EN Program Entry Guide Control Panel D9112B.
D9112B | Program Entry Guide | EN | 2 Bosch Security Systems | 2/04 | 74-06145-000-D Notice The material and instructions covered in this manual were carefully checked for accuracy and presumed to be reliable.
D9112B | Program Entry Guide | Contents EN | 3 Bosch Security Systems | 2/04 | 74-06145-000-D Table of Contents 1.0 Panel Wide Parameter .................................. 8 1.1 Phone ................................................................. 8 Phone 1 .
D9112B | Program Entry Guide | Contents EN | 4 Bosch Security Systems | 2/04 | 74-06145-000-D W## Open Early Begin............................................. 36 W## Open Window Start ........................................36 2.4.1 Programming Two Opening Windows on the Same Day .
D9112B | Program Entry Guide | Contents EN | 5 Bosch Security Systems | 2/04 | 74-06145-000-D L## Remote Program ..................................................59 Move to Area ...............................................................59 L## Move to Area.
D9112B | Program Entry Guide | Contents EN | 6 Bosch Security Systems | 2/04 | 74-06145-000-D Point Index ................................................................... 80 BFSK Code ................................................................
D9112B | Program Entry Guide | Contents EN | 7 Bosch Security Systems | 2/04 | 74-06145-000-D Table of Tables Table 1: Modem II Communication Format Data – User ID Numbers ( Point/User Flag ) .............. 10 Table 2: Modem II Communication Format Data – Point Numbers ( Point/User Flag ) .
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 8 Bosch Security Systems | 2/04 | 74-06145-000-D 1 .0 Panel W ide Paramet er Use this programming module to define the operating characteristics that affect panel-wide functions.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 9 Bosch Security Systems | 2/04 | 74-06145-000-D Default: Blank Selection: Up to 24 characters (do not enter [SPACE]) 0 - 9 Numbers zero through nine C 3 sec. pause D 7 sec. dial-tone detect.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 10 Bosch Security Systems | 2/04 | 74-06145-000-D Point/User Flag This program item determines how point and User ID numbers are presented at the D6500 display, printer, and computer RS-232 output.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 11 Bosch Security Systems | 2/04 | 74-06145-000-D User ID 5 = ZONE F User ID 6 = ZONE 6 User ID 7 = ZONE 7 User ID 8 = ZONE 8 User ID 91 = .
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 12 Bosch Security Systems | 2/04 | 74-06145-000-D BFSK Duress Code Default: 0 Selection: 0 to 9 When transmitting in BFSK ( Modem Format is programmed NO), you must assign a number to identify Duress reports at the central station.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 13 Bosch Security Systems | 2/04 | 74-06145-000-D Table 3: Phone Routing Report Group Description Blank Not reported to this phone number. P Primary: Send all reports from this group to this phone number.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 14 Bosch Security Systems | 2/04 | 74-06145-000-D Table 6: Phone Routing Worksheet – Alarm/ Res/Cncl (Non-Fire Alarm/Restoral/ Cancel) Re.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 15 Bosch Security Systems | 2/04 | 74-06145-000-D Table 10: Phone Routing Worksheet – Open/Close Report Type Phone 1 Phone 2 Phone 3 Phon.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 16 Bosch Security Systems | 2/04 | 74-06145-000-D Table 12: Phone Routing Worksheet – Test/Stat Rpt (Test and Status Reports) Report Type.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 17 Bosch Security Systems | 2/04 | 74-06145-000-D Table 14: Phone Routing Worksheet – Power/Phone Report Type Phone 1 Phone 2 Phone 3 Pho.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 18 Bosch Security Systems | 2/04 | 74-06145-000-D Ph# Test/Stat Rpt Default: Blank Selection: Blank, P, B, or D See the introduction to Phone Routing for a description of the selections. Test reports and Status reports are enabled in the Skeds section of the program.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 19 Bosch Security Systems | 2/04 | 74-06145-000-D Ph# Service Default: Blank Selection: Blank, P, B, or D See the introduction to Phone Routing for a description of the selections. 1.3 Power Supervision AC Fail Time Default: 10 Selection: 1 to 90 sec.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 20 Bosch Security Systems | 2/04 | 74-06145-000-D Bat Fail/Res Rpt Determines if battery (DC) power supervision reports are sent.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 21 Bosch Security Systems | 2/04 | 74-06145-000-D P## Area Assign Default: 1 Selection: 1 to 8 Assign each installed printer to an area of the D9112. This allows the proper routing of events as determined by the Printer Scope.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 22 Bosch Security Systems | 2/04 | 74-06145-000-D 1.5 RAM Parameters These program items are used to enable RAM functions in the D9119. RAM Passcode Default: 999999 Selection: 0 to 9, A to F (6 characters required) RAM programming security passcode.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 23 Bosch Security Systems | 2/04 | 74-06145-000-D RAM Call Back Used to add an additional level of communication security to RAM sessions.
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 24 Bosch Security Systems | 2/04 | 74-06145-000-D Ram Ph The phone number the panel dials to contact RAM.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 25 Bosch Security Systems | 2/04 | 74-06145-000-D 2.0 Area W ide Paramet ers This programming module contains three programming categories: • Area Parameters • Bell Parameters • Opening and Closing 2.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 26 Bosch Security Systems | 2/04 | 74-06145-000-D A# Delay Res Default: No Selection: Yes or No Yes Restoral report is delayed until the area bell time expires, and the point returns to normal.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 27 Bosch Security Systems | 2/04 | 74-06145-000-D Immediately after the detector trips, the area’s sensor reset relay interrupts power to points connected to it for the time in Verify Time .
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 28 Bosch Security Systems | 2/04 | 74-06145-000-D A# Fire Pat Select the bell pattern this area uses to signal an alarm on a fire point. Press the [SPACE] bar to scroll through the selections.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 29 Bosch Security Systems | 2/04 | 74-06145-000-D A# Single Ring This program item determines if an alarm from a non-fire point can restart the alarm bell time with each alarm event, or only initiate alarm output once per arming period.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 30 Bosch Security Systems | 2/04 | 74-06145-000-D Selective Combinations of Account and Area Opening and Closing Reports You can eliminate Area Opening and Closing reports from selected areas in the account by programming A# Area O/C NO for those areas.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 31 Bosch Security Systems | 2/04 | 74-06145-000-D A# Area O/C An Area Opening report is sent to the central station when each individual area is opened (disarmed). An Area Closing report is sent to the central station when each individual areas is closed (armed).
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 32 Bosch Security Systems | 2/04 | 74-06145-000-D A# Restricted O/C This item determines if this area can restrict Opening and Closing report activity. A Restricted Opening report refers to the panel sending an Area Opening report ONLY when the area is disarmed after a non-fire alarm.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 33 Bosch Security Systems | 2/04 | 74-06145-000-D A# Perimeter O/C This item determines if this area can send Perimeter Opening and Closing reports to the central station. Modem Format reporting is required.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 34 Bosch Security Systems | 2/04 | 74-06145-000-D A# Auto Close The panel can automatically arm the area at the end of the closing window. Default: No Selection: Yes or No Yes The area automatically arms at the end of the close window.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 35 Bosch Security Systems | 2/04 | 74-06145-000-D 2.4 O/C Windows Set a schedule for disarming and arming. The disarming and arming schedules provide several independent features: • Suppress normal Opening and/or Closing reports when A# Disable O/C in Window is programmed YES.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 36 Bosch Security Systems | 2/04 | 74-06145-000-D W## Thursday Default: No Selection: Yes or No Yes Activate this window on Thursdays. No Do not activate this window on Thursdays. W## Friday Default: No Selection: Yes or No Yes Activate this window on Fridays.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 37 Bosch Security Systems | 2/04 | 74-06145-000-D 2.4.1 Programming Two Opening Windows on the Same Day Table 17: Programming for Two Openi.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 38 Bosch Security Systems | 2/04 | 74-06145-000-D 0101 0101 0101 Disabled windows have a blank “begin” time. If the entry for this prompt is blank, but the times are programmed for Close Window Start and Close Window Stop the window is disabled.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 39 Bosch Security Systems | 2/04 | 74-06145-000-D W## Xept Holiday You can determine if the window is disabled on holidays, or is active only on holidays. To prevent the windows from activating on certain days of the year, program Xept Holiday YES, and enable at least one Holiday Index.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 40 Bosch Security Systems | 2/04 | 74-06145-000-D 2.4.4 Opening/Closing Windows Worksheet Use Table 21 to determine the proper entries for your application.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 41 Bosch Security Systems | 2/04 | 74-06145-000-D Table 22: Normal Store Hours* OPEN CLOSE W# Day of Week Early Begin Start Stop Early Begi.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 42 Bosch Security Systems | 2/04 | 74-06145-000-D 2.5 Command Center This programming module contains three programming categories: • Cmd Cntr Assignment • Area Text • Custom Function 2.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 43 Bosch Security Systems | 2/04 | 74-06145-000-D CC# Area Default: 1 Selection: 1 to 8 Each installed command center must be assigned to an area of the D9112. This allows proper event displays as well as user authority operations.
D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 44 Bosch Security Systems | 2/04 | 74-06145-000-D 2.5.3 Custom Function Custom Functions are a way to simplify the use of complex keystroke sequences that can be entered at the command center.
D9112B | Program Entry Guide | 3.0 User Interface EN | 45 Bosch Security Systems | 2/04 | 74-06145-000-D Command Center Scope affects how a Custom Function executes: The Scope of the command center where the Custom Function is accessed can affect the way the Custom Function operates.
D9112B | Program Entry Guide | 3.0 User Interface EN | 46 Bosch Security Systems | 2/04 | 74-06145-000-D Custom functions simplify the use of the command center by providing a method of displaying complex functions in a simplified form using custom text.
D9112B | Program Entry Guide | 3.0 User Interface EN | 47 Bosch Security Systems | 2/04 | 74-06145-000-D Table 28: Authority Level Selections Blank Disable this function for the authority level specified. E Enable this function for the authority level specified.
D9112B | Program Entry Guide | 3.0 User Interface EN | 48 Bosch Security Systems | 2/04 | 74-06145-000-D Master Arm There are three arming functions enabled by this prompt: • Master Arm All Areas: Arms all areas according to the Scope of the command center where the function is entered (see Cmd Cntr Assignment ).
D9112B | Program Entry Guide | 3.0 User Interface EN | 49 Bosch Security Systems | 2/04 | 74-06145-000-D Mstr Arm Inst Master Arm Instant: [COMMAND] [1] [1] There are three instant master arming functions enabled by this prompt: Master Arm All Areas Instant, Master Arm An Area Instant, and Command 11 Local Area Arm Instant.
D9112B | Program Entry Guide | 3.0 User Interface EN | 50 Bosch Security Systems | 2/04 | 74-06145-000-D L## Master Arm Inst Master Arm Default: See Program Record Sheet Selection: Blank or E Blank Disable this function for Authority Level (L##) specified, if this Command Center Function item requires a passcode (P).
D9112B | Program Entry Guide | 3.0 User Interface EN | 51 Bosch Security Systems | 2/04 | 74-06145-000-D L## Perim Inst Perimeter Instant Arm Default: See Training Sheet Selection: Blank or E Blank Disable this function for Authority Level (L##) specified, if this Command Center Function item requires a passcode (P).
D9112B | Program Entry Guide | 3.0 User Interface EN | 52 Bosch Security Systems | 2/04 | 74-06145-000-D L## Perim Delay Perimeter Delay Arm Default: See Program Record Sheet Selection: Blank or E Blank Disable this function for Authority Level (L##) specified, if this item in Command Center Function requires a passcode (P).
D9112B | Program Entry Guide | 3.0 User Interface EN | 53 Bosch Security Systems | 2/04 | 74-06145-000-D Watch Mode Default: E Selection: Blank, E, or P Watch Mode [COMMAND] [6]: This command center function operates only in the area where the command center is assigned.
D9112B | Program Entry Guide | 3.0 User Interface EN | 54 Bosch Security Systems | 2/04 | 74-06145-000-D View Pt Status Default: E Selection: Blank, E, or P View Point Status: View points assigned to the area where the command center is assigned.
D9112B | Program Entry Guide | 3.0 User Interface EN | 55 Bosch Security Systems | 2/04 | 74-06145-000-D Send Report Default: P Selection: Blank, E, or P Send Report [COMMAND] [4] [1] and [COMMAND] [4] [2]: Test the communications link between the panel and the central station receiver(s).
D9112B | Program Entry Guide | 3.0 User Interface EN | 56 Bosch Security Systems | 2/04 | 74-06145-000-D L## Chg Passcode Default: See Program Record Sheet Selection: Blank or E Change Passcodes: See Authority Level Selections in the introduction to the Authority Lvl Assign programming module for descriptions of selections.
D9112B | Program Entry Guide | 3.0 User Interface EN | 57 Bosch Security Systems | 2/04 | 74-06145-000-D See Command Center Function Selections in the introduction to the Command Center Functions programming module for descriptions of selections.
D9112B | Program Entry Guide | 3.0 User Interface EN | 58 Bosch Security Systems | 2/04 | 74-06145-000-D Bypass a Pt Default: P Selection: Blank, E, or P Bypass a Point [COMMAND] [0]: Bypass points in areas within the Scope of the command center where the function is entered (see Cmd Cntr Assignment ).
D9112B | Program Entry Guide | 3.0 User Interface EN | 59 Bosch Security Systems | 2/04 | 74-06145-000-D L## Remote Program Default: See Program Record Sheet Selection: Blank or E Remote Programming: See Authority Level Selections in the introduction to the Authority Lvl Assign programming module for descriptions of selections.
D9112B | Program Entry Guide | 3.0 User Interface EN | 60 Bosch Security Systems | 2/04 | 74-06145-000-D See Command Center Function Selections in the introduction to the Command Center Functions programming module for descriptions of selections.
D9112B | Program Entry Guide | 3.0 User Interface EN | 61 Bosch Security Systems | 2/04 | 74-06145-000-D L## Area O/C Send Area Opening and Closing Reports: Default: See Program Record Sheet Selection : Blank or E Blank Disable this function for the authority level specified.
D9112B | Program Entry Guide | 4.0 Command Menu EN | 62 Bosch Security Systems | 2/04 | 74-06145-000-D L## Passcode Arm Determines the user’s ability to arm the panel without having to use the Command menu or an arming command. When enabled for an authority level, users with that authority level can arm the area by entering their passcode.
D9112B | Program Entry Guide | 4.0 Command Menu EN | 63 Bosch Security Systems | 2/04 | 74-06145-000-D Function numbers 128 to 143 are programmed in the Custom Function section of the program. See the Command Center, Custom Function page of the D9112 Program Record Sheet to determine which custom functions you can use in the Command menu.
D9112B | Program Entry Guide | 5.0 User Access Windows EN | 64 Bosch Security Systems | 2/04 | 74-06145-000-D 5.0 User Access W indows Build up to 15 User Access Windows. Once the windows are set up, assign a window to selected passcodes. See User Window in the Passcode Worksheet section of the program.
D9112B | Program Entry Guide | 5.0 User Access Windows EN | 65 Bosch Security Systems | 2/04 | 74-06145-000-D To disable the window, both the hours and minutes spaces must be blank. 0101 0101 0101 Do not program a single window to cross the midnight boundary.
D9112B | Program Entry Guide | 6.0 Passcode Worksheet EN | 66 Bosch Security Systems | 2/04 | 74-06145-000-D 6.0 Passcode W orksheet The next 100 groups of entries determine the user passcodes and the authority level each user has in each area. Within these groups are entries to determine the supervision reporting for the user passcode.
D9112B | Program Entry Guide | 6.0 Passcode Worksheet EN | 67 Bosch Security Systems | 2/04 | 74-06145-000-D User Default: 1 Selection: 0 or 1 to 99 Enter the User number you are programming. 0101 0101 0101 User 0 is the Service Authority Level (Level 15).
D9112B | Program Entry Guide | 6.0 Passcode Worksheet EN | 68 Bosch Security Systems | 2/04 | 74-06145-000-D 0101 0101 0101 User Window times cannot be changed from the command center. Once a window is assigned to a user number, the user number always has a window.
D9112B | Program Entry Guide | 7.0 Point Index EN | 69 Bosch Security Systems | 2/04 | 74-06145-000-D 7 .0 P oint Index Use this programming module to construct “personality types”: for points used in the D9112 system. The index numbers are used in “point assignments.
D9112B | Program Entry Guide | 7.0 Point Index EN | 70 Bosch Security Systems | 2/04 | 74-06145-000-D 2 Interior: Interior points are armed only by master arming the area. They are NOT armed when using perimeter arming commands (COMMAND 2, COMMAND 3, and COMMAND 8).
D9112B | Program Entry Guide | 7.0 Point Index EN | 71 Bosch Security Systems | 2/04 | 74-06145-000-D 4 There are two ways to use Point Type 4 to arm and disarm an area: Keyswitch Maintain: Program Point Response as 1 . Do not connect initiating devices to a Keyswitch point.
D9112B | Program Entry Guide | 7.0 Point Index EN | 72 Bosch Security Systems | 2/04 | 74-06145-000-D 7 Point Open/Close with a D279: Used for Point Arming and Disarming. Point Response must be programmed 1 . Local bells are silenced through the command center (to have bell control at the D279 see Point Index entry 4 ).
D9112B | Program Entry Guide | 7.0 Point Index EN | 73 Bosch Security Systems | 2/04 | 74-06145-000-D P## Entry Delay Default: See Program Record Sheet Selection: 5 sec. to 600 sec. This program item does not require an entry unless the point Type and Point Response entry provides entry delay on this point.
D9112B | Program Entry Guide | 7.0 Point Index EN | 74 Bosch Security Systems | 2/04 | 74-06145-000-D P## Audible After 2 Failures Use with non-fire points programmed for “silent bell” to provide local alarm bell output in the event that the panel cannot send the Alarm report.
D9112B | Program Entry Guide | 7.0 Point Index EN | 75 Bosch Security Systems | 2/04 | 74-06145-000-D P## Relay Follows Point Default: No Selection: Yes or No Yes When this point goes into alarm, it activates a relay with the same address number. For example, if this were point #28, relay #28 activates when the point goes into alarm.
D9112B | Program Entry Guide | 7.0 Point Index EN | 76 Bosch Security Systems | 2/04 | 74-06145-000-D P## Local While Armed Default: No Selection: Yes or No Yes This option suppresses Alarm , Trouble , and Restoral reports from this point while the area it is assigned to is armed.
D9112B | Program Entry Guide | 7.0 Point Index EN | 77 Bosch Security Systems | 2/04 | 74-06145-000-D P## Bypassable Bypass and force arm the point. Points can be bypassed by entering the Bypass a Point function at a command center, a RAM II command, or a “Bypass a Point” SKED.
D9112B | Program Entry Guide | 7.0 Point Index EN | 78 Bosch Security Systems | 2/04 | 74-06145-000-D P## Defer Bypass Report A 24-hour point generates a Point Bypass report if it was previously bypassed and is still bypassed at the time the area is armed.
D9112B | Program Entry Guide | 8.0 Point Assignments EN | 79 Bosch Security Systems | 2/04 | 74-06145-000-D 8.0 P oint Assignment s These entries assign Point Indexes to the points and the points to the areas.
D9112B | Program Entry Guide | 8.0 Point Assignments EN | 80 Bosch Security Systems | 2/04 | 74-06145-000-D Table 31: BFSK/Relay Codes BFSK Code Trips Relay 1 = 73 2 = 74 3 = 75 4 = 76 5 = 77 6 = 78 7 = 79 8 = 80 Use these codes to activate relays on the D8129 OctoRelay or C8137 Transmitter Interface.
D9112B | Program Entry Guide | 8.0 Point Assignments EN | 81 Bosch Security Systems | 2/04 | 74-06145-000-D Point Text Default: Command 9 Selection: Up to 16 characters alphanumeric Enter alphabetic characters A to Z in capital letters Note: Period (.
D9112B | Program Entry Guide | 9.0 Relay Parameters EN | 82 Bosch Security Systems | 2/04 | 74-06145-000-D 9.0 Relay Paramet ers Relays provide basic alarm system functions (such as Bell Output and Reset Sensors) as well as a number of more advanced functions typically used in association with system annunciation devices.
D9112B | Program Entry Guide | EN | 83 Bosch Security Systems | 2/04 | 74-06145-000-D 9.1 Area Wide Relays Each area can be assigned a unique relay number for each of the events listed in this section.
D9112B | Program Entry Guide | EN | 84 Bosch Security Systems | 2/04 | 74-06145-000-D A# Force Armed Default: Blank Selection: Blank, 1 to 128, A, B, or C Activates when the specified area is Force Armed. It remains activated until the area is disarmed or the panel is reset.
D9112B | Program Entry Guide | EN | 85 Bosch Security Systems | 2/04 | 74-06145-000-D A# Command 7 Default: Blank Selection: Blank, 1 to 128, A, B, or C Activates when Command 7 is executed at a command center assigned to the specified area. Burg Time must be programmed in Bell Parameters .
D9112B | Program Entry Guide | 10.0 Skeds EN | 86 Bosch Security Systems | 2/04 | 74-06145-000-D Log % Full Default: Blank Selection: Blank, 1 to 128, A, B, or C Enter the number of the relay that activates when the log has reached the programmed percentage of its capacity as programmed in RAM Parameters program item Log % Full .
D9112B | Program Entry Guide | 10.0 Skeds EN | 87 Bosch Security Systems | 2/04 | 74-06145-000-D S## Function Code Enter the function code you want this Sked to execute. The programmer automatically displays the parameter prompt after you enter the function code if the Sked function requires additional parameters.
D9112B | Program Entry Guide | 10.0 Skeds EN | 88 Bosch Security Systems | 2/04 | 74-06145-000-D Default Description Sub-prompt Selection 2 S## Area 1 Yes No Disarm Area 1. Do not disarm Area 1. Disarm Area(s). Entries in the Disarm Area prompts define the area(s) this Sked disarms.
D9112B | Program Entry Guide | 10.0 Skeds EN | 89 Bosch Security Systems | 2/04 | 74-06145-000-D Default Description Sub-prompt Selection S## Area 5 Yes No Unbypass all points in Area 5. Do not unbypass all points in Area 5. S## Area 6 Yes No Unbypass all points in Area 6.
D9112B | Program Entry Guide | 10.0 Skeds EN | 90 Bosch Security Systems | 2/04 | 74-06145-000-D Default Description Sub-prompt Selection S## Defer Test Yes No Defer the Test report. Send the Test report on schedule. 9 Test Report. This function generates a Test report from Area 1.
D9112B | Program Entry Guide | 10.0 Skeds EN | 91 Bosch Security Systems | 2/04 | 74-06145-000-D Default Description Sub-prompt Selection S## Cmd Center Enter a command address, 1 to 8. 11 Execute Custom Func. This function executes one of the custom function items programmed in Custom Function .
D9112B | Program Entry Guide | 10.0 Skeds EN | 92 Bosch Security Systems | 2/04 | 74-06145-000-D Default Description Sub-prompt Selection 14 Adjust Time Backward One Hour. This Sked function is used to make adjustments to the panel’s clock. A typical application is to program this to take effect at 2:00 a.
D9112B | Program Entry Guide | 10.0 Skeds EN | 93 Bosch Security Systems | 2/04 | 74-06145-000-D S## Monday Default: No Selection: Yes or No Yes Activate this Sked on Mondays No Do not activate this Sked on Mondays. S## Tuesday Default: No Selection: Yes or No Yes Activate this Sked on Tuedays No Do not activate this Sked on Tuesdays.
D9112B | Program Entry Guide | 11.0 Holiday Indexes EN | 94 Bosch Security Systems | 2/04 | 74-06145-000-D S## Holiday 3 If no Holiday Index is selected, the Sked operates regardless of any holiday. Default: No Selection: Yes or No Yes Use Holiday Index 3 with this Sked.
D9112B | Program Entry Guide | 11.0 Holiday Indexes EN | 95 Bosch Security Systems | 2/04 | 74-06145-000-D Holiday Index 2 Default: No Selection: Yes or No Yes Use this date in Holiday Index 2. No Do not use this date in Holiday Index 2. Holiday Index 3 Default: No Selection: Yes or No Yes Use this date in Holiday Index 3.
© 2004 Bosch Security Systems 74-06145-000-D Bosch Security Systems 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189.
An important point after buying a device Bosch Appliances D9112B (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bosch Appliances D9112B yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bosch Appliances D9112B - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bosch Appliances D9112B you will learn all the available features of the product, as well as information on its operation. The information that you get Bosch Appliances D9112B will certainly help you make a decision on the purchase.
If you already are a holder of Bosch Appliances D9112B, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bosch Appliances D9112B.
However, one of the most important roles played by the user manual is to help in solving problems with Bosch Appliances D9112B. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bosch Appliances D9112B along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center