For use by the heating contractor

Please file in Service Binder
997692210VIEUS0x-mub-en – V01 05/2014 1



Carefully read this manual before installation and commissioning. Non-observance of the instructions in this manual may lead to serious material damage and serious injuries that may result in death.
Indicates that there is risk of death, serious injuries or considerable material damage if suitable safety precautions are not taken.
Indicates that there is a risk of light injuries if suitable safety precautions are not taken.
Keep this manual in close proximity of the system for later use.
Indicates that there is a risk of material damage if suitable safety precautions are not taken.
1.2 Designated use
This manual describes the function, installation, commissioning and operation of the solar stations Solar-Divicon DN25B. The chapters called [specialist] are only addressed to installation contractors.
The solar station is a pre-assembled fitting assembly checked for tightness and used for recirculating the solar fluid in a closed loop solar circuit. The solar station must only be used in solar thermal systems as pumping station in the solar circuit, taking into consideration the technical limit values indicated in this manual. The station may only be assembled indoors. The station must be assembled and operated as described in this manual!
For other components of the solar installation, such as collectors, storage tanks, expansion tanks, and controllers, please refer to the instructions of the corresponding product.
Unintended use of the solar station will invalidate any liability claims.
Only use accessories from Viessmann.
The wrapping materials are made of recyclable materials that can be recycled by standard recycling operations.
Installation and commissioning of this equipment should be done by qualified installers [specialist] in accordance with local, state, provincial, and federal codes which may be applicable.
The following must also be observed during installation and commissioning:
Relevant regional and national regulations (for
example Occupational Safety and Health Act)
Relevant accident prevention regulations (for
example of the Employer's Liability Insurance Association)
Instructions and safety instructions mentioned in
this manual
![Page 4 of the Viessmann Solar Divicon (DN25B) user manual — 1.4 Hand-over of the system [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-4.webp?w=400)
After installation and commissioning, the installer is responsible for familiarizing the end user with the functions of the system and the basic safety measures.
After commissioning, fill in the log on the last page of
this manual. Hand the manual over to the end user and instruct
them to to keep the manual in close proximity to the system. Instruct the end user to have the solar station
serviced and repaired by a specialist only. The controller settings must not be changed by the customer. Explain to the end user the function of the system and
of the safety devices. Point out to the end user that the shell must remain mounted during operation and that the ball valves in the temperature gauges and flowmeter must always be open. 1.5 General safety instructions
Before installing and commissioning the product, you must read and observe the following safety instructions:
Personal injury and material damage caused by excess pressure! Closing both ball valves will disconnect the safety assembly from the heat exchanger. Heating the storage tank can result in the formation of high pressures, which may lead to material damage and personal injury! In operation, the ball valves with
collector temperatures are below 150 °F (70 °C). Connect a discharge line to the
safety assembly. Observe the instructions regarding the pressure relief valve. The pressures calculated by the
temperature gauges and the ball valve at the flowmeter must always be open. Close the ball valves only when
installation planner for the expansion tank and the operating pressure of the installation must be set prior to filling system
service is required.
Material damage due to mineral oils! Mineral oil products permanently damage the EDPM sealing elements, resulting in a loss of their sealing characteristics. We cannot be held liable for damage caused by seals thus damaged, nor will we offer a replacement under warranty. It is imperative to prevent the EPDM sealing
Risk of burns! The valves, fittings and the pump may heat up to more than 212 °F (100 °C) during operation.
The shell must remain closed during
operation.
elements from making contact with substances containing mineral oils. Use silicone- or polyalkylene-based lubricants free of
mineral oil, such as Unisilikon L250L and Syntheso Glep 1 from the company Klüber or a silicone spray

Only use solar fluid specified in the Vitosol Collector Installation Manuals and the Vitosol Operating and Service Instructions.
Also refer to these manuals to determine the following:
Solar fluid fill pressure Fluid volume required to fill system pH testing Maintenance requirements.
Propylene glycol: Hazardous in case of ingestion!
Propylene glycol is hazardous in case of ingestion. It is irritant in case of eye or skin contact.
Wear chemical resistant protective gloves and safety
glasses with side-shields when handling propylene glycol mixtures.
Observe the instructions of the antifreeze
manufacturer.
It often happens that solar thermal systems cannot be completely drained after flushing. Thus, there is a risk of frost damage when flushing with water. Therefore, the solar thermal system should only be flushed and filled with the solar fluid used later on.
All components in the solar station are resistant to a percentage of propylene glycol of up to 50%.


The solar station is mounted on a wall support and held by clip springs. The station contains important valves, fittings and safety equipment for operating a solar thermal system:
1.1 Return to the collector field
1.2 Ball valve with temperature gauge in the return equipped with replaceable spindle (blue)
1.3 Pressure relief valve, 87 psi (6 bar)
1.4 Fill valve
1.5 Connection for the expansion tank
1.6 Pressure gauge 87 psi (6 bar)
3.1 Ball valve in flowmeter
3.2 Drain valve
3.3 Flowmeter

3.4 Return from the storage tank
4.1 Supply to the storage tank
4.2 Airstop equipped with manual bleeder
5.2 Ball valve with temperature gauge in the supply equipped with replaceable spindle (red)
5.1 Supply from the collector field
2 Solar pump · Assembly example

The solar station may only be installed indoors with a power supply of 120 V / 60 Hz. The installation site must be dry, stable and frost-free.
Material damage due to high temperatures!
Since the solar fluid may be very hot near the collector, the fitting assembly must be installed at a sufficient distance from the collector field.
It may be necessary to install an upstream tank, in order to protect the expansion tank
![Viessmann Solar Divicon (DN25B) — 3 Assembly and installation [specialist] diagram (page 7)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-5.webp)

level the unit. Mark the mounting hole locations
(next to the temperature gauges) onto the mounting
surface.
the solar station to the wall by means of the
enclosed screws and, if required, the enclosed wall
anchors.
![Page 8 of the Viessmann Solar Divicon (DN25B) user manual — 3 Assembly and installation [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-8.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 3 Assembly and installation [specialist] diagram (page 8)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-7.webp)
All pipe connections are designed as cutting-ring compression fitting 1" copper pipe. Pipe size can be reduced to ¾” copper if required.
![Viessmann Solar Divicon (DN25B) — 3 Assembly and installation [specialist] diagram (page 8)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-8.webp)
Assembly of the cutting-ring compression fitting:
Push the union nut ② and the cutting ring ③ onto the 1” copper
pipe ①. The pipe must protrude at least ⅛" (3 mm) from the cutting ring in order to ensure the force transmission and the sealing.
Insert the support sleeve ④ into the copper pipe.
Insert the copper pipe with the plugged-on individual parts (②, ③
and ④) all the way into the housing of the cutting-ring fitting ⑤.
First tighten the union nut ② manually.
Tighten the union nut ② by rotating it by one full turn.
Secure the housing of the cutting-ring fitting ⑤ against distortion in order to avoid damaging the sealing ring.
![Viessmann Solar Divicon (DN25B) — 3 Assembly and installation [specialist] diagram (page 8)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-9.webp)
![Page 9 of the Viessmann Solar Divicon (DN25B) user manual — 3 Assembly and installation [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-9.webp?w=400)
Risk of electric shock!
Prior to commencing electrical work, disconnect the main power supply!
Only after completing all installation work, flushing and filling should the mains plug be plugged
into an outlet! This avoids an unintentional start of the pump motor.
Wiring can run in the slots in the back foam insulation panel of the solar station.
Observe all local electrical code requirements.
120V power supply connection
The assembly of the solar station is now complete, and you can commission the station.
Electric cable slots
![Page 10 of the Viessmann Solar Divicon (DN25B) user manual — 4 Commissioning [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-10.webp?w=400)
Before commissioning the solar station, you must read and observe the following safety instructions:
Risk of burns and scalding!
Propylene glycol: hazardous in case of ingestion!
The valves and fittings may heat up to more than 212 °F (100 °C). During flushing, filling and venting, the solar fluid can escape as vapor and result in scalding.
Propylene glycol is hazardous in case of ingestion. It is irritant in case of eye or skin contact.
Wear chemical resistant protective gloves and safety
glasses with side-shields when handling propylene glycol mixtures.
Flush and fill the system only if the
Observe the instructions of the antifreeze
collector temperatures are below 150 °F (70 °C).
manufacturer.
It often happens that solar thermal systems cannot be completely drained after flushing. Thus, there is a risk of frost damage when flushing with water.
When commissioning the system, first fill the storage
circuit and then the solar circuit. This guarantees that any absorbed heat can also be dissipated.
Therefore, the solar thermal system should only be
flushed and filled with the solar fluid used later on.
Use a water and propylene glycol mixture with max.
50% of propylene glycol as solar fluid, in order to avoid damaging the seals.
Risk of frost!

The fill and drain connections required for flushing and filling have been integrated into the solar station.
In order to flush any dirt particles that may still be present out of the system, use only flush and fill stations equipped with suitable micro filters.
Ball valve with integrated check valve
(Normal direction of flow in the picture: downstream)
![Viessmann Solar Divicon (DN25B) — 4.1 Flushing and filling the solar circuit [specialist] diagram (page 11)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-10.webp)
![Viessmann Solar Divicon (DN25B) — 4.1 Flushing and filling the solar circuit [specialist] diagram (page 11)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-11.webp)
![Viessmann Solar Divicon (DN25B) — 4.1 Flushing and filling the solar circuit [specialist] diagram (page 11)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-12.webp)
Check valve in operation, through-flow in flow direction only (normal operating position).
Check valve not in operation, through-flow in both directions (use this positioning to help purge air during intial commissioning).
Ball valve closed, no through-flow (service postion).
0° 45° 90°
![Page 12 of the Viessmann Solar Divicon (DN25B) user manual — 4.1 Flushing and filling the solar circuit [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-12.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 4.1 Flushing and filling the solar circuit [specialist] diagram (page 12)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-13.webp)
The airstop with manual bleeder is used to bleed the solar thermal system. To ensure a perfect ventilation of the solar circuit, the flow velocity must be at least 0.3 m/s in the supply.
The air liberated from the solar fluid is collected in the upper area of the airstop and can be discharged via the vent plug [4.2].
Venting the solar thermal system after commissioning
Immediately after installation, vent the solar thermal system daily and then weekly or monthly, depending on the vented air quantity. This ensures optimum operation of the solar thermal system. Check the system pressure after venting and increase it to the prescribed operating pressure, if necessary.
Airstop
![Page 13 of the Viessmann Solar Divicon (DN25B) user manual — 4.3 Flushing and filling [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-13.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 4.2 Preparation for flushing [specialist] diagram (page 13)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-14.webp)
The solar circuit is flushed in the direction of flow.
![Viessmann Solar Divicon (DN25B) — 4.2 Preparation for flushing [specialist] diagram (page 13)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-15.webp)
![Viessmann Solar Divicon (DN25B) — 4.3 Flushing and filling [specialist] diagram (page 13)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-16.webp)
Compact mobile charging cart for flushing,
filling and purging the solar circuit
![Page 14 of the Viessmann Solar Divicon (DN25B) user manual — 4.2 Preparation for flushing [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-14.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 4.2 Preparation for flushing [specialist] diagram (page 14)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-17.webp)
![Viessmann Solar Divicon (DN25B) — 4.2 Preparation for flushing [specialist] diagram (page 14)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-18.webp)
Check the pressure on the pressure relief valve
(87 psi/6 bar)!
![Page 15 of the Viessmann Solar Divicon (DN25B) user manual — 4.4 Setting the solar loop flowrate [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-15.webp?w=400)
Risk of electric shock!
Check if the sensors and the pump are properly connected to the controller and if the controller
housing is closed. Only then should the mains plug of the controller be plugged into an outlet.
11. Connect the controller (to be provided on site) to the power supply and set the solar circuit pump in the manual mode to ON as described in the controller manual. Run the solar circuit pump at maximum rotation speed for at least 15 minutes. In the meantime, vent the solar thermal system several times at the vent plug of the airstop until the solar fluid escapes without forming bubbles (see page 12). If necessary, increase the system pressure to the operating pressure again.
![Viessmann Solar Divicon (DN25B) — 4.4 Setting the solar loop flowrate [specialist] diagram (page 15)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-19.webp)
![Viessmann Solar Divicon (DN25B) — 4.4 Setting the solar loop flowrate [specialist] diagram (page 15)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-20.webp)
![Viessmann Solar Divicon (DN25B) — 4.4 Setting the solar loop flowrate [specialist] diagram (page 15)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-21.webp)
Reading edge = Upper edge of the floating body
Refer to “Vitosol Operating and Service Instructions”) for the correct adjustment of the flow rate.
Correct · Incorrect
![Page 16 of the Viessmann Solar Divicon (DN25B) user manual — 6 Maintenance and decommissioning [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-16.webp?w=400)
The valves, fittings and the pump may heat up to more than 212 °F (100 °C) during operation.
The shell must remain closed
when cleaning.
Clean the solar station only from the outside with a damp cloth. Never use scouring or sand-containing cleaning agents.
Before maintaining and decommissioning the product, you must read and observe the following safety instructions:
Risk of electric shock!
Risk of burns and scalding!
Disconnect all electrical devices in
The valves and fittings may heat up
the heating circuit from the power supply before carrying out maintenance work or decommissioning!
to more than 212 °F (100 °C). During maintenance or decommissioning, the solar fluid may escape as vapor and result in scalding!
Secure the electrical devices
Flush and fill the system only if the
against being switched on again.
collector temperatures are below 122 °F (50 °C).
Wait until the solar fluid has cooled
down to 122 °F (50 °C).
Risk of burns!
![Page 17 of the Viessmann Solar Divicon (DN25B) user manual — 6.2 Complete draining of the solar installation [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-17.webp?w=400)
Partial draining allows components in the station below the ball valves (5.2 and 1.2), for example the pump, to be replaced, without having to drain the collector array and piping.
![Viessmann Solar Divicon (DN25B) — 6.1 Partial draining of the solar installation [specialist] diagram (page 17)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-22.webp)
secure it against being switched on again.
valve [5.2|1.2] by rotating them to the 90° position
(90°, see page 11).
Make sure that the solar fluid is collected in a heat-
resistant container.
close it again (see 12).
The escaping solar fluid can be very hot.
Position and secure the heat-resistant collecting container such that persons nearby and the
environment are not put at risk when the solar thermal system is drained.
Complete draining enables replacement of the solar fluid, dismounting of the solar station and replacement of seals above the ball valves (5.2 and 1.2).
![Page 18 of the Viessmann Solar Divicon (DN25B) user manual — 6.4 Replacing the gaskets in the solar station [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-18.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 6.3 Replacing the pump [specialist] diagram (page 18)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-23.webp)
![Page 19 of the Viessmann Solar Divicon (DN25B) user manual — 6.5 Dismounting [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-19.webp?w=400)
![Viessmann Solar Divicon (DN25B) — 6.5 Dismounting [specialist] diagram (page 19)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-24.webp)
![Viessmann Solar Divicon (DN25B) — 6.5 Dismounting [specialist] diagram (page 19)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-25.webp)
![Viessmann Solar Divicon (DN25B) — 6.5 Dismounting [specialist] diagram (page 19)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-26.webp)
![Viessmann Solar Divicon (DN25B) — 6.5 Dismounting [specialist] diagram (page 19)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-27.webp)
![Viessmann Solar Divicon (DN25B) — 6.5 Dismounting [specialist] diagram (page 19)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-28.webp)
![Page 20 of the Viessmann Solar Divicon (DN25B) user manual — 7 Application range of the check valves [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-20.webp?w=400)
Within their application range, the two check valves in the solar station prevent unwanted gravity circulation. The efficiency of the check valves depends on:
the installation height the temperature difference between the storage tank and the collector the type of heat transfer medium
In the diagram below you can see whether the check valves integrated in the stations are sufficient . If the check valves are not sufficient, you need to install additional components to prevent gravity circulation. You can mount components such as syphons ("heat traps"), 2-way valves (zone valves) or additional check valves.
Example:
You would like to install a Solar-Divicon solar station. The station comprises two check valves, 2 x 7.9 inch head = 15.8 inch head (2 x 200 mm wc = 400 mm wc).
You use a mixture of water and 40% of propylene glycol as a solar fluid. The installation height between the collector and the storage tank is ~33 ft (10 m).
![Viessmann Solar Divicon (DN25B) — 7 Application range of the check valves [specialist] diagram (page 20)](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/rimg-29.webp)
Installation height in ft
Temperature difference storage tank/collector in °R Result:
The check valves prevent gravity circulation up to a temperature difference of about 112 °R (~62 K). If the temperature difference between the collector and the tank is larger, the difference in density of the solar fluid will be so large, that the check valves are pushed open.
The density of the solar fluid decreases with rising temperature. In high installations with large temperature differences, the difference in density will cause gravity circulation. This circulation can cool down the storage tank
*Solar fluid = mixture of water and 40% glycol
![Page 21 of the Viessmann Solar Divicon (DN25B) user manual — 8 Spare parts [specialist]](/cdn/reader/00/003b5308633056fefc534fadcef4c7efb06f04170cee8e13f718a7cae1d39685/images/page-21.webp?w=400)

Total width 12.1" (307 mm)
Depth 6.3" (160 mm)
Center distance supply/return 3.94" (100 mm)
Pipe connections 1" cutting-ring compression fitting
Connection for the expansion tank ¾" female thread, NPT
Outlet of pressure relief valve ¾" female thread
Max. operating temperature 248 °F (120 °C)
Short-term load 320 °F (160 °C) < 15 minutes
Max. propylene glycol content 50 %
Pressure gauge 0-87 psi (0–6 bar)
Check valves 2 x 7.9 inch head (2 x 200 mm wc), can be opened Flowmeter 1 - 10 USgpm (4-38 lpm)
Solar loop pump Wilo Star 30U-25
Insulation EPP, = 0.043 W/(m K)



Gaskets EPDM · Check valves Brass


Pressure loss - ft of head
Flow rate - USgpm
Solar-Divicon DN25B

Collectors (number / type)
Collector surface area ft²
System height ft. (Height difference between
station and collector field)
Pipeline ⌀ = in l = ft
Ventilation (collector field) ⃞ Manual bleeder ⃞ Automatic bleeder
⃞ No ⃞ Vented
Airstop (station) ⃞ Vented
Solar fluid (type) % of glycol
Controller Pump stage (I, II, III)
Software version Expansion tank (type)

Pressure relief valve ⃞ Checked
Check valves ⃞ Checked
Installation company Date, Signature


Job: Engineer: Contractor: Rep:
ITEM NO. MODEL NO.
Features:

All medium-carrying parts are made of
For use in closed loop design only. The
solar station is used on the primary loop of
1" cutting-ring compression fittings
solar thermal systems to control the
Fully pre-assembled on steel wall
temperature in the hot water storage tank.
support, quick and easy to mount on
This station contains the functional and
the wall due to stable snap-lock
safety devices for optimum circuit control.
technology Two ball valves with brass check
The components enable:
valves (7.9 inch head / 200 mm wc)
Medium circulation with solar pump
and spindle exchangeable under

Safety against pressure increase
Exact flow rate control
Flushing, filling and draining the circuit
integrated into the ball valve with
Measuring the supply and return
Flowmeter 1-10 USgpm or 5-40 l/min
Deaerating the solar loop
Shutting off the circuits
Safety assembly with pressure relief
Thermal insulation of the components
valve 87 psi / 6 bars, pressure gauge
and connection for expansion tank
Airstop with manual bleeding for
venting the solar circuit, flush and fill
Total height 19.6" / 498 mm
Total width 12.1" / 307 mm Depth 6.3" / 160 mm

Center distance, supply/return 3.94" /100 mm
Pipe connections 1" compression fitting
Max. operating temperature 248 °F / 120 °C
Max. propylene glycol content 50%
Valves and fittings Brass
Insulation EPP, = 0.043 W/(m K) Flow rate [US gpm]
Viessmann products specified in Imperial or metric units are approximate and are provided for reference only. For precise measurements, please contact Viessmann Technical
Service.
Viessmann reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such
changes and modifications on Viessmann products previously or subsequently sold .

Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario, N2V 2G5, Canada TechInfo Line: 1-888-484-8643 1-800-387-7373, Fax (519) 885-0887 www.viessmann.ca [email protected]
Viessmann Manufacturing Company (U.S) Inc. 45 Access Road Warwick, Rhode Island, 02886, USA TechInfo Line: 1-888-484-8643 1-800-288-0667, Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com
5516 057 - 01 05/2014