0-5V Input:
Emerson’s Wireless Module System allows a quick and easy monitoring for a variety of Refrigeration and HVAC applications by connecting temperature probes, product simulators, humidity probes or switches to the Wireless Module that transmits these signals to the Wireless Gateway. The Gateway translates the signal into usable information to send to the building controller, E2 (version 4.08 or higher) or Supervisory controller, where the data can be logged into reports or used by algorithms to make control decisions. The Wireless Gateway can receive signals from up to 99 Modules. The Wireless Module is flexible and configurable with up to three (3) analog or digital inputs that can be used for a variety of applications in Refrigeration and HVAC, eliminating installation materials and costly labor-intensive wiring.
NTC/Dig Input:
Table 1 - DIP Switch Settings
The Wireless Module must be associated with the Gateway through the Commissioning process. With proper range planning, all Modules can be commissioned to the Gateway prior to mounting. For complete instructions on setup and commissioning of the Wireless Module, refer to the Wireless User Manual (P/N 026-1734).

Steps to set up and commission the Wireless Module in E2:
1. Go to the Add Application screen to add required number of RF Modules (Menu, 6, 1, F4: Lookup, 23. RF Module) then press Enter. 2. Enter how many (99 max per Gateway) and press Enter. 3. Once the RF Module application has been added, go to Configured Applications to commission the device (Menu, 5, 230. RF Module). 4. Select an RF Module from the list and press Enter. 5. Pull up the Actions Menu, and initiate commissioning (Enter, 9, 1: Commission Device). 6. The application will enter learning mode. 7. Within one (1) minute, press the Learn button on the Module.
Figure 1 - Wireless Module Board Inside Enclosure
If this is a User Selected Input Module (P/N 814-3600), you must set the DIP switch setting based on the input being received from the sensor; either 0 to 5V or NTC/Digital.


Figure 2 - Wireless Module Enclosure
Document Part # 026-4255 Rev 3 Page 1 of 2 ©2021 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.climate.emerson.com for the latest technical documentation and updates.

During the commissioning process, press the Learn button and the following occurs: Blue LED:

Table 2 - SSI Signal Strength Values
Figure 3 - Overlapping Coverage Area
For a copy of the full Wireless User Manual, scan the QR Code:
Table 3 - Ordering Information
Document Part # 026-4255 Rev 3 Page 2 of 2
This document may be photocopied for personal use. Visit our website at http://www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook. http://on.fb.me/WUQRnt For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applica-
bility. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.

Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.