GENERAL YORK Model B*CH units are single package heat pump s designed for outdoor installation on a roof top or a slab. These units can be equipped with factory installed electric heaters for supplemental heating applications. The units are completely assembled on rigid, permanently attached base rails.
035-18895-000-A-0902 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with applicable national and local or municipal safety codes. Refer to T able 1 for Unit Application Dat a and to T able 2 for Electric Heat Application Data.
FIXED OUTDOOR AIR INT AKE DAMPER This damper assembly is shipped inside the return air compartment. It is completely assembled and ready for installation. A damper baffle inside the hood is adjustable to provide variable amounts of outdoor air int ake on units that are not provided with an economizer or motorized damper option.
insulated wires 1.0mm 2 (#18 A WG) should be used to connect thermostat to unit. Eight conductors are required. The subbase on the low voltage thermostat includes an “Emergency Heat ” position on the system switch and a pilot light. In the “Emergency Heat” position, the thermostat provides electric resistance heat only .
035-18895-000-A-0902 6 Unitary Products Group These heaters are located within the central compartment of the unit with the heater elements extending into the supply air chamber . Refer to Figure 7 for access panel location. Fuses are supplied, where required, by the factory .
035-18895-000-A-0902 Unitary Products Group 7 WEIGHTS (kg. / lbs.) BASIC UNIT 180 948 / 2091 OPTIONS Economizer 73 / 160 Motorized Damper 68 / 150 Electric Heater 18 kW 1 1 / 25 36kW 14 / 30 54 kW 16 .
035-18895-000-A-0902 8 Unitary Products Group FIG . 7 - DIMENSIONS AND CLEARANCES All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimen - sions will be provided upon request.
035-18895-000-A-0902 Unitary Products Group 9 FIG . 7 (Cont'd.) - DIMENSIONS AND CLEARANCES DET AIL “X” ACCESSOR Y SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS DUCT COVERS - Units are shipped with all air duct openings covered. For sideflow duct applications; 1.
035-18895-000-A-0902 10 Unitary Products Group T ABLE 4 - SUPPL Y AIR BLOWER PERFORMANCE BLOWER SPEED, RPM MOTOR PULLEY (TURNS OPEN)* AIRFLOW 1.77 m 3 /s 2.
035-18895-000-A-0902 Unitary Products Group 11 DESCRIPTION EXTERNAL ST A TIC PRESSURE DROP - RESIST ANCE, iwg/Pa m 3 /s (CFM) 180 UNIT 1.77 (3750) 2.12 (4500) 2.48 (5250) 2.83 (6000) WET COIL 0.1 / 25 0.1 / 25 0.1 / 25 0.1 / 25 ELECTRIC HEA T OPTIONS 18 kW 0.
COOLING SYSTEM The cooling section is a complete factory package utilizing an air-cooled condenser . The system is factory-charged with Refrigerant-22. The compressors are hermetically sealed, internally sprung and base-mounted with rubber-insulated hold-down bolts.
HEA T ANTICIP ATOR SETPOINT It is important that the anticipator setpoint be correct. T oo high a setting results in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint causes shorter “ON” cycles and may result in the lowering of the temperature within the conditioned space.
DEFROST SEQUENCE OF OPERATION These heat pumps have a unique “ambient modified” time- temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control shortens the defrost initiation time periods above 2°C (35°F) and extends the defrost initiation time periods below 2°C (35°F .
035-18895-000-A-0902 Unitary Products Group 15 SECURE OWNER'S APPROV AL : When the system is functioning properly , secure the owner's approval. Show him the location of all disconnect switches and the thermostat. T each him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.
035-18895-000-A-0902 5005 Y ork Drive, Norman Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright by Y ork International Corporation 2002.
An important point after buying a device York SUNLINE 2000 B2CH180 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought York SUNLINE 2000 B2CH180 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data York SUNLINE 2000 B2CH180 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, York SUNLINE 2000 B2CH180 you will learn all the available features of the product, as well as information on its operation. The information that you get York SUNLINE 2000 B2CH180 will certainly help you make a decision on the purchase.
If you already are a holder of York SUNLINE 2000 B2CH180, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime York SUNLINE 2000 B2CH180.
However, one of the most important roles played by the user manual is to help in solving problems with York SUNLINE 2000 B2CH180. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device York SUNLINE 2000 B2CH180 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center