CS875-575-375-275-175 Alarm System Installer Manual with CS5500 Handle



We declare under our own and exclusive liability that this product complies with the Directive 93/68/EEC (certification) and/or with the essential requirements and all other relevant requirements of 1999/5/EC (R&TTE) based on test results obtained according to (non-) harmonised standards in accordance with the mentioned Directives.
Copyright (c) 2006 GE Security B.V. All rights reserved. GE Security B. V. grants the right to reprint this manual only for internal use. GE Security B. V. reserves the right to modify the information contained in this manual without prior notice.
The European Directive on Waste Electrical and Electronic Equipment (WEEE) aims to minimise the impact of waste from electrical and electronic equipment on the environment and human health. In order to comply with this Directive, electrical equipment marked with this symbol should not be incorporated into European public waste systems.
European users of electrical equipment should now offer end-of-life equipment for processing.For more information, please visit the following website: http://www.recyclethis.info/
Regulatory


1.1.1 Welcome Welcome to our range of CSx75 systems. We hope you will find this a useful addition to our product range.
Thanks to the unique CSx75 system design, we can house a fully equipped system in one metal or plastic housing. If necessary, the system can be extended to include additional modules. Five different types of power stations are available: the CS175, CS275, CS375, CC575 and CS875. In this manual they are collectively referred to as the CSx75.
This manual describes the installation of a CSx75 using the CS5500, the menu-controlled control panel. With the CS5500, it can easily be programmed using a menu structure.
1.1.2 Standard country codes Table 1-1: Standard country codes Summary of the standard codes for each country.
< The additional digits for 6-digit codes are shown in brackets.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.1.1

1.2.1 CS5500 Handle The CS5500 LCD control panel allows you to program the CSx75 system via a menu structure.

In multiple areas in .-) . these keys have specific functions. If you select one or more areas in this view:
You can program these keys to perform a function outside multiple areas .
Press No. to:
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.1.2

Press OK to:
While editing text and phone numbers:
delete.
Use arrow keys to override menu lists and options.
In multiple areas . . or when you are not in a menu:
While editing text and phone numbers:
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.1.3
Witch · Arrow Keys

2.1 System versions There are five versions of the CSx75. The following table gives an overview of the properties of each version and the differences between its versions.
Number of wired zones on the CSx75
4 6 8 8
Maximum number of zones 8 16 24 (CS375) 48 (CS575) 128
Outputs 3 (2 open collector and 1 fire reset)
4 integrated (open collector)
4 integrated (2 relay / 2 open collector)
4 integrated (2 relay / 2 open collector)
Alarm outputs Internal alarm monitor with built-in siren driver for internal alarm transmitter
Separate integrated external and internal alarm with built-in driver for the internal alarm provider
Separate integrated external and internal alarm with built-in driver for the internal alarm provider
Separate integrated external and internal alarm with built-in driver for the internal alarm provider
1 2 4 8
Report formats Fast Format, Telim, Franklin 4+2, SIA, XSIA, Sirentoon, 200 baud FSK, Speech and contact Contact ID report formats
Fast Format, Telim, Franklin 4+2, SIA, XSIA, Sirentoon, 200 baud FSK, Speech and contact Contact ID report formats
Fast Format, Telim, Franklin 4+2, SIA, XSIA, Sirentoon, 200 baud FSK, Speech and contact Contact ID report formats
Fast Format, Telim, Franklin 4+2, SIA, XSIA, Sirentoon, 200 baud FSK, Speech and contact Contact ID report formats
Hardware Extension 1 module Controls do not count as modules on the CS175
3 modules Controls do not count as modules on the CS175
16 modules (CS375) 32 modules (CS575) Control parts count as modules on the CS375-575
32 modules Operating parts count as modules on the CS875
8 (4- or 6-digit codes) 40 (4- or 6 digit codes) 66 (6-digit codes), or 99 (4-digit codes).
66 (6-digit codes) or 99 (4-digit codes).
Maximum number of servants (max. 8 by area)
No, no. Yes, yes.
CS875-575-375-175 Installation Manual with CS5500 control panel A.2.1
Maximum number of areas · Maximum number of user codes · Card reader support

CS5500 Control Part Used to program the system. Other LCD and LED controls can also be used for this purpose.
CS208/CS208H/CS216 Entry module Used to extend the number of wired zones to 8 or 16 areas. The wired zone expansion modules are only suitable for the CS 375, CS575 and CS875. The CS175 and CS275 can only be extended with a wireless receiver.
CS507 Output Module Expands the number of outputs available on the system.

Used as: 1. A direct interface between the panel and the PC. 2. A memory module, connected to the PC only. It is also possible to read/write from 1 of the 4 locations via UDx75 software. 3. A memory module, connected to the panel only. It is also possible to read/write from 1 of the 4 locations on the CSx75. The CS590 RS232 Direct Connect cable is used for the CS275-375-575-875 and is connected directly to the PCB. The CS586 can be used on any panel within the range and connected to the three-way control connection.

CS7002 GPRS module Provides the ability to report events via a GSM or GPRs network.
CS1700 Card reader Proxinity card reader/door controller module. It can be programmed to control access in any area or in all areas. The CS1700 is only suitable for the CS575 and CS875.
Provides additional power for connected modules of a panel.
CS535 Voice Module Provides the ability to report events through voice messages.
CS875-575-375-175 Installation Manual with CS5500 control panel A.2.2
Part Number · CS586 Memory/RS232 module · Cs320 Additional power supply module

CS534 Audio (enlisting) module
Two-way audio (enlisting) communication module that allows you to start a listening session, and/or remotely check the system via a telephone connection. CS7050 TCP/IP module Double-executed microprocessor controlled Internet / intranet interface for connecting a CSx75 central unit to an OH network receiver. CS7501 ISDN module ISDN network selector that allows digital data to be transmitted over an ISDN line.
CS7050 TCP/IP module Double-executed microprocessor controlled Internet/intranet interface for connecting a CSx75 central to an OH network receiver.
CS7501 ISDN module ISDN network selector that allows digital data to be transmitted over an ISDN line.

AS500 and AS290/390 External alarms
DB701 + DP721 and DB722 + DD721R Smoke detector
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.2.3
Part Number · Item Number · AS270/271 Internal alarms

Piece number 433 MHz 868 MHz Purpose
Wireless receiver RX8I4CA PCb RX16I4CA PCb
RF 433 versions offer RF functions for 8, 16 or 48 wireless / RF components.
RF868 versions offer RF functions for 8, 16 or 32 wireless / RF components.
RF352I4 (2 buttons) RF35414 (4 buttons).
RF354W8 (4 buttons) Turns the system on and off.
RF356I4 Not available Used for triggering a police, medical or other alarm throughout the property. When you press the robbery button, the LED light flashes under the front lid and an alarm signal is sent.
Wireless waterproof medical pendant
RF360I4 Not available At the touch of a button, sends an alarm signal to the panel.

Wireless Smoke Detector RF572SI4 RF572NSTI4
RF572SW8 Battery power fire detector.

CS875-575-375-275-175 Installation Manual with CS5500 control panel A.2.4
RX8W8CA PCb RX16W8CA PCbRX32W8CCA PCB · Wireless remote controls · Multifunctional micro-robbery button

Piece number 433 MHz 868 MHz Purpose
RF300W8 RF300W8B
Forwards events to the power station via the RF receiver.

Wireless vibration detector RF620I4 RF62014B
Not available Forwards events to the power station via the RF receiver.

RF903I4 RF9003W8 Forwards events to the power station via the RF receiver.
RF425W8 RF425W8PI
PIR on battery power.
CS875-575-375-275-175 Installation Manual with CS5500 Control Part A.2.5
Wireless door window detector · Wireless glass break detector · wireless motion detector

3.1 Net connection Use the mains connection clamp for connecting power supply. You can use a fixed cable or flexible power cord to a grounded socket. A separate circuit breaker shall be installed in the power distribution network when a fixed wiring is used. In any case, the grid connection must comply with local requirements.
LET OP: This unit can be supplied with a built-in lead battery. This battery may only be disposed of in accordance with the regulations for chemical waste.
3.4 Wired-out guidelines The central CSx75 was developed, built and tested on the basis of requirements of current standards for safety, emission and insensitivity to electrical and electromagnetic interference due to environmental factors. This system may only be connected to the mains voltage or telephone system by a qualified electro-monitor or specially trained personnel.
CS875-575-375-175 Installation Manual with CS5500 Control Part A.3.1

3.5 Bringing the power plant back to default settings IMPORTANT: Before installing and programming the system, default values of the handheld must be restored to ensure that you work with correct standard values in accordance with local regulations.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.3.2

3.6 Working with the DIP switch schematics • When the DIP switch is up, it is on. The schemes shall indicate:
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.3.3

4.1.1 General The entrances to the power plant are equipped as standard EOL (4K7) freely programmable zones. However, by programming the zones as a double loop all zone entrances of the plant can be programmed in such a way that they give alarm and sabotage messages on the same area.
4.1.2 Double principle A zone contains both alarm and sabotage wiring.
The alarm devices are switched in series and a 4K7 resistance is placed parallel to the closed circuit contacts.
The sabotage contacts are connected in series with a 4K7 EOL resistance.

1 Zone Connector 3 Alarm Contact
2 Melder 4 Sabotagecontact
4.1.3 A single principle Two zones are required: one for alarm and one for sabotage. The sabotage contacts are connected in series with a 4K7 EOL resistance.

1 Zone Connector 3 Alarm Contact
2 Melder 4 Sabotagecontact
Information on programming of zones can be found in Chapter B-2 The central programming.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.1

4.2 Installing the central The power plant is available in three different enclosures. The process of installation and placing expansion modules varies depending on the housing used.
The instructions for installing a base system are given below. For more information about the installation of CS7050, CS7501 and CS7002 you can find in the relevant chapters.
4.2.1 CS575M/CS875M (large metal housing) This large metal housing is suitable for the CS375, CS575 and CS875.

- Connect a belt cable to the CS7002 GPRS module.
- Connect a belt cable to the CS534 communication module.
- Connect the CS7002 GPRS module and CS535 voice module using the band cable.
- Connect the CS534 communication module and the CC535 voice module to the band cable.
- Place the supports for the CS7002 GPRS module on the circuit board.
- Connect the CS7002 GPRS module to the circuit board via jumpers and supports.
- Place the CS534 communication module and the CC535 voice module on top of the CR7002 GPRS module in the enclosure.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.2

- Connect the belt cable to the CS534 communication module.
- Connect the CS534 communication module and the CC535 voice module to the band cable.
- Place the supports for the CS535 voice module on the circuit board.
- Connect the CS535 voice module to the circuit board via jumpers and supports.
- Secure the support for the CS534 communication module on the enclosure.
- Place the CS534 communication module in the enclosure.

CS7002
CS216
e b b
b
CS507 CS216
CS507
a
a
d
)
) )
CS375/575/875
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.3

4.2.2 CS275/CS375/CS575/CS875 (policate housing) This polycarbonate housing is suitable for the CS275, CS375, CS575 and CS875.

CS275/375/575/875
- Connect the belt cable to the CS7002 GPRS module.
- Connect the belt cable to the CS534 communication module.
- Remove the adhesive strips and place the supports for the CS7002 GPRS module in the housing.
- Connect the CS7002 GPRS module to the circuit board.
- Drop the PCB mounting plate.
- Place the supports for the CS535 voice module on the circuit board.
- Connect the CS535 voice module to the circuit board via jumpers and supports.
- Connect the CS7002 GPRS module and CS535 voice module using the band cable.
- Connect the CS535 voice module and the CC534 communication module to the band cable.
- Connect the belt cable to the CS534 communication module.
- Remove the adhesive strips and place the supports for the CS534 communication module in the housing.
CS875-575-375-275-175 Installation Manual with CS5500 Control Part A.4.4

- Place the CS534 communication module in the enclosure.
- Drop the PCB mounting plate.
- Place the supports for the CS535 voice module on the circuit board.
- Connect the CS535 voice module to the circuit board via jumpers and supports.
- Connect the CS534 communication module and the CC535 voice module to the band cable.

CS535
CS534
CS535
CS275/375/575/875
CS275/375/575/875
CS507 CS216
CS275/375/575/875
CS216
CS507
CS275/375/575/875 CS275/375/575/875
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.5

4.2.3 CS175M/CS275M/CS375m/CS575SM (small metal housing) This is a small metal housing suitable for the CS175, CS275, CS375 and CS575.

CS535
CS535
CS534
CS175/275/375/575 CS175/275/375/575
CS175/275/375/575 CS175/275/375/575
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.6

- Attach the supports for the CS7002 GPRS module to the circuit board.
- Mount the CS535 voice module on the expansion port (jumper).
- Connect a belt cable to the CS534 communication module.
- Connect the CS534 communication module and the CC535 voice module to the band cable.
- Attach the CS7002 GPRS module to the supports on the circuit board.
- Place the supports for the CS534 communication module or CS535 voice module on the main print.
- Mount the CS534 communication module or CS535 voice module on the expansion port (jumper).
- Mount the CS534 communication module or CS535 voice module on the supports on the main print.

CS216 CS507
CS507 CS216
CS575/875
CS175/275/375/575
CS875-575-375-175 Installation Manual with CS5500 Control Part A.4.7



4.3.1 Wiring to the handheld The handheld shall be connected to the control unit as follows.
Data 13.8V
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.8
Aux + · CSx75 CS5500

4.3.2 Connecting multiple servants A total of 800 m cable shall not be used. The diagram below shows which wire diameter to use. These values apply to one handheld at the end of the wiring. When multiple controls are connected to the end of the wiring, a larger wire diameter is required.
Length Connected to CSx75
Length in metres Wire (mm2)
110 0.50
200 0.75
333 1.00
500 1.50
800 2.50
4.3.2.1 Multidrop network In a multidrop network, servants are connected. Each handheld is switched in parallel with the previous handheld.

4.3.2.2 Star Network In a star network, each control panel is connected separately to the power plant's terminal clamps.

CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.9

4.3.2.3 Star and multidrop network It is possible to compile a combination of star and multidrop networks. The picture below shows how four handhelds can be connected via both methods.
4.4.1 Wire an alarm with EOL security Each zone can be used for this purpose. The zone shall be programmed as anti-sabotage and with one EOL.
CSX75
TAMPAR
TAMPAR
DATA
AUX+
COM
COM
R1NC
R1NO
AUX+
OUT2
COM
R3NC
R3NO
AUX+
COM
OUT4
COM
COM
COM
COM
INT
EXT
R1C
R3C
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
4K7 4K7
4K7
9 8 7 6 5 4 3 2 10 1 11
1 Hold-off beacon 5 Sabotage 9 Piezo
2 Hold-off siren 6 Sabotage A Piezo
3 +13.8 V 7 Beacon B Piezo
4 SNE 8 Beacon
" In all cases, select negative hold-off on the alarm provider.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.10

" A resistance must be added between the COM and the Ext on the panel circuit board. This resistance prevents the panel from constantly being in alarm condition. Both the internal and external siren are supervised.

1 Sabotage 4 0 V loudspeaker
2 Sabotage 5 0 V flash (AS271) only
" With this wiring for the AS271, the flash can track the built-in siren.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.11

CSX75

9 8 7 6 5 4 3 2 10 1
9 8 7 6 5 4 3 2 10 1
1 Piezo 4 Beacon 7 GND
2 Piezo 5 Sabotage 8 +13.8 V
3 Beacon 6 Sabotage 9 Hold-off siren
" Interrupt jumpers 5 and 7 for negative hold-off of the alarm.
Information on the programming of alarm providers can be found in chapter B-2 The central programming.
4.5 Wire smoke detectors In a 4-wire configuration, you can connect as many detectors as you want, as long as you do not exceed the AUX power of the panel.
In a two-wire configuration, you can connect up to three smoke detectors to the same loop.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.12
A Hold-off beacon

DB702 +DB721R DB702 +DB721R

CS375
CS575
CS875
1 + Lead in 4 NC (normally closed)
2 + Lead from 5 COM
DB701 +DB721R DB701 +DB721R

CS375
CS575
CS875
1 + Leading in
2 + Lead off
" A fire alarm is activated as an alarm on zone 8 at the CS375-575-875 and as an alert on zone 7 on the Cs275. The Fire detector feed is connected to AUX and exit.
If you are using a 2-wire fire detector, please press the menu option for 2-wire alarm To - I'm sorry.
The CS175 does not work with a 2-wire fire detector. A fire alarm activates the zone connected to the 4-wire fire detector.
CS875-575-375-275-175 Installation Manual with CS5500 Control Part A.4.13

DB702 +DB721R DB702 +DB721R
AUX+
CS175
COM
SMOKE
Z1
COM
1 + Lead in 4 NC (normally closed)
2 + Lead from 5 COM
If you are working with a CS175, you must program output 3 for the fire alarm.
CS875-575-375-175 Installation Manual with CS5500 control panel A.4.14


CS275
1 Contacts loadable up to 1A. Relays are powered and switched from the panel. No external power supply is needed to switch the relay. 2 Digital outputs limited to 40mA.
Information on programming outputs can be found in chapter B-2 The central programming.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.15


1 Zones 1-4 6 External alarm B Serial expansion
2 Input sabotage enclosure 7 Bus control C Telephone connector
3 Reset output smoke detector 8 Additional databus connector D Telephone communication LED
DATA Communication / Extension module data bus (0101) (including control) COM Earthing
AUX+ Communication / Extension module power supply (including control) TAMPER Sabotage loop
COM Communication / Extension module earthing (including control gear) Z1 Entry 1
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.16


4 1 9 8 7 6 5 3 2
1 Zones 1-6 7 Open collector 1 C Serial expansion
2 Sabotage lid 8 External alarm D Databus control LED
3 Input sabotage enclosure 9 Internal alarm monitor E Full expansion port
4 Open collector 4 (2-wire smoke) A Bus control F Telephone connector
5 Open collector 3 B Extra data bus connector G Telephone communication LED 3
6 Open collector 2 C Serial expansion
4.7.2.1 Entry and exit points

DATA Communication / Extension module data bus (0101) (including control) OUT 4 Output 4
AUX+ Communication / Extension module power supply (including control) TAMPER Sabotage loop
COM Communication / Extension module earthing (including control gear) Z1 Entry 1
INT Internal call return COM Earthing
COM Earthing Z2 Entrance 2
EXT External siren Z3 Entry 3
OUT1 Exit 1 COM Earthing
AUX+ Power Z4 Entrance 4
OUT 2 Exit 2 Z5 Entry 5
OUT 3 Exit 3 COM Earthing
AUX+ Power Z6 Entrance 6
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.17
COM Earthing


1 9 8 7 6 5 4 3 2
1 Zones 1-8 7 Relay 1 D Databox control LED
2 Sabotage cover * 8 External alarm E Full expansion gate
3 Input sabotage enclosure * 9 Internal alarm clock F Telephone connector
4 Open collector 4 (2-wire smoke) A Bus control G Telephone communication LED
5 Relais 3 B Additional databus connector
6 Open collector 2 C Serial expansion
" *Always in parallel switching. There is always only one of them that can be used.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.18

4.7.3.1 Entry and exit points
TAMPAR
DATA
AUX+
R1NC
R1NO
AUX+
OUT2
R3NC
R3NO
AUX+
OUT4
COM
COM
EXT
R1C
COM
R3C
COM
COM
COM
COM
COM
INT
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
DATA Communication / Extension module data bus (0101) (including control gear)
AUX+ Communication/Extra power expansion module (including control gear)
COM Communication/Expansion module earthing (including control gear)
INT Internal telephone power supply
R1NC Relais 1 (normally closed)
R1NO Relay 1 (normally open)
R1C Relais 1 (earthing)
OUT 2 Exit 2
R3NC Relais 3 (normally closed)
R3NO Relais 3 (normally open)
R3C Relais 3 (earthing)
OUT 4 Exit 4
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.4.19

5.1 Start-up of the system If the CS5500 control is connected for the first time, enter language, default settings, area and server number. Every time the handheld is reset to default, you need to do these settings again.
Use deμ¶ keys to scroll between the different options and press OK to select an option. See 5.3 Navigate in the menus for more information.
5.2 Go into programming mode With your installer code you can program the system via the installer menu. There are 2 programming levels in the installer menu. The Light menu contains the most important options. The Advanced menu contains all additional options.
< You the Menu advanced select, navigate with µ¶ to functions > advanced and select active. The handheld is in advanced mode until this option is not activated.
See Chapter B-3 Programming the available operators for more information on setting up the language.
< The handheld automatically returns to the default display after a certain time.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.5.1

5.3.1 Function menu You can open a limited number of menu options without entering your installer code. This is how you open the function menu:
5.5 Change a menu option The CSx75 has several editors that allow you to change the value of certain programmable menu options. It is possible to change items in drop-down lists, option selections, phone numbers and text. This section describes how to change items in drop-down lists, option selections, numerical entries and phone numbers. More information on changing text can be found in 5.7 Text Operation.
- If the new value is valid, let the handheld hear one beep to confirm the change and return to the menu option.
- If the new value is invalid, the handheld will display three beeps to cancel the change and return to the menu option.
- If the new values are valid, the handheld will display one beep to confirm the change and return it to the menu option.
- If the new value is invalid, the handheld will display three beeps to cancel the change and return to the menu option.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.5.2

- Press a number key to erase the current value and display the value of the pressed button.
- Press μ to increase the current value by one unit.
- Press ¶ to lower the current value by one unit.
- Press## to set the current value to 0.
- If the new value is valid, let the handheld hear one beep to confirm the change and return to the menu option.
- If the new value is invalid, the handheld will display three beeps to cancel the change and return to the menu option.
- Press μ to switch between insert and overwrite (insert new digits, and overwriting over existing numbers).
- Press ¶ to erase the number at the cursor position.
- Press #¶ to erase all digits from the digit at cursor position until last digit.
- Press the keys 0 to 9 to introduce new figures.
- Press #0 To insert G.
- Press #1 to insert an asterisk.
- Press #2 to insert a #.
- Press #3 to insert a four-second break while programming the numbers on the control panel.
- Press #3 to insert an + while programming numbers on the CS7002 GPRS module.
- Press #4 to insert a P (this is the pulse dial).
- If the new number is valid, the handheld will give one beep to confirm the change and return it to the menu option.
CS875-575-375-275-175 Installation Manual with CS5500 control panel A5.3

- If the new number is invalid, the handheld will display three beeps to cancel the change and return to the menu option.
5.7.1 Overview The CSx75 has a text editor with an integrated glossary. With the help of this editor, you can change the text of certain programmable text options.
< A flashing cursor indicates the character you are editing. Press F2 to blink the current word.
5.7.2 Example If you have a zone name of Zone 2 in Upstairs wants to change:
CS875-575-375-275-175 Installation Manual with CS5500 Control Part A.5.4

< Under the keys 0 to 9 are the lower case letters and capitals, numbers and language-specific characters. By pressing the same key several times, you can browse through the characters.
5.7.3 Glossary The Glossary is a fixed set of words that accelerates text entry. When you enter a character, the handheld automatically displays a word from the vocabulary. The Glossary function is enabled by default. A complete list of the words in the Glossary can be found in chapter C-1 Annex 6: Glossary words.
5.7.4 Installer Message The LCD display can show up to four messages when the control is not used or a menu returns itself after some time to the default screen. If you activate more than one message, the messages shown will alternate continuously.
Activate the Customer Message as follows:
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.5.5

6.1 Reporting The CSx75 supports various ways to report events to different dispatches of the Dispatch. There are six phone numbers and each telephone number has its own customer number, protocol and events. The pre-choice number is the same for all six phone numbers. If the dial number has a delay time of four seconds, the integrated voter does not wait for a tone at the power station but chooses the voters without an detection. The following descriptions are examples of how different reporting methods can be set up.
6.1.1 Reporting to one telephone number The voter reports events to only one PAC. You enter the settings for phone number 1. The most common events for phone number 1 are enabled by default.
< The characters B, C, D, E, F can be used in account codes for power stations. The letter "A'-Scan not be used in the codes as it acts as a cutoff character.
Level 1 Level 2 Value Status
Telephone Telephone number 1 123456
Customer number Telephone 1 BE5566
Protocol Telephone 1 SIA
Events Telephone 1 - Alerts Active
Telephone 1 . . Active
Telephone 1 . . Active
Telephone number 2 - Alerts
Telephone number 2 . .
Telephone 2 . . Sabotage and recovery
6.1.2 Backup reporting Backup reporting configures the voter for reporting to two or more reporting banks. The first telephone number is that of the main login bank and all other phone numbers belong to the backup reporters. Events are reported to the first number, but if the voter cannot reach this number he calls the backup number(s). The voter makes two calls to each number in the series. The electorate performs the attempts as often as specified in Selections PAC or until it receives a kiss-off message. The same customer number is used for reporting to all numbers. Events for phone number 1 are enabled by default and events for telephone numbers 2 . If phone number 1 and telephone number 2 are programmed, the standard sequence is 1.1 2.2 1.1 2.2 for a total of eight calls to each number.
Level 1 Level 2 Value Status
Telephone Telephone number 1 123456
Customer number Telephone 1 BE5566
CS875-575-375-275-175 Installation Manual with CS5500 Control Part A.6.1

Level 1 Level 2 Value Status
Protocol Telephone 1 SIA
Events Telephone 1 - Alerts Active
Telephone 1 . . Active
Telephone 1 . . Active
Telephone number 2 - Alerts Not active
Telephone number 2 . . Not active
Telephone 2 . . Sabotage and recovery Not active
6.1.3 Double reporting Double reporting configures the voter for reporting to two different reporting banks. Events must be reported to both telephone numbers. The dispatcher calls the first number twice. If it cannot reach this number, the second number will be called twice. The electorate performs the attempts as often as specified in Selections PAC or until the voter receives a kiss-off message from both reporting banks. The same customer number is used for reporting to both numbers. Events for phone number 1 are enabled by default and events for telephone number 2 are off standard.
Level 1 Level 2 Value Status
Telephone Telephone number 1 123456
Customer number Telephone 1 BE5566
Protocol Telephone 1 SIA
Events Telephone 1 - Alerts Active
Telephone 1 . . Active
Telephone 1 . . Active
Telephone number 2 - Alerts Active
Telephone number 2 . . Active
Telephone 2 . . Sabotage and recovery Active
6.1.4 Separate reporting Separate reporting configures the voter for reporting to two different reporting banks. Some events must be reported to phone number 1, and others to telephone number 2. The voter calls the first number twice. If it cannot reach this number, the second number will be called twice. The electorate performs the attempts as often as specified in Selections PAC or until it has reported the relevant event to each number. The same customer number is used for reporting to both numbers. Events for phone number 1 are enabled by default and events for telephone number 2 are off standard.
Level 1 Level 2 Value Status
Telephone Telephone number 1 123456
CS875-575-375-275-175 Installation Manual with CS5500 control panel A6.2

Level 1 Level 2 Value Status
Customer number Telephone 1 BE5566
Protocol Telephone 1 SIA
Events Telephone 1 - Alerts Active
Telephone 1 . . Active
Telephone number 1 - Sabotage and recovery Not active
Telephone number 2 - Alerts Not active
Telephone number 2 . . Not active
Telephone 2 . . Sabotage and recovery Active
CS875-575-375-275-175 Installation Manual with CS5500 control panel A.6.3
Telephone number 2 445566 · Phone number 2 SIA

Install and program the modules
1 Modules register B-1-1
2 Central programming B-2-1
3 The available operators program B-3-1
4 The other servants program B-4-1
5 Set the RF receivers B-5-1
6 The CS208H / CS208 / CC216 setup B-6-1
7 Set the CS507 B-7-1
8 Set the CS586 B-8-1
9 Set the CS534 B-9-1
10 Set the CS320 B-10-1
11 Set the CS535 B-11-1
12 Set the CS1700 B-12-1
13 Set the CS7002 B-13-1
14 Reserved B-14-1
15 Set the CS7050 B-15-1
16 Set the CS7501 B-16-1
17 Read the log B-17-1
18 Programming with the UDx75 software B-18-1

To register and bring to default settings the system modules you need to enable the advanced menu. Select Functions > Advanced menu >: Active and press OK.
1.1 Recording of system modules When selecting the Register module option, new modules are registered on both the control and the handheld.The manual must register the modules to display the menu options in question.
< The modules are recorded again and again when you leave the programming mode. In that case, the message Register will appear, but it does not sound like a beep.
1.2 Bring Modules to Default Settings Each module can be returned to the default settings (to default setting). It is advisable to return the module to its default settings before you start programming the module.
1 Register modules A menu option that activates the function that all data bus-connected controls and modules are read by the power station, making it an internal list.
1.1 Registers Menu containing information on the registering of modules.
1.2 Number of modules Menu Option where the total number of modules recorded is indicated.
Register Number of Modules

2.1 Overview Before you can program the system, you need to register and bring it to default settings. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules.
(1) Zone 1 Zone type
2.1.1.1
2.1.1.1.1
Zone 2-168 See above For more than 16 zones, the zones are displayed first in groups and then as above.
2.1.1.1.2 2.1.1.1.2.1
Languages 2 - 4 Same as above
2.1.1.1.3
2.1.1.1.4
2.1.3.1
2.1.3.1.1 2.1.3.1.1.1
Fire 24 Hours Key switch Access zone* In/outrun 1 Walk-in 2 Internal Entry Guard Last door setting Roll-out switch B alarm zone Failure
Zone type configuration 2 -20 Same as above
2.1.3.1.1.2
2.1.3.1.1.3
2.1.3.1.1.4
2.1.3.1.1.5
2.1.3.1.1.6 2.1.3.1.1.7 2.1.3.1.1.8 2.1.3.1.1.9
2.1.3.1.1.10 2.1.3.1.1.11
2.1.3.1.1.12
*Active/neit active depending on the 24 Hours zone option
2.1.3.1.2
2.1.3.1.3
2.1.3.1.3.2 2.1.3.1.3.1
EOL Resistance Zone reaction time Double pulse Swinger shutdown Possible Forced in Group Bridging Area Inactivity Monitoring Pulse key switch* Not Visible on handheld**
2.1.3.1.3.3
2.1.3.1.3.5 2.1.3.1.3.4
2.1.3.1.3.7 2.1.3.1.3.6
2.1.3.1.3.9 2.1.3.1.3.8
2.1.3.1.3.10
*Active/neit active depending on key switch option **Active /neit actively depending on 24 Hours zone option
2.1.3.1.4 2.1.3.1.4.1
Signaling 2-Tone siren 1-Tone Siren Control part buzzer Doorbell
2.1.3.1.4.2
2.1.3.1.4.3
2.1.3.1.4.4
Reporting 2.1.3.1.5
2.1.3.1.5.1
Local Recovery Report* Chooser Delay Subscribe
2.1.3.1.5.4 2.1.3.1.5.3 2.1.3.1.5.2
*Active/neit active depending on key switch option
2.1.3.1.6
(1) Inbraak 2.1.3.1.6.1
An entry is a zone programmed on the system. An area shall be protected by one or more detection modules. A zone is in the system for one entry. A zone may be accommodated in any combination of areas. A zone located in more than one area shall be a common zone and reported to its lowest area number. A common zone shall only be activated when all areas to which it belongs are enabled. The zone shall be deactivated immediately as soon as one of the areas to which it belongs is eliminated.
The power plant can have up to eight built-in inputs. RF receivers and CS208H / CS208/CS216 input modules can be used to increase the number of inputs up to 128 depending on the model of the power plant. More information on the maximum number of zones per model can be found in chapter
< Note:Red text given gives the wrong impression of panel configurations in terms of extensions regarding inputs and wireless and wire expansions. The reference to the

location where the correct configuration can be found. We expect undesirable discussions here that can be avoided by modifying this text. I'd like to rephrase.
2.2.1 Defining a zone You must select the language in which to program the new name and also assign areas to the zone. You can choose a zone type and zone name for each new area. The following steps show how to select a zone type and zone name for a new zone.
2.2.2 Copy Zone Settings You can copy the settings of one zone to another zone or different other zones. All zone settings (except the user-input zone name and RF settings) are copied to target zones. The steps below show how to copy the settings from one zone to another.

2.2.3 Edit a zone type A zone type is a set of characteristics. All zones belonging to a given zone type share the same characteristics. All zones shall be of a zone type. There are 20 predefined zone types and you can edit them. Before you can edit a zone type, activate the advanced menu. In the following example, an intrusion zone type is edited so that the input is activated 24-hour and can be automatically passed if the alarm goes off five times within one switching on period.
2.2.4 Configure Swinger shutdown Swinger shutdown allows the selected zone to be automatically overlaid after a certain number of alarms Before you can configure swinger shutdown, turn on the advanced menu. In the following example, the swinger shutdown is set to 5. This means that a swinger shutdown zone can be activated five times within one set-up period before it is automatically bridged.

Prog. exits
2.2.1.1
2.2.1.1.1
2.2.1.1.1.1
Alarm In/Disable Communication Controls Sirene Sabotage and Failure Test Other
2.2.1.1.1.4 2.2.1.1.1.3 2.2.1.1.1.2
Outputs 2 - 4 Same as above
2.2.1.1.1.5
2.2.1.1.1.6
2.2.1.1.1.7
2.2.1.1.1.8
2.2.1.1.2
2.2.1.1.4 2.2.1.1.3
2.2.1.1.5
2.2.1.1.5.1
2.2.1.1.5.3 2.2.1.1.5.2
2.2.1.1.5.4
2.2.1.1.5.5
2.2.2.1
2.2.2.1.1
2.2.2.1.1.1
2.2.2.1.1.2
2.2.2.1.3 2.2.2.1.2
2.2.2.2
Short siren activation (pulse)
2.2.2.2.1
Enable End of time Kiss-off after activation In/Out keychap/distance bed.
2.2.2.2.2
2.2.2.2.3
2.2.2.2.4
2.2.2.3
2.2.3.1
2.2.3.1.1
2.2.3.1.1.1
Enabled system Disabled system
2.2.3.1.1.2
2.2.3.1.4 2.2.3.1.3 2.2.3.1.2
Power voltage error Battery B alarm zone Sabotage Module failure
2.2.3.1.6 2.2.3.1.5
The power plant contains up to four built-in outputs. The number of outputs can be increased by a CS507 output module and a Cs320 power supply module. For more information about the CS507 output module, see chapter 11. For more information about the CS320 power supply module, see chapter 15.
To program the built-in outputs select Centrale >Outputs.
2.3.1 Configure an output You can change the characteristics of each output. You must specify the events and/or areas that activate an exit, as well as the length of time during which the output should be activated. Events are grouped into the programming structure. A complete list of all possible selectable events can be found in Table 2-1: Central - Outline events. In the following example, output 1 is configured to activate for 15 minutes when a break-in alarm occurs.

# Event # Event
8 Every bridge. 12 Fire control 0 9 Break-in alarm
11 9 Disable under duress 13 9 Control unit medical 1 9 Fire alarm
48 9 Enter code (Note 1) 14 9 Panic function robbery 2 9 24 Hour alarm
37 Programming mode 15 Sabotage Handle 3 9 Malfunction (zone)
49 * 9 Option 1 remote control 27 Doorbell 4 9 Sabotage alarm
50 * 9 Option 2 remote control 47 Control part buzzer 46 9 Any alarm
Test 56 Robbery loud 17 Alarm Memory
29 Dyn. Battery test 57 Robbery silent SIRENE
52 Manual test Sabotage and interference 5 Breaking and entering siren
16 9 Automatic test 25 Brand LED 6 Brand siren
59 Running test 39 Smoke detector reset (node 2) 7 Every siren
To/Disable 40 Flood 60 External siren
21 Enabled 41 Sabotage housing 61 Internal siren
22 Disabled 42 Sirene sabotage Communication
23 System ready 43 Every underbreak. 32 Listen
24 Syst not ready 44 Any short circuit 33 Selecter busy
53 Fully in 45 Any error/open 35 Comm. error
54 Partially in 26 Fire failure 36 Tel. line error
30 Open Period 28 9 Module malfunction 38 Up/Download
31 Closed period 9 Power voltage error 55 Aux comm. error
18 Wrap 10 Battery error
* Events 49 and 50 can only function with RX8w8, RX16w8,RX32w8,rX8i4,RX16i4,or RX48i4 wireless receivers. 9 If these events are programmed to follow (not continuous), the duration of these events is a second.
< 1. When Event 48 is programmed, it is possible to program a user code authorization to select the outputs that can be activated by a particular code.
< 2. Programming Event 39, Reset fire alarm, always following (not continuous).
2.3.2 Configuring the internal siren You can specify the circumstances and/or events that activate the internal siren. Before you can configure the internal siren, turn on the advanced menu. In the following example, a short
Other Controls Alarm · 19 Range · 20 In/Off

signal from the internal siren at the time when the system is switched on with a key switch configured.
2.3.3 Programming the dial-up summer You can specify the circumstances and/or events that activate the control zoom. Before you can configure the buzzer, turn on the advanced menu. In the following example, the control-type zoom is configured to activate it when a malfunction is detected in an expansion module.
2.3.2 2.3.2.1
2.3.2.1.1 2.3.2.1.2
Enable only after closing Enable Only To/Disable Master Code Override Zones In/DiSable Reporting
2.3.2.1.3 2.3.2.1.4
2.3.2.2
2.3.2.1.5
2.3.2.1.6
Region 2.3.2.3
System codes can be four or six digits long. There are two types of programmable codes; one installer code and one coercive code. A coercive code shuts down the system and triggers a compulsive alarm. This is a silent alarm that sends a special report to the reporting destination. To program the codes select Centrale > Codes.
2.4.1 Set the installer code An installer code is linked to enable options and access rights. Before you can set permissions and access rights, activate the advanced menu. In the following example, a new installer code is set for areas 1 and 2 to enable system only.


2.4.1 2.4.1.1
2.4.1.2
2.4.1.2.1
2.4.1.2.1.2
2.4.1.2.1.1
Telephone Customer number Protocol
Phone numbers 2 - 6 Same as above
2.4.1.2.1.3
2.4.1.2.1.4 2.4.1.2.1.4.1
Events Alarm and In/Out
2.4.1.2.1.4.1.1
2.4.1.2.1.4.1.2
Alarm Alarm Recovery In/Disable Zone in/out bridge
2.4.1.2.1.4.1.3 2.4.1.2.1.4.1.4
2.4.1.2.1.4.2
2.4.1.2.1.4.2.1
Sabotage and Recovery Zone malfunction and repair fault module and repair Sirene/tel.line error and recovery Miss RF detector and repair Battery failure RF Detector and repair
2.4.1.2.1.4.2.2
2.4.1.3
2.4.1.3.1
2.4.1.2.1.4.2.3
2.4.1.2.1.4.2.4
Areas 2 - 8 Same as above
2.4.1.2.1.4.2.5
2.4.1.4
2.4.1.4.1
Targets PAC
2.4.1.2.1.4.2.6
2.4.1.4.2
2.4.1.4.3
2.4.1.2.1.4.3
2.4.1.2.1.4.3.1
Nutritional error and repair Aux. Flooding and recovery
2.4.1.2.1.4.3.2
2.4.1.5
2.4.1.6
Send Level Voice Chooser Delay Time Listen
2.4.1.7
2.4.1.2.1.4.4
2.4.1.2.1.4.4.1
2.4.1.2.1.4.4.2
2.4.1.8
2.4.1.8.1
After disabling After stopping siren
2.4.1.8.2
2.4.1.2.1.4.5
2.4.1.2.1.4.5.1
Programming and U/D Zone inactivity monitoring
2.4.1.2.1.4.5.2
2.4.1.2.1.5
2.4.1.2.1.5.1
Channel 1-8 Channel 9-16
U/D Callback number Access code U/ D Callback Number Used Call signals for recording Ignore answering machine Activation callback number after test report Code required for U/d
2.4.1.2.1.5.2
2.4.2.1
2.4.2.3 2.4.2.2
2.4.2.4
2.4.2.6 2.4.2.5
2.4.2.7
2.4.2.8
2.4.2.8.1
System Out of Business Local Programming Communication Settings Download Options
2.4.2.8.2
2.3.2.8.3 2.4.2.8.4
2.4.3.1
2.4.3.2
Autotest Central Interval Hours Minutes Provide Time
2.4.3.4 2.4.3.3
2.4.3.5
2.4.4.1
2.4.4.1.1
Enable/Disable Zone bridging Zone recovery Zone failure Zone sabotage Cancel Recent activation Outrun error
2.4.4.1.2 2.4.4.1.3
2.4.4.1.4 2.4.4.1.5
2.4.4.1.6 2.4.4.1.7
2.4.4.1.8
2.4.4.2
2.4.4.2.1
2.4.4.2.1.1
Sabotage enclosure Module fault Siren malfunction RF Detector absent RF Battery error
2.4.4.2.1.2
2.4.4.2.1.3 2.4.4.2.1.4
2.4.4.2.1.5
2.4.4.2.2
2.4.4.2.2.1
Power voltage error Battery fault Aux. Flood
2.4.4.2.2.2
2.4.4.2.2.3
2.4.4.2.3
2.4.4.2.3.1
Phone Line Error Communication error Automatic test notification Test notification only on in
2.4.4.2.3.2 2.4.4.2.3.3
2.4.4.2.3.4
2.4.4.2.4
2.4.4.2.4.1
2.4.4.2.4.2
Log Full Start/End Programming End Up/Download
2.4.4.2.4.3
2.4.4.2.5 2.4.4.2.6
Bridges when forced in First out/last in
2.4.4.3
Zone type configuration 4.4.3.1 (1) Break-in SIA Code* Contact ID code* Fast format channel*
2.4.4.3.1.1
2.4.4.3.1.1.1
2.4.4.3.1.1.2
Zone Type Configuration 2 - 20 Same as above
2.4.4.3.1.1.3 2.4.4.3.1.1.4
2.4.4.3.1.1.5
Fast format channel recovery*
2.4.4.3.1.1.6
2.4.4.3.1.1.7
2.4.4.3.1.1.8
4+2 Reporting code* 4+ 2 Report code recovery* 200 Bd FSK channel* 200Bd FSC Recovery Canaan Speech message number*
2.4.4.3.1.1.9 2.4.4.3.1.1.10
2.4.4.3.1.1.11
4.4.3.2 Disable/Open Enable Enable Partial Enable Recent Enable Outrun Error Cancel
2.4.4.3.2.1
2.4.4.3.2.1.1
Fast format channel* TELIM Channel* 4+2 Reporting code* 200 Bd FSK channel* Speech message number*
2.4.4.3.2.2
2.4.4.3.2.3
2.4.4.3.2.1.2
2.4.4.3.2.1.3
2.4.4.3.2.4
2.4.4.3.2.1.4 2.4.4.3.2.1.5
2.4.4.3.2.5
2.4.4.3.2.6
Sabotage and malfunction 4.4.3.3 Fast format channel* TELIM Channel* 4+2 Reporting code* 200 Bd FSK channel* Voice message number*
B-Alarm zone 2.4.5.3.1.1
2.4.4.3.3.1
2.4.4.3.3.1.2
2.4.4.3.3.1.3 2.4.4.3.3.1.4
2.4.4.3.3.1.5
2.4.4.3.3.2
Zone sabotage Zone malfunction Sirene sabotage Enclosure tamper Module failure RF Detector absent RF Battery error
2.4.4.3.3.2.1
Fast format channel recovery*
2.4.4.3.3.3 2.4.4.3.3.4
2.4.4.3.3.2.2 2.4.4.3.3.2.3
TELIM Channel* 4+2 Reporting code* 4 + 2 Report code recovery* 200 Bd FSK channel*
2.4.4.3.3.5
2.4.4.3.3.2.4 2.4.4.3.3.2.5
2.4.4.3.3.6 2.4.4.3.3.7
2.4.4.3.3.2.6
2.4.4.3.3.8
2.4.4.3.3.2.7
2.4.4.3.3.2.8
200Bd FSK Recovery Channel*
2.4.4.3.4
2.4.4.3.4.1
Forced shutdown Sabotage control Panic function Robbery Panic feature 1 fire Panic functionality 2 medical
2.4.4.3.4.1.1
Fast format channel* TELIM Channel* 4+2 Reporting code* 200 Bd FSK channel* Speech message number*
2.4.4.3.4.2
2.4.4.3.4.1.2
2.4.4.3.4.3 2.4.4.3.4.4
2.4.4.3.4.1.3
2.4.4.3.4.1.4
2.4.4.3.4.5
2.4.4.3.4.1.5
2.4.5.3.5 Power supply failure Battery error Aux. Flood
2.4.4.3.5.1
2.4.4.3.5.1.1
2.4.4.3.5.2
2.4.4.3.5.1.2
Fast format channel recovery*
2.4.4.3.5.3
2.4.4.3.5.1.3 2.4.4.3.5.1.4
TELIM Channel* 4+2 Reporting code* 4 + 2 Report code recovery* 200 Bd FSK channel*
2.4.4.3.5.1.5
2.4.4.3.5.1.6
200Bd FSK Recovery Channel* 2.4.5.3.5.1.7
2.4.4.3.5.1.8
Communication 2.4.5.3.6 Fast format channel*
2.4.4.3.6.1
Phone line error 2.4.4.6.1.1
2.4.4.3.6.1.2
Fast format channel recovery*
2.4.4.3.6.1.3
TELIM Channel* 4+2 Reporting code* 4 + 2 Report code recovery* 200 Bd FSK channel*
2.4.4.3.6.1.4 2.4.4.3.6.1.5
2.4.4.3.6.1.6
2.4.4.3.6.1.6 2.4.4.3.6.1.7 2.4.4.3.6.1.8
200Bd FSK Recovery Channel*
2.4.4.3.6.2
2.4.4.3.6.2.1
Fast format channel* TELIM Channel* 4+2 Reporting code* 200 Bd FSK channel* Speech message number*
2.4.4.3.6.3
2.4.4.3.6.2.2
2.4.4.3.6.2.3
2.4.4.3.6.2.4 2.4.4.3.6.2.5
2.4.4.3.7
2.4.4.3.7.1
Log Full Start Programming End of programming End of up/downloading
2.4.4.3.7.1.1
Fast format channel* TELIM Channel* 4+2 Reporting code* 200 Bd FSK channel* Speech message number*
2.4.4.3.7.2
2.4.4.3.7.1.2
2.4.4.3.7.3
2.4.4.3.7.4
2.4.4.3.7.1.3
2.4.4.3.7.1.4
2.4.4.3.7.1.5
Special protocol 2.4.5 Selection properties 1 Selection properties 2
2.4.5.1
2.4.4.3.8
Zones 200 Bd FSK
2.4.4.3.8.1
Zones 2 - 99 Same as above For more than 16 zones, the areas are first displayed in groups and then as above.
(1) Zone 1 200 Bd FSK channel*
2.4.4.3.8.1.1
*Active if a relevant protocol is selected at the login bank phone numbers
2.4.5.2

The central bank may report all or specific events to a reporting destination. The communication between the control centre and the reporting destination shall be checked for damage and malfunctions. The power plant can also communicate with the up/download software when a download session is established. To program the built-in outputs select Centrale > Communication.
2.5.1 Set up communication with a reporting destination You can set up a maximum of six reporting destinations to which events are reported by the power station. You can also set which events should be reported to which reporting destination. More information about setting up a communicator can be found in chapter 21. An example of programming the telephone settings can be found in chapter 5.
You can set various conditions to be met before a reporting between the central and reporting destination is established. Before you can set up options for a recovery notification, you need to activate the advanced menu. In the following example, the power station is configured to try calling the reporting destination three times before a communication failure is reported. A recovery notification is also sent when the system is disabled.
2.5.2 Configure communication with up/download software You can set various conditions to be met before a communication connection between the central and up/download software is established. More information about programming through the up/download software can be found in chapter 22.
2.5.3 Configuring the system's automatic test The automatic test shall be performed with set interval to verify that the communication between the control and reporting destination or central and up/download software is functioning properly. In the following example, automatic system testing is set so that it is done every Friday at 12.45 p.m. I would like to thank the rapporteur for his excellent work.

2.5.4 Enable logins You must enable the notification of events on the power station and program the events and zone types for which the notifications are sent. You must set the format of the report and, in case of voice reporting, link each event to a recorded message. You can also assign a message to multiple events. In the following example, voice reporting to phone number 2 is activated for a telephone line error and a spoken message is assigned to this event.
2.5.1.1
Invoer 1 Uitlever 1 Ionlever 2 Ion loud 2
2.5.1.2
2.5.1.3 2.5.1.4
2.5.2.1
Enable Quick-Enable Re-Exit Silent Automatic Activation Always Shut Down With Zone Loss
2.5.2.1.1 2.5.2.1.2
2.5.2.1.3
2.5.2.1.4
2.5.2.1.5
2.5.2.2
2.5.2.2.1 2.5.2.2.2
Panic (7+9) silent robbery Panic (7+9) loud robbery Panics (1+3) fire Panic (4+6) medical Code sabotage OK-LED disable
2.5.2.2.3
2.5.2.2.4
2.5.2.2.5
2.5.2.2.6
2.5.2.3
Bridges Automatic bridge Code required for bridging Control part buzzer Use bridging key
2.5.2.3.1
2.5.2.3.2 2.5.2.3.3
2.5.2.3.4
2.5.2.4
2.5.2.4.1 2.5.2.4.2
Control pane buzzer net/accue error Sabotage in case of zone loss
An area is a group of zones that operate as one and can be switched on and off independently from other areas in the system. Areas are also called partitions. The power station can be divided into separate areas with separate zones, control and user codes for each area. For each area, switching on and bridging options can be set. To program area settings select Centrale >Displayers menu.
2.6.1 Set Timers You can set up within how much time a user needs to disable or enable the system before reporting a full alarm. In the following example, the time for users to leave the monitored zone is set at 12 seconds after system activation. The time for the user to disable the system is also set at 10 seconds.

2.6.2 Configuring an area You can configure area settings, such as options for enable and bridge. You can also activate wireless panic pressers for the operators of an area. In the following example, zonal loss enabler is enabled and a key combination is set to activate a robbery alarm.
< When the Enable zone loss option is enabled, user can always enable the system even if wireless PIR or contact has not sent a monitoring notification within the short supervision time. See page 9 for more information about short supervision times.

Fire verification time Zone inactivity time Zone Inactivity monitoring Zone inaction monitoring Double pulse double pulse opentime B-alarm timer
2.6.1.1
2.6.1.1.1
2.6.1.1.2
2.6.1.1.3 2.6.1.1.4
2.6.1.1.5 2.6.1.1.6
2.6.1.1.7
2.6.1.2
2.6.1.2.1 2.6.1.2.2
Battery test time Power supply failure delay Start-up delay
2.6.1.2.3
2.6.1.3
2.6.1.3.1
Internal siren time External siren times Doorbell time
2.6.1.3.2
2.6.1.3.3
2.6.1.4
2.6.1.4.1
2.6.2.1
Entry Zones Central Sabotage housing 2-wire smoke detector Use standard zone types
2.6.2.1.1
2.6.2.1.2
2.6.2.1.3
2.6.2.1.4
2.6.2.2
2.6.2.2.1
Active battery test Battery test Powerful siren test Manual dialer test Running test
2.6.2.2.2
2.6.2.2.3 2.6.2.2.4
2.6.2.2.5
2.6.2.3
2.6.2.3.1 2.6.2.3.2
Frequency power voltage indicator system time loss Summer/Wintime
2.6.2.3.3
2.6.2.4
2.6.2.4.1 2.6.2.4.2 2.6.2.4.3
Brandsirene Recovery sabotage with main code Trafotype Cancel all Clear controls Restore tamper before turning on
2.6.2.4.4
2.6.2.4.5
2.6.2.4.6
Serial port Configuration Baudrate
2.6.3.1
2.6.3.2
System configurations that can be configured include timers, input options, system clock, serial port and various test options which can be run from the power station. To program system settings, select Centrale >System settings.
2.7.1 Configure Timers You can set timers to check various system functions. In the next example, the timer for the internal siren is set to five minutes. The moment the siren goes off, the timer starts counting. When the timer is over, the siren will automatically be switched off.
2.7.2 Configuring System Options You can set various system options, enable the test options that can be executed from the power station and set the clock options. In the following example, the control centre is programmed to activate the siren and a manual test report to the reporting destination is made during self-test.

2.7.1.1
2.7.1.1.1 2.7.1.1.2 2.7.1.1.3 2.7.1.1.4
Sunday Monday Tuesday Wednesday Thursday Friday Saturday
Areas 2 - 8 Same as above
2.7.1.1.5
2.7.1.1.6 2.7.1.1.7
2.7.2.1
2.7.2.1.1
Sunday Monday Tuesday Wednesday Thursday Friday Saturday 45 Minutes repeat timer
Areas 2 - 8 Same as above
2.7.2.1.2 2.7.2.1.3
2.7.2.1.4 2.7.2.1.5
2.7.2.1.6
2.7.2.1.7 2.7.2.1.8
2.7.3.1
2.7.3.1.1
2.7.3.1.2
2.7.3.2
2.7.3.2.1 2.7.3.2.2
The plant may be programmed to open and close areas automatically at regular intervals and days. Before you can program time schedules, turn on the advanced menu. Select Missions > Advanced menu >: Active and press OK. Then select Centrale >Timesheets.
2.8.1 Set up Schemes You can set a schedule to control the opening and automatically enable any area. In the following example, a scheme is set for area 1 which allows this area to automatically be at 6 p.m. on Mondays. is closed if there is no activity in the property. If activity is observed at the time of closure, the power station shall try to switch on the system after 45 minutes each time until the next opening time or when the system is manually switched on.

2.8.2.1
Interface configuration Zone status Time recording zone Status area Moment recording areas Status system X-10 Message Event log Control text
2.8.2.2
2.8.2.3
2.8.2.4 2.8.2.5
2.8.2.6
2.8.2.7
2.8.2.8 2.8.2.9
Interface configuration Zone name Zone status Site location Status area Location of the site Status of the system Log effect
2.8.3.1
2.8.3.1.1
2.8.3.1.2 2.8.3.1.3 2.8.3.1.4
2.8.3.1.5
2.8.3.1.6 2.8.3.1.7
2.8.3.1.8
Steering X-10 Message Save event in log log Toggle zone bridging
2.8.3.2
2.8.3.2.1 2.8.3.2.2 2.8.3.2.3
2.8.3.3
Programming Querying programming data Forwarding programming dates
2.8.3.3.1
2.8.3.3.2
2.8.3.3.3
Get User Info Set user code Configure users authorization
2.8.3.3.3.1
With PIN Without PIN
2.8.3.3.4 2.8.3.3.5
2.8.3.3.3.2
2.8.3.3.6
2.8.3.4
Control Part Options Panic Function 1
2.8.3.4.1
2.8.3.4.1.1
2.8.3.4.1.2 With PIN Without PIN
2.8.3.4.2
Panic function 2 Control control panel text Control terminal mode
2.8.3.4.3
2.8.3.4.4
The control panel can communicate with home automation controls protocols such as the X-10 protocol. The connection between the control unit and the X-10 home automation control module is made via the RJ11 connectors of the CS507 output module or the CC534 communication module. The integrated RS232 connector on the CS275, CS375, CS575 and CS875 can be used for connection to other home automation control systems. Consult your local GE Security Customer Service for more information.
Updated system information can be transmitted from the power station to the home automation control system in binary or ASCII format. The plant can respond to the applications of the home automation control system and also send orders to the home electronics control system. Before you can program a home automation control system, activate the advanced menu. Select Missions > Advanced menu >: Active and press OK. Then select Centrale >Domotica control.

2.9.1 Activate Broadcasts You can set how updated information is sent from the RS232 interface to the home automation control system. In the following example, the home automation control protocol is enabled to send different end-user messages to the handheld display.
2.9.2 Enable commands and requests You can set which commands can be sent to the serial port by the home automation control system. Possible controls include switching on and off, programming and bridging zones. In the following example, primary functions of the control device transmitted by the home automation control system are activated, accompanied by a valid user code.

2 Central Here all options related to the central processing unit of the alarm system are grouped. The central point of an alarm system receiving the signals from the detectors, checking and processing them and controlling the alarm providers
2.1 Entry points A menu option where options are grouped across all zones
2.1.1 Zones A menu option that contains zone options.
2.1.1.1.1 Zone type A menu option that determines the zone type of a particular zone.
2.1.1.1.2 Zone name A menu option that allows the installer to define a name for each installed zone. For example, Zone 1 can be called Living room PIR
2.1.1.1.3 Region A menu option that shows all areas assigned to the selected zone The selected zone can activate an event for these areas. A zone may be allocated in any combination of areas. A zone located in more than one area shall be a common zone and reported to its lowest area number. A common zone shall only be activated when all areas to which it belongs are enabled. It will be eliminated as soon as one of the areas to which it belongs is taken out.
2.1.1.1.4 Copy zone A menu option that copies the settings for a particular zone to a contiguous set of other zones.
2.1.2 Swinger shutdown A zone property that allows the selected area to be automatically bridged after a certain number of alarms An option from the menu Entry which contains the swinger shutdown counter
2.1.3 Zone type configuration A menu option that contains the properties of zone types and allows the installer to select a predefined zone type. There are 20 predefined zone types. The properties of each zone can be changed. For example, whether a handheld buzzer is activated, or the zone is an In/Outrun 1 or In/outrun 2 zone, a 24-hour zone, etc.
2.1.3.1.1 Zone type A menu option where options are grouped that determine the properties of the selected zone type.
2.1.3.1.1.1 Brand A zone type that generates a fire alarm when activated.
2.1.3.1.1.2 24 Uur Zone type where the reaction is not dependent on the state (on/off) of the system. This zone type is permanently active, 24 hours a day, unless covered by forced activation. An example of a 24-hour zone is a fire, robbery or glass breakage area.
2.1.3.1.1.3 Key switch A zone type that can be used to switch an area on or off with a switch connected to a zone instead of a code. Both pulse and continuous key switches can be used.
2.1.3.1.1.4 Access zone A zone type that operates as a normal break-in zone except during the time of entry and exit when suppressed. The start time is when an In/Out run-in zone is opened. The zone is ready when the system is switched on and no time to enter or exit.

2.1.3.1.1.5 In/Out run 1 A zone type whose events may be delayed for a certain period of time before an alarm is given. This zone type is usually used to allow entry and exit of the property. The time intervals for an In/Out zone are defined in Walk-in 1 and Walking-out 1.
2.1.3.1.1.6 In/Out A zone type whose events may be delayed for a certain period of time before an alarm is given. This zone type is usually used to allow entry and exit of the property. The time intervals for an In/Out zone are defined in Walk-up 2 and Walking 2.
2.1.3.1.1.7 Internal A zone type that is covered when the system is in partial mode.
2.1.3.1.1.8 Entry Guard A zone type that limits false alarms. If a zone with activity monitoring is opened, the control zoom is activated and the time of entry starts before an alarm is created. This can be programmed as a zone type.
2.1.3.1.1.9 Last door setting A zone type that activates the system as soon as the exit area (door) is closed. This zone differs from an exit terminator zone because it is available on the standard CSx75 and connected to a zone that can also give alarms, etc.
2.1.3.1.1.10 Roller shutter switch A zone type used with shutters. These zones can only be used on the power station. They cannot be used on a CS208/CS216 Input module.
2.1.3.1.1.11 B alert zone A zone type that generates a B alarm. The event is reported to the reporting bank using codes set in the reporting code menu of the B-Alarm zone. Usually all alarms are A-alarms. Both A-alarms and B-alerts activate sirens and buzzers. Yet the dispatcher reacts differently to A- as B-alarms. When an A alarm is reported (full alert), a police patrol is sent out, while a security guard is sent off in case of a B-alarm (almost-alert). When two B-alarm enabled events occur within the set B-allenge timer, the second B-Alarm is considered an A-alert. Note:Red indicated text does not cover the charge for alarm follow-up in The Netherlands, hangs many additional appointments around between control room and end user doesn't really want to suggest that it is hanging from an A or B alarm. Please modify.
2.1.3.1.1.12 Malfunction A zone type that sends an alarm when the system is switched on and sends a malfunction when the device is disabled.
2.1.3.1.2 Zone type name A menu option that indicates the name of a given zone type. The name can also be changed with this option.
2.1.3.1.3 Attributes A menu option that groups the additional properties of the selected zone type.
2.1.3.1.3.1 EOL Resistance A characteristic of a zone type specifying that one or two 4K7 EOL (End of Line) resistors are used. An EOL resistance is a resistor placed on a line to prevent the signal from being reflected. Note:EOL resistors are used here to distinguish detection levels, please modify text.

2.1.3.1.3.2 Zone response time A zone property of integrated zones of the power plant, which determines the response rate: This may be 500 ms or 50 ms.
2.1.3.1.3.3 Double pulse A property of a zone type that only causes an alarm if the area is activated twice within a specified time. This is intended to prevent false alarms on PIR.
2.1.3.1.3.4 Swinger shutdown A zone property that allows the selected area to be automatically bridged after a certain number of alarms An option from the menu Entry which contains the swinger shutdown counter
2.1.3.1.3.1 Crossing possible A zone property allowing the area to be bridged.
2.1.3.1.2.1 Forced in A zone property that allows the area to be forced into action.
2.1.3.1.3.1 Crossing the Group A property of a zone type that allows the user to cross multiple zones in one go.
2.1.3.1.3.8 Inactivity monitoring zone A zone property that sends a report to the reporting destination when the zone is not in condition (once activated) within a specified time period
2.1.3.1.3.9 Pulse key switch A zone property that allows you to use a zone input with a pulse key switch. Each activation of the key switch switches on/off the power station state.
2.1.3.1.3.10 Not visible on handheld A zone type property that does not reveal the zone status when enabled.
2.1.3.1.4 Signaling A menu option where the alarm provider properties are grouped for a particular zone type. These properties determine the tones that produce sirens and servants when the selected zone is activated.
2.1.3.1.4.1 2-Tone siren A menu option that activates a 2-tone siren when a break-in alarm is triggered.
2.1.3.1.4.2 1-Tone siren A menu option that determines whether a zone type activates a fire or an inbraaksirene.
2.1.3.1.4.3 Control part buzzer A menu option that activates the handheld zoom when an alarm occurs.
2.1.3.1.4.4 Door bubble A menu option that determines whether a zone type activates a bubble. A doorbell is usually a single signal and is often used as an indicator on a shop door. Option can be set in the zone type. When you turn on the bell, a sound sounds like it, but when you switch off the belly, no.
2.1.3.1.5 Reporting A menu option where reporting options are grouped for the selected zone type
2.1.3.1.5.1 Local A zone property that ensures that the relevant area does not report alarm notifications to the reporting destination. Locally, sirens are activated based on the other characteristics of the zone type.
2.1.3.1.5.2 Recovery notification A menu option that ensures recovery events are reported to the reporting destination.
2.1.3.1.5.3 Selector delay A menu option that determines that a zone type with this zone property is actively delayed by reporting depending on the time set in the dial delay time menu-option. If the system is switched off during this waiting time, the cancelable alarm will not be sent to the reporting destination. The delay can be set from 0- 255 seconds. The value 0 means that no delay is set.

2.1.3.1.5.4 Listen One menu option that sends a report to the reporting destination to indicate that an listening session should be started. To use the listening function, a CS534 communication module must be installed and a microphone connected. When an alarm is activated and reported, the reporting destination can monitor what happens on site. Certain protocols (such as SIA, XSIA Contact ID and 200Bd FSK) include . . listening blocks . that are sent along with the alarm code and indicate that a listen-in session should be started.
2.1.3.1.6 Copy zone type A menu option that copies the zone type settings to a new zone type.
2.2 Outputs A menu option that groups options related to all programmable outputs.
2.2.1 Prog. exits A menu option where options are grouped that configure the outputs.
2.2.1.1.1 Event A random incident, such as system encodings, malfunctions and alarm notifications. A menu option that specifies which event activates an exit.
2.2.1.1.1.1 Alarm A menu option that groups all alarm events which can be selected to send an exit.
2.2.1.1.1.2 To/Toggle A menu option where events are grouped to send outputs. This item is intended to facilitate the selection of output events
2.2.1.1.1.3 Communication A menu option that groups all communication events which can be selected to send an exit
2.2.1.1.1.4 Controls A menu option where the server events are grouped that activate an output.
2.2.1.1.1.5 Sirene A menu option where all siren events are grouped that can be selected to send an exit
2.2.1.1.1.6 Sabotage and malfunction A menu option that groups all sabotage and malfunction events which can be selected to control an output
2.2.1.1.1.7 Test A menu option that contains settings for different tests. This concerns, for example, automatic test reports, active battery tests and so on. should be changed to: An option in the menu Outputs where all test events are grouped together that can be selected to steer an output.
2.2.1.1.2 Time unit A menu option that indicates whether the outputs are controlled in minutes or seconds.
2.2.1.1.3 Tijd A menu option that sets how long an output is activated. If this value is set to 0, the output will follow the event.
2.2.1.1.4 Region A menu option that displays all the areas assigned to the selected output. The selected output can be activated by an event in these areas. A zone may be accommodated in any combination of areas. A zone located in more than one area shall be a common zone and reported to its lowest area number. A common zone shall only be activated when all areas to which it belongs are enabled. She will be eliminated as soon as one of the areas she belongs to is taken out.

2.2.1.1.5 Attributes A menu option in which the programmable attributes of the selected output are grouped.
2.2.1.1.5.1 Continuous One menu option that keeps an output activated until a code is entered on the control panel.
2.2.1.1.5.2 Stop time control with code A menu option that allows the time control to be reset for programmable outputs by entering a valid user code.
2.5.1.1.5 Active during closure One menu option that activates an output after closing time and before opening time. During these periods codes can be used to turn the system on/off. These times are set in time schedules.
2.2.1.1.5.4 Active at opening One menu option that activates an output between opening time and closing time.
2.2.1.1.5 Invert One menu option that reverses the status of an output (normally activated and then deactivated when an event occurs).
2.2.2 Internal siren A menu option that groups options setting the conditions/events to activate internal siren. This is a siren going off inside the building.
2.2.2.1 Sirene activation A menu option that groups events that activate the internal siren.
2.2.2.1.1 Phone line error A menu option that groups options to activate the internal siren when a phone line error occurs.
2.2.2..1.1 Enabled system A menu option that activates the internal siren when a phone line error occurs with an enabled system
2.2.2.1.1.2 Disabled system A menu option that activates the internal siren when a phone line error occurs in an disabled system
2.2.2.1.2 Sabotage A menu option that activates the internal siren when a sabotage occurs
2.2.2.1.3 Module malfunction A menu option that activates the internal siren in case of an expansion module malfunction
2.2.2.2 Short siren activation (pulse) A menu option where internal siren options are grouped. Each option specifies an event where the internal siren is briefly activated. These options are: Enablement, End of maturity, Kiss-off after activation and In/off key switch/remote control.
2.2.2.2.1 Enable A menu option that causes the internal buzzer to go off when the system is enabled
2.2.2.2.2 End of maturity One menu option that ensures internal siren gives a pulse sound after the end of the output time.
2.2.2.2.3 Kiss-off after activation One menu option that will enable the internal siren when the reporting destination receives a switch on message.
2.2.2.2.4 In/Out of key chess/distance bed. One menu option that allows the internal siren to give a short pulse when the system is switched on with a key switch or turned on and off with a Key Switch. One warning signal for activation and two sound signals for shutdown.

2.2.3.3 Output signal type One menu option transforming the internal siren driver output for a speaker into a voltage output for an siren. The built-in 112db siren driver can be converted into a 1A voltage output. The speaker can have a power of up to 15 or 30 Watt, with an impedance of 4, 8 or 16 Ohm.
2.2.3 Controls A menu option where the options for the handheld zoom are grouped.
2.2.3.1 Brighter handheld A menu option where events are grouped that activate the handheld zoommer.
2.2.3.1.1 Phone line error A menu option where the options that activate the dial-up buzzer when a phone line error occurs are grouped.
2.2.3.1.1.1 Enabled system A menu option that activates the dial-up when a phone line error occurs with an enabled system
2.2.3.1.2 Disabled system A menu option that activates the handheld zoom when a phone line error occurs with an disabled system
2.2.3.1.2 Power supply failure A menu option that activates the handheld zoom when power goes out.
2.2.3.1.3 Battery error One menu option that activates the dial-up when a battery error occurs.
2.2.3.1.4 B alert zone A menu option that activates the handheld zoom when a B alarm occurs.
2.2.3.1.5 Sabotage A menu option that activates the handheld zoom when a sabotage occurs
2.2.3.1.6 Module malfunction A menu option that activates the control-duver in case of an expansion module malfunction
2.3 Codes A menu option where options related to the user code are grouped.
2.3.1 4/6 Number codes A menu option indicating whether a four or six digit code is used.
2.3.2 Installer code A 4- or 6-digit code that allows you to program the system. This menu option specifies the areas and parts of the system to which the installer has access. The code can also be used as a default enable/disable code. In that case, the code shall be considered as user 255. An option in the menu Codes where options relating to the installer code are grouped.
2.3.2.1 Code A menu option that sets the user code. This is a number of four or six digits that gives access to the system.
2.3.2.2 Authorisation code A menu option that groups user rights. These options specify the user rights of a person when using the power station.
2.3.2.2.1 Enable only after closure A menu option that can be assigned to a code which only the system may still enable between closing time and opening time (when the system should normally be enabled). If the code is entered between opening time and closing time, the user can normally turn it on/off.
2.3.2.2.2 Enable only A menu option that can be assigned to a code which may only enable the system but cannot perform any other function. This code can be assigned to service personnel, for example.

2.3.2.2.3 To/To disable A menu option that can be assigned to a four or six digit code to enable or disable the system depending on its current status
2.3.2.2.4 Main code A menu option that specifies a code so it can program other user codes, provided it has access to the same areas as the user code. User 1's code is the default main code.
2.3.2.2.5 Crossing Zones A menu option that allows the selected code to bridge zones.
2.3.2.2.6 Enable/Disable reporting A menu option specifying a code that reports (close) and disables (open) to the reporting destination.
2.3.2.3 Region An option from the menu Codes which lists all areas assigned to the selected code The selected code may activate an event for these areas.
2.3.3 Force Code A menu option that sets the coercive code. A coercive code shuts down the system and triggers a compulsive alarm. This is a silent alarm that sends a special report to the reporting destination.
2.4 Communication A menu option where options are grouped for communication between the central and up/download software or reporting destinations.
2.4.1 Reporting destinations A menu option that groups out options related to the transmission. This is a remote location designed to monitor alarm system signals and reports, sending help if necessary. This is also called a control station or PAC.
2.4.1.1 Telephone number for dialling A menu option that specifies the phone number. This four-digit phone number can be used to select DTMF and pulse choices, enter a waiting time or wait for dialing. This series is pre-selected by each telephone number. - Press #0 To insert G. - Press #1 to insert an asterisk. - Press #2 to insert a #. - Press #3 to insert a four-second break. - Press #4 to insert a P (this is the pulse dial). If a waiting time of four seconds is programmed as the first digit, the power station does not wait for an dial tone before choosing the number. Select this option when the phone system has a different dial tone or does not give a dial tones.
2.4..1.2 Telephone numbers A menu option where reporting options of phone numbers are grouped.
2.4.1.1.1 Telephone No A menu option to set the phone number where events should be reported. The operator can report to up to six telephone numbers.
2.4..1.2.2 Customer number A menu option specifying a unique code sent by the voter on the switchboard to the selected phone number. This code is used to identify and invoice the user. Different customer numbers can be set for each phone number and area. This is also called the account number. The letters B, C, D, E, F can be used in account codes for power stations.

2.4.1.1.2.1.3 Protocol A menu option setting the communication protocol used for transmission to the recipient. A maximum of six telephone numbers can be set. There are several protocols available, such as Contact ID, SIA, XSIA, and Fast Format. The recommended protocols are Contact ID and SIA. Please refer to the instructions of the alarm centre receiver to determine which format should be used.
2.4.1.2.1.4 Events A menu option where institutions are grouped to determine which events are reported via the voter to the reporting destination.
2.4.1.2.1.4.1 Alarm and in/out A menu option where events are grouped to the selected phone number
2.4.1.2.1.4.1.1 Alarm A menu option that sends a message to the selected phone number when an alarm situation occurs.
2.4.1.4.2.2.1. A menu option that sends a notification to the reporting destination when the alarm is restored after an alarm.
2.4.1.2.1.4.1.3 To/To disable A menu option that sends a message to the selected phone number indicating when the system is disabled and enabled
2.4.1.2.1.4.1.4 Zone in/out of bridging A menu option that sends a message to the selected phone number when a zone is covered. A notification is also sent when the zone is restored (override terminated)
2.4.1.2.1.4.2 Sabotage and malfunction A menu option where the sabotage and malfunction events are grouped that are reported to the selected phone number
2.4.1.2.1.4.2.1 Sabotage and Recovery A menu option that sends a message to the selected phone number when a sabotage takes place. A recovery notification is also sent when sabotage is no longer active
2.4.1.2.1.4.2.2 Zone interference and recovery A menu option that sends a report to the selected phone number when a zone failure occurs. A notification is also sent when the malfunction is no longer active
2.4.1.2.1.4.2.3 Deterioration and Recovery Module A menu option that sends 'progress module and recovery' notifications to the selected phone number.
2.4.1.2.1.4.2.4 Sirene/tel.line error and repair A menu option that sends a message to the selected phone number when a siren or telephone line error occurs. A recovery message is sent when the error has been repaired.
2.4.1.2.1.4.2.5 Missing RF detector and recovery A menu option that sends a message to the selected phone number when an RF detector is missing. A recovery notification is sent to the reporting destination when the recipient receives a valid signal from the missing transmitter
2.4.1.2.1.4.2.6 Battery fault RF detector and repair A menu option that sends a report to the selected phone number when battery error occurs in an RF detector. A recovery notification is also sent when the battery error is no longer active.
2.4.1.2.1.4.3 Food One menu option where the nutrition events reported to the selected phone number are grouped
2.4.1.2.1.4.3.1 Nutritional error and repair A menu option that reports power error, power failure recovery, battery error and battery error recovery events to the selected phone number

2.4.1.2.1.4.3.2 Aux. Flooding and recovery A menu option that sends a message to the selected phone number when too high a power take is detected. A recovery notification is also sent when the flood situation has been restored
2.4.1.2.1.4.4 Communication A menu option where the communication events reported to the selected telephone number are grouped
2.4.1.2.1.4.4.1 Communication error A menu option that reports a communication error event to the selected phone number
2.4.1.2.1.4.4.2 Automatic test reports A menu option that sends a test message to the selected phone number at fixed times. Units can be set in days or hours
2.4.1.2.1.4.5.1 Programming and U/D A menu option that reports programming and up/download events to the selected phone number
2.4.1.2.1.4.5.2 Inactivity monitoring zone A menu option that sends a notification to the selected phone number when an inactivity event occurs
2.4.1.2.1.5 Fast Format Channels A menu option that determines which Fast Format channels are enabled. These are grouped as Channels 1 . . and Channels 9 .
2.4.1.3 Area of customer numbers A menu option that lists the customer number for each area. The customer number is sent when the relevant area is reported.
2.4..1.4. A menu option that groups options for group skies.
2.4.1.4.1. A menu option determining the number of electoral attempts (1 to 15 attempts) that the voter performs when reporting to the reporting destination.
2.4.1.4.2 Selections FTC A menu option where options are grouped in relation to the number of dialing attempts to a given phone number that is executed before reporting a communication error
2.4.1.4.3 Voice/ peeping / siren A menu option that determines the number of dialing attempts (1 to 15) performed by the voter if voice, pager or siren protocol is selected.
2.4.1.5 Send level voter A menu option setting the volume of the output tone. The electoral transmission level can only be used in combination with the independent ISDN voter TDA2001.
2.4.1.6 Selector delay time A menu option that determines how long (in seconds) the voter waits before a cancelable alarm is sent to the reporting destination.
2.4.1.7 Listening time A menu option that determines how long the control room can listen through microphones at the location of the alarm.
2.4.1.8 Area recovery notification A menu option where recovery reporting options are grouped. Each option specifies when the recovery report is sent to the reporting destination. Recovery messages can be sent When they perform, On shutdown or After stopping siren.
2.4.1.8.1 After switching off A menu option that sends a recovery notification to the reporting destination when entering a code to disable the system.
2.4.1.8.2 After siren has stopped A menu option that sends a recovery report to the reporting destination when the siren stops.
2.4.2 Up/Download A menu option that contains options used to send download sessions between the up/download software and the power station.

2.4.2.1 U/D Callback number A menu option that contains the telephone number to which the operator will call as the option Use U/D Callback Number is on.
2.4.2.2 Access code A menu option that specifies the eight digit access code sent to the power station by the up/download software. The centralized system allows up/download when the centralized operator receives this code from the up/ download software.
2.4.2.3 U/D Use dialback number A menu option that determines the access of up/download software. When the software calls the central, the control center answers the call and then hangs up. After about 36 seconds, the power plant calls back to up/download software.
2.4.2.4 Call signals for recording A menu option that determines the number of call signals required before the operator records to start an up/download session. If the value is 0, the power station will never record the line
2.4.2.5 Ignore Answering Device A menu option used to ignore an answering machine. If the "Two Call Ignore Answerer" option is activated, two phone calls are needed to ignore the answering machine. The first call will be made once or twice. The control unit detects the bell signals and starts a 45-second waiting time. During this waiting time, the operator will answer the next call at the first call. This way is not recommended for commercial applications.
2.4.2.6 Activation callback number after test notification A menu option that allows the power plant to use the callback function when an automatic test message has been sent to the reporting destination. After the test message has been sent, the operator calls up/download software via the callback number. Upload events such as log and download phone numbers can be selected in the up/download software.
2.4.2.7 Code required for U/D A menu option that requires a user code before the user can start up/download.
2.4.2.8 Locks A menu option that groups options which lock certain system functions.
2.4.8.1 Out-of-service system A menu option that allows the up/download software to disable the power station. This option can only be set from the up/download software. The LCD will be sent with a message explaining why the system was shut down. As long as the system is shut down, it's completely inactive. It is not possible to turn the system on/off and no notifications are sent or sirens activated.
2.4.2.8.2 Local programming An option in the menu Communications which disables the installer menu. This option can only be set up via the up/download software.
2.3.2.5.3 Communication institutions A menu option that prevents the installer from changing communication settings (phone numbers, customer numbers etc.). This option should be set using the up/download software.
2.4.2.8.4 Download options A menu option that prevents the installer from changing the following download options: Ignore answering machine U/D Callback number Use locks>System out of service Locks>Local programming Lockdowns>Communication settings Lockouts>Download options Activation callback number after test notification This option should be set up via the up/download software.

2.4.3 Automatic test report A menu option where options are grouped in relation to the automatic tests that can be performed by the system
2.4.3.1 Autotest Central A menu option that determines whether the automatic test message takes place after a certain number of days or hours. The automatic test message can be suppressed if another notification is sent.
2.4..3.2 Interval A menu option that sets the time between two automatic test messages in hours or days. The unit is set in Autotest Central. The options Hour and Minute set the time at which the test is to be performed.
2.4.3.5 Time provided A menu option setting how much time has passed since the previous automatic test. This option determines when the next test report is sent to the reporting destination.
4.4 Reporting A menu option that groups reporting options.
2.4.4.1 Reporting areas A menu option that specifies the events enabled for each area. Events specified in this option will be connected to all areas of the system.
2.4.4.4.1.1 To/To disable A menu option that activates the shutdown report
4.4.1.2 Zone bridging A menu option that sends a notification to the reporting destination when zones are covered.
2.4.4.4.1.3 Zone Recovery A menu option that sends a notification to the reporting destination when zones are restored.
4.4.1.4 Zone disturbance A menu option that sends a notification to the reporting destination when a zone failure occurs
2.4.1.5 Zone sabotage A menu option that sends a notification to the reporting destination when a zone abotage takes place
4.4.1.6 Cancel A menu option that activates the recovery report. A recovery notification is sent to the reporting destination when the system is disabled (within time, set by the voter delay) after an alarm
2.4.1.7 Recent involvement A menu option that sends a notification to the reporting destination if an alarm occurs within five minutes after the power station is switched on. The user number with which the system is enabled is also sent
2.4.8.1.8 Outrun error A menu option that provides for the central authority to send a run-down error reporting code if an in/outrun zone is disturbed when the maturity has expired. This notification is sent along with the user's user number that enabled the system if the power station is not switched off before the timeout expires. The alarm reporting code is also sent. Even if this function is not enabled, the siren will go off as an in/out zone disturbed when the exit time has expired.
2.4.4.2 System reporting A menu option where options are grouped on system reporting.
2.4.42.2 Sabotage and malfunction One menu option where the sabotage and malfunction events are grouped that are reported to the reporting destination.
2.4.4.4.1.1 Sabotage housing A menu option that activates the sabotage switch on the central. The CSx75 has an entrance for a normally closed sabotage switch. When it opens, a sabotage of the housing is reported as an event.

2.4.4.2.1.2 Module malfunction A menu option that sends a notification to the reporting destination in case of an extension module malfunction
2.4.4.2.1.3 Sirene interference A menu option that guards the siren to see if any wires have been cut. If the wires are cut, the central unit sends a notification to the reporting destination.
2.4.4.4.2.1.4 RF Detector absent A menu option that sends a notification to the reporting destination when an RF detector is missing send out RF detectors every 15 or 64 minutes of supervision signals depending on frequency. An RF receiver must receive these signals within a specified time. This time is set in the Supervision Timer menu item. If the RF receiver does not receive these signals during this time window, the Rf detector is considered absent.
2.4.4.2.1.5 RF Battery error A menu option that sends a notification to the reporting destination when battery error occurs in an RF detector
2.4.4.2 Food A menu option where the nutrition events reported to the reporting destination are grouped
2.4.4.2.2.1 Power supply failure A menu option that sends a notification to the reporting destination when power supply fails. For this reporting a delay time can be set.
2.4.4.2.2.2 Battery error A menu option that activates battery error reporting on the power station
2.4.4.2.2.3 Aux. Flood A menu option that activates overflow reporting. A notification is sent to the selected reporting destination when too much power is being taken from a module fed by the system
2.4.5.3 Communication A menu option that groups the communication events reported to the reporting destination
2.4.4.2.3.1 Phone line error A menu option that sends a notification to the reporting destination once the phone line error is fixed.
2.4.4.2.3.2 Communication error A menu option that sends a notification to the reporting destination when, after the number of attempts set in Number of Tries FTC, the system has not been able to connect with the reporting location. The notification shall be sent after the communication with the reporting destination has been restored.
2.4.4.2.3.3 Automatic test report A menu option that sends an automatic test report to the reporting destination with a certain interval
2.4.4.2.3.4 Test notification only on in A menu option that provides automatic test messages only to be sent with an enabled system.
2.4.4.2.4.1 Full log A menu option that sends a notification to the reporting destination when the log is full
2.4.4.2.4.2 Start/end of programming A menu option that ensures the notifications are sent to a given phone number. A notification is sent when local programming is started and terminated.
2.4..4.2.4.3 End Up/Download A menu option that sends a notification to the reporting destination when up/downloading the up/ download software with the central system is complete
4.4.2.5 Bridges when forced into A menu option that activates the bridging report when a zone is forced to turn on.

2.4.4.6 First out/last in A menu option that sends a switch on/off message to the reporting destination indicating when the system is switched on and disabled. This option can only be used in a multi-area system. A report shall be sent indicating the first area opened. A logbook shall then be kept for when the other areas are opened and closed. This information is sent in a second report when the last open area is closed.
2.4.4.3 Reporting codes A menu option that contains the codes sent to the reporting destination when a particular event takes place.
4.4.3.1 Zone type configuration A menu option where all reporting codes are grouped for the selected zone type
2.4.4.3..1.1 SIA Code A menu option setting the SIA code reported for the selected zone type
4.4.3.1.1.2 Contact ID code A menu option that specifies the contact ID code to be used when reporting the selected zone type.
2.4.4.3.1.1.3 2.4.4.3.2.1.1 2.4.4.3.2.1.1 2.4.4.3.3.1.1 2.4.4.3.3.2.1 2.4.4.3.4.1.1 2.4.4.3.5.1.1 2.4.4.3.6.1.1 2.4.4.3.6.2.1 2.4.4.3.7.1.1
Fast format channel A menu option that specifies that the Fast Format channel protocol is used to report selected zone, zone type or event. Other options with this definition are:
2.4.4.3.1.1.4 2.4.4.3.3.2.2 2.4.4.3.5.1.2 2.4.4.3.6.1.2
Fast format channel recovery A menu option setting the channel used in the selected zone, zone type or event for FF channel recovery.
2.4.4.3.1.1.5 2.4.4.3.2.1.2 2.4.4.3.3.1.2 2.4.4.3.3.2.3 2.4.4.3.4.1.2 2.4.4.3.5.1.3 2.4.4.3.6.1.3 2.4.4.3.6.2.2 2.4.4.3.7.1.2
TELIM Channel A menu option that specifies that the TELIM channel protocol is used to report selected zone, zone type or event.
2.4.4.4.3.1.1.6 TELIM Code A menu option that determines the text message sent to the recipient with the TELIM channel. This message contains additional information.
2.4.4.3.1.1.7 2.4.4.3.2.1.3 2.4.4.3.3.1.3 2.4.4.3.3.2.4 2.4.4.3.4.1.3 2.4.4.3.5.1.4 2.4.4.3.6.1.4 2.4.4.3.6.2.3 2.4.4.3.7.1.3
4+2 Reporting code A menu option that lists the reporting code sent to the reporting destination for a 4+2 alarm.

2.4.4.3.1.1.8 2.4.4.3.3.2.5 2.4.4.3.5.1.5 2.4.4.3.6.1.5
4+2 Recovery reporting code A menu option that lists the reporting code sent to the reporting destination for a 4+2 recovery.
2.4.4.3.1.1.9 2.4.4.3.2.1.4 2.4.4.3.3.1.4 2.4.4.3.3.2.6 2.4.4.3.4.1.4 2.4.4.3.5.1.6 2.4.4.3.6.1.6 2.4.4.3.6.2.4 2.4.4.3.7.1.4 2.4.4.3.8.1.1
200 Bd FSK channel A menu option setting the channel used in the selected zone, zone type or event for the 200 Bd FSK protocol. Zones 1 to 99 can be allocated to separate channels. Zones 100 to 128 follow the 200 Bd FSK channel as specified in the zone type.
2.4.4.3.1.1.10 2.4.4.3.5.1.7 2.4.4.3.3.2.7 2.4.4.3.6.1.7
200Bd FSK Recovery Channel A menu option setting the channel used in the selected zone, zone type or event for recovery events of the 200 Bd FSK protocol.
2.4.4.3.1.1.11 2.4.4.3.2.1.5 2.4.4.3.3.1.5 2.4.4.3.3.2.8 2.4.4.3.4.1.5 2.4.4.3.5.1.8 2.4.4.3.6.1.8 2.4.4.3.6.2.5 2.4.4.3.7.1.5
Speech Message Number A menu option setting the voice message to be reported for the selected zone type or event. The message number corresponds to one of the 15 pre-recorded voice messages.
4.4.3.2 In/Out and Cancel A menu option where all reporting codes are grouped for events of in-, out- and cancellation.
2.4..4.3.2.1 Disable/Open A menu option where codes are grouped that are reported at a disable event (opening)
2.4.4.3.2.2 Enable A menu option where the reporting codes are grouped and sent to the reporting destination when the system is enabled
2.4..4.3.2.3 Enable partially A menu option where the reporting codes are grouped and sent to the reporting destination when partly switched on.
2.4..4.3.2.4 Recent deployment A menu option specifying the code (SIA/ContactID/FastFormat/200bd FSK) or voice channel to be used for recent events
2.4..4.3.2.5 Outrun error A menu option where the reporting codes are grouped and sent to the reporting destination when an alarm is activated during the timeout
2.4..4.3.2.6 Cancel A menu option that groups the reporting codes sent to the reporting destination when a cancellation event takes place
2.4.2.3.3 Sabotage and malfunction A menu option where reporting codes are grouped for reporting sabotage and malfunction events to the reporting destination.
2.4.4.3.3.1 B alert zone A menu option where the reporting codes are grouped and sent to the reporting destination when a B alert is taking place.

2.4.4.3.3.2 Zone sabotage A menu option where the reporting codes are grouped and sent to the reporting destination when a zone sabotage event takes place
2.4.5.3 Zone disturbance A menu option where the reporting codes are grouped and sent to the reporting destination when a zone failure occurs
2.4..4.3.3.4 Sirene sabotage A menu option where the reporting codes are grouped and sent to the reporting destination when a siren sabotage takes place.
2.4.5.3.5 Enclosure sabotage A menu option where the reporting codes are grouped and sent to the reporting destination when a Enclosure sabotage situation.
2.4.5.3.6 Module malfunction A menu option where the reporting codes are grouped and sent to the reporting destination in case of an extension module malfunction
2.4.4.3.3.7 RF Detector absent A menu option where the reporting codes are grouped and sent to the reporting destination when an RF detector occurs absent event.
2.4.4.3.3.8 RF Battery error A menu option specifying the code (SIA/ContactID/FastFormat/200bd FSK) or voice channel to be used for RF battery error events
4.4.3.4 Control pan A menu option where the reporting codes are grouped and sent to the reporting destination for any handheld events.
2.4..4.3.4.1 Disable under duress A menu option where the reporting codes are grouped for a Forced Event Disablement. A Forced Off event is a situation in which the user is threatened and forced to disable the system. A coercive code is entered to disable the system normally and activate a compulsive alarm.
2.4..4.3.4.2 Sabotage control A menu option where the reporting codes are grouped and sent for an event sabotage control.
2.4.4.3.4.3 Panic function robbery A menu option where the reporting codes are grouped and sent for an event panic function robbery.
2.4.4.3.4.4 Panic function 1 fire A menu option where the reporting codes are grouped and sent for an event robbery function 1 (fire).
2.4.4.3.4.5 Panic function 2 medical A menu option where the reporting codes are grouped and sent for an event robbery function 2 (medical).
2.4.5.3 Food A menu option where the reporting codes are grouped and sent to the reporting destination when events concerning the power supply occur
2.4..4.3.5.1 Power supply failure A menu option where the reporting codes are grouped that are used to report a power supply error
2.4..4.3.5.2 Battery error A menu option where the reporting codes are grouped and sent to the reporting destination for a battery error. A recovery report is sent to the reporting destination when this condition is no longer active
2.4.5.3 Aux. Flood A menu option where the reporting codes are grouped and sent to the reporting destination when an overflow event takes place

2.4.4.6 Communication A menu option where reporting codes are grouped for reporting the communication events to the reporting destination.
2.4.4.3.6.1 Phone line error A menu option where the reporting codes are grouped and sent when a telephone line error occurs
2.4.4.3.6.2 Communication error A menu option where the reporting codes are grouped and sent to the reporting destination when a communication error event occurs
2.4.4.3.6.3 Automatic test report A menu option that groups the reporting codes sent to the reporting destination when an automatic test report is performed
2.4.4.3.7.1 Full log A menu option where the reporting codes are grouped and sent to the reporting destination when the log is full
2.4.4.3.7.2 Start of programming A menu option where the reporting codes are grouped and sent to the reporting destination when entered in the programming mode.
2.4.4.3.7.3 End of programming A menu option where the reporting codes are grouped and sent to the reporting destination when the installer closes the programming mode.
2.4.4.3.7.4 End Up/Download A menu option where the reporting codes are grouped and sent to the reporting destination when downloading is complete
2.4.4.3.8 Zones 200 Bd FSK A menu option that groups the options for the 200Bd FSK protocol.
2.4.5 Special protocol A menu option that allows you to set up communication protocols when it does not work with a standard reporting destination. Please consult the technical service before using this option.
2.4.5.1 Selection properties 1 A menu option that allows you to configure your own reporting protocol based on the active options.
2.4.5.2 Selection properties 2 A menu option that allows you to configure your own reporting protocol based on the active options.
2.5 Area settings A menu option in which all area settings are grouped. These settings include area options, region estimates and so on.
2.5.1 Times A menu option where the time-driven options are grouped.
2.5.1.1 Timeline 1 A menu option that allows you to set the time within which user must disable system before an alarm occurs. This time can be set from 10 to 255 seconds.
2.5.1.2 Timeout 1 A menu option that allows you to set the time within which user must exit the secure area after system activation before an alarm occurs. This time can be set from 10 to 255 seconds.
2.5.1.3 Period of operation 2 A menu option that allows you to set the time within which user must disable system before an alarm occurs. This time can be set from 10 to 255 seconds.
2.5.1.4 Timeout 2 A menu option that allows you to set the time within which user must exit the secure area after system activation before an alarm occurs. This time can be set from 10 to 255 seconds.

2.5.2 Options A menu option that groups all optional options related to areas.
2.5.2.1 Enable A menu option that groups the enable characteristics of the selected area.
2.5.2.1.1 Quick-onset A menu option that activates the function keys for partial activation and full activation. These options only work on a handheld set for one area.
2.5.2.1.2 Re-exit A menu option that activates the ability to restart the output time without disabling the system. The output time can be restarted if a partially switched system is given the Full in command on the user menu or by means of a function key programmed by the installer to activate the fully enabled mode.
2.5.2.1.3 Silent automatic activation A menu option that automatically switches on the system at a certain time, without the control zoom going off.
2.5.2.1.4 Always silent out A menu option that prevents the buzzer from being activated when the system is switched on or during re-exit time.
2.5.2.1.8 Enable zone loss A menu option that lets the system turn on anyway when RF zones have not reported to the RF receiver for longer than their long supervision time. When this option is off, the system cannot be enabled if an RF zone is not present.
2.5.2.2 Controls A menu option that groups options for the handheld.
2.5.2.2.1 Panic function robbery silent (7+9) A menu option specifying that audio/visual indications are not activated when a robbery alarm is triggered.
2.5.2.2.2 Panic function robbery loud (7+9) A menu option that causes the handheld to beep and triggers internal and external sirens when a panic alarm is triggered.
2.5.2.3 Panic function 1 fire (1+3) A menu option that activates keys 1 and 3 as a keyboard combination for fire alarm. When this option is enabled and these keys are pressed simultaneously, a fire alarm is generated.
2.5.2.4 Panic function 2 medical (4+6) A menu option that activates keys 4 and 6 as a button combination for medical alarm. When this option is enabled and these keys are pressed simultaneously, a medical alarm is generated.
2.5.2.5 Code sabotage A menu option that disables the control for 60 seconds and sends a sabotage message to the reporting destination when 30 keys are pressed without entering a valid code.
2.5.2.2.6 Disable OK LED A menu option that turns off control panel lighting on or off for all areas.
2.5.2.3 Bridges Temporarily disable a zone when switching on the system. A menu option where options for bridging are grouped.
2.5.2.3.3 Auto-Bridging A menu option that automatically bridges track zones when no run-off is detected during the run-out time. The run-off is detected by opening and closing a walk-in/out zone.
2.5.2.3.2 Code required for bridging A menu option that determines whether a user code is required to bridge zones.
2.5.2.3.3 Control part buzzer A menu option that activates the control zoom when a user activates it with one or more oversized zones.

2.5.2.3.4 Use bridging key A menu option that allows the zone to be internally bridged or removed from a bridging system with the zone option.
2.5.2.4.1. Control pane buzzer net/accu error A menu option that causes the control-duver to start beeping when power supply has gone out or a battery error is detected.
2.5.2.4.2 Sabotage in case of loss A menu option specifying that a notification must be sent to the reporting destination and a sabotage alarm is activated when no supervision signals are received from an RF detector. Different reporting codes are sent depending on the system status. In the case of an enabled system, the sabotage and RF detector are sent away reporting codes. In the case of a disabled system, only the RF detector is sent away from reporting code.
2.6 System Settings A menu option that contains programmable system options and reporting options.
2.6.1 Times A menu option where the time-driven options are grouped.
2.6.1.1 Entry points A menu option where the time settings are grouped with respect to entries.
2.6..1.1 Fire verification time A menu option that sets the time span within which a second activation must take place on a smoke detector to generate an alarm.
2.6.1.1.2 Zone inactivity time A menu option that allows you to configure the zone's inactivity option into hours or days.
2.6.1.1.3 Zone inactivity monitoring A menu option setting the zone inactivity time It is possible to specify this time in minutes or hours
2.6.1.1.4 Double pulse time A menu option setting the double pulse time. If a double pulse zone is opened twice within this time, an alarm is triggered.
2.6.1.1.5 Double-pull open time A menu option that sets the double-pull open time. If a double pulse zone remains open for longer than this time, an alarm is triggered.
2.6.1..1.6 B alarm timer A menu option setting the time span in which a second B-alarm Enabled event is considered to be a full-fledged break-in alarm.
2.6.1.2 Food A menu option that groups the timer options related to nutritional events.
2.6.1.2.1 Battery test time A menu option setting how long the central active battery test is executed. It can be set between 0 to 255 minutes, with 0 for "no test."
2.6.1.2.1 Power supply failure delay A menu option that determines the time between detecting a power voltage error on the power station and sending a notification to the reporting destination. The recovery event is transmitted four minutes after the mains voltage has been restored.
2.6.1.2.3 Start-up delay A menu option that sets the time for a nutritional error to be repaired in case of a power failure or when restarting the system. The time after which the output takes place can be set to 0-60 seconds. 0 does not mean boot delay.
2.6.1.3 Alarmers A menu option that contains timers for internal siren, external siren and doorbell on the handset.
2.6.1.3.1 Internal siren time A menu option that determines how long the internal siren is audible before it automatically stops. This time can be set from 0 to 255 minutes. If 0 is set here, the siren remains active until a valid code is entered on the handler.

2.6.1.3.2 External siren time A menu option that determines how long the external siren will continue to go off before it automatically stops. A new alarm will activate the external siren again during the time specified in this option. This time can be set from 0 to 255 minutes. If 0 is set here, the siren remains active until a valid code is entered on the handler.
2.6.1.3.3 Door-door time A menu option that sets the doorbell time. This time can be set from 0 . . 12 seconds in steps of 50 ms (1/20 seconds) 0 = following zone.
2.6.1.4 Communication A menu option in which timers for communication events are grouped.
2.6.1.4.1 Line error delay time A menu option that determines the waiting time before a phone line error is reported after a telephone line error has been detected. A telephone line error is reported in Service required > Restore if Line error delay time = 0.
2.6.2 Options A menu option that groups all optional options related to the settings of the power plant.
2.6.2.1 Entry points A menu option where options are grouped that options regarding other zone settings.
2.6.2.1.1 Central zone A menu option that disables any hardware zone inputs on the power station. This gives a fully wireless alarm system.
2.6.2.1.2 Sabotage housing A menu option that activates the sabotage switch on the central. The CSx75 has an entrance for a normally closed sabotage switch. When it opens, a sabotage of the housing is reported as an event.
2.6.2.1.3 2-Druff smoke detector A menu option that activates the 2-wire smoke detector capability in the central. A 2-wire smoke detector is connected to the power plant with two wires instead of four. Maximum three 2-wire smoke detectors can be connected.
2.6.2.1.4 Use standard zone types A menu option that uses the default zone types in the country-specific default settings for the selected country instead of configured zone types.
2.6.2.2 Test options A menu option that groups test options. These options specify the tests that can be performed on the plant.
2.6.2.2.1 Active battery test A menu option that activates a test to determine whether the battery is connected to the system. This test is usually performed automatically when the system is first started and then at periodic times.
2.6.2.2.2 Battery test on switch-on A menu option that activates a battery test when switched on. This is an automatic test performed by the power station during switching on to check that the battery is functioning properly. The power plant lowers the charge voltage so that current is absorbed from the battery. If the system is not switched on between 00:01 to 23:59 hours, the test shall be performed at 00:00.
2.6.2.3 Manual siren test A menu option that activates the siren test when in the User's menu command Manual test is selected.
2.6.2.4 Manual voting test A menu option that inserts a voter test into the manual test. A manual call to the reporting destination is executed and the corresponding signal is sent.

2.6.2.5 Running test A menu option that activates the loop mode. In this mode, a authorized user can test the detectors and check that all zone inputs are working correctly.
2.6.2.3 Clock A menu option that groups options which configure the clock.
2.6.2.3.1 Frequency of mains voltage A menu option that provides an accurate clock in situations where different power frequencies are used: possible settings are 50 Hz or 60 Hz.
2.6.2.3.2 System time loss indication A menu option that activates the service message .Control system time loss .
2.6.2.3.3 Summer/Winter time A menu option that allows an automatic transition between summer and winter time.
2.6.4.1 Brandsirene A menu option that determines the type of siren to be activated when a fire alarm occurs: a 2-tone or 1-tone siren.
2.6.2.4.2 Recovery of sabotage with main code A menu option that allows a main user to reset the system after a service message. If this option is disabled, an installer must reset the system every time a service message appears. The user must detect the cause of the alarm before switching on again and contact the installer if necessary.
2.6.2.4.3 Trafotype A menu option that specifies the trafotype used. There are two possibilities: 25 VA or 40/50 VA. Depending on the setting, power supply from CS275, CS375 and CS875 can deliver a capacity of 0.5 A (25 VA setting) or 1 A (40/50 VA set up) to the AUX connections. If this is not enough, additional CS320 power modules can be used.
2.6.2.4 Cancel All A menu option that cancels every outstanding report to be reported. Any alarms in the buffer that are still to be sent to the reporting destination will be cancelled.
2.6.2.4.5 Clear controls A menu option that allows a authorized user to disable all LED drives on the control (except for voltage LED) and lock the controls so it does not respond to pressed keys anymore.
2.6.2.4.6 Reset sabotage for enable A menu option that forces you to reset the sabotage notification after a tamper event has been reported before a user can enable the system. To do this, you need to start and leave the programming mode.
2.6.3 Serial port A menu option where the settings are grouped from the integrated Serial RS232 communication port.
2.6.3.1 Protocol A menu option on the serial port that specifies what the serial gate is used for. This can be set to Serial printer or Domotica control protocol.
2.6.3.2 Baudrate A menu option that sets the speed of data communication from the computer to the central. This can be set from 600 baud to 76800 baud. It is recommended to use the default setting of 9600 baud
2.7 Timing A menu option in which time schedule mismatches are grouped. These options configure the time frame performances used by the power plant for automatic activation.
2.7.1 Area opening A menu option that lists the weekdays in which each area is open.

2.7.2 Auto-integrating Areas A menu option that allows the power plant to automatically enable at a specified time. At that moment, the control device will beep for 50 seconds before the power station activates. The activation process is stopped when a code is entered on the control panel.
2.7.2.1.8 45 Minutes repeat timer A menu option that the power station tries to enable every 45 minutes, until the next opening time or until the system is switched on. The 45 minute Repeat timer is extended when there is activity in the building. This ensures that the Ready LED goes off and on. If enabled notifications are sent, the corresponding user code is 97.
2.7.3 Switching Times A menu option where items related to automatic switching on and the opening and closing schedules of areas are grouped.
2.7.3.1 Disable/Open A menu option setting the time at which the selected schedule switches to opening time. At that time, codes with the .- . . enable only after closure .
2.7.3.2 Include/Enclose auto A menu option that determines the time when to use Auto-enabled areas start automatically to enable selected areas. Users with the permission 'only enable after closure', may use Area opening Enable selected areas only after this time period has passed.
2.8 Domotic control A menu option that groups options related to the home automation control system.
2.8.1 Protocol A menu option setting the home automation control protocol to binary or ASCII
2.8.2 Authorization transition A menu option that contains methods to send updated information to the home automation control system from the RS232 interface.
2.8.2.1 Interface configuration A menu option that activates interface configuration transition broadcasts. This authorisation transmits changes to zones, areas and so on to the home automation control system
2.8.2.2 Zone status A menu option that sends the full status for one zone
2.8.2.3 Time frame A menu option that allows the power plant to send a snapshot of the current status of the zones. A snapshot transmits the activated, bridged, malfunction/sabotage and alarm memory status for sixteen zones. This is done separately by zone
2.8.2.4 Area status A menu option that activates status area transition broadcasts
2.8.2.5 Sites for momentisation A menu option that activates the snapshot area transition broadcasts
2.8.2.6 System status A request/demand command from the home automation control system to the CS586 Memory/RS232 module to forward system status
2.8.2.7 X-10 Message A menu option that activates an X-10 message transition broadcasts
2.8.2.8 Event log A menu option that activates the event log transition broadcasts
2.8.2.9 Control section text A menu option that allows the home automation control protocol to send different end-user messages to the handheld display.
2.8.3 Changes/retrieving A menu option that performs controls sent by the home automation control system to the serial port module.
2.8.3.1 Retrieving A menu option in which the home automation control requests are grouped.

2.8.1.1.1 Interface Configuration A menu option that allows the power plant to respond to 'interface configuration' retrievals from home automation control system
2.8.3.1.2 Zone name A menu option that allows the home automation control system to change on central zone names
2.8.3.1.3 Zone status A menu option that allows the power plant to respond to zone status retrievals from home automation control system
2.8.3.1.4 Time frame A menu option that allows the power plant to respond to snapshot zone retrieval from home automation control system
2.8.3.1.5 Area status A menu option that allows the power plant to respond to status field retrievals from home automation control system.
2.8.3.1.6 Sites of interest A menu option that allows the power plant to respond to snapshot field retrieval from home automation control system
2.8.3.1.7 Status system A menu retrieval from the home automation control system to the CS586 memory/RS232 module to view the entire system status
2.8.3.1.8 Log event A menu option that allows the power plant to write an event in the log every time an output on the CS507 Output Module is activated and each time an exit is restored
2.8.3.2 Steering A menu option in which home automation control commands are grouped.
2.8.3.2.1 X-10 Message A menu option that allows the power plant to respond to X-10 message commands from home automation control system
2.8.3.2.2 Save event to log A menu command that allows a serial port-connected module to store events in the log and send them to the reporting destination using the voter.
2.8.3.2.3 Toggle zone bridging A menu option that allows the power plant to respond to toggle zone bridging commands from home automation control system.
2.2.3.3 Programming A menu option in which home automation control commands are grouped.
2.8.3.3.1 Requesting programming dates A request/demand command sent by the home automation control system to the CS586 Memory/RS232 module. This is used to read configuration data from the power station via the serial port.
2.8.3.3.2 Forwarding programming dates A request/demand command sent by the home automation control system to the CS586 Memory/RS232 module. This retrieval is used to configure the system via the serial port.
2.8.3.3.3 Get User Info A menu command that allows the serial port-connected module to read out programmed settings for a specific user. This can be activated with a PIN or without a PINS.
2.8.3.3.4 Configuration of user code A menu option in which home automation control commands are grouped. The home automation control protocol allows you to define new users in the power station. These commands specify the user code.
2.8.3.3.5 Configuration Users Authorisation A menu option in which home automation control commands are grouped. The home automation control protocol allows you to define new users in the power station. These commands specify the user permission, such as on/off.
2.8.3.3.3.1 With PIN A request/request command from the home automation control system to the CS586 Memory/RS232 module to allow user access only with a PIN code.

2.8.3.3.3.2 Without PIN A request/demand command from the home automation control system to the CS586 Memory/RS232 module to allow user access only without a PIN code.
2.8.3.3.6 Set date/time A request/request command sent by the home automation control system to the CS586 Memory/RS232 module for setting date and time.
2.8.3.4 Control Options Another menu option where settings are grouped that activate home automation control commands regarding servants.
2.8.6.1 Panic function 1 A menu item in which control options for home automation control commands are grouped. These command cocks activate the first panic function of a handler. These options are: With PIN and Without PIN.
2.8.3.4.1.1 With PIN A request/request command from the home automation control system to the CS586 Memory/RS232 module to allow user access only with a PIN code.
2.8.3.4.1.2 Without PIN A request/demand command from the home automation control system to the CS586 Memory/RS232 module to allow user access only without a PIN code.
2.8.3.4.2 Panic function 2 A menu option that activates the home automation control command which can trigger a handheld's second robbery function.
2.8.3.4.3 Handlebar Text A request/demand command sent to the control system by the home automation control system. It is used in terminal mode to enable the serial port-connected module to place text on the control panel.
2.8.3.4.4 Control terminal mode A menu option that makes the control panel a home automation controller when requested by the CS586 memory/RS232 module.
2.8.4 Address LCD handheld A menu option that uses the programmed address of the handheld as the terminal mode of the server and the control text.
Net input voltage (25VA Trafo) 230V - 50Hz - 25VA
Net input voltage (40VA Trafo) 230V - 50Hz - 40VA
Power consumption at 230V~ (25 VA) 0.108 A
Power consumption at 230V~ (40 VA) 0.173 A
Main panel supply 16.5 V~ characteristic
Power supply 13.8V ± 2%
Lamp current (CS275-375 -575-875) 2.0 A max. at 13.8V ± 2%
Lamp current (CS175) 1.0 A max. at 13.8V ± 2%
Aux. Power output (CS275-375 -575-875) 1,2 A max. at 13.8V ± 2%
Aux. Power output (CS175) Note: Maximum continuous current to power supply outside the control equipment in the absence of alarm situations.
0,5 A max. at 13.8V ± 2%
Power supply specifications · Food specifications

Battery power output (CS275-375 -575-875) 0,800 A max. at 13.8V ± 2%
Exit power battery (CS175) 0,500 A max. at 13.8V ± 2%
Battery type and max. Power (Great metal housing for CS575M-CS875M)
Rechargeable lead-acid battery, 16 Ah 12 V nom.
Battery type and max. power (Policarbonate housing for CS275 .CS375-CS575-CS875)
Rechargeable lead-acid battery, 10 Ah 12 V nom.
Battery type and max. Power (Small metal housing for CS175M-CS275M-CS575M)
Rechargeable acid-lead battery, 7.2 Ah 12 V nom.
Main power consumption main panel (No EOL) 60 mA at 13.8V ± 2%
Main power consumption panel (with EOL on zones and monitored fire and siren outputs)
91 mA at 13.8V ± 2%
105 mA at 13.8V ± 2%
Main power consumption panel (with EOL on zones and monitored fire and siren outputs) and phone line active

Number of code combinations From 9,999 (4 digits) to 99,999 (6 digits)
Double loop (default) 4.7 kOhm, 2% 0.25W
Double loop (2-wire smoke) 560 Ohm, 2% 0.25W
Built-in siren drive 2-tone (pulsing and mooring)
Aux outputs (relais) NC/NO relay P
Aux outputs (OC) Electronic output Permissible power: 40 mA at 13.8 V
External siren Electronic output P permeable power: 1 A at 13.8 V
Internal siren Electronic output P permeable power: 1 A at 13.8 V
Environment (commodity) IP protection class IP30
Large metal housing Dimensions 315x447x80 mm Color Beige
Small metal housing Dimensions 250x250x80 mm Color Beige
Large plastic housing Dimensions 257x400x112 mm Colour Grey
Small plastic housing Dimensions 257x228x112 mm Colour Grey
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
* Phase F315 mA L 20x5 F1 Battery T 5 A L 20 x 5
General provisions specifications · Shipping weight 4,500 Kg · Fuses

3.1 Overview Each handset is equipped with a buzzer and an LCD screen on which messages can be displayed in various languages.
Each handheld must be registered, set to the country settings of the selected country and reset to factory settings before you start programming the system. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules.
View Control Options 3.1 3.1.1
3.1.1.1
Zone info on enabled Service message Customer message Clock 24-hour notation OK for menu Locking control panel texts OK LED disable Codes not visible Always Multiple areas
3.1.1.2 3.1.1.3
3.1.1.4
3.1.1.5 3.1.1.6
3.1.1.7 3.1.1.8 3.1.1.9
3.1.1.10
Quiet handler Doorbell 5 Sec. silence after reviewave Peeptoon panic keys Beeptoone at zone loss
3.1.2.1
3.1.2.2 3.1.2.3
3.1.2.4
3.1.2.5
3.1.3 3.1.4
Sabotage enclosure Main control panic keys Wrjzigen tel.nr by user
F2 - F3 Functions Same as above
X-10 Module 1
3.3.1.1
Module 2 - 10 Same as above
3.3.1.2
3.4.1.1
(1) Area 1 Control 1
3.4.1.1.1
Areas 2 - 8 Same as above
Controls 2 - 8 Same as above
3.5.1.1
Languages 2 - 4 Same as above
3.5.2.1
3.5.2.1.1 3.5.2.1.1.1
Customer message Out of business message
Rule 1 rule 2
Languages 2 - 4 Same as above
3.5.2.1.2
3.5.2.1.1.2
3.5.2.1.3
3.5.2.1.3.1
Zones 2 - 168 Same as above
3.5.2.1.4
3.5.2.1.4.1
Areas 2 - 8 Same as above
3.5.2.1.5
Taal 1 3.5.2.1.5.1
3.5.3.1
Usernames 2 - 99 Same as above
3.5.4.1
Zone Name 2 - 20 Same as above
Zone Part number Control part Def. Model Version Default Settings
3.10 3.11
To program the current handheld, select Installer menu > This handheld.
3.2 Configure control sharing options You can configure the LCD screen, control zoom and combination keys. In the following example, the control is configured to show all codes as stars on the screen instead of numbers. The handheld zoom is also configured to give a sound if the wireless receiver does not respond within the time of supervision. More information on supervision can be found in chapter 9.

3.3 Multi-area display You can program a handheld in such a way that it displays one area or multiple areas by default. A single-area control device allows the user to switch on only one area, while a main-range control unit can enable one or more areas. A user with the right rights of use can convert a handheld for one area into a handset that can display multiple areas.
3.4 X-10 Assign modules The control panel can be used to activate selected X-10 modules. In the following example, module number for module 1 is set to 3 and house code on L.
3.5 Copying the server settings The settings of the current handheld can be copied to one or more other servants within the system. In the following example, the settings of the current handheld are copied to another control device within the system.

3.6 Configure the text on the handheld You can set different languages on the handheld. In the following example, French is set as a second language on the handheld.
More information about changing the language of the user interface or setting up messages on the handheld can be found in chapter 5.
3.7 Set the operating sub-area and control part number When you first start the handler, you are asked to specify the language, country and area and number of the servant. The handheld can only connect to the bus after these numbers have been set. The prompts for the area number and control number appear only on first startup. You can change these numbers again by going to This handheld >Handel and This handheld part number.
3 This handheld A menu option that contains the settings of the current handheld. This provides the ability to bring the handheld to default settings, configure control options and check software version and type.
3.1 Control Options A menu option that groups options for the handheld.
3.1.1 Display A menu option that groups LCD view options for the control.
3.1.1.1 Zone info on enabled A menu option that activates mode that displays zone status on the control panel when the system is enabled. When this mode is off, the zone status will not be displayed when the system is switched on.
3.1.1.2 Service message A menu option that turns on or off the service messages on the control panel. A message on the LCD handheld informing user or installer about a system error. The service message disappears from the control panel when the installer goes in and out of the programming mode. The message is used as an installer reset.
3.1.1.3 Customer message A menu option that displays the customer message on the LCD handheld.
3.1.1.4 Clock A menu option that displays the clock on the handheld. This is the internal real-time clock used for switching times and intervals for automatic test reports
3.1.1.5 24-hour notation A menu option that changes between 24-hour and 12-hour notation.
3.1.1.6 OK for Menu A menu option that activates the menupromps . .OK for menu .

3.1.1.7 Locking control handles A menu option that prevents the standardized handheld message from being edited.
3.1.1.8 Disable OK LED A menu option that turns off control panel lights on or off for a particular handset. Both options must be activated to enable this function OK turn off LED switches all LEDs on the control panel (except for the Power-LED) when no key has been pressed in 60 seconds. All LED performances will be lit again as soon as any button is pressed.
3.1.1.9 Codes not visible A menu option that displays the user code as dashes when programming codes with the handheld. If this option is disabled, the numbers will be displayed instead of the dashes themselves.
3.1.1.10 Multiple areas always A menu option that allows you to activate a mode in which the status of an area is always displayed on the main control pane, regardless of the state of the area.
3.1.2 Summer A menu option that groups buzzer features for the current handheld. It determines the events that activate the handheld summerer.
3.1.2.1 Quiet handheld A menu option that expands the entry/exit buzzer of the handset and doorbell.
3.1.2.1 Door bubble A menu option that sets the sound of a doorbell. This could be a thing dong or a beep.
3.1.2.3 5 Sec. silence after reviewave A menu option that dampens the pulsating handheld zoom for five seconds when pressing a key.
3.1.2.4 Peep tone panic keys A menu option that sounds a beep on the control panel when the key combination for a panic alarm is held back long enough.
3.1.2.5 Beep tone in case of zone loss A menu option that activates the handheld zoom, which starts to squeak when an RF transmitter is absent. This beep indicates that the receiver has not received a wireless transmitter supervision signal.
3.1.3 Sabotage housing A menu option that sends a tamper report to the reporting bank and activates a siren and/or control lever when a malfunction occurs on the operator's enclosure. A sabotage occurs when the enclosure of a hardware device (e.g. central, siren or control gear) is disturbed. The CSx75 has an entrance for a normally closed sabotage switch. When it opens, a sabotage of the housing is reported as an event.
3.1.4 Main control A menu option that sets the default mode of the selected control panel to multiple areas. This is a operating mode on a control panel that gives a user or installer access to different areas in the system and allows him to perform functions in those areas. A control panel in the .v.Several area display .fashion can be temporarily switched to the ♪One area display "Fashion" mode and a handheld with .g.Show one area .w. mode can be switched to "Multi-area display" mode for a time.
3.1.5 Panic keys A menu option that allows you to program panic keys. The CSx75 allows the user to generate different types of robbery alarms by pressing two keys simultaneously.

3.1.6 Change user's tel.nr A menu option that allows the user to change the phone numbers used for alarm reporting. Usually the installer programming the telephone numbers of the reporter and he/she is the only person who can change the number. When a Speech Protocol and Sirene protocol are used, the user may change the telephone number. These protocols usually report to a mobile phone of the owner instead of to the reporting bank.
3.2 Function keys A menu option that groups all programmable function key options. Function keys can be programmed by the installer to a specific function per key.
3.3 X-10 Modules A menu option that contains X-10 module options for the selected handheld
3.3.1.1 Module number A menu option setting the X-10 module number used to identify a particular X-10 modules on the selected module. Each system module shall be assigned a CSx75 databus module number. The system uses this number to identify the module. It is also used to report module problems (such as sabotage and module oversight issues) to the reporting bank.
3.3.1.2 X-10 Home code A menu option setting the code to identify a particular building. This code is required if any neighbouring buildings are also equipped with an X-10 home automation control system. More information about the X-10 home automation control system can be found at www.x- 10europe.com.
3.4 Copy Handle A menu option that copies the current control settings to one or more other servers in the system.
3.4.1 To one handheld A menu option that specifies that the current control settings are copied to a particular handheld.
3.4.2 To all servants A menu option that specifies that the current control settings are copied to all connected servants.
3.5 Control section of texts A menu option that groups the language options for the current handheld. This allows the installer to set up texts such as zone name descriptions and user names.
3.5.1 Language choice A menu option that sets the language of the handheld. There are four languages possible.
3.5.2 Texts by language A menu option that groups descriptors such as Customer Message and Outdoor Business message. These messages are independent of the language.
3.5.2.1.1 Customer Message An option in the menu This handheld where customer message can be changed
3.5.2.1.2 Out of business message A menu option that displays the message text displayed on the control panel when the power station is in off-line mode
3.5.2.1.3 Zone names A menu option that indicates the names of all zones and allows these names to be changed.
3.5.2.1.4 Area names A menu option that specifies the name of each area.
3.5.2.1.5 Copy language A menu option that copies data from the current server descriptors to one or more other servants in the system. These include zone descriptors, customer message, disable message, zone names and area names.

3.5.3 Usernames A menu option that specifies a name for each user code. The maximum length for a username is 15 characters.
3.5.4 Zone type name A menu option that allows the installer to define names for each installed zone type. For example, Type 1 Break-in A alarm, Type 2 Fire alarm, type 3 Walk-in/Wallout etc.
3.5.5 Glossary A menu option that activates the Glossary. This is a fixed set of words that accelerates the creation of texts. When the user/installer enters a character, the handheld automatically displays a word it already knows. The Glossary function is enabled by default.
3.6 Zone A menu option that specifies the area to which the selected handheld has access if it is a control for one region. This menu option also determines, together with the control number, the bus module number for both controls for one or more areas.
3.7 Control Part Number A menu option setting the control number within the area. The handheld can be numbered from one to eight. The number chosen is linked to the module number reported to the reporting bank in case of sabotage or problems with expansion modules.
3.8 Control section Def. A menu option for resetting the handheld to the country settings of the selected country.
3.9 Model Menu option showing the current model of the handheld.
3.10 Version Menu option showing the current software version of the handheld.
3.11 Default Settings A menu option that reset the handheld to factory settings.


Power consumption . . Normal conditions (piezo off) 78 mA at 13.8V ± 2%
Power consumption . . Normal conditions (pieze on) 90 mA at 13.8V ± 2%
Power consumption . . Stand by 7 mA at 13.8V ± 2%
Power consumption . . In alarm 36 mA at 13.8V ± 2%
Size PCB Dimensions (width x height x depth) 90x135x1.2 mm
Size housing Dimensions (width x height x depth) 102x153x29 mm

Power consumption . . Normal conditions (piezo off) 92 mA at 13.8V ± 2%
Power consumption . . Normal conditions (piezo on) 103 mA at 13.8V ± 2%
Power consumption . . Stand by 12 mA at 13.8V ± 2%
Power consumption . . In alarm 65 mA at 13.8V ± 2%
Size PCB Dimensions (width x height x depth) 90x135x1.2 mm
Size housing Dimensions (width x height x depth) 102x153x29 mm

Power supply 13.8V ± 2%
Power consumption . . Normal conditions (piezo off) 90 mA at 13.8V ± 2%
Power consumption . . Normal conditions (pieze on) 100 mA at 13.8V ± 2%
Power consumption . . Stand by 7 mA at 13.8V ± 2%
Power consumption . . In alarm 36 mA at 13.8V ± 2%
Size PCB Dimensions (width x height x depth) 90 x 135 x 1.2
Size housing Dimensions (width x height x depth) 102x153x29 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Short circuit Enabled Change status
Double loop 9k4 Disabled Silent
4k7 Enabled Change status
Short or fully open

(1) Zone Control 1 Model Version Default settings
4.1 4.1.1
4.1.1.1
4.1.1.3 4.1.1.2 Areas 2 - 8 Same as above
Controls 2 - 8 Same as above
For programming other servants select Installer menu > Other servants and select the area to which the handler belongs. You can view the version and model of the handheld, and bring the selected handheld to default settings.
4 Other servants A menu option that groups programming options for other servers in the system.
4.1.1.1 Model Menu option showing the current model of the selected handheld.
4.1.1.2 Version Menu option showing the current software version of the selected handler.

5.1 Overview It is possible to connect a wireless receiver of 868 MHz or 433 MHz to the CSx75. By connecting a receiving module, the CSx75 control panel is compatible with wireless detectors and remote controls.
RX8I4CA PCb 433 MHz receiver for up to 8 wireless zones.
RX16I4CA PCb 433 MHz receiver for up to 16 wireless zones.
RX48I4CA PCb 433 MHz receiver for up to 48 wireless zones.
RX8W8CA PCb 868 MHz receiver for up to 8 wireless zones.
RX16W8CA PCb 868 MHz receiver for up to 16 wireless zones.
RX32W8CA PCb 868 MHz receiver for up to 32 wireless zones.
Type of receiver Description


1 Processor 4 LED . . Wireless communication . 7 Not used
2 No function 5 Control part databus connection 8 Antenna
3 Databus control LED 6 Sabotage lid 9 Dipswitches
5.2.1 Connecting an RF433 MHz Wire the RF433 MHz receiver connections 5 as follows:
POS(+) Connect to the KP DATA connection of the CSx75. Power consumption is 30 mA.
COM Connect to the KP SNE (earth) connection of the CSx75.
Data Connect to the KP DATA connection of the CSx75.
Connection Description

1 34 5 38
2 33 6 37
3 32 (default) 7 36
4 39 8 35
= AAN = UIT DIP switch 4 not used
5.2.3 Status states RF433 MHz receiver When you switch on the CSx75, the middle (red) LED must start blinking. The LEDs on the receiver represent the status of the module.
Red Blinking Red
Normal data communication with the CSx75. No data communication with the CSx75. Check the wiring and power supply.
Yellow flashing yellow out
Receives radio signals from wireless reading detectors. There are no radio signals coming in at the moment.
" The red LED at the bottom of the RF433 MHz receiver can burn weakly, but is not used as an indicator and may be ignored.
For more information about installing the RF433 MHz receiver in different enclosures, see chapter A-4 Install a base system.


1 Set up jumper 5 LED . .wireless communication .
2 Sabotage lid 6 Control part databus connection A Processor
3 Eeprom 7 Not used B Dipswitches
4 Databox Control LED 8 Antenna
Data Connect to the KP DATA connection of the CSx75.
COM Connect to the KP SNE (earth) connection of the CSx75.
POS(+) Connect to the KP DATA connection of the CSx75. Power consumption is 30 mA.
Connection Description

" Some RX8W8, RX16W8 and RX32W8 receivers have DIP switches with the On/Out designation instead of Open/Closed. In the table below you will find both indications. On the recipient's label you will always find the indications Open/Closed (O/C).
1 34 5 38
2 33 6 37
3 32 (default) 7 36
4 39 8 35
= C (AAN) = O (UIT) DIP switch 4 not used
5.3.3 Status states RF868 receiver When you switch on the CSx75, the red LED must start to blink. The LEDs on the receiver represent the status of the module.
Normal data communication with the CSx75. No data communication with the CSx75. Check the wiring and power supply.
Red Blinking Red
Green Blinking Green
Receives radio signals from wireless reading detectors. There are no radio signals coming in at the moment.
" When installing a system in the Netherlands or Belgium, you must use RX 9008 test antennas for installation of an RF868 system.
For more information about installing the RF868 MHz receiver in different enclosures, see chapter A-4. Install a base system.

Start zone 32 RF receiver 5.1 5.1.1
Reading mode 5.1.2
Start reading (1) Zone 1 5.1.2.1.1
5.1.2.1
5.1.2.2
Entry 5.1.3
Station 15.1.3.1
5.1.3.1.1
Active Supervision Fire supervision
Senders 1 - 168
5.1.3.1.2 5.1.3.1.3
The transmitter range depends on the number of channels and the start zone number
5.1.3.1.4
5.1.3.1.4.1
Option 1 remote control Option 2 remote control Areas
5.1.3.1.4.3 5.1.3.1.4.2
Internal drove contact External contact
5.1.3.1.5
5.1.3.1.5.1 5.1.3.1.5.2
*Not active for 868 Mhz receivers
5.1.3.1.6
5.1.3.1.6.1
*Not active for 868 Mhz receivers
5.1.3.1.7
RF Receiver settings 5.1.4.1
Jam detection Distance bed. Send ID Distance bed. battery low message Sabotage antenna* Sabotation housing*
5.1.4.2
5.1.4.3
5.1.4.4
5.1.4.5
*Not active for 868 Mhz receivers
Long supervision time Short supervision time Fire supervision time
5.1.5.1 5.1.5.2 5.1.5.3
5.1.6.1
Zone number RSSI value* RSSI Value* Zendteller**
5.1.6.2
5.1.6.3
*Not active for 433 Mhz receivers **Not active to 868 Mhze receivers Model Version Default Settings
5.1.7 5.1.8
5.4.1 Return wireless modules to default settings Before you can program the RF receivers, you need to register them and bring them to default settings.
You must return the modules to default settings before you start programming the modules.

Door/Raamcontact Activate the sabotage switch by taking off the lid.
Door/Venster with external contact Activate the sabotage switch by taking off the lid.
PIR Activate the sabotage switch by taking off the back plate of the PIR.
Fire detector Hold the test button down.
Robbery pusher Hold the button down.
Remote control Hold the switch on and off simultaneously.
< Select Installer Menu >RF Recipients >:RF Receiver x>Entry > Detector x<Remove to remove a registered RF zone.
5.4.3 Configuring receiver options The receiver can be configured, inter alia, for sabotage messages and communication errors. In the following example, RF failure detection is enabled for RF receiver 32. The RF wireless communication is considered disturbed when a interference signal is active for more than 30 seconds in a 60-second time window.
5.4.4 Setup of the monitoring times There are three options for wireless supervision: Short supervision, Long supervision and Brand supervision. Wireless PIRs and contacts follow the short and long supervision times.
Short and long supervision times are configured differently depending on the country and frequency. 868 MHz transmitters usually report every 15 minutes, while 433 MHz transmitter normally report every 64 minutes.
Transmitter Action

" When installing a system in the Netherlands or Belgium, you must set supervision values to 120 for a long period of supervision. Set the short supervision time in Belgium to 15 and 20 in the Netherlands. The monitoring times for wireless smoke detectors shall be set to 240.
When the option Enable with zone loss is enabled, the user can always enable the system even if the wireless PIR or contact has not sent a supervision notification within the short time of supervision.
Smoke detectors follow fire surveillance time. 433 MHz and 868 MHz smoke detectors report every 64 minutes. Smoke detectors only follow the fire monitoring time and report to the reporting bank when they do not send any supervision reports within the fire surveillance time.
5.5.1 RF433 MHz system The RF433 MHz system operates on the basis of a transmitter to determine the quality of data reception. It shows the number of RF data received at the last transmission. In the following example, the last round count is tested for detectors registered on RF receiver 33.
5.5.2 RF868 MHz system The Remote Signal Strength Indication (RSSI) is a measure for the RF reception and is similar to the signal indicator on a mobile phone. The value is linked to the signal strength between the wireless detectors and the RF receiver. On an 868 MHz system, the RF receiver stores the signal strength of the transmission it receives from the Rf detector from a given zone. The values in this zone are as follows:
RSSI values can be changed by environmental conditions such as additional furniture or metal structures. In the following example, the RSSI value of zone 2 is tested for receiver 32.
5.6 Remove Detectors You can program a receiver to ignore a detector. The detector identification is not removed from the module memory. The detector can be reactivated later or a

new detector is read in the zone. In the following example, detector 10 is removed which has been read on receiver 32.
5.1 RF receiver 32 One menu-option where all options for the selected RF receiver are grouped.
5.1.1 Start of zone One menu-option specifying the starting zone number of the zones on the RF receiver.
5.1.2 Reading Mode One menu-option that activates the mode in which a new wireless transmitter is registered in the system.
5.1.2.1 Reading a Start menu-command that activates the reading mode of RF detectors.
One menu-option allowing a group of RF detectors to read in consecutively. Once the first detector (Start Reading Detector) is configured, the detectors can be read one by one. The value of .-Start Reading dynamometer is automatically increased. This option simplifies programming.
5.1.2.2 Reading sequentially
5.1.3 Entry A menu-option grouping options on RF zones.
5.1.3.1.2 Supervision A menu-option that activates supervision of the selected RF detector.
5.1.3.1.3 Fire supervision menu-option which determines that the RF433 or RF868 receiver uses fire supervision time.
5.1.3.1.4 Remote control A menu-option grouping options concerning each module that sends commands via a wireless receiver.
One menu-option that activates the lamp key on the remote control for an event . . If this option is activated, an event . . Option 1 remote control . is sent at the touch of the lamp key. The programmable outputs of the central and outputs can be programmed to respond to this event.
5.1.3.1.4.1 Option 1 remote control
One menu-option that activates the * key on the remote control for the selected RF zone on the selected rf receiver. If this option is activated, an event . . Option 2 remote control . is sent with a press of * key. The programmable outputs of the central and outputs can be programmed to respond to this event.
5.1.3.1.4.2 Option 2 remote control
One menu-option listing all areas assigned to the selected remote control. The selected remote control can activate an event for these areas. A zone may be accommodated in any combination of areas. A zone located in more than one area shall be a common zone and reported to its lowest area number. A common zone shall only be activated when all areas to which it belongs are enabled. It will be eliminated as soon as one of the areas to which it belongs is taken out.
5.1.3.1.4.3 Region

An option in the menu RF receiver Configures the door/window settings on an RF 433 MHz receiver. This implies the use of internal reed contacts and additional external contact from wireless door/window transmitters.
5.1.3.1.5 Door/Raamcontact
5.1.3.1.5.1 Internal contact menu-option on an RF door/window detector that activates the internal drove contact.
One menu-option on an RF door/window detector that activates an additional external contact. When the external contact is activated, an alarm is given on the same zone number as the door/window detector (reed contact) itself.
5.1.3.1.5.2 External contact
5.1.3.1.6 Fire One menu-option which groups the smoke detector options.
5.1.3.1.6. Sabotage One menu-option which switches on/off the tamper detection of a smoke detector.
5.1.3.1.7 Remove A menu-option that removes a registered RF zone.
5.1.4 RF Receiver institutions A menu-option in which programmable options for RF receivers are grouped.
5.1.4.1 Jam detection A menu option that activates the RF jam detection.
A menu option that lets the remote control report as the area in which it is read. When this option is turned off, all remote controls report their opening/closure reports as user 99.
5.1.4.2 Distance bed. Send ID
A menu option that reports a weak remote control battery. This option is only available on the 868 MHz RF receiver. The 'weak battery' status is reset by simultaneously pressing the On (Lock) and Off (Unlock) button. If this option is on, each registered remote control in the system will take one zone. If this option is off, remote controls in the system do not take into a zone and may overlap with an used area.
5.1.4.3 Distance bed. battery low notification
5.1.4.4 Sabotage antenna A menu option that sends a notification when the antenna on the selected RF receiver is removed or damaged (cut)
5.1.4.5 Sabotage enclosure A menu option that activates the sabotage switch on the selected RF receiver.
5.1.5 Supervision Times A menu option that groups wireless supervision options.
A menu option that specifies the long supervision time for RF modules. RF modules at 433 MHz usually send a supervision signal every 64 minutes. RF modules at 868 MHz usually send a supervision signal every 15 minutes. Depending on national regulations, this Short supervision period should be set to certain values.
5.1.5.1 Long supervision period
A menu option that gives up the short supervision time for RF modules. RF modules at 433 MHz usually send a supervision signal every 64 minutes. RF modules at 868 MHz usually send a supervision signal every 15 minutes. Depending on national regulations, this Short supervision period should be set to certain values.
5.1.5.2 Short supervision time
A menu option that gives up the RF supervision to be used for the Rf smoke detectors. The RF smoke detectors send a supervision every 64 hours, regardless of whether it is a 433 MHz or 868 MHz module.
5.1.5.3 Fire supervision time
5.1.6 RSSI Control A menu option that groups items regarding the measurement of strength of the RF signal.

A menu option that contains the zone number from which you want to check signal strength. The RF receiver stores the signal strength of the transmission it receives from the RF detector with this sun number. To read the signal strength, you need to activate (open/close) the zone and then select the menu option RSSI Value select.
5.1.6.1 Zone number RSSI value
RSSI stands for Remote Signal Strength Indication Value. This is a measure for the RF reception and is similar to the signal indicator on a mobile phone. A menu option that displays the RSSI value. The value is linked to the signal strength between wireless transmitters and RF receiver
5.1.6.2 RSSI Value
A menu option where a signal counter indicates the quality of the received RF data at the last transmission. This option is only available on a 433 MHz system and is replaced by the RSSI value in an 868 MHz system.
5.1.6.3 Sending counter
5.1.7 Model Menu option showing the model of the selected receiver.
5.1.8 Version A menu option that displays the current software version of the selected recipient.
5.1.9 Default settings A menu option that reset the selected recipient to factory settings.

Power supply 13.8V ± 2%
Power consumption 20 mA at 13.8V ± 2%
Wireless frequency 433 MHz
Size PCB Dimensions (width x height x depth) 110x81x25,4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Power supply 13.8V ± 2%
Power consumption 20 mA at 13.8V ± 2%
Wireless frequency 868 MHz
Size PCB Dimensions (width x height x depth) 117x81x25,4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Size housing Dimensions (width x height x depth) 110x81x25,4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

6.1 Overview With the CS208H, CS208 and CS216 entrance expansion you can add extra wired zones to a CSx75 power plant. Each CS208H and CS208 input expansion offers up to 8 extra wired zones. Each CS216 entry expansion offers up to 16 extra wired zones. Each CS208 / CS216 input expansion is equipped with an optional sabotage switch and voltage sifler. Each CS208H input expansion is equipped with a sabotage switch and power output.
6.2 CS208 / CS216 expansion of inputs The CS208 input expansion and the CS216 entry extension are broadly similar. The only difference is in the number of entrances they offer. In the drawing below you can see the CS216 input extension.

1 Zone connections (16 sets) 5 No function
2 Sabotage connection (requires) 6 Control LED
3 Control part databus connection 7 DIP switches (6 modes)
4 Additional databox connector 8 Processor


6.2.2.1 DIP switch 6 (CS216 only) To disable the last group of 8 inputs on the CS216 input expansion, you need to turn on DIP switch 6. This is only necessary if you need an 8 input extension at a particular location.
More information about installing the CS208 / CS216 input expansion in one of the different enclosures can be found in chapter A-4 Install a base system.

6.2.3 Wire the CS208 / CS216 input expansion For more information on wiring the CS208 / CS216 input extension, see Table 6-2: Connections CS208 / CS216 input extension. Any unused inputs shall be closed with an EOL resistance unless all 8 entries are switched off by DIP switch 6 (CS216 only). The CS208 / CS216 inputs extensions are broadly equal to the CS507 output expansion. A white connector J9 can be used to connect the CSx75 panel into a housing in the power plant.
Connector on the left 3
Data Connect to the KP DATA connection of the CSx75.
Other Connect to the KP DATA connection of the CSx75. Power consumption is 30 mA.
COM (-) Connect to the CSx75 FP COM connection.
V-Out Allows you to power the extensions directly from the CS208 / CS 216. The power supply is from CSx75 and the power consumption of the modules must be added to the total power output of the CS208 / CS216. The output current connected to a COM connection is limited to 100 mA.
TAM If not in use, connect connections to COM connection.
Z9 Connect to one side of the loop from entrance 9. Connect the other side to the COM connection. Open or short-circuited triggers alarm.
COM Normal (-) connection for zones 9 and 10.
Z10 Connect to one side of the loop from entrance 10. Connect the other side to the COM connection. Open or short-circuited triggers alarm.
Z11-Z24 Connect as described for Z9 and Z10.
Additional control connector 4 (from top to bottom)
2 COM
3 Not in use
Connection Description · Lower connector 1

6.3 CS208H input expansion The CS208H input expansion is delivered in a private housing. The print is different from that of the CS208 input extension.


1 Accessories (8) 3 Sabotage switch
2 Control part databus connection 4 Dipsets



6.3.4 Wiring of the CS208H input expansion For more information about wiring the CS208H input extension, see Table 6-4: Connections CS208H input extension. Any unused inputs shall be closed with an EOL resistance.
Data Connect to the DATA connection of the CSx75.
Connect to the DATA connection of the CSx75. Power consumption is 30 mA.
COM (-) Connect to the CSx75 com connection.
V-Out This allows you to power the modules directly from the CS208H. The power supply is supplied by the CSx75 and the consumed power of the modules must be added to the total power output of the Cs208H. The output current connected to a COM connection is limited to 100 mA.
Z1 Connect to one side of loop from entrance 1. Connect the other side to the COM connection. Open or short-circuited triggers alarm.
COM Ordinary (-) connection for input 1 and 2.
Z2 Connect to one side of loop from entrance 2. Connect the other side to the COM connection. Open or short-circuited triggers alarm.
Z3-Z8 Connect as described for Z1 and Z2.
16 Entry module 6.1
The inputs on the CS208H / CS208/CS216 input expansion are programmed in the same way as inputs. More information on programming integrated zones can be found in chapter B-2 The central programming. Before you can program the system, you must first register all entries to default settings. Bringing more information about and to default settings is provided in chapter B-1 Registering modules. To program the zones of input modules, select Centrale >CS208/CS216 Entrance extension.
Connection Description

6 CS208 / CS216 input extension An expansion module that extends the number of wired inputs these can be used for a specific entry programming. The module is equipped with an optional sabotage switch and the possibility to power additional components via input programming. Ut extension cannot be used on the CS175 or CS275 power plant. The CS208 has 8 entrances and the CS216 has 16 zones. A menu option that groups the options for the CS208/CS216 entry extension.
Power supply 13.8V ± 2%
Power consumption (with 4K7 EOL) 64 mA at 13.8V ± 2%
Aux. Power output 100 mA max at 13.8V ± 2%
Print Dimensions (width x height x depth) 110x95x25.4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Power supply 13.8V ± 2%
Power consumption (with 4K7 EOL) 64 mA at 13.8V ± 2%
Aux. Power output 100 mA max at 13.8V ± 2%
Print Dimensions (width x height x depth) 80x60x105 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

7.1 Overview The CS507 output expansion is a auxiliary module used to extend the output capabilities of the CSx75 control panel with the following functionality:
The CS507 output expansion can be programmed in such a way:

1 Exchange contact relay connections (2 relays) + 5 open collector 7 X-10 communication LED
2 Sabotage connection 8 X-10 connector
3 Auxiliary power supply connection 9 Processor
4 Databus connection A DIP switches (4 modes)
5 Additional databox connector B Relais
6 Databus communication LED

Address Exits Institution DIP-
More details about the installation of CS507 output expansion in different enclosures can be found in chapter A-4 Install a base system.
Data Connect to the DATA connection of the CSx75.
Connect to the DATA connection of the CSx75. Power consumption is 30 mA.
COM (-) Connect to the CSx75 com connection.
V-out This connection can deliver up to 100 mA. Note: Each current take-off of this output shall be added to the total power consumption of the CSx75. This way the power supply from the plant is separated from the external equipment. If a short circuit is located behind the AUX connection, this equipment will fail but all other devices such as CS507 output expansion will continue to work. The CS507 output expansion reports this to the power station, so that a malfunction of the output extension power supply is displayed on the control panel.

TAM If not in use, connect to the COM connection.
Output 1-5 Open Collector outputs that switch to minus when activated (they can operate up to 100 mA). Note: If equipment is connected to these outputs, a connection must be made from the Aux to this collector exit. The built-in resistors shall be used. Switch off the resistance between AUX and the output used.
Relay 6 /NC Normal Closed contact from 1A at 30 VDC.
Relay 6 /NO Normal dry contact of 1A at 30 VDC.
Relais 6 /CO Common contact 1A at 30 VDC.
Relay 7 /NC Normal Closed contact from 1A at 30 VDC.
Relay 7 /NO Normal Open contact from 1A at 30 VDC.
Relais 7 /CO Common contact 1A at 30 VDC.
Additional control connector 5 (from top to bottom)
2 COM (-)
3 Not in use
An additional J1 connector (left middle) offers a direct bus connection to the controller. An additional cable is provided at the plant in case you install the expansion module into the housing of the CSx75. This cable is connected to J6 on the CS575. There are 2 options to connect the CS507 output expansion to the Csx75 controller.
Connection Description

24 Output module 7.1
7.1.1.1
7.1.1.1.1
7.1.1.1.1.1
Alarm In/Disable Communication Controls Sirene Sabotage and Failure Test Other
7.1.1.1.1.2
Outputs 2 - 8 Same as above
7.1.1.1.1.3 7.1.1.1.1.4
7.1.1.1.1.5 7.1.1.1.1.6 7.1.1.1.1.7 7.1.1.1.1.8
7.1.1.1.2
Zone/user Time Unit Time Areas
7.1.1.1.3 7.1.1.1.4
7.1.1.1.5
7.1.1.1.6
7.1.1.1.6.1
Continuously Stop Time Control with Code Active During Closing Active Durer Opening Invert Event Log
7.1.1.1.6.2
7.1.1.1.6.4 7.1.1.1.6.3
7.1.1.1.6.5
7.1.1.1.6.6
7.1.1.1.7
7.1.1.1.8.2 Module number X-10 House code
7.1.1.1.8
7.1.1.1.8.1
7.1.2.1
7.1.2.1.1
7.1.2.1.1.1 7.1.2.1.1.2
Schedules 2 - 8 Same as above
7.1.2.1.2
Sunday Monday Tuesday Wednesday Thursday Friday Saturday Holidays
7.1.2.1.3
7.1.2.1.3.1
7.1.2.1.3.4 7.1.2.1.3.3 7.1.2.1.3.2
7.1.2.1.3.6 7.1.2.1.3.5
7.1.2.1.3.7
7.1.2.1.3.8
January February March April May June July August September October November December
7.1.3.1 7.1.3.2 7.1.3.3
7.1.3.1.1
Days 2 - 8 Same as above
7.1.3.4 7.1.3.5
7.1.3.6
7.1.3.8 7.1.3.7
7.1.3.9
7.1.3.10
7.1.3.11 7.1.3.12
Outputs 7.1.4.1.1
7.1.4.1
User 2 - 99 Same as above For more than 10 users, the user will be displayed first per group of 10 and then as above.
Model Version Default Settings
7.1.7 7.1.6
The outputs of the CS507 are programmed in the same way as the outputs on the power plant. The outputs are activated based on different events. Events are grouped into the programming structure. A complete list of all possible events can be found in Table 7-3: CS507 output expansion - exit events. Before you can program the system, register all output expansion s and bring it to default settings. More information on registration and resetting can be found in chapter B-1 Registering modules. To program the outputs, select Installation menu >CS507 output expansion .

# Event # Event
9 Power supply failure 8 Every bridge. 32 Listen
10 Battery error 11 9 Disable under duress 33 Chooser busy
25 Brand LED 45 9 Code enter 34 Fail to communicate (FTC) communication error
26 fault fire 36 programming mode 35 telephone line error
28 9 Module malfunction 46 99 Option 1 remote 37 Up/Download
39 Flood 47 99 Option 2 remote control 55 End Listen In (integrated only)
40 Sabotage housing 51 CS507 Schema Enable/disable
41 Sirene sabotage 52 X-10 Alarmgeh. 18 Walk-in
42 Each open zone 53 X-10 Sirene 19 Walk-out
58 Low Battery Detector 56 X10 commands compare with programmed outputs
59 Detector Lost Controls 21 Enabled
64 Brand Reset Function 12 9 Manual fire warning 22 Not enabled
65 Antimasking Output 13 9 Control unit medical 23 System ready
Alert 14 9 Panic function robbery control lever 24 System not ready
0 9 Break-in alarm 15 Controls Sabotage 30 * Open period
1 9 Fire alarm 27 Door bubble 31 * Closed period
2 9 24 Hour alarm 44 Control part buzzer 48 Auto in control
3 9 Malfunction (ingress) SIRENE 49 Check Auto Out
4 9 Sabotage alarm 5 Breaking and entering siren 50 Auto/out of control
17 Alarm memory 6 Fire siren 54 Enabled Provide Wrap
43 9 Every alarm 7 Any siren 57 Partially in
62 Breaking and entering Verified 61 External siren Test
63 Fire Verified 16 9 Automatic test
29 Dyn. Battery test
* See Disable/open switch time and Enable/close auto. 9 If these events are programmed to follow (not continuous), the duration of these events is a second.
Sabotage Other Communication · 20 In/Off · 60 Running test

99 Events 46 and 47 can only function with RX8w8, RX16w8,RX32w8,rX8i4,rX16i4,or RX48i4 wireless receivers.
Events 48, 49 and 50 enable or disable the CSx75 at the opening (disabled) or closing (set-in) time of the relevant timetable performances. < For events 48 and 50, the buzzer of the control lever will beep for one minute before automatically turning on if zone value is 1. If the zone value is 0, the control lever will not beep before automatically turning on.
7.3.1 Set up Schemes You can set a time frame to program the day and time when the system is automatically switched on or off, or set the days at which special output events are activated. You can also set certain days when the timetable is not active. For example, you can use a time schedule to disable the system every morning at a certain time. But on holidays, the system may not have to be shut down at that time. In the following example, 1 January is set as the day on which timeline 1 is not active.
7.3.2 Configuring an output You can set the events, users and areas that can activate a particular output. The output can be controlled by a time frame or an X-10 module. If an exit is controlled by a timetable, it can be activated during the times set in the time schedule. If the output is controlled by an X-10 module, it can be activated during times when the X-10 device is switched on or off. In the following example, output 1 on output expansion 24 is configured to activate it when the enclosure is sabotaged. This exit is controlled by timetable 1.
7.3.3 Configuring Users You can set a user code that activates the selected output. In the following example, user code 1 is set to activate outputs on output expansion 24.

7 CS507 output expansion An extension card that increases the number of outputs which can be used with the power plant. A menu option that groups the options for CS507 output expansion.
7.1.1 Outputs A menu option that groups options related to all programmable outputs. There are two types of outputs; relay and open collector. The power plant contains up to four programmable outputs. The CS507 output expansion offers additional outputs.
7.1..1.1 Event A random event, such as system activations, malfunctions and alarm notifications. A menu option that specifies which event activates an exit.
7.1.1.1.1.1 Alarm An option in the menu CS507 output expansion where all alarm events can be selected to send an exit.
7.1.1.1.1.2 To/Disable A menu option that groups events to send outputs.
7.1.1.1.1.3 Communication A menu option that groups all communication events selected to send an exit
7.1.1.1.1.4 Controls A menu option that groups the control events which activate an output.
7.1.1.1.1.5 Sirene A menu option that groups all siren events which can be selected to send an exit
7.1.1.1.1.6 Sabotage and malfunction A menu option that groups all sabotage and failure events which can be selected to control an exit
7.1.1.1.1.7 Test A menu option that contains settings for different tests. This concerns, for example, automatic test reports, active battery tests and so on.
7.1.1.1.2 Zone/user A menu option that specifies that the selected event must occur on a particular zone or be executed by a specific user
7.1.1.1.3 Time Unit A menu option that specifies whether the outputs are controlled in minutes or seconds.

7.1.1.1.4 Time A menu option that sets how long an output is activated. If this value is set to 0, the output will follow the event.
7.1.1.1.5 Areas A menu-option listing all areas allocated to the selected exit. The selected output can be activated by an event in these areas.
7.1.1.1.6 Attributes A menu option in which the programmable attributes of the selected output are grouped.
7.1.1.1.6.1 Continuously A menu option that keeps an output activated until a code is entered on the control panel.
7.1.1.1.6.2 Stop time control with code A menu option that allows the time control to be reset for programmable outputs by entering a valid user code.
7.1.1.1.6.3 Active during closure A menu option that activates an output after closing time and before opening time. During these periods codes can be used to turn the system on/off. These times are set in time schedules.
7.1.1.1.6.4 Active during opening A menu option that activates an output between the opening time and closing time.
7.1.1.1.6.5 Invert A menu option that reverses the status of an output (normally activated and then deactivated when an event occurs).
7.1.1.1.6.6 Event Log A menu option that allows the selected output to record an event in the log when it is activated.
7.1.1.1.7 Timing A menu option that selects the time frame templates related to the selected output.
7.1.11.8 X-10 Address A menu option setting the address of an X-10 module. This is a unique number assigned to an X-10 module. It consists of the module number and house code. The system uses this address to identify the module.
7.1.1.1.8.1 Module Number A menu option setting the X-10 module number used to identify a particular X-10 modules on the selected module. Each system module shall be assigned a CSx75 databus module number. The system uses this number to identify the module. It is also used to report module problems (such as sabotage and module oversight issues) to the reporting bank.
7.1.1.1.8.2 X-10 Home Code A menu option setting the code to identify a particular building. This code is required if any neighbouring buildings are also equipped with an X-10 home automation control system. More information about the X-10 home automation control system can be found at www.x- 10europe.com.
7.1.2 Timing A menu option that groups time schedule performances. These options set the times for starting and ending an action.
7.1.2.1.1 Disable/Open A menu option setting the time when the selected schedule switches to opening time.
7.1.2.1.2 Enable a menu option setting the time when the selected calendar is enabled
7.1.2.1.3 Active A menu option that lists the weekdays on which a particular switching time is active.
7.1.2.1.3.2 Not active on holiday days A menu option for activation of the holiday function. The selected time frame is not active on the days specified in Holidays.
7.1.3 Holidays A menu option that sets the holiday days. If the holiday function (7.1.2.1.3.2) is activated, these days' timetables are not active. Up to eight holiday days per month can be specified.

7.1.4 Users A menu option that specifies the zone or user number which activates the output on the expansion module or power supply module
7.1.4.1.1 Outputs A menu option that specifies which outputs the selected user can use The user menu can only be used if event 45 (code entry) is used.
7.1.5 Model Menu option showing the current model of selected output expansion .
7.1.6 Version A menu option that displays the current software version of the selected output expansion.
7.1.7 Default settings A menu option for bringing the selected output extension to default settings .
Power supply 13.8V ± 2%
Power consumption . . No outputs active 10 mA at 13.8V ± 2%
Power consumption . . All outputs active 25 mA at 13.8V ± 2% + power consumption of each connected device.
Aux. Power output 100 mA max at 13.8V ± 2%
Size PCB Dimensions (width x height x depth) 110x95x25.4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Food specifications · General provisions specifications · Shipping weight 115 g

8.1 Overview The CS586 Memory/RS232 module is an optional module used to connect the up/download software directly to the power station if the integrated serial port is not available. The CS586 Memory/RS232 module has four program memories.

1 RS232 connection 4 LED . .Wait for bus communication .
2 RJ11 (back connection) 5 LED . .
3 LED . .Wait for host communication . 6 LED ♪Data received .
TXD PIN 3 PIN 2
GND PIN 5 PIN 7
Sub-D9 D25

8.2.2 Connecting the CS586 to a PC and central Connect the CS586 memory/RS232 module to the serial port of the PC and to the panel as specified in the previous paragraph. The black and red connector can be connected to a 12V DC source; the green connector does not need to be connected.

"
DATA
#
AUX+
COM
CS375/575/875
8.2.3 Connecting the CS586 to a power station
< If you are operating with a CS875 and have installed a control gear in area 8, Control 8 this must be removed during this operation.
Files File 1 Type central Panel to file File to panel Options Baudrate
8.1.1.1
8.1.1.2 8.1.1.3 Files 2 - 4 Same as above
The program memory of the central can be copied to one of four programs on the CS586 Memory/RS232 module, and vice versa. Before you can program the system, you need to register and bring it to default settings. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules.

To program the CS586 from the Cs5500 control panel, select CS586 Memory/RS 232 module. If you want to program the CS586 using a PC, start the UDx75 up/download software on your PC.
8.3.1 Memory transfer with the CS5500 handler In the following example, the CS5500 control is used to copy program memory from the central to program memory 2 on the CC586. Next, the program information of program memory 3 on the CS586 is copied to the control center.
8.3.2 Memory transfer with the UDx75 software In the following example, UDx75 software is used to copy program memory from central to program memory 2 on the CS586. Next, the program information of program memory 3 on the CS586 is copied to the control center.

8 CS586 Memory/RS232 module A menu-driven module used to connect the up/download software directly to the power station if the integrated serial port is not available.
8.1 Files A menu option in which the four program memory is grouped into the memory/RS232 module.
8.1.1 File 1 A menu option that selects the program memory in the memory/RS232 module. There are four possible program memories.
8.1.1.1 Central type A menu option that displays the information about the central type stored in one of the four memory/RS232 module programs. Possible values are CS175, CS275, CS375, CC575 and CS875.
8.1.1.2 Panel to file A menu option for copying programming from a central unit to one of the memory/RS232 module program memories. There are four possible program memories in the CS586.
8.1.1.3 File to Panel A menu option to copy program memory from one of the four memory locations in the memory/RS232 module to the central.
8.2.1 Baudrate A menu option that adjusts the speed of data communication from the CS586 memory/RS232 module to the central. This can be set from 600 baud to 76800 baud. It is recommended to use the default setting of 9600 baud
Power supply 13.8V ± 2%
Power consumption 30 mA at 13.8V ± 2%
Size housing Dimensions (width x height x depth) 57x100x20 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

9.1 Overview The CS534 communication module is a two-sided audio and voice communication module for the CSx75 control panel. Once the operator has sent an alarm, the CS534 communication module allows a security service operator to monitor the local situation with the customer. It also offers the possibility of an elementary two-sided voice communication. This procedure is controlled from the reporting bank by means of a DTMF telephone.
9.2 Install the CS534 communication module The CS534 communication module is installed on top of the main print and must be connected to the expansion port. For more information about the installation of the CS534 communication module in the different enclosures, see chapter A-4. Install a base system.

1 Microphone channels A and B The length of the wire can be 300 m if the microphone cables are in a different mantle than the loudspeakers, 150 m when they are in the same cloak.
2 Speaker clips Maximum wire length of speakers = 300 m Minimum loudspeaker power is 5W, 8 Ohm

Connector on the left.
1 Connect here the positive side of microphone #A.
2 Connect here the negative side of microphone #A.
3 Connect here the positive side of microphone #B.
4 Connect here the negative side of microphone #B.
SPK+ SPK- Connection of the loudspeaker (s). Maximum length of the speakers: 300 m. Minimum loudspeaker power: 5 Watt, 8 Ohm. Don't go below four Ohm.
9.2.2 General operating instructions The system works as follows, regardless of how a two-sided session was started.
9.2.2.1 Line-keeping mode
9.2.2.2 Callback mode
Connection · Description · ed

9.2.3 Control levels The level of fashion can be changed at any time by: * press, followed by the desired level number. If no key is pressed on the phone within three seconds, the buffer will be automatically deleted. Press the * key twice to return to the beginning.
" Levels 1, 2 and 4 are not supported. Any attempt to set these levels will bring you back to Level 0.
0 Returns to the original session settings when activated. This also applies to microphone selection and audiomode.
1 High speech enhancement to location and extension of session time.
3 High listening strength from location and extension of session time.
2, 4, 5, 7, 8, 9 Extends session time.
6 Low listening strength from location and extension of session time.
88 Ends the session and starts the callback mode.
99 Ends the session, returns to standby and awaits a new activation.
0 Returns to the original session settings when activated. This also applies to microphone selection and audiomode.
1 Switches on microphone 1, microphone 2 off, and extends session time.
2 Switches on microphone 2, microphone 1 off, and extends session time.
3, 4, 5, 6, 7, 8 Extends session time.
9 Switches both microphones and extends the session time.

5 Output/Relay control level (negative-disable)
0 Returns to the original session settings when activated. This also applies to microphone selection and audiomode.
6 Output/Relay Control Level (positive switching)
0 Returns to the original session settings when activated. This also applies to microphone selection and audiomode.
0 Returns to the original session settings when activated. This also applies to microphone selection and audiomode.
1 Enabled status: If area 1 is enabled, you will hear a positive tone. When it's off, a negative tone sounds.
2 Ready status: If the area is in Ready state, you will hear a positive tone. When it is not ready, a negative tone resounds.
3 Voltage status: If the power supply and battery are good, you will hear a positive attachment tone. If the power voltage or battery is bad, you will hear a negative tone.
8 Enable/ Disable Area 1
9.2.4 Show The following indication tones can be heard in the reporting bank during a two-sided session. The definition of these indicative tones is as follows:
LOW = 400 HZMID = 1000 HZ HIGH = 1600 HZ
A high tone for 100 ms Indication time tone .
A median tone over 100 ms Indication time tone .B.J.
A middle tone of 100 ms, 100 m s silence, a high tone 100 mS New alarm active for the same area.
A high tone of 100 ms, 100 m s silence, a middle note of 100ms, a 100 mS silence, high tones of 100ms New alarm active for another area.
High tone continuously on/off for 100 ms each; stops after receiving a digit.
System is waiting for secret access code.
Low tone for 200 ms (if on) Deblocking
A middle tone for 500 ms Confirmation of level change.

A 250 ms middle tone, 250 m s silence, a 250 msp midtone, 250ms silence, 250ms average
Low tone for 100 ms Relay/Exit IN-switched, or Positive Status Response, or Area 1 enabled.
Low tone of 100 ms, 200 ms silence, low tone 100 mS relay / output OFF-switched, or Negative Status Response, or Area 1 disabled.
Fashion Listen only Loudspeaker lock Start-up condition microphone A Boot-up conditions microphone B Ignore Answer Device Status Control In/Disable
9.1.2 9.1.3
9.1.5 9.1.6 9.1.7
Access code callback mode Access cipher linekeeping mode Number of wrong code-ingave Call signals for recording
9.5 9.4
9.6.1 9.6.2 9.6.3
Withdrawal time line holding mode Time new activation withdrawal period Callback mode Break time no activity Indication time show A indicator time show B Interval deblocking tone
9.6.4 9.6.5
Microphone low-strength Microphone high-strengthening Speaker
9.7.2 9.7.3
9.8.1.1
Modules 2 - 9 Same as above
9.8.1.2
9.11 9.10
Before you can program the CS534 module, register and bring it to default settings. More information about registering and resetting can be found in chapter 6. For programming the CS534, select CS534 Communication module.
9.3.1 Configuring listening options You can configure the listening mode and listen-in options. The following example prevents the reporter from switching on the speaker when a coercive or robbery alarm is reported by the operator.
9.3.2 Programming timers You can set timers to control the various functions of the CS534 Communication Module. In the following example, the line holding mode access rate is set to 2 and the queue hold mode waiting time is set at 60 seconds.

9.3.3 Set Volume You can adjust the volume level of the CS534 Communication Module. In the following example, high microphone enhancement volume level is set to Level 4.
Assign 9.3.4 X-10 modules The CS534 Communication Module can activate an X-10 module via a telephone connection. In the following example, module 1 (module number 5, house code L) is assigned to the CS534 Communication Module.
9 CS534 Communication Module A two-way audio/voice communication module. If the operator sends an alarm, the audio module allows the control room to start a two-way communication session or check its location by listening in remotely.
9.1 Options A menu option that groups all options concerning area settings, system settings of the central unit, etc.
9.1.1 Mode A menu option that specifies whether the communication module is used in line holding mode or callback mode.

9.1.2 Listen only A menu option that only activates the mode. This is the fashion where the control room can only listen in to the customer's building but cannot create two-way communication.
9.1.3 Speaker lock A menu option that prevents the reporter from switching on the speaker when a coercive or robbery alarm is reported by the control centre.
9.1.4 Startup condition microphone A A menu option that activates microphone A when listening in.
9.1.5 Startup condition microphone B A menu option that activates microphone B when listening in.
9.1.6 Ignore Answering Tool A menu option used to ignore an answering machine. A telephone call to the location is made, which is answered by an answering machine or another device. When "Toongdetected Ignore Answerer" is activated, only one call is needed to ignore the answering machine. The computer calls the power station in the normal way. When the answering machine picks up, the control panel hears the tones of the modem and the central operator opens the phone line for a download.
9.1.7 Status Control A menu option that allows the end user to check system status using a DTMF phone. This option activates level 7.
9.1.8 On/Disable A menu option that allows the end user to switch on/off remotely using a DTMF phone (e.g. GSM). This option activates level 8.
9.2 Callback access code A menu option that contains the code which starts a listening session when the switchboard is in callback mode. This code may not exceed six digits.
9.3 Access code line holding mode A menu option that states the number of a two-sided session starts when the power station is in line mode.
9.4 Number of wrong code-ingave A menu option that specifies the maximum number of wrong digits which can be entered for dial-up and call-in functions before locking the power plant.
9.5 Recording Call signals A menu option that determines the number of call signals required before the switchboard picks up to start a listening session. If this value is 0, the control or CS534 will never respond to an incoming call and therefore never record. In some countries, the legislation does not allow an installer or control room to dial without final approval. In this case, use the menu options Reply U/D or Start U/D.
9.6 Times A menu option in which the time-driven options are grouped.
9.6.1 Withdrawal period line holding mode A menu option that determines how long the communication module keeps the line open without activity from the control room. This time can be set from 30 to 255 seconds. If the communication module does not receive the digit within this time, the module will disconnect.
9.6.2 Underbr.time new activation A menu option that sets the time during a two-way communication session, when a new event occurs in the same area, requires pressing a button to extend the session time.
9.6.3 Withdrawal period Callback Mode A menu option that, in one minute steps, sets how long the CS534 listener module waits to call back after an alarm is notified.
9.6.4 Break time in case of no activity A menu option that determines how long the communication module keeps the line open without any activity from the control room.

9.6.5 Indication time show A A menu option setting the remaining time after indication tone .A.J is sent to the reporting bank. After this time, the two-way communication session will be terminated if no other activity of the dispatch room is to occur. This time can be set from 1 to 255 seconds.
9.6.6 Indication time Show B A menu option that sets the remaining time after indication tone .B.O.B is sent to the reporting bank. After this time, the two-way communication session will be terminated if no other activity of the dispatch room is to occur. This time can be set from 1 to 255 seconds.
9.6.7 Interval unblocking tone A menu option that sets the interval which determines how much time the control room receives the unblockation tone.
9.7 Volume settings A menu option that contains options to adjust the sound level in the CS534 communication module.
9.7.1 Microphone low reinforcement A menu option that switches on the mode whereby the control room listens in to the customer's premises. This mode is used in environments where background noise can disrupt sound reproduction.
9.7.2 Microphone High Power Supply A menu option that activates the high microphone enhancement. This is a listening mode that is usually used in environments with very low noise levels.
9.7.3 Speaker A menu option that sets the volume of the speaker.
9.8 X-10 Modules A menu option that contains X-10 module options for the selected listening module
9.8.1.1 Module Number A menu option that sets the X-10 module number used to identify a particular X-10 modules on the selected module. Each system module shall be assigned a CSx75 databus module number. The system uses this number to identify the module. It is also used to report module problems (such as sabotage and module oversight issues) to the reporting bank.
9.8.1.1 X-10 Home Code A menu option that sets the code to identify a particular building. This code is necessary if any neighbouring buildings are also equipped with an X-10 home automation control system. More information about the X-10 home automation control system can be found at www.x- 10europe.com.
9.9 Model Menu option showing the current model of the selected module.
9.10 Version A menu option that displays the current software version of the selected module.
9.11 Default settings A menu option that reset the selected module to factory settings.

Power supply 13.8V ± 2%
Power consumption . . Not in session 50 mA at 13.8V ± 2%
Power consumption . .
Size PCB Dimensions (width x height x depth) 110x96x25,4 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

10.1 Overview The CS320 is an auxiliary power supply module that can be used in combination with the CSx75 panels. It is equipped with three programmable outputs and a separate alarm transmitter output.
Up to eight CS320 auxiliary power modules can be added to the CSx75 plant. In total, 32 outputs are possible, of which 24 programmable and eight separate alarm transmitter outputs. The 24 programmable outputs can be used for auxiliary power smoke detectors and alarms.
10.2 Install the CS320 auxiliary power module Each CS320 auxiliary power supply module is equipped with a sabotage connection that can be used for the monitoring of the enclosure.
When the CS320 auxiliary power module is connected to the Csx75, the maximum total wiring length to all devices is 750 meters. Each CS320 auxiliary power module shall be connected separately to the CSx75 and not switched into series.


2 3 4 5 6 7
1 Dipswitches 4 Call 7 Earth
2 Outgoing connections 5 Sabotage connection 8 Sabotation switch (not used)
3 Outputs 6 Incoming bus connections 9 AC inputs

Data Connect to the KP DATA connection of the CSx75. This connection is the incoming data signal connector of the CS320 auxiliary power module.
COM Connect to the CSx75 FP COM connection. This connection connects the common power supply to the CS320 auxiliary power module.
POS(+) Connect to the KP DATA connection of the CSx75.
DATA This connection is the outgoing data signal connector for tube expansion.
COM Common connection for each device supplied by the CS320 auxiliary power module.
OUT A Programmable output, current limited to 1.9 A.1
OUT B Programmable output, current limited to 1.9 A.
COM Common connection for each device supplied by the CS320 auxiliary power module.
OUT C Programmable output, current limited to 1.9 A.
BELL + Positive current less than 2.5 A.
BELL - Negative current buzzer limited to 2,5 A.
TAM Optional sabotage connection. Switch the normally closed sabotage switch between this connection and COM. If DIP switch 4 is off, this option is not used.
AC AC input. Connect to a 16.5 V 50 VA transformer.
1.The total current of the CS320 auxiliary power module is 2.5 A. A total of 1,9 A may be present between outputs A, B and C, and a total of 2,5 A between buzzers and exits.
10.2.2 Set the DIP switches The DIP switches 1-3 determine the address of the CS320 auxiliary power module.

DIP switch 4 controls the sabotage option. On triggering sabotage. Out deactivates sabotage.
10.1 10.1.1
10.1.1.1
10.1.1.1.1
Alarm In/Disable Communication Control Sirene Sabotage and Failure Test Other
10.1.1.1.1.1
Outputs 2 -3 Same as above
10.1.1.1.1.2
10.1.1.1.1.4 10.1.1.1.1.3
10.1.1.1.1.7 10.1.1.1.1.6 10.1.1.1.1.5
10.1.1.1.1.8
10.1.1.1.2 10.1.1.1.3 10.1.1.1.4
10.1.1.1.5
Attributes Continuous Stop time control with code Invert Not active on listen-in
10.1.1.1.5.1
10.1.1.1.5.2
10.1.1.1.5.4 10.1.1.1.5.3
Users (1) User 1
10.1.2.1
10.1.2.1.1
User 2 - 99 Same as above For more than 10 users, the user will be displayed first per group of 10 and then as above.
Options Delay time power failure Battery battery time
10.1.3.1
10.1.3.2
10.1.3.3
10.1.3.4
10.1.3.4.1 10.1.3.4.2
Power voltage error Siren tamper/fault
10.1.3.4.3
Model Version Default Settings
Before you can program the CS320 auxiliary power module, register and bring it to default settings. More information about registering and bringing to default settings can be found in Register the CS320 auxiliary power module above and in Chapter B-1 Registering modules. To program the CS320 power module, select CS320 Food modules.
10.3.1 Configure outputs You can set the events and areas that can activate a particular output. The outputs are activated based on different events. Events are grouped into the programming structure. A complete list of all possible selectable events can be found in Table 10-3: CS320 power module - output events. You can also assign a defined attribute to the output. In the following example, user code 1 is set for resetting timer to output 1, power module 84, at the moment a self-test is performed.

# Event # Event
17 Alarm memory 21 Enabled 32 Code entry
Test 22 Disabled 7 Programming mode
3 Dyn. Battery test 23 System ready 0 Always on
Sabotage 18 Walk-in Controls
25 Brand LED 19 Range 29 Control part fire
11 Fire reset 20 In/ Outflow 30 Control part medical
8 Flood 24 Syst not ready 31 Panic function robbery
9 Sabotage housing SIRENE 28 Control part buzzer
10 Sirene sabotage 12 Breaking and entering siren 27 Doorbell
26 Failure fire 13 Brandsirene Communication
1 Power supply failure 14 Every siren 4 Please listen
2 Battery error 15 Brandsir constant 5 Selector busy
16 Every Sir 1-tone 6 Tel. line error
10.3.2 Configuration options You can configure test and reporting functions for the CS320 power module. In the following example, a battery test is activated which lasts 60 minutes and a report sends to the reporting bank when the battery voltage is low.
Alarm Enable/Disable Other

10 CS320 Power module An additional power supply module in case the system controls more peripherals than the power supply of the power plant can feed.
10.1 84 Nutrition module A menu option that groups reporting options for the selected power supply module.
A menu option that groups options related to all programmable outputs. There are two types of outputs; relay and open collector. The power plant contains up to four programmable outputs. The CS320 power supply module offers additional outputs.
10.1.1 Outputs
A random incident, such as system encodings, malfunctions and alarm notifications. A menu option that specifies which event activates an exit.
10.1.1.1.1 Event
10..1.1.1.1 Alarm A menu option that groups all alarm events which can be selected to send an exit
10.1.1.1.1.2 To/Disable A menu option that groups events to send outputs.
10.1.1.1.1.3 Communication A menu option that groups all communication events which can be selected to send an exit
10.1.1.1.1.4 Controls A menu option that groups the control events which activate an output.
10.1.1.1.1.5 Sirene A menu option that groups all siren events which can be selected to send an exit
10.1.1.1.1.6 Sabotage and Failure A menu option that groups all sabotage and malfunction events that can be selected to control an exit
A menu option that contains settings for different tests. This concerns, for example, automatic test reports, active battery tests and so on.
10.1.1.1.1.7 Test
10.1.1.1.2 Time Unit A menu option that specifies whether the outputs are controlled in minutes or seconds.
10.1.1.1.3 Time A menu option that sets how long an output is activated. If this value is set to 0, the output will follow the event.
A menu option that lists all areas assigned to the selected output. The selected output can be activated by an event in these areas.
10.1.1.1.4 Region
10.1.1.1.5 Attributes A menu option in which the programmable attributes of the selected output are grouped.
10.1.1.1.5.1 Continuously A menu option that keeps an output activated until a code is entered on the control panel.
A menu option that allows the time control to be reset for programmable outputs by entering a valid user code.
10.1.1.1.5.2 Stop time control with code
10..1.1.5.3 Invert A menu option that reverses the status of an output (normally activated and then deactivated when an event occurs).

A menu option that disables the selected output while listening. This option is normally used to dampen sirens while listening. After the listening session, sirens are reactivated.
10.1.1.1.5.4 Not active on listening in
10.1.2 Users A menu option that specifies the zone or user number which activates the output on the expansion module or power supply module
10.1.2.1.1 Outputs A menu option that specifies which outputs the selected user can use
10.1.3 Options A menu option that groups all optional options related to the selected module.
A menu option that determines the time span between detecting a power supply failure on a power module and sending a report to the reporting bank. The recovery event is transmitted four minutes after the mains voltage has been restored.
10.1.3.1 Delay time power failure
A menu option that activates a test to determine whether the battery is connected to the power supply module. This test is usually performed automatically when the system is first started and then at periodic times.
10.1.3.2 Battery test
A menu option that sets how long the power module performs the battery test. It can be set between 0 to 255 minutes, with 0 for "no test."
10.1.3.3 Battery time
10.1.3.4 Reporting A menu option that groups reporting options for the selected module.
A menu option that sends a report to the reporting bank if power is lost during time programmed in Delay time mains voltage error. If this option is disabled, the report will only be sent if the power plant has not sent a Netvoltage absent report and will Power voltage error reporting enabled. This option applies only to the CS320 power supply module and not to the control unit.
10.1.4.1 Power supply failure
10.1.3.4.2 Battery error A menu option that activates battery fault reporting on a CS320 power module
10.1.3.4.3 Sirene sabotage/failure A menu option that sends a notification to the reporting bank when siren tampering or malfunctions occur with a power supply module.
10.1.4 Model Menu option showing the current model of the selected module.
10.1.4 Version A menu option that shows the current software version of the selected module.
10.1.5 Default settings A menu option that reset the selected module to factory settings.

Net input voltage (25VA Trafo) 230V ~ - 50Hz ± 10% - 25VA
Net input voltage (40VA Trafo) 230V ~ - 50Hz ± 10% - 40VA
Power consumption at 230V~ (25 VA) 0.108 A
Power consumption at 230V~ (40 VA) 0.173 A
Main panel supply 16.5 V~ characteristic
Power supply 13.8V ± 2%
Power consumption . . Stand by 40 mA at 13.8V ± 2%
Power consumption . .
Size PCB Dimensions (width x height x depth) 161x108x28 mm
Size housing Dimensions (width x height x depth) DHX75PB 380x260x120 mm DHx75PBM 450x300x90 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

11.1 Overview The CS535 voice module can transmit notifications to telephone numbers by recorded voice messages. You record the voice messages using a regular analogue phone. When an event triggers an alarm, the central unit connects to a pre-specified telephone number and controls the CS535 voice module so that the configured event is reported.
The CS535 voice module can send four types of speech messages in a report.
The voice module informs the panel when the notification is complete and the panel disconnects from the phone.
11.2 Install the CS535 voice module The CS535 voice module can be connected directly to the panel. If a CS534 communication module is used, the CS535 voice module is connected to the print site and the CC534 communications module is linked by means of a band cable. If a CS7002 GPRS module is used, this CS 7002 G PRS module will be connected to the panel and the CS535 communication module will then be connected by means of a band cable.
For more information about installing the CS535 voice module in the different enclosures, see chapter A-4. Install a base system.

1 Connector rear 5 RJ11 telephone connection
2 Reporting LED 6 Recording/display LED
3 Databox control LED 7 Recording/display key
4 Processor 8 Extension port for CS534 communication module

11.1.4 11.1.3
Single voice message Multiple voice messages
11.1.3.1
Messages 2 - 15 Same as above
11.1.6 11.1.5
11.2.4 11.2.3
Single voice message Multiple voice messages
11.2.3.1
Messages 2 - 15 Same as above
11.2.6 11.2.5
11.5 11.6 11.7
Before you can program the CS535 voice module, register and bring it to default settings. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules. To program the CS535, select CS535 Voice module.
11.3.1 Configure central for voice notifications You must enable the notification of events on the power station and program the zone types for which the notifications are sent. You must also assign each event to a recorded message. You can also assign a message to multiple events. For more information, see Chapter B-2 The central programming.
Events can be reported to up to six telephone numbers. Each phone number has its own customer number, protocol and events. You must program this information for phone number 1. In addition, you can set the number of dial attempts and a delay for voice reporting. For more information, see Chapter B-2 The central programming.
< Als de functie Alles annuleren is ingeschakeld, kan een gebruiker meldingen annuleren en spraakberichten beëindigen door een gebruikerscode in te voeren. Dit is bijvoorbeeld handig bij een vals alarm. Selecteer Central >System settings >:Options > Other>Cancel All > and press OK.
11.3.2 Recording voice messages In the CS535 voice module, as many as 18 recorded speech messages can be stored. Two of these messages, the introduction and address message, are always required. You can also specify an optional kiss-off message. The remaining 15 messages are event messages. Messages may be recorded in a sequential or separate manner. Certain events can be reported in one message. Below you will find the steps for recording different messages.
- If you want to record all messages, go to Successive and press OK.
- If you want to record messages separately, go to the corresponding menu option and press OK. For example, if you want to record the introduction message, go to Introduction message and press OK.
- If you want to record a message for one event, go to Voice Message only and press OK. Select the number of the message (1-15) and press OK.
- If you want to record a message for a series of events, go to Multiple voice messages and press OK. Select the number of first message (1-15) and press OK.

11.3.3 Play messages Recorded voice messages can be played sequentially or separately. Below you will find the steps for playing different messages.
- If you want to play all messages, go Successive and press OK.
- If you want to play messages separately, go to the corresponding menu option and press OK.
- If you want to play a message for one event, go to Voice Message only and press OK. Select the number of the message (1-15) and press OK.
- If you want to play a message for a series of events, go to Multiple voice messages and press OK. Select the number of first message (1-15) and press OK.
11.3.4 Configure a handshake enkiss-off The handshake and kiss-off can be programmed as a press on any or specific key of the phone. Below you will find the steps to configure these numbers.
< The voice protocol cannot generate a 'communication error' signal.

11 CS535 Voice Module A module used to send pre-recorded voice messages via the voter in an alarm event.
A menu command that records all voice module messages in order. The order is: Introduction message; 15 messages that may be related to different types of events (such as alarms or switch on/off); kiss- off message, address message
11.1.1 Successive
A menu command that records the introduction message. This message is sent by the CS535 voice module at the beginning of a telephone call with speech reporting
11.1.2 Introduction message
A menu command that records one voice message. This message is sent by the voice module and shows the event that has occurred
11.1.3 Single voice message
A menu command that records a random voice message. This message is sent by the CS535 voice module and lists events that have occurred
11.1.4 Multiple voice messages
A menu command that records the address message. This message is sent by the CS535 voice module and shows at which location an event occurred
11.1.5 Address Message
A menu command that records the kiss-off message. This message is sent by the CS535 voice module at the end of a telephone call with speech reporting, to indicate that the kiss-off number has been received.
11.1.6 Kiss-off message
11.2 Play A menu option that contains options to enable the installer to play recorded voice messages.
11.2.1 Successive A menu option that plays all voice module messages in order.
11.2.1 Introduction Message A menu command that displays the introduction message.
11.2.3 Single voice message A menu command that displays one message
11.2.4 Multiple voice messages A menu command that displays all voice messages in a row
11.2.5 Address Message A menu command that displays the address message
11.2.6 Kiss-off message A menu command that displays the kiss-offs message
A menu option with the handshake number. This number is sent from the control room (in case of a CS535 voice module, this is usually home or mobile phone) to the central unit for connection.
11.3 Handshake digit
A menu option that contains the number accepting the voice module as a signal from the phone indicating that the person has understood the message.
11.4 Kiss-off digit
11.5 Model Menu option showing the current model of the selected module.
11.6 Version A menu option that shows the current software version of the selected module.
11.7 Default settings A menu option that reset the selected module to factory settings.

Power supply 13.8V ± 2%
Power consumption . . Not in session 30 mA at 13.8V ± 2%
Power consumption . .
Size PCB Dimensions (width x height x depth) 57x100x20 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation

12.1 Overview The CS1700 is a proximity card reader/door controller module. Up to 15 card readers can be connected to the CSx75 control panel, depending on the model of the panel. The CS1700 can be programmed to provide access in any area or all areas. The LEDs can be programmed to track the system's output status and/or enabled or ready state. The reader is equipped with an optical sabotage switch. The CS170 proximity card reader is only suitable for the CS375, CS575 and CS875.
There are three badge actions that can activate an assigned function on an X-10 module. These actions vary depending on whether you work in standard mode or legacy mode.
In standard mode:
In legacy mode:



Green (data) Connect to the data connection of the power plant. This wire forms the data signal connection with all modules on the bus.
Black (com) Connect to the COMMON connection of the power plant. This wire connects the common connection of the power supply to the CS1700 proximity card reader.
Red (pos) Connect to the AUX POWER + connection of the power plant. This wire provides the CS1700 proximity card reader with power.
This is an optional RTE input. To use this option, you need to connect the normally open output request printer between this connection and COM. If this option is not used, it does not need to be connected.
Blue (exit) This is an optional open collector EXPLANATION. To use this option, connect the coil contacts of a relay between this connection and AUX POWER +.
12.2.2 Register the CS1700 proximity card reader Unlike most other CSx75 expansion modules, the CS1700 proximity reader determines his own address once the installation is complete. This is the first step in reader programming. For the registration of a reader, you will proceed as follows:
Pagers Address Peeptones Address
1 113 9 121
2 114 10 122
3 115 11 123
4 116 12 124
5 117 13 125
6 118 14 126
7 119 15 127
Cable Description · White (Output request)

Single badge Double badge Badge holds
Enter code Fully in Partially switched off Option 1 remote control Option 2 remote control Send X-10 function Activate relay
12.1 12.1.1
Badge functions 113 Prox. Reader
12.1.1.1
12.1.1.1.1 12.1.1.1.2 12.1.1.1.3 12.1.1.1.4
12.1.1.2 12.1.1.3
(2 Beeps) (3 Beep)
12.1.1.1.5 12.1.1.1.6
12.1.1.1.7 12.1.1.1.8
12.1.2.1
12.1.2.2
12.1.2.3
12.1.2.3.1
Single badge e (1 Beep) Double badge (2 Beeps) Badge holding (3 Beeps)
12.1.2.3.2
12.1.2.3.3
12.1.3.1
Activate programming card Optical sabotage Follow handset buzzer Doorbell X-10 Function in log as code-ingave Log RTE (Zone) Map Scan Mode
12.1.3.2 12.1.3.3
12.1.3.4
12.1.3.5
12.1.3.6 12.1.3.7
12.1.4 12.1.4.1 12.1.4.2 12.1.4.3
Access Options Magnetic Lock PenLock Access at Capped Not Closed When Disabled Active during Opening Active During Closure Access Without RTE Log Forced Access Exit Timing Selection
12.1.4.4 12.1.4.5
12.1.4.6 12.1.4.7 12.1.4.8
LED 1 (green) Ready status Relay status Invert
12.1.5.1
12.1.5.2 12.1.5.3
12.1.6.1
Enabled state Relais status Invert
12.1.6.2 12.1.6.3
Other Door alarm zone Request To Exit Zone Door alert time DTLO Time Badge time double/hold Relay active time Areas Log Area
12.1.7 12.1.7.2 12.1.7.1
12.1.7.3
12.1.7.4
12.1.7.5
12.1.7.6 12.1.7.7
12.1.7.8
12.1.8 Timing schedule 1
12.1.8.1
12.1.8.1.1 12.1.8.1.2
12.1.8.1.1.1
12.1.8.1.1.2
12.1.9.1 12.1.9.2
January February March April May June July August September October November December
12.1.8.1.3
12.1.8.1.3.1 12.1.8.1.3.2
Sunday Monday Tuesday Wednesday Thursday Friday Saturday Holidays
12.1.9.3 12.1.9.4 12.1.9.5 12.1.9.6
12.1.8.1.3.3 12.1.8.1.3.4
12.1.10 12.1.11
Reset Reader Address Model Version Default Settings
Dag 1 12.1.9.1.1
12.1.8.1.3.5
12.1.12 12.1.13
12.1.9.7
12.1.8.1.3.6 12.1.8.1.3.7 12.1.8.1.3.8
12.1.9.8
12.1.9.9 12.1.9.10 12.1.9.11 12.1.9.12
Before you start programming the system, you need to register and bring all CS1700 proximity readers to default settings. More information about registration can be found in Register the CS1700 proximity reader above. More information on bringing to default settings can be found in chapter 6. If the proximity reader is moved to another control unit, then delete the module number and reread the reader on the power station using the option Reset Reader Address. To program the CS1700 select CS1700 Prox reader.
12.3.1 Program the badge functions The three badge actions can each activate a particular function. The following example explains how function 1 of the remote control can be linked to the single badge feature on proximity reader 113. To activate this feature, you must also program the remote control function in RF receivers. For more information, see Chapter 9.

12.3.2 X-10 Configuration functions You can program which X-10 function is performed when a card is offered. In the following example, X-10 module 4 (module number 6, house code B) is linked to the dual badge function on proximity reader 113. To activate the double badge operation, you need to set scan time. In this example, the scan time is set to 1 second.
Function Description Function Description
0 All units from 4 Helderh. Slow down.
1 All units to 5 Helderh. Hey, hey.
2 to 6 All lights off
12.3.3 Add and Remove Maps If you want to add or delete cards, enter information on the handheld and then offer the tickets. Before a card can be added, the system must have a CS1700 proximity card reader programmed for user card programming. It is advisable to do so only
3 Out

Activate one reader in the system. You should use a reader close to the handler. This CS1700 proximity card reader sends the information to all other CS1700 proximity card readers in the system once programming is complete. In the following example, user card programming is enabled on reader 113.
< The proximity reader recognizes the predefined serial numbers of the cards. It is advisable not to change these serial numbers.
Add one card 1. Select User menu >CS1700 Prox readers>Add one map. 2. Enter the user number to be assigned to the card and press OK. 3. LED1 on any activated readers starts to blink. 4. Offer the card intended for the user entered. If the user card does not exist in the system, it will be added and LED1 stops flashing. If the card already exists in the system, the reader beeps three times and keeps blinking LED1. 5. 40 seconds after you have finished scanning, all readers in the system are updated with new user card data.
1. Select User menu >CS1700 Prox readers>Add multiple cards. 2. Enter the user number to be assigned to the card and press OK. 3. LED1 on any activated readers starts to blink. 4. Offer the card intended for the user entered. If the user card does not exist in the system, it will be added. LED1 keeps blinking to indicate that the next card can be scanned. If the card already exists in the system, the reader beeps three times and keeps blinking LED1. 5. 40 seconds after you have finished scanning, all readers in the system are updated with new user card data.
Clear one user 1. Select User menu >CS1700 Prox readers >: Remove one card. 2. Enter the user number assigned to the card and press OK. 3. The user card data of the entered user number is erased and LED1 stops flashing. After about 40 seconds, all readers in the system are updated with new user card data.
Activate a card 1. Select User menu:CS1700 Prox readers Activate map. 2. Enter the user number assigned to the card and press OK. 3. The user card data of the entered user number is activated and LED1 stops flashing. After about 40 seconds, all readers in the system are updated with new user card data.
Deactivate a card 1. Select User menu:CS1700 Prox readers. 2. Enter the user number assigned to the card and press OK. 3. User card data of the entered user number are deactivated and LED1 stops flashing. After about 40 seconds, all readers in the system are updated with new user card data.
Task Steps · Add multiple users

12 CS1700 Prox. reader A proximity card reader/door controller that can be programmed to control access in certain or all areas.
12.1 113 Card Reader A menu option that groups reporting options for the selected proximity reader.
12.1.1 Badge features A menu option that groups the functions that are activated by Single badge, Double badge and Badge hold.
12.1.1.1 Single badge (1 beep tone) A menu option that groups the functions activated by keeping a proximity card once for the proximity card reader.
12.1.1.2 Double badge (2 beeps) A menu option that groups the functions activated by a proximity card twice within time at Badge Hold is set to hold the proximity card reader
12.1.1.3 Badge holds (3 beeps) A menu option that groups the functions activated by a proximity card longer than time provided in Badge Hold is set to hold the proximity card reader
12.1.1.1.1 Enter code A menu option that activates Enter code for the selected operation of the proximity card reader.To be linked to its Single badge, Double badge and Badge hold. This function sends the same control to the power station via the proximity card than would send a handler when a valid code is entered. For example, if the system is enabled, the selected operation will disable the system.
12.1.1.1.2 Fully in A menu option that fully activates the function for selected operation of the proximity card reader. To match his Single badge, Double badge and Badge hold.
12.1.1.1.3 Partially in a menu option that activates the partially mode function for selected operation of the proximity card reader. To match his Single badge, Double badge and Badge hold.
12.1.1.1.4 Disable A menu option that activates the disable function for selected operation of the proximity card reader. To match his Single badge, Double badge and Badge hold.
12.1.1.1.5 Option 1 remote A menu option that sends an event •Option 1 remote control •Purchase for the selected operation of the proximity card reader. To match his Single badge, Double badge and Badge hold.
12.1.1.1.6 Option 2 remote control A menu option that sends an event . .Option 2 remote controller . for the selected operation of the proximity card reader. To match his Single badge, Double badge and Badge hold.
12.1.1.1.7 Send X-10 Function A menu option that ensures the proximity card reader sends an X-10 function to the home automation operating system.
12.1.11.8 Activate relay A menu option that activates the integrated open collector output in the Proxinity card reader instead of an external open collector exit/relais.

12.1.2 X-10 Features A menu option that contains X-10 module information and the functions for the selected proximity card reader. The X-10 functions are linked to the access card reader. It is possible to send X-10 modules using the badge on the card reader. It is also possible to configure the actions activated by each card operation. 0 All units out 1 All lamps on 2 to 3 Out All other 4 Increase Brightness 5 Lower Brightliness 6 All lights off
12.1.2.1 Module Number A menu option that sets the X-10 module number used to identify a particular X-10 modules on the selected module. Each system module shall be assigned a CSx75 databus module number. The system uses this number to identify the module. It is also used to report module problems (such as sabotage and module oversight issues) to the reporting bank.
12.1.2.1 X-10 Home Code A menu option setting the code to identify a particular building. This code is necessary if any neighbouring buildings are also equipped with an X-10 home automation control system. More information about the X-10 home automation control system can be found at www.x- 10europe.com.
12.1.2.3 Features A menu option that groups the functions which can be linked between a CS1700 proximity card reader and X-10 features.
12.1.2.3.1 Single badge (1 beep tone) A menu option setting the X-10 event sent once a proximity card is held for the proximity card reader.
12.1.2.3.2 Double badge (2 beeps) A menu option setting the X-10 event that is sent when a proximity card is twice within time provided by Badge Hold is set before holding the proximity card reader.
10.2.3.3.3 Keep Badge (3 beeps) A menu option setting the X-10 event sent when a proximity card exceeds the time provided by Badge Hold is set before holding the proximity card reader.
12.1.3 Options A menu option that groups all optional options related to the selected proximity reader.
12.1.3.1 Activate programming card A menu option that allows user cards to program.
12.1.3.2 Optical sabotage A menu option that sends a report to the reporting bank when a tamper occurs on the proximity card reader. The optical sabotage is a take-off protection.
12.1.3.3 Follow handheld buzzer A menu option that ensures the reader's buzzers are the same as those of the handheld.
12.1.3.4 Doorbell A menu option that activates a doorbell
12.1.3.1 Log RTE (Map) A menu option that records a RTE event in the log. A RTE (Map) event is a request for an extension by scanning a card.
12.1.2.1 Log RTE (Zone) A menu option that records a RTE event in the log. A RTE (Zone) event is a request for an exit by activating a zone.

12.1.3.1 Map Scan Mode A menu option that switches between the old and new scan mode. The old mode is displayed as Single/ Double/ Keep and the new as 1/2/3 Beeps.
1.1.4 Access Options A menu option that groups group access options for the selected proximity reader.
12.1.4.1 Magnetic lock Pen lock A menu option that controls a magnet lock or pen lock. If a door zone is programmed while this option is enabled, the proximity reader monitors the door zone and waits for it seconds after closing before the lock is activated. This prevents a door from closing due to the action of the magnet lock, or is not locked at all by triggering the pen lock too early.
12.1.4.2 Access enabled A menu option that allows the user to activate/deactivate the selected proximity reader while the system is switched on.
12.1.4.3 Not Closed When disabled A menu option that prevents a door open during the open period from remaining open.
12.1.4.4 Active during opening A menu option that activates the selected proximity reader between opening time and closing time. During these periods, a card can be used to turn the system on/off. These times are set in time schedules.
12.1.4.5 Active during closure A menu option that activates the selected proximity reader after closing time and before opening time. During these periods, a card can be used to turn the system on/off. These times are set in time schedules.
12.1.4.6 Access Without RTE A menu option that allows the user to open a door without an exit request (RTE).
12.1.4.7 Log Forced access A menu option that records a forced entry in the log.
12.1.48 Exit Timing Selection A menu option that selects the time frame used by the selected proximity reader. Eight timetables can be implemented simultaneously and complement each other.
12.1.5 LED 1 (green) A menu option that groups options to make the LED 1 green. In the proximity reader is a LED built (at the top of the reader) that can give or be out of a green light. The LED follows the ready status or status of the built-in relay in the proximity card reader. It is possible to invert the action that activates the LED.
12.1.5.1 Ready status A menu option that lets LED 1 (Green) of the CS1700 burn when the system is ready to be switched on.
12.1.5.2 Relay status A menu option that lets the selected LED burn when the open collector output/relais of the CS1700 module is activated.
12.1.5.3 Invert A menu option that lets the selected LED (Green/Red) burn in rest
1.2.4 LED 2 (red) A menu option that groups options to make the LED 2 red. In the proximity reader is an LED built (at the bottom of the reader) that can emit or be out a red light. The LED tracks the enabled state or condition of the built-in relay in the proximity card reader. It is possible to invert the action that activates the LED.
12.1.6.1 Enabled condition A menu option that lets LED 2 (Red) of the Proxinity reader burn when the system is enabled.

12.1.6.2 Relais status A menu option that lets the selected LED burn when the open collector output/relais of the CS1700 module is activated.
1.2.1.3 Invert A menu option that lets the selected LED (Green/Red) burn in rest
12.1.7.1 Door shunt zone A menu option setup which zone signals that the door is opened, for alarms and warnings.
12.1.7.2 Request To Exit Zone A menu option that selects the zone monitored for signaling a run-off request (RTE). You must activate the RTE zone type for the selected area.
12.1.7.3 Door error warning time A menu option that sets after how much time a warning tone is displayed before a door error alarm is reported.
12.1.7.4 DTLO Time A menu option that determines the time in which to close a door before reporting an error alarm.
12.1.7.5 Scantime A menu option that determines the time span during which the proximity card must be held for the proximity map reader to activate its functions. A proximity card reader can be programmed to activate different functions depending on whether the card is held one or twice within this time span or continuously for that duration of time in front of the card reader.
12.1.7.6 Relay active time A menu option that determines how long the open collector output/relais is activated when a proximity card is held for the proximity card reader.
12.1.7.7 Areas A menu option that displays all the areas assigned to the selected proximity reader. The selected proximity reader can activate an event for these areas.
12.1.7.8 Log Area A menu option that determines the area number which adds the proximity reader to events recorded in the log.
12.1.8 Timing A menu option that is combined with Exit Time schedule Selection select the time frames that influence the working of the proximity reader.
12.1.8.1.1 Disable/Open A menu option setting the time when the selected schedule switches to opening time.
12.1.8.1.2 Enable a menu option setting the time at which the selected schedule is switched on.
12.1.8.1.3 Active A menu option that lists the weekdays on which the selected switching time is active.
12.1.8.1.3.1 Not active on holiday days A menu option for activation of the holiday function. The selected time frame is not active on the days specified in Holidays.
12.1.9 Holidays A menu option that sets the holiday days. If the holiday function (12.1.8.1.3.1) is activated, these days' timetables are not active. Up to eight holiday days per month can be specified.
12.1.10 Reset reader address A menu option that clears the module number of the proximity card reader so that the reader can be read again on the control panel.
12.1.11 Model A menu option that displays the current model of proximity reader.
12.1.12 Version A menu option that displays the current software version of the proximity reader.

12.1.13 Default settings A menu option that reset the selected proximity reader to factory settings.
Power supply 13.8V ± 2%
Power consumption . . Stand by 40 mA at 13.8V ± 2%
Power consumption . .
Size reader Dimensions (width x height x depth) 35x118x15 mm
Environment Ambient temperature +0° C to + 40 °C
Air humidity Max. 93% without condensation
Food specifications · General provisions specifications · Shipping weight 115 g

13.1 Overview The CS7002 is the GPRS module that can be connected to a plant in the CSX75 series. The CS7002 GPRS module has the following characteristics, inter alia:


BUS COM
BUS COM
SIM ERR
GPRS ACTIVE
REPORTING
PSU ERR
GSM IN USE
NETWORK OK
BC
1 VVMiQ connector 7 Battery connectors for main panel battery cables
2 SIM card holder 8 External connection for CS534/535
3 GPRS modem 9 Main panel connection
4 Antenna connection A Lights
5 Flash-upgrade connection B TCP socket open LED
6 Loose connectors for connection to battery poles
C LED for network control The CS7002 is logged into the GSM network (LED)
The CS7002 GPRS module can be connected directly to the panel. If a CS534 communication module and/or a CC535 voice module is used, the CS7002 GPRS module is connected to the circuit board and the CC534 communication module or CS535 speech module is linked to the module via a band cable.
For more information about the installation of the CS7002 GPRS module in the different enclosures, see chapter A-4. Install a base system.
13.2.1 Registering the SIM card within the GSM network Before installing the SIM card in the CS7002 GRPS module, register the map on the GSM network.

+ Connect to the +-wire of the battery of the power plant
- Connecting to the .-wire of the battery of the power plant
Perform the wiring of the CS7002 as follows:
More information can be found in the installation manual of the CS7002 GPRS module.
13.2.4 Notification LEDs The LEDs on the module indicate the current status of the CS7002.
Connection Description

Reporting Control Reporting (1) Reporting 1 13.1 13.1.1 13.1.1.1 Location Backup Location
13.1.1.1.1
Reportage 2-6 As above
13.1.1.1.2
Events Alarm Alarm Recovery In/Disable Zone in/out bridge
13.1.1.1.3
13.1.1.1.3.1
13.1.1.1.3.1.1 13.1.1.1.3.1.2
13.1.1.1.3.1.3 13.1.1.1.3.1.4
13.1.1.1.3.2
Sabotage and malfunction Sabotation and recovery Zone failure and repair Storm module and repair Sirene/tel.line error and repair Miss RF detector and repair Battery fault RF Detector and repair
13.1.1.1.3.2.1
13.1.1.1.3.2.2 13.1.1.1.3.2.3 13.1.1.1.3.2.4 13.1.1.1.3.2.5
13.1.1.1.3.2.6
13.1.1.1.3.3
Nutrition Nutritional error and repair Aux. Flooding and recovery
13.1.1.1.3.3.1 13.1.1.1.3.3.2
13.1.1.1.3.4
Communication Communication error Automatic test reports
13.1.1.1.3.4.1
13.1.1.1.3.4.2
Other Programming and U/D Zone Inactivity Monitoring
13.1.1.1.3.5
13.1.1.1.3.5.1
13.1.1.1.3.5.2
13.1.1.1.4
Reporting Delay Report as
13.1.1.1.5
13.1.2 (1) Recipient 1
13.1.2.1
13.1.2.1.1
13.1.2.1.1.1 13.1.2.1.1.2
IP Address Customer number Recipient No. Line Number
Receiver 2 As above
13.1.2.1.1.3
13.1.2.1.1.4
13.1.2.2
Reporting Format Recipient Polling Polling Tiid
13.1.2.3
13.1.2.4
(1) Recipient 1 Telephone No. Customer number
13.1.3.1.1
13.1.3.1
Receiver 2 As above
13.1.3.1.2
13.1.3.1.3 13.1.3.1.3.1
Protocol SIA only b SIA several b SIA area modif. Contact ID
13.1.4.1
13.1.3.1.3.2
Areas 2 - 8 Same as above
13.1.3.1.3.3
13.1.3.1.3.4
13.1.5.1
Max. Reporting Attempts FTC Reporting Attempting Max Messages in 24 Hours Reporting Timeout CentralTimeout
13.1.5.2
13.1.5.3
13.1.5.4
13.1.5.5
CSD GPRS Protocol Up/Download
13.2.1 13.2.1.1 13.2.1.2 13.2.2
Telephone IP Address Start U/D Allow U/d Call Accepting Automatic Answer Using U/ D Callback Number Auto U/T During Test Time
13.2.5 13.2.6
GSM PIN code SIM Options
13.3.1.1
13.3.1.2
13.3.1.2.1
Operator selection Current operator
13.3.1.2.2
13.3.1.3
SMS Service Center address RSSI Value Bit error rate
13.3.1.4
13.3.1.5
13.3.1.6
13.3.1.6.1
Line error RF value Delay line error
13.3.1.6.2
Manufacturer Type Software Version Serial Number
13.3.1.7
13.3.1.7.1
13.3.1.7.2
13.3.1.7.3 13.3.1.7.4
CSD (Circuit Swiched Data) Baudrate Use V1.110 Mode
13.3.2.1
13.3.2.2
13.3.2.3
Network DHCP IP Address PPP User ID PPP Password GPRS APN GPRs APN 2
13.3.3.1
13.3.3.3 13.3.3.2
13.3.3.4 13.3.3.5
13.3.3.6
13.3.3.5.1
TCP/IP Alert Gate U/D Port
13.3.3.5.2
GSM check status Connection
13.3.4.1.1
GSM Module communication PIN code SIM accepted Sign in on GSM-net SIM PUK Necessary Send SMS Use GSM Audio Use GSM CSD GPRS Connected RSSI Good
13.3.4 13.3.4.1
13.3.4.1.2
13.3.4.1.3
13.3.4.1.4
13.3.4.1.7 13.3.4.1.6 13.3.4.1.5
Food 13.3.4.2
13.3.4.2.1
Battery Failure SM PSU Deposit Bus Power Supply Malfunction
13.3.4.2.2
13.3.4.1.8
13.3.4.2.3
13.3.4.1.9
Model Version Default Settings
Application 13.3.4.3
13.3.4.3.1
Up/Download Start Download Reporting Max. Report in 24 H
13.3.4.3.2
13.3.4.3.3 13.3.4.3.4
Before you can program the CS7002 GPRS module, register and bring it to default settings. More information about registering and bringing to default settings can be found in chapter

B-1 Registering modules. To program the CS7002 GPRS module select CS7002 GPRS Module.
13.3.1 Testing the RSSI value During the registration procedure, you must check the RSSI value (signal strength) of the CS7002 and note it in the system documentation. The RSSI value is linked to the signal strength of the GSM network and varies from 0-31% (99 = unknown). If the RSSI value is not sufficient, you need to move the antenna for better reception. Below are the steps for reading the RSSI value.
13.3.2 Reporting The CS7002 has six reporting settings that can use four reporting locations. You can configure which events are reported and specify two locations for each reporting setting. Two of these could be text messages, and two TCP/IP. The backup location, which is used when the voter encounters problems, must be another electorate, for example PSTN.
< All events in Reporting Control 1 are enabled by default.
The module can send primary, secondary and backup reports.
13.3.2.1 Primary reports Primary reports are the main method of reporting selected events.
13.3.2.2 CS7002 as backup facilities alongside another voter The CS7002 reports the event if the central or other voter cannot.
13.3.2.3 CS7002 backup facility, reporting format (SMS/GPRS) Central
The report facility controls the control centre and reports selected events if the power plant cannot do so.
The CS7050 is a backup chooser for TCP/IP. The CS7501 is an ISDN-chooser. If neither can report the event, a module communication error is sent that is forwarded by the CS7002.
13.3.2.4 CS7002 backup, reporting format (audio reporting) Central

The power plant is able to send reports in GSM Audio instead of PSTN. The panel can also use GSM Audio and PSTN side by side.
< Press #0 to enter a .gvm on a CS5500 control panel or press 10 on a CS-LCD or CS LED control panel.
13.3.2.5 Central/CS7002 as backup facility for CS7002 Backup reports will be sent if the CS7002 fails to send the primary report. Backup reports can be sent by another reporting device on the module or other module within the system.
13.3.2.6 CS7002 as backup
13.3.2.7 Central as backup facility If the CS7002 cannot report an event, a module communication error is sent that is forwarded by either the central or backup chooser.
13.3.3.1 GSM CSD connection The up/download access code configures you on the power station via Up/ Download > Access code. For more information, see Chapter B-2 The central programming. In the following example, the CS7002 GPRS module is configured to answer only calls from phone number 5666666. The computer starts the upload/download session.

13.3.3.2 GPRS CSD connection. The connection is established via a TCP/IP network. Instead of a telephone number, an IP address is set. The options Use U/D Callback Number and Accept Call from deactivated.
13 CS7002 GPRS Module Module that acts as GPRS and GSM module for reporting and up/download.
13.1 Reporting A menu option that groups reporting options.
13.1.1 Reporting Control A block of report data containing settings for the way selected events are formulated in accordance with predefined settings in one or more messages for transmission to given destinations. A menu option that groups reporting control options.
13.1.1.1.1 Location Menu option to configure the report destination for the selected reporting setting.
13.1.1.1.2 Backup Location Menu option to configure the backup destination for the selected reporting setting. If you are using another module as backup destination, select the reporting format in Backup Format and enable test report events on the backup module.
13.1.1.1.3 Events A menu option that contains all configurable events for the different reporting settings. All events for Reporting Control 1 are enabled by default. The events for all other reporting settings are disabled by default. Enabled events are stored in one or more messages according to preconfigured settings and sent to the selected reporting destination. If you use the CS7002 as backup facility in combination with another extra voter, you should only Test reports enable.
13.1.1.1.3.1 Alarm and in/out A menu option that groups events reported to the selected reporting institution
13.1.1.1.3.1.1 Alarm A menu option that sends a notification to the selected reporting setting when an alarm situation occurs.
13.1.1.1.3.1.2 Alarm recovery A menu option that sends a notification to the selected reporting setting when the alarm is restored after an alarm.
13.1.1.1.3.1.3 To/To disable A menu option that sends a message to the selected reporting setting indicating when the system is disabled and enabled.
13.1.1.1.3.1.4 Zone in/out of bridge A menu option that sends a notification to the selected reporting setting when a zone is crossed. A notification is also sent when the zone is restored (breakdown is lifted)
13.1.1.1.3.2 Sabotage and malfunction A menu option that groups the sabotage and malfunction events reported to the selected reporting institution
13.1.1.1.3.2.1 Sabotage and recovery A menu option that sends a notification to the selected reporting setting when a sabotage situation occurs. A recovery notification is also sent when sabotage is no longer active

13.1.1.1.3.2.2 Zone interference and recovery A menu option that sends a report to the selected reporting institution when a zone failure occurs. A report is also sent when the malfunction is no longer active
13.1.1.1.3.2.3 Deterioration and repair module A menu option that sends "problem module and recovery" notifications to the selected reporting setting.
13.1.1.1.3.2.4 Sirene/tel.line error and repair A menu option that sends a notification to the selected reporting setting when a siren or phone error occurs. A recovery message is sent when the error has been repaired.
13.1.1.1.3.2.5 Missing RF detector and recovery A menu option that sends a notification to the selected reporting setting when an RF detector is missing. A recovery report is sent to the reporting bank when the recipient receives a valid signal from the missing transmitter
13.1.1.1.3.2.6 Battery fault RF detector and repair A menu option that sends a report to the selected reporting setting when battery error occurs in an RF detector. A recovery report is also sent when the battery error is no longer active.
13.1.1.1.3.3 Nutrition A menu option where the nutrition events are grouped and reported to the selected reporting institution.
13.1.1.1.3.3.1 Nutritional error and repair A menu option that reports power error, power failure recovery, battery error and battery error recovery events to the selected phone number, reporting setting, recipient or email account.
13.1.1.1.3.3.2 Aux. Flooding and recovery A menu option that sends a notification to the selected reporting setting when too high a current loss is detected. A recovery report is also sent when the flood situation has been restored
13.1.1.1.3.4 Communication A menu option where the communication events are grouped and reported to the selected reporting institution.
13.1.1.1.3.4.1 Communication error A menu option that reports a communication error event to the selected reporting setting.
13.1.1.1.3.4.2 Automatic test reports A menu option that sends a test report to the selected reporting setting at fixed times. Units can be set in days or hours
13.1.1.1.3.5.1 Programming and U/D A menu option that reports programming and up/download events to the selected reporting setting.
13.1.1.1.3.5.2 Zone inactivity monitoring A menu option that sends a notification to the selected reporting setting when an area inactivity event takes place
13.1.1.1.4 Reporting Delay A menu option to configure the waiting time in seconds before the CS7002 module sends a message. If other events occur during this period, they will be sent in one message together with the first event. This time can be set from 0 to 255 seconds. This institution is only useful in SMS reporting.
13.1.1.1.5 Report as Menu option to enable primary reporting (Always Report) or secondary reporting (Central Selector Problem) for the selected reporting setting.
13.1.2 TCP/IP Reporting A menu option that groups TCP/IP reporting options.
13.1.2.1 Recipients A menu option that groups options for the TCP/IP receiver.
13.1.2.1.1.1 IP Address A menu option to configure the address of the selected TCP/IP receiver.

13.1.2.1.1.2 Customer number A menu option specifying a unique code sent by the voter on the central or electoral system to the selected reporting setting or number. This code is used to identify and invoice the user. Different customer numbers can be set for each phone number and area. This is also called the account number. In the customer numbers for the CS7002 GPRS module you can also use letters A, B, C, D, E and F.
13.1.2.1.1.3 Recipient No. A menu option for configuring the number of the telephone line receiver associated with the recipient's account.
13.1.2.1.1.4 Line Number A menu option to configure the line number associated with the recipient's account.
13.1.2.1 Reporting Format A menu option for configuring the communication format to report to TCP/IP recipients. Please refer to the instructions of the alarm centre receiver to determine which format should be used.
13.1.2.3 Recipient Polling A menu option for configuring the polling message sending module to report recipients.
13.1.2.4 Polling Time A menu option for configuring the TCP/IP polling time. This value must correspond to the TCP/IP polling time set on the TCP/IP receiver. The value chosen depends on the desired level of security and the cost of data transfer. This time can be set from 1 to 255 minutes. If 0 is selected, the option will be disabled.
13.1.3 SMS Reporting A menu option where SMS reporting options are grouped.
13.1.3.1.1 Telephone No. A menu option setting the phone number to which SMS reports are sent.
13.1.3.1.2 Customer number A menu option specifying a unique code sent by the voter on the central or the electoral dial to the selected reporting setting. This code is used to identify and invoice the user. Different customer numbers can be set for each phone number and area. This is also called the account number. The letters B, C, D, E, F can be used in account codes for power stations. In the customer numbers for the CS7002 GPRS module you can also use letters A, B, C, D, E and F.
13.1.3.1.3 Protocol A menu option to configure the communication format used for notification to the selected SMS receiver.
13.1.3.1.3.1 SIA only b A menu option to set SMS reporting options so that events are grouped and sent as separate messages to individual account codes.
13.1.3.1.3.2 SIA multiple b A menu option to set SMS reporting options so that events for different account codes can be sent in one message.
13.1.3.1.3.3 SIA area modif. A menu option that allows area modifiers to be used to identify areas.
13.1.3.1.3.4 Contact ID A menu option that selects the contact ID protocol.

13.1.4 Area of customer numbers A menu option that lists the customer number for each area. The customer number is sent when the relevant area is reported. There are two groups of customer numbers. First, a customer number is assigned to each report destination. In addition, a customer number is assigned to each area. If you try to use both customer numbers, the customer number for the area is priority.
13.1.5 Reporting Attempts A menu option that groups the report options.
13.1.5.1 Max. Reporting Attempts A menu option to configure the number of times the CS7002 tries to send a report. This value can be set from 0 to 15.
13.1.5.2 FTC Reporting Attempts A menu option to configure the number of attempts made to a given report destination before reporting a communication error. This value can be set from 1 to 15.
13.1.5.3 Max Messages in 24 hours A menu option to configure the maximum number of reports that may be sent by CS7002 within 24 hours. The CS7002 stops reporting when the number of messages exceeds this number within 24 hours. Possible values are 1 to 255. If the value is 0, there is no limit. This applies to SMS and TCP/IP.
13.1.4.4 Reporting Timeout A menu option to configure the maximum time that the CS7002 tries to report to each recipient. If the notification is not completed within this time, the attempt will be specified. This time can be set from 0 to 255 seconds.
13.1.5.5 CentralTimeout A menu option to configure the maximum period during which a central operator must report an event. If the CS7002 reporting setting is configured for dual/back-up reporting and the central authority does not report the event during this period, the reporting institution shall report the occurrence. This time can be set from 1 to 255 seconds. If 0 is selected, the option will be disabled.
13.1.6 Backup Format A menu option for configuring the reporting format when using another module as backup. On the backup module you need to set the same reporting format.
13.2 Up/Download A menu option that contains options used to send download sessions between the up/download software and the power station.
13.2.1 Protocol A menu option that selects a CSD or GPRS connection.
13.2.1.1 CSD (Circuit Switched Data) Circuit Switched Data. This form of communication is used for uploading/downloading data. It is similar to a modem, but is wireless and built into the CS7002.
13.2.1.2 GPRS General Packet Radio Service. Global standard for wireless communication. Supports various bandwidths and can send and receive both small data packages as well as large amounts of data.
13.2.2 Phone No. A menu option setting the phone number of the computer running upload/download software.
13.2.3 IP Address A menu option to configure the address of the selected TCP/IP receiver.
13.2.4 Start U/D A menu option that can start an upload/download session between the module and PC from a control panel.

13.2.5 Allow U/D A menu option that allows an upload/download session between the module and PC to be started from a PC. The computer's ringing in on the module. You must choose the data phone number to call on the GSM for up/download. This option depends on other options (Accept call from, answer automatically and use U/D callback number).
13.2.6 Call Accept From Menu option for answering incoming calls only from known phone numbers. If you want to be able to use this setting, please Allow U/D select and program the phone number of the computer in Up/Download>Phone number..
13.2.7 Automatic Reply A menu option to automatically reply the CS7002 incoming calls. If you want to be able to use this option, you must enable U/D.
13.2.8 U/D Use dial-back Menu option to have the CS7002 call back to computer to start an upload/download session. If you want to be able to use this option, you must enable U/D.
13.2.9 Auto U/D During Test Time A menu option that configures the module to automatically call the PC, so an upload/download session can be started after a car test. You need to program the auto test on central.
13.3.1 GSM Global System for Mobile Communications. Global standard for wireless communication. Supports narrowband Time Division Multiple Access (TDMA). A menu option where the settings of the GSM connection are grouped.
13.3.1.1 PIN code SIM A menu option for entering the code used to register the SIM card on the GSM network.
13.3.1.2 GSM operator A menu option that contains information about the current GSM operator and allows you to manually choose a specific GSM operator.
13.3.1.2.1 Operator selection A menu option for configuring the GSM network provider used by the module. If you set this option to 00000, the SIM card can automatically choose a network provider. It is also possible to enter an operator ID for selecting a network provider yourself.
13.3.1.2.2 Current operator A menu option that displays the name of the automatically or manually selected GSM network provider. This option is only valid if the module is logged into a GSM network.
13.3.1.3 SMS Service Centre Address A menu option for configuring the SMS service centre's telephone number. Usually this number is left blank, as it is automatically selected by the SIM card. The number must start with the country code.
13.3.1.4 RSSI Value RSSI stands for Remote Signal Strength Indication. This is a measure for the RF reception and is similar to the signal indicator on a mobile phone. A menu option that displays the current RSSI value. The RSSI value is updated periodically when you are logged into the network. RSSI values range from 0 to 31 (99 = unknown).
13.3.1.5 Bit error rate A menu option that displays the current Bit Error Rate (BER). The BER value is updated periodically when the module is logged into the network. This information shall be used only for verification purposes. The BER values range from 0% to 7% (99 = unknown). Applicable only to GPRS.

13.3.1.6 Connection error options A menu option where connection error options are grouped. A connection error occurs when the module cannot login to the GSM network.
13.3.1.6.1 Line error RF value A menu option for setting the minimum acceptable level of the RSSI signal. If the signal falls below this level for the time specified in Delay line error, a line error is generated. Possible values are 1 to 31. If the value is 0, the setting is disabled.
13.3.1.6.2 Delay line error A menu option that determines how long the RSSI signal must be below the minimum RF level before a line error is generated. This time can be set from 0 to 255 seconds.
13.31.17 GSM Module info A menu option that brings together the information coming back from the integrated GSM module on the GSM module.
Manufacturer A menu option containing the identification of the manufacturer of the GSM module.
13.3.1.7.2 Type A menu option for displaying the type of GSM modem used by the module.
13.3.1.7.3 Software version A menu option that shows the current software version of the selected module.
13.3.1.7.4 Serial number A menu option to display the serial number of the GSM modem used by the module. This is only used for diagnostic purposes.
13.3.2 CSD (Circuit Switched Data) Circuit Switched Data. This form of communication is used for uploading/downloading data. It is similar to a modem, but is wireless and built into the CS7002.
13.3.2.1 Baudrate Menu option for configuring the baudrate to download via CSD/ GSM. This setting must match the Baudrate set to the computer modem.
13.3.2.2 Use V1.110 A menu option for performing V1.110 CSD GSM calls that are initiated by the site. Use this option if the computer is located on an ISDN line and uses an ISDN modem.
13.3.2.3 Mode A menu option for configuring the mode used for CSD GSM calls that are initiated by the site. If you have problems up/downloading, change this setting of transparent mode in non-transparent mode or vice versa.
13.3.3 Network A menu option that groups network options.
13.3.3.1 DHCP IP Address A menu option that displays the IP address assigned to CS7002 during login with GPRS network.
13.3.3.2 PPP User ID A menu option to configure the user ID for a PAP login. Please inform the network provider if PAP login is required and ask for a user ID and password.
13.3.3.3 PPP Password A menu option for configuring the password for a PAP login. Please inform the network provider if PAP login is required and ask for a user ID and password.
13.3.3.4 GPRS APN A menu option to configure the name of the GPRS access point. Get this name from the network provider. This is a mandatory institution when using TCP/IP reporting.

13.3.3.5 GPRS APN 2 A menu option for the CS7002 GPRS module for configuring the name of GPRS access point. Get this name from the network provider. This is used if the connection cannot be made via GPRS APN.
13.33.6 Gate Numbers A menu option where options for the TCP/IP port are grouped.
13.3.3.6.1 TCP/IP Alert Port A menu option that configures the number of the TCP/IP port to which polling and alarms are reported. The default value is 9999 and it does not need to be changed under normal circumstances.
13.3.3.6.2 U/D Port A port configuration menu option used for up/download.
13.3.4 Status of control A menu option that groups the status messages for GSM events.
13.3.4.1 GSM Connection A menu option that groups the settings of the GSM connection.
13.3.4.1.1 GSM Communication Module A menu option that indicates the connection to the GSM module has been established.
13.3.4.1.2 PIN code SIM accepted A menu option that indicates that the PIN code for the SIM card was correctly entered.
13.3.4.1.3 Logged-in on GSM network A menu option that indicates the GSM module is logged into the GSM network.
13.3.4.1.4 SIM PUK Necessary A menu option that indicates that the SIM card is blocked and that a PUK code must be entered to unblock it. Place the card in a mobile phone and enter the PUK code. After the card has been unblocked, place it back in the GPRS module.
13.3.4.1.5 Send SMS A menu option that indicates the module is in progress sending a message via the GSM network.
13.3.4.1.6 Use GSM Audio A menu option that indicates the module uses GSM sound. The GSM audio channel is used when the central station reports through the voice channel of the GSM network.
13.3.4.1.7 Use GSM CSD A menu option indicating that the GSM CSD module is using.
13.3.4.1.8 GPRS Connected A menu option that indicates the module is logged into the GPRS network.
13.3.4.1.9 RSSI Good A menu option that indicates that the current RSSI level is equal to or higher than the required signal level configured in Line error RF Value. If the RSSI level falls below this value, a GSM line error is reported.
13.3.4.2 Food A menu option that groups the status messages related to the power supply.
13.3.4.2.1 Battery fault A menu option that indicates there is a problem with the battery.
13.3.4.2.2 SM PSU Failure A menu option that indicates a problem with the connected 3.8 V power module.
13.3.4.2.3 Bus Power supply Disruption A menu option that indicates there is a problem with the power supply to the bus.
13.3.4.3 Application A menu option that groups the status messages related to the application.
13.3.4.3.1 Up/Download A menu option that indicates the download is ongoing.
13.3.4.3.2 Start Download A menu option that indicates the download is starting.

13.3.4.3.3 Reporting A menu option that displays a status message when reporting.
13.3.4.3.4 Max. Report in 24 H A menu option that indicates that the maximum number of reports allowed within 24 hours has been reached. This applies to SMS and GPRS reporting.
13.4 Model A menu option that shows the current model of the selected module.
13.5 Version A menu option that shows the current software version of the selected module.
13.6 Default Settings A menu option that resets the selected module to factory settings.
Power voltage 12V ± 2%
Power consumption . . Stand by 30 mA at 12V ± 2%
Power consumption . .
Size PCB Dimensions (width x height x depth) 97x102x24 mm
Environment Ambient temperature +0° C to + 49 °C


15.1 Overview The CS7050 TCP/IP module is a dual-processor-controlled internet/intranet interface for connection of the CSx75 central to the OH network receiver. This interface allows all signals from a CSx75 to be transmitted over the network. The CS7050 TCP/IP module has the following characteristics:

1 2 3 4
1 SIM pin 15 RS232
2 Modem pin 2 6 Connect to CSx75 panel

More information about installing the CS7050 TCP/IP module in different enclosures can be found in chapter A-4 Install a base system.
+ Connect to the Aux+ connection on the bus of the power station.
COM Connect to the COM connection on the bus of the power station.
DATA Connect to the DATA connection of the bus at the power station.
J16 Connect the Ethernet plug J16 (10BT) to a 10BT-EtherNet hub, router or gateway. Do not use a CASCADE or X port in crossover mode.
DS1 Blinks whenever the CS7050 has an opportunity to reach Aritech CSx75 bus. If it's right, this LED flashes about twice a second.
DS3 Blinks while waiting for signals from the Ethernet module.
DS4 To while waiting for an answer from an Aritech CSx75 bus device.
DS5 Blinks at the time when the CS7050 receives a package from the Ethernet module.
DS6 To when the bus wants to send a message to the network. " DS3 - DS6 are disabled if the system is initialized, normal and pending new events to report.
L1 (on SIM module) Blinks Ethernet activity.
L2 (on SIM module) To when an Ethernet connection is established via the 10BT cable.
DS2 The sixth LED is located at the back of the card. It is used for hardware and only burns weak when the card is connected to the CSx75 control panel.
Connection Description · light Description

TCP/IP Reporting 15.1
1 Recipient (1) IP Address 15.1.1 15.1.1.1
Receiver 2 As above
Alarm en in/uit 15.1.1.2.1 15.1.1.2.1.1 15.1.1.2
Events Alarm Alarm Recovery In/Disable Zone in/out bridge
15.1.1.2.1.2
15.1.1.2.1.3
15.1.1.2.1.4
Sabotage and malfunction Sabotation and recovery Zone failure and repair Storm module and repair Sirene/tel.line error and repair Miss RF detector and repair Battery fault RF Detector and repair
15.1.1.2.2.1
15.1.1.2.2
15.1.1.2.2.2
15.1.1.2.2.3
15.1.1.2.2.4
15.1.1.2.2.5
15.1.1.2.2.6
Nutrition Nutritional error and repair Aux. Flooding and recovery
15.1.1.2.3
15.1.1.2.3.1 15.1.1.2.3.2
15.1.1.2.4
Communication Communication error Automatic test reports
15.1.1.2.4.1
15.1.1.2.4.2
Other 15.1.1.2.5
15.1.1.2.5.1 15.1.1.2.5.2
Programming and U/D Zone inactivity monitoring
E-Mail Address 15.2.1 15.2
1 E-mail (1) E-Mail Address 15.2.2.1 15.2.2.1.1 Email Account 15.2.2
Email 2 As above
Events 15.2.2.1.2
15.2.2.1.2.1 Alarm Alarm Recovery In/Disable Zone in/out bridge
Alarm en in/uit 15.2.2.1.2.1.1 15.2.2.1.2.1.2
15.2.2.1.2.1.3 15.2.2.1.2.1.4
15.2.2.1.2.2
Sabotage and malfunction Sabotation and recovery Zone failure and repair Storm module and repair Sirene/tel.line error and repair Miss RF detector and repair Battery fault RF Detector and repair
15.2.2.1.2.2.1
15.2.2.1.2.2.2 15.2.2.1.2.2.3 15.2.2.1.2.2.4 15.2.2.1.2.2.5
15.2.2.1.2.2.6
15.2.2.1.2.3
Nutrition Nutritional error and repair Aux. Flooding and recovery
15.2.2.1.2.3.1
15.2.2.1.2.3.2
15.2.2.1.2.4
Communication Communication error Automatic test reports
15.2.2.1.2.4.1
15.2.2.1.2.4.2
Other 15.2.2.1.2.5
15.2.2.1.2.5.1
Programming and U/D Zone inactivity monitoring
15.2.3.1
Domain Name IP Address
15.2.2.1.2.5.2
15.2.3.2
15.3 Customer numbers
15.3.2.1 Area of customer numbers
Areas 2 - 8 Same as above
Recipient No Line Number
15.4.1 15.4.2
Start U/D Allow U/d Auto U/ D for Test Time IP Address
15.4.3 15.4.4
Domotics 15.5
Activate Domotica IP Address
Send to Recorder IP Address
Reporting Reporting Format Central is Backup Recipient 2 as Backup Receiver Polling Polling Tiid
15.7.1.2
15.7.1.1
15.7.1.3
15.7.1.4
15.7.1.5
Use DCHP Own IP Address Gateway IP Address Subnet Mask Network Timeout Max Network Attempts
15.7.2.1 15.7.2.2
15.7.2.3
15.7.2.4
15.7.2.5
15.7.2.6
15.7.0.7 TCP/IP Alert Gate U/D Port E-Mail Gate Domotica Port
15.7.2.7.1
15.7.2.7.2
15.7.2.7.3
15.7.2.7.4
Model Version Default Settings

Before you can program the system, you need to register and bring it to default settings. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules. You can program the GS7050 TCP/IP module via a control panel or using UDx75 software. For programming the CS7050 using a control panel select CS7050 TCP/IP Module.
15.3.1 Configure TCP/IP reporting The CS7050 TCP/IP module can report to two reporting banks. You can set which events to report, what format should be used and which connection parameters apply. In the following example, TCP/IP reporting is used to send primary reports for sabotage events in area 1 to receiver 1 (IP address 122.168.1.1).
- In Windows 9X / Windows ME type ipconfig on the DOS command line.
- In Windows 2000 / XP type ipconfig on the command line.
15.3.2 Configure email reporting When reporting to email addresses, you can think of computers, mobile phones, paging and other devices. You can set which events to report, what format should be used and which connection parameters apply. If you want to use email reporting, configure the server settings and e-mail address and port of the CS7050. In the following example, e-mail reporting is used to send primary alarm reports in area 2 of own mail@mijemail.com to email 1 (user1@mijemail.com).

15.3.3 Configuring reporting options The CS7050 TCP/IP module can send primary, backup and dual reports. Below are the steps to configure the various reports.
- Select Dispatch is backup and press OK.
- Turn on the auto test report to the telephone events of the plant and system events.
- Make sure that the reporting format used by the power plant is equal to what is set up in Reporting format.
- Select Receiver 2 as Backup >Not active and press OK.
- Select Disabled control and press OK.
- Activate all event categories on the control panel.
15.3.4 Upload/download configure If you want to be able to up/download, you need to configure the settings for initiating a session on the CS7050 TCP/ IP module and set the IP address and port of the computer. The up/download access code is set in the power station. In the following example, download sessions are activated during call calls. The calls come from a reporting bank (IP address 192.37.57.3) via the TCP/IP alarm port.

15 CS7050 TCP/IP module Module that acts as Ethernet communication module for reporting and up /download.
15.1 TCP/IP Reporting A menu option that groups TCP/IP reporting options.
15.1.1.1 IP Address A menu option to configure the address of the selected TCP/IP receiver.
A menu option that contains all configurable events for the different recipients or email accounts. By default, all areas are enabled. Enabled events are stored in one or more messages according to preconfigured settings and sent to the selected report destination or email address. Set the areas you want to take with each report. If a region is not selected, no events from the area concerned will be reported via the network, regardless of what is set elsewhere.
15.1.1.2 Events
15.1.1.2.1 Alarm and in/out A menu option that groups events reported to the selected recipient
15.1.1.2.1.1 Alarm A menu option that sends a message to the selected recipient when an alarm situation occurs.
15.1.1.2.1.2 Alarm recovery A menu option that sends a message to the selected recipient when the alarm is restored after an alarm.
15.1.1.2.1.3 To/To disable A menu option that sends a message to the selected recipient indicating when the system is disabled and enabled.
A menu option that sends a notification to the selected recipient when a zone is crossed. A notification is also sent when the zone is restored (override terminated)
15.1.1.2.1.4 Zone in/out of bridging

15.1.1.2.2 Sabotage and malfunction A menu option that groups the sabotage and malfunction events reported to the selected receiver
A menu option that sends a notification to the selected recipient when sabotage occurs. A recovery notification is also sent when sabotage is no longer active
15.1.1.2.2.1 Sabotage and recovery
A menu option that sends a report to the selected recipient when a zone failure occurs. A report is also sent when the malfunction is no longer active
15.1.1.2.2.2 Zone interference and recovery
15.1.1.2.2.3 Deterioration and repair module A menu option that sends "progress module and recovery" notifications to the selected recipient.
A menu option that sends a message to the selected recipient when a siren or phone error occurs. A recovery message is sent when the error has been repaired.
15.1.1.2.2.4 Sirene/tel.line error and repair
A menu option that sends a notification to the selected receiver when an RF detector is missing. A recovery report is sent to the reporting bank when the recipient receives a valid signal from the missing transmitter
15.1.1.2.2.5 Missing RF detector and recovery
A menu option that sends a report to the selected receiver when battery error occurs in an RF detector. A recovery report is also sent when the battery error is no longer active.
15.1.1.2.2.6 Battery fault RF detector and repair
15.1.1.2.3 Food A menu option where the nutrition events are grouped and reported to the selected recipient
15.1.1.2.3.1 Nutritional error and repair A menu option that reports power error, power failure recovery, battery error and battery error recovery events to the selected receiver.
A menu option that sends a message to the selected receiver when too high a current is detected. A recovery report is also sent when the flood situation has been restored
15.1.1.2.3.2 Aux. Flooding and recovery
15.1.1.2.4 Communication A menu option where the communication events are grouped and reported to the selected recipient.
15.1.1.2.4.1 Communication error A menu option that reports a communication error event to the selected reporting setting.
15.1.1.2.4.2 Automatic test reports A menu option that sends a test report to the selected receiver. Units can be set in days or hours
15.1.1.5.1.1 Programming and U/D A menu option that reports programming and up/download events to the selected recipient.
15.1.1.2.5.2 Zone inactivity monitoring A menu option that sends a notification to the selected recipient when a zone inactivity event occurs.
15.2 E-Mail Reporting A menu option where email reporting options are grouped.
A menu option to configure the email address assigned to the CS7050 TCP/IP module. This is a mandatory e-mail reporting setting. The email server must accept the domain name. Some email servers only accept messages from their own domain to prevent spam.
15.2.1 E-Mail Address
15.2.2 E-Mail Account A menu option where email account options are grouped.

A menu option to configure the address of the selected mail account. This must be a functional e-mail address known to work. Different destinations can be used, including computers, mobile phones, paging devices and other devices.
15.2.2.1.1 E-mail address
A menu option that contains all configurable events for the different recipients or email accounts. By default, all areas are enabled. Enabled events are stored in one or more messages according to preconfigured settings and sent to the selected report destination or email address. Set the areas you want to take with each report. If a region is not selected, no events from the area concerned will be reported via the network, regardless of what is set elsewhere.
15.2.2.1.2 Events
15.2.2.1.2.1 Alarm and in/out A menu option where events are grouped that report to the selected email account
15.2.2.1.2.1.1 Alarm A menu option that sends a notification to the selected email account when an alarm situation occurs.
15.2.2.1.2.1.2 Alarm recovery A menu option that sends a notification to the selected email account when the alarm is restored after an alarm.
15.2.2.1.2.1.3 To/Disable A menu option that sends a notification to the selected email account indicating when the system is disabled and enabled.
A menu option that sends a notification to the selected email account when a zone is crossed. A notification is also sent when the zone is restored (override terminated)
15.2.2.1.2.1.4 Zone in/out of bridging
15.2.2.1.2.2 Sabotage and malfunction A menu option that groups the sabotage and malfunction events reported to the selected email account
A menu option that sends a notification to the selected email account when sabotage occurs. A recovery notification is also sent when sabotage is no longer active
15.2.2.1.2.2.1 Sabotage and Recovery
A menu option that sends a report to the selected email account when a zone failure occurs. A report is also sent when the malfunction is no longer active
15.2.2.1.2.2.2 Zone malfunction and recovery
15.2.2.1.2.2.3 Failure module and recovery A menu option that sends "promot module failure and recovery" notifications to the selected email account.
A menu option that sends a notification to the selected email account when a siren or phone error occurs. A recovery message is sent when the error has been repaired.
15.2.2.1.2.2.4 Sirene/tel.line error and repair
A menu option that sends a notification to the selected email account when an RF detector is missing. A recovery report is sent to the reporting bank when the recipient receives a valid signal from the missing transmitter
15.2.2.1.2.2.5 Missing RF detector and recovery
A menu option that sends a report to the selected email account when battery error occurs in an RF detector. A recovery report is also sent when the battery error is no longer active.
15.2.2.1.2.2.6 Battery fault RF detector and repair
15.2.2.1.2.3 Food A menu option where the nutrition events are grouped and reported to the selected email account
15.2.2.1.2.3.1 Nutritional error and repair A menu option that reports power error, power failure recovery, battery error and battery error recovery events to the selected email account.

A menu option that sends a notification to the selected email account when too high a power collection is detected. A recovery report is also sent when the flood situation has been restored
15.2.2.1.2.3.2 Aux. Flooding and recovery
15.2.2.1.2.4 Communication A menu option where the communication events reported to the selected email account are grouped
15.2.2.1.2.4.1 Communication error A menu option that reports a communication error event to the selected email account.
A menu option that sends a test report to the selected email account at fixed times. Units can be set in days or hours
15.2.2.1.2.4.2 Automatic test reports
15.2.2.1.5.1 Programming and U/D A menu option that reports programming and up/download events to the selected email account.
15.2.2.1.2.5.2 Zone inactivity monitoring A menu option that sends a notification to the selected email account when an area inactivity event occurs
15.2.3 E-Mail Server A menu option where email server options are grouped.
15.2.3.1 Domain Name A menu option to configure the domain name of the e-mail server where reports are sent.
15.2.3.2 IP Address A menu option to configure the address of the selected mail server.
15.3 Customer numbers A menu option that groups options regarding the account code.
A menu option for configuring the SIA or Contact ID customer numbers to the different report recipients. SIA customer numbers consist of 6 digits. Contact ID customer numbers consist of 4 digits. These should be preceded by additional zeros. If you try to use both system customer numbers and area client numbers, the area customer numbers will take precedence.
15.3.1 System Client Numbers
A menu option that lists the customer number for each area. The customer number is sent when the relevant area is reported. There are two groups of customer numbers. First, a customer number is assigned to each report destination. In addition, a customer number is assigned to each area. If you try to use both customer numbers, the customer number for the area is priority.
15.3.2 Area of customer numbers
15.3.3 Recipient No. A menu option for configuring the number of the telephone line receiver associated with the recipient's account.
15.3.4 Line Number A menu option to configure the line number associated with the recipient's account.
15.4 Up/Download A menu option that contains options used to send download sessions between the up/download software and the power station.
15.4.1 Start U/D A menu option that can start an upload/download session between the module and PC from a control panel.
A menu option that allows an upload/download session between the module and PC to be started from a PC. The computer's ringing in on the module. You must choose the data phone number to call on the GSM for up/download. It is advisable to use this setting only in private networks with a firewall.
15.4.2 Allow U/D

A menu option that configures the module to automatically call the PC, so an upload/download session can be started after a car test. You need to program the auto test on central.
15.4.3 Auto U/D During Test Time
15.4.4 IP Address A menu option setting the address of the computer running upload/download software.
15.5 Domotica A menu option that groups automation options.
15.5.1 Activate Domotica A menu option that allows the system to be automatically controlled with the CS7050 TCP/IP module.
15.5.2 IP Address A menu option setting the address of the computer on which the automation software is run.
15.6 Event Recorder A menu option that groups the event registration options.
15.6.1 Transfer To Recorder This option is not used in Europe.
15.6.2 IP Address A menu option to configure the address of the selected event registration.
15.7.1 Reporting A menu option that groups TCP/IP reporting options.
A menu option for configuring the communication format to report to TCP/IP recipients. Please refer to the instructions of the alarm centre receiver to determine which format should be used.
15.7.1.1 Reporting Format
A menu option. This allows you to backup the plant for the CS7050. If the CS7050 fails to send a report, an expansion event is sent to the control center and the central station sends the report.
15.7.1.2 Central is Backup
15.7.1.3 Receiver 2 as Backup A menu option to configure the module for sending backup reports to the second TCP/IP receiver.
15.7.1.4 Recipient Polling A menu option for configuring the polling message sending module to report recipients.
A menu option for configuring the TCP/IP polling time. This value must correspond to the TCP/IP polling time set on the TCP/IP receiver. The value chosen depends on the desired level of security and the cost of data transfer. This time can be set from 1 to 255 seconds. If 0 is selected, the option will be disabled.
15.7.1.5 Polling Time
15.7.2 Network A menu option that groups network options.
A menu option for configuring the CS7050 to use a dynamically assigned IP address. If this option is selected, you need to configure a Polling Time. If this option is disabled, configure Own Email Address, Gateway IP Address and Subnet Mask.
15.7.2.1 Use DHCP
15.7.2.2 Own IP Address A menu option to configure the IP address assigned to the module.
A menu option to configure the IP address of the gateway used by the module. You need to disable the CS7050 module and turn it back on to initialize the new IP address.
15.7.2.3 Gateway IP Address

A menu option for configuring the subnet mask. Usually this is 255.255.255.0. Please contact the network administrator to confirm. All IP addresses up to and including the local gateway should be allowed. When using a cable modem/DSL, this mask is similar to the one used by the computer.
15.7.2.4 Subnet Mask
A menu option to configure the maximum total time that the CS7050 reports to each recipient. If the notification is not completed within this time, the attempt will be specified. This time can be set from 30 to 255 seconds.
15.7.2.5 Network Timeout
A menu option to configure the number of times that the module tries to send a report. This value can be set from 1 to 15.
15.7.2.6 Max Network Attempts
15.7.0.7 Port Numbers A menu option where options for the TCP/IP port are grouped.
A menu option that configures the number of the TCP/IP port to which polling and alarms are reported. The default value is 9999 and it does not need to be changed under normal circumstances.
15.8.2.7.1 TCP/IP Alert Gate
A port configuration menu option used for up/download. The default value is 9999 and it does not need to be changed under normal circumstances.
15.8.2.7.2 U/D Port
A menu option for configuring the port used by the mail server to send email. The default value is 0025, and it does not need to be changed under normal circumstances.
15.8.2.7.3 E-Mail Port
A menu option for configuring the port used for automation. The standard value is 0000 and does not need to be changed under normal circumstances.
15.8.2.7.4 Domotica Gate
15.8 Model A menu option that shows the current model of the selected module.
15.9 Version A menu option that shows the current software version of the selected module.
15.10 Default Settings A menu option that resets the selected module to factory settings.
Power supply 13.8 V ± 2%
Power consumption . . Stand by 90 mA
Power consumption - during communication 120 mA
Size PCB Dimensions (width x height x depth) 153x84x25 mm
Environment Ambient temperature +0° C to + 40 °C

16.1 Overview The CS7501 ISDN selector allows you to transmit digital data via a regular telephone line. The voter supports ISDN channels B and D.

J4
J1
D11
J5 D13
JP2/3
J1 ISDN connector for receiving incoming signal
J2/J3 Bi-directional connector for the power plant. Connects the audio circuits to the central and CS543 for up-/download and listening.
J4 1 DAT Connected to the DATA connection at the power station
2 COM Connected to the COM connection at the power station
3 POS Connected to the AUX+ connection at the power station
4 COM Power supply for the black battery wire.
5 PWR Power supply for the red battery wire
J5 ISDN Outbound Signal Connector
JP2/JP3 ISDN shutter-off resistors. The total impedance of the S0 bus must be 50 Ohm. The 2 jumpers JP2/ 3 may all be placed if the "priority relay" is used and you do not have EOL resistors on any device other than the CS7501.
D11 Green LED ISDN communication status.
Objective

D13 Red LED Central communication status.
The CS7501 ISDN connection is in use
Fast flashing The CS7501 is located between two calls or tries other destinations
From The CS7501 has no connection to the power station
The CS7501 is in the process of connecting to the reporting bank or reporting events to the reporter.
Fast flashing The CS7501 has had a connection to the power station
Flashing The CS7501 is waiting for the next report
Red LED From The CS7501 does not communicate with the central
Flashing The CS7501 communicates with the central







Cables: Brown - Blue - Orange - Green.








E
B



F

D



16.2.3 Connecting the battery wires The battery wires shall be connected to the panel battery as follows:
For more information about installing the CS7501 TCP/IP module in different enclosures, see chapter A-4 Install a base system.

Phone numbers Reporting Phone number (1) 16.1 16.1.1 16.1.1.1 Telephone number Customer number Protocol
16.1.1.1.1 16.1.1.1.2
Phone Numbers 2-4 As above
16.1.1.1.3
16.1.1.1.4
16.1.1.1.4.1
16.1.1.1.4.2
16.1.1.1.5
Events Alarm Alarm Recovery In/Disable Zone in/out bridge
16.1.1.1.5.1
16.1.1.1.5.1.1 16.1.1.1.5.1.2
16.1.1.1.5.1.3 16.1.1.1.5.1.4
16.1.1.1.5.2
Sabotage and malfunction Sabotation and recovery Zone failure and repair Storm module and repair Sirene/tel.line error and repair Miss RF detector and repair Battery fault RF Detector and repair
16.1.1.1.5.2.1
16.1.1.1.5.2.2
16.1.1.1.5.2.3 16.1.1.1.5.2.4 16.1.1.1.5.2.5
16.1.1.1.5.2.6
16.1.1.1.5.3
Nutrition Nutritional error and repair Aux. Flooding and recovery
16.1.1.1.5.3.1
16.1.1.1.5.3.2
Communication Communication error Automatic test reports
16.1.1.1.5.4
16.1.1.1.5.4.1
16.1.1.1.5.4.2
16.1.1.1.5.5
Other Programming and U/D Zone Inactivity Monitoring
16.1.1.1.5.5.1 16.1.1.1.5.5.2
.
16.1.2.1 16.1.2.2 16.1.2.3
Selections PAC.
Version 4 and above
Break-in & Failure Telim channel
Disable system Enabled system
16.1.3.1
Version 4 and above
16.1.3.2
Preference Reporting Preference Type Chooser Settings*
*Version 4 and above
16.2 16.2.1 16.2.2
Up/Download Phone No. U/D As Enabled Delay Time
Configuration MSN Number Polling D-channel TEI Value D- channel X.25 LCGN D-canal X.25LCN D-kanal
16.3 16.3.1
16.3.1.1
16.3.1.2
16.3.1.3 16.3.1.4
16.3.1.5
16.3.1.6
16.3.2.1
CS534 Comm.mod Delay time
16.3.2.2
16.3.3.1
CS534 Comm.mod
16.3.3.1.1
16.3.3.1.2
16.3.3.2
16.3.3.2.1
16.3.3.2.2
Model Version Default Settings
Before you can program the CS7501 ISDN voter, you need to register and bring the module to default settings. More information on registration and bringing to default settings can be found in chapter B-1 Registering modules. To program the CS7501 select CS7501 ISDN Chooser.
16.3.1 Configuring Phone Reporting The CS7501 ISDN voter can report to up to four telephone numbers. You can set which events to report, what format should be used and which connection parameters apply. In the following example, alarm events that occur are reported to telephone number 8888999, customer number 445566 in SIA format.

16.3.2 Configuring an ISDN connection with AL2 supervision If you are using an ISDN connection with AL2 oversight, you must also set up the D-channel polling and D- channel Terminal Equipment Identifier (TEI), as well as the telephone number, customer number and events. In the following example, alarm events are reported to telephone number 02048888999, customer number 55555 and through Alphacom X25 D channel protocol.
" By default, all events are activated for the voter.
16.3.3 Uploading and downloading There are two methods for up- and download, call back and start U/D with code.
When using the CS534, ISDN makes voters different between both methods.

16.3.3.1 Time synchronization The CS7501 automatically corrects the date and time on the power station if the difference between the central and ISDN network exceeds 5 minutes. This is done with every communication to the B channel.
16.3.3.2 Callback The control panel is set up to call the reporting bank back to start an up/download session. When the reporting bank calls the central authority, the central operator answers the call and then hangs up. A little later, the CS7501 returns the callback.
Before using the CS7501 ISDN voter for callback, you need to configure both the Cs7501 and the central. In the next example set for a four-second pause before answering the call. The up/download session does not start until after the callback.
16.3.3.3 Starting U/D with code The user starts up/downloading by selecting an option from the User menu.

16 CS7501 ISDN Chooser Module acting as ISDN communication module for reporting and up/download.
16.1 Reporting A menu option that groups ISDN reporting options.
16.1.1 Telephone numbers A menu option that groups reporting options from phone numbers.
16.1.1.1.1 Telephone No. A menu option to set the phone number where events should be reported. The operator may report to up to six telephone numbers.
16.1.1.1.2 Customer number A menu option specifying a unique code sent by the voter on the central or electoral system to the selected telephone number. This code is used to identify and invoice the user. Different customer numbers can be set for each phone number and area. This is also called the account number.
16.1.1.1.3 Protocol A menu option to configure the communication format used for notification to the selected phone number. Please refer to the instructions of the alarm centre receiver to determine which format should be used.
16.1.1.1.4 Selecter Settings A menu option bringing together the options to set the order in which the backup ISDN phone numbers should be selected.
16.1.1.1.4.1. A menu option that determines the number of attempts to connect between module and control before trying another destination.
16..1.1.4.2 Choose Order A menu option that determines the order in which the configured phone numbers are selected.
16.1.1.1.5 Events A menu option that contains all configurable events for the different phone numbers.
16.1.1.1.5.1 Alarm and in/out A menu option where events are grouped to the selected phone number.
16.1.1.1.5.1.1 Alarm A menu option that sends a message to the selected phone number when an alarm situation occurs.
16.1.1.1.5.1.2 Alarm recovery A menu option that sends a notification to the reporting bank when the alarm is restored after an alarm.
16.1.1.1.5.1.3 To/To disable A menu option that sends a message to the selected phone number indicating when the system is disabled and enabled
16.1.1.1.5.1.4 Zone in/out of bridge A menu option that sends a message to the selected phone number when a zone is covered. A notification is also sent when the zone is restored (override terminated)
16.1.1.1.5.2 Sabotage and malfunction A menu option where the sabotage and malfunction events are grouped that are reported to the selected phone number
16.1.1.1.5.2.1 Sabotage and recovery A menu option that sends a message to the selected phone number when a sabotage takes place. A recovery notification is also sent when sabotage is no longer active
16.1.1.1.5.2.2 Zone malfunction and recovery A menu option that sends a report to the selected phone number when a zone failure occurs. A report is also sent when the malfunction is no longer active

16.1.1.1.5.2.3 Malfunction module and recovery A menu option that sends 'progress module and recovery' notifications to the selected phone number.
16.1.1.1.5.2.4 Sirene/tel.line error and repair A menu option that sends a message to the selected phone number when a siren or telephone line error occurs. A recovery message is sent when the error has been repaired.
16.1.1.1.5.2.5 Missing RF detector and recovery A menu option that sends a message to the selected phone number when an RF detector is missing. A recovery report is sent to the reporting bank when the recipient receives a valid signal from the missing transmitter
16.1.1.1.5.2.6 Battery fault RF detector and repair A menu option that sends a report to the selected phone number when battery error occurs in an RF detector. A recovery report is also sent when the battery error is no longer active.
16.1.1.1.5.3 Nutrition A menu option that groups the nutrition events reported to the selected phone number
16.1.1.1.5.3.1 Nutritional error and repair A menu option that reports power error, power failure recovery, battery error and battery error recovery events to the selected phone number
16.1.1.1.5.3.2 Aux. Flooding and recovery A menu option that sends a message to the selected phone number when too high a power take is detected. A recovery report is also sent when the flood situation has been restored
16.1.1.1.5.4 Communication A menu option where the communication events reported to the selected telephone number are grouped
16.1.1.1.5.4.1 Communication error A menu option that reports a communication error event to the selected phone number
16.1.1.1.5.4.2 Automatic test reports A menu option that sends a test report to the selected telephone number at fixed times. Units can be set in days or hours
16.1.1.1.5.5.1 Programming and U/D A menu option that reports programming and up/download events to the selected phone number
16.1.1.1.5.5.2 Zone inactivity monitoring A menu option that sends a notification to the selected phone number when an inactivity event occurs
16.1.2 A menu option where options for choosing are grouped.
16.1.2.1 Selections PAC A menu option that determines the number of attempts (1 to 15 attempts) which the voter performs when reporting to the selected phone number.
16.1.2.1 Selections FTC A menu option that specifies the number of dialing attempts which the GSM module executes to a specific phone number before reporting a communication error.
16.1.2.3 Voice/ pager/ siren A menu option that determines the number of dialing attempts (1 to 15) performed by the voter if voice, pager or siren protocol is selected.
16.1.3 Breaking and breach of Telim channel A menu option that allows you to determine which TELIM channels are used for intrusion and malfunction reports.
16.1.3.1 Disabled System A menu option that determines which TELIM channel is used to pass intrusion and malfunction alams when the system is disabled.
16.1.3.2 Enabled system A menu option that determines which TELIM channel is used to transmit intrusion and malfunction alams at the time of system activation.

16.1.4 Preference Reporting A menu option that activates priority reporting.
16.1.5 Preferred Type A menu option to configure the preferred type used for preferably reporting. If this option is set to Free B Channel Control, the voter disconnects from transmitting an alarm message by trying to clear the B channel. If the channel cannot be cleared, the S0 bus will close. If this option is set to S0 bus chip. (2nd attempt), breaks the voter's connections for passing an alarm message by shutting down the S0 bus.
6.1.6 Selecter Settings A menu option that configures the GSM backup control in SIA or CID or which configureS ISDN as a backup for GSM. .
16.2 Up/Download A menu option that contains options used to send download sessions between the up/download software and the power station.
16.2.1 Telephone No. A menu option to set the phone number where events should be reported. The operator may report to up to six telephone numbers.
16.2.2 U/D As enabled Menu option to allow an upload/download session between the module and computer at the initiative of the computer when the system is enabled.
16.2.3 Delay time A menu option to set the number of seconds that should expire before the panel starts an upload/download session.
16.3.1 ISDN A menu option where ISDN connection settings are grouped.
16.3.1.1 Protocol A menu option that specifies the type of ISDN connection. You can choose from Point-to-Point and Point-To-Multipoint.
16.3.1.2 MSN Number Multiple Subscriber Number. You can have multiple phone numbers on a single ISDN connection. MSN is only used for Point-to-Multipoint connections. If you can connect to multiple modules on the same ISDN connection, the MSN number is assigned only to one module. When you call this number, only the module to which the number is assigned will be included. This module number is configured using a menu option.
16.3.1.3 Polling D channel A menu option for configuring the D-channel polling.
16.3.1.4 TEI Value D channel A menu option for configuring the TEI for the D channel.
16.3.1.5 X.25 LCGN D channel A menu option for configuring X.25 LCGN for the D channel. X.25 LCGN is a logical channel group number. Get this number from the network provider. This could be a number from 0 to 255. The default value is 0.
16.3.1.6 X.25 LCN D channel A menu option for configuring X.25 LCN for the D channel. X.25 LCN is a logical channel number. Get this number from the network provider. This could be a number from 1 to 255. The default value is 0.
16.3.2 Listening to the report A menu option that groups options for listening. To use the listening function, a CS534 communication module must be installed and a microphone connected. When an alarm is activated and reported, the reporting bank can monitor what happens on site. Certain protocols (such as SIA, XSIA Contact ID and 200Bd FSK) include . . listening blocks . that are sent along with the alarm code and indicate that a listen-in session should be started.
16.3.2.1 CS534 Comm.mod A menu option for enabling listening to the CS534 Communication Module.

16.3.2.2 Delay time A menu option to set the number of seconds that should expire before the panel starts a listening session.
16.3.3 Setting volume A menu option that includes options to adjust the sound level with the CS534 communication module.
16.3.3.1 CS534 Comm.mod A menu option for configuring the volume of incoming and outgoing communication with the CS534 Communication Module.
16.3.3.2 Up/Download A menu option for configuring the volume of incoming and outgoing communications during an up/download session.
16.4 Model A menu option that shows the current model of the selected module.
16.5 Version A menu option that shows the current software version of the selected module.
16.6 Default Settings A menu option that resets the selected module to factory settings.
Power voltage 12V ± 2%
Power consumption . . Stand by 30 mA at 12V ± 2%
Power consumption . .
Size PCB Dimensions (width x height x depth) 150x80x24 mm
Environment Ambient temperature +0° C to + 49 °C

Alarm memory Reset fire detector Service required Manual test Logbook X-10 Modules Advanced Menu Zone Status Module/location programming
17.7 17.6 17.5
The logbook shall contain the details of all events that have occurred in the system. The logbook shall record a maximum of 512 events.
If you want to read the log, proceed as follows:
Alert 3 Pressure F3 Alarm 3 128 17:32 > 25/9 028
In this case, an alarm has been triggered in zone 128 in area 3 at 17:32. No notification was sent to the reporting bank. The event took place on 25 September. This is the twenty-eightth event in the log.
L1 EventType PN Partition
L2 Zone/User Name UN/ZN HH:MM DD/MM LOG
EventType The type of event that has occurred.
PN The number of the area in which the event took place.
PartitionName The name of the area in which the event took place.
Zone/User Name The name of the zone or user.
UN/ZN The user's number, zone or module.
HH:MM The time (HU:MM) when the event occurred.
DD/MM The day and month of the event.
LOG The position of the event in the log.
Description

Alert An alarm has been activated
Recovery alarm See Alert event message.
Automatic test report The reporting code . . automatic test report . was sent to the reporting bank.
B-alarm A full alarm on a B-zone type that is considered as a burglar alarm.
Sabotage enclosure A sabotage housing.
See Closet sabotage event message.
Breaking and entering. There's been a breach zone activated.
Recovery of burglary See Breaking and entering event message.
Overriding a zone.
See Bridging event message.
Cancel Reporting to the reporting bank was cancelled. This happens when a user enters a code after an alarm.
CleanMe A smoke detector is dirty.
CleanMe Recovery See CleanMe event message.
Clock set A user has set date and time.
Engagement Involvement by a specific user.
Code entry The exit of the access card reader was activated. The output can be activated by an accepted proximity card or by an exit request printer. An output request pusher is a button that can be pressed by a user to open the door's electrical lock. Also called "RTE . . Request-to-Exit." When the Enter code option is activated, the card reader sends a log message to the control panel to indicate that the output was activated.
Data loss The control panel failed to send alarm notifications to the reporting bank. The control panel tries to send these notifications several times, according to the specified values in the FTC (choosing for communication error). The alarm messages to be sent are lost.
- Drop the dice. after alarm A user has disabled the power station during an alarm situation.
A coercive code has been entered by a user. An alarm message is being sent to the reporting bank.
Too early A user disabled the system before opening time specified in timetables.
End Up/Download The end of an up/download.
End programming exiting Programming. The installer has left the programming mode.
End of run test See Running test event message.
Registered Modules are registered on the bus. The module numbers are stored.
Outrun error An entry/outrun zone has remained open after the exit time has expired.
Module failure There is a problem with an expansion module.
Repair module malfunction See Module failure event message.

Module event A bus module has generated an event for reporting circumstances that are not described by other events.
Communication error The central or module tried to send a notification to a reporting bank, but it failed.
Fire A fire alarm has been activated
Fire repair See Fire event message.
First shutdown The time when the first area is disabled.
Sabotage Handle A sabotage of the handler.
Last activation The time when the last area is enabled.
Late enabled A user switched on the system after closing time specified in the calendar templates.
Listen to the start of a listening session.
Log full The log is full and the events must be downloaded to the up/download software. The log is full can also be sent to the reporting bank.
Battery error recovery See Battery error event message.
Battery error The standby battery for the central/module is weak.
Fixing power supply failure See Power voltage error event message.
Power supply failure The 220 V power voltage has gone.
A manual fire alarm has been given using the keys 1 and 3 On the handstand.
Manual test A manual test has been performed to the reporting bench.
Medical A medical alarm has been given using the keys 4 and 6 On the handstand.
Disabled Shut-off by a specific user
Exit An exit has been activated or restored. The source number is recorded. This is linked to the output module number.
Recovery output See Exit event message.
Exit activation An exit has been activated.
Overflow An excessive amount of electricity has been extracted from one of the outputs.
Overflow recovery See Flood event message.
PA Robbery alert A robbery alarm has been activated.
Panic Handle A panic alarm has been given using the keys 7 and 9 On the handstand.
Partially Enable See Enable partially event message.
Partially in Part-Involvement of the system by a specific user.
Recent activation An alarm has occurred within the first five minutes after the power station is switched on.
Re-exit A special option to prevent false alarms.
Recovery A user has manually reset a smoke detector.
Recovery jam detection See Jam detection event message.
Jam detection Jam sensing
Event Message Statement · Manual fire notification

RF Battery error An RF detector reported a battery failure.
Repair RF battery error See RF Battery error event message.
End of service End of . . Installer on site . (service mode).
Start service Start of . .Installer on site .
Robbery silent A silent robbery alarm.
Siren sabotage sabotage of a siren.
Restore siren sabotage See Sirene sabotage event message.
Start up/download The beginning of an up/ download.
Start programming Beginning of programming. The installer went into the programming mode.
Sabotage sabotage.
Restoration sabotage See Sabotage event message.
Fix Phone Line Error See Phone Line Error event message.
Interrupt A fault condition.
Repair fault See Malfunction event message.
Running test The start/end of a running test.
Recovery zone inactivity See Zone inactivity event message.
Zone inactivity A message that there has been no activity on a zone for a certain time.
RF Detector absent An RF detector has lost supervision with the wireless receiver. This is done when the transmitter has not sent its supervision message to the RF receiver within the long time of supervision. See Appendix 5.
Restore RF detector absent
See Zone absent event message.
This is a security facility. This event occurs when someone tries to break into the system.
17 Functions A menu option that groups options related to the delivery of controls by the installer.
17.1 Alarm memory A menu option that shows a list of alarm messages, including the location where they occurred. Only the alarms that occurred during the last on/off cycle are displayed in the alarm memory log.
17.2 Reset fire detector A menu command that reset the two- and four-wire smoke detectors and the Fire LED. For fixed wired smoke detectors, the power supply to the smoke detectors is temporarily interrupted. RF smoke detectors are equipped with an automatic reset because the RF communication is only in one direction (from RF detector to RF receiver). This command does not reset the RF smoke detectors, but must be used to reset Fire LED.
Event Message Statement · Phone line error Telephone line error · 10 failed download attempts

17.3 Service required A menu command used to check service messages. The service message disappears when the installer goes into the programming mode and then goes out. If Recovery sabotage is enabled with main code, a main user can reset the service message by entering a main code.
17.4 Manual test A menu command that performs the LED and LCD control of the handheld and manual tests activated in Diagnosis. The siren is activated during the test as the menu option Manual siren is on. Similarly, a manual testop call to the report bank is made as the menu option Manual voter test is on.
17.5 Log A menu command used to view the log. The log is a list of events occurring in the system, whether it is switched on or off. These are kept in a sequential event list with a time and date stamp. When the log is full, the oldest events are overwritten with new data. These events can be viewed later by uploading them.
17.6 X-10 Modules A menu option that provides an overview of the X-10 modules which can be switched ON/OFF.
17.7 Advanced menu A menu option that activates certain options in the Installer Menu structure.
17.8 Zone Status A menu option that indicates the status of the zone.
17.9 Module/Location programming A menu command that switches to the alternative programming mode (address programming mode). This method works with modules, locations and segments. In this mode: Use the OK/Menu button instead of the * key. Use the F2 key instead of the Away button. It is recommended to use the menu structure instead of modules and locations.

18.1 Other programming methods You can program the system using either the CS5500 control panel or UDx75 software. With this software you can upload the programming data from the central to the computer on which the UDx75 software runs, then change that data and download the changes again from the computer to the mainframe. It is also possible to view the program and event log. If you want to program the system with this software, you need to connect the power station to your computer.
18.2 Connecting the power plant to the computer You can connect the power station directly to your computer via RS232 serial port or remotely through a modem connection.
18.2.1 Connecting via serial port Connecting via a serial port is useful when you are on site and want to make a direct connection with the alarm system.
The connection to the CS275, CS375, CS575 or CS875 is done via the RS232 port by using the CC590 programming cable. The CS175 is not equipped with a RS232 port. The connection of the CS175 is done via the Cs586 module, which has a standard RS232 bidirectional DB-9 connector. The CS586 can be used as a programming module for each power station, provided it is connected to the data bus. The CS586 stores the settings of the control unit, which you can upload/download with your handheld or computer. More information on reading data from the CS586 can be found in chapter B-8 Set the CS586.
Use of the UDx75 software with a direct connection:
< The default operator name is Aritech and the default password is 1278. You may need to enter this twice depending on the settings of the software.
18.2.2 Connecting via a modem You can connect the remote control to the computer via a modem. This may be useful if you are not on site and still want to connect with the alarm system.
You can establish the connection in the normal way or with Ignore Answering Device (AMD). If you are using AMD, the 'automatic time-controlled 2 calls ignore answering machine order' is used.
Using the UDx75 software with a modem connection:

18.3 Programming with up/download software You can download the existing programming data or log from your control center. Uploading allows you to send your set programming data from the computer to the power station, using UDx75 software. If the system is programmed with UDx75, the control panel can be reset after the system has been disabled. This prevents text from being lost.
Before downloading or uploading data, you must first do the following:
The data downloaded and the download speed depend on the settings for Send All/ Read All. The default number of strings sent to the handheld is 192, but it is possible to limit the amount of string sent. If the default number is reduced, download time decreases. For more information on setting up/download options, please see the UDx75 Online Help.
Serial gate 9600 Baud
Domotics Control >Automation Transition Make sure all options Off Stand up. This is the default status.
Domotics control >Stations/Retrieval Make sure all options ToStand up. This is the default status.
Control menu option Value · Connection type Domotics control · Domotics Control > Protocol Binair

18.3.1 Programming tasks You can perform all the available programming tasks using UDx75 software. Table 18-2: UDx75 Menupades shows the UDx75 menu order for each task.
Adding Operators Program > Settings >:Add/Change Operators
Backup database Tools >Backup database
Change a customer record Display > Customers >: Separate client
Change a Master or Operator Password Program >Change Password
Change operator rights Program > Settings >: Add/change operators
Program additional phone settings Display > Centrale (Telephone Additional Settings tab)
Programming the reporting codes Advanced >4+2 Codes
Change the download options Program > Settings >: Download options
Program the areas View >Central (Zona tab)
Programming reporting settings Display > Centrale (Phone Numbers tab)
Program the system 1 settings View > Central (System 1) tab
Program the system 2 settings Display > Central (System 2)
Program system 3 settings Display > Central (System 3) tab
Change the UDx75 settings Program >Settings >:Setting program
Program user's switch-on/off codes
Compressing the database Tools >Comppress database
Connect via modem Download >Connect >:Connell or Download> Connect >
Connect via serial port Download >Connect >:Connell through RS232
Copying a customer's central settings Program > Settings >: Copy functions
Delete a customer record Display >Customers >: Separate Customer
Clear the log Download >Logbook >:Clear log
Download and update the module list Download > List modules> Register modules
Download the log Download >Logbook>Read full log
Export a database Tools > Export database
Import a database Tools >Import database
Loading defaults Advanced > Default settings
Print a list of customer records Program >Print preview>Customer list
Print the program log Program >Print preview>Logbook program

Print a programming sheet Program >Print preview>Programme worksheet
Print a list of operators Program >Print preview>Operation List
Print the log Program >Print preview>Logbook
The CS-1700 programming Modules >CS1700>1
The CS208/CS216 programming Display >Central (Zones tab)
The CS-320 programming Modules >CS320>1
The CS-507 programming Modules >CS507>1
The CS534 programming Modules >CS534
Programming the CS535 Modules >CS535
Programming the handheld messages/zone names
Programming the operators Modules >Control Options <Display 1 >:Control 1
Program the wireless RF receivers Modules >wireless>1
Programming zones Display > Centrale (Zones tab)
Restore the database Tools >Repair Database
Reset the database Tools >Reset database
Find and view a customer record Display >Customers >:Special Customer
Diagnosis Tools >Diagnosis
Automatic Callback Options Settings >Call back
Configure the country and language Program >Settings>Country/Language
Configure the Download Access Advanced >Download Options
Special protocols programming Advanced >Special protocols
Programmable outputs Advanced >Programmable exits
Configure the TCP/IP settings Program > Settings >:TCP/IP Settings
Programming Time Functions Advanced >Time Functions
Programming zone type Advanced >Zone types
Set a customer record Display > Customers >: Separate client
Configure the modem Program >Settings >: Modem Settings
Ignore replyer settings Program > Settings >: AMD settings
Program direct connection settings
Program serial port settings Advanced >Serial port setting
Switch operator Program >Next Operator

Remove the software Start >Settings>Control Panel
View a list of customer records Display > Customers >: List
View a list of operators Program >Settings>Add/Change Operators
View the errors of auto-answering
Customers > Errors when replying automatically
View the central settings Display > Central
View the log Download >Logbook >:Read full log
View the status of the handheld Display >Status code control
Task UDx75 menu option · Upload Download > Read all

Reference
1 Annexes C-1-1

1.1 Annex 1: Reporting of fixed codes in Contact ID or SIA Table 1-1: Event codes Provides an overview of the reporting codes sent for different notifications (if activated) when using Contact ID and SIA formats. The zone, user or module number in brackets is the number reported as a number behind the reporting code. If there are no brackets, the zone is 0. An asterisk represents the first sign of the event code of the zone that has been bridged or disturbed.
Report To= Contact ID
Report To= Contact ID
SIA
Manual test 601 RX Sabotage code control part 137 TA
Automatic test report 602 RP Panic function robbery (sound) 120 PA
Disable (user number) 401 OP Panic function robbery (silent) 121 HA
Enablement (user number) 401 CL Force code 121 HA
Cancellation (user number) 406 OC Panic function 1 110 FA
Start local programming 627 LB Panic function 2 100 MA
End local programming 628 LX RF detector absent (zone number) 381 *T
401 CR RF detector repair (zone number) 381 *R
Outrun error (user number) 457 EE Battery fault RF detector (zone number) 384 XT
Log is full 605 JL Battery error RF detector recovery (zone number)
RT RT RT restriction of competition (0811)
Module failure (module number) 333 ET Zone failure and recovery (zone number) 380 *R
Module repair (module number) 333 ER Zone sabotage (zone number) 137 TA
Phone line error 351 LT Zone sabotage (zone number) 137 TR
Telephone line repair 351 LR Zone bridging (zone number) 570 *B
Sirene sabotage (module number) 321 YA Zone bridging recovery (zone number) 570 *U
Sirene Recovery (module number) 321 YH Near alert (A/B Alarm) 138 BM
Aux. power error (module number) 312 YP disabled too early/ turned on late
Aux. power error repair (module number)
312 YQ Partially Enable 456 CF
Battery error (module number) 309 YT Zone activity error 391 NA
Battery Error Recovery (module number) 309 YR Zone Activity Recovery 391 NS
Power voltage error (module number) 301 AT Switch-on error 454 CI
Power voltage recovery (module number) 301 AR RF Jam detection 344 XQ
Sabotage enclosure (module number) 137 TA RF Jam detection recovery 344 XH
Sabotage enclosure recovery (module number)
137 TR Fire detectorCleanMe 393 YX
CS875-575-375-275-175 Installation Manual with CS5500 control panel C.1.1
On= · On= · Recent activation (user number)

1.2 Annex 2: Overview of module numbers Each control, extension module and wireless reception module have a module number.
CS535 77
CS7002 78
CS7050 79
CS7501 76
1.2.1 CS1700 card reading module
Reading order Module number Reading sequence Module number
1 113 9 121
2 114 10 122
3 115 11 123
4 116 12 124
5 117 13 125
6 118 14 126
7 119 15 127
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8
1 192 193 194 195 196 197 198 199
2 200 201 202 203 204 205 206 207
3 208 209 210 211 212 213 214 215
4 216 217 218 219 220 221 222 223
5 224 225 226 227 228 229 230 231
6 232 233 234 235 236 237 238 239
7 240 241 242 243 244 245 246 247
8 248 249 250 251 252 253 254 255
CS875-575-375-275-175 Installation Manual with CS5500 control panel C.1.2
Module number · CSx75 0 · Code-operated operators

1.3 Annex 3: Communication protocols Different communication protocols can be used for the transmission to a control room. Please consult the dispatcher to determine which protocol is compatible with their emergency banks. Table 1-4: Communication Protocols gives an overview of the possible programming.
# Description Protocol # Description protocol
1 To= Contact ID 12 Sirene tone
2 On= SIA 13 In/ Disable
3 SIA with area modifiers 14 In/ Disable
4 Speech with handshake and DTMF kiss-off 15 Special protocol (program your own protocol)
5 To/ Disable 16 To/Disable
6 4+2 with 1400/1900 double round parity 17 200 Baud FSK (France only)
7 4+2 with 1400/1900 checksum parity 18 200 Baud FSK Conversely (in France only)
8 4+2 with 2300/1800 double round parity 19 XSIA
9 4+2 with 2300/1800 checksum parity 20 XSIA with area modifier
10 Fast format 8 channels 21- 255 In/ Disable
11 Fast format 16 channels
< If you need a protocol that is not in this list, you should set the special options in Communication >Special Protocol to configure the desired protocol. Then select Special protocol in Communication > Reporter >: Telephone numbers >.Phone number n>Protocol.
< 2. The voice protocol does not generate a communication error (FTC .
1.4 Annex 4: Service messages The control panel displays service messages following manual and automatic system tests of the power plant. Table 1-5: Service messages provides an overview of the different messages and indicates what you need to do to solve the problem. When the handheld shows a beep due to an error condition, you can click on the key # print to display information about the error condition.
The control panel housing counter is not closed.
Check that the housing is correctly mounted on a flat surface and not damaged. If there is no damage, check that the housing is properly closed.
The dispatcher tried to send a report to the reporting bank, but it failed.
Check that the phone line is properly connected. Check using a test phone to see if the telephone network works. Check that the telephone number of the reporter and customer and protocol options are correct.
The power supply of the plant has been completely non-voltage and the clock must be reset.
Set the system clock and date of delivery.
The standby battery for the power plant is weak. The battery may need to be replaced. This may also be a temporary condition due to a long power failure.
CS875-575-375-275-175 Installation Manual with CS5500 control panel C.1.3

The power plant has observed an excessive flow through one of the outputs and has prevented this exit from being switched off.
Check the system for wiring errors. An overflow message can only be reset by correctly activating the siren, for example, by triggering a sabotage on an area that activates the sirens. This is a safety function to check that the flood message has disappeared and sirens can work properly again.
The phone line connected to the power station is not working properly.
Check that the phone line is properly connected. Use a test phone to check the operation of the telephone line.
The mains voltage is not present on the power plant. Check why the mains voltage is not present at the power station and check the power supply fuse in the plant.
The connection between the siren and the power station is broken.
Check the wiring to the siren and restore the interrupted loop.
Module Aux comm. error
A communication module tried to send a message to the reporter, but it failed.
Check that the phone line is properly connected. Check using a test phone to see if the telephone network works. Check that the telephone number of the reporter and customer and protocol options are correct. Check that the module is connected and working.
The enclosure offset switch of a module is not closed.
Check that the housing is not damaged and correctly mounted on a flat surface. If there is no damage, check that the housing is properly closed.
The module battery is not connected or insecure.
The battery may need to be replaced. This may also be a temporary condition due to a long power failure.
The expansion module has observed an excessive flow loss via one of the outputs and has prevented this exit from being switched off.
Check the module for wiring errors.
The power supply is not present on the power supply of an expansion module.
Check why the mains voltage is not present. Check the mains voltage fuse of the module.
The connection to the siren of an expansion module has been disconnected.
Check the wiring to the siren and restore the interrupted loop.
An expansion module or control panel no longer communicates with the power plant.
Check that the module is correctly connected to the power station.
There's been a malfunction in an area. Check the cabling and detector for damage and repair any malfunctions.
Zone problem Press OK
There's a problem with one or more zones. Press OK to identify the zone (s) and problem situations. One of the following messages will appear when you click OK Press.
CleanMe A smoke detector (e.g. DP721) is dirty. The central detects a certain amount of contamination in the smoke detector's optical room.
Clean the fire alarm's optical smoke chamber.
CS875-575-375-275-175 Installation Manual with CS5500 control panel C.1.4

Away The system has not received any supervision signals from the RF detector for a long time. Depending on how the system is programmed, this will be forwarded to the control room. In addition, a sabotage alarm may also be activated if enabled.
Check that the wireless zone module is in order and that the module has not been sabotaged. Recover any malfunctions.
Battery error The wireless transmitter's battery is running low.
Replace the battery.
RF short absence The system has recently received no more supervision signals from an RF detector. This situation is hampering the deployment.
Check that the wireless zone module is in order and that the module has not been sabotaged. Recover any malfunctions.
Malfunction There's been a malfunction in an area.
Check the cabling and detector for damage and repair any malfunctions.
Set the LCD contrast .
Answer an up/download call ♪
Enable and disable the system. 9* . . 9* If authorization permits it.
Crossing a zone 9* 9*9* if authorization permits.
Configure domotic controls . .
Performing domotics controls • ♪
Reset service messages . . 9* If enabled for main users
Start an up/download call. . . 9* If allowed for use without code.
Perform a system test • ♪
Perform a service check ♪ ♪ Oh, my God ♪
Perform a run test .
Programming voice telephone numbers . .
Reset smoke detectors • •
Set system date and time .
Set user authority level . .
CS875-575-375-275-175 Installation Manual with CS5500 control panel C.1.5

Set up user codes . . 9* Custom code only All master user codes.
Switch to multiple areas view
Watch the alarm memory ♪ ♪ Oh, my God ♪
View the log . .
Alarm Delay Outside House Microwave Room Smoke On
Area Den Brand Infrared Movement Playroom Sound Utility
Audio Detector for Immediately North Safe South Safe
Back Eat Game Internal Sick Detector Trap Warehouse
Bathroom Door Garage Rommel Bureel Shock Storage West
Ray Under Glass Breaker Kitchen Panic keys Shop Study Window
Bedroom Force Code Guest Library Storage Side Sabotage Wing
Key East Hall Light Telephone Skylight Television Wireless
Ceiling Emergency Hot Living PIR Sliding Disturbation Garden
Enclosure Shutdown Robbery Head of Portic Small TV Zone