MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT)

24 pages·737 KB·Thermostat·PDF·ENDEFRITNLJA
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT)
Table of Contents 61 sections Bookmark 1 · Table of Contents · Chapter - 1. MCS Thermostat’s Interface · Chapter - 2. Thermostat’s Display (Display Test) · … ShowHide
Bookmark 1p.13Table of Contentsp.3Chapter - 1. MCS Thermostat’s Interfacep.5Chapter - 2. Thermostat’s Display (Display Test)p.6Chapter - 3. Icons Displayp.7Chapter - 4. Installationp.84.1. REQUIRED FOR INSTALLATIONp.84.2. MOUNTING LOCATIONp.84.3. WIRING AND DISTANCEp.8Chapter - 5. Installation - Mountingp.95.1. UTILIZING J-BOXp.95.2. PUNCTURE SMALL HOLEp.95.3. OUTPUT WIRESp.95.4. SCREWSp.9Chapter - 6. Wiring Instructions to MicroMagp.106.1. Rev. 6.0 (or less) 24VAC, 115VAC and 230VACp.106.2. Rev. 6.1 - 24VAC, 115VAC AND 230VACp.116.3. Rev. 7.0 - 12 VOLT SYSTEMSp.12Chapter - 7. Thermostat Menu Screensp.137.1. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)p.137.2. MAINp.137.3. CONFIG MENUp.13Chapter - 8. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)p.148.1. NETWORK ADDRESSp.148.2. UNITS DEGREESp.148.3. AUTHORIZATION LEVEL SETUPp.148.4. SOUND ALARM STATp.158.5. ADJUST BACKLIGHTp.158.6. STANDBY BACKLIGHTp.158.7. EXIT SETUP MENUp.15Chapter - 9. Main Menu Settingsp.169.1. UNIT STATUSp.169.2. CONFIG MENUp.169.3. ENTER PASSWORDp.169.4. UNIT STATUS (RUN/STOP)p.169.5. COOL TARGETp.169.6. HEAT TARGETp.169.7. HUMIDITY TARGETp.169.8. CO2 TARGETp.169.9. SHOW VERSION NUMBERp.169.10. TIME AND DATEp.169.11. LAST ALARMp.169.12. LOCKOUT RESETp.16Chapter - 10. Config Menu Settingsp.1710.1. AUTH LEVEL SETUPp.1710.2. ZONE OR SUPPLY TEMPp.1710.3. UNIT = DEGREESp.1710.4. MODIFY SCHEDULESp.1710.5. MODIFY HOLIDAYSp.1810.6. TEMP CALp.1910.7. HUMIDITY CALp.1910.8. DISPLAY TESTp.1910.9. ADJUST BACKLIGHTp.1910.10. STANDBY BACKLIGHTp.1910.11. ADJUST TIMEp.1910.12. ADJUST DATEp.1910.13. THERMOSTAT RESETp.1910.14. SOUND ALARMp.19Chapter - 11. Update Firmware on Thermostatp.2011.1. MCS-Thermostat firmware uploadp.20Chapter - 12. Troubleshoot Sectionp.22
Page 1 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 5580 Enterprise Pkwy. Fort Myers, FL 33905
Page 1 · click to enlarge
Page 1
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) diagram (page 1)
Fig. 1

Firmware 2.00E

Installation & Reference Guide

Version 1.7

5580 Enterprise Pkwy. Fort Myers, FL 33905

Office: 239-694-0089 Fax: 239-694-0031

MCS-THERMOSTAT

www.mcscontrols.com

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5580 Enterprise Pkwy. Fort Myers, FL 33905 diagram (page 1)
Fig. 2 · 5580 Enterprise Pkwy. Fort Myers, FL 33905
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5580 Enterprise Pkwy. Fort Myers, FL 33905 diagram (page 1)
Fig. 3 · 5580 Enterprise Pkwy. Fort Myers, FL 33905

MCS Total Solution for all your Control Needs Energy Efficient and RoHS Compliant

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5580 Enterprise Pkwy. Fort Myers, FL 33905 diagram (page 1)
Fig. 4 · 5580 Enterprise Pkwy. Fort Myers, FL 33905

Revsion 2021-06-04

Page 2 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual
Page 2 · click to enlarge
Page 2

Micro Control Systems, Inc.

5580 Enterprise Parkway Fort Myers, Florida 33905 PH:(239) 694-0089 FAX:(239) 694-0031

www.mcscontrols.com

All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc. No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others outside your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees, agents, and other personnel that may have access to this document. Copyright ©2021

Page 3 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Table of Contents
Page 3 · Contents
Contents

Contents

Bookmark 1p.13Table of Contentsp.3Chapter - 1. MCS Thermostat’s Interfacep.5Chapter - 2. Thermostat’s Display (Display Test)p.6Chapter - 3. Icons Displayp.7Chapter - 4. Installationp.84.1. REQUIRED FOR INSTALLATIONp.84.2. MOUNTING LOCATIONp.84.3. WIRING AND DISTANCEp.8Chapter - 5. Installation - Mountingp.95.1. UTILIZING J-BOXp.95.2. PUNCTURE SMALL HOLEp.95.3. OUTPUT WIRESp.95.4. SCREWSp.9Chapter - 6. Wiring Instructions to MicroMagp.106.1. Rev. 6.0 (or less) 24VAC, 115VAC and 230VACp.106.2. Rev. 6.1 - 24VAC, 115VAC AND 230VACp.116.3. Rev. 7.0 - 12 VOLT SYSTEMSp.12Chapter - 7. Thermostat Menu Screensp.137.1. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)p.137.2. MAINp.137.3. CONFIG MENUp.13Chapter - 8. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)p.148.1. NETWORK ADDRESSp.148.2. UNITS DEGREESp.148.3. AUTHORIZATION LEVEL SETUPp.148.4. SOUND ALARM STATp.158.5. ADJUST BACKLIGHTp.158.6. STANDBY BACKLIGHTp.158.7. EXIT SETUP MENUp.15Chapter - 9. Main Menu Settingsp.169.1. UNIT STATUSp.169.2. CONFIG MENUp.169.3. ENTER PASSWORDp.169.4. UNIT STATUS (RUN/STOP)p.169.5. COOL TARGETp.169.6. HEAT TARGETp.169.7. HUMIDITY TARGETp.169.8. CO2 TARGETp.169.9. SHOW VERSION NUMBERp.169.10. TIME AND DATEp.169.11. LAST ALARMp.169.12. LOCKOUT RESETp.16Chapter - 10. Config Menu Settingsp.1710.1. AUTH LEVEL SETUPp.1710.2. ZONE OR SUPPLY TEMPp.1710.3. UNIT = DEGREESp.1710.4. MODIFY SCHEDULESp.1710.5. MODIFY HOLIDAYSp.1810.6. TEMP CALp.1910.7. HUMIDITY CALp.1910.8. DISPLAY TESTp.1910.9. ADJUST BACKLIGHTp.1910.10. STANDBY BACKLIGHTp.1910.11. ADJUST TIMEp.1910.12. ADJUST DATEp.1910.13. THERMOSTAT RESETp.1910.14. SOUND ALARMp.19Chapter - 11. Update Firmware on Thermostatp.2011.1. MCS-Thermostat firmware uploadp.20Chapter - 12. Troubleshoot Sectionp.22
Page 5 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 1. MCS Thermostat’s Interface
Page 5 · click to enlarge
Page 5

Chapter - 1. MCS Thermostat’s Interface

The MCS-THERMOSTAT’S interface allows the viewing of 17 different parameters and has the ability to adjust 9 settings, including cooling & heating set points, operational schedules, holiday schedules, calibration and password protection.

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 1. MCS Thermostat’s Interface diagram (page 5)
Fig. 5 · Chapter - 1. MCS Thermostat’s Interface

Enter Confirms changes and adjustments.

Menu Access the primary menu.

Override Permits override Room is occupied Room is unoccupied.

The primary means of cycling through the thermostat’s options, menus, and settings- press the up button or down buttons to cycle thru the options.

Selection Up Button · Selection Down Button

Page 6 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 2. Thermostat’s Display (Display Test)
Page 6 · click to enlarge
Page 6

Chapter - 2. Thermostat’s Display (Display Test)

The LCD screen displays seven icons reporting operational mode, current status and alarms.

Unit is in HEATING mode Unit is in COOLING mode Unit is in DEHUMIDIFICATION

Indicates position of outside Air Damper

An ALARM is ACTIVE

Indicates Speed of FAN (Low, Medium, High)

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 2. Thermostat’s Display (Display Test) diagram (page 6)
Fig. 6 · Chapter - 2. Thermostat’s Display (Display Test)

Display shows current views, OCCUP (Occupied) UNOCCUP (Unoccupied) OVERRIDE

Display shows day of week, MO, TU, WE, TH, FR, SA, SU & HD (Holiday)

Display shows current sensor value and current Set Point

Thermostat is LOCKED

Page 7 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 3. Icons Display
Page 7 · click to enlarge
Page 7

Chapter - 3. Icons Display

Unit has an active alarm. Unit is in cooling mode. Unit is in dehumidification mode. LOW MED HIGHEvaporate fan is running (speed indicator low, medium, high). Unit is in heating mode. Outside air damper is closed. Outside air damper is open. Thermostat is locked-no changes allowed without Authorization. Up arrow key. Down arrow key Enter arrow key Override button-takes unit out of unoccupied (set point based) Unit is in unoccupied mode. MO -MONDAY FR-FRIDAY TU-TUESDAY SA-SATURDAY WE-WEDNESDAY SU-SUNDAY TH-THURSDAYDay of week icons.
Page 8 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 4.3. WIRING AND DISTANCE
Page 8 · click to enlarge
Page 8

Chapter - 4. Installation

The MCS-THERMOSTAT is powered by a +5vdc supply from an MCS controller via a two wire connection that can be wired with the communication network cabling. Improper wiring or installation may damage the thermostat. Wiring must conform to local and national electrical codes.

WARNING!

Before installing the thermostat, turn off all power to the unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.

BY AIR FROM NEARBY DUCT WORK, ELECTRONIC EQUIPMENT, ETC.

4.1. REQUIRED FOR INSTALLATION

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 4.1. REQUIRED FOR INSTALLATION diagram (page 8)
Fig. 7
  • An MCS-THERMOSTAT with a +5 volt power supply
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 4.1. REQUIRED FOR INSTALLATION diagram (page 8)
Fig. 8
  • 1/4” Phillips screwdriver
  • 5/64” flathead screwdriver
  • 2 ½ pan machine screws (included)
  • 1 Wire cutter/stripper
  • 4 Wire 22 to 20 awg Shielded Cable
  • J-Box (USA or International)

4.2. MOUNTING LOCATION

  • Install the MCS-THERMOSTAT on an interior wall. Exterior walls that are poorly insulated can affect the Thermostat temperature and humidity readings and may lead to wasted energy.
  • Install the MCS-THERMOSTAT away from drafts, direct sunlight or anything that would cause the temperature to be artificially high or low.
  • Install the MCS-THERMOSTAT so that it’s not blocked by doors or other obstructions.
  • The Thermostat should be mounted approximately 5’ (1.5m) above the floor.

4.3. WIRING AND DISTANCE

Use 4 wire 22 to 20 awg Shielded Cable for installation. The MCS-THERMOSTAT can be installed up to 1000 feet from the MCS CONTROLLER.

Page 9 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 5.4. SCREWS
Page 9 · click to enlarge
Page 9

Chapter - 5. Installation - Mounting

5.1. UTILIZING J-BOX

MCS recommends you install the MCS-THERMOSTAT utilizing a J-Box. Prior to installing the MCS-THERMOSTAT punch out the corresponding mounting holes on the MCS-THERMOSTAT housing based on the J-box you are utilizing.

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5.1. UTILIZING J-BOX diagram (page 9)
Fig. 9
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5.1. UTILIZING J-BOX diagram (page 9)
Fig. 10
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5.1. UTILIZING J-BOX diagram (page 9)
Fig. 11

USA

International Style Junction Box

USA Style Junction Box

5.2. PUNCTURE SMALL HOLE

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5.2. PUNCTURE SMALL HOLE diagram (page 9)
Fig. 12

Puncture a small hole in the grommet on the back side of the thermostat. You want the wires to be tight so no air passes through affecting the thermostat’s reading.

5.3. OUTPUT WIRES

Push the output wires from the MCS Controller through the rear hole of the MCS-THERMOSTAT’S mounting plate. It may be good practice to wait until the wires are in position to be attached to the

MCS-THERMOSTAT before they are stripped or cut with a tool.

5.4. SCREWS

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 5.4. SCREWS diagram (page 9)
Fig. 13

Using a ¼” Phillips screwdriver, insert one of ¼” machine screws into one of the mounting slots depending on the J-box you are utilizing and tighten the screw to hold the mounting wall plate into position.

Screw the second ¼” machine screw into the lower mounting slot to secure the wall plate.

International

Page 10 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — ONE THERMOSTAT PER MCS-CONTROLLER
Page 10 · click to enlarge
Page 10

Chapter - 6. Wiring Instructions to MicroMag

6.1. Rev. 6.0 (or less) 24VAC, 115VAC and 230VAC

TURN POWER OFF TO CONTROLLER AND THERMOSTAT FIRST

Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.

ONE THERMOSTAT PER MCS-CONTROLLER

MicroMag I/O port (located on top of board as shown below)

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — ONE THERMOSTAT PER MCS-CONTROLLER diagram (page 10)
Fig. 14

5 Sensors available Power for Thermostat (can be wired to any empty sensor)

Enlarged view of Thermostat block wiring

Page 11 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — ONE THERMOSTAT PER MCS-CONTROLLER
Page 11 · click to enlarge
Page 11

6.2. Rev. 6.1 - 24VAC, 115VAC AND 230VAC

TURN POWER OFF TO CONTROLLER AND THERMOSTAT FIRST

Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.

ONE THERMOSTAT PER MCS-CONTROLLER

MicroMag I/O port (located on right of board as shown below)

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — ONE THERMOSTAT PER MCS-CONTROLLER diagram (page 11)
Fig. 15

5 Sensors available Power for Thermostat (can be wired to any empty sensor)

first and last boards on the network

Enlarged view of Thermostat block wiring

Page 12 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — ONE THERMOSTAT PER MCS-CONTROLLER
Page 12 · click to enlarge
Page 12

6.3. Rev. 7.0 - 12 VOLT SYSTEMS

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 6.3. Rev. 7.0 - 12 VOLT SYSTEMS diagram (page 12)
Fig. 16 · 6.3. Rev. 7.0 - 12 VOLT SYSTEMS

TURN POWER OFF TO CONTROLLER AND THERMOSTAT FIRST

Begin wiring (not supplied) from the MCS CONTROLLER to the MCS-THERMOSTAT as shown in the wiring diagram.

ONE THERMOSTAT PER MCS-CONTROLLER

Page 13 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 7.3.13 Units - F/C
Page 13 · click to enlarge
Page 13

Chapter - 7. Thermostat Menu Screens

Use ‘UP’ ‘DOWN’ and ‘ENTER’ BUTTON TO MOVE BETWEEN SETTINGS

7.1. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)

7.1.1 Net Address (Factory Set At 1)

7.1.2 Units Degrees (F) Or (C)

7.1.3 Auth Level Setup

SEE NEXT PAGE FOR DESCRIPTIONS

7.1.4 Sound Alarm Stat

OF MENU ITEMS AND AN EXAMPLE OF AUTHORIZATIONS LEVELS

7.1.5 Adjust Backlight

7.1.6 Standby Backlight

7.1.7 Exit Setup Menu

7.2. MAIN

7.2.1 Unit Status

*NOTE: SOME MENU OPTIONS MAY NOT SHOW ON YOUR THERMOSTAT LCD SCREEN.

7.2.2 Lockout Reset

7.2.3 Last Alarm

THESE SELECTIONS MAY NOT BE SETUP IN THE CONFIGURATION FILE FOR YOUR CONTROLLER.

7.2.4 Time And Date

7.2.5 Show Version Number

7.2.6 Cool Target

7.2.7 Unit (Run/Stop) *

AFTER LAST SELECTION HAS BEEN MADE

CLICK ON ‘MENU” TO RETURN TO THE

7.2.8 Enter Password

‘UNIT STATUS SCREEN’

7.2.9 Config Menu

7.3. CONFIG MENU

7.3.1 Auth Level Setup

**SUPPLY TEMP IS ONLY AVAILABLE IN THE MICROMAG CONFIG SETTINGS IF AVAILABLE

7.3.2 Zone or Supply Temp **

7.3.3 Sound Alarm Stat

SEE THERMOSTAT CONFIG MENU SETUP

7.3.4 Thermostat Reset

ON HOW TO LOAD

7.3.5 Adjust Date & DOW

7.3.6 Adjust Time

7.3.7 Standby Backlight

7.3.8 Adjust Backlight

7.3.9 Display Test

7.3.10 Temp Cal

7.3.11 Modify Holidays

CLICK ON THERMOSTAT RESET

7.3.12 Modify Schedules

PRESS ENTER TO UPDATE. THE THERMOSTAT WILL REBOOT AND LOCK

7.3.13 Units - F/C

Page 14 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 8.3. AUTHORIZATION LEVEL SETUP
Page 14 · click to enlarge
Page 14

Chapter - 8. SETUP (APPEARS FIRST TIME THERMOSTAT IS TURNED ON)

SETUP

ADDITIONAL CHANGES CAN BE MADE USING THE CONFIG MENU AFTER THE ‘INITAL SETUP’

Net Address:

SETTING UP THE THERMOSTAT FOR THE FIRST TIME

AT THIS POINT, YOU SHOULD HAVE WIRED THE THERMOSTAT TO THE MICROMAG OR MAGNUM controller. Turn power on to the MicroMag or MAGNUM, Thermostat will power up and enter the ‘SETUP MENU’. The following items will appear in the setup menu:

8.1. NETWORK ADDRESS

The Thermostat is factory set to Network address one (1) This cannot be changed.

8.2. UNITS DEGREES

Allows the user to choose between Celsius and Fahrenheit. Directions: Use the Up/Down arrows to move between Celsius and Fahrenheit. Press ‘Enter’ to select the desired unit degrees and the display will confirm the change.

8.3. AUTHORIZATION LEVEL SETUP

The user will be able to see all functions of the thermostat if the controller’s configuration file is setup to allow this. Some functions of the thermostat may be turned off in the configuration file to help protect unauthorized users from making changes.

Authorization Levels- The MicroMag and MAGNUM allow several levels of password protection that have been setup in your thermostat - ‘Service’, ‘Supvsr’ (Supervisor), and ‘Factory.’

The Installer can setup the Authorization Levels at this time. This will allow a user with the correct password to make changes.

OPERATION OF THE THERMOSTAT CAN BE CONTROLLED BY THESE LEVELS OF AUTHORIZATION. SEE EXAMPLE NEXT PAGE

Occup

Page 15 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — IF YOU ARE AUTHORIZED
Page 15 · click to enlarge
Page 15

SAMPLE TO SHOW HOW TO USE AUTHORIZATION LEVELS FOR THE THERMOSTAT

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 8.4. SOUND ALARM STAT diagram (page 15)
Fig. 17

Modify Schedule and 24 hour clock NO YES YES YES

AS SHOWN IN THE ‘SAMPLE’ ABOVE AUTHORIZATION LEVEL ‘VIEW’ (DEFAULT) WILL HAVE THE LOWEST LEVEL OF ACCESS TO THE THERMOSTAT WHEREAS AUTHORIZATION LEVEL ‘FACTORY’ WILL HAVE THE HIGHEST AUTHORIZATION FOR MAKING CHANGES TO THE THERMOSTAT.

YOU CAN SET UP THE AUTHORIZATION LEVEL FOR EACH SELECTION SHOWN IN THE ‘CONFIG’ MENU SO A USER WILL BE LIMITED AS TO WHAT CHANGES THEY CAN MAKE.

8.4. SOUND ALARM STAT

Hit ‘ENTER’ - Allows the user to turn alarm on or off.

8.5. ADJUST BACKLIGHT

Allows the user to adjust the backlight setting from 25% to 100%.

8.6. STANDBY BACKLIGHT

Hit ‘ENTER’ - Allows user to make changes to the backlight - OFF or 25% to 100%

8.7. EXIT SETUP MENU

Press ENTER to exit the SETUP menu, all changes made in the SETUP settings will be saved in the MCS-THERMOSTAT non volatile flash memory.

YOUR THERMOSTAT IS SETUP AND READY FOR USE. ADDITIONAL CHANGES CAN BE MADE USING THE CONFIG MENU

IF YOU ARE AUTHORIZED

Setup (continued)

Page 16 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 9.12. LOCKOUT RESET
Page 16 · click to enlarge
Page 16

Chapter - 9. Main Menu Settings

CLICK ON MENU TO SEE THE SCREENS BELOW AUTHORIZATION PASSWORD LEVEL MAY BE REQUIRED

9.1. UNIT STATUS

Hit ‘ENTER’ shows status of thermostat.

9.2. CONFIG MENU

Hit ‘ENTER’ - Allows user to enter Config Menu to make adjustment to the thermostat.

9.3. ENTER PASSWORD

Hit ‘ENTER’ - Authorization password level for the changes to the thermostat.

9.4. UNIT STATUS (RUN/STOP)

Hit ‘ENTER’ - Allows user to ‘RUN/STOP’ the unit controlling the thermostat. (This must be confiured in your controller for viewing on your thermostat).

9.5. COOL TARGET

Hit ‘ENTER’ - Allows the user to SET THE COOL SET POINT FOR THE AREA.

9.6. HEAT TARGET

Hit ‘ENTER’ - Allows the user to SET THE HEAT SET POINT FOR THE AREA.

9.7. HUMIDITY TARGET

Hit ‘ENTER’ - Allows the user to SET THE HUMIDITY SET POINT FOR THE AREA.

9.8. CO2 TARGET

Hit ‘ENTER’ - Allows the user to SET THE C02 SET POINT FOR THE AREA.

9.9. SHOW VERSION NUMBER

Hit ‘ENTER’ - Shows current version of firmware the thermostat is using.

9.10. TIME AND DATE

Hit ‘ENTER’ - Shows current time and date of unit operating thermostat.

9.11. LAST ALARM

Displays abbreviations for the last three alarms on the first screen before flashing to a second screen displaying the time/date of respective alarm.

For example, in a displayed ‘LO DIS PSI’ alarm listing, the user interface would switch to a screen displaying ‘Jan 31 12:10’ as the occurrence time for the first ‘LO’ alarm before jumping back to the ‘LO PSI LO’ alarm display and switching to a screen displaying ‘Feb 2 12:10’ as the occurrence time for the second ‘PSI’ alarm.

9.12. LOCKOUT RESET

Hit ‘ENTER’ - Allows used to reset lockout if authorized.

Page 17 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 10.4. MODIFY SCHEDULES
Page 17 · click to enlarge
Page 17

Chapter - 10. Config Menu Settings

MENU

MENU

SHOWS UNLOCKED

CLICK ON MENU - USE DOWN BUTTON TO SEE THE CONFIG MENU

AUTHORIZATION PASSWORD IS REQUIRED

10.1. AUTH LEVEL SETUP

Authorization Levels- The thermostat allows three levels of passwords - Service, Supervisor, and Factory.

10.2. ZONE OR SUPPLY TEMP (ONLY ON MICROMAG FIRMWARE VER 2.00E and MicroMag Config 18.00N and up)

Hit ‘ENTER’ - Allows the user to change between showing ‘ZONE TEMP’ or ‘SUPPLY TEMP’ if “SUPPLY TEMP’ is used.

10.3. UNIT = DEGREES

Hit ‘ENTER’ -Allows the user to change between Celsius and Fahrenheit. Directions: Use the Up/Down arrows to move between Celsius and Fahrenheit. Press ‘Enter’ to select the desired unit degrees and the display will confirm the change.

10.4. MODIFY SCHEDULES

Unlike Thermostats that are used at home and in an some office buildings, the MCS Thermostat ‘SCHEDULES’ control the run/stop of the controller’s cool target and heat target setting only.

Think of the Thermostat ‘SCHEDULES’ as controlling whether a building or room is ‘OCCUPLIED or ‘UNOCCUPLIED’. We can still allow the building or room to be cooled or heated, but with target setting, we can lower (or raise) the temperature depending on whether the building or room is ‘OCCUPLIED’.

For example if you set ‘SCHEDULE ONE’ to start at 8:00am the thermostat will start either the cooling process or heating process of the unit based on the cooling/heating targets that you have setup in the Thermostat or configuration of the controller. Setting ‘SCHEDULE ONE’ to end at 17:00 (5:00pm) the Thermostat can change how the building or room is heated or cooled.

Show 4 more labels / short text on this page
Occup · Occup · Config Menu · Config Menu
Page 18 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — HOLIDAY DATES
Page 18 · click to enlarge
Page 18

Config Menu (continued)

The advantage of the MCS Thermostat is that you can override the target settings of the UNIT’S heating, cooling and humidity from the thermostat without the going to the actual unit. See an example of setting up the schedules and holidays on the next pages.

10.4.1 SETTING EACH DAY OF THE WEEK

Schedule setting start with Sunday as the first day.

1. Press Menu button to ‘CONFIG MENU’ , press ‘ENTER’
2. Use ‘DOWN’ to ‘MODIFY SCHEDULES’ , press ‘ENTER’
3. The first schedule day will appear on the screen ‘SUN Schedule 1 start’ press ‘ENTER’ to accept this day.

4. The next screen display will show the Hour ‘BLINKING’ - enter the hour, press ‘ENTER’ to move to the minutes. After you set the minutes, press ‘ENTER’ to accept, the following screen will appear ‘Prs Enter to continue’. The information will be sent to the controller. 5. Be sure to set the ‘START and ‘END TIMES’ for each day for ‘SCHEDULE 1’ and for ‘SCHEDULE 2’ before proceeding to the next day on the Thermostat. 6. IF YOU DO NOT SEE THE ‘HOUR BLINKING’ YOU FORGOT TO PRESS ENTER FOR THE NEXT SCHEDULE DAY.

SHOWS SCHEDULE

00 : 01

FOR 24 HOUR

23 : 59

OPERATION

Sun Set Schedule 1 Start

Sun Set Schedule 1 End

Below is a screen shot from MCS-CONNECT showing what the schedule settings look like in the configuration setup. Basically this is what you are setting up when you are setting the ‘SCHEDULES and HOLIDAYS’ times in the Thermostat.

10.5. MODIFY HOLIDAYS

These settings allows the user to adjust the thermostat’s “START and END’ times for holidays that

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — 10.5. MODIFY HOLIDAYS diagram (page 18)
Fig. 18

HOLIDAY DATES

ARE SETUP IN

MCS-CONNECT

Occup · Occup

Page 19 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — 10.14. SOUND ALARM
Page 19 · click to enlarge
Page 19

have been setup in the configuration file or thru MCS-CONNECT. Press the Up/Down arrows and Enter buttons to make adjustments. See screen shot on previous page as an example.

10.6. TEMP CAL

Allows the user to make changes to the temperature setting of the Thermostat using a calibrated hand held temperature meter to check the current temperature of the area.

Directions: Use the Up/Down arrows to move between the offset range. Press ‘Enter’ to select the desired temperature offset and the display will confirm the change.

10.7. HUMIDITY CAL

Allows the user to make changes to the humidity setting of the Thermostat using a calibrated hand held meter to check the current humidity of the area.

Directions: Use the Up/Down arrows to move between the offset range. Press ‘Enter’ to select the desired temperature offset and the display will confirm the change.

10.8. DISPLAY TEST

Allows the user to test the thermostat to make sure all icons are working.

10.9. ADJUST BACKLIGHT

Allows the user to adjust the backlight setting from 25% to 100%.

10.10. STANDBY BACKLIGHT

Hit ‘ENTER’ - Allows user to make changes to the backlight - OFF or 25% to 100%

10.11. ADJUST TIME

Allows the user to change the displayed time from the MCS-THERMOSTAT. Directions: Use the Up/Down arrows and Enter button to first adjust the hour per a 24-hour schedule (ex. 1:00am is 0100 and 1:00pm is 1300) and press ‘Enter’ to move on to the minutes. After adjusting the minutes, press ‘Enter’ to move on to the seconds. Press ‘Enter’ to complete the time adjustment.

10.12. ADJUST DATE

Allows the user to change the displayed date from the MCS-THERMOSTAT.

10.13. THERMOSTAT RESET

Hit ‘ENTER’ to update-’RESTARTING THE UNIT’ (THIS RE LOCKS THE THERMOSTAT)

10.14. SOUND ALARM

Hit ‘ENTER’ - Allows the user to turn alarm on or off.

Page 20 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 11. Update Firmware on Thermostat
Page 20 · click to enlarge
Page 20

Chapter - 11. Update Firmware on Thermostat

11.1. MCS-Thermostat firmware upload

Loading new ‘Firmware’ to the Thermostat (requires proper authorization)

Consult support@mcscontrols.com for upgrading your Thermostat firmware and acquiring the necessary TERMINAL BLOCK CABLE TO ATTACH TO THERMOSTAT.

1. REMOVE COVER FROM THERMOSTAT AND REMOVE THE WIRES FROM THE PLUS AND MINUS FOR THE COMMUNICATION OF THE THERMOSTAT.
2. CONNECT THE TERMINAL BLOCK SUPPLIED TO THE THERMOSTATWHITE WIRE TO PLUS(+) AND THE BLACK WIRE TO GROUND (-) .
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 19 · Chapter - 11. Update Firmware on Thermostat
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 20 · Chapter - 11. Update Firmware on Thermostat
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 21 · Chapter - 11. Update Firmware on Thermostat
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 22 · Chapter - 11. Update Firmware on Thermostat

Cable with terminal block

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 23 · Chapter - 11. Update Firmware on Thermostat

Enlarged view of Thermostat block wiring

3. USING A MCS-USB-RS485 CABLE (not supplied) PLUG THE RS-485 END INTO THE SUPPLIED TERMINAL AND THE USB END INTO YOUR COMPUTER.
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 24 · Chapter - 11. Update Firmware on Thermostat
4. Open MCS-Connect and select Setup.
5. In the drop down menu select Communications.
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 20)
Fig. 25 · Chapter - 11. Update Firmware on Thermostat
Page 21 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 11. Update Firmware on Thermostat
Page 21 · click to enlarge
Page 21
6. On the communications Setup Screen select the LOCAL Comm. COM port from your computer and then set the baud rate to 38400. Press Save and click SERIAL to connect with the MCS-Thermostat.
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 21)
Fig. 26 · Chapter - 11. Update Firmware on Thermostat
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 11. Update Firmware on Thermostat diagram (page 21)
Fig. 27 · Chapter - 11. Update Firmware on Thermostat
7. When MCS-Connect screen opens a red line will appear on the site info showing the Software information of the MCS-Thermostat.
8. While on the site info screen press ‘Load Firmware’ and select the location for the new Hex file to load the new firmware. (supplied by MCS-SUPPORT)
9. When the firmware finishes downloading to the thermostat:
1. Remove the TERMINAL BLOCK wiring from the thermostat.
2. Re-connect the MCS-Thermostat to the MCS controller.
Page 22 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — PASSWORDS RESET
Page 22 · click to enlarge
Page 22

Chapter - 12. Troubleshoot Section

Check to make sure you have the wiring correct to the Thermostat (see wiring in beginning of this install guide). Check to see that the Thermostat and Controllers are Terminated correct. In MCS-CONNECT or Keypad, check to see if the baud rate is correct(38,400)

THERMOSTAT WILL NOT TURN ON OR COMMUNICATE WITH THE CONTROLLER

MCS-THERMOSTAT remains in locked mode until the proper password is entered. Press the Menu button until you see Password - press enter, than your first password number - press enter until the correct password has been entered. LOCKED ICON SHOULD SHOW UNLOCKED. Password Code will lock back in 2 minutes

THERMOSTAT IS IN LOCKED MODE

THERMOSTAT HEATING AND COOLING IS NOT CORRECT TO ROOMS CONDITIONS

Check the Setting Menu to make sure you have the proper Unit Degrees chosen - Celsius or Fahrenheit.. Reset the Temp Calibration using the Config Menu to adjust for tempera- ture variations.

To make sure all of your Thermostats Icons are working - Press Menu to get to the Config Menu using the up/down arrows until you see Display Test- press enter - all icons should show on the screen.

THERMOSTAT ICONS TEST

THERMOSTAT NOT WORKING- SHOWS UNOCCUPIED OVERRIDE BUTTON ON LEFT SIDE OF UNIT IS SET TO UNOCCUPIED.

Max. LOCKOUTS PER DAY Reset Lockouts – Does require being authorized. However only a limited number of Lockouts(6) can be reset in one day without a higher authorization level.

THERMOSTAT STAYS IN HEAT- ING OR COOLING MODE AND WON’T CHANGE

Check your Cooling and Heating Set Points - consult HVAC Technician

TO DISABLE THE CURRENT PASSWORD - AT THE MENU LEVEL, PRESS MENU UNTIL YOU SEE ENTER PASSWORD. ENTER A PASSWORD THAT IS NOT USED BY THE SYSTEM TO RELOCK THE UNIT SO UNAUTHORIZED CHANGES CANNOT BE MADE.

PASSWORDS RESET

Page 23 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Chapter - 12. Troubleshoot Section
Page 23 · click to enlarge
Page 23
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 12. Troubleshoot Section diagram (page 23)
Fig. 28 · Chapter - 12. Troubleshoot Section

1-12-15 DEW Edits made as per Brian, setting menu\

6-01-15 DEW Edits made to wiring and setup config

12-2/3-15 DEW Add run/stop feature, add new MicroMag board to wiring

03-10-21 DEW Change to Rev. 1.6 - add 12 volt wiring

04-08-16 DEW Add wiring and distance on installation page

The MCS Commitment is to provide practical solutions for the industries

needs and to be both a leader and partner in the effective use of

Microprocessor controls.

Micro Control Systems, Inc.

5580 Enterprise Parkway Fort Myers, Florida 33905 PH:(239) 694-0089 FAX:(239) 694-0031

www.mcscontrols.com

Revision Page

Page 24 of the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) user manual — Providing HVAC/R Control Solutions Worldwide
Page 24 · click to enlarge
Page 24
MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) — Chapter - 12. Troubleshoot Section diagram (page 24)
Fig. 29 · Chapter - 12. Troubleshoot Section

Providing HVAC/R Control Solutions Worldwide

5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: (239) 694-0089

Fax: (239) 694-0031 www.mcscontrols.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT)

Be the first to ask — other owners or our team will answer.

Original document

MiCRO CONTROL SYSTEMS Micro Control System (MCS-THERMOSTAT) manual PDF

24 pages·737 KB·Thermostat·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…