52/ 56 125/128 6.5/ 8.7 31.3/36.3 64.7/ 71.0 70/ 80 61/ 67 133/138 7.9/10.5 38.0/43.8 73.1/ 80.4 80/ 90 69/ 75 139/145 9.8/13.0 47.1/54.2 84.5/ 93.4 90/100 79/ 87 148/155††

208/230-1-60 187 254 16.0 88.0 0.7 4.9

—/— —/— 18.5/ 18.5 20/ 20** 18/ 18 90/ 90 3.3/ 4.4 9.2/10.6 30.0/ 31.7 30/ 35** 29/ 30 99/101 4.9/ 6.5 13.6/15.6 35.5/ 38.0 40/ 40** 34/ 36 104/106 6.5/ 8.7 18.0/20.9 41.0/ 44.6 45/ 45** 39/ 42 108/111 7.9/10.5 21.9/25.3 45.9/ 50.1 50/ 60** 43/ 47 112/116 12.0/16.0 33.3/38.5 60.1/ 66.6 70/ 70 57/ 63 124/129

208/230-3-60 187 254 10.3 77.0 0.7 4.9

— — 9.0 15** 9 46 6.0 7.2 18.0 20** 17 53 8.8 10.6 22.2 25** 21 57 11.5 13.8 26.2 30** 25 60 14.0 16.8 30.0 30** 28 63

460-3-60 414 508 5.1 39.0 0.4 2.2

50TFQ004-012 549B036-120

—/— —/— 35.2/ 35.2 40/ 40** 34/ 34 142/142 3.3/ 4.4 15.9/18.3 55.1/ 58.1 60/ 60** 52/ 55 158/161 6.5/ 8.7 31.3/36.3 74.4/ 80.6 80/ 90 70/ 75 174/179 9.8/13.0 47.1/54.2 94.1/103.0 100/110 88/ 96 189/196†† 13.1/17.4 63.0/72.5 114.0/125.9 125/150 106/117 205/215†† 15.8/21.0 76.0/87.5 130.2/144.6 150/150 121/134 218/230††

208/230-1-60 187 254 23.7 129.0 0.7 4.9

—/— —/— 22.5/ 22.5 25/ 25** 22/ 22 112/112 4.9/ 6.5 13.6/15.6 39.5/ 42.0 40/ 45** 38/ 40 126/128 6.5/ 8.7 18.0/20.9 45.0/ 48.6 45/ 50** 43/ 46 130/133 12.0/16.0 33.3/38.5 64.1/ 70.6 70/ 80 60/ 66 146/151 15.8/21.0 43.9/50.5 77.4/ 85.6 90/100 72/ 80 156/163

208/230-3-60 187 254 13.5 99.0 0.7 4.9

— — 11.9 15** 12 57 6.0 7.2 20.9 25** 20 64 11.5 13.8 29.1 30** 27 70 14.0 16.8 32.9 35** 31 73 23.0 27.7 46.5 50** 43 84

460-3-60 414 508 7.4 49.5 0.4 2.2

—/— —/— 46.3/ 46.3 50/ 50** 45/ 45 216/216 4.9/ 6.5 23.6/27.1 75.8/ 80.2 80/ 90 72/ 76 240/243 6.5/ 8.7 31.3/36.3 85.4/ 91.7 90/100 81/ 87 247/252†† 9.8/13.0 47.1/54.2 105.2/114.1 110/125 99/107 263/270†† 13.1/17.4 63.0/72.5 125.1/136.9 150/150 117/128 279/289†† 15.8/21.0 76.0/87.5 141.3/155.7 150/175 132/146 292/304††

208/230-1-60 187 254 28.8 169.0 1.5 8.8

—/— —/— 28.9/ 28.9 30/ 30** 28/ 28 168/168 4.9/ 6.5 13.6/15.6 45.9/ 48.4 50/ 50** 44/ 46 181/183 7.9/10.5 21.9/25.3 56.3/ 60.6 60/ 70 53/ 57 190/193 12.0/16.0 33.3/38.5 70.6/ 77.1 80/ 80 67/ 73 201/208 15.8/21.0 43.9/50.5 83.8/ 92.1 90/100 79/ 86 212/218†† 19.9/26.5 55.2/63.8 97.9/108.7 100/110 92/102 223/232††

208/230-3-60 187 254 17.3 123.0 1.5 5.8

— — 14.7 15** 14 84 6.0 7.2 23.7 25** 23 92 11.5 13.8 31.9 35** 30 98 14.0 16.8 35.7 40** 34 101 23.0 27.7 49.3 50** 46 112 25.5 30.7 53.0 60** 50 115

460-3-60 414 508 9.0 62.0 0.8 2.6

—/— —/— 32.8/ 32.8 35/ 35** 32/ 32 200/200 4.9/ 6.5 13.6/15.6 49.8/ 52.3 50/ 60** 47/ 50 214/216 7.9/10.5 21.9/25.3 60.2/ 64.5 70/ 70 57/ 61 222/225 12.0/16.0 33.3/38.5 74.5/ 81.0 80/ 90 70/ 76 233/239 15.8/21.0 43.9/50.5 87.7/ 96.0 90/100 82/ 90 244/251†† 19.9/26.5 55.2/63.8 101.8/112.6 110/125 95/105 255/264††

208/230-3-60 187 254 20.5 156.0 1.4 5.8

— — 15.2 20** 15 92 6.0 7.2 24.2 25** 23 99 11.5 13.8 32.5 35** 31 106 14.0 16.8 36.2 40** 34 109 23.0 27.7 49.8 50** 47 120 25.5 30.7 53.6 60** 50 123

460-3-60 414 508 9.6 70.0 0.6 2.6

Show 5 more labels / short text on this page
VOLTAGE (V-Ph-Hz) · 036 (3 Tons) · 048 (4 Tons) · 060 (5 Tons) · 072 (6 Tons)
Page 92 of the Bryant 549B user manual — LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEND
Page 92 · click to enlarge
Page 92

ELECTRICAL DATA (cont)

UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

RANGE COMPRESSOR OFM IFM ELECTRIC

POWER SUPPLY

MINIMUM UNIT

UNIT 549B

NOMINAL

DISCONNECT

SIZE Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA

HEAT*

—/— —/— 38.2/ 38.2 40/ 40** 40/ 40 242/242 7.8/10.4 21.7/ 25.0 65.3/ 69.5 70/ 70 65/ 69 264/267 12.0/16.0 33.3/ 38.5 79.8/ 86.3 80/ 90 79/ 85 275/281†† 18.6/24.8 51.6/ 59.7 102.7/112.8 110/125 100/109 294/302†† 24.0/32.0 66.6/ 77.0 121.5/134.5 125/150 117/129 309/319†† 31.8/42.4 88.3/102.0 148.6/165.7 150/175 142/158 330/344††

208/230-3-60 187 254 12.4 88.0 1.4 7.5

090*** (71/2 Tons)

— — 19.2 20** 20 121 13.9 16.7 40.1 45** 39 138 16.5 19.8 44.0 45** 43 141 27.8 33.4 61.0 70 59 155 33.0 39.7 68.8 70 66 161 41.7 50.2 82.0 90 78 171

460-3-60 414 508 6.4 44.0 0.7 3.4

—/— —/— 56.8/ 56.8 60/ 60** 60/ 60 337/337 7.8/10.4 21.7/ 25.0 84.0/ 88.1 90/ 90 85/ 89 358/362†† 12.0/16.0 33.3/ 38.5 98.5/105.0 100/110 98/104 370/375†† 24.0/32.0 66.6/ 77.0 140.1/153.1 150/175 136/148 403/414†† 31.8/42.4 88.3/102.0 167.2/184.3 175/200 161/177 425/439†† 37.6/50.0 104.4/120.3 187.3/177.1 200/200 180/198 441/457††

208/230-3-60 187 254 19.3 123.0 1.4 10.6

50TFQ004-012 549B036-120

— — 28.7 30 30 170 16.5 19.8 53.3 60 53 189 27.8 33.4 70.5 80 69 203 33.0 39.7 78.3 80 76 209 41.7 50.2 91.5 100 88 220†† 50.0 60.1 88.8 100 99 230††

460-3-60 414 508 10.0 62.0 0.7 4.8

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEND

FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps

= 100 x max voltage deviation from average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455

= 457 Determine maximum deviation from average voltage.

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v and 480 v. If

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. **Fuse or HACR circuit breaker. ††Optional disconnect switch cannot be used. ***Units have 2 outdoor fan motors.

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Show 5 more labels / short text on this page
VOLTAGE (V-Ph-Hz) · 120*** (10 Tons) · % Voltage Imbalance · average voltage · = 1371
Page 93 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 93 · click to enlarge
Page 93

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET

VOLTAGE

RANGE COMPRESSOR OFM IFM ELECTRIC

POWER SUPPLY

MINIMUM UNIT

UNIT 549B

NOMINAL

DISCONNECT

SIZE Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA

HEAT*

—/— —/— 30.4/ 30.4 35/ 35** 30/ 30 106/106 3.3/ 4.4 15.9/18.3 50.3/ 53.3 60/ 60** 49/ 51 122/124 4.9/ 6.5 23.6/27.1 59.9/ 64.3 60/ 70 58/ 62 130/133 6.5/ 8.7 31.3/36.3 69.5/ 75.8 70/ 80 66/ 72 137/142 7.9/10.5 38.0/43.8 77.9/ 85.2 80/ 90 74/ 81 144/150†† 9.8/13.0 47.1/54.2 89.3/ 98.2 90/100 85/ 93 153/160††

208/230-1-60 187 254 16.0 88.0 0.7 4.9

—/— —/— 23.3/ 23.3 25/ 25** 24/ 24 95/ 95 3.3/ 4.4 9.2/10.6 34.8/ 36.5 35/ 40** 34/ 36 104/106 4.9/ 6.5 13.6/15.6 40.3/ 42.8 45/ 45** 39/ 42 109/111 6.5/ 8.7 18.0/20.9 45.8/ 49.4 50/ 50** 45/ 48 113/116 7.9/10.5 21.9/25.3 50.7/ 54.9 60/ 60** 49/ 53 117/120 12.0/16.0 33.3/38.5 64.9/ 71.4 70/ 80 62/ 68 128/134

208/230-3-60 187 254 10.3 77.0 0.7 4.9

— — 11.2 15** 11 48 6.0 7.2 20.2 25** 20 55 8.8 10.6 24.4 25** 24 59 11.5 13.8 28.4 30** 27 62 14.0 16.8 32.2 35** 31 65

460-3-60 414 508 5.1 39.0 0.4 2.2

50TFQ004-012 549B036-120

—/— —/— 40.0/ 40.0 45/ 45** 39/ 39 147/147 3.3/ 4.4 15.9/18.3 59.9/ 62.9 60/ 70 58/ 60 163/165 6.5/ 8.7 31.3/36.3 79.2/ 85.4 80/ 90 75/ 81 178/183†† 9.8/13.0 47.1/54.2 98.9/107.8 100/110 93/102 194/201†† 13.1/17.4 63.0/72.5 118.8/130.7 125/150 112/123 210/220†† 15.8/21.0 76.0/87.5 135.0/149.4 150/150 127/140 223/235††

208/230-1-60 187 254 23.7 129.0 0.7 4.9

—/— —/— 27.3/ 27.3 30/ 30** 27/ 27 117/117 4.9/ 6.5 13.6/15.6 44.3/ 46.8 45/ 50** 43/ 45 131/133 6.5/ 8.7 18.0/20.9 49.8/ 53.4 50/ 60** 48/ 52 135/138 12.0/16.0 33.3/38.5 68.9/ 75.4 70/ 80 66/ 72 150/156 15.8/21.0 43.9/50.5 82.2/ 90.4 90/100 78/ 86 161/168††

208/230-3-60 187 254 13.5 99.0 0.7 4.9

— — 14.0 15** 14 59 6.0 7.2 23.0 25** 22 66 11.5 13.8 31.3 35** 30 73 14.0 16.8 35.0 40** 33 76 23.0 27.7 48.7 50** 46 86

460-3-60 414 508 7.4 49.5 0.4 2.2

—/— —/— 51.1/ 51.1 60/ 60** 50/ 50 221/221 4.9/ 6.5 23.6/27.1 80.6/ 85.0 90/ 90 78/ 82 245/248†† 6.5/ 8.7 31.3/36.3 90.2/ 96.5 100/100 86/ 92 252/257†† 9.8/13.0 47.1/54.2 110.0/118.9 110/125 105/113 268/275†† 13.1/17.4 63.0/72.5 129.9/141.7 150/150 123/134 284/293†† 15.8/21.0 76.0/87.5 146.1/160.5 150/175 138/151 297/308††

208/230-1-60 187 254 28.8 169.0 1.5 8.8

—/— —/— 33.7/ 33.7 35/ 35** 34/ 34 173/173 4.9/ 6.5 13.6/15.6 50.7/ 53.2 60/ 60** 49/ 52 186/188 7.9/10.5 21.9/25.3 61.1/ 65.4 70/ 70 59/ 63 194/198 12.0/16.0 33.3/38.5 75.4/ 81.9 80/ 90 72/ 78 206/211 15.8/21.0 43.9/50.5 88.6/ 96.9 90/100 84/ 92 216/223†† 19.9/26.5 55.2/63.8 102.7/113.5 110/125 97/107 228/236††

208/230-3-60 187 254 17.3 123.0 1.5 5.8

— — 16.8 20** 17 87 6.0 7.2 25.8 30** 25 94 11.5 13.8 34.1 35** 33 100 14.0 16.8 37.8 40** 36 103 23.0 27.7 51.5 60** 49 114 25.5 30.7 55.2 60** 52 117

460-3-60 414 508 9.0 62.0 0.8 2.6

—/— —/— 37.6/ 37.6 40/ 40** 37/ 37 205/205 4.9/ 6.5 13.6/15.6 54.6/ 57.1 60/ 60** 53/ 55 219/221 7.9/10.5 21.9/25.3 65.0/ 69.3 70/ 70 63/ 66 227/230 12.0/16.0 33.3/38.5 79.3/ 85.8 80/ 90 76/ 82 238/243†† 15.8/21.0 43.9/50.5 92.5/100.8 100/110 88/ 95 249/255†† 19.9/26.5 55.2/63.8 106.6/117.4 110/125 101/111 260/269††

208/230-3-60 187 254 20.5 156.0 1.4 5.8

— — 17.4 20** 17 94 6.0 7.2 26.4 30** 26 101 11.5 13.8 34.6 35** 33 108 14.0 16.8 38.4 40** 37 111 23.0 27.7 52.0 60** 49 122 25.5 30.7 55.8 60** 53 125

460-3-60 414 508 9.6 70.0 0.6 2.6

Show 5 more labels / short text on this page
VOLTAGE (V-Ph-Hz) · 036 (3 Tons) · 048 (4 Tons) · 060 (5 Tons) · 072 (6 Tons)
Page 94 of the Bryant 549B user manual — LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEND
Page 94 · click to enlarge
Page 94

ELECTRICAL DATA (cont)

UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

VOLTAGE

RANGE COMPRESSOR OFM IFM ELECTRIC

POWER SUPPLY

MINIMUM UNIT

UNIT 549B

NOMINAL

DISCONNECT

SIZE Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA

HEAT*

—/— —/— 43.0/ 43.0 45/ 45** 46/ 46 247/247 7.8/10.4 21.7/ 25.0 70.1/ 74.3 80/ 80 71/ 75 269/272 12.0/16.0 33.3/ 38.5 84.6/ 91.1 90/100 84/ 90 280/285†† 18.6/24.8 51.6/ 59.7 107.5/117.6 110/125 105/115 298/307†† 24.0/32.0 66.6/ 77.0 126.3/139.3 150/150 122/134 313/324†† 31.8/42.4 88.3/102.0 153.4/170.5 175/175 147/163 335/349††

208/230-3-60 187 254 12.4 88.0 1.4 7.5

090*** (71/2 Tons)

— — 21.4 25** 23 123 13.9 16.7 42.3 45** 42 140 16.5 19.8 46.1 50** 46 143 27.8 33.4 63.1 70 61 157 33.0 39.7 71.0 80 68 163 41.7 50.2 84.1 90 80 174††

460-3-60 414 508 6.4 44.0 0.7 3.4

—/— —/— 61.6/ 61.6 70/ 70 65/ 65 341/341 7.8/10.4 21.7/ 25.0 88.8/ 92.9 90/100 90/ 94 363/366†† 12.0/16.0 33.3/ 38.5 103.3/109.6 110/110 104/110 375/380†† 24.0/32.0 66.6/ 77.0 144.9/157.9 150/175 142/154 408/418†† 31.8/42.4 88.3/102.0 172.0/189.1 175/200 167/183 430/443†† 37.6/50.0 104.4/120.3 192.1/181.9 200/200 185/204 446/462††

208/230-3-60 187 254 19.3 123.0 1.4 10.6

50TFQ004-012 549B036-120

— — 30.9 35** 33 172 16.5 19.8 55.6 60** 55 191 27.8 33.4 72.6 80 71 205 33.0 39.7 80.5 90 78 211 41.7 50.2 93.6 100 90 222†† 50.0 60.1 91.0 100 102 232††

460-3-60 414 508 10.0 62.0 0.7 4.8

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEND

FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps

= 100 x max voltage deviation from average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455

= 457 Determine maximum deviation from average voltage.

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v and 480 v. If

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. **Fuse or HACR circuit breaker. ††Optional disconnect switch cannot be used. ***Units have 2 outdoor fan motors.

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

NOTES: 1. In compliance with NEC requirements for multimotor and combina- tion load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Show 5 more labels / short text on this page
VOLTAGE (V-Ph-Hz) · 120*** (10 Tons) · % Voltage Imbalance · average voltage · = 1371
Page 95 of the Bryant 549B user manual — 50TFQ004-012 549B036-120
Page 95 · click to enlarge
Page 95

TYPICAL WIRING SCHEMATIC

Bryant 549B — TYPICAL WIRING SCHEMATIC diagram (page 95)
Fig. 19

50TFQ004-012 549B036-120

549B036-120

Page 96 of the Bryant 549B user manual — 24V POTTER & BRUNFIELD
Page 96 · click to enlarge
Page 96

TYPICAL WIRING SCHEMATIC (cont)

LEGEND FOR TYPICAL WIRING SCHEMATIC IMPORTANT: Consult unit wiring label for actual wiring schematic.

AHA — Adjustable Heat Anticipator AWG — American Wire Gage C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CLO — Compressor Lockout COMP — Compressor Motor DB — Defrost Board DFT — Defrost Thermostat ECON — Economizer FPT — Freeze-Up Protection Thermostat FSS — Filter Status Switch FU — Fuse GND — Ground HC — Heater Contactor (Strip Heat) HPS — High-Pressure Switch HR — Heater Relay IFC — Indoor-Fan Contactor IFM — Indoor-Fan Motor LPS — Low-Pressure Switch LSM — Limit Switch (Manual Reset) MTR — Motor OAT — Outdoor-Air Thermostat OFM — Outdoor-Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal R — Relay RAT — Return-Air Thermostat

RVS — Reversing Valve Solenoid SAT — Supply Air Thermostat SW2 — Switch, Fully Closed SW3 — Switch, Minimum Vent Position TB — Terminal Block TC — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer

50TFQ004-012 549B036-120

Accessory or Optional Wiring

To indicate common potential only, not to represent wiring

1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 2. Three phase motors are protected under primary single phasing conditions. 3. Thermostat: HH07AT170, 172, 174 Subbase: HH93AZ176 4. Set heat anticipator at .8 amp for 1st stage & .3 amp for 2nd stage. 5. Use copper conductors only. 6. Use copper, copper clad aluminum. or aluminum conductors. 7.

VOLTAGE

CB MUST

RATING

TRIP AMPS HFG. PT. NO.

24V POTTER & BRUNFIELD

W2BX-1024-3.2 3.2

Show 10 more labels / short text on this page
Field Splice · Marked Wire · Terminal (Marked) · Terminal (Unmarked) · Terminal Block · Splice · Splice (Marked) · Factory Wiring · Field Control Wiring · Field Power Wiring
Page 97 of the Bryant 549B user manual — 50TFQ004-012 548F/549B036-120
Page 97 · click to enlarge
Page 97

GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS

PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 3 TO 10 TONS, NOMINAL (COOLING) BRYANT MODEL NUMBER: 548F,

3. Cabinet panels shall be easily removable for servicing. 4. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging. 5. Unit shall have a factory-installed, sloped conden- sate drain pan made of a non-corrosive material, pro- viding a minimum 3/4-in.-14 NPT. connection with both vertical and horizontal drains, and shall comply with ASHRAE Standard 62. 6. Unit shall have a factory-installed filter access panel to provide filter access with tool-less removal. 7. Unit shall have standard thru-the-bottom power con- nection capability (accessory kit is required). C. Fans:

549B PART 1 — General 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, electrically controlled air-to-air heat pump unit utilizing a hermetic reciprocating (548F) or scroll (549B) compressor for cooling and heating duty and electric resistance coils for auxiliary heating duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standards 210/

1. Indoor Fan: a. Fan shall be direct or belt driven as shown on the

240 or 360 and 270. Designed in accordance with UL Standard 1995. B. Unit shall be designed to conform to ASHRAE 15, latest

equipment drawings. Belt drive shall include an adjustable-pitch motor pulley. b. Fan wheel shall be double-inlet type with forward-

revision. C. Unit shall be UL-tested and certified in accordance

curved blades. c. Bearings shall be sealed, permanently lubricated

with ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements. D. Roof curb shall be designed to conform to NRCA

ball-bearing type for longer life and lower maintenance. 2. Indoor fan shall be made from steel with a corrosion- resistant finish and shall be dynamically balanced. 3. Outdoor fan shall be of the direct-driven (with totally enclosed motors) propeller type and shall discharge air vertically. 4. Outdoor fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynam- ically balanced. D. Compressor(s):

Standards. E. Insulation and adhesive shall meet NFPA 90A require-

ments for flame spread and smoke generation. F. Unit casing shall be capable of withstanding 500-hour salt

spray exposure per ASTM B117 (scribed specimen). G. Unit shall be designed in accordance with ISO 9001, and

shall be manufactured in a facility registered to ISO 9002/ BS5750, Part 2. H. Each unit shall be subjected to a completely automated

50TFQ004-012 548F/549B036-120

1. Fully hermetic type, internally protected, scroll or reciprocating type. 2. Factory mounted on rubber grommets and internally spring mounted for vibration isolation. 3. On independent circuits (548F090-120 and 549B090,120). E. Coils:

run testing on the assembly line. Units contain a factory- supplied printout indicating tested pressures, amperages, data, and inspectors; providing certification of the unit status at the time of manufacture. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recommendations. PART 2 — Products 2.01 EQUIPMENT (STANDARD) A. General:

1. Standard indoor and outdoor coils shall have copper or aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed. 2. Coils: a. Copper-fin coils shall be constructed of copper

Factory assembled, single-piece heat pump unit. Con- tained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:

fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper con- struction shall provide protection in moderate coastal environments.

1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a prepainted baked enamel finish on all externally exposed surfaces. 2. Indoor fan compartment interior cabinet surfaces shall be insulated with a minimum 1 / 2 -in. thick, 1 lb. density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil-faced fiberglass insulation shall be used in the gas heat compartment.
Page 98 of the Bryant 549B user manual — 50TFQ004-012 548F/549B036-120
Page 98 · click to enlarge
Page 98

GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)

b. E-Coated aluminum-fin coils shall have a flexible

H. Filter Section:

epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be alumi- num fins mechanically bonded to copper tubes. c. E-Coated copper-fin coils shall have a flexible

1. Standard filter section shall consist of factoryinstalled, low velocity, throwaway 2-in. thick fiberglass filters of commercially available sizes. 2. Filter face velocity shall not exceed 320 fpm at nominal airflows. 3. Filter section should use only one size filter. 4. Filters shall be accessible through an access panel with “no-tool” removal. I. Controls and Safeties:
1. Unit Controls: Unit shall be complete with self-contained lowvoltage control circuit protected by a fuse on the 24-v transformer side (090-120 units have a resettable circuit breaker). 2. Safeties: a. Unit shall incorporate a solid-state compressor

protector which provides anti-cycle reset capabil- ity at the space thermostat, should any of the fol- lowing standard safety devices trip and shut off compressor. 1) Compressor overtemperature, overcurrent. 2) Loss-of-charge/low-pressure switch. 3) Freeze-protection thermostat, evaporator coil. 4) High-pressure switch. 5) Automatic reset motor thermal overload protector. The lockout protection shall be easily discon- nected at the control board, if necessary. b. Heating section shall be provided with the follow-

epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting sheet metal coil pan to maintain coating integrity and minimize corrosion potential between coil and pan. d. Optional pre-coated aluminum-fin coils shall have

ing minimum protections: 1) High-temperature limit switches. 2) Overcurrent protection. c. Unit shall incorporate an outdoor coil defrost sys-

50TFQ004-012 548F/549B036-120

tem to prevent excessive frost accumulation dur- ing heating duty, and shall be controlled as follows: 1) Defrost shall be initiated on the basis of time and coil temperature. 2) A 30/50/90-minute timer shall activate defrost cycle only if the coil temperature is low enough to indicate a heavy frost condition. 3) Defrost cycle shall terminate when defrost thermostats are satisfied and shall have a pos- itive termination time of 10 minutes. J. Operating Characteristics:

a durable epoxy-phenolic coating to provide pro- tection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimum gal- vanic action between dissimilar metals. F. Heating Section:

1. Unit shall be capable of starting and running at 115 F (548F) or 125 F (549B) ambient outdoor tempera- ture, meeting maximum load criteria of ARI Standard 210/240 or 360 at +10% voltage. 2. Compressor with standard controls shall be capable of operation down to 25 F (in cooling mode) ambient outdoor temperature. 3. Compressor with optional controls shall be capable of operation down to –20 F (in heating mode) ambi- ent outdoor temperature. 4. Unit shall be capable of simultaneous heating duty and defrost cycle operation when using accessory electric heaters.

1. May be equipped with field-installed electric resistance heater(s) of the characteristics shown in the equipment schedule. 2. Heater elements shall be open wire, adequately supported and insulated with ceramic bushings. G. Refrigerant Components:

Refrigerant circuit components shall include:

1. Fixed orifice metering system. 2. Refrigerant filter drier. 3. Reversing valve. 4. Service gage connections on suction, discharge, and liquid lines.
Page 99 of the Bryant 549B user manual — 50TFQ004-012 548F/549B036-120
Page 99 · click to enlarge
Page 99

GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)

K. Electrical Requirements:

*5. 100% Two-Position Dampera. Two-position damper package shall include single

All unit power wiring shall enter unit cabinet at a single factory-predrilled location. L. Motors:

blade damper and motor. Admits up to 100% out- door air. b. Damper shall close upon indoor (evaporator) fan

1. Compressor motors shall be cooled by refrigerant gas passing through motor windings and shall have line break thermal and current overload protection. 2. Indoor-fan motor shall have permanently lubricated bearings and inherent automatic-reset thermal overload protection. 3. Totally enclosed outdoor-fan motor shall have permanently lubricated bearings, and inherent automaticreset thermal overload protection. M. Special Features:

shutoff. c. Designed to close damper during loss of power

situations. d. Equipped with 15% barometric relief damper. *6. 25% Two-Position Damper: a. Two-position damper package shall include single

blade damper and motor. Admits up to 25% out- door air. b. Damper shall close upon indoor fan shutoff. *7. Head Pressure Control Package: Consists of solid-state control and condenser-coil temperature sensor to maintain condensing temper- ature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. *8. Electric Resistance Heaters: a. Open wire nichrome elements with all necessary

Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office.

1. Roof Curbs (Horizontal and Vertical): a. Formed galvanized steel with wood nailer strip

and shall be capable of supporting entire unit weight. b. Permits installation and securing of ductwork to

curb prior to mounting unit on the curb. *2. Integrated Economizers: a. Integrated integral modulating type capable

safety operating controls. b. UL listed and indicated on basic unit information

of simultaneous economizer and compressor operation. b. Includes all hardware and controls to provide

plate. c. Available in multiples to match heating require-

ments. d. Single point kits available for each heater when

cooling with outdoor air. c. Equipped with low-leakage dampers, not to exceed

required. *9. Electronic Programmable Thermostat: Capable of using deluxe full-featured electronic ther- mostat. Shall use built-in compressor cycle delay control for both heating and cooling duty. *10. Thermostat and Subbase: Provides staged cooling and heating automatic (or manual) changeover, fan control, and indicator light. *11. Outdoor Coil Hail Guard Assembly: Hail guard shall protect against damage from hail and flying debris. *12. Unit-Mounted, Non-Fused Disconnect Switch: Shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall provide unit power shutoff. Shall be accessible from outside the unit and shall provide power off lockout capability. *13. Convenience Outlet: Shall be factory-installed and internally mounted with easily accessible 115-v female receptacle. Shall include 15 amp GFI receptacle with independent fuse protection. Voltage required to operate conve- nience outlet shall be provided by a factory-installed step-down transformer. Shall be accessible from out- side the unit. *14. Outdoor Coil Grille: The grille protects the outdoor coil from damage by large objects without increasing unit clearances.

3% leakage at 1 in. wg pressure differential. d. Capable of introducing up to 100% outdoor air. e. EconoMi$er shall be equipped with a barometric

50TFQ004-012 548F/549B036-120

relief damper. f. Designed to close damper(s) during loss-of-

power situations with spring return built into motor. g. Dry bulb outdoor-air temperature sensor shall be

provided as standard. Enthalpy, differential tem- perature, and differential enthalpy control shall be provided as an option. h. EconoMi$er is a gear-driven parallel blade

design. i. EconoMi$er shall provide control of internal build-

ing pressure through its accessory two-stage power exhaust function. j. EconoMi$er shall be capable of control from a 4

to 20 mA signal. 3. 25% Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 25% outdoor air for year-round ventilation. *4. 50% Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year-round ventilation.

Page 100 of the Bryant 549B user manual — 50TFQ004-012 548F/549B036-120
Page 100 · click to enlarge
Page 100

GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)

15. Compressor Cycle Delay: Unit shall be prevented from restarting for minimum of 5 min. after shutdown. *16. Thru-the-Bottom Utility Connectors: Kit shall provide connectors to permit electrical con- nections to be brought to the unit through the basepan. *17. Fan/Filter Status Switch: Provides status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat. *18. Solid-State Enthalpy Control: a. For use with Durablade economizer package only. b. Capable of sensing outdoor-air enthalpy content

*23. Return Air Enthalpy Sensor: The return air enthalpy sensor shall be used with the EconoMi$er device. When used in conjunction with an outdoor air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control. *24. Return Air Temperature Sensor: The return air temperature sensor shall be used with the EconoMi$er device. When used in conjunction with the standard outdoor air temperature sensor, the EconoMi$er device will provide differential tem- perature control. *25. Power Exhaust Auxiliary Transformer: Field-installed 460v to 230v transformer to provide power to the 230v power exhaust when attached to a 460v rooftop unit. *26. Ultra-Violet Germicidal Lamps: Ultra-violet germicidal lamps are designed to elimi- nate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germicidal lamps are field installed in the evaporator section of the unit, aimed at the evaporator coil and condensate pan. The short wavelength ultra-violet light inhibits and kills mold, fungus and microbial growth. The lamps have an output rating at 45 F in 400 fpm air- flow of 120 microwatts/cm2 at 1 meter. *27. Hinged Panel Option (549B only): Hinged panel option provides hinged access panels for the filter, compressor, evaporator fan, and control box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is perma- nently attached to the rooftop unit. 28. Emergency Heat Control Package: When mechanical heating is locked out, auxiliary heat shall be activated when necessary. 29. Alternate Motors and/or Drives 548F036-060, 090, 120): Alternate motors and drives shall be factory-installed to provide additional performance range. 30. High-Static Motor(s) and Drive(s) (548F036-120): High-static motor(s) and drive(s) shall be factory- installed to provide and additional performance range.

(temperature and humidity) and controlling econ- omizer cut-in point to have minimum heat content air passing over the indoor coil for most efficient system operation. *19. Differential Enthalpy Sensor: a. For use with Durablade economizer only. b. Capable of comparing enthalpy content (tempera-

ture and humidity) of outdoor and indoor air and controlling economizer cut-in point at the most economical level. *20. EconoMi$er with Power Exhaust: Package shall provide control of internal building pressure. The two-stage system shall exhaust up to 100% of return air (vertical only). *21. Two-Stage Power Exhaust Accessory for EconoMi$er:

50TFQ004-012 548F/549B036-120

Power exhaust shall be used in conjunction with EconoMi$er to provide system exhaust of up to 100% of return air. The power exhaust is a field-installed accessory (vertical and horizontal applications). The individual fans are energized through the end switches located in the actuator, which will open as the outdoor-air damper opens. These end switches are factory set for 30 and 70% of outdoor-air, and can be set to meet specific job requirements. *22. Outdoor Air Enthalpy Sensor: The outdoor air enthalpy sensor shall be used with the EconoMi$er device to provide single enthalpy control. When used in conjunction with a return air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control. The sensor allows the EconoMi$er controller to determine if outside air is suitable for free cooling.

Page 101 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 101 · click to enlarge
Page 101

MODEL NUMBER NOMENCLATURE — 542J150,180 UNITS

542J E X 150 000 AB H B

542J – High-Efficiency Rooftop Units Electric Heat Pumps

Fan Drive Position (Standard Motor) B – Standard Low-Medium

Fan Drive Static Capability D – Alternate High Fan

Voltage Designation E – 460-3-60 P – 208/230-3-60

Heat Type X – No Heat Installed

Factory-Installed Outdoor Air Upgrade Options C – Economizer H – 25% Manual Damper

Nominal Cooling Capacity 150 – 12 Tons 180 – 15 Tons

Electric Heaters 000 – No Factory-Installed Electric Heaters Accessory Field-Installed Electric Heaters Available

Design Series Code AB – EconoMi$er Design Change

Bryant 549B — MODEL NUMBER NOMENCLATURE — 542J150,180 UNITS diagram (page 101)
Fig. 20

50TFQ004-012 542J150,180

Drive Static Capability

Page 102 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 102 · click to enlarge
Page 102

ARI* CAPACITY RATINGS

542J150,180 UNITS

COOLING HEATING-HIGH TEMP HEATING-LOW TEMP SOUND RATING (decibels) Total

UNIT 542J

150 14.3 140,000 4500 12.4 9.8 136,000 12.4 3.2 72,000 10.0 2.1 87 180 18.5 172,000 5200 9.7 9.3 172,000 15.3 3.3 90,000 12.5 2.2 88

Cooling ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: ESP: –.35 in. wg Cooling Standard: 80 F db, 67 wb indoor coil entering-air temperature and 95 F outdoor entering-air temperature. High-Temp Heating Standard: 70 F db indoor coil entering-air temper- ature and 47 F db, 43 F wb outdoor coil entering-air temperature. Low-Temp Heating Standard: 70 F db indoor coil entering-air temper- ature and 17 F db, 15 F wb outdoor coil entering-air temperature. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

COP — Coefficient of Performance db — Dry Bulb EER — Energy Efficiency Ratio ESP — External Static Pressure IPLV — Integrated Part-Load Value kW — Kilowatts wb — Wet Bulb

*Air-Conditioning and Refrigeration Institute.

PHYSICAL DATA

Bryant 549B — PHYSICAL DATA diagram (page 102)
Fig. 21
Bryant 549B — PHYSICAL DATA diagram (page 102)
Fig. 22

WEIGHT DISTRIBUTION AND CENTER OF GRAVITY

WEIGHT WEIGHT OF CORNER DIMENSIONS

UNIT 542J

Lb Kg A B C D X Y Z Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm 150 1615 733 366 166 356 161 360 163 534 242 3′-1″ 947 3′-2″ 965 1′-10″ 559 180 1925 874 464 211 496 225 477 217 487 221 3′-6″ 1059 3′-8″ 1105 1′-10″ 559

50TFQ004-012 542J150,180

Show 12 more labels / short text on this page
Net Capacity · Total Capacity · Total · Total Capacity · Total · Cfm IPLV EER · kW COP · kW COP · kW · (Btuh) · (Btuh) · (Btuh)
Page 103 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 103 · click to enlarge
Page 103

PHYSICAL DATA (cont)

542J150,180

UNIT 542J 150 180 OPERATING WT (lb)

Unit 1615 1925 Electric Heat 65 65 EconoMi$er 80 80 Roof Curb* 200 200 COMPRESSOR Semi-Hermetic Model Number (Quantity) 06D-328 (1) 06D-818 (2) Cylinders 6 4 Capacity Staging (%) 0,66,100 0,50,100 Oil Change (oz) 11 88 (each) REFRIGERANT TYPE R-22 Charge (lb) System 1 26.0 16.5 System 2 — 16.5 OUTDOOR COIL 3/8 in. Enhanced Copper Tubes, Aluminum Lanced or Copper Plate Fins Rows 3 3 Fins/in. 15 15 Total Face Area (sq ft) 21.7 21.7 OUTDOOR FAN Propeller Type, Direct Drive Nominal Cfm 9,000 9,000 Number...Diameter (in.) 3...22 3...22 Motor Hp (1075 Rpm) 1/2 1/2 Watts Input (Total) 1090 1090 INDOOR COIL 3/8-in. Enhanced Copper Tubes, Aluminum Double Wavy or Copper Plate Fins, Face Split Rows 3 3 Fins/in. 15 15 Total Face Area (sq ft) 17.5 17.5 INDOOR FAN Centrifugal, Adjustable Pitch Belt Drive Quantity...Size (in.) 2...10 x 10 2...12 x 12 Nominal Cfm 5000 6000 Fan Rpm Range STD 891-1179 817-1038 ALT 1227-1559 1082-1303 Motor Nominal Rpm 1725 1745 Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter (in.) STD 3.1-4.1 3.7-4.7 ALT 3.7-4.7 4.9-5.9 Fan Pulley Pitch Diameter (in.) STD 6.0 7.9 ALT 5.2 7.9 Belt, Quantity...Type...Length (in.) STD 1...BX...42 1...BX...46 ALT 1...BX...42 1...BX...50 Pulley Center Line Distance (in.) 13.5-15.5 13.3-14.8 Factory Setting 3.5 3.5 Factory Speed Setting STD 1035 934 ALT 1389 1199 Motor Hp (Service Factor) 3.7 (1.15) 5 (1.15) Motor Frame Size 56H 184T Motor Efficiency 0.86 0.875 HIGH-PRESSURE SWITCH

Cutout (psig) 426 Reset (psig) 320 LOW-PRESSURE/LOSS-OF-CHARGE SWITCH

Cutout (psig) 7 Reset (psig) 22 FREEZE PROTECTION THERMOSTAT (F)

Opens 30 ± 5 Closes 45 ± 5 AIR INLET SCREENS Cleanable

Economizer, Quantity...Size (in.) 2...20 x 25 x 1 1...20 x 20 x 1 RETURN-AIR FILTERS (Type) 10% Efficient — 2-in. Throwaway Fiberglass

50TFQ004-012 542J150,180

Quantity...Size (in.) 4...20 x 20 x 2 4...16 x 20 x 2 POWER EXHAUST 1/2 Hp 208/230 or 460 V Motor, Direct Drive Propeller Fan (Factory Wired for 460 V)

Al — Aluminum Cu — Copper

*Weight of 14 in. roof curb

Page 104 of the Bryant 549B user manual — 542J150,180
Page 104 · click to enlarge
Page 104

BASE UNIT DIMENSIONS

Bryant 549B — BASE UNIT DIMENSIONS diagram (page 104)
Fig. 23

UNIT 542J MAXIMUM SHIPPING WEIGHT*

Lb Kg 150 1895 860 180 2205 1000

*Units with aluminum indoor and outdoor coil fins.

DIMENSIONS X Y Ft-in. mm Ft-in. mm 150 3-1 947 3-2 965 180 3-6 1059 3-8 1105

UNIT 542J

1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.

4. Ductwork to be attached to accessory roof curb only. 5. Minimum clearance: a. Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions permit coil removal from the top. b. Left side: 4′-0″ (1219) for proper outdoor coil airflow. c. Front: 4′-0″ (1219) for control box access. d. Right side: 4′-0″ (1219) for proper operation of damper and power exhaust (if so equipped). e. Top: 6′-0″ (1829) to assure proper outdoor fan operation. f. Local codes or jurisdiction may prevail. 6. With the exception of clearance for the outdoor coil and the damper and power exhaust as stated in note no. 5, a remov- able fence or barricade requires no clearance. 7. Dimensions are from outside of corner post. Allow 0′-5/16″ (8) on each side for top cover drip edge.

50TFQ004-012 542J150,180

WEIGHT OF CORNER* A B C D Lb Kg Lb Kg Lb Kg Lb Kg 150 366 166 356 161 360 163 534 242 180 464 211 496 225 477 217 487 221

UNIT 542J

*Weights are for unit only and do not include options or crating.

542J150,180

KO — Knockout

Page 105 of the Bryant 549B user manual — ACCESSORY DIMENSIONS
Page 105 · click to enlarge
Page 105

ACCESSORY DIMENSIONS

Bryant 549B — ACCESSORY DIMENSIONS diagram (page 105)
Fig. 24
6. A 90 degree elbow must be installed on the supply ductwork

below the unit discharge for units equipped with electric

2. Insulated panels: 1 ″ thick neoprene coated 1 1 / 2 lb density.

pan of the indoor section, unit can only be pitched as shown.

Page 106 of the Bryant 549B user manual — Convenience Outlet — 542J150,180
Page 106 · click to enlarge
Page 106

ACCESSORY DIMENSIONS (cont)

Bryant 549B — ACCESSORY DIMENSIONS (cont) diagram (page 106)
Fig. 25 · ACCESSORY DIMENSIONS (cont)

ACCESSORY PACKAGE NO.

CURB HEIGHT DESCRIPTION

CRRFCURB013A00 2′-0″ (610) Pre-Assembled

High Static Horizontal Adapter

Horizontal Adapter Installation — 542J150,180

Bryant 549B — Horizontal Adapter Installation — 542J150,180 diagram (page 106)
Fig. 26 · Horizontal Adapter Installation — 542J150,180

50TFQ004-012 542J150,180

K.O. — Knockout

Convenience Outlet — 542J150,180

Page 107 of the Bryant 549B user manual — Power Exhaust — 542J150,180
Page 107 · click to enlarge
Page 107

ACCESSORY DIMENSIONS (cont)

Bryant 549B — ACCESSORY DIMENSIONS (cont) diagram (page 107)
Fig. 27 · ACCESSORY DIMENSIONS (cont)

Non-Fused Disconnect — 542J150,180

50TFQ004-012 542J150,180

2'-2 1/16" 1'-6 5/16"

Power Exhaust — 542J150,180

2'-1 5/8"

Page 108 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 108 · click to enlarge
Page 108

SELECTION PROCEDURE (WITH 542J180 EXAMPLE)

I DETERMINE HEATING AND COOLING REQUIRE-

Enter the Electric Heating Capacities table at 230-3-60. The 34-kW heater satisfies the electric heater requirements. IV DETERMINE FAN SPEED AND MOTOR HORSEPOWER

MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) 164,000 Btuh Sensible Heat Capacity (SHC) 120,000 Btuh Required Heating Capacity 170,000 Btuh Outdoor-Air Temperature (Cooling) 95 F Indoor Entering-Air Temperature

REQUIREMENTS AT DESIGN CONDITIONS. Before entering Fan Performance table, calculate the total static pressure required based on unit components. From the given and the Accessory/FIOP Static Pressure table on page 112, find:

External static pressure 1.30 in. wg EconoMi$er static pressure 0.07 in. wg Electric heat static pressure 0.09 in. wg

(Cooling) 80 F Edb/67 F Ewb Outdoor Coil Entering-Air Temperature

(Heating) 0° F Indoor Winter Design Temperature 70 F Indoor-Air Quantity 6000 Cfm External Static Pressure (ESP 1.30 in. wg Electrical Characteristics (V-Ph-Hz) 230-3-60 EconoMi$er is specified. Edb — Entering dry bulb Ewb — Entering wet bulb II SELECT UNIT BASED ON REQUIRED COOLING

Total static pressure 1.46 in. wg

Enter the Fan Performance table on page 111. At 6000 cfm and 1.46 in. wg external static pressure, the fan speed is 1214 and the bhp is 3.95 (interpolation required). The standard motor and alternate high static drive are suitable. V DETERMINE NET CAPACITIES.

Capacities are gross and do not include the effect of indoor-fan motor (IFM) heat. Determine net cooling capacity as follows: Net capacity = Gross capacity – IFM heat

CAPACITY. Enter Cooling Capacity table on page 109 at outdoor- entering temperature of 95 F, indoor air entering at 6000 cfm and 67 F ewb. The 542J180 will provide a total capacity (TC) of 180,800 Btuh, a sensible heat capacity (SHC) of 136,400 Btuh and a total unit kW of 15.88. For indoor-air temperature other than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in Note 3 following the Cooling Capacities table on page 109. NOTE: Unit ratings are gross capacities and do not include the effect of indoor-fan motor heat. To calculate net capacities, see Step V. III SELECT ELECTRIC HEAT.

= 180,800 – 3.95 bhp x hp .85 = 180,800 – 11,827 = 168,973 Btuh

Net sensible capacity = 136,400 – 11,827 = 124,573 Btuh Determine net heating capacity as follows: Net capacity = Gross capacity + IFM heat + Electric heat capacity = 58,500 + (IFM kW x 3412) + (Elec. kW x 3412) = 58,500 + 11,827 + (34 x 3412) = 58,500 + 11,827 + 116,008 = 186,335 Btuh

Enter the Integrated Heating Capacities table on page 110 at 6000 cfm. At 70 F return indoor air and 0° F air entering the outdoor coil, the integrated heating capacity is 58,500 Btuh with a unit input kW of 11.71 (interpolation required). The required heating capacity is 170,000 Btuh; therefore, 111,500 Btuh (170,000 – 58,500) additional electric heat is necessary. Determine the additional electric heat capacity in kW.

111,500 Btuh = 32.6 kW 3412 Btuh/kW

50TFQ004-012 542J150,180

2545 Btuh

Page 109 of the Bryant 549B user manual — BYPASS FACTOR
Page 109 · click to enlarge
Page 109

PERFORMANCE DATA

COOLING CAPACITIES

542J150

Air Entering Indoor Coil — Cfm/BF 3750/0.04 4500/0.05 5000/0.05 5625/0.06 6250/0.07 Air Entering Indoor Coil — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62

75 TC 167.0 154.0 140.0 171.0 158.0 144.0 173.0 159.0 146.0 171.0 162.0 148.0 173.0 161.0 151.0 SHC 79.6 100.0 120.0 85.0 108.0 131.0 87.5 114.0 138.0 94.5 120.0 146.0 97.7 127.0 150.0 kW 10.00 9.77 9.50 10.10 9.87 9.61 10.20 9.93 9.68 10.20 10.00 9.74 10.20 10.00 9.80

85 TC 160.0 148.0 133.0 164.0 151.0 137.0 167.0 154.0 140.0 168.0 155.0 143.0 166.0 157.0 146.0 SHC 77.6 98.9 118.0 82.0 107.0 129.0 86.1 113.0 136.0 89.6 118.0 142.0 95.3 125.0 146.0 kW 11.10 10.80 10.40 11.20 10.90 10.60 11.30 11.00 10.70 11.30 11.00 10.80 11.30 11.10 10.80

95 TC 155.0 141.0 127.0 157.0 144.0 131.0 160.0 146.0 133.0 161.0 149.0 137.0 163.0 149.0 140.0 SHC 76.1 96.3 115.0 80.3 105.0 126.0 84.4 110.0 132.0 86.5 117.0 137.0 91.7 121.0 140.0 kW 12.20 11.80 11.40 12.20 11.90 11.50 12.40 12.00 11.60 12.40 12.10 11.80 12.50 12.10 11.90

105 TC 147.0 133.0 120.0 150.0 137.0 124.0 152.0 138.0 127.0 153.0 140.0 131.0 154.0 141.0 134.0 SHC 73.6 93.3 112.0 78.5 102.0 123.0 81.6 108.0 127.0 85.1 114.0 131.0 88.6 120.0 134.0 kW 13.20 12.70 12.30 13.30 12.90 12.50 13.40 13.00 12.60 13.50 13.10 12.80 13.50 13.10 12.90

115 TC 140.0 126.0 112.0 141.0 129.0 118.0 144.0 130.0 121.0 144.0 131.0 125.0 146.0 133.0 128.0 SHC 71.4 90.3 109.0 75.1 99.1 117.0 78.9 104.0 121.0 81.9 110.0 125.0 87.0 117.0 128.0 kW 14.20 13.70 13.20 14.30 13.90 13.50 14.40 14.00 13.70 14.50 14.00 13.90 14.60 14.10 14.00

125 TC 131.0 118.0 105.0 134.0 120.0 111.0 135.0 122.0 115.0 137.0 123.0 118.0 136.0 124.0 121.0 SHC 68.1 87.6 105.0 73.5 96.4 111.0 75.7 102.0 115.0 80.7 108.0 118.0 83.4 113.0 121.0 kW 15.20 14.70 14.10 15.40 14.90 14.50 15.40 14.90 14.70 15.60 15.00 14.90 15.60 15.10 15.00

542J180

Air Entering Indoor Coil — Cfm/BF 4500/0.06 5250/0.08 6000/0.10 6750/0.10 7500/0.12 Air Entering Indoor Coil — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62

75 TC 210.0 192.0 173.4 216.0 196.6 178.4 220.0 202.0 182.2 222.0 204.0 185.6 224.0 206.0 190.2 SHC 100.6 125.2 148.2 106.0 134.0 160.6 110.6 143.0 172.2 115.0 151.2 183.2 120.2 158.2 190.0 kW 13.58 13.12 12.66 13.76 13.28 12.84 13.88 13.44 12.98 13.96 13.52 13.10 14.02 13.60 13.26

85 TC 202.0 183.0 164.4 208.0 187.8 169.0 212.0 191.4 172.8 212.0 194.0 177.2 214.0 195.8 182.2 SHC 98.0 121.8 144.2 103.8 131.2 156.4 109.0 140.0 168.6 112.0 148.0 177.0 116.2 155.6 182.2 kW 14.86 14.32 13.78 15.08 14.52 13.98 15.22 14.66 14.14 15.26 14.78 14.30 15.34 14.86 14.50

95 TC 192.4 173.2 155.0 196.2 177.8 159.2 200.0 180.8 163.4 202.0 183.4 169.0 204.0 185.4 174.2 SHC 94.8 118.0 140.0 100.2 127.4 152.6 105.6 136.4 163.4 110.6 144.8 169.0 114.2 153.2 173.8 kW 16.16 15.52 14.88 16.32 15.72 15.10 16.48 15.88 15.30 16.62 16.00 15.54 16.64 16.12 15.76

105 TC 182.0 163.0 145.0 186.4 167.0 149.4 188.6 170.0 155.4 191.0 172.2 160.8 193.0 173.8 165.2 SHC 91.0 114.2 135.2 96.8 123.6 147.6 101.8 132.6 155.2 107.2 141.2 160.6 112.2 149.6 165.2 kW 17.36 16.64 15.92 17.58 16.86 16.16 17.70 17.04 16.48 17.84 17.18 16.74 17.94 17.28 16.96

115 TC 171.2 152.4 134.8 175.0 156.2 140.6 177.8 158.8 146.8 179.4 160.8 152.2 179.6 162.2 156.4 SHC 87.4 110.2 130.8 92.6 119.4 140.6 98.8 128.2 146.8 103.6 136.8 151.8 107.2 144.6 156.2 kW 18.54 17.72 16.90 18.76 17.94 17.24 18.94 18.12 17.60 19.02 18.28 17.90 19.04 18.38 18.16

125 TC 159.4 141.2 125.0 162.8 143.8 132.0 165.6 147.0 137.8 166.6 148.8 143.0 168.2 150.0 146.8 SHC 83.6 105.8 125.0 89.0 115.0 131.8 94.4 123.6 137.8 99.8 132.2 142.8 105.0 139.6 146.6 kW 19.64 18.74 17.88 19.86 19.00 18.34 20.00 19.12 18.72 20.20 19.28 19.00 20.20 19.40 19.28

3. SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input SHC — Gross Sensible Heat Capacity (1000 Btuh) TC — Gross Total Capacity (1000 Btuh)

ENTERING AIR DRY-BULB TEMP (F) 79 78 77 76 75 under 75 81 82 83 84 85 over 85 Correction Factor .05 1.04 2.07 3.11 4.14 5.18

BYPASS FACTOR

(BF)

50TFQ004-012 542J150,180

1. Direct interpolation is permissible. Do not extrapolate. 2. The following formulas may be used:

Use formula shown below. .10.98 1.96 2.94 3.92 4.90 .20.87 1.74 2.62 3.49 4.36 .30.76 1.53 2.29 3.05 3.82

tldb = tedb – sensible capacity (Btuh)

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leav-

Interpolation is permissible. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

ing indoor coil (hlwb)

hlwb = hewb – total capacity (Btuh)

4.5 x cfm

Whereh ewb = Enthalpy of air entering indoor coil
Show 6 more labels / short text on this page
Temp (F) · Air Ent Outdoor · Coil · Temp (F) · Air Ent Outdoor · Coil
Page 110 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 110 · click to enlarge
Page 110

INTEGRATED HEATING CAPACITIES

542J150

Temp Air Entering Outdoor Coil (F db at 75% RH) –10 0 10 17 20 30 40 47 50 60

CFM

Air Temp F (db)

Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW

3750 55 40.4 7.81 53.0 8.35 65.6 8.89 74.5 9.27 78.5 9.47 91.9 10.10 120.0 11.00 140.0 11.50 147.0 11.80 168.0 12.60 70 37.7 8.19 49.8 8.85 61.9 9.51 70.3 9.97 74.1 10.20 86.8 11.00 114.0 11.90 133.0 12.50 139.0 12.90 161.0 13.90 80 35.4 8.41 47.1 9.15 58.8 9.89 67.0 10.40 70.8 10.70 83.4 11.50 109.0 12.50 128.0 13.20 134.0 13.60 156.0 14.70

4500 55 40.3 7.98 53.9 8.49 67.5 9.00 77.0 9.35 80.9 9.54 93.8 10.10 123.0 10.90 144.0 11.40 149.0 11.60 167.0 12.30 70 36.7 8.38 49.8 9.00 62.9 9.62 72.0 10.00 75.9 10.30 88.6 11.00 116.0 11.80 136.0 12.50 142.0 12.70 163.0 13.60 80 33.2 8.64 46.4 9.32 59.6 10.00 68.7 10.50 72.6 10.70 85.2 11.50 112.0 12.50 131.0 13.10 137.0 13.40 159.0 14.50

5000 55 41.0 8.11 54.7 8.60 68.4 9.09 78.0 9.43 81.9 9.60 95.0 10.20 124.0 10.90 144.0 11.40 149.0 11.60 165.0 12.10 70 44.7 8.45 55.2 9.07 65.7 9.69 73.1 10.10 76.9 10.30 89.7 11.00 118.0 11.90 138.0 12.50 143.0 12.70 163.0 13.50 80 33.6 8.76 47.0 9.43 60.4 10.10 69.8 10.60 73.6 10.80 86.3 11.60 113.0 12.50 132.0 13.10 139.0 13.40 160.0 14.40

5625 55 42.0 8.27 55.7 8.74 69.4 9.21 79.0 9.54 83.0 9.71 96.2 10.30 124.0 10.90 144.0 11.40 148.0 11.50 164.0 12.10 70 42.7 8.66 54.3 9.24 65.9 9.82 74.1 10.20 77.9 10.40 90.9 11.10 120.0 11.90 140.0 12.50 145.0 12.70 163.0 13.40 80 34.5 8.94 48.0 9.57 61.5 10.20 70.9 10.70 74.7 10.90 87.4 11.60 115.0 12.50 134.0 13.10 140.0 13.40 160.0 14.30

6250 55 44.0 8.43 57.3 8.89 70.6 9.35 79.9 9.67 83.9 9.83 97.3 10.40 124.0 11.00 143.0 11.40 147.0 11.50 160.0 12.00 70 45.7 8.79 56.8 9.37 67.9 9.95 75.6 10.40 79.4 10.50 91.9 11.20 120.0 12.00 140.0 12.50 145.0 12.70 161.0 13.30 80 35.2 9.04 48.8 9.72 62.4 10.40 71.9 10.80 75.7 11.00 88.4 11.70 117.0 12.60 136.0 13.20 142.0 13.40 159.0 14.20

542J180

Temp Air Entering Outdoor Coil (F db at 75% RH) –10 0 10 17 20 30 40 47 50 60

CFM

Air Temp F (db)

Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW

3750 55 46.4 9.80 60.8 10.60 75.6 11.34 85.8 11.84 91.4 12.10 110.0 12.96 150.2 14.00 178.2 14.72 189.4 15.08 228.0 16.32 70 39.6 10.04 54.4 10.96 69.8 11.86 80.4 12.48 85.8 12.78 103.4 13.82 141.6 15.02 168.4 15.84 179.0 16.26 214.0 17.64 80 35.0 10.20 50.2 11.20 65.8 12.20 76.8 12.90 81.8 13.24 99.2 14.38 136.0 15.70 161.8 16.60 172.0 17.04 206.0 18.52

4500 55 47.8 10.02 62.0 10.78 77.0 11.48 87.6 11.96 93.2 12.20 112.0 12.98 153.2 13.92 182.2 14.58 193.4 14.90 230.0 15.94 70 40.6 10.26 55.8 11.16 71.2 12.00 82.0 12.60 87.4 12.90 105.4 13.86 144.6 14.98 172.0 15.74 182.8 16.12 220.0 17.36 80 36.0 10.44 51.6 11.40 67.4 12.36 78.4 13.04 83.6 13.36 101.0 14.44 138.8 15.68 165.2 16.52 175.8 16.94 212.0 18.30

5000 55 48.6 10.26 63.0 10.98 78.4 11.64 89.2 12.10 94.8 12.32 113.6 13.06 155.2 13.94 184.4 14.56 195.8 14.86 234.0 15.80 70 41.8 10.50 56.8 11.36 72.6 12.18 83.6 12.76 89.0 13.04 107.2 13.96 147.0 15.00 174.8 15.74 185.8 16.08 222.0 17.24 80 37.2 10.66 52.8 11.62 68.6 12.54 79.8 13.20 85.0 13.50 103.0 14.56 141.4 15.72 168.2 16.52 179.0 16.90 216.0 18.18

5625 55 49.2 10.50 63.8 11.18 79.4 11.82 90.2 12.26 96.0 12.46 115.2 13.18 158.0 14.02 187.8 14.60 198.4 14.84 234.0 15.64 70 42.6 10.72 58.0 11.58 73.6 12.38 84.6 12.92 90.2 13.20 108.6 14.08 149.2 15.08 177.6 15.78 188.4 16.10 224.0 17.14 80 38.2 10.88 54.0 11.84 69.8 12.74 81.0 13.38 86.4 13.68 104.4 14.68 143.4 15.80 170.8 16.58 181.6 16.94 218.0 18.14

6250 55 50.0 10.72 64.6 11.40 80.2 12.00 91.0 12.42 97.0 12.64 116.6 13.30 159.8 14.14 190.0 14.70 200.0 14.92 234.0 15.58 70 43.4 10.96 58.8 11.80 74.6 12.58 85.6 13.12 91.2 13.36 110.0 14.22 151.0 15.20 179.6 15.88 190.2 16.16 226.0 17.12 80 39.0 11.12 54.8 12.06 70.8 12.94 82.0 13.56 87.6 13.86 105.6 14.84 145.0 15.92 172.6 16.66 183.6 17.00 220.0 18.16

LEGEND NOTES:

1. Integrated heating capacity ratings shown are not adjusted for the effects of the indoor-fan motor power and heat. A deduction has been made for defrosting the outdoor coils at temperatures below 40 F. 2. Direct interpolation is permissible. Do not extrapolate. 3. When using auxiliary and/or supplementary heating, the maximum allowable leaving-air temperature is 140 F.

Cap. — Capacity (1000 Btuh) Edb — Entering Air Dry-Bulb Temperature (F) Ldb — Leaving Air Dry-Bulb Temperature (F) kW — Compressor and Outdoor-Fan Power Input RH — Relative Humidity

Ldb F = Edb F + Total heating cap. (Btuh)

1.10 x airflow cfm

4. For supplementary glycol coil: Fluid flow Gpm

= fluid capacity (Btuh) 500 x fluid temperature drop (F)

50TFQ004-012 542J150,180

Return · Return

Page 111 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 111 · click to enlarge
Page 111

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS

542J150

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 724 481 0.55 838 685 0.78 937 889 1.01 1028 1097 1.25 1111 1309 1.49 4000 754 613 0.70 865 824 0.94 962 1034 1.18 1050 1247 1.42 1131 1463 1.67 4250 786 757 0.86 893 975 1.11 987 1191 1.36 1073 1408 1.60 1152 1629 1.86 4500 818 914 1.04 922 1138 1.30 1013 1360 1.55 1097 1583 1.80 1174 1808 2.06 4750 850 1084 1.23 951 1313 1.50 1040 1541 1.76 1122 1770 2.02 1197 2000 2.28 5000 883 1267 1.44 980 1501 1.71 1068 1736 1.98 1147 1969 2.24 1221 2204 2.51 5250 917 1464 1.67 1011 1703 1.94 1096 1943 2.21 1174 2183 2.49 1246 2423 2.76 5500 950 1675 1.91 1041 1918 2.19 1124 2165 2.47 1201 2409 2.75 1272 2655 3.02 5750 985 1901 2.17 1072 2147 2.45 1153 2400 2.73 1228 2650 3.02 1298 2901 3.31 6000 1020 2142 2.44 1103 2391 2.72 1183 2649 3.02 1256 2905 3.31 1324 3160 3.60 6250 1055 2398 2.73 1135 2650 3.02 1213 2912 3.32 1284 3175 3.62 1352 3435 3.91

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3750 1190 1526 1.74 1265 1746 1.99 1337 1972 2.25 1405 2199 2.51 1471 2431 2.77 4000 1208 1684 1.92 1281 1908 2.17 1351 2136 2.43 1418 2368 2.70 1483 2603 2.97 4250 1227 1853 2.11 1299 2082 2.37 1367 2313 2.64 1433 2548 2.90 1496 2787 3.18 4500 1247 2036 2.32 1317 2268 2.58 1384 2503 2.85 1448 2742 3.12 1510 2983 3.40 4750 1269 2232 2.54 1337 2468 2.81 1403 2707 3.08 1465 2948 3.36 1526 3194 3.64 5000 1291 2441 2.78 1358 2680 3.05 1422 2923 3.33 1484 3168 3.61 1544 3418 3.89 5250 1315 2664 3.03 1380 2907 3.31 1443 3154 3.59 1503 3403 3.88 1562 3655 4.16 5500 1339 2900 3.30 1403 3148 3.59 1464 3398 3.87 1524 3651 4.16 — — — 5750 1364 3151 3.59 1426 3403 3.88 1486 3657 4.17 — 6000 1389 3416 3.89 1450 3672 4.18 — 6250 1415 3695 4.21 —

1. Standard drive range is 891 to 1179 rpm. Alternate drive range is 1227 to 1559. Other rpms may require a field-supplied drive. 2. Maximum continuous bhp is 4.25 and maximum continuous watts are 3775. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

Refer to this page for general Fan Performance notes.

542J180

External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 584 717 0.8 695 952 1.1 798 1205 1.3 893 1483 1.7 984 1786 2.0 4800 609 839 0.9 717 1085 1.2 815 1346 1.5 907 1630 1.8 994 1938 2.2 5100 634 971 1.1 738 1229 1.4 833 1500 1.7 921 1791 2.0 1006 2104 2.4 5400 660 1118 1.3 760 1389 1.6 852 1669 1.9 937 1968 2.2 1019 2286 2.6 5700 687 1284 1.4 783 1566 1.8 873 1858 2.1 956 2165 2.4 1034 2490 2.8 6000 712 1458 1.6 805 1752 2.0 892 2055 2.3 973 2371 2.7 1049 2703 3.0 6300 736 1644 1.8 826 1952 2.2 911 2265 2.5 990 2591 2.9 1064 2930 3.3 6600 763 1856 2.1 851 2176 2.4 933 2502 2.8 1010 2837 3.2 1082 3186 3.6 6900 788 2078 2.3 873 2410 2.7 954 2747 3.1 1029 3093 3.5 1099 3451 3.9 7200 813 2316 2.6 896 2662 3.0 975 3011 3.4 1048 3367 3.8 1117 3734 4.2 7500 841 2584 2.9 921 2943 3.3 998 3304 3.7 1070 3672 4.1 1137 4049 4.5

External Static Pressure (in. wg) 1.2 1.4 1.6 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1070 2113 2.4 1151 2458 2.8 1229 2819 3.2 1302 3194 3.6 — — — 4800 1078 2269 2.5 1157 2620 2.9 1233 2990 3.3 1306 3374 3.8 — — — 5100 1086 2439 2.7 1164 2795 3.1 1238 3170 3.5 — 5400 1097 2626 2.9 1172 2986 3.3 1245 3366 3.8 — 5700 1110 2835 3.2 1183 3200 3.6 1253 3584 4.0 — 6000 1122 3053 3.4 1193 3422 3.8 1262 3810 4.3 — 6300 1135 3286 3.7 1204 3660 4.1 1271 4052 4.5 — 6600 1151 3549 4.0 1218 3928 4.4 1283 4325 4.8 — 6900 1167 3821 4.3 1232 4207 4.7 1295 4608 5.2 — 7200 1183 4113 4.6 1246 4505 5.0 — 7500 1202 4437 5.0 1264 4837 5.4 —

50TFQ004-012 542J150,180

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

1. Standard drive range is 817 to 1038 rpm. Alternate drive range is 1082 to 1303. Other rpms may require a field-supplied drive. 2. Maximum continuous bhp is 5.90 and maximum continuous watts are 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

Refer to this page for general Fan Performance notes.

GENERAL NOTES FOR FAN PERFORMANCE TABLES 1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Indoor-Fan Motor Performance table on page 114.

2. Values include losses for filters, unit casing, and wet coils. See page 112 for accessory/FIOP static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate.
Show 10 more labels / short text on this page
Airflow · (Cfm) · 542J150 (cont) · Airflow · (Cfm) · Airflow · (Cfm) · 542J180 (cont) · Airflow · (Cfm)
Page 112 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 112 · click to enlarge
Page 112

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180

ACCESSORY/FIOP UNIT SIZE UNIT VOLTAGE kW CFM 3750 4500 5000 5600 6000 6250 7200 7500

150 208/230-3-60 14-34 0.05 0.05 0.07 0.08 0.09 0.09 0.11 0.12 42,56 0.06 0.06 0.08 0.10 0.12 0.13 0.16 0.17

460-3-60 15,32 0.05 0.05 0.07 0.08 0.09 0.09 0.11 0.12 55 0.06 0.06 0.08 0.10 0.12 0.13 0.15 0.15

180 208/230-3-60 26,34 * * * 0.08 0.09 0.09 0.11 0.12 42,56 0.10 0.12 0.13 0.16 0.17

460-3-60 32,55 * * * 0.08 0.09 0.09 0.11 0.12 0.10 0.12 0.13 0.15 0.17 EconoMi$er All All — 0.03 0.03 0.05 0.06 0.07 0.07 0.09 0.10 Glycol Coil All All — 0.16 0.18 0.25 0.31 0.35 0.37 0.44 0.46

FIOP — Factory-Installed Option

1. Heaters are rated at 208/240 v and 480 v. 2. The static pressure must be added to external static pressure. The sum and the indoor-air section entering-air cfm should then be used in conjunction with the Fan Performance table to determine blower rpm, bhp, and watts.

*Units with electric heat are not designed to operate at these ranges.

FAN RPM AT MOTOR PULLEY SETTINGS* — 542J150,180

UNIT 542J MOTOR PULLEY TURNS OPEN 0 1/2 1 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6

150† — — 1179 1150 1121 1093 1064 1035 1006 978 949 920 891 150** — — 1559 1522 1488 1455 1422 1389 1356 1323 1289 1256 1227 180† — — 1038 1023 1001 979 956 934 912 890 868 846 817 180** — — 1303 1288 1266 1244 1222 1199 1177 1155 1133 1111 1082

*Approximate fan rpm shown. †Standard motor with standard drive. **Standard motor with alternate drive.

Bryant 549B — FAN RPM AT MOTOR PULLEY SETTINGS* — 542J150,180 diagram (page 112)
Fig. 28

50TFQ004-012 542J150,180

Fan Performance Using Accessory Power Exhaust

Electric Heaters

Page 113 of the Bryant 549B user manual — GLYCOL COIL RATINGS
Page 113 · click to enlarge
Page 113
Bryant 549B — ACCESSORY DIMENSIONS diagram (page 113)
Fig. 29
Bryant 549B — ACCESSORY DIMENSIONS diagram (page 113)
Fig. 30

Horizontal Supply/Return Fan Performance with CRRFCURB013A00 High Static Regain Adapter

ELECTRIC HEATING CAPACITIES — 542J150,180

HEATER STAGES

% HEAT PER STAGE

MAXIMUM

UNIT 542J

STAGES* Unit Voltages 208 230 460

150 14 19 15 1 100 1 26 34 32 2 50/50 2 42 56 55 2 33/67 3

180 26 34 32 2 50/50 2 42 56 55 2 33/67 3

*Maximum number of stages using accessory outdoor-air thermostats. NOTE: Heaters are rated at 208 v, 240 v and 480 v. See multiplication factors table on page 54.

GLYCOL COIL DATA*

CFM 4400 5000 6200 % Glycol 25 50 25 50 25 50 Cap. Gpm Ldb Cap. Gpm Ldb Cap. Gpm Ldb Cap. Gpm Ldb Cap. Gpm Ldb Cap. Gpm Ldb

EDB EGT

55 200 310 33 120 293 33 116 333 35 117 315 36 113 375 40 111 353 40 108 180 255 27 108 237 27 105 274 29 106 254 29 102 308 33 101 285 33 98 160 200 21 97 181 21 93 215 23 95 194 22 91 241 25 91 217 25 87

70 200 274 29 127 257 29 124 294 31 124 276 31 121 331 35 119 310 35 116 180 218 23 116 201 23 112 235 25 114 216 25 110 264 28 109 241 28 106 160 164 17 104 146 17 100 176 19 103 156 18 99 197 21 99 174 20 96

80 200 249 26 132 233 27 129 268 28 130 250 28 126 301 32 125 280 32 122 180 194 21 121 177 20 117 209 22 119 190 22 115 234 25 115 212 24 112 160 140 15 109 123 14 106 150 16 108 131 15 104 168 18 105 146 17 102

LEGEND *This accessory glycol coil is intended for use with a MINIMUM of 25% glycol solution. It IS NOT intended for use solely with water due to freeze-up conditions and the resulting water damage to the condi- tioned space. NOTE: Fluid ∆t = 20 F.

50TFQ004-012 542J150,180

Cap. — Btuh x 1000 EDB — Entering Dry-Bulb Temperature (F) EGT — Entering Glycol Temperature (F) Gpm — Gallons per Minute Ldb — Leaving Dry-Bulb Temperature (F)

GLYCOL COIL RATINGS

ENTERING

CFM 4000 5000 6000 8000

FLUID

TEMP

(F)

GPM ∆P GPM ∆P GPM ∆P GPM ∆P

200 27 1.2 31 1.5 35 1.8 41 2.4 180 22 0.9 25 1.1 27 1.3 32 1.6 160 16 0.6 19 0.7 20 0.8 24 1.0

HEATER kW

Page 114 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 114 · click to enlarge
Page 114

INDOOR-FAN MOTOR PERFORMANCE — 542J150,180

MAXIMUM ACCEPTABLE CONTINUOUS

MAXIMUM ACCEPTABLE

UNIT 542J UNIT VOLTAGE

MAXIMUM AMP DRAW

MOTOR EFFICIENCY

OPERATING

BHP*

WATTS

150 208/230 4.25 3775 10.5 85.8 460 4.9 85.8

180 208/230 5.90 5180 15.8 87.5 460 7.9 87.5

LEGEND *Extensive motor and electrical testing on these units ensures that the full horse- power range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance trip- ping or premature motor failure. Unit warranty will not be affected.

Bhp — Brake Horsepower

ELECTRICAL DATA

VOLTAGE

COMPRESSOR OUTDOOR

INDOOR FAN

POWER EXHAUST ELECTRIC HEAT* POWER SUPPLY DISCONNECT

FAN MOTOR

UNIT 542J VOLTAGE (3 PH, 60 Hz)

RANGE

SIZING No. 1 No. 2

MOTOR

Min Max RLA LRA RLA LRA Qty FLA

(ea) Hp FLA FLA LRA FLA kW MCA MOCP† RLA LRA

—/— —/— 65/ 65 100/100 64/ 64 387/387 39/ 45 14/19 114/122 125/150 64/ 64 72/ 92 26/34 155/168 175/175 94/107 117/135 42/56 211/200 225/225 147/167

208/230 187 253 39.7 228 — — 3 1.7 3.7 10.5/10.5

4.6 18.8 —/— —/— 70/ 70 100/100 69/ 69 406/406 39/ 45 14/19 119/126 125/150 69/ 69 72/ 82 26/34 159/173 175/175 100/112 117/135 42/56 216/205 225/225 152/173

— — 32 50 31 189 18 15 54 60 31 39 32 81 90 50 66 55 98 110 82

460 414 508 19.9 114 — — 3 0.8 3.7 4.8

2.3 6.0 — — 34 50 34 195 18 15 57 70 34 39 32 83 90 53 66 55 100 110 84

— — —/— —/— 84/ 84 110/110 89/ 89 499/485 72/ 82 26/34 174/187 175/200 101/112 117/135 42/56 231/219 250/225 153/173

208/230 187 253 28.2 160 28.2 160 3 1.7 5 15.8/158

4.6 18.8 —/— —/— 89/ 89 110/110 94/ 94 518/504 72/ 82 26/34 179/191 200/200 106/118 117/135 42/56 235/224 250/225 158/179

— 42 50 44 238 39 32 91 100 54 66 55 108 110 85

460 414 508 14.1 80 14.1 80 3 0.8 5 7.9

2.3 6.0 — — 44 50 47 244 39 32 93 100 57 66 55 110 125 88

1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).

FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code RLA — Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Fuse or HACR circuit breaker. This is the maximum size permissible; smaller

fuse size may be used where conditions permit.

50TFQ004-012 542J150,180

Page 115 of the Bryant 549B user manual — TYPICAL WIRING SCHEMATIC
Page 115 · click to enlarge
Page 115

TYPICAL WIRING SCHEMATIC

Bryant 549B — TYPICAL WIRING SCHEMATIC diagram (page 115)
Fig. 31
Page 116 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 116 · click to enlarge
Page 116

TYPICAL WIRING SCHEMATIC (cont)

LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATIC

AHA — Adjustable Heat Anticipator BKR W/AT — Breaks with Amp Turns C — Contactor, Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor CT — Current Transformer CTD — Compressor Time Delay DAT — Discharge Air Thermistor DB — Defrost Board DFT — Defrost Thermostat DM — Damper Motor DR — Defrost Relay DU — Dummy Terminal EC — Enthalpy Control EQUIP — Equipment FL — Fuse Link FPT — Freeze Protection Thermostat GND — Ground HC — Heater Contactor HPS — High-Pressure Switch HR — Heat Relay HTR — Heater IFC — Indoor-Fan Contactor IFCB — Indoor-Fan Circuit Breaker IFM — Indoor Fan Motor IP — Internal Protector

L — Light LOR — Lock Out Relay LPS — Low-Pressure Switch LS — Limit Switch OAT — Outdoor-Air Thermostat OFC — Outdoor-Fan Contactor OFM — Outdoor Fan Motor OP — Overcurrent Protector PL — Plug Assembly QT — Quadruple Terminal RVR — Reversing Valve Relay RVS — Reversing Valve Solenoid TB — Terminal Block TC — Thermostat Cooling TH — Thermostat Heating TRAN — Transformer

To Indicate Common Potential OnlyNot To Represent Wiring

50TFQ004-012 542J150,180

1. Compressor and/or fan motor(s) thermally protected. Three-phase motors are protected against primary single phasing conditions. 2. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent. 3. CB1,2 must trip amps are equal to or less than 156% FLA, IFCB 140%. 4. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. 5. Jumpers are omitted when unit is equipped with economizer. 6. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally-closed contact. Plain (no line) number signifies a normally-open contact. 7. Remove jumper between terminals RC and RH.

Show 7 more labels / short text on this page
Terminal (Marked) · Terminal (Unmarked) · Terminal Block · Splice · Factory Wiring · Field Wiring · Option/Accessory Wiring
Page 117 of the Bryant 549B user manual — Optional Non-Fused Disconnect — 542J150,180
Page 117 · click to enlarge
Page 117

TYPICAL WIRING SCHEMATIC (cont)

6T3 4T2 2T1 LOAD

5L3 3L2 1L1 LINE

1. If the non-fused disconnect Service Option is ordered for size 150,180 units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.

Optional Non-Fused Disconnect — 542J150,180

50TFQ004-012 542J150,180

Page 118 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 118 · click to enlarge
Page 118

GUIDE SPECIFICATIONS — 542J150,180 UNITS

PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP — CON- STANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 12 to 15 TONS, NOMINAL (COOLING)

4. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging. 5. Unit shall have a factory-installed, sloped conden- sate drain pan made of a non-corrosive material, pro- viding a minimum 3/4-in. 14 NPT connection with both vertical and horizontal drains, and shall comply with ASHRAE Standard 62. 6. Unit shall have a factory-installed filter access panel to provide filter access with tool-less removal. 7. Unit shall have standard thru-the-bottom power con- nection capability (accessory kit is required). C. Fans:

136,000 to 172,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBER: 542J PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, electrically controlled air-to-air heat pump unit utilizing reciprocating, semi-hermetic com- pressor(s) for cooling duty and electric resistance coils for heating duty. Unit shall discharge supply air vertically or horizontally (with horizontal supply/return adapter assem- bly or roof curb) as shown on contract drawings. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standard 340.

1. Indoor Fan: a. Fan shall be belt driven with an adjustable-pitch

motor pulley. The standard fan drive shall have a factory-installed low-medium static pressure fan drive. The alternate fan drive option shall have a factory-installed high static pressure fan drive. b. Fan wheel shall be double-inlet type with forward-

Designed in accordance with UL Standard 1995. B. Unit shall be designed to conform to ASHRAE 15, latest

revision. C. Unit shall be UL-tested and certified in accordance

curved blades. c. Bearings shall be sealed, permanently lubricated

with ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements. D. Roof curb shall be designed to conform to NRCA

ball-bearing type for longer life and lower maintenance. d. Bearings shall be pillow block type (180 only). 2. Indoor fan shall be made from steel with a corrosion- resistant finish and shall be dynamically balanced. 3. Outdoor fan shall be of the direct-driven (with totally enclosed motors) propeller type and shall discharge air vertically. 4. Outdoor fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynam- ically balanced. D. Compressor(s):

Standards. E. Insulation and adhesive shall meet NFPA 90A require-

ments for flame spread and smoke generation. F. Unit casing shall be capable of withstanding 500-hour salt

spray exposure per ASTM B117 (scribed specimen). G. Unit shall be designed in accordance with ISO 9001, and

shall be manufactured in a facility registered to ISO 9002/ BS5750, Part 2. H. Each unit shall be subjected to a completely automated

run testing on the assembly line. Units contain a factory- supplied printout indicating tested pressures, amperages, data, and inspectors; providing certification of the unit status at the time of manufacture. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be stored and handled per manufacturer’s recommendations. PART 2 — PRODUCTS 2.01 EQUIPMENT (STANDARD) A. General:

1. Reciprocating semi-hermetic compressors with factory-installed crankcase heaters. 2. Factory mounted on rubber grommets and internally spring mounted for vibration isolation. 3. On independent circuits (180). 4. The size 150 unit semi-hermetic compressor shall be equipped with an electric unloader for capacity control. E. Coils:
1. Standard indoor and outdoor coils shall have copper or aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed. 2. Coils: a. Copper-fin coils shall be constructed of copper

Factory assembled, single-piece heat pump unit. Con- tained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up. B. Unit Cabinet:

50TFQ004-012 542J150,180

1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a prepainted baked enamel finish on all externally exposed surfaces. 2. Indoor fan compartment interior cabinet surfaces shall be insulated with a minimum 1 / 2 -in. thick, 1 lb. density, flexible fiberglass insulation, neoprene coated on the air side. 3. Cabinet panels shall be easily removable for servicing.

fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper con- struction shall provide protection in moderate coastal environments.

Page 119 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 119 · click to enlarge
Page 119

GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)

b. E-Coated aluminum-fin coils shall have a flexible

H. Filter Section:

epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be alumi- num fins mechanically bonded to copper tubes. c. E-Coated copper-fin coils shall have a flexible

1. Standard filter section shall consist of factoryinstalled, low velocity, throwaway 2-in. thick fiberglass filters of commercially available sizes. 2. Filter face velocity shall not exceed 320 fpm at nominal airflows. 3. Filter section should use only one size filter. 4. Filters shall be accessible through an access panel with “no-tool” removal. I. Controls and Safeties:
1. Unit Controls: Unit shall be complete with self-contained lowvoltage control circuit protected by a resettable circuit breaker on the 24-v transformer side. 2. Safeties: a. Unit shall incorporate a solid-state compressor

protector which provides anti-cycle reset capabil- ity at the space thermostat, should any of the fol- lowing standard safety devices trip and shut off compressor. 1) Compressor overtemperature, overcurrent. 2) Loss-of-charge/low-pressure switch. 3) Freeze-protection thermostat, evaporator coil. 4) High-pressure switch. 5) Automatic reset motor thermal overload protector. The lockout protection shall be easily discon- nected at the control board, if necessary. b. Heating section shall be provided with the follow-

epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss — 60 deg of 65 to 90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in.-lb (ASTM D2794-93). Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corro- sion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90. Coil construction shall be copper fins mechanically bonded to copper tubes with copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting sheet metal coil pan to maintain coating integrity and minimize corrosion potential between coil and pan. d. Optional pre-coated aluminum-fin coils shall have

ing minimum protections: 1) High-temperature limit switches. 2) Overcurrent protection. c. Unit shall incorporate an outdoor coil defrost sys-

tem to prevent excessive frost accumulation dur- ing heating duty, and shall be controlled as follows: 1) Defrost shall be initiated on the basis of time and coil temperature. 2) A 30/50/90-minute timer shall activate defrost cycle only if the coil temperature is low enough to indicate a heavy frost condition. 3) Defrost cycle shall terminate when defrost thermostats are satisfied and shall have a pos- itive termination time of 10 minutes. J. Operating Characteristics:

a durable epoxy-phenolic coating to provide pro- tection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize gal- vanic action between dissimilar metals. F. Heating Section:

1. Unit shall be capable of starting and running at 125 F ambient outdoor temperature, meeting maximum load criteria of ARI Standard 210/240 or 360 at + 10% voltage. 2. Compressor with standard controls shall be capable of operation down to 40 F (in cooling mode) ambient outdoor temperature. 3. Compressor shall be capable of operation down to –20 F (in heating mode) ambient outdoor temperature. 4. Unit shall be capable of simultaneous heating duty and defrost cycle operation when using accessory electric heaters.

1. May be equipped with field-installed electric resistance heater(s) of the characteristics shown in the equipment schedule. 2. Heater elements shall be open wire, adequately supported and insulated with ceramic bushings. G. Refrigerant Components:

50TFQ004-012 542J150,180

Refrigerant circuit components shall include:

1. Fixed orifice metering system. 2. Refrigerant filter drier. 3. Reversing valve. 4. Service gage connections on suction, discharge, and liquid lines.
Page 120 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 120 · click to enlarge
Page 120

GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)

K. Electrical Requirements:

5. Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year round ventilation. *6. 25% Two-Position Damper: a. Two-position damper package shall include single

All unit power wiring shall enter unit cabinet at a single factory-predrilled location. L. Motors:

1. Compressor motors shall be cooled by refrigerant gas passing through motor windings and shall have line break thermal and current overload protection. 2. Indoor-fan motor shall have permanently lubricated bearings and inherent automatic-reset thermal overload protection. 3. Totally enclosed outdoor-fan motor shall have permanently lubricated bearings, and inherent automaticreset thermal overload protection. M. Special Features:

blade damper and motor. Admits up to 25% out- door air. b. Damper shall close upon indoor fan shutoff. *7. Head Pressure Control Package: Consists of solid-state control and condenser-coil temperature sensor to maintain condensing temper- ature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles. *8. Electric Resistance Heaters: a. Open wire nichrome elements with all necessary

Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office.

1. Roof Curbs (Horizontal and Vertical): a. Formed galvanized steel with wood nailer strip

safety operating controls. b. UL listed and indicated on basic unit information

and shall be capable of supporting entire unit weight. b. Permits installation and securing of ductwork to

plate. c. Available in multiples to match heating requirements. d. Single point kits available for each heater when

curb prior to mounting unit on the curb. 2. Horizontal Adapter Roof Curb: Includes factory-assembled adapter and duct which substantially improves indoor fan static motor perfor- mance (static regain). NOTE: Power exhaust and barometric relief must be mounted in the return ductwork when used in con- junction with this accessory. *3. Integrated EconoMi$er: a. Integrated integral modulating type capable of

required. *9. Electronic Programmable Thermostat: Capable of using deluxe full-featured electronic ther- mostat. Shall use built-in compressor cycle delay control for both heating and cooling duty. *10. Thermostat and Subbase: Provides staged cooling and heating automatic (or manual) changeover, fan control, and indicator light. *11. Unit-Mounted, Non-Fused Disconnect Switch: Shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall provide unit power shutoff. Shall be accessible from outside the unit and shall provide power off lockout capability. *12. Convenience Outlet: Shall be factory-installed and internally mounted with easily accessible 115-v female receptacle. Shall include 15 amp GFI receptacle with independent fuse protection. Voltage required to operate conve- nience outlet shall be provided by a factory-installed step-down transformer. Shall be accessible from out- side the unit. *13. Compressor Cycle Delay: Unit shall be prevented from restarting for minimum of 5 min. after shutdown. *14. Fan/Filter Status Switch: Provides status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat.

simultaneous EconoMi$er and compressor operation. b. Includes all hardware and controls to provide

cooling with outdoor air. c. Equipped with low-leakage dampers, not to exceed 2% leakage at 1 in. wg pressure differential. d. Capable of introducing up to 100% outdoor air. e. EconoMi$er shall be equipped with a barometric

relief damper. f. Designed to close damper(s) during loss-of-

power situations with spring return built into motor. g. Dry bulb outdoor-air temperature sensor shall be

provided as standard. Enthalpy, differential tem- perature, and differential enthalpy control shall be provided as an option. h. EconoMi$er is a gear-driven parallel blade

50TFQ004-012 542J150,180

design. i. EconoMi$er shall provide control of internal build-

ing pressure through its accessory two-stage power exhaust function. j. EconoMi$er shall be capable of control from a 4

to 20 mA signal. 4. Barometric Relief Damper: a. Package shall include damper, seals, hardware,

and hoods to relieve excess internal pressure. b. Damper shall close due to gravity upon unit

shutdown.

Page 121 of the Bryant 549B user manual — 50TFQ004-012 542J150,180
Page 121 · click to enlarge
Page 121

GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)

15. Power Exhaust Accessory: Power exhaust shall be used to provide system exhaust of up to 100% of return air. The power exhaust is a field-installed accessory (vertical applications). 16. Outdoor Air Enthalpy Sensor: The outdoor air enthalpy sensor shall be used with the EconoMi$er device to provide single enthalpy control. When used in conjunction with a return air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control. The sensor allows the EconoMi$er controller to determine if outside air is suitable for free cooling. 17. Return Air Enthalpy Sensor: The return air enthalpy sensor shall be used with the EconoMi$er device. When used in conjunction with an outdoor air enthalpy sensor, the EconoMi$er device will provide differential enthalpy control. 18. Return Air Temperature Sensor: The return air temperature sensor shall be used with the EconoMi$er device. When used in conjunction with the standard outdoor air temperature sensor, the EconoMi$er device will provide differential tem- perature control. 19. Ultra-Violet Germicidal Lamps: Ultra-violet germicidal lamps are designed to elimi- nate odor causing mold and fungus that may develop in the wet area of the evaporator section of the unit. The high output, low temperature germicidal lamps are field installed in the evaporator section of the unit, aimed at the indoor coil and condensate pan. The short wavelength ultra-violet light inhibits and kills mold, fungus and microbial growth. The lamps

have an output rating at 45 F in 400 fpm airflow of 120 microwatts/cm2 at 1 meter. 20. Hinged Panel Option: Hinged panel option provide hinged access panels for the filter, compressor, evaporator fan, and control box areas. Filter hinged panels permit tool-less entry for changing filters. Each hinged panel is perma- nently attached to the rooftop unit. 21. Emergency Heat Control Package: When mechanical heating is locked out, auxiliary heat shall be activated when necessary. 22. Glycol Coil: Coil shall be 2-row copper tube (1/2-in. OD) with alu- minum plate fins (15 fins/in.) and 1.625 in. OD cop- per headers. Input and output connections shall be 1.625 in. ODM copper stubs for sweat connection. Coil shall be furnished with suitable support rails, end plates, and hardware for ready field installation in the heater compartment. 23. Winter Start Time Delay: Used in conjunction with the accessory low ambient kit or head pressure control device, the kit permits operation in cooling at lower outdoor temperatures. See price pages for more information. 24. Alternate Drive: Alternate drive shall provide higher static drive capa- bility to enhance indoor fan performance rpm range. 25. Stainless Steel Condensate Pan: Stainless steel condensate pans shall be available for condensate collection.

50TFQ004-012 542J150,180

Page 122 of the Bryant 549B user manual — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Page 122 · click to enlarge
Page 122

INDEX

542J150,180 section 101-121 548F036-120 section 18-66,97-100 549B036-120 section 67-100 Airflow Configuration 14 Maximum 14 Minimum 14 Application data 14,15 ARI capacity ratings 542J150,180 102 548F036-120 18 549B036-120 67 EconoMi$er 548F036-120 53 549B036-120 89 Changeover, heating to cooling 14 Controls 10-14 Convenience outlet 7,106 Cooling capacities 542J150,180 109 548F036-120 26-28 549B036-120 75,76 Dimensions Accessory 542J150,180 105-107 548F036-120 23,24 549B036-120 72,73 Base unit 542J150,180 104 548F036-120 21,22 549B036-120 70,71 Ductwork 14 Economizer 6,14,53,89 Electric heating capacities 542J150,180 113 548F036-120 54 549B036-120 90 Electrical data 542J150,180 114 548F036-120 56-64 549B036-120 91-94 Fan performance 542J150,180 111,112 542J150,180 with horizontal adapter 113 548F036-120 32-51 549B036-120 80-87 Fan RPM at motor pulley settings 542J150,180 112 548F036-120 52 549B036-120 88 Features/Benefits 1-3 Glycol coil 7,113 Guide specifications 542J150,180 118-121 548F036-120 97-100 549B036-120 97-100 Horizontal adapter 106,113 Heating ratings Instantaneous and integrated heating ratings 548F036-120 28-31 549B036-120 77-79 Integrated heating ratings 542J150,180 110

Indoor fan motor performance 542J150,180 114 548F036-120 55 549B036-120 89 Internal unit design 14 Minimum ambient cooling operating temperature 14 Model number nomenclature 542J150,180 101 548F036-120 18 549B036-120 67 Multiplication factors 542J150,180 54 548F036-120 54 549B036-120 90 Non-fused disconnect 542J150,180 7,107 Options and accessories 4-9 Outdoor sound power 549B036-120 90 Outdoor installation 14 Performance data 542J150,180 109-114 548F036-120 26-55 549B036-120 75-90 Physical data 542J150,180 102,103 548F036-120 19,20 549B036-120 68,69 Piping and wiring 542J150,180 17 548F036-120 16 549B036-120 16 Power exhaust 542J150,180 107,112 548F036-120 53 549B036-120 89 With EconoMi$er 548F036-120 53 549B036-120 89 Roof Curb 542J150,180 105 548F036-072 23 548F090-120 24 549B036-072 72 549B090,120 73 Selection procedure 542J150,180 108 548F036-120 25 549B036-120 74 Static pressure drop 542J150,180 112 548F036-120 52 549B036-120 88 Thermostats 8,14 Thru-the-bottom power connections 14 Wiring schematic 542J150,180 115-117 548F036-120 65,66 549B036-120 95,96

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

Copyright 2002 Bryant Heating & Cooling Systems Printed in U.S.A. 1/02 Catalog No. 5254-804

Ask about the Bryant 549B

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bryant 549B

Be the first to ask — other owners or our team will answer.

Original document

Bryant 549B manual PDF

122 pages·3 MB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…