SI 5TE SI 7TE SI 9TE SI 11TE SI 14TE SI 17 TE SI 21TE






1 Read directly please
1.1 Key clues
The construction and execution of the heat pump comply with all corresponding EC directives (see CE conformity assessment).
The electrical connection of the heat pump must comply with the corresponding EN and IEC standards as well as national guidelines. In addition, the connection conditions of energy supply companies must be respected.
The heat pump shall be integrated in the heating and source system according to the relevant requirements.
Persons, especially children, who are unable to use the device on a safe mother or her because of their physical, sensory or mental skills or due to lack of knowledge or experience, may not use it without supervision or instruction by an responsible person.
Don't let children go unsupervised to make sure they don't play with the plane.
By using this heat pump you contribute to the stool of our environment. For efficient operation, careful dimensioning of the heating system and its heat source is very important. The main focus should be on the lowest possible departure temperature of water. Therefore, all connected energy users should be suitable for a low departure temperature. A 1 K hot water temperature increases energy consumption by approx. 2.5%. Low temperature heating with moving temperatures between 30 °C and 50 °C is perfectly suitable for energy saving.

3 Basic device
The basic unit consists of a ready-to-use heat pump for installation inside with a steel plate housing, switching device and integrated controller. In the cooling cycle, the coolant R407C is done. The coolant R407C is CFC free, does not break down ozone and is non-inflammable.
The ground water heat pump can be used in existing or newly installed heating installations. The heat carrier in the thermal source system is glycol water. The heat source may be used as ground heat exchangers, earth collectors or similar installations.
All the components necessary for operation of the heat pump are attached to the control panel. A sensor for the external wall temperature with mounting material as well as a filter are supplied with the heat pump. The ballast and steering currents must be installed on site.
The power supply of the glycol water pump to be applied on site shall be connected to the control panel. If required, it shall be fitted with an engine contactor.
The earth stores the warmth of the sun, wind and rain. This geothermal heat is in the earth collector, the ground heat wiper and similar. low temperature glycol water. A circulating pump then transports the .heated .glycol water to the vaporizer of the heat pump. This heat is transferred to the coolant in the cooling cycle. The glycol water cools off again so that it can absorb heat energy in the glycolwa-t cycle.
The collector with the glycol water distributor shall be fitted on site.
The coolant is sucked in by the electrically driven compressor, compressed and pumped to a higher temperature level . The electrical power input in this process is not lost, but is largely transferred to the coolant.

Then the coolant enters the condenser and here again transfers its heat energy to the heating water. Depending on the operating point, heating water is thus heated to 60 °C.
·

6 Placement
4.1 Glycol water distributor
6.1 General instructions
The glycol water distributor unites the collector loops of the heat source system into one main line, which is connected to the heat pump. The integrated ball-cars can be used to close separate glycol water circuits.
The apparatus shall be placed only in dry interior areas on an ef-, smooth and horizontal surface. The frame must be close to the ground in order to ensure a suitable sound insulation. If not, additional noise-reducing measures may be necessary.

The heat pump must be designed so that service can be performed without problems on the ap- standby. This is guaranteed if there is a distance of approx. 1 m in front and side of the heat pump.

6.2 Noise emissions
A lift is suitable for transport on an even surface. If the heat pump has to be transported on an uneven surface or over stairs, it can be carried out with a support belt. These can be passed directly under the wooden rose-ter.
The effective sound insulation makes the heat pump very quiet. To prevent vibration transmission on the foundation, an appropriate dampening rubber mat must be placed under the main frame of the heat pump.
To avoid the transmission of sound to the heating system, it is advisable to connect the heat pump with pieces of hose to the heater.

In order to illuminate the device without pallet, drill holes fitted sideways in the frame must be used. The side-section covers must be removed. A used tube can be used as a support.

7.3 Connection to heat source
The connection shall be performed as follows:
Connect the glycol water line to the departure and the return of the heat pump. The hydraulic principle diagram must be respected.
The heat pump shall be equipped with the following connections:
In addition, a separator of micro-air bubbles must be installed in the heat source installation.
The glycol water shall be produced before filling the installation. The glycol water concentration shall be at least 25%. This ensures a frost freeness to -14 °C.
For hot water-sided heat pump connection, the heating system should be flushed down to allow possible dirt, residual insulation material etc. to be removed. If the condenser is blocked by waste and contamination, this may lead to a drop in the heat pump.
Only monoethylene glycol or propylene glycol-based antifreeze agents may be used.
The heat source system shall be ventilated and checked for density.
After installation of the heating system, it is necessary to fill up and air out and put pressure on.
The sensors connected and separately inserted in the control box must be applied and isolated, as shown in the principle diagram.
The minimum water flow rate of the heat pump shall be guaranteed in each heating mode. This can be done, for example. The system is designed to be capable of being installed by means of a differential pressure-free detector or an overflow valve. The establishment of an overflow valve is explained in the chapter Entrance.
The following electrical connections shall be performed on the heat pump:
. . Connection of the steering line to the control panel of the
heat pump via clamps X1: L/N/PE.
. . Connection of the power cable to the switch panel
of the heat pump via clamps X5/X6: L1/L2/L3/PE.
• Connection of the glycol water pump (on site) to the
heat pump switch panel via clamp X1: PE and pump protection K2: 2/4/6 (SI 5TE - SI 17TE), respectively. engine contactor F7: 2/4/6 (SI 21TE). Optionally, a single-phase glycol water pump can be used for SI 5TE - SI 14TE (see the clamping connection diagram).
If the regulators and heating circulation pumps are in operation, then the frost protection of the regulator works. In the case of external heat pump propulsion or power failure, the in-stallion shall be emptied. In the case of heat pump systems where power failure cannot be recognized (holiday home), use shall be made of the heating circuit with an appropriate frost protection.
All electrical components necessary for the operation of the heat pump are on the switch panel.
Exact instructions on connection and operation of the heat pump controller (e.g. enclosed outer wall sensor) is provided in the attached instructions for use of the regulator.
An alpile cut-off with at least 3 mm contact opening distance (e.g. The power supply is connected to the electrical control or safety contact system, as well as a 3-pole power switch with one off for all external cables. The necessary cable diameter shall be determined in accordance with the use of the heat pump, technical connection conditions of the electricity company concerned and applicable rules. The heat pump consumption can be found in the product information or on the label plate. The terminal clamps are for a cable diameter of max. 10 mm2 designed.
. . Departure/reversion glycol water system · .

8.3 Operation of the commissioning process
The heat pump is operated via the heat pump controller.
For commissioning according to the requirements, it must be carried out by a factory-competent service department. Under certain conditions, an extension of the guarantee is associated (if not applicable). Guarantee fee).
If the minimum water flow rate is secured by means of a overflow valve, it shall be adjusted to the heating system. A wrong attitude can lead to incorrect working and increased electrical energy requirements. To properly adjust the flood valve, we recommend to act as follows:
Before entry into service, the following points shall be examined:
. . All connections of the heat pump must be mounted
Close all heating circuits, which may be closed even when the installation is working depending on use, so that the water flow in this mode is as unfavourable as possible. These are usually the heating circuits in the rooms on the south and west side. At least one ring of heating must remain geo-pn (e.g. bath).
(see Chapter 7).
. The heat source system and the heating circuit shall be:
are filled and checked.
. The filter must be in the glycol water input of the heat pump
are built in.
• In the glycol water and heating circuit all slides must be
The overflow valve shall be opened so far that the current heat source temperature results in the maximum temperature difference between the change-off and the decrease-off as specified in the table below. The temperature difference shall be measured as close to the heat pump as possible. In the case of mono-energy installations, the heating element shall be deactivated.
The Commission has also proposed that the Council should adopt a decision on this matter.
• The heat pump regulator must be equipped with the appropriate equipment.
instructions for use on the heating system have been approved.
Malfunctions in a working installation are shown on the heat pump regulator and can be concealed as described in the instructions for use of the heat pumps controller.

10 Malfunctions / malfunction diagnosis
9.1 Maintenance
This heat pump is a quality product that must work without interference. If a malfunction occurs, it is displayed on the heat pump manager's display. To this end, see the page Malfunctions and Disturbance in the instructions for use of the heat pump controller.
The heat pump is maintenance-free. In order to prevent operational malfunctions caused by the accumulation of dirt in heat exchangers, care must be taken to ensure that no dirt can enter the hot-source system and heating plant. If such malfunctions occur, the installation shall be cleaned as described below.
If you cannot resolve the malfunction yourself, please inform the competent service department.
Especially when using steel components, oxygen can cause oxi-dation products (rust) in the hot water cycle. The rust enters the heating system via valves, circulation pumps or artificial dust pipes. Therefore, a diffuse-proof installation should be considered - particularly in the case of underfloor heating pipes.
Before disassembling the heat pump, the machine must be voltage-free and all valves closed. Environmentally relevant requirements waste recovery, recycling and disposal of waste and components should be respected according to normal standards. This is particularly true for the professional removal of coolant and cooling oil.
Also residues of lubricating and sealing agents can pollute the hot water.
If the pollution is so high that the con-sensor's power in the heat pump is reduced, an installer must clean the installation.
According to current knowledge, we recommend cleaning with a 5% phosphoric acid or, if more frequent cleansing is required, with a 5 per cent formic acid.
In both cases, the cleaning solution must be at room temperature. It is advisable to rinse out the heat exchanger against normal flow direction.
To prevent acidic cleaning agent from entering the heat system, we recommend that the washing machine be connected directly to the departure and backflow of the condenser. Afterwards, rinse thoroughly with appropriate neutra-lising agents to avoid damage by any residual residue of a cleansing agent in the system.
Acids must be used with caution and the relevant requirements observed.
In case of doubt, the cleaning agent must be consulted with him.
One day after the filter has been put into service, the filter sieve must be cleaned and then it must be done weekly. If there is no more visible contamination, the filter sieve can be dismantled to reduce pressure loss.



Dimplex products are produced with the greatest possible care. Nevertheless, it may occur that a defect occurs. Your installer will restore this on request, both within and outside the warranty period. The life of the product is therefore not affected. The guarantee conditions under consideration are based on EU Directive 99/44/EC and the Civil Code. The rights arising therefrom shall be without prejudice. This manufacturer's guarantee is also without prejudice to the laws of the consumer/end user in relation to his supplier. The guarantee obligations of the installer to end-user are also unaffected. We offer a warranty for this product according to the following conditions:
These warranty conditions apply to products purchased and/or in use in the Netherlands. If a product is transported abroad, the user must verify that it meets the technical conditions (e.g. voltage, frequency, installation requirements, type of gas, climate conditions) in the country concerned.
For products purchased abroad, the supplier must verify that the provisions in the Netherlands are complied with. Emergency business or desired adjustments are not covered by the guarantee, and cannot always be made. . . chemical and electrochemical action of water,
• abnormal environmental conditions in general
.Of course, the product is not subject to any conditions of use
. contact with aggressive substances.

2 Diagrams A-IV
2.1 Curves SI 5TE A-IV 2.2 Curves S 7TE A - V 2.3 Curves Si 9TE A‐VI 2.4 Curves si 11TE A
3.1 Sturgeon SI 5TE - SI 17TE A-XI 3.2 Power SI 5te - SI 16TE A -XII 3.3 Clamp connection scheme SI 5Te - SI 15TE A/XIII 3.4 Legend SI 5LE - SI 18TE A‐XIV 3.5 Steering SI 21TE A
5 Declaration of conformity A-XXI
www.dimplex.de A-I

1.1 Dimensions SI 5TE - SI 17TE


7RHYRHU . . HOHNWULVFKH .
9HUZDUPLQJVYHUWUHN . 8LWJDQJÍXLW .:3A .EXLWHQGUDDG
:DUPWHEURQ ,QJDQJÍLQ.:3A SAME NAME
:DUPWHEHURQ. • 8LWJDQJ. @XLW • 3A • EXLWHQGUDDG
9HUZDUPLQJVWHUXJORRS ,QJDQJÍLQ.:3A SAME NAME
www.dimplex.de A-III

2.1 Curves SI 5TE














3.1 Sturting SI 5TE - SI 17TE






A1 Wirebridge, should be installed when no safety switch is available for the primary pump A2 Wirebridge must be removed if a second block ring input is used.A3 Wirebridge shall be removed when an engine protection contact is used for the main pump.B2* Low pressure pressure glycolwater B3* Thermostate hot water (alternative to R3) B4* Thermostat swimming pool water E9* Dummy heating element hot water E10* 2nd heat source (boiler or leak). heating element) F2 Locking for N1 relay outputs on J12 and J13 4.0 ATr F3 Lock securing for N1-relai outputs at J15 - J18 4.0 Atr F4 Pressostat high pressure F5 Pressure sensor low pressure F15 Motor contactor M11 H5* Light failure indication remotely J1...J18 Clamp connector for N 1 K1 Safety switch compressor K5 Safety switch primary pump (PUP) K11* Electron. relay for H5 (on N11) K12* Electron. Relays for M19 (on N11) K20* Safety switch 2nd heat source K21* Safety switches for hot water K22* EVB safety switch K23* SPR auxiliary relay M1 Compressor M11* Primary pump (PUP) M13* Heating circulation pump M15* Heater-circulation pump 2nd heating circuit M16* Additional circulating pump M18* Hot water circulation pump m19* Swimming pool water circulation station M21* Mixing valve main circuit M22* Mixer crane 2nd heater N1 Heat pump controller N7 Soft start control (falls into SI 5TE and SI 7TE devices) N11* Relay module R1 External temperature sensor R2 Backflow sensor R3 Warm water sensors (alternative to warmwater thermal state) R5 Footer for 2nd boiler R6 Foot protection against freezing R7 Enclosure resistance 40k2 R9 Departure sensor T1 Safety sensor 230/24V AC-R2 Clock/R2 LED system
Abridged information: EVB Entrance seal electricity company SPR Additional lock-in MA Mixing crane open MZ Mixing valve closed * Components should be made available externally, respectively. are available as accessory







A1 Wirebridge, should be placed when no shut-off contactor is required A2 Wirebridge shall be removed from the 2nd block ring input closed contact = no lock/WP to B2* Low pressure pressostat glycolwater B3* Thermostat hot water B4* Thermostatic pool water E9* Electric. hot water heating element E10* 2nd Heat source (boiler or leak. heating element) F2 Locking device for N1 relay outputs on J12 and J13 4.0 ATr F3 Lock securing system for N1-relais outputs at J15 - J18 4.0 Atr F4 Pressostat high pressure F5 Low pressure pressostat - limiter with manual reset F12 Thermorelais N7 F14 Electronic motor contactor compressor 1 H5* Light fault indication remotely J1...J18 Clamp connector for N1, K1 Safety switch compressor K5 Safety switch primary pump K1.1 Safety switch draw current limitation K1.2 Time relays for delay of K1 K11* Electron. remote relay fault indicator (relaismodule) K12* Electron. relay circulation pump pool water (relaismodule) K20* Safety switch 2nd heat source (boiler or electric. heating element) K21* Safety switch electric. Submersible heating element for hot water K22* EVB safety switch K23* SPR auxiliary relay M1 Compressor M11* Primary pump M13* Heating circulation pump M15* Heater-circulation pump 2nd circuit M16* Additional circulating pump M18* Warm water circulation pump m19* Pool water circulation pumps M21* Mixing valve main circuit M22* Mixer crane 2nd heat exchanger N1 Heat pump regulator N7 Softstartplatin N11* Relay module N14 Control panel Q1 Safety switch glycol water pump Q2 Safety switch compressor R1 External temperature sensor R2 Backflow sensor R3 Hotwater sensor (alternative) R5 Footer for 2nd heating circuit R6 Peeler to prevent freezing R7 Code resistance 40k2 T1 Security separator 230/24V AC- 28VA X1 Radio control system L/N/PE-230V AC/PE-50 Hz/C/Cheals/Choarders/Charles/Chorses/CHX3 components - 6th series of motor vehicles - 4rd cycle drive
Abridged information: EVB Entrance seal electricity company SPR Additional locking entry MA Mixing valve open MZ Mixing tap closed * Components should be made available externally

4.1 Schematic image









Glen Dimplex Deutschland GmbH Geschäftsbereich Dimfix Am Goldenen Feld 18 D-95326 Kulmbach
Errors and changes reserved.