INST ALLA TION MANUAL - 50 Hz CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INST ALL YOUR UNIT . SA VE THIS MANUAL SINGLE P ACKAGE HEA T PUMP HIGH EFFICIENCY BP090 and 120 (7-1/2 and 10 TON) 66307-YIM-B-0606 CONTENTS GENERAL . . . . . . . . . . .
66307-YIM-B-0606 2 Unitary Products Group T ABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 5 INSPECTION . . . . . . . . . . . . . . . .
66307-YIM-B-0606 Unitary Products Group 3 LIST OF FIGURES Fig. # Pg. # 1 UNIT SHIPPING BRA CKET . . . . . . . . . . . . . . . . . . . . . 8 2 CONDENSER COIL COVERING . . . . . . . . . . . . . . . . . 8 3 COMPRESSOR SECTION . . . . . . . . . . . . . . .
66307-YIM-B-0606 4 Unitary Products Group LIST OF T ABLES Tbl. # Pg. # 1 UNIT TEMPERATURE LIMIT ATIONS . . . . . . . . . . . . . 9 2 UNIT VOLTAGE LIMITATIO NS . . . . . . . . . . . . . . . . . . 9 3 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . .
66307-YIM-B-0606 Unitary Products Group 5 GENERAL YORK ® Predator ® Heat Pump units are single package, reverse cycle air conditioners designed fo r outdoor installa- tion on a rooftop or slab and for non-residential use. These units can be equipped with factory or field installed electric heaters for heatin g applications.
66307-YIM-B-0606 6 Unitary Products Group REFERENCE Additional information is available i n the following re ference forms: • T echnical Guide - 259336 • General Installation - 66307 • Pre-start.
66307-YIM-B-0606 Unitary Products Group 7 NOMENCLA TURE B P 090 C00 A 7 A AA 3 0 1 2 4 A Product Category B = HP, Single Pkg., R-22 A = Std. Motor Airflow B = Std. Motor/Econo./Barometric Relief (Downflow Only) C = Std. Motor/Econo./Power Exhaust (Downflow Only) D = Std.
66307-YIM-B-0606 8 Unitary Products Group INST ALLA TION INST ALLA TION SAFETY INFORMA TION Read these instructions before conti nuing this appliance installation.
66307-YIM-B-0606 Unitary Products Group 9 LOCA TION Use the following guide lines to select a suitable locatio n for these units: 1. Unit is designed for outdoor installation only . 2. Condenser coils must have an unlimi ted supply of air . Where a choice of location is possible, position the unit on either north or east side of bu ilding.
66307-YIM-B-0606 10 Unitary Products Group RIGGING AND HANDLING Exercise care when movi ng the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails.
66307-YIM-B-0606 Unitary Products Group 11 CLEARANCES All units require particular cl earances for proper operation and service. Refer to T able 6 for clearances required for con- struction, servicing, a nd proper unit operation .
66307-YIM-B-0606 12 Unitary Products Group . FIGURE 9 - BOTTOM DUCT OPENINGS (FROM A BOVE).
66307-YIM-B-0606 Unitary Products Group 13 DUCTWORK Ductwork should be d esigned and sized ac cording to the methods in Manual D of the Air Cond itioning Contractors of America (ACCA) or as reco mmende d by any other recog- nized authority such as ASHRAE or SMACNA.
66307-YIM-B-0606 14 Unitary Products Group Note orientation. Panel i s “insulation” side up. FIGURE 1 1 - PREDA TOR ® ROOF CURB DIMENSIONS 5 0 - 1 / 2 ( 1 2 8 5 ) 3 0 ( 7 6 0 ) 2 0 ( 5 1 0 ) 8 0 - 5 / 8 ( 2 0 5 0 ) 6 ( 1 5 0 ) 2 T Y P .
66307-YIM-B-0606 Unitary Products Group 15 CONDENSA TE DRA IN The side condensate drain is reversible and maybe re -ori- ented to the rear of the cab i net to facilitate condensate pip- ing. A condensate drain connection is available through the base pan for piping inside the roof curb.
66307-YIM-B-0606 16 Unitary Products Group comply with electrical codes should not be required. If an y of the wire su ppl ie d wi th th e un it must be repla ce d, r eplac em en t wire must be of the type show n on the wiring diagram and the same minimum gauge as the replaced wire.
66307-YIM-B-0606 Unitary Products Group 17 FIGURE 18 - FIELD WIRING 24 VOL T THERMOST A T O C C W 1 W 2 Y 1 G Y 2 X R S D C R E M O T E M I N P O S W 1 W 2 Y 1 G Y 2 C U N I T C O N T R O L B O A R D T - S T A T R H R C The thermostat must provide a “G” signal when there is a call for “W1.
66307-YIM-B-0606 18 Unitary Products Group T ABLE 8: ELECTRICAL DATA - 7-1/2 TON HP Vo l t a g e Compressors OD Fan Motors Supply Air BLower Motor FLA Pwr Exh Motor Electric Heater Model No. Actual Kw Heater Amps Minimum Circuit Ampacity (Amp s) MCA with Power Exhaust (Amps) Max Fuse Size * (Amps) Max Fuse Size w/Pwr .
66307-YIM-B-0606 Unitary Products Group 19 FACTORY INST ALLED OPTIONS/ FIELD INST ALLED ACCESSORIES ELECTRIC HEA T ACCESSORY Electric heaters are available as field installed accessories.
66307-YIM-B-0606 20 Unitary Products Group MOTORIZED OUTDOOR DAMPER The Motorized Outdoor Damper can be a factory installed option or a field installed accessory . If facto ry installed, refer to the instructio ns included with the outdoor air hood to com- plete the assembly .
66307-YIM-B-0606 Unitary Products Group 21 • For a dual enthalpy o peration, carefully tu rn the set point adjusting screw fully clockwise past the "D" setting. POWER EXHAUST DAMPER SET POINT (WITH OR WITH- OUT POWER EXHAUST) • With no power exha ust opti on, adjust the Exhaust Air Adjustment Screw fully clockwise.
66307-YIM-B-0606 22 Unitary Products Group PHASING Predator ® units are properly phased at the factory . Check for proper compressor rotation. If the blower or compressors rotate in the wrong direction at start-up, the electrical connec- tion to the unit is misphased.
66307-YIM-B-0606 Unitary Products Group 23 FIGURE 22 - BELT ADJUSTMENT A A A B SPAN LENGTH DEFL. FORCE C* * NEVER LOOSEN Procedure for adjusting belt tension: 1. Loosen six nuts (top and bottom) A. 2. Adjust by turning (B). 3. Never loosen nuts (C). 4.
66307-YIM-B-0606 24 Unitary Products Group T ABLE 13: BLOWER PERFOR MA NCE 7-1/2 TON ST AN DARD MOTOR - SIDE DUCT (IMPERIAL) ESP (iwg) T urns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM W atts BHP C FM W atts BHP CFM Watt s BHP 0.2 - - - - - - - - - - - - 3698 1382 1.
66307-YIM-B-0606 Unitary Products Group 25 T ABLE 16: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (METRIC) ESP (Pa) T urns Open 012345 m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) 100 -- --- --- --- - 1 .
66307-YIM-B-0606 26 Unitary Products Group T ABLE 19: BLOWER PERFOR MA NCE 10 TON OP TIONAL MOTOR - SIDE DUCT (IMPERIAL) ESP (iwg) T urns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM W atts BHP C FM W atts BHP CFM Watt s BHP 0.4 -- - -- - - - - -- - -- - 4 9 6 0 2 4 9 5 2 .
66307-YIM-B-0606 Unitary Products Group 27 T ABLE 21: BLOWER PERFORMANCE 7-1/2 T O N STANDARD MOTOR - DOWNSHOT (IMPERIAL) ESP (iwg) T u rns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts B HP 0.2 - - - 3838 1772 1.
66307-YIM-B-0606 28 Unitary Products Group T ABLE 24: BL OW ER PE RFOR MANCE 7-1/2 TO N OPTIONAL MOTOR - DOWNSHOT (METRIC) ESP (Pa) T u rns Open 012345 m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) 50 - - - - - - - - - - - - 1.
66307-YIM-B-0606 Unitary Products Group 29 T ABLE 27: BLOWER PERFORM ANCE 10 T ON OP TIONAL MOTOR - DOWNSHOT (IMPER IAL) ESP (iwg) T u rns Open 012345 CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP 0.2 -- - -- - -- - - - - 4966 2666 2.
66307-YIM-B-0606 30 Unitary Products Group AIR BALANCE S tart the supply air blower motor . Adjust the resistances in both the supply and the return air duct systems to balance the ai r distribution throughout the cond it ioned space. The job specifications may requ ire that this balancing be done by some one other than the equipment installer .
66307-YIM-B-0606 Unitary Products Group 31 SUPPL Y AIR DRIVE ADJUSTMENT At unit start-up, the measured CFM may be higher or lower than the required CFM.
66307-YIM-B-0606 32 Unitary Products Group T ABLE 30: ADDITIONAL STATIC RESIST ANCE - IMPERIAL CFM Cooling Only * Ec onomizer † ‡ Electric Heat KW † 9 1 82 43 65 4 2300 0.08 0.02 0.07 0.08 0.09 0.10 0.13 2500 0.09 0.02 0.08 0.09 0.10 0.1 1 0.14 2700 0.
66307-YIM-B-0606 Unitary Products Group 33 OPERA TION SEQUENCE OF OPERA TIONS OVERVIEW For the Predator ® series of units, the thermostat makes a cir- cuit between "R" and "Y1" for the first stage of cooling.
66307-YIM-B-0606 34 Unitary Products Group "Y1" energizes the economize r . The dampers will modulate to maint ain a const ant supply air temperatur e as monitored by the discharge air sensor . If the outdoor air enthalpy is above the set point, "Y1" energizes compre ssor #1.
66307-YIM-B-0606 Unitary Products Group 35 and the thermostat is calling fo r coolin g, the U CB will operate in the low ambient mode. Low ambient mode operates the co mpressors in this manner: 10 minutes on, 5 minutes off. The indoor blo wer is operated throughout the cycle.
66307-YIM-B-0606 36 Unitary Products Group at the position of the defrost thermostats . This action is repeated unti l, at the completion of a run time cycle , one of the defrost thermo stat s is found to be clo sed and the DC enters defrost mode. When the DC enters the defros t mode, it’s on-board defrost relay is powered.
66307-YIM-B-0606 Unitary Products Group 37 • If blower ro tation is in the wrong direction. Refer to Phasing Section in general info rmation section. • Check bl ower drive belt tension. 6. Check the unit supply air (CFM). 7. Measure evaporator fan moto r's amp draw .
66307-YIM-B-0606 38 Unitary Products Group T ABLE 35: SUPERHEA T CHARGING SUCTION PRESSURE PSIG (Service Port) SUCTION TUBE TEMPERA TURE 0 * 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61.5 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 64.2 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 67.
66307-YIM-B-0606 Unitary Products Group 39 TROUBLESHOOTING PREDA TOR ® FLASH CODES Various flash codes are utilized by the unit co ntrol board (UCB) to aid in troubleshooting. Flash codes are distinguished by the short on a nd off cycle used (approximately 200ms on and 200ms off).
66307-YIM-B-0606 40 Unitary Products Group FIGURE 24 : UNIT CONTRO L BOARD T ABLE 38: UNIT CON TROL BOARD FLASH CODES FLASH CODE DESCRIPTION GREEN LED 16 RED LED 8 RED LED 4 RED LED 2 RED LED 1 On S t.
66307-YIM-B-0606 Unitary Products Group 41 COOLING TROUBL ESHO OTIN G GUI DE On calls for cooling, if the compressors are operati ng but the supply air blower motor do es not energize after a sho rt delay (the room thermostat fan switch is in the “AUTO” position): 1.
66307-YIM-B-0606 42 Unitary Products Group locked out the compressor for repeat trips. The UCB should be flashing an alarm code . If not, press and release the ALARMS button on the UCB. The UCB will flash the last five alarms on th e LED. If the compre ssor is locked out, cancel any call for cooling.
66307-YIM-B-0606 Unitary Products Group 43 low-pressure switch, or freeze stat. Check for 24 volts at the HPS2, LPS2, and FS2 terminals of th e UCB. If a switch has opened, there shou ld be a voltage potential between the UCB termin als, e.g. if LPS2 has opened, there will be 24 volts of potential between the LPS2 te r- minals.
Subject to change without notice. Print ed in U.S.A. 66307-YIM-B-0606 Copyright © 2006 by Unitary Products Gro up. All rights reserved. Supersedes: 66307-YI M-A- 0704/035-17277-004-A -0704 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 present, trace the wiring from Y1 “OUT” for in correct wir- ing.
An important point after buying a device York BP 090 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought York BP 090 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data York BP 090 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, York BP 090 you will learn all the available features of the product, as well as information on its operation. The information that you get York BP 090 will certainly help you make a decision on the purchase.
If you already are a holder of York BP 090, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime York BP 090.
However, one of the most important roles played by the user manual is to help in solving problems with York BP 090. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device York BP 090 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center