EN
PowerTech logo
Official user manual

PowerTech PTS-25

66 pages·3.5 MB·Generator·PDF·ENDEFRITNLJA
PowerTech PTS-25
Table of Contents 80 sections PTS-15 PTS-17.5 · PTS-20 PTS-25 · Operators · Manual · … ShowHide
PTS-15 PTS-17.5p.1PTS-20 PTS-25p.1Operatorsp.1Manualp.1634 STATE RD. 44 LEESBURG, FL. 34748-8103p.2(352) 365-2777 FAX (352) 787-5545 www.PowerTech-Gen.comp.2TABLE of CONTENTSp.4SECTION 1: “SAFETY”p.4SAFE OPERATION 1-4 SECTION 2: “ENGINE”p.4SECTION 1p.5SECTION 2p.10“ENGINE”p.10OPERATING THE ENGINEp.12ENGINE STARTING CONTROLSp.12ENGINE SPECIFICATIONSp.13MODELp.13SERVICE PARTSp.13Engine Maintenance Service Schedulep.14Air Filter Replacement ** X Or Once a Yearp.14ENGINE OIL MAINTENANCEp.15CHECKING ENGINE OIL LEVELp.15V-1903-BG, V-2003-T, V-2203-BG ENGINEp.15REFILL CAPACITIESp.15LUBRICATING OIL VISCOSITYp.15LUBRICATING OILp.15SPECIFICATIONp.15CF Engine Oilp.15SAE 10W-40p.15ENGINE COOLANT MAINTENANCEp.16CHECKING RESERVOIR TANKp.16OPERATING HOURS and SERVICE LOGp.17ENGINE STARTS BUT WON’T RUNp.18REPLACEp.18BLUE GRAY/WHITE BLACKp.19ENGINE RUNS ROUGH or SLOWp.19HIGH ALTITUDEp.19YES NOp.20ENGINE WILL NOTp.20STARTp.20GENERATOR ASSEMBLY INFORMATIONp.22ELECTRONIC VOLTAGE REGULATIONp.22VOLTAGE CONNECTIONp.22EXCITER FIELD COIL VOLTAGE SOURCEp.22ROTATING FIELD ASSEMBLY (ROTOR)p.23CORE ASSEMBLYp.23FIELD COILp.23BEARINGp.23STATOR ASSEMBLYp.23“M” SERIES EXCITER TYPE GENERATOR ASSEMBLYp.24DESCRIPTION PART NUMBERp.24“K” SERIES EXCITER TYPE GENERATOR ASSEMBLYp.25DESCRIPTION PART NUMBERSp.25ZERO OR LOWp.26VOLTAGEp.26BAD OK ON OFF OK BADp.26OKp.26BADp.26OK 5p.26VOLTAGE TESTp.27AVRp.2712 VOLT BATTERY TESTp.27RPM 1800p.27OVERLOAD CONDITIONp.28BAD OK BAD OKp.28RESISTANCE CHARTp.29120 VOLT CONNECTION “M” SERIES EXCITER TYPEp.30120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPEp.31KW 16 21 MARKS COLORp.32PLATE ASSEMBLY 1.462 1.334 N/A N/Ap.32EXCITER ROTOR / DIODEp.32(352) 365-2777 FAX (352) 787-5545p.32634 STATE ROAD 44 LEESBURG, FL 34748-8103p.32MAIN ROTOR 3.1 3.3 N/A N/Ap.33SAFTEY PRECAUTIONSp.36GENERATOR INSTALLATION in RECREATIONAL VEHICLESp.38MARINE APPLICATIONp.38GENERAL INFORMATIONp.38GENERATOR COMPARTMENT SIZEp.39COMPARTMENT FRAMINGp.39AIR REQUIREMENTSp.39
Page 1 of the PowerTech PTS-25 user manual — PTS-15 PTS-17.5
Page 1 · click to enlarge
Page 1
PowerTech PTS-25 — PTS-15 PTS-17.5 diagram (page 1)
Fig. 1

PTS-15 PTS-17.5

PTS-20 PTS-25

Operators

Manual

Power Technology Southeast, Inc. 634 State Road #44 Leesburg, FL 34748-8103 ♦ (352) 365-2777 ♦ Fax (352) 787-5545 ♦ 8/2010 MANPT15-20

Page 2 of the PowerTech PTS-25 user manual — 634 STATE RD. 44 LEESBURG, FL. 34748-8103
Page 2 · click to enlarge
Page 2

FORWARD You are now the proud owner of a Power Technology Generator powered by a Kubota engine. This engine is a product of Kubota’s quality engineering and manufacturing. The engine is made with fine materials and manufactured under the strictest quality control standards and will assure you long satisfactory service. To obtain the best use of your engine, please read this manual carefully. It will help you become familiar with the operation of the engine and contains many helpful hints regarding engine maintenance. Continuing improvements and advancements in product design may have caused changes to your engine, which are not included in this manual.

Please contact Power Technology’s Customer Service Department for latest information on your Kubota engine or for the number of your local Kubota dealer.

TO OUR CUSTOMERS Thank you for your purchase of a Power Technology Generator. The information contained in this manual applies to PTS-15, PTS-17.5, PTS-20 and PTS-25 generators. In the event you experience a problem with your generator please contact the sales dealer, one of our authorized service centers or Power Technology’s Customer Service Department directly at 1-800-760-0027 from 8:00 a.m. to 5:00 p.m. EST. Please have the generator model and serial numbers available when you call. This will help expedite service and parts to you. Parts may be obtained directly through Power Technology and shipped the same day if ordered by 3:00 p.m. EST.

Generator Model Number Generator Serial Number

POWER TECHNOLOGY SOUTHEAST, INC.

634 STATE RD. 44 LEESBURG, FL. 34748-8103

(352) 365-2777 FAX (352) 787-5545 www.PowerTech-Gen.com

Page 3 of the PowerTech PTS-25 user manual — 634 STATE RD. 44 LEESBURG, FL. 34748-8103
Page 3 · click to enlarge
Page 3
PowerTech PTS-25 — 634 STATE RD. 44 LEESBURG, FL. 34748-8103 diagram (page 3)
Fig. 2

Limited Warranty on Power Tech Generators

Power Technology Southeast, Inc. warrants to you, the original purchaser, that each product of our manufacture is free from defects in materials, and workmanship. That each generator will deliver its rated output as indicated on The Power Technology Nameplate, if properly installed, serviced, and operated under normal conditions in accordance with Power Technology’s instructions. THE WARRANTY COVERAGE TERMS: 2 years from date of purchase, or 3000 hours whichever comes first, or 36 months from the date of manufacture. Parts, and labor, including diagnostic labor, removal, and reinstallation are covered for the first 12 months from date in service or 1000 hours whichever comes first. Parts and labor are covered only on the following generator and engine parts for 2 years or 3000 hours whichever comes first. Generator Parts: Main Rotor and Main Stator. Engine Parts: Cylinder Block, cylinder head, crankshaft, camshaft, cylinder head gears, connecting rods, flywheel and flywheel housing, intake and exhaust manifold (only if flexible connection is used). 3) Stand-by Units are covered for a period of 1 year from date of installation, or 1000 hours, or 24 months from the date of manufacture whichever comes first. 4) Replacement Parts are warranted: 30 days. (Excluding the following: voltage regulators, fuses, controllers, capacitors, brushes, and switches) WHAT POWER TECHNOLOGY WILL DO: Power Tech will at our option, repair or replace any part covered by this warranty which becomes defective, malfunctions or otherwise fails to conform to this warranty under normal use and service during the term of this warranty. WHAT YOU MUST DO TO OBTAIN WARRANTY SERVICE: In order to obtain warranty repairs you must deliver the product, together with proof of purchase to an authorized Power Tech service facility. In the case of repairs pertaining to the engine only, you must use an authorized dealer or distributor of that make of engine, to be covered under their warranty. Engines used in the manufacture of Power Tech products are warranted solely by the engine manufacturer. PRIOR APPROVAL IS REQUIRED FOR ANY WARRANTY SERVICE Failure to obtain authorization prior to the repair being performed will result in the claim being denied. All claims must be submitted within 30 days of the repair. Along with the following: a copy of the original repair order, Power Tech authorization number, Power Tech serial number, and operation hours shown on the genset mounted hour meter. THIS WARRANTY DOES NOT COVER THE FOLLOWING: A. Normal wear items, including but not limited to: turbo-chargers, fuel injector (s), starter, alternator, and electronic components, as well as normal engine and/or generator wear. A1. Travel time and fuel charges to and from the repair facility or travel time and fuel charges for mobile service. (Except stationary units with a maximum of 2-hours travel time.) B. Defects, malfunctions or failure resulting from accidents, abuse, misuse, improper servicing, improper installation, improper storage, and lack of performance of required maintenance service. C. Products which have been subjected to alteration, modification, neglect or unauthorized repairs. D. Troubleshooting, routine service, tune-ups, replacement of filters, belts, coolant, lubricants, hoses, clamps, exhaust system components, fuel system components, gaskets and/or seals. E. Electrical items damaged by welding or jump-starting. F. Damage caused by water ingestion or electrolysis. G. Damage caused by ingestion of substances other than clean filtered air, fuel, or intake water. H. Damage caused by faulty repairs performed by a repair facility not authorized in writing by Power Tech. I. Damage caused by operation with improper fuel or at speeds, loads, conditions, modifications, or installation contrary to published specifications or recommendations. J. Original installation charges and startup costs. K. Removal and re-installation charges of more than 1-hour labor for outside units, 2-hours for compartment mounted units, and 3-hours for below deck marine units. Customer is responsible for additional labor/charges due to difficult access, removal or installation. L. Starting batteries and labor or charges related to battery service. M. Loss of revenue or the rental of equipment due to down time. N. Generator repairs made within the warranty period other than by an authorized Power Tech service dealer without prior written approval from Power Tech warranty department. O. Damage caused by negligent maintenance such as but not limited to: Failure to provide the specified type and quantity of lubricating oil, cooling air flow, and proper coolant mixture and level. Failure to provide adequate air intake/or maintenance of the air intake system. Failure to provide scheduled maintenance as prescribed in supplied manuals. P. Engine fluids such as fuel, oil or coolant/antifreeze. Q. Shop supplies such as adhesives, cleaning agents, rags, paint, or other miscellaneous supplies. R. Use of other than factory supplied or approved repair parts or procedures. Replacement of a failed Power Tech component with a non-Power Tech component voids the Power Tech warranty on that component and any and all failures related to that component. S. Fuel injection pumps repaired by anyone other than the factory authorized dealer or distributor of that engine. T. Expenses incurred investigating performance complaints unless defective Power Tech materials or workmanship are discovered. U. Generator sets used in rental applications. V. Cleaning, service, or repair of generator sets the have not been kept free of dirt, debris, or other items that prevent the unit from being able to operate properly. W. Any generator set not application approved. X. Loss of excitation due to prolonged storage. Y. Any damage attributed to low battery monitoring or automatic generator starting systems. Z. Optional accessories are warranted solely by the manufacturer of that item including but not limited to the following item: Block heaters, oil pan heaters, electric cooling fans, air-bag isolators, compartment heaters, fuel tanks, trailers, battery chargers, battery monitors. To obtain warranty service: For your nearest Power Tech authorized service center, on the World Wide Web at: http://www.powertech-gen.com/parts_service.php Call 1-352-365-2777 or write to Power Tech Warranty Department, P.O. Box 490133 Leesburg, FL 34749 USA. Power Tech must be notified in writing within five (5) business days of any product failure. General Conditions: This Warranty is the sole property of the original owner /user. A transfer of ownership shall terminate this Warranty. This Warranty is only valid within the contiguous United States and Canada. Warranty coverage is available outside the U.S. and Canada; please speak to a factory representative for those details. This Warranty does not cover any products or parts not purchased from Power Technology. Power Technology reserves the right to make design improvements and model changes without any obligation to change units or parts previously manufactured. Warranty registration card must be completed and mailed to Power Tech at the above address to validate the Warranty. This is the only express warranty on Power Tech products No person, agent, or dealer is authorized to give any Warranties on behalf of Power Technology Southeast, Inc., and not to assume for Power Technology Southeast, Inc. any other liability in connection with any of its products unless made in writing and signed by an officer of Power Technology Southeast, Inc. LIMITATIONS ON OUR RESPONSIBILITY WITH RESPECT TO PRODUCTS PURCHASED AND USED FOR PERSONAL, FAMILY OR HOUSEHOLD USE: Our responsibility is to repair or replace defective parts as stated above. We will not be responsible for any other expenses, losses or inconvenience which you may Sustain as a result of the purchase, use, malfunction or defective condition of our products. ANY IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE PERIOD SET FORTH ABOVE. Some states do not allow limitations on how long an implied Warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above Limitations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may have other rights which vary from state to state. This Warranty is in lieu of all other Warranties, expressed or implied and of any other obligations or liability on our part. Our responsibility for any and all losses and IN NO EVENT WILL WE BE LIABLE FOR LOSS OF USE, LOSS OF PROFITS, INCONVIENCE, COMMERCIAL LOSS OR OTHER INCIDENTIAL OR CONSEQUENTIAL DAMAGES WHATSOEVER.

Power Technology S.E., Inc. P.O. Box 490133 Leesburg, FL 34749 USA. Z code 04/20/2010

Page 4 of the PowerTech PTS-25 user manual — Table of Contents
Page 4 · Contents
Contents

Contents

PTS-15 PTS-17.5p.1PTS-20 PTS-25p.1Operatorsp.1Manualp.1634 STATE RD. 44 LEESBURG, FL. 34748-8103p.2(352) 365-2777 FAX (352) 787-5545 www.PowerTech-Gen.comp.2TABLE of CONTENTSp.4SECTION 1: “SAFETY”p.4SAFE OPERATION 1-4 SECTION 2: “ENGINE”p.4SECTION 1p.5SECTION 2p.10“ENGINE”p.10OPERATING THE ENGINEp.12ENGINE STARTING CONTROLSp.12ENGINE SPECIFICATIONSp.13MODELp.13SERVICE PARTSp.13Engine Maintenance Service Schedulep.14Air Filter Replacement ** X Or Once a Yearp.14ENGINE OIL MAINTENANCEp.15CHECKING ENGINE OIL LEVELp.15V-1903-BG, V-2003-T, V-2203-BG ENGINEp.15REFILL CAPACITIESp.15LUBRICATING OIL VISCOSITYp.15LUBRICATING OILp.15SPECIFICATIONp.15CF Engine Oilp.15SAE 10W-40p.15ENGINE COOLANT MAINTENANCEp.16CHECKING RESERVOIR TANKp.16OPERATING HOURS and SERVICE LOGp.17ENGINE STARTS BUT WON’T RUNp.18REPLACEp.18BLUE GRAY/WHITE BLACKp.19ENGINE RUNS ROUGH or SLOWp.19HIGH ALTITUDEp.19YES NOp.20ENGINE WILL NOTp.20STARTp.20GENERATOR ASSEMBLY INFORMATIONp.22ELECTRONIC VOLTAGE REGULATIONp.22VOLTAGE CONNECTIONp.22EXCITER FIELD COIL VOLTAGE SOURCEp.22ROTATING FIELD ASSEMBLY (ROTOR)p.23CORE ASSEMBLYp.23FIELD COILp.23BEARINGp.23STATOR ASSEMBLYp.23“M” SERIES EXCITER TYPE GENERATOR ASSEMBLYp.24DESCRIPTION PART NUMBERp.24“K” SERIES EXCITER TYPE GENERATOR ASSEMBLYp.25DESCRIPTION PART NUMBERSp.25ZERO OR LOWp.26VOLTAGEp.26BAD OK ON OFF OK BADp.26OKp.26BADp.26OK 5p.26VOLTAGE TESTp.27AVRp.2712 VOLT BATTERY TESTp.27RPM 1800p.27OVERLOAD CONDITIONp.28BAD OK BAD OKp.28RESISTANCE CHARTp.29120 VOLT CONNECTION “M” SERIES EXCITER TYPEp.30120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPEp.31KW 16 21 MARKS COLORp.32PLATE ASSEMBLY 1.462 1.334 N/A N/Ap.32EXCITER ROTOR / DIODEp.32(352) 365-2777 FAX (352) 787-5545p.32634 STATE ROAD 44 LEESBURG, FL 34748-8103p.32MAIN ROTOR 3.1 3.3 N/A N/Ap.33SAFTEY PRECAUTIONSp.36GENERATOR INSTALLATION in RECREATIONAL VEHICLESp.38MARINE APPLICATIONp.38GENERAL INFORMATIONp.38GENERATOR COMPARTMENT SIZEp.39COMPARTMENT FRAMINGp.39AIR REQUIREMENTSp.39
Page 5 of the PowerTech PTS-25 user manual — SECTION 1
Page 5 · click to enlarge
Page 5

SECTION 1

“SAFETY” SAFE OPERATION 1-4 Observe Safety Instructions Wear Safety Clothing Check Before Operating the Engine Keep Area Around the Engine Clean Safe Handling of Fuel and Lubricants Exhaust Gases and Fire Prevention Escaping Fluids Cautions Against Burns and Battery Explosion Keep Hands and Body Away From Rotating Parts Anti-Freeze and Disposal of Fluids Conducting Safety Checks and Maintenance This symbol, the industry’s “Safety Alert Symbol”, is used throughout this manual and on labels attached the machine itself. It warns of the potential for personal injury. It is essential that you carefully read the instructions and safety regulations before you attempt to assemble or use this unit.

PowerTech PTS-25 — SECTION 1 diagram (page 5)
Fig. 3

if instructions are not followed. NOTE: Indicates helpful information.

Page 6 of the PowerTech PTS-25 user manual — SECTION 1
Page 6 · click to enlarge
Page 6

SAFE OPERATION Cautious operation is your best insurance against an accident. Read and understand this section carefully before operating the engine. All operators, no matter how knowledgeable they may be, should read this and other related manuals before operating the engine or any equipment attached to it. It is the owner’s responsibility to instruct all operators in safe operation. Be sure to observe the following for safe operation. OBSERVE SAFETY INSTRUCTIONS • Read, understand and follow this “OPERATORS MANUAL” and “LABELS ON THE ENGINE” before starting and operating the engine.

PowerTech PTS-25 — SECTION 1 diagram (page 6)
Fig. 4
  • Learn how to operate and work safely. Know your equipment and its limitations. Always keep the engine in good condition.
  • Before allowing other people to use your engine, explain how to operate and have them read this manual before operation.
  • DO NOT modify the engine. UNAUTHORIZED MODIFICATIONS to the engine may impair the function and/or safety and affect engine life. WEAR SAFETY CLOTHING
  • DO NOT wear loose, torn or bulky clothing around machinery. Entanglement in rotating parts, controls or projections may cause personal injury.
  • Use additional safety items, e.g. hardhat, eye protection, gloves, etc., as appropriate or required.
  • DO NOT operate machinery or equipment while under the influence of alcohol, medication, or other drugs, or while fatigued.
  • DO NOT wear radio or music headphones while operating engine. CHECK BEFORE OPERATING THE ENGINE
  • If the engine is malfunctioning DO NOT operate until repairs are made.
  • Be sure all guards and shields are in place before operating the engine. Replace any that are damaged or missing.
  • Check to see that the area around the engine is clear of foreign objects before starting.
  • Always keep the engine at least 3 feet (1 meter) away from buildings or other facilities.
  • DO NOT allow children or livestock to approach the machine while in operation.
  • DO NOT start the engine by shorting across starter terminals.
PowerTech PTS-25 — SECTION 1 diagram (page 6)
Fig. 5
PowerTech PTS-25 — SECTION 1 diagram (page 6)
Fig. 6
Page 7 of the PowerTech PTS-25 user manual — SECTION 1
Page 7 · click to enlarge
Page 7
  • KEEP AREA AROUND THE ENGINE CLEAN
  • Be sure to stop the engine before cleaning.
  • Keep the engine clean and free of accumulated dirt, grease and trash.
  • DO NOT stop the engine without idling; Temperatures around the engine rises suddenly. Keep the engine idling for about 5 minutes before stopping.
PowerTech PTS-25 — SECTION 1 diagram (page 7)
Fig. 7
  • SAFE HANDLING OF FUEL AND LUBRICANTS
  • Always stop the engine before refueling or lubricating.
  • DO NOT smoke or allow flames or sparks in your working area. Fuel is extremely flammable and explosive. Never store flammable liquids in the engine compartment.
  • Refuel at a well-ventilated and open place. If fuel or lubricants spill, clean up immediately and properly dispose of.
  • DO NOT mix gasoline or alcohol with diesel fuel. The mixture can cause a fire. EXHAUST GASES AND FIRE PREVENTION
  • Engine exhaust fumes can be very harmful if allowed to accumulate. Be sure to run the engine in a well-ventilated area where there are no people or livestock near by.
  • The exhaust gas from the muffler is very hot. To prevent a fire, do not expose dry grass, oil or any other combustible materials to exhaust gas. Keep the engine and mufflers clean all the time.
  • To avoid a fire, be alert for leaks of flammables from hoses and lines. Be sure to check for leaks from hoses and pipes, such as fuel and hydraulic by following the maintenance check list.
  • To avoid a fire, do not short across power cables and wires. Check to see that all power cables and wires are in good condition. Keep all power connections clean. Bare wire or frayed insulation can cause a dangerous electrical shock and personal injury. 2
PowerTech PTS-25 — SECTION 1 diagram (page 7)
Fig. 8
PowerTech PTS-25 — SECTION 1 diagram (page 7)
Fig. 9

CALIFORNIA Proposition 65 Warning

Diesel Engine Exhaust and some of it’s constituents are known by the

to cause Cancer, Birth Defects and Other

Reproductive harm.

State of California

Page 8 of the PowerTech PTS-25 user manual — SECTION 1
Page 8 · click to enlarge
Page 8
  • ESCAPING FLUIDS
  • Relieve all pressure in the air, oil and cooling systems before any lines, fittings or related items are removed or disconnected.
  • Be alert for possible pressure release when disconnecting any device from a system that is pressurized. DO NOT check for pressure leaks with your hands. High-pressure oil or fuel can cause personal injury.
  • Escaping hydraulic fluid under pressure has sufficient force to penetrate skin causing serious personal injury.
  • Fluid escaping from pinholes may be invisible. Use a piece of cardboard or wood to search for suspected leaks: do not use hands and body. Use safety goggles or other eye protection when checking for leaks.
  • If injured by escaping fluid, see a medical doctor immediately. This fluid can produce gangrene or severe allergic reaction.
PowerTech PTS-25 — SECTION 1 diagram (page 8)
Fig. 10
  • CAUTIONS AGAINST BURNS AND BATTERY EXPLOSION
  • To avoid burns, be alert for hot components during operation and just after the engine has been shut off. Such as the muffler, muffler cover, radiator, piping, engine body, coolants, engine oil, etc.
  • DO NOT remove the radiator cap while the engine is running or immediately after stopping. Wait approximately ten minutes for the radiator to cool before removing the cap.
  • Be sure the radiator drain valve / petcock and hose clamps are tighten. Check radiator pressure cap and oil fill cap before operating the engine.
  • The battery presents an explosive hazard. When the battery is being activated, hydrogen and oxygen gases are extremely explosive.
  • Keep sparks and open flames away from the battery, especially during charging. DO NOT strike a match near the battery.
  • DO NOT check a batteries charge by placing a metal object across the terminals. Use a voltmeter or hydrometer.
  • DO NOT charge a battery if frozen, it may possibly explode. Frozen batteries must be warm up to at least 61°F (16°C) before charging. KEEP HANDS AND BODY AWAY FROM ROTATING PARTS
  • Keep your hands and body away from all rotating parts, such as cooling fan, v-belts, pulleys and flywheel. Contact with these rotating parts can cause serious personal injury.
  • Be sure to stop the engine before adjusting belt tension or checking the cooling fan.
  • DO NOT run the engine without safety guards installed. Be sure the safety guards are properly aligned and securely fastened before operating the engine.
PowerTech PTS-25 — SECTION 1 diagram (page 8)
Fig. 11
PowerTech PTS-25 — SECTION 1 diagram (page 8)
Fig. 12
Page 9 of the PowerTech PTS-25 user manual — SECTION 1
Page 9 · click to enlarge
Page 9
  • ANTI-FREEZE AND DISPOSAL OF FLUIDS
  • Anti-freeze contains toxic chemicals. Wear rubber gloves when handling anti-freeze. In case of contact with skin, wash immediately to avoid personal injury.
  • DO NOT mix different types of Anti-freeze. The mixture can produce a chemical reaction resulting in the formation of harmful substances. Only use anti-freeze that is recommended and approved by Caterpillar.
  • Be mindful of the environment. Before draining any fluids, be prepared to dispose of them in a manner consistent with environmental protection regulations in your location.
  • When draining fluids from the engine, use appropriate containers to hold the different fluids, do not mix fuel, oil or coolant together.
  • Dispose of spent filter cartridges and batteries properly.
  • DO NOT pollute the soil, or any water source. Never pour fluids down a drain. CONDUCTING SAFETY CHECKS AND MAINTENANCE
  • When performing safety checks or engine service, be sure the engine is level and well supported. Use approved stands designed for this type of service.
PowerTech PTS-25 — SECTION 1 diagram (page 9)
Fig. 13
  • DO NOT service an engine that is only supported by a lift jack or hoist.
  • Detach the battery from the engine before conducting service. Put a “DO NOT OPERATE!” tag in the key switch to avoid accidental starting.
  • To avoid sparks from an accidental short circuit always disconnect the 12V DC power at the battery.
  • Be sure to stop the engine and remove the key when conducting daily and periodic maintenance, servicing and cleaning.
  • Check or conduct maintenance after the engine, radiator, muffler, or muffler cover has cooled off completely.
  • Always use the appropriate tools and jig-fixture when performing any service work. Be sure to understand and follow the instructions included with these tools.
  • Use ONLY correct engine barring techniques for manually rotating the engine. DO NOT attempt to rotate the engine by pulling or prying on the cooling fan and V-belt. Serious personal injury or damage to the cooling fan may occur.
  • Replace fuel hoses and hose clamps every 2 years or earlier whether they are damaged or not. They are made of rubber and are aged gradually.
  • When service is performed with two or more people present, take care to perform all work safely. Be aware of their location especially when starting the engine.
  • Keep a first aid kit and fire extinguisher handy at all times.
PowerTech PTS-25 — SECTION 1 diagram (page 9)
Fig. 14
Page 10 of the PowerTech PTS-25 user manual — SECTION 2
Page 10 · click to enlarge
Page 10

SECTION 2

“ENGINE”

PRE-OPERATION CHECK 1 Engine Break-in Period Daily Check OPERATING THE ENGINE 2 Engine Starting Controls Starting the Engine Check Engine After Starting Stopping the Engine ENGINE SPECIFICATIONS 3 Kubota Model’s V-1903-BG, V-2003-T, and V-2203-BG Service Parts ENGINE MAINTENANCE SERVICE SCHEDULE 4 ENGINE OIL MAINTENANCE 5 Checking Engine Oil Level Lubricating Oil Specifications Engine Refill Capacities Lubricating Oil Viscosity Recommendations ENGINE COOLANT MAINTENANCE 6 Coolant Recommendations Ethylene Glycol / Propylene Glycol Checking Radiator Coolant Level Coolant Service Life Checking Reservoir Tank Coolant Level Cleaning Radiator Core OPERATING HOURS AND SERVICE LOG 7 ENGINE TROUBLESHOOTING GUIDES 8-10 Engine Starts but Won’t Run Engine Runs Rough or Slow Engine Will Not Start

Page 11 of the PowerTech PTS-25 user manual — SECTION 2
Page 11 · click to enlarge
Page 11

PRE-OPERATION CHECK ENGINE BREAK-IN PERIOD During the engine break-in period, observe the following recommendations: 1. Change the engine oil and oil filter cartridge after the first 50 hours of operation. (See “ENGINE OIL” in ENGINE MAINTENANCE SERVICE SCHEDULE). 2. In ambient temperature above 32°F (0°C) approximately 3-5 minutes without a load is sufficient for engine warm up. Allow additional warm up time when temperatures are below 32°F (0°C) before placing an operating load on the engine.

DAILY CHECK To prevent future engine problems from occurring, it is important to know and keep track of the engines condition. Below are items to be Inspected and Checked on a daily basis.

  • Be sure all safety shields and guards are attached to the engine when operating.
  • To prevent a fire hazard, keep foreign materials, fuel and oil away from the battery, wiring, muffler and engine. Check and clear them daily. Be aware of the muffler and exhaust gas heat underneath the engine compartment, this heat may ignite grass or other flammable materials.
  • Follow all safety precautions as outlined in the “SAFE OPERATION” section. 1. For accurate readings the engine should be on level ground when checking engine fluids. 2. Check fluids before starting the engine. (Cold Engine)
  • Lubrication System: Check Engine oil level Check for Engine oil leaks
  • Cooling System: Check coolant level and condition Check for coolant leaks Check for proper installation of the radiator cap
  • Fuel System: Check for sufficient quantity of fuel Check for fuel leaks 3. Check engine after starting. (Warm Engine)
  • Proper Operation: Check for easy engine start Check for fluid leaks Check for abnormal engine noises Check for abnormal exhaust gas
Page 12 of the PowerTech PTS-25 user manual — ENGINE STARTING CONTROLS
Page 12 · click to enlarge
Page 12

OPERATING THE ENGINE

ENGINE STARTING CONTROLS

1) Generator Main Switch must be in the ON position. 2) Hold Start/Stop Switch for 1 second and release. 3) Glow Plugs will preheat for 8 seconds. LED flashes slowly. 4) Preheating will cease during engine cranking cycle. LED continues flashing. 5) Engine begins an 8 seconds crank cycle, After 4 seconds of cranking the PT-ECU-63 will check for an AC signal from the generator. If an AC signal is verified the engine will start and the LED will remain ON during the normal run operation. If the AC signal is not verified the PT-ECU-63 will terminate the cranking cycle and LED will flash a fault code. 6) Starter disengages immediately after engine run is verified. 7) PT-ECU-63 deactivates the Low Oil Pressure and High Water Temperature Switches for 6 seconds, this will assure oil pressure build-up time. If oil pressure does not build-up the engine will immediately shut down and go into a fault mode. Likewise for a high temperature situation. 8) If engine will not start on the first attempt the PT-ECU-63 will initiate the start cycle 2 more times before going into a fault mode. Glow Plugs will preheat for 8 seconds per attempt. Engine will crank for 8 seconds per attempt. 9) To shut down the engine under normal operations, hold the Start/Stop Switch for 1 second and release. 10) If a fault occurs turn Generator Main Switch OFF and then ON to reset PT-ECU-63. CHECKING ENGINE AFTER STARTING

1. Allow the engine to warm up 3 to 5 minutes before applying a load. In colder climates allow a few extra minutes longer. 2) Perform a visual inspection of all areas of the engine and generator. 3) Listen for any abnormal noises. 4) Check for any abnormal exhaust gases. STOPPING THE ENGINE

It is recommended to disconnect or reduce the power load from the generator before shutting down the engine. Then follow the steps outlined above for normal shut down. NOTE: The PT-ECU-63 is designed to operate on 12V DC power. In a low battery situation the

PT-ECU-63 may not initiate the normal cranking cycle. To start the generator you can press and hold the Start/Stop Switch for approximately 10 seconds or until the engine starts. Once the engine starts the PT-ECU-63 will resume normal operations. If this situation re-occurs, charge or replace the battery. IMPORTANT: Damage to the Starter Motor, Starter Solenoid, Run Solenoid or any generator component due to excessive or prolonged starting attempts attributed to an external Low Battery Control Monitoring or Auto-Start System will not be covered by the Power Technology Southeast, Inc. Limited Warranty.

Page 13 of the PowerTech PTS-25 user manual — SERVICE PARTS
Page 13 · click to enlarge
Page 13

ENGINE SPECIFICATIONS

V-1505-T V-1903-BG V-2003-T V-2203-BG Air Induction

MODEL

Turbo-Charged Naturally Aspirated Turbo-Charged Naturally Aspirated Continuous Output

25.5 HP @ 1800 rpm 26 HP @ 1800 rpm 36.6 HP @ 1800 rpm 32.5 HP @ 1800 rpm Cubic Capacity 68.53 in³ (1.123 L) 113.32 in³ (1.85L) 121.99 in³ (1.99L) 134.07 in³ (2.19L)

Bore and Stroke 3.07” x 3.09” (78.0 x 78.4mm)

3.43x3.64 (87x92.4mm) Cylinder Arrangement 3 In-Line 4 In-Line 4 In-Line 4 In-Line Firing Order 1-2-3 1-3-4-2 1-3-4-2 1-3-4-2 Compression Ratio 22:1 23:1 22:1 23:1 Engine Oil Capacity 5.38qts. (5.1L) 8.5 qts. (8.04L) 8.5 qts. (8.04L) 8.5 qts. (8.04L) Fuel and Type Diesel 4 Cycle Diesel 4 Cycle Diesel 4 Cycle Diesel 4 Cycle Minimum Fuel Consumption See Specification Chart See Specification Chart See Specification Chart See Specification Chart

3.15x3.64 (80x92.4mm)

3.27x3.64 (83x92.4mm)

SERVICE PARTS

Power Technology Part #

Filters: Oil 01FO091 Fuel 08FF081 Air with Metal Canister 04FA080 Air with Plastic Canister 04FA2E1

Belts: With Alternator 03BF0203 With Idler Pulley 03BF9447

Radiator Hoses: Upper 03HS0203U Lower 03HS0203L

Page 14 of the PowerTech PTS-25 user manual — Air Filter Replacement ** X Or Once a Year
Page 14 · click to enlarge
Page 14

Engine Maintenance Service Schedule

PowerTech PTS-25 — Engine Maintenance Service Schedule diagram (page 14)
Fig. 15 · Engine Maintenance Service Schedule

Fuel Leakage X Fuel Filter Re- placement X Or Once a Year

Air Filter Replacement ** X Or Once a Year

Exhaust Gas Condition X * Engine oil and filter must be changed after the first 50 hours of operation. Then every 100 hours or once a year whichever comes first. ** Air filter replacement interval will vary depending on operating conditions. Adverse conditions may require frequent service. NOTE: Under normal operation items such as Belts, Hoses and Filters are not covered by Power Technology Southeast, Inc. Limited Warranty.

Page 15 of the PowerTech PTS-25 user manual — SAE 10W-40
Page 15 · click to enlarge
Page 15

ENGINE OIL MAINTENANCE

CHECKING ENGINE OIL LEVEL

V-1903-BG, V-2003-T, V-2203-BG ENGINE

REFILL CAPACITIES

( Y ) “ADD” mark. ( X ) “FULL” mark. 1. Maintain the engine oil level between “ADD” mark and “FULL” mark on oil level gauge. Do not fill crankcase above “FULL” mark. 2. Remove the oil filler cap and add oil, if necessary. Clean the oil filler cap. Install the oil filler cap. The refill capacities for the engine crankcase Reflect the approximate capacity of the crankcase or sump plus a standard oil filter. Auxiliary oil filter systems will require additional oil.

Crankcase Oil Sump 8.5 Qts. (8.04L) and Filter

PowerTech PTS-25 — CHECKING ENGINE OIL LEVEL diagram (page 15)
Fig. 16

LUBRICATING OIL VISCOSITY

RECOMMENDATIONS The minimum ambient temperature during cold engine start-up and the maximum ambient temperature during engine operation determine the proper SAE viscosity grade of oil. Refer to the Engine Oil Viscosity Table below (Minimum Temperature) in order to determine the required oil viscosity for starting an engine in cold conditions. Refer to the Engine Oil Viscosity Table below (Maximum Temperature) in order to select the oil viscosity for engine operation at the highest ambient temperature that is anticipated.

LUBRICATING OIL

Ambient Temperature Oil Viscosity Above 25°C (77°F)

SPECIFICATION

SAE 10W-30 SAE 30 or

Use only good quality lubricating oil, which meets

SAE 10W-40 0 to 25°C (32° to 77°F) SAE 10W-30 SAE 20 or

SAE10W-40 Below 0°C (32°F)

SAE 10W-30 SAE 10W or

CF Engine Oil

SAE 10W-40

the following Specification · API Class

Page 16 of the PowerTech PTS-25 user manual — CHECKING RESERVOIR TANK
Page 16 · click to enlarge
Page 16

ENGINE COOLANT MAINTENANCE

COOLANT RECOMMENDATIONS For optimum performance, Power Technology recommends a 1:1 mixture of water / glycol. NOTE: Use a mixture that will provide protection against the lowest ambient temperature. NOTE: 100 percent pure glycol will freeze at a temperature of –23°C (-9°F). Most conventional heavy-duty coolant / antifreezes use Ethylene Glycol. Propylene Glycol may also be used in a 1:1 mixture with water. Ethylene and Propylene Glycol provide similar protection against freezing and boiling. See the tables below.

COOLANT SERVICE LIFE Coolant Type Service Life Commercial Heavy-Duty Coolant/Antifreeze that 3000 Service Hours Meets “ASTM D5345” or Two Years Commercial Heavy-Duty Coolant/Antifreeze that 3000 Service Hours Meets “ASTM D4985” or One Year NOTE: Do not use a commercial coolant/antifreeze that only meets the ASTM D3306 or D4656 specification. This type of coolant/antifreeze is made for light duty automotive applications.

ETHYLENE GLYCOL Freeze Boil Concentration Protection Protection 50 Percent -36°C (-33°F) 106°C (223°F) 60 Percent -51°C (-60°F) 111°C (232°F)

CHECKING RESERVOIR TANK

COOLANT LEVEL (At a Minimum of 25 Hours of Operation) Ensure that the coolant level of the radiator reservoir tank is between the upper limit (FULL) and the lower limit (LOW) on the side of the reservoir tank.

PROPYLENE GLYCOL Freeze Boil Concentration Protection Protection 50 Percent -29°C (-20°F) 106°C (223°F)

PowerTech PTS-25 — CHECKING RESERVOIR TANK diagram (page 16)
Fig. 17

CLEANING RADIATOR CORE Visually inspect the core for any obstructions such as dirt or debris. Use running water to clean particles from between fins. IMPORTANT: Never use hard objects to clean radiator core, damage to core could result.

1. Fill to the bottom of the fill neck and check after every 25 hours of operation.
Page 17 of the PowerTech PTS-25 user manual — OPERATING HOURS and SERVICE LOG
Page 17 · click to enlarge
Page 17

OPERATING HOURS and SERVICE LOG

THIS SERVICE LOG IS PROVIDED TO HELP YOU KEEP AN ACCUMULATIVE RECORD OF OPERATION HOURS ON YOUR GENERATOR

SET AND THE DATES REQUIRED SERVICES WERE PERFORMED. ENTER TIME TO THE NEAREST HOUR.

PowerTech PTS-25 — OPERATING HOURS and SERVICE LOG diagram (page 17)
Fig. 18 · OPERATING HOURS and SERVICE LOG
Page 18 of the PowerTech PTS-25 user manual — REPLACE
Page 18 · click to enlarge
Page 18

Engine Runs OK Has Power NO Power Has Power NO Power Engine runs OK NO Power 8

ENGINE STARTS BUT WON’T RUN

Problem with Remote Connection.

Contact Equipment Manufacturer Jump across Oil Pressure Switch

Check Power to Hold Circuit of Run Solenoid Check Oil Pressure With Gauge

Disconnect Wire to Test

Replace Oil Pressure Switch

REPLACE

Remove Wire From Water Temperature Switch

Remote OK Problem with Remote

Show 21 more labels / short text on this page
Unplug Remote · Start-Stop from · Control Box · with Jumper Wire · (2 pole) · Oil Pressure Switch · Single Pole · If “OK” · Replace · Switch · Defective Solenoid · Check Safety Shutdown · System · Plug Remote · Back IN · Check Shutdown · Relay · Replace Water · Temperature · Switch · Check Wiring
Page 19 of the PowerTech PTS-25 user manual — HIGH ALTITUDE
Page 19 · click to enlarge
Page 19

BLUE GRAY/WHITE BLACK

ENGINE RUNS ROUGH or SLOW

NO Visible Exhaust Smoke Excessive Exhaust Smoke

Insufficient Fuel to Engine

HIGH ALTITUDE

Injector Glow Plug Not Activating

Check With 12 volt DC

Show 18 more labels / short text on this page
Excessive Oil Level · Check Fuel Level · Replace Fuel Filter · Dirty Air Filter · Engine Overheated · Air IN · Check · Engine Over Loaded · Fuel System · Fuel PUMP · Clogged Muffler · Over Fueling Injector · Check Safety Shutdowns · And Fuel Solenoid · Engine Cold · Incomplete Combustion · Over-fueling · Test Light
Page 20 of the PowerTech PTS-25 user manual — YES NO
Page 20 · click to enlarge
Page 20

YES NO

ENGINE WILL NOT

START

Engine Cranks Engine Does NOT

Oil Viscosity TOO HEAVY

Show 38 more labels / short text on this page
Engine Cranks SLOW · Crank · Main Switch Battery · Dead · NO Exhaust · Smoke · Turn Switch · From Exhaust · Smoke · “ON” Start Switch · Check · Check Terminal · LOW Battery Voltage · Glow Plugs · Check · Ends · Fuel Supply · Starter · Check Fuel · Relay · Solenoid · NO Power While · Check Glow Plug · Check · Starter · Cranking · Relay · Fuel Pump · Motor · Check Spark · Air IN · Arrestor Muffler for · Defective · Fuel System · Solenoid · Clogging · No Power · From Starter Terminal
Page 21 of the PowerTech PTS-25 user manual — YES NO
Page 21 · click to enlarge
Page 21

SECTION 3 “GENERATOR END” PRINCIPLES OF OPERATION 1-2 Rotating Field Assembly (Rotor) Core Assembly Field Coil Voltage Connection Electronic Voltage Regulation Exciter Field Coil Voltage Source Balance Bearing Stator Assembly “M” SERIES EXCITER TYPE GENERATOR ASEMBLY 3 “K” SERIES EXCITER TYPE GENERATOR ASSEMBLY 4 GENERATOR END TROUBLESHOOTING GUIDES 5-7 Zero or Low Voltage Voltage Test 12-Volt Battery Test Overload Condition RESISTANCE CHART 8 WIRING SCHEMATICS 9-13 120 Volt Connection “M” Series Exciter Type 120 / 240 Volt Connection “M” Series Exciter Type 120 Volt Connection “K” Series Exciter Type VR 2.4 120 Volt Connection “K” Series Exciter Type VR 3.1A 120 / 240 Volt Connection “K” Series Exciter Type

Page 22 of the PowerTech PTS-25 user manual — EXCITER FIELD COIL VOLTAGE SOURCE
Page 22 · click to enlarge
Page 22

GENERATOR ASSEMBLY INFORMATION

EXCITER TYPE GENERATOR The exciter pole pieces contain residual magnetism, which sets up lines of force across the air gap to the exciter armature. When the exciter begins to rotate a voltage is induced and current flow is initiated in the exciter armature AC windings. This voltage is fed to the rotating rectifier assembly, rectified and fed to the alternator field, which sets up lines of force across the air gap to the alternator stator windings and to the output circuit.

A static voltage regulator is connected to the generator output. The regulator will rectify part of the output voltage to provide a DC voltage to the exciter field coils. This will increase the density of the lines of force in the exciter, increasing the voltage induced into the exciter armature windings, and therefore, to the rotating rectifiers. The rotating rectifier output will be increased which will increase the alternator field strength and generator output will build up its rated voltage. Adjustment of the generator output to the rated voltage level is accomplished by controlling the current fed to the exciter field coils. Regulation is automatic with the static type voltage regulator. An additional voltage adjustment range is provided if desired by turning the Voltage Adjust Rheostat.

ELECTRONIC VOLTAGE REGULATION

Electronic Voltage Regulator (EVR) also referred to, as an Automatic Voltage Regulator (AVR) is a very reliable device, which uses solid-state electronics to maintain voltage accuracy at ±2% of the regulated voltage. The Voltage Regulator is designed to automatically regulate and maintain the generated AC voltage through out the load range that is from no load to full load.

VOLTAGE CONNECTION

The generator may be connected at the terminal board to deliver 120/240 volts to a 3 wire grounded neutral system, or 120-volts only to a 2 wire distribution system. If any equipment requires 240-volts, then the 120/240-volt connection must be used. If all equipment requires 120-volts then the 120-volt connection is preferred, even if two lines leave the same switch box. The two lines at the inputs to the switch box are both connected to the un-grounded 120-volt lines from the generator. The 120-volt connection enables the Electronic Voltage Regulator (EVR) to hold the voltage very close to the 115 or 120 volts, as initially adjusted, regardless of the power distribution amount the different distribution lines. The 120-volt connection is recommended if the entire electrical load requires only 115 or 120 volts.

Although the 120/240-volt connection may also be used when all loads requires only 110 volts, it should be pointed out that this connection, the 240-volts, is regulated and the lightly loaded phase, or line, will deliver a high line to neutral voltage and the heavily loaded phase will deliver a low line to neutral voltage. The heavily loaded line may have such a low voltage that air conditioning will have more difficulty in starting, and long starting lines may overload generator and trip circuit breakers

EXCITER FIELD COIL VOLTAGE SOURCE

Field coil DC voltage is obtained by rectifying the voltage from the phase to neutral line of the generator output, or either appropriate terminal to provide the needed voltage reference.

The rectifier bridge is an internal part of the static regulator. The static regulator senses a change in the generator output and automatically regulates current flow in the exciter field coil circuit to increase or decrease the exciter field strength. An adjustable rheostat sized to be compatible with the regulator is used to provide adjustment of the regulator sensing circuit.

Page 23 of the PowerTech PTS-25 user manual — STATOR ASSEMBLY
Page 23 · click to enlarge
Page 23

ROTATING FIELD ASSEMBLY (ROTOR)

The rotating field assembly consists basically of four members: 1) the shaft assembly, 2) the core assembly, 3) the field coil damper windings, and 4) balance lugs to provide a high degree of static and dynamic balance.

CORE ASSEMBLY

The core assembly consists of a quantity of thin steel plates compressed and fastened together to form a single laminated assembly. The field windings are wound around this assembly.

FIELD COIL

Field coils of heavily insulated wire are “wet” wound directly onto the poles. Field coil leads are brought out to the rectifier assembly for connection to the source of DC excitation voltage. BALANCE The rotor assembly is precision balanced to a high degree of static and dynamic balance. Although the balance will remain dynamically stable at speeds in excess of the design frequencies, the prime mover should be adequately governed to prevent excessive over speed. High centrifugal forces created by excessive over speed may damage the rotor windings and field coils.

BEARING

The generator rotor assembly is suspended on a shielded factory lubricated ball bearing. A visual inspection of the bearing is recommended at typical service intervals. If signs of abnormal wear or leakage are observed, the bearing should be replaced. Never use liquids of any kind to clean the generator end and bearing.

STATOR ASSEMBLY

The stator assembly consists of laminations of steel mounted in a rolled steel frame. Random wound stator coils are fitted into the insulated slots.

Page 24 of the PowerTech PTS-25 user manual — DESCRIPTION PART NUMBER
Page 24 · click to enlarge
Page 24
PowerTech PTS-25 — “M” SERIES EXCITER TYPE GENERATOR ASSEMBLY diagram (page 24)
Fig. 19

**NOTE: Item #6 MAIN STATOR ASSEMBLY is a one-piece unit. The Stator cannot be separated from the Generator’s outer housing.

2. EXCITER ROTOR 02RTR1520EXC 02RTR1520EXC 02RTR1520EXC 3. EXCITER STATOR 02STA1520EXCG 02STA1520EXCG 02STA1520EXCG 4. REAR HOUSING BRACKET 02HB15TCGE 02HB175 02HB15TCGE 5. ROTOR BEARING 02BRG207 02BRG207 02BRG207 6. MAIN STATOR ASSEMBLY** 02STMN15 02STMN175 02STMN20 7. MAIN ROTOR ASSEMBLY 02RTRMN15 02RTRMN175 02RTRMN20 GENERATOR ASSEMBLY 02GEN15TCGE 02GEN175TCGE 02GEN20TCGE VOLTAGE REGULATOR 06REG634AVC 06REG634AVC 06REG634AVC

15KW 17.5KW 20KW 1. END COVER NS-GENCAN NS-GENCAN NS-GENCAN

“M” SERIES EXCITER TYPE GENERATOR ASSEMBLY

DESCRIPTION PART NUMBER

Page 25 of the PowerTech PTS-25 user manual — DESCRIPTION PART NUMBERS
Page 25 · click to enlarge
Page 25
PowerTech PTS-25 — “K” SERIES EXCITER TYPE GENERATOR ASSEMBLY diagram (page 25)
Fig. 20

Generator’s outer housing. Item #8 MAIN ROTOR ASSEMBLY is a one-piece unit. Hub, blower fan

** NOTE: Item #3 MAIN STATOR ASSEMBLY is a one-piece unit. The Stator cannot be separated from the

5. ROTOR BEARING 02BRG62206-2RS1 02BRG62206-2RS1 6. DIODE PLATE 02PLD21CR 02PLD21CR 7. EXCITER ROTOR 02RTR16EXCR 02RTR21EXCR 8. MAIN ROTOR ASSEMBLY ** 02RTR16KON 02RTR21KON GENERATOR ASSEMBLY 02GEN16EXCR 02GEN21EXCR VOLTAGE REGULATOR 02REG24 02REG24

16KW 21KW 1. BEARING PLATE 02BRPLKONCAR 02BRPLKONCAR 2. EXCITER STATOR 02STA21EXCR 02STA21EXCR 3. MAIN STATOR ASSEMBLY ** 02STAMN16 02STAMN21 4. O-RING O-RING KON O-RING KON

“K” SERIES EXCITER TYPE GENERATOR ASSEMBLY

DESCRIPTION PART NUMBERS

and coupler are included.

Page 26 of the PowerTech PTS-25 user manual — OK 5
Page 26 · click to enlarge
Page 26

ZERO OR LOW

VOLTAGE

BAD OK ON OFF OK BAD

Check Gen Fuse Check Main Breaker is “ON”

Main Coil Output to Breaker

OK

BAD

12 V Battery Test

OK 5

Show 12 more labels / short text on this page
Replace · Turn “ON” · Fuse · Breaker · Wiring To · Defective · Panel · Breaker · Check Ohm’s on · Exciter Leads · Replace Exciter · Replace Voltage Regulator
Page 27 of the PowerTech PTS-25 user manual — AVR
Page 27 · click to enlarge
Page 27

VOLTAGE TEST

Overload Output Voltage OK

Draw From equipment Check Main Breaker

AVR

may be Higher than the other

12 VOLT BATTERY TEST

One Coil Low Voltage

Both Coils Low Voltage

AVR

RPM 1800

Show 19 more labels / short text on this page
Zero · High Voltage · or Low Voltage · Check AMP · Replace · On GenSet · Check Load Distribution · One Voltage Line · Check Gen End · Sensing Voltage · Replace · Low or None · Replace · Check Connections · Replace · Stator · Stator · Check Engine · Replace Stator
Page 28 of the PowerTech PTS-25 user manual — BAD OK BAD OK
Page 28 · click to enlarge
Page 28

OVERLOAD CONDITION

BAD OK BAD OK

AVR

Conduct 12-Volt Battery Test

Engine Problem Check Stator Coil

Replace Stator Replace AVR

Show 6 more labels / short text on this page
Check AMP Draw · Check Load Distribution · Disconnect · Resistance · See Engine Troubleshooting · And Test
Page 29 of the PowerTech PTS-25 user manual — RESISTANCE CHART
Page 29 · click to enlarge
Page 29

RESISTANCE CHART

PTS MODELS “M” SERIES EXCITER TYPE KW 15 17.5 20 and 25 Marks Color Main Stator Less Than 1.0

PowerTech PTS-25 — RESISTANCE CHART diagram (page 29)
Fig. 21

Main Rotor 1.84 2.00 2.10 N/A N/A Exciter Stator 23.0 – 28.0 23.0 – 28.0 23.0 – 28.0 F+ – C Black / Black Exciter Rotor 0.655 – 0.720 0.655 – 0.720 0.655 – 0.720 N/A N/A Aux. Winding 1.0 – 1.4 1.0 – 1.4 1.0 – 1.4 E1 – E4 Black / Black “K” SERIES EXCITER TYPE

PowerTech PTS-25 — RESISTANCE CHART diagram (page 29)
Fig. 22

KW 16 21 Marks Color Main Stator 0.20 0.20 U1-V1 or

Main Rotor 3.1 3.3 N/A N/A Exciter Stator 145 145 F1 – F2 Red / White Exciter Rotor / Diode Plate Assembly 1.462 1.334 N/A N/A

Aux. Phase 0.20 Jumper N/A Black / Black Sensing Winding 0.20 0.20 N/A 16Ga. Black / Black

Page 30 of the PowerTech PTS-25 user manual — 120 VOLT CONNECTION “M” SERIES EXCITER TYPE
Page 30 · click to enlarge
Page 30
PowerTech PTS-25 — 120 VOLT CONNECTION “M” SERIES EXCITER TYPE diagram (page 30)
Fig. 23

120 VOLT CONNECTION “M” SERIES EXCITER TYPE

Page 31 of the PowerTech PTS-25 user manual — 120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPE
Page 31 · click to enlarge
Page 31
PowerTech PTS-25 — 120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPE diagram (page 31)
Fig. 24

120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPE

Page 32 of the PowerTech PTS-25 user manual — (352) 365-2777 FAX (352) 787-5545
Page 32 · click to enlarge
Page 32

MAIN STATOR 0.20 0.20 U1-V1 or U2-V2 10 GA Black / Black MAIN ROTOR 3.1 3.3 N/A N/A

SENSING WINDING 0.20 0.20 N/A 16 GA Black / Black

EXCITER STATOR 145 145 F1-F2 Red / White

AUX. WINDING 0.20 Jumper AW Black / Black

KW 16 21 MARKS COLOR

PLATE ASSEMBLY 1.462 1.334 N/A N/A

PowerTech PTS-25 — KW 16 21 MARKS COLOR diagram (page 32)
Fig. 25

AC ELECTRICAL CIRCUIT FOR “K” SERIES GENERATORS 120 VOLTS LINE TO NEUTRAL. VR2.4

RESISTANCE CHART

EXCITER ROTOR / DIODE

POWER TECHNOLOGY SOUTHEAST, INC.

(352) 365-2777 FAX (352) 787-5545

634 STATE ROAD 44 LEESBURG, FL 34748-8103

Page 33 of the PowerTech PTS-25 user manual — (352) 365-2777 FAX (352) 787-5545
Page 33 · click to enlarge
Page 33

MAIN STATOR 0.20 0.20 U1-V1 or U2-V2 10 GA Black / Black

SENSING WINDING 0.20 0.20 N/A 16 GA Yellow / Green

AUX. WINDING 0.20 Jumper AW Black / Black

EXCITER STATOR 145 145 F1-F2 Red / White

KW 16 21 MARKS COLOR

MAIN ROTOR 3.1 3.3 N/A N/A

PLATE ASSEMBLY 1.462 1.334 N/A N/A

AC ELECTRICAL CIRCUIT FOR “K” SERIES GENERATORS 120VOLTS LINE TO NEUTRAL. VR3.1A

PowerTech PTS-25 — KW 16 21 MARKS COLOR diagram (page 33)
Fig. 26

RESISTANCE CHART

EXCITER ROTOR / DIODE

POWER TECHNOLOGY SOUTHEAST, INC.

(352) 365-2777 FAX (352) 787-5545

634 STATE ROAD 44 LEESBURG, FL 34748-8103

Page 34 of the PowerTech PTS-25 user manual — (352) 365-2777 FAX (352) 787-5545
Page 34 · click to enlarge
Page 34

AC ELECTRICAL CIRCUIT FOR “K” SERIES GENERATORS 120 VOLTS LINE TO NEUTRAL 240 VOLTS LINE TO LINE

MAIN STATOR 0.20 0.20 U1-V1 or U2-V2 10 GA Black / Black MAIN ROTOR 3.1 3.3 N/A N/A

SENSING WINDING 0.20 0.20 N/A 16 GA Black / Black

EXCITER STATOR 145 145 F1-F2 Red / White

AUX. WINDING 0.20 Jumper AW Black / Black

KW 16 21 MARKS COLOR

PLATE ASSEMBLY 1.462 1.334 N/A N/A

PowerTech PTS-25 — KW 16 21 MARKS COLOR diagram (page 34)
Fig. 27

RESISTANCE CHART

EXCITER ROTOR / DIODE

POWER TECHNOLOGY SOUTHEAST, INC.

(352) 365-2777 FAX (352) 787-5545

634 STATE ROAD 44 LEESBURG, FL 34748-8103

Page 35 of the PowerTech PTS-25 user manual — MAIN ROTOR 3.1 3.3 N/A N/A
Page 35 · click to enlarge
Page 35

SECTION 4 “INSTALLATION” SAFETY PRECAUTIONS 1-2 Hot Piping Dangerous Fuels Explosive Battery Gases Electrocution Moving Parts High Voltage Explosion Hot Coolant Lethal Exhaust Gas Excessive Noise Electrical Shock Backfire Flash Fire Fire Hazard Marine Application Unit Starts Without Notice Loose Components GENERATOR INSTALLATION in RECREATIONAL VEHICLES 3-6 Introduction Marine Application General Information Specification Charts Fuel Consumption in Gallons per Hour Installation Factors Generator Compartment Size Compartment Frame Air Requirements Air Requirements Cont’d SYSTEMS CONNECTION 7-12 Remote Radiator Cooling System Remote Radiator Cooling System with AC Fan Remote Radiator Cooling System with DC Fan Fuel System Exhaust System Fuel Line Diagram ELECTRICAL CONNECTIONS 13-15 Electrical Wiring AC Load Lead Connections Motor Loads Kilowatt De-Rating Electrical Loads Appliance Loads Extension Cords ENGINE CONTROLS 16-19 ES52F Engine controller GAC ESD2110 Series Speed Control Unit PT-ECU-63 Engine Control Module WIRING SCHEMATICS

12 Volt DC Engine Control, PT-ECU-63 12 Volt DC Engine Control, New Kubota Run Solenoid 12 Volt DC Engine Control for 200 / 300 / 400 Series 12 Volt DC Engine Control for 200 / 300 / 400 Series with Electronic Governor 12 Volt DC Engine Control for 500 Series ES52F Auto Start System with Latching Relay

Page 36 of the PowerTech PTS-25 user manual — SAFTEY PRECAUTIONS
Page 36 · click to enlarge
Page 36

SAFTEY PRECAUTIONS

A generator set can be potentially dangerous if not properly maintained and operated. The best Safe Guard against a dangerous situation is education, good judgment and common sense. For safe trouble free operation of your generator set some general precautions are listed below. Be sure to read, understand and follow these precautions. Please call Power Technology Southeast, Inc. with any concerns you may have with your generator set. 1) HOT PIPING: An engine and exhaust system may get extremely hot while running. Do not work on a generator set until it has sufficiently cooled. 2) DANGEROUS FUELS: Use extreme caution when handling, storing and using fuels. All fuels are highly explosive in a vaporous state. Store fuel in a well ventilated area away from spark producing equipment. Keep fuels and all chemicals out of the reach of children. Never add fuel to the tank while the engine is running. Spilled fuel may ignite on contact with hot parts or from ignition spark. Always keep fuel lines and connections tight and in good condition. Don’t replace flexible fuel lines with rigid lines. If you notice any fuel leakage, fuel accumulation or electrical sparks, DO NOT OPERATE THE GENERATOR SET. 3) EXPLOSIVE BATTERY GASES: The gases generated by a battery being charged are highly explosive. Do not smoke or permit any flames or sparks to occur near a battery at any time, especially when it is being charged. Avoid contact between terminals with tools to prevent sparks and possible burns. Always remove wristwatch, rings, or other jewelry before handling a battery. Any compartment containing batteries should be well ventilated to prevent the accumulation of explosive gases. To avoid sparks never disturb the battery charging connections while the battery is being charged. Always turn off the battery charger before disconnecting terminal clips. 4) ELECTROCUTION: Failure to install a generator set with an electrical system consistent with governing regulations and standards is UNLAWFUL and may cause ELECTROCUTION of vehicle occupants. Your generator set must not be used to “Back Feed” by connecting it to a building or outdoor electrical circuit. Back feeding can cause serious injury or death to utility personnel working to repair a power outage and may also seriously injure persons in your vehicle. Unauthorized connections are unlawful in some states and/or localities. A transfer switch must be installed to prevent interconnection of the generator set power and outside power. 5) MOVING PARTS: Keep hands, feet, and clothing away from belts and related pulleys when unit is running. Replace guards, covers, and screens before operating the generator set. Serious personal injury may occur from contact with moving parts. 6) HIGH VOLTAGE: Remember the function of a generator set is to produce electricity. Wherever electricity is present there is a potential danger of electrocution. Apply the same precautions to the vehicles electrical appliances as you would for any home appliance. Keep away from electrical circuits and wiring while the generator set is running. Have electrical service performed only by qualified electricians. Be sure any unauthorized person; especially children are denied access to the generator set. Keep the compartment door securely latched or locked at all times. Be sure the generator is properly grounded. Never touch electrical leads or appliances with wet hands, or when standing on wet ground.

Page 37 of the PowerTech PTS-25 user manual — SAFTEY PRECAUTIONS
Page 37 · click to enlarge
Page 37

7) EXPLOSION: Never connect the negative (-) battery cable to the positive (+) connection terminal of the starter solenoid, or test the battery by shorting terminals together. This could ignite fuel vapors or cause the battery to explode. To disconnect the battery remove the negative battery cable first and reconnect it last. Do not modify the fuel tank or propulsion engine fuel system. Your vehicle must be equipped with a fuel pick-up arrangement as described in the Fuel System section of this manual. Fuel tank and installation must conform to applicable regulations. 8) HOT COOLANT: Allow engine to cool and release pressure from the cooling system before opening the radiator pressure cap. To release the pressure, cover the radiator cap with a thick cloth then turn it slowly counterclockwise to the first stop. After the pressure is released and the engine has cooled, remove the cap. 9) LETHAL EXHAUST GAS: When installing an exhaust system position the tail pipe end so that the discharged gases may not be drawn into the vehicle interior through windows, doors, air conditioners, etc. The engine powering your generator set discharges deadly carbon monoxide as part of the exhaust gas when running. It is essential that the exhaust system be leak proof and routinely inspected. 10) EXCESSIVE NOISE: Never operate the generator set without an adequate muffler or with a faulty exhaust system. Exposure to excessive noise can lead to a hearing impairment. 11) ELECTRICAL SHOCK: A battery can cause electrical burns and shocks. Use reasonable care when working near the battery to avoid electrical connections by contacting the battery terminals with tools. Remove wristwatch, rings and all jewelry when working on the generator set. 12) BACKFIRE: A sudden backfire can cause serious burns. Do not operate your generator set without its air cleaner / flame arrestor in place. 13) FLASH FIRE: A sudden flash fire can cause serious burns. To avoid the possibility of a flash fire do not smoke or permit a flame or spark to occur near the carburetor, fuel lines, fuel filter, fuel pump or other potential source of spilled fuel or vapors. 14) FIRE HAZARD: Be careful when parking your vehicle to prevent grass fires from being started by hot exhaust gases or exhaust system. Keep away from hot engine and generator parts to avoid burning yourself. Keep the generator set and compartment clean and free of debris, especially combustible materials. Never store fuel, oil or rags in the generator compartment. 15) MARINE APPLICATION: RV generator sets do not comply with United States Coast Guard (USCG) requirements. They must not be used for marine applications. Use only generator sets specified for marine use in a marine application. USCG regulation 33CFR183 requires a generator set to be ignition protected for use in a gasoline-fueled environment. 16) UNIT STARTS WITHOUT NOTICE: To prevent accidental starting on the units with remote start / stop switch, always disconnect the battery by removing the negative (-) terminal first and then the positive (+). Always disconnect the unit in this manner before working on the generator or any equipment connected to it. 17) LOOSE COMPONENTS: Periodically check for and tighten any fasteners that may have become loose from vibration or road shock. Serious damage may possibly occur if components become dislodged or misaligned.

Page 38 of the PowerTech PTS-25 user manual — GENERAL INFORMATION
Page 38 · click to enlarge
Page 38

GENERATOR INSTALLATION in RECREATIONAL VEHICLES

INTRODUCTION Use this section as a guide when installing a generator set in a recreational vehicle, and then refer to the appropriate operation section for specific instructions. When installing a RV generator set the installation must comply with current standards of ANSI / RVIA EGS-1, ANSI A 119.2 / NFPA 501C, and applicable articles of ANSI / NFPA 70 of the National Electrical Code. Generator set installations must also comply with state and local requirements.

MARINE APPLICATION

RV generator sets do not comply with United States Coast Guard (USCG) requirements and must not be used for marine applications. Use only generator sets specified for marine use in marine installations. USCG regulation 33CFR183 requires a generator set to be “ignition protected” when used in a gasoline fueled environment.

GENERAL INFORMATION

This information section covers the RV generator set models listed below. To determine which model is involved, check the model number found on the Power Technology nameplate attached to the frame of the generator being installed. Follow all instructions to ensure proper installation and operation. Each generator set features a Kubota diesel engine, rotating-field alternating current generator, and a relay controller. The generator is directly connected to the engine for permanent alignment. Each controller includes a Start / Stop switch for test operating the set at the controller. Also included is an On /Off switch to reset the controller or lockout any remote switch to prevent starting while service is being performed. The controller may be equipped with a switch to operate the mechanism used to move the generator out of the coach for servicing. (Supplied by the coach manufacture). After the set is attached to the frame of the vehicle, all that is usually required to make it operational is the following. 1. Attaching the exhaust system. 2. Add proper amount of radiator coolant. 3. Add oil to crankcase, to the dipstick FULL mark. 4. Connect fuel lines, remote switch, load leads and battery terminals. (Consult the Specification Charts on the Following Pages for Requirements)

PowerTech PTS-25 — GENERAL INFORMATION diagram (page 38)
Fig. 28

MODEL PTS-15 PTS-17.5 PTS-20 and 25 GENERATOR DIMENSIONS L x W x H 46.5” x 23.0” x 32.0” 47.0” x 23.0” x 32.0” 48.0” x 23.0” x 32.0” WEIGHT 830 840 850 ENGINE Kubota V-1903-BG Kubota V-2003-T Kubota V-2203-BG RPMs 1800 1800 1800 KW RATING 15 17.5 20 AC VOLTAGE 120 / 240 120 / 240 120 / 240 AMPERAGE 125 / 63 146 / 73 166 / 83 Hz 60 60 60 PHASE 1 1 1 GENERATOR COMPARTMENT FREE AIR OPENING

400 Square Inches RADIATOR AIR REQUIREMENTS 2120 CFM 2120 CFM 2120 CFM

Page 39 of the PowerTech PTS-25 user manual — AIR REQUIREMENTS
Page 39 · click to enlarge
Page 39

GENERATOR COMPARTMENT SIZE

In planning the size of the generator compartment or bay allow for the minimum clearance necessary to adequately cool the generator set. The thickness of insulation and sound deadening material used to line the compartment must be taken into consideration when planning this clearance. To maintain minimum clearance it may be necessary to enlarge the compartment. The generator set must be securely fastened to avoid unwanted movement from vibration and road shock. If the unit is equipped with a mounting tray the tray is usually supported on the ends by angle iron and has a full door for service access. Be sure to use all mounting holes in the tray to secure the tray to the vehicle support structure. Units not equipped with mounting tray are secured by attaching Genset mounts (two in front, two in rear) directly to the vehicle frame. Skid mounted units can either be affixed to a tray for tray mounting or attached directly to the vehicle frame. The generator is easily removed from the coach if a carriage with rollers is incorporated into the support structure. When designing the compartment allow sufficient access for routine maintenance and for removal when major service is required. Also keep in mind that the compartment door must have air intake opening having a free area equal to or greater than that specified under the “Air Requirements” section of this manual. Make sure that the compartment is vapor tight and completely sealed off from the inside of the vehicle to prevent exhaust or other items from entering the vehicle. Avoid road splash and the possibility of igniting combustible materials beneath the coach by enclosing all unnecessary free space beneath the generator compartment. Line the compartment with a good sound deadening material. The material selected must be fireproof or highly fire resistant. An available type of 3-layer foam material is very efficient for absorbing sound. This type of material is easily cut to size with scissors and can be quickly installed using special fire resistant adhesive which bonds the material to almost any clean dry surface. Other materials such as fiberglass insulation with heat barrier have also been used successfully in mobile installations.

COMPARTMENT FRAMING

The generator must be bolted to a metal frame, which is either bolted or welded to the frame of the vehicle. This frame must be designed to withstand a minimum force of 5Gs in any direction. The frame must support the entire base plate around the outer perimeter and center section. Additional framing may be required if excessive vibration occurs.

AIR REQUIREMENTS

Each engine is equipped with a high water temperature shutdown switch, which will automatically shut down the set if the operating temperature climbs too high. To prevent the generator set from shutting down make sure the compartment openings are large enough to allow adequate circulation of cooling air. The minimum free air opening in the compartment door is 400 sq. in. or 2580 sq. cm. Remember that louvers, screens and protective grills will restrict airflow. A relatively open mesh screen will restrict airflow as much as 45%. The intake opening must be increased to compensate for such restrictions.

Page 40 of the PowerTech PTS-25 user manual — INSTALLATION FACTORS
Page 40 · click to enlarge
Page 40

SPECIFICATION CHARTS

PowerTech PTS-25 — SPECIFICATION CHARTS diagram (page 40)
Fig. 29

FUEL CONNECTION ¼” NPT FUEL RECOMMENDATION DIESEL FUEL No.1-D or No.2-D ASTM / D975 BATTERY VOLTAGE 12 VOLTS DC BATTERY CRANKING AMPS 420 BATTERY COLD CRANKING AMPS 590 MINIMUM BATTERY GROUND NEGATIVE

FUEL CONSUMPTION IN GALLONS PER HOUR

LOAD PERCENTAGE 15KW 17.5KW 20KW and 25KW 25% .33 GPH .39 GPH .45 GPH 50% .67 GPH .79 GPH .90 GPH 75% 1.01 GPH 1.18 GPH 1.35 GPH 100% 1.35 GPH 1.57 GPH 1.80 GPH

PowerTech PTS-25 — FUEL CONSUMPTION IN GALLONS PER HOUR diagram (page 40)
Fig. 30

INSTALLATION FACTORS

Each generator set is received as a unit except for the optional exhaust system components, which are shipped loose for assembly after the set is installed in the vehicle. When preplanning the installation, the following factors must be considered. 1. COMPARTMENT SIZE: Will there be sufficient room around the set to maintain the minimum clearance of one inch? 2. AIR REQUIREMENTS: Are the compartment air inlets and outlets sized to allow adequate circulation of air for cooling and combustion? 3. COMPARTMENT FLOOR: Is the compartment floor strong enough to support the weight of the generator set? 4. COOLING SYSTEM: Is the cooling system large enough to adequately cool the generator set? ** 5. FUEL SYSTEM: Is the fuel system properly designed to prevent fuel starvation of either the main engine or generator engine? 6. EXHAUST SYSTEM: Will the exhaust system meet all safety requirements after installation? 7. ELECTRICAL CONNECTIONS: Will all systems, (battery, load and remote switch) be compatible with the vehicles system?

** NOTE: When using a radiator not supplied by Power Technology consult your radiator manufacturer to ensure that heat rejection values are met.

Page 41 of the PowerTech PTS-25 user manual — AIR REQUIREMENTS CONT’D
Page 41 · click to enlarge
Page 41

AIR REQUIREMENTS CONT’D

PowerTech PTS-25 — AIR REQUIREMENTS CONT’D diagram (page 41)
Fig. 31

15KW 17.5KW 20KW and 25KW ENGINE SPEED IN RPM 1800 1800 1800 OUTPUT IN HORSEPOWER 26 36.6 32.5 WATER FLOW – GAL. / MIN. 7.93 8.75 8.75 ENGINE INLET WATER TEMP. N/A N/A N/A THERMOSTAT – RATING 180°F 180°F 180°F THERMOSTAT FULL OPEN 195°F 195°F 195°F ENGINE OUTLET WATER TEMP.MAX. 230°F 235°F 235°F HIGH TEMP. SHUTDOWN SITCH 230°F 230°F 230°F HEAT REJECTION – BTU / MIN. 1295 1650 1650 HEAT REJECTION – BTU / HR. 77,700 99,000 99,000 AIR FLOW – CU. FT. / MIN. 2120 2120 2120 ENGINE OIL TEMP. MAX. 268°F 268°F 268°F COMBUSTION AIR TEMP. * N/A N/A N/A

* Combustion Air Temperature: The output of the engine will decrease about 1% for every 10°F of air temperature above 77°F or 25°C. IMPORTANT: Insulation and Sound Absorbing Material used inside of the generator compartment Must Not reduce the specified airspace clearances or restrict the airflow around the generator. Such reduction in airspace may lead to an overheating situation and reduced generator performance. Also be sure the air inlet and outlet openings meet the specified requirements. Allow clearance inside the generator compartment for easy access when routine maintenance is required. WARNING: The generator compartment Must Be sealed to prevent hazardous fumes and vapors from entering the vehicles other compartments and interior spaces. Plugging holes and sealing all seams will greatly reduce this hazard.

Page 42 of the PowerTech PTS-25 user manual — REMOTE RADIATOR ASSEMBLY
Page 42 · click to enlarge
Page 42

SYSTEMS CONNECTION

REMOTE RADIATOR COOLING SYSTEM Use the following data in designing and installing the generator set cooling system. To insure a safe effective installation, be sure the cooling system selected follows these parameters. Power Technology offers radiator assemblies, which meet these requirements and will adequately cool the generator. Select the radiator assembly best suited for the generator installation. Due to the multitude of coach manufacturers and the variety of generator installations, only general guidelines are provided. Adapt these recommendations to the installation. In a typical installation the radiator assembly is installed in the same compartment as the generator. If a blower fan radiator assembly is used, cooling air is drawn across the generator and engine and then through the radiator. If a suction fan radiator assembly is used the suction fan pulls cooling air through the radiator and then past the generator set. If the radiator assembly alone is used the installer must supply an electric blower or suction fan to circulate the cooling air. See the specification table for total air requirements. Depending on space limitations the radiator can be located in front of, adjacent to, or in a ventilated remote location from the engine compartment, no more than 10 feet from the generator. To prevent re- circulation of heated air be sure to maintain a tight seal between the radiator and the discharge chute. Generally the discharge chute opening should be approximately one and one half times the size of the radiator core. NOTE: If the radiator is to be located in a compartment separate from the engine, refer to the engine combustion air and heat rejection requirements of the generator and engine block when designing the cooling system. A supplemental cooling fan capable of 500cfm (28.m³/min) should be installed to supply air to the generator compartment for these requirements. Connect the radiator fan motor to the generator output leads L1 and L2. Be sure the radiator fan motor rotates in the correct direction and is of the proper voltage. To protect against overload and short circuits it is recommended that the motor be adequately fused. Install fuses between the motor and L1 / L2 connection. A close relationship exists between the cooling system design and the generator compartment size. Availability of space is often the determining factor in the cooling system design. See the “Compartment Size” section of this manual prior to designing and installing the generator cooling system. CAUTION: The fill inlet and reservoir tank must be located at the highest point in the cooling system. If the fill inlet is not located as directed, coolant will not completely fill the engine. The cooling system must be purged of all air pockets for the system to function properly. If air pockets remain in the engine the high water temperature shutdown switch will malfunction and cause the engine to over heat. Also if the cooling system is not completely full, the low water level shutdown switch will prevent normal engine operations.

PowerTech PTS-25 — SYSTEMS CONNECTION diagram (page 42)
Fig. 32

REMOTE RADIATOR ASSEMBLY

Page 43 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 43 · click to enlarge
Page 43
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 43)
Fig. 33
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 43)
Fig. 34
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 43)
Fig. 35
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 43)
Fig. 36
Page 44 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 44 · click to enlarge
Page 44
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 44)
Fig. 37
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 44)
Fig. 38
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 44)
Fig. 39
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 44)
Fig. 40
Page 45 of the PowerTech PTS-25 user manual — EXHAUST SYSTEM
Page 45 · click to enlarge
Page 45

SYSTEMS CONNECTION

FUEL SYSTEM

The diesel fuel system for the generator set must be designed to operate independently from the vehicles main engine if both engines are to be operated at the same time. The best way to do this is to have separate fuel tanks, but this is usually impractical because of space restrictions. In most installations both engines operate from a common fuel tank with separate pick-up tubes for each engine, not a Tee fitting arrangement. This prevents either or both engines from being starved for fuel. The generator set fuel pick-up tube is generally shorter than the vehicles; therefore fuel may not be available to the generator when fuel supply is low. This will prevent the generator from depleting the fuel supply needed by the main engine. NOTE: Using a simple Tee fitting to supply both engines from a common fuel line is not recommended. This practice may possible cause a fuel starvation situation to either or both engines. Also, if excessive pressure were to build up in the main supply line it could possible cause a failure of the generators fuel lines or connectors and a hazardous fuel leak may occur. Care must be taken when routing the fuel line from the main tank to the generator set. Keep the fuel line as short as possible while maintaining adequate clearance from the exhaust system. Fuel lines must be run along the frame side rails or coach under carriage. Never run fuel lines inside of the coach. Securely fasten the fuel lines with hardware that is recommended for the type of fuel line used. The fuel lines should enter the generator compartment at a point nearest to the generators fuel line connection fittings. Allow for a minimum of 8inches of flexible fuel line to make the connection. Use proper size fuel line to accommodate the fuel flow needed. Steel fuel line or high quality fuel hose is recommended, either one should have a minimum of ¼” ID and strong enough to withstand road and climatic conditions.

EXHAUST SYSTEM

Exhaust system components will vary from one installation to another; therefore a muffler and tailpipe may not always be furnished with the Genset. However, it is imperative to install a muffler and tailpipe to reduce exhaust noise and direct exhaust gases beyond the vehicles perimeter and away from the normal head-on air stream. Install a tail pipe with as few bends as possible to prevent excessive backpressure. A properly installed exhaust system must be vapor tight, quiet and completely safe for the vehicle, its occupants and surroundings. Installation of an approved Spark Arrestor is highly recommended. The exhaust system components must be approved and properly installed to meet the codes and regulations required by Federal and State agencies. Exhaust Mufflers and Spark Arrestors supplied by Power Technology meet code and standard requirements set forth by the USDA Forest Service. Laws pertaining to application and maintenance of a Spark Arrestor may vary depending on your location and State regulations. Federal laws apply on Federal lands. If a generator is used in a forest, on brush or grass covered unimproved land it must be equipped with a Spark Arrestor. It is the responsibility of the vehicle owner or operator to install and maintain the entire exhaust system in good working condition. CAUTION: Any person (s) who installs an unapproved Muffler, Spark Arrestor or other exhaust system component, and/or modifies an exhaust system or component that may result in a hazardous condition is liable for damages, injuries or warranty expense caused by such unapproved installation and/or modification.

Page 46 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 46 · click to enlarge
Page 46

EXHAUST SYSTEM IMPORTANT SAFETY TIPS: When exhaust system components are not furnished by Power Technology as part of the Genset, the installer is responsible for meeting the following requirements.

1) Only use exhaust system components, which do not restrict exhaust flow. A restricted exhaust system will create excessive backpressure and may cause poor engine performance and possible engine damage. 2) Maintain a minimum of 3 inches (76mm) between the exhaust system components and any surrounding combustible materials. If the minimum clearance cannot be maintained, an insulating shield must be installed to prevent the combustible material from exceeding temperatures of 117°F (65°C) above ambient temperature. 3) Extend the exhaust system a minimum of 1 inch (25mm) beyond the vehicles perimeter. Never terminate the exhaust system underneath the vehicle. 4) Terminate the exhaust system in a direction, which prevents the exhaust gases from being drawn back into the generator compartment and re-circulated. 5) If the exhaust system in located in an area which may become susceptible to road damage from curbs, speed bumps, or other road obstacles a protective device such as a skid bar or plate should be installed. 6) To prevent excessive movement and vibration of the exhaust system, install hangers and clamps designed for use in exhaust systems. 7) Never join or tee the generator exhaust system and the vehicle exhaust system together. Doing so may cause excessive back pressure on the generator engine, also condensation from one engine can damage the other engine. WARNING: LETHAL EXHAUST GAS! When installing the exhaust system position the tail pipe end so that discharged exhaust gases are not drawn into the vehicle interior through windows, doors, air conditioners, etc. During operation an engine discharges deadly carbon monoxide with its exhaust. Carbon monoxide is particularly dangerous since it is odorless, tasteless, and non-irritating. It can cause death if inhaled for even a short period of time. Be especially careful if operating the generator set when parked under calm, windless conditions. Gases may accumulate in these conditions. Park your vehicle so that the exhaust discharges downwind. Always be aware of others in your vicinity. Make sure that your exhaust discharges away from other vehicles and buildings. CAUTION: Make sure the exhaust system components are positioned well away from drain openings beneath the generator set. Also, be sure not to block access to the oil drain plug.

Page 47 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 47 · click to enlarge
Page 47
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 47)
Fig. 41
Page 48 of the PowerTech PTS-25 user manual — AC LOAD LEAD CONNECTIONS
Page 48 · click to enlarge
Page 48

ELECTRICAL CONNECTIONS

ELECTRICAL WIRING

All wiring must be applicable with local electrical codes. A qualified licensed electrician must perform all electrical wiring connections. Ground Fault (GFCI) breakers must be installed to protect all vehicle branch circuits. All switches and controls must be securely mounted to prevent damage and accidental opening or closing from vibration, road shock and vehicle motion. Battery, load leads and the remote switch panel connections are necessary for completing the installation. Make final connections to the battery only after all other connections have been made, as this will prevent unintentional starting. Some specific details on each connection are stated in the following paragraphs. Refer to the wiring diagram for specific details. All wiring to the generator set shall be securely supported or harnessed to prevent abrasion. Additional support is required to prevent exposure to the exhaust system and any possible leakage of fuel, oil, or grease. At least 2 inches of clearance must be maintained between electrical wiring and hot exhaust parts. Wiring must not be located directly below or close to the fuel system, oil fill and drain locations. If the coach is equipped with a mechanism for removing the generator set from the compartment such as a mounting base or slide rack, be certain all wiring is long enough to allow for free movement of the generator for servicing. A separate 12-volt battery is recommended for the generator set. With a separate battery, cables should be kept short in length thus eliminating problems with excessive voltage drop. See the Table below for cable size (AWG) to length requirements. NOTE: A heavy gauge #4 ground strap must be connected between the ground lug on the generator set and the frame of the vehicle. All wiring connections made at the time of installation should be readily accessible for periodic inspection and servicing.

DISTANCE BETWEEN GENERATOR SET AND

CABLE SIZE (AWG) REQUIREMENTS

AT VARIOUS TEMPERATURES

BATTERY

0°F (-18°C) 32°F (0°C) 75°F (24°C) 40’ (12.2M) 00 0 1 30’ (9.2M) 0 1 2 25’ (7.6M) 1 2 4 20’ (6.1M) 2 2 6 15’ (4.6M) 2 4 6 10’ (3.0M) 4 6 8 5’ (1.5M) 6 6 8 2.5’ (0.8M) 8 8 8

AC LOAD LEAD CONNECTIONS

Some generator sets have four color-coded leads. The Black leads (L1 & L3) are hot. The White or Gray lead (L2) is neutral and the Green lead is ground. The load leads can be routed directly from the junction box to the vehicle AC circuit or transfer switch connection. All installations require that the load leads be routed through flexible conduit from the generator end bracket to the junction box location. The load lead junction box must be accessible for servicing and inspection. AC load lead (L2) White or Gray is always the neutral lead on PTS generator sets. Make sure the neutral of the AC circuit in the vehicle is connected to the (L2) White or Gray lead. If equipment ground type plugs and receptacles (3 prong) are used in the vehicle, the green wire must be connected to the chassis ground. On vehicles, which also have provisions for using an outside AC, power source, the neutral lead as well as the Black (L1 & L3) hot leads must be completely isolated from the generator set when power is switched to the outside source.

Page 49 of the PowerTech PTS-25 user manual — BASED ON CODE “G” ELECTRIC MOTOR ELECTRIC MOTOR
Page 49 · click to enlarge
Page 49

MOTOR LOADS

When figuring generator set capacity requirements for installation involving motor loads, do not overlook the high current demanded by the motor during start-up. The “In-Rush” of starting current may be 2 to 5 times higher than that required when the motor reaches normal operating speed. Reserve capacity must be allowed for in rush demands plus other loads, which could be on the line as the motor starts.

Air conditioning units are the most common type of motor loads for a generator set in a recreational vehicle. The starting characteristics of the different makes of air conditioners vary greatly. For example, a particular 12,000 BTU unit may have lower starting requirements than a 10,000 BTU unit of another make. When only one unit is involved there is usually no starting problem provided of course the lighting and appliance load is not too high when unit is started. The trend seems to be toward larger capacity air conditioners and the use of more than one unit in larger vehicles. Simultaneously starting two large units can present a problem if the capacity is marginal. Because of the variation in starting characteristics of the different makes of air conditioners, no definite statement can be made in this publication regarding multiple-motor starting capabilities.

Delayed starting or use of “easy starting” devices on air conditioner units should be considered whenever simultaneous starting of more than one motor is involved. The starting and running requirements of some motor loads common to mobile applications are listed in the table below. Use this as a guide when selecting generator set capacity requirements involving motor loads. Also note the Kilowatt De-rating factor for generator set capabilities regarding air conditioners. Capabilities will vary according to “Kilowatt De-rating”.

BASED ON CODE “G” ELECTRIC MOTOR ELECTRIC MOTOR

HORSEPOWER STARTING WATTS RUNNING WATTS ½ 2000 1100 1 3800 1800 2 6000 2800 3 8000 4000 4 11000 5500 5 13000 6500

KILOWATT DE-RATING All units are rated at 1.0 power factor. The Kilowatts of the generator set will decrease 3.5% per 1,000 feet (305m) above 500 feet (152m) above sea level. De-rate 1% for every 10 °F (5.5°C) above 68°F. ELECTRICAL LOADS While the electrical load of the vehicle should have been calculated prior to purchase of the generator set, you may want to recheck the load before installing the set to make sure the capacity is ample to meet the demands without possible overloading. The lighting load is usually easiest to calculate in most cases, simply add the wattage of each lamp to be operated off the generator set. Note that in many applications, not all of the lights or lamps are in the generator sets AC circuit. Some are DC powered by the 12-volt battery in the vehicle. Make sure the total includes only lights actually on the generator sets AC circuit. The lighting load is usually not to heavy in mobile installations however it must be accurately calculated to prevent overloading. For example, if all lights are on at the same time and the air conditioner or other motor equipment starts up, this may possibly cause an overload situation.

Page 50 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 50 · click to enlarge
Page 50

APPLIANCE LOADS Generator sets in recreational vehicles are often used to supply AC voltage for appliances. With the exception of a resistance-type load such as a water heater, requirements for appliances are usually low. However, such loads must not be overlooked when calculating the total wattage requirements. To avoid an overload situation, reserve capacity should also be calculated for unanticipated appliance loads. The average power requirements for some common electrical appliances are listed below as a guide.

DETERMINING ALTERNATOR LOAD REQUIREMENTS CHECK √ APPLIANCE WATTS REQUIRED VCR 70 LIGHT BULB 100 RADIO 100 TELEVISION 100 STEREO 100 FRY PAN 150 HOME COMPUTER 150 VACUUM CLEANER 250 ATTIC FAN 1/4 HP 400 SUMP PUMP 1/3 HP 500 REFRIGERATOR 500 FURNACE FAN 1/3 HP 600 FREEZER 800 JET WATER PUMP ¾ HP 900 ELECTRIC STOVE ELEMENT 1000 SUBMERSIBLE WATER PUMP 1 HP 1000 TOASTER 1000 COFFEE MAKER 1200 DISHWASHER 1200 HAIR DRYER 1200 MICROWAVE OVEN 1500 SUBMERSIBLE WATER PUMP 2 HP 1600 WATER HEATER 3000 OVEN 4500 TOTAL WATTS CHECKED

PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 50)
Fig. 42

EXTENSION CORDS An extension cord is normally used to provide electrical power from the generator set to a remote location. The extension cord size (AWG#) and length must be adequate to safely maintain the amperage requirements. A proper size extension cord will help minimize the voltage drop between the generator set and remote location.

PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 50)
Fig. 43

AMPS LOAD IN WATTS CORD LENGTH 120 VOLTS 240 VOLTS AWG#10 AWG#12 AWG#14 5 600 1200 500 FT 300 FT 200 FT 10 1200 2400 250 FT 150 FT 100 FT 20 2400 4800 125 FT 75 FT 50 FT 30 3600 7200 60 FT 35 FT 25 FT 40 4800 9600 30 FT 15 FT 10 FT 50 6000 12000 15 FT

Page 51 of the PowerTech PTS-25 user manual — “LED” INDICATORS
Page 51 · click to enlarge
Page 51

ES52F ENGINE CONTROLLER

The ES52F Engine Controller is designed to enable automatic Start/Stop capability as well as providing fault protection for the generator. The ES52F will automatically Start the generator upon command and will monitor vital engine and generator functions. In the event a failure was to occur, the ES52F will automatically Stop the engine thus preventing further problems. CAUTION: To prevent automatic or accidental Starting or short circuit, disconnect the 12V DC power source before performing any maintenance or repairs. Turn OFF the Master Disconnect Switch or disconnect the 12V DC power at the battery. SPECIFICATIONS: 3.3V DC to 30V DC Operating Limits. 12mA Standby Current Draw. 175mA Operating Current Draw. Internally Protected against Reverse Polarity. Speed Sensing accepts Generator AC Output. Speed Sensing rated to a Maximum of 300V AC. -40°C to +85°C Operating Temperature.

ES52F “LED” INDICATIONS

LED Indication Condition / Failure No LEDs ON “Ready” unit waiting for start signal,+12/24V DC to Auto terminal. “Off”, no +12/24V DC to Auto terminal. Low Oil, steady Low Oil Pressure Failure Low Oil, flashing Auxiliary Input Failure High Temperature, steady Over Temperature Failure Over-Crank, steady Engine would not start after specified Crank tries. Engine Running, steady Engine Controller is in running mode of operation. Engine Running, flashing Crank-rest period. Cranking will resume soon. Preheat On, steady Glow Plug timer feature – With jumper in place, preheat is set for 8 seconds. With jumper removed or cut, preheat is set for 16 seconds.

“LED” INDICATORS

PowerTech PTS-25 — “LED” INDICATORS diagram (page 51)
Fig. 44
Page 52 of the PowerTech PTS-25 user manual — TROUBLESHOOTING
Page 52 · click to enlarge
Page 52

TROUBLESHOOTING

Trouble Possible Cause Suggested Action Power leads to unit are reversed.

Confirm correct wiring for ground And bat, and re-attempt testing. Unit does not operate when powered to test mode

Bad ground connection from engine to controller unit.

Run wire directly from battery – to the ground terminal #6 on controller unit. Battery is low or terminals are dirty.

Engine doe not crank

Clean terminals and re-charge battery. Replace battery if necessary. Crank circuitry wiring improperly connected.

Refer to engine control wiring and check crank connections. Bad ground connection from engine to controller.

Run wire directly from battery – to the ground terminal #6 on controller unit.

Crank relay damaged. Or on board fuse is blown.

Check wiring, on board 10A fuse and relay. Replace fuse, relay and re-test controller again. Out of fuel. Check fuel level, add fuel if necessary. Ignition control wiring not installed properly

Engine cranks but doesn’t start

Refer to engine control wiring and check ignition connections.

Fuel relay damaged Check fuel relay and replace if damaged. Engine starts but shuts down after “Oil Bypass period” due to low oil / high temp / extra.

Oil / temp. / extra input wiring improperly connected.

Check wiring for proper connections.

Engine starts, but running LED does not illuminate.

Check for fault, once fault is corrected then operation resumes. Annunciation output not working Fault (short or overload) on one of the annunciated outputs.

Fault (short or overload) on one of the annunciated outputs.

Check for fault, once fault is corrected then operation resumes. Preheat LED works OK but timer output does not activate

Check for fault, once fault is corrected then operation resumes.

Fault (short or overload) on timer output.

Page 53 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 53 · click to enlarge
Page 53

GAC ESD2110 SERIES SPEED CONTROL UNIT The ESD2110 Speed Control Unit is part of an engine governing system designed to control engine speed and stability throughout the load range. Operating in combination with a magnetic pick-up and electric actuator the ESD2110 will maintain the proper engine speed by adjusting the fueling system according to the applied load. By maintaining a set engine speed the generator voltage output and frequency will remain constant and stable.

PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 53)
Fig. 45
Page 54 of the PowerTech PTS-25 user manual — PT-ECU-63 ENGINE CONTROL MODULE
Page 54 · click to enlarge
Page 54

PT-ECU-63 ENGINE CONTROL MODULE

1) Generator Main Switch must be in the ON position. 2) Hold Start/Stop Switch for 1 second and release. 3) Glow Plugs will preheat for 8 seconds. LED flashes slowly. 4) Preheating will cease during engine cranking cycle. LED continues flashing. 5) Engine begins an 8 seconds crank cycle, After 4 seconds of cranking the PT-ECU-63 will check for an AC signal from the generator. If an AC signal is verified the engine will start and the LED will remain ON during the normal run operation. If the AC signal is not verified the PT-ECU-63 will terminate the cranking cycle and LED will flash a fault code. 6) Starter disengages immediately after engine run is verified. 7) PT-ECU-63 deactivates the Low Oil Pressure and High Water Temperature Switches for 6 seconds, this will assure oil pressure build-up time. If oil pressure does not build-up the engine will immediately shut down and go into a fault mode. Likewise for a high temperature situation. 8) If engine will not start on the first attempt the PT-ECU-63 will initiate the start cycle 2 more times before going into a fault mode. Glow Plugs will preheat for 8 seconds per attempt. Engine will crank for 8 seconds per attempt. 9) To shut down the engine under normal operations, hold the Start/Stop Switch for 1 second and release. 10) If a fault occurs turn Generator Main Switch OFF and then ON to reset PT-ECU-63.

Fault Codes: LED Flashes Failure to start 1 Engine High Water Temperature 2 Low Oil Pressure 3 No AC Signal 4 Low Coolant Level (Option) 5

PowerTech PTS-25 — PT-ECU-63 ENGINE CONTROL MODULE diagram (page 54)
Fig. 46

NOTE: The PT-ECU-63 is designed to operate on 12V DC power. In a low battery situation the PT-ECU-63 may not initiate the normal cranking cycle. To start the generator you can press and hold the Start/Stop Switch for approximately 10 seconds or until the engine starts. Once the engine starts the PT-ECU-63 will resume normal operations. If this situation reoccurs, charge or replace the battery.

Page 55 of the PowerTech PTS-25 user manual — 06REG12DCAT
Page 55 · click to enlarge
Page 55
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 55)
Fig. 47

BLUE to 12V GENERATOR WINDING

BLUE to 12V GENERATOR WINDING

PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 55)
Fig. 48

YELLOW to RUN RELAY

GREEN NOT USED

RED to +12V DC

12 VOLT DC CHARGING

06REG12DCAT

06REG12DC

BLACK to GROUND

Page 56 of the PowerTech PTS-25 user manual — (352) 365-2777 FAX (352) 787-5545
Page 56 · click to enlarge
Page 56
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 56)
Fig. 49

12V DC ENGINE CONTROL PT-ECU-63

POWER TECHNOLOGY SOUTHEAST, INC.

(352) 365-2777 FAX (352) 787-5545

634 STATE ROAD 44 LEESBURG, FL 34748-8103

Page 57 of the PowerTech PTS-25 user manual — (352) 365-2777 FAX (352) 787-5545
Page 57 · click to enlarge
Page 57
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 57)
Fig. 50

12 VOLT DC ENGINE CONTROL NEW KUBOTA RUN SOLENOID

POWER TECHNOLOGY SOUTHEAST, INC.

(352) 365-2777 FAX (352) 787-5545

634 STATE ROAD 44 LEESBURG, FL 34748-8103

Page 58 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 58 · click to enlarge
Page 58
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 51
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 52
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 53
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 54
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 55
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 56
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 57
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 58
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 59
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 60
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 58)
Fig. 61
Page 59 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 59 · click to enlarge
Page 59
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 62
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 63
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 64
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 65
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 66
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 67
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 68
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 69
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 70
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 71
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 59)
Fig. 72
Page 60 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 60 · click to enlarge
Page 60
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 73
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 74
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 75
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 76
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 77
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 78
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 79
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 80
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 81
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 82
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 60)
Fig. 83
Page 61 of the PowerTech PTS-25 user manual — GENERATOR COMPARTMENT SIZE
Page 61 · click to enlarge
Page 61
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 84
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 85
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 86
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 87
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 88
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 89
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 90
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 91
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 92
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 93
PowerTech PTS-25 — GENERATOR COMPARTMENT SIZE diagram (page 61)
Fig. 94
Page 62 of the PowerTech PTS-25 user manual — ENGINE DOES NOT CRANK ENGINE CRANKS ENGINE CRANKS
Page 62 · click to enlarge
Page 62

ENGINE DOES NOT CRANK ENGINE CRANKS ENGINE CRANKS

SLOW

ENGINE WILL NOT START

PCMD

YES NO

Show 36 more labels / short text on this page
Low Battery · Voltage · Oil Viscosity · Too Heavy · Starter Motor · Start Switch · Main Switch Battery · Turn Switch · On · Terminals · Check · Dead · Check Spark · Muffler for · Glow Plugs · Arrestor · Clogging · Check · Smoke Smoke From · Fuel System · Exhaust · Check Fuel · Check Fuel · Air in · Pump · Supply · No Power · From · No Exhaust · Check Fuel · NO Power · Solenoid · Cranking · While · Solenoid · Replace
Page 63 of the PowerTech PTS-25 user manual — GREY/WHITE SMOKE
Page 63 · click to enlarge
Page 63

GREY/WHITE SMOKE

BLACK SMOKE

ENGINE RUNS ROUGH OR SLOW

BLUE SMOKE

Show 32 more labels / short text on this page
Engine Cold · Combustion · Over Fueling · Incomplete · Injector · Excessive Exhaust Smoke · Over Fueling Injector · Engine Overheated · Engine Overloaded · Glow Plug Circuit · Dirty Air Filter · Clogged Muffler · Not Operating · High Altitude · Oil Consumption · Excessive · Oil Level · Excessive · Fuel Pump · Check · Replace · Fuel Filter Check · Exhaust Smoke · Fuel to Engine · No Visible · Insufficient · And Fuel Solenoid · Fuel System · Check Safety · Shutdowns · Air in · Fuel Level
Page 64 of the PowerTech PTS-25 user manual — Stator Check Rotor
Page 64 · click to enlarge
Page 64

Stator Check Rotor

Turn “ON”

Breaker / s OK

Ohm’s

OK BAD

OFF

Check Ohm’s

Stator Leads

On Main

BAD Wiring To

ZERO or LOW

VOLTAGE

Breakers are

Check Main

Main Coil

Output to

Breakers

“ON”

Replace

ON

Panel Defective

Breaker / s

Check Brushes

Applicable

if

Page 65 of the PowerTech PTS-25 user manual — Voltage
Page 65 · click to enlarge
Page 65

Voltage

Voltage Overload Output

OK

From equipment

Regulator Check AMP

Draw

VOLTAGE TEST

High

Check

Main Breaker / s

Low Voltage

On Generator

Gen End

Check

Zero

Check

or

Page 66 of the PowerTech PTS-25 user manual — Replace Stator
Page 66 · click to enlarge
Page 66

Replace Stator

Stator Coil

Resistance

Check

OVERLOAD CONDITION

Check AMP Draw

Check Load

Engine Problem

Troubleshooting

See Engine

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Unit does not operate when powered to test modePower leads to unit are reversed.Confirm correct wiring for ground And bat, and re-attempt testing. p.52
Unit does not operate when powered to test modeBad ground connection from engine to controller unit.Run wire directly from battery – to the ground terminal #6 on controller unit. p.52
Engine doe not crankBattery is low or terminals are dirty.Clean terminals and re-charge battery. Replace battery if necessary. p.52
Engine doe not crankCrank circuitry wiring improperly connected.Refer to engine control wiring and check crank connections. p.52
Engine doe not crankBad ground connection from engine to controller.Run wire directly from battery – to the ground terminal #6 on controller unit. p.52
Engine doe not crankCrank relay damaged. Or on board fuse is blown.Check wiring, on board 10A fuse and relay. Replace fuse, relay and re-test controller again. p.52
Engine cranks but doesn’t startOut of fuel.Check fuel level, add fuel if necessary. p.52
Engine cranks but doesn’t startIgnition control wiring not installed properlyRefer to engine control wiring and check ignition connections. p.52
Engine cranks but doesn’t startFuel relay damagedCheck fuel relay and replace if damaged. p.52
Engine starts but shuts down after “Oil Bypass period” due to low oil / high temp / extra.Oil / temp. / extra input wiring improperly connected.Check wiring for proper connections. p.52
Engine starts, but running LED does not illuminate.Fault (short or overload) on one of the annunciated outputs.Check for fault, once fault is corrected then operation resumes. p.52
Annunciation output not workingFault (short or overload) on one of the annunciated outputs.Check for fault, once fault is corrected then operation resumes. p.52
Preheat LED works OK but timer output does not activateFault (short or overload) on timer output.Check for fault, once fault is corrected then operation resumes. p.52

Ask about the PowerTech PTS-25

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the PowerTech PTS-25

Be the first to ask — other owners or our team will answer.

Original document

PowerTech PTS-25 manual PDF

66 pages·3.5 MB·Generator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…