MCS-THERMOSTAT
www.mcscontrols.com


MCS Total Solution for all your Control Needs Energy Efficient and RoHS Compliant

Revsion 2021-06-04

Micro Control Systems, Inc.
5580 Enterprise Parkway Fort Myers, Florida 33905 PH:(239) 694-0089 FAX:(239) 694-0031
All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc. No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others outside your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees, agents, and other personnel that may have access to this document. Copyright ©2021


The MCS-THERMOSTAT’S interface allows the viewing of 17 different parameters and has the ability to adjust 9 settings, including cooling & heating set points, operational schedules, holiday schedules, calibration and password protection.

Enter Confirms changes and adjustments.
Menu Access the primary menu.
Override Permits override Room is occupied Room is unoccupied.
The primary means of cycling through the thermostat’s options, menus, and settings- press the up button or down buttons to cycle thru the options.
Selection Up Button · Selection Down Button

The LCD screen displays seven icons reporting operational mode, current status and alarms.
Unit is in HEATING mode Unit is in COOLING mode Unit is in DEHUMIDIFICATION
Indicates position of outside Air Damper
An ALARM is ACTIVE
Indicates Speed of FAN (Low, Medium, High)

Display shows current views, OCCUP (Occupied) UNOCCUP (Unoccupied) OVERRIDE
Display shows day of week, MO, TU, WE, TH, FR, SA, SU & HD (Holiday)
Display shows current sensor value and current Set Point
Thermostat is LOCKED


The MCS-THERMOSTAT is powered by a +5vdc supply from an MCS controller via a two wire connection that can be wired with the communication network cabling. Improper wiring or installation may damage the thermostat. Wiring must conform to local and national electrical codes.
Before installing the thermostat, turn off all power to the unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
BY AIR FROM NEARBY DUCT WORK, ELECTRONIC EQUIPMENT, ETC.


Use 4 wire 22 to 20 awg Shielded Cable for installation. The MCS-THERMOSTAT can be installed up to 1000 feet from the MCS CONTROLLER.

MCS recommends you install the MCS-THERMOSTAT utilizing a J-Box. Prior to installing the MCS-THERMOSTAT punch out the corresponding mounting holes on the MCS-THERMOSTAT housing based on the J-box you are utilizing.



International Style Junction Box
USA Style Junction Box

Puncture a small hole in the grommet on the back side of the thermostat. You want the wires to be tight so no air passes through affecting the thermostat’s reading.
Push the output wires from the MCS Controller through the rear hole of the MCS-THERMOSTAT’S mounting plate. It may be good practice to wait until the wires are in position to be attached to the
MCS-THERMOSTAT before they are stripped or cut with a tool.

Using a ¼” Phillips screwdriver, insert one of ¼” machine screws into one of the mounting slots depending on the J-box you are utilizing and tighten the screw to hold the mounting wall plate into position.
Screw the second ¼” machine screw into the lower mounting slot to secure the wall plate.
International

6.1. Rev. 6.0 (or less) 24VAC, 115VAC and 230VAC
Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.
MicroMag I/O port (located on top of board as shown below)

5 Sensors available Power for Thermostat (can be wired to any empty sensor)
Enlarged view of Thermostat block wiring

6.2. Rev. 6.1 - 24VAC, 115VAC AND 230VAC
Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.
MicroMag I/O port (located on right of board as shown below)

5 Sensors available Power for Thermostat (can be wired to any empty sensor)
first and last boards on the network
Enlarged view of Thermostat block wiring

6.3. Rev. 7.0 - 12 VOLT SYSTEMS

Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.

Use ‘UP’ ‘DOWN’ and ‘ENTER’ BUTTON TO MOVE BETWEEN SETTINGS
7.1. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)
7.1.2 Units Degrees (F) Or (C)
7.1.3 Auth Level Setup
SEE NEXT PAGE FOR DESCRIPTIONS
7.1.4 Sound Alarm Stat
OF MENU ITEMS AND AN EXAMPLE OF AUTHORIZATIONS LEVELS
7.1.6 Standby Backlight
7.1.7 Exit Setup Menu
7.2. MAIN
7.2.1 Unit Status
*NOTE: SOME MENU OPTIONS MAY NOT SHOW ON YOUR THERMOSTAT LCD SCREEN.
7.2.3 Last Alarm
THESE SELECTIONS MAY NOT BE SETUP IN THE CONFIGURATION FILE FOR YOUR CONTROLLER.
7.2.5 Show Version Number
7.2.6 Cool Target
7.2.7 Unit (Run/Stop) *
AFTER LAST SELECTION HAS BEEN MADE
CLICK ON ‘MENU” TO RETURN TO THE
7.2.8 Enter Password
‘UNIT STATUS SCREEN’
7.2.9 Config Menu
7.3. CONFIG MENU
7.3.1 Auth Level Setup
**SUPPLY TEMP IS ONLY AVAILABLE IN THE MICROMAG CONFIG SETTINGS IF AVAILABLE
SEE THERMOSTAT CONFIG MENU SETUP
7.3.4 Thermostat Reset
ON HOW TO LOAD
7.3.5 Adjust Date & DOW
7.3.6 Adjust Time
7.3.7 Standby Backlight
7.3.8 Adjust Backlight
7.3.9 Display Test
7.3.10 Temp Cal
7.3.11 Modify Holidays
CLICK ON THERMOSTAT RESET
7.3.12 Modify Schedules
PRESS ENTER TO UPDATE. THE THERMOSTAT WILL REBOOT AND LOCK

ADDITIONAL CHANGES CAN BE MADE USING THE CONFIG MENU AFTER THE ‘INITAL SETUP’
Net Address:
AT THIS POINT, YOU SHOULD HAVE WIRED THE THERMOSTAT TO THE MICROMAG OR MAGNUM controller. Turn power on to the MicroMag or MAGNUM, Thermostat will power up and enter the ‘SETUP MENU’. The following items will appear in the setup menu:
The Thermostat is factory set to Network address one (1) This cannot be changed.
Allows the user to choose between Celsius and Fahrenheit. Directions: Use the Up/Down arrows to move between Celsius and Fahrenheit. Press ‘Enter’ to select the desired unit degrees and the display will confirm the change.
The user will be able to see all functions of the thermostat if the controller’s configuration file is setup to allow this. Some functions of the thermostat may be turned off in the configuration file to help protect unauthorized users from making changes.
Authorization Levels- The MicroMag and MAGNUM allow several levels of password protection that have been setup in your thermostat - ‘Service’, ‘Supvsr’ (Supervisor), and ‘Factory.’
The Installer can setup the Authorization Levels at this time. This will allow a user with the correct password to make changes.
OPERATION OF THE THERMOSTAT CAN BE CONTROLLED BY THESE LEVELS OF AUTHORIZATION. SEE EXAMPLE NEXT PAGE
Occup

SAMPLE TO SHOW HOW TO USE AUTHORIZATION LEVELS FOR THE THERMOSTAT

Modify Schedule and 24 hour clock NO YES YES YES
AS SHOWN IN THE ‘SAMPLE’ ABOVE AUTHORIZATION LEVEL ‘VIEW’ (DEFAULT) WILL HAVE THE LOWEST LEVEL OF ACCESS TO THE THERMOSTAT WHEREAS AUTHORIZATION LEVEL ‘FACTORY’ WILL HAVE THE HIGHEST AUTHORIZATION FOR MAKING CHANGES TO THE THERMOSTAT.
YOU CAN SET UP THE AUTHORIZATION LEVEL FOR EACH SELECTION SHOWN IN THE ‘CONFIG’ MENU SO A USER WILL BE LIMITED AS TO WHAT CHANGES THEY CAN MAKE.
Hit ‘ENTER’ - Allows the user to turn alarm on or off.
Allows the user to adjust the backlight setting from 25% to 100%.
Hit ‘ENTER’ - Allows user to make changes to the backlight - OFF or 25% to 100%
Press ENTER to exit the SETUP menu, all changes made in the SETUP settings will be saved in the MCS-THERMOSTAT non volatile flash memory.
YOUR THERMOSTAT IS SETUP AND READY FOR USE. ADDITIONAL CHANGES CAN BE MADE USING THE CONFIG MENU
Setup (continued)

CLICK ON MENU TO SEE THE SCREENS BELOW AUTHORIZATION PASSWORD LEVEL MAY BE REQUIRED
Hit ‘ENTER’ shows status of thermostat.
Hit ‘ENTER’ - Allows user to enter Config Menu to make adjustment to the thermostat.
Hit ‘ENTER’ - Authorization password level for the changes to the thermostat.
Hit ‘ENTER’ - Allows user to ‘RUN/STOP’ the unit controlling the thermostat. (This must be confiured in your controller for viewing on your thermostat).
Hit ‘ENTER’ - Allows the user to SET THE COOL SET POINT FOR THE AREA.
Hit ‘ENTER’ - Allows the user to SET THE HEAT SET POINT FOR THE AREA.
Hit ‘ENTER’ - Allows the user to SET THE HUMIDITY SET POINT FOR THE AREA.
Hit ‘ENTER’ - Allows the user to SET THE C02 SET POINT FOR THE AREA.
Hit ‘ENTER’ - Shows current version of firmware the thermostat is using.
Hit ‘ENTER’ - Shows current time and date of unit operating thermostat.
Displays abbreviations for the last three alarms on the first screen before flashing to a second screen displaying the time/date of respective alarm.
For example, in a displayed ‘LO DIS PSI’ alarm listing, the user interface would switch to a screen displaying ‘Jan 31 12:10’ as the occurrence time for the first ‘LO’ alarm before jumping back to the ‘LO PSI LO’ alarm display and switching to a screen displaying ‘Feb 2 12:10’ as the occurrence time for the second ‘PSI’ alarm.
Hit ‘ENTER’ - Allows used to reset lockout if authorized.

MENU
CLICK ON MENU - USE DOWN BUTTON TO SEE THE CONFIG MENU
AUTHORIZATION PASSWORD IS REQUIRED
Authorization Levels- The thermostat allows three levels of passwords - Service, Supervisor, and Factory.
10.2. ZONE OR SUPPLY TEMP (ONLY ON MICROMAG FIRMWARE VER 2.00E and MicroMag Config 18.00N and up)
Hit ‘ENTER’ - Allows the user to change between showing ‘ZONE TEMP’ or ‘SUPPLY TEMP’ if “SUPPLY TEMP’ is used.
Hit ‘ENTER’ -Allows the user to change between Celsius and Fahrenheit. Directions: Use the Up/Down arrows to move between Celsius and Fahrenheit. Press ‘Enter’ to select the desired unit degrees and the display will confirm the change.
Unlike Thermostats that are used at home and in an some office buildings, the MCS Thermostat ‘SCHEDULES’ control the run/stop of the controller’s cool target and heat target setting only.
Think of the Thermostat ‘SCHEDULES’ as controlling whether a building or room is ‘OCCUPLIED or ‘UNOCCUPLIED’. We can still allow the building or room to be cooled or heated, but with target setting, we can lower (or raise) the temperature depending on whether the building or room is ‘OCCUPLIED’.
For example if you set ‘SCHEDULE ONE’ to start at 8:00am the thermostat will start either the cooling process or heating process of the unit based on the cooling/heating targets that you have setup in the Thermostat or configuration of the controller. Setting ‘SCHEDULE ONE’ to end at 17:00 (5:00pm) the Thermostat can change how the building or room is heated or cooled.

The advantage of the MCS Thermostat is that you can override the target settings of the UNIT’S heating, cooling and humidity from the thermostat without the going to the actual unit. See an example of setting up the schedules and holidays on the next pages.
Schedule setting start with Sunday as the first day.
4. The next screen display will show the Hour ‘BLINKING’ - enter the hour, press ‘ENTER’ to move to the minutes. After you set the minutes, press ‘ENTER’ to accept, the following screen will appear ‘Prs Enter to continue’. The information will be sent to the controller. 5. Be sure to set the ‘START and ‘END TIMES’ for each day for ‘SCHEDULE 1’ and for ‘SCHEDULE 2’ before proceeding to the next day on the Thermostat. 6. IF YOU DO NOT SEE THE ‘HOUR BLINKING’ YOU FORGOT TO PRESS ENTER FOR THE NEXT SCHEDULE DAY.
00 : 01
FOR 24 HOUR
23 : 59
OPERATION
Sun Set Schedule 1 Start
Sun Set Schedule 1 End
Below is a screen shot from MCS-CONNECT showing what the schedule settings look like in the configuration setup. Basically this is what you are setting up when you are setting the ‘SCHEDULES and HOLIDAYS’ times in the Thermostat.
These settings allows the user to adjust the thermostat’s “START and END’ times for holidays that

ARE SETUP IN
MCS-CONNECT
Occup · Occup

have been setup in the configuration file or thru MCS-CONNECT. Press the Up/Down arrows and Enter buttons to make adjustments. See screen shot on previous page as an example.
Allows the user to make changes to the temperature setting of the Thermostat using a calibrated hand held temperature meter to check the current temperature of the area.
Directions: Use the Up/Down arrows to move between the offset range. Press ‘Enter’ to select the desired temperature offset and the display will confirm the change.
Allows the user to make changes to the humidity setting of the Thermostat using a calibrated hand held meter to check the current humidity of the area.
Directions: Use the Up/Down arrows to move between the offset range. Press ‘Enter’ to select the desired temperature offset and the display will confirm the change.
Allows the user to test the thermostat to make sure all icons are working.
Allows the user to adjust the backlight setting from 25% to 100%.
Hit ‘ENTER’ - Allows user to make changes to the backlight - OFF or 25% to 100%
Allows the user to change the displayed time from the MCS-THERMOSTAT. Directions: Use the Up/Down arrows and Enter button to first adjust the hour per a 24-hour schedule (ex. 1:00am is 0100 and 1:00pm is 1300) and press ‘Enter’ to move on to the minutes. After adjusting the minutes, press ‘Enter’ to move on to the seconds. Press ‘Enter’ to complete the time adjustment.
Allows the user to change the displayed date from the MCS-THERMOSTAT.
Hit ‘ENTER’ to update-’RESTARTING THE UNIT’ (THIS RE LOCKS THE THERMOSTAT)
Hit ‘ENTER’ - Allows the user to turn alarm on or off.

11.1. MCS-Thermostat firmware upload
Loading new ‘Firmware’ to the Thermostat (requires proper authorization)
Consult support@mcscontrols.com for upgrading your Thermostat firmware and acquiring the necessary TERMINAL BLOCK CABLE TO ATTACH TO THERMOSTAT.




Cable with terminal block

Enlarged view of Thermostat block wiring






Check to make sure you have the wiring correct to the Thermostat (see wiring in beginning of this install guide). Check to see that the Thermostat and Controllers are Terminated correct. In MCS-CONNECT or Keypad, check to see if the baud rate is correct(38,400)
THERMOSTAT WILL NOT TURN ON OR COMMUNICATE WITH THE CONTROLLER
MCS-THERMOSTAT remains in locked mode until the proper password is entered. Press the Menu button until you see Password - press enter, than your first password number - press enter until the correct password has been entered. LOCKED ICON SHOULD SHOW UNLOCKED. Password Code will lock back in 2 minutes
THERMOSTAT HEATING AND COOLING IS NOT CORRECT TO ROOMS CONDITIONS
Check the Setting Menu to make sure you have the proper Unit Degrees chosen - Celsius or Fahrenheit.. Reset the Temp Calibration using the Config Menu to adjust for tempera- ture variations.
To make sure all of your Thermostats Icons are working - Press Menu to get to the Config Menu using the up/down arrows until you see Display Test- press enter - all icons should show on the screen.
THERMOSTAT NOT WORKING- SHOWS UNOCCUPIED OVERRIDE BUTTON ON LEFT SIDE OF UNIT IS SET TO UNOCCUPIED.
Max. LOCKOUTS PER DAY Reset Lockouts – Does require being authorized. However only a limited number of Lockouts(6) can be reset in one day without a higher authorization level.
THERMOSTAT STAYS IN HEAT- ING OR COOLING MODE AND WON’T CHANGE
Check your Cooling and Heating Set Points - consult HVAC Technician
TO DISABLE THE CURRENT PASSWORD - AT THE MENU LEVEL, PRESS MENU UNTIL YOU SEE ENTER PASSWORD. ENTER A PASSWORD THAT IS NOT USED BY THE SYSTEM TO RELOCK THE UNIT SO UNAUTHORIZED CHANGES CANNOT BE MADE.


1-12-15 DEW Edits made as per Brian, setting menu\
6-01-15 DEW Edits made to wiring and setup config
12-2/3-15 DEW Add run/stop feature, add new MicroMag board to wiring
03-10-21 DEW Change to Rev. 1.6 - add 12 volt wiring
04-08-16 DEW Add wiring and distance on installation page
The MCS Commitment is to provide practical solutions for the industries
needs and to be both a leader and partner in the effective use of
Microprocessor controls.
Micro Control Systems, Inc.
5580 Enterprise Parkway Fort Myers, Florida 33905 PH:(239) 694-0089 FAX:(239) 694-0031
Revision Page


5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: (239) 694-0089
Fax: (239) 694-0031 www.mcscontrols.com