- Split system air conditioner -
This product is marked as it satisfies Directives:
– Low voltage no. 2006/95/EC. (Standard: EN60335-2-40:2003 (incl. Corr.:2006) + A11:2004 + A12:2005 + A13:2012
+ A1:2006 + A2:2009 con EN 60335-1:2002 + A11:2004 + A1:2004 + A12:2006 + A2:2006 + A13:2008 + A14:2010 + A15:2011). – Electromagnetic compatibility no. 2004/108/EC, 92/31 EEC and 93/68 EEC. (Standard: EN55014-1 (2006) + A1(2009)
+ A2(2011), EN 55014-2 (1997) + A1(2001) + A2 (2008), EN 61000-3-2 (2006) + A1(2009) + A2(2009), EN 61000-3-3 (2008) – RoHS2 no.2011/65/EU. – Regulation (EU) no. 206/2012, of 6 march 2012, concerning the specifications for ecodesign requirements of air
conditioners and fans. – Regulation (EU) no. 626/2011, of 4 may 2011, concerning the labeling indicating the energy consumption of air
conditioners. This declaration will become void in case of misuse and/or non observance though partial of manufacturer's installation and/or operating instructions.
Cooling Maximum conditions
Heating Maximum conditions
Outdoor temperature : 43°C D.B. Room temperature : 32°C D.B. / 23°C W.B.
Outdoor temperature : 24°C D.B. / 18°C W.B. Room temperature : 27°C D.B.
Cooling Minimum conditions
Heating Minimum conditions
Outdoor temperature : –15°C D.B. Room temperature : 10°C D.B. / 6°C W.B.
Outdoor temperature : –15°C D.B. Room temperature : 5°C D.B.
Tools required for installation (not supplied)
1.Standard screwdriver
19.Hammer
Model Combinations:
2.Phillips head screwdriver
10.Drill
3.Knife or wire stripper
11.Tube cutter
4.Tape measure
12.Tube flaring tool
5.Level
13.Torque wrench
6.Sabre saw or key hole saw
14.Adjustable wrench
7.Hacksaw
15.Reamer (for reburring)
16.Hex. key
Power Supply:
REGULATION (EU) No. 517/2014 - F-GAS
The unit contains R410A, a fluorinated greenhouse gas with a global warming potential (GWP) of 2087.50. Do not release R410A into the atmosphere.
37.4255.122.01 01/2017

Fresh air intake side
REFRIGERANT TUBING SIDE
Refrigerant tubing joint (NARROW tube)
Refrigerant tubing joint (WIDE tube) Condensate drain piping



This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
When transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing In a ceiling or wall Make sure the ceiling/wall is strong enough to hold the unit- weight. It may be necessary to build a strong wooden or metal frame to provide added support.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
... In a room Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
... In moist or uneven locations Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
If necessary, get help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
... In area with strong winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
In case of improper installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When wiring

ASICS10 MODEL
REDUCTION 5/8F - 1/2M + BOCCHETTONE
1 ASIDS13 MODEL
1. ADAPTER 1/2F - 3/8F - 5/8M
2. REDUCTION 1/4F - 3/8M + WASHER
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
l Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
foamed polyethylene (min. thickness 8mm).
l PVC pipe for condensate drain pipe (ø int.18mm) in lenght suitable to let the condensate flow into the outside drainage.
l Anti-freeze oil for flare connections (about 30g).
l Electric wire: use insulated copper wires of size and length as shown in the paragraph “WIRING DIAGRAMS”.
SEE INSTALLATION INSTRUCTIONS OF OUTDOOR UNIT
(go on page 6)

Drill a 65 mm diameter hole, insert a PVC pipe.
Eseguire un foro di diametro 65 mm, inserire ed adattare un tubo in plastica.
Faire un trou de diamètre 65 mm, introduire et adapter un tube PVC.
Ein Loch mit Durchmesser 65 mm in die Wand schneiden, ein PVC- Rohr einfügen.
Hacer un orificio de 65 mm, introducir y adaptar un tubo de plástico.
Faça o furo de 65 mm de diametro, introduza o tubo de plástico.
Anoivxte miva ophv diamevtrou 65 ciliostwvn. Topoqethvste mevsa evna swlhvna PVC (plastikov) kai prosarmovste to plastikov kapavki pou diativqetai me thn monavda.
ASICS10-ASIDS13
A
4 holes ø 3,1
ø112

H monavda diaqevtei upodochv gia th suvndesh enov" agwgouv gia aevra ananevwsh" . O anemisthvra" anarrovyhsh" nwpouv aevra eivnai proairetikov" kai an egkatastaqeiv creiavzetai xecwristhv parochv reuvmato" mevsw diakovpth ON-OFF kai hlektrikhv" asyavleia". H anarrovyhsh nwpomv aevra den mporeiv na uperbaivnei se kammiva perivptwsh to 10% th" sunolikhv" parochv" aevra th" suskeuhv". Ahoixte to prostateutiko kapaki , topoqethste mia flantza diametrou 70 mm kai sundeste to qermika monwmeno kanali. Se perivptwsh anarrovyhsh" apov th suskeuhv nwpouv aevra eivnai aparaivthth crhvsh kavpoiou yivltrou aevra, wvste na apoyeucqeiv h eisrohv skovnh" kai akaqarsiwvn stou" agwgouv" kai kat epevktash sth suskeuhv.
J Remove the electrical box cover to operate on the terminal strip.
Rimuovere il coperchio scatola componenti elettrici per accedere alla morsettiera.
Enlever le capot de la boîte des composants électriques.
Die Abdeckplatte des Klammbrettes entfernen.
Quitar la tapa de la caja de los componentes eléctricos para acceder a la regleta de bornes.
Remova o painel de acesso dos componentes elétricos para ter acesso aos terminas.
Afairevste to kavlumma tou hlektrikouv kibwtivou gia na evcete provsbash sto morsevto.
Coperchio del quadro elettrico

Colocar el cable eléctrico y concitarlo al tablero de bornes (véase esquema de conexiones). Bloquear el cable a la abrazadera.
ADVERTÊNCIA
Controlar que los bornes de los cables estén bien sujetos en el tablero de bornes. De otro modo, podrían recalentarlo o provocar problemas en el funcionamiento del acondicionador con riesgo le incendio. Al cerrar la caja de los componentes eléctricos, controlar que los cables no sobresalgar y que no se queden atrapados entre la tapa y la unidad. Controlar que la lengüeta esté alineada y apretar los tornillos.
Posicione o fio elétrico para a ligação com os terminais e ligue-o (consulte o esquema elétrico para a ligação). Fixe o fio com uma anilha especial à braçadeira.
Assegure-se que os fios estejam bem apertados a fim de evitar um superaquecimento dos terminais um malfuncionamento da unidade ou mesmo um incêndio. Ao fechar a caixa de componentes eléctricos, tome cuidado para não deixar de fora parte dos fios ou deixar que estes sejam apanhados entre a tampa e a unidade. Verifique se a lingueta está alinhada e depois aperte os parafusos.
Etoimavste ta kalwvdia gia th suvndesh me to morsevto kai sundevste ta. (Deivte to schvma gia thn suvndesh kalwdivwn). Mplokavrete to kalwvdio sth sthvrixh th" flavntza".
Elevgxte an oi avkre" twn kalwdivwn eivnai sfiktav sundedemevne" pavnw sto morsevto. An oi avkre" den eivnai sfiktav sundedemevne" mporeiv na proklhqeiv uperqevrmansh tou morsevtou kai na dhmiourghqouvn problhvmata sthn leitourgiva tou klimatistikouv, me kivnduno purkagiav". ;ΔOtan kleivnete to koutiv tou hlektrikouv diamerivsmato", prosevcete na mhn afhvnete mevro" twn kalwdivwn evxw hv piasmevna metaxuv tou kaluvmmato" kai th" movando". Bebaiwqeivte ovti h proexochv tou kaluvmmato" evcei mpei sthn antivstoich egkophv kai metav sfivggete ti" bivde".

B
TP2
V. ISTRUZIONI DI INSTALLAZIONE UNITA' ESTERNA
V. NOTICE D'INSTALLATION UNITE EXTERIEURE
SEHEN SIE INSTALLATIONSANLEITUNGEN VON AUSSENEINHEIT
VER INSTRUCCIONES DE INSTALACIÓN DE LA UNIDAD EXTERIOR
VER INSTRUÇÕES DE INSTALAÇÃO DA UNIDADE EXTERIOR ODHGIES TOPOQETHSHS - Exwterikev" monavde"
EG Connecting wire B (SHIELDED): Bipolar electric shielded wire; size and length of the suggested electric wire are showed in the installation instructions of outdoor unit. The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21). Connecting wire C (with ground conductor): Multipolar electric wire; size and length of the suggested electric wire are showed in the installation instructions of outdoor unit. The wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22). Make sure the length of the conductors between the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Cavo di collegamento B (SCHERMATO): Cavo elettrico bipolare schermato; la sezione e la lunghezza del cavo elettrico consigliato sono indicate nelle istruzioni di installazione dell’unità esterna. Il cavo non deve essere più leggero del tipo H05VVC4V5-K (secondo CEI 20-20 CENELEC HD21). Cavo di collegamento C (con conduttore di terra): Cavo elettrico multipolare; la sezione e la lunghezza del cavo elettrico consigliato sono indicate nelle istruzioni di installazione dell’unità esterna. Il cavo non deve essere più leggero del tipo H07RN-F (secondo CEI 20-19 CENELEC HD22). Assicurarsi che la lunghezza dei conduttori fra il punto di fissaggio del cavo ed i morsetti sia tale che i conduttori attivi si tendano prima del conduttore di messa a terra.

Indoor units that are part of a multisplit system must be properly configured to be able to communicate with the outdoor unit over different channels (Indoor A, Indoor B, etc...) of the communication bus. Each indoor unit address must correspond to the physical connection of the indoor unit to the outdoor unit refrigerant circuit, i.e.: Refrigerant Circuit A Indoor Unit Address A Refrigerant Circuit B Indoor Unit Address B ... There are three methods to set the address of an indoor unit: (1) Dip-switch setting: the address is set by mean of a dip-switch located on the indoor unit pcb. (2) Remote controller procedure (still available): the address is set by mean of a special setting on the remote controller. (3) Automatic addressing procedure: the address is automatically set on every indoor unit of the system by mean of an
automatic procedure.
(1) ADDRESS SETTING THROUGH DIP-SWITCHES (UP TO 4 INDOOR UNITS)
Check that the setting of switch SW2 (PCB) corresponds to the figure:
INDOOR UNIT B
SW2 (PCB factory state) 1=off 2=off
INDOOR UNIT C
INDOOR UNIT D
PCB
PCB

(2) ADDRESS SETTING THROUGH REMOTE CONTROLLER (UP TO 8 INDOOR UNITS)
Set the remote controller as shown in the table.
SETTING
Indoor unit A: 11°C Indoor unit B: 12°C Indoor unit C: 13°C Indoor unit D: 14°C Indoor unit E: 15°C Indoor unit F: 16°C Indoor unit G: 17°C Indoor unit H: 18°C
working mode (COOL - HEAT)
AUTO
ON OFF
night mode / high mode
At this point, press together FAN + IFEEL buttons for more than 7 seconds and release them pointing the remote controller to the indoor unit receiver. Be sure to send the signal to only one indoor unit and that there is no other indoor unit that could receive the same signal. If the signal is received, the indoor unit will emit 5 consecutive beeps.

System requirements: Outdoor unit must have a recent firmware version that supports the automatic addressing procedure. Indoor units must have a recent firmware version that supports the automatic addressing procedure Dip-switch for communication address setting on the indoor unit (SW2) must be left to the factory default state, i.e. to the OFF position.
Activation of automatic addressing procedure Power on the whole system. Verify that there is no error on the indoor units, but the error “Address not set” (see Auto-diagnosis table). Switch on the remote controller of any of the indoor units of the system and set it as follows:
SETTING
working mode (COOL - HEAT)
24°C AUTO
filter night mode / high mode
Any Any
Press together FAN + IFEEL buttons for more than 7 seconds and release them pointing the remote controller to the indoor unit receiver. Be sure to send the signal to only one indoor unit and that there is no other indoor unit that could receive the same signal.
If the signal is received, the indoor unit will emit 5 consecutive beeps.
After some seconds, every indoor unit will show the following LED combination to confirm that the automatic addressing procedure has been activated.
OPER TIMER STBY
From this moment until the end of the procedure the indoor units will not receive anymore the signals from the remote controllers (infrared receiver is disabled).
Execution of automatic addressing procedure Once the procedure has been activated, the system will run automatically to set the address of every indoor unit. In this period, compressor and fan motor will be activated. Once activated, the procedure takes about 4-5 minutes per outdoor unit circuit to be completed. This time doesn’t depend on the number of indoor units actually connected to the outdoor unit, but on the number of refrigerant circuits of the outdoor unit.
End of automatic addressing procedure When all the circuits have been tested and the address of every indoor unit has been set, the outdoor unit will stop and every indoor unit will switch off (standby mode). In any case (procedure successful or failed) the infrared receiver of every indoor unit will be re-activated. If there is no error on the indoor units, the system is ready to be used. If there is the error “Address not set” (see Auto-diagnosis table) on any indoor unit, re-run the automatic addressing procedure or manually set the address on that indoor unit with the dip-switch or with the remote controller.

Set SW1 as shown in the table.
Impostare SW1 come indicato in tabella.
Régler SW1 comme indiqué dans le tableau.
Stellen Sie SW1 ein, wie in der Tabelle gezeigt ist.
Regular SW1 como indicado en la tabla.
Ajustar SW1 como mostrado na tabela.
ƒ˘ıÌ›ÛÙ ÙÔ SW1 fiˆ˜ ·Ó·Ê¤ÚÂÙ·È ÛÙÔÓ ›Ó·Î·.
REMOTE CONTROLLER
TELECOMANDO TELECOMMANDE FERNBEDIENUNG MANDO A DISTANCIA CONTROLE REMOTO
PCB
INNENEINHEIT UNIDAD INTERIOR UNIDADE INTERIOR Eswterikev" monavde"
FACTORY STATE
1=OFF 2=OFF 3= OFF 4=OFF 5=ON 6=ON SW1: 1=OFF 2=OFF
1=ON 2=OFF 3=OFF 4=OFF 5=ON 6=ON SW1: 1=ON 2=OFF
1=OFF 2=ON 3=OFF 4=OFF 5=ON 6=ON SW1: 1=OFF 2=ON
1=ON 2=ON 3=OFF 4=OFF 5=ON 6=ON SW1: 1=ON 2=ON

l Detach the plastic cover of the remote controller terminal block.
l Open the batteries compartment, remove the batteries and set microswitches 5 and 6 in OFF position.
l Close the compartment without replacing the batteries (remote controller will be powered by wire). CONNECTION Use a tripolar electric shielded wire 0,5mm
2, max. length 15m. The wires have not to be lighter than Mod. H05VVC4V5- K (according to CEI 20-20 CENELEC HD21). CONNECTING THE REMOTE CONTROLLER TO THE 5 POLES TERMINAL BLOCK INSIDE THE ELECTRICAL PANEL, AS FOLLOWS:
l Remove the “bridge” wire between the terminals 2 and 4.
l Connect the terminal 1 to the bottom terminal of remote control terminal block (+ pole).
l Connect the terminal 2 to the medium terminal of remote control terminal block (IR).
l Connect the terminal 3 to the upper terminal of remote control terminal block (- pole).
l Staccare il coperchietto in plastica della morsettiera del telecomando.
l Aprire il vano batterie, rimuovere le batterie e settare i microinterruttori 5 e 6 in posizione OFF.
l Chiudere il vano batterie senza rimettere le batterie (il telecomando sarà alimentato da filo). COLLEGAMENTO Utilizzare un cavo elettrico tripolare schermato 0,5mm
2, lunghezza max. 15m. Il cavo non deve essere più leggero del tipo H05VVC4V5-K (secondo CEI 20-20 CENELEC HD21). COLLEGARE IL TELECOMANDO ALLA MORSETTIERA 5 POLI ALL’INTERNO DEL QUADRO ELETTRICO, COME SEGUE:
l Rimuovere il cavo ponte tra i morsetti 2 e 4.
l Connettere il morsetto 1 con il terminale inferiore della morsettiera sul telecomando (polo +).
l Connettere il morsetto 2 con il terminale centrale della morsettiera sul telecomando (IR).
l Connettere il morsetto 3 con il terminale superiore della morsettiera sul telecomando (polo -).

l Retirez le couvercle en plastique de la borne de la télécommande.
l Ouvrez le compartiment des piles, retirer les piles et régler les interrupteurs 5 et 6 en la position OFF.
l Fermez le compartiment des piles sans mettre les piles (la télécommande sera alimentée par le câble). LIAISON Utilisez un câble électrique tripolaire blindé 0,5mm
2, longueur max.15m. Le câble doit être de type H05VVC4V5-K minimum (selon CEI 20-20 CENELEC HD21). RELIER LA TELECOMMANDE A LA BORNE 5 POLES A L’INTERIEUR DU TABLEAU ELECTRIQUE, COMME SUIT:
l Retirez le câble "pont" jaune.
l Connecter le terminal qui se termine avec les câbles vertes avec la borne inférieure de la plaque à bornes de la télécommande (pole +).
l Connecter le terminal qui se termine avec le câble purple avec la borne centrale de la plaque à bornes de la télécommande (IR).
l Connecter le terminal qui se termine avec les câbles noires avec la borne supérieure de la plaque à bornes de la télécommande (polo -).
l Entfernen Sie die Plastikabdeckung vom Terminal der Fernbedienung.
l Öffnen Sie das Batteriefach, entfernen Sie die Batterien und die Schalter 5 und 6 in die Position OFF stellen.
l Schließen Sie das Batteriefach ohne die Batterien wiederzusetzen (die Fernbedienung wird mit dem Kabel angeschlossen). ANSCHLUSS Verwenden Sie ein elektrisches dreipoliges Aschirmkabel 0,5mm
2, Länge max.15m. Das Kabel soll nicht leichter als H05VVC4V5-K-Typ sein (gemäß CEI 20-20 CENELEC HD21). SCHLIESSEN SIE DIE FERNBEDIENUNG AN DEN KLEMMENBLOCK 5P IM SCHALTSCHRANK, WIE FOLGT:
l Entfernen Sie das gelbe „Brücke“ Kabel.
l Schließen Sie das Terminal, das mit der grünen Kabeln endet, mit dem unteren Anschluss der Klemme auf der Fernbedienung (positive).
l Schließen Sie das Terminal, das mit dem violetten Kabel endet, mit dem zentralen Anschluss der Klemme auf der Fernbedienung(IR).
l Schließen Sie das Terminal, das mit der schwarzen Kabeln endet, mit dem oberen Anschluss der Klemme auf der Fernbedienung (negativen).
l Quitar la tapa de plástico del terminal del mando a distancia.
l Abrir el compartimiento de las pilas, extraer las pilas y ajustar los interruptores 5 y 6 en la posición OFF.
l Cerrar el compartimiento de las pilas sin poner las pilas (el mando a distancia sera alimentado por el cable). CONEXIÓN Utilizar un cable eléctrico tripolar blindado de 0,5 mm
2, longitud max.15m. El cable no debe ser más ligero del tipo H05VVC4V5-K (según CEI 20-20 CENELEC HD21). CONECTAR EL MANDO A DISTANCIA AL TERMINAL 5P DEL PANEL ELÉCTRICO, COMO SIGUE:
l Retirar el cable puente amarillo.
l Conectar el terminal que termina con los cables de color verde con el terminal inferior del bloque de terminales del mando a distancia (positivo).
l Conectar el terminal que termina con el cable de color violeta con el terminal central del bloque de terminales del mando a distancia (IR).
l Conectar el terminal que termina con los cables de color negro con el terminal superior del bloque de terminales del mando a distancia (negativo).

S.A.C. - Printed in italy
Via Varese, 90 - 21013 Gallarate - Va - Italy
Tel. +39 0331 755111 - Fax +39 0331 776240